APPLICATION
The 2232-053 Room Humidity Transmitter is designed to
measure room humidity over a 30 to 80% R.H. span, and
transmit a proportional 3 to 15 psig signal to controlling and
indicating devices such as receiver-controllers, receiver
gauges and sensitive pressure switches.
This device is a one-pipe, force balanced transmitter which
ires an external restrictor in the supply line. It
requ
incorporates a highly sensitive hygroscopic nylon element
and a ball valve for pneumatic feedback which ensures
accuracy and stability over the entire operating range. All
internal parts are corrosion resistant, and there is an internal
filter to maintain cleanliness of operating parts.
Accessories
Part
Number
20-660 6-441 Cover screw
20-707 10-53 Metal thermostat guard
20-715 10-62 Clear thermostat guard
21-876 10-76 Opaque thermostat guard
21-928 Gray plastic cover, blank dial
21-933 Gray plastic cover,
20-881 N2-4 Calibration wrench
22-138 MCS-GA Branch tap gauge adaptor
900-002
10-82-SS
20-850 10-82 Outlet box mounting plate, black
20-642 Mounting ring
21-473 Snap-in drywall mounting
22-021 Universal drywall mounting kit
22-022 N5-95 Competitor replacement mounting kit
22-024 Standard mounting kit
Replaces
Model
Description
Accessories
°F/°C dial
Calibration
Thermostat calibration kit
Installation
Outlet box mounting plate, stainless
steel
SPECIFICATIONS
Action: direct acting, proportional.
Range: 30% to 80% R.H.
Output pressure: 3 to 15 psig.
Main air pressure: 20 psig operating, 30 psig maximum.
Air consumption: 29 scim.
Air connection: barbed nipple for 3/16" O.D.
ing-reinforced tubing.
spr
Calibration point: 9 psig at midrange.
Maximum ambient temperature: 140°F.
2232-053
Room Humidity Transmitter
Installation Instructions
person with due regard for safety, as improper installation
could result in a hazardous condition.
Model Chart
Schneider
Electric
Number
2232-053 H53-301
*Other rough-in hardware and installation fittings must be ordered
separately.
GENERAL INSTRUCTIONS
1. Transmitter should be mounted where it will be affected
only by average room humidity. Free circulation of air must
exist at mounting location. Avoid locations that are
affected by drafts, radiant heat, water pipes, air ducts, etc.
2. Avoid outside wall locations. When this location is
fied, use 20-716 Insulating Backplate.
speci
3. Mount Transmitter only after wall surface has been
finished. Allow the device time to reach ambient
conditions before calibrating.
4. Receiver gauge must be 3-15 psig range and graduated
30-80% R.H. to match transmitter output.
5. The nylon hygroscopic element must be kept clean. Do
not touch with fingers or other foreign objects.
Installation
• Tools (not provided):
– Appropriate screwdriver for mounting the thermostat
– 20-881 Thermostat calibration and cover screw
wren
Replaces
Model
Description*
Includes 1/4" by 3/16" barbed
gs, 20-693 tubing,
couplin
standard mounting plate and
screws.
ch (or 1/16" and 1/4" hex wrenches)
Caution: This device should be installed by a qualified
Printed in U.S.A. 6-10 Copyright 2010 Schneider Electric All Rights Reserved. F-27504-2
Figure-1
Eyelet
Tube Clamp
Eyelet
Tube Coupler
Tubing
Eyelet
Tube Coupler
Connect to Thermostat
1. Assemble the eyelets and two tube couplers to tubing.
2. Connect the assembly by inserting the tube coupler into
isting tubing in the wall (Figure-1).
ex
3. Pull tubing through center hole in mounting plate and screw
mounting plate to wall with flat head screws. Cut tubing. The
tubing is connected into the port on the thermostat (Figure-1).
4. Affix thermostat to mounting ring with round head screws,
taking care not to kink the tubing.
CALIBRATION
After mounting, check calibration. Calibration is accomplished by
turning calibrating screw (1) clockwise to decrease branch
pressure or counterclockwise to increase the branch pressure. DO
NOT TOUCH THE HYGROSCOPIC ELEMENT!
MOUNTING DIMENSIONS
TYPICAL APPLICATION
On
there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand
changes.
Copyright 2010, Schneider Electric
All brand names, trademarks and registered
trademarks are the property of their respective
owners. Information contained within this
document is subject to change without notice.
F-27504-2
October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however