Schneider Electric 2232-053 Installation Instructions

APPLICATION

The 2232-053 Room Humidity Transmitter is designed to measure room humidity over a 30 to 80% R.H. span, and transmit a proportional 3 to 15 psig signal to controlling and indicating devices such as receiver-controllers, receiver gauges and sensitive pressure switches.
This device is a one-pipe, force balanced transmitter which
ires an external restrictor in the supply line. It
Accessories
Part
Number
20-660 6-441 Cover screw
20-707 10-53 Metal thermostat guard
20-715 10-62 Clear thermostat guard
21-876 10-76 Opaque thermostat guard
21-928 Gray plastic cover, blank dial
21-933 Gray plastic cover,
20-881 N2-4 Calibration wrench
22-138 MCS-GA Branch tap gauge adaptor
900-002
10-82-SS
20-850 10-82 Outlet box mounting plate, black
20-642 Mounting ring
21-473 Snap-in drywall mounting
22-021 Universal drywall mounting kit
22-022 N5-95 Competitor replacement mounting kit
22-024 Standard mounting kit
Replaces
Model
Description
Accessories
°F/°C dial
Calibration
Thermostat calibration kit

Installation

Outlet box mounting plate, stainless steel

SPECIFICATIONS

Action: direct acting, proportional. Range: 30% to 80% R.H. Output pressure: 3 to 15 psig. Main air pressure: 20 psig operating, 30 psig maximum. Air consumption: 29 scim. Air connection: barbed nipple for 3/16" O.D.
ing-reinforced tubing.
spr
Calibration point: 9 psig at midrange. Maximum ambient temperature: 140°F.

2232-053

Room Humidity Transmitter
Installation Instructions
person with due regard for safety, as improper installation could result in a hazardous condition.
Model Chart
Schneider
Electric Number
2232-053 H53-301
*Other rough-in hardware and installation fittings must be ordered
separately.

GENERAL INSTRUCTIONS

1. Transmitter should be mounted where it will be affected only by average room humidity. Free circulation of air must exist at mounting location. Avoid locations that are affected by drafts, radiant heat, water pipes, air ducts, etc.

2. Avoid outside wall locations. When this location is
fied, use 20-716 Insulating Backplate.
speci

3. Mount Transmitter only after wall surface has been finished. Allow the device time to reach ambient conditions before calibrating.

4. Receiver gauge must be 3-15 psig range and graduated 30-80% R.H. to match transmitter output.

5. The nylon hygroscopic element must be kept clean. Do not touch with fingers or other foreign objects.

Installation
Tools (not provided):
– Appropriate screwdriver for mounting the thermostat – 20-881 Thermostat calibration and cover screw
wren
Replaces
Model
Description*
Includes 1/4" by 3/16" barbed
gs, 20-693 tubing,
couplin
standard mounting plate and
screws.
ch (or 1/16" and 1/4" hex wrenches)
Caution: This device should be installed by a qualified
Printed in U.S.A. 6-10 Copyright 2010 Schneider Electric All Rights Reserved. F-27504-2

Figure-1

Eyelet
Tube Clamp
Eyelet
Tube Coupler
Tubing
Eyelet
Tube Coupler
Connect to Thermostat

1. Assemble the eyelets and two tube couplers to tubing.

2. Connect the assembly by inserting the tube coupler into isting tubing in the wall (Figure-1).
ex
3. Pull tubing through center hole in mounting plate and screw
mounting plate to wall with flat head screws. Cut tubing. The tubing is connected into the port on the thermostat (Figure-1).
4. Affix thermostat to mounting ring with round head screws,
taking care not to kink the tubing.

CALIBRATION

After mounting, check calibration. Calibration is accomplished by turning calibrating screw (1) clockwise to decrease branch pressure or counterclockwise to increase the branch pressure. DO
NOT TOUCH THE HYGROSCOPIC ELEMENT!

MOUNTING DIMENSIONS

TYPICAL APPLICATION