The information provided in this documentation contains general descriptions and/or technica l characteristics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific user
applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, or maintain it. The following special messages may appear throug hout this
documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.
S1A45606 08/20145
6S1A45606 08/2014
At a Glance
Document Scope
Validity Note
About the Book
The purpose of this document is to provide information about safety functions incorporated in Altivar 32.
These functions allow you to develop applications oriented in the protection of man and machine.
FDT/DTM (field device tool / device type manager) is a new technology chosen by several companies in
automation.
To install the Altivar 32 DTM, you can download and install our FDT: SoMove lite on www.schneiderelectric.com. It is including the Altivar 32 DTM.
The content of this manual is also accessible through the ATV32 DTM online help.
This documentation is valid for the Altivar 32 drive.
The technical characteristics of the devices described in this document also appear online. To access this
information online:
StepAction
1Go to the Schneider Electric home page www.schneider-electric.com
2In the Search box type the reference of a product or the name of a product range.
z Do not include blank spaces in the model number/product range.
z To get information on grouping similar modules, use asterisks (*).
3If you entered a reference, go to the Product Datasheets search results and click on the reference that
interests you.
If you entered the name of a product range, go to the Product Ranges search results and click on the product
range that interests you.
4If more than one reference appears in the Products search results, click on the reference that interests you.
5Depending on the size of your screen, you may need to scroll down to see the data sheet.
6To save or print a data sheet as a .pdf file, click Download XXX product datasheet.
.
Related Documents
The characteristics that are presented in this manual should be the same as those characteristics that
appear online. In line with our policy of constant improvement, we may revise content over time to improve
clarity and accuracy. If you see a difference between the manual and online information, use the online
information as your reference.
BMP Synchronous Motor Manual 0198441113981
ATV32 Certificates, See www.schneider-electric.comNA
You can download these technical publications and other technical information from our website at
www.schneider-electric.com.
Product Related Information
The information provided in this manual supplements the product manuals.
Carefully read the product manuals before using the product.
Read and understand these instructions before performing any procedure with this drive.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
z Only appropriately trained persons who are familiar with and understand the contents of this manual
and all other pertinent product documentation and who have received safety training to recognize and
avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment,
repair, and maintenance must be performed by qualified personnel.
z The system integrator is responsible for compliance with all local and national electrical code
requirements as well as all other applicable regulations with respect to grounding of all equipment.
z Many components of the product, including the printed circuit boards, operate with mains voltage. Do
not touch. Use only electrically insulated tools.
z Do not touch unshielded components or terminals with voltage present.
z Motors can generate voltage when the shaft is rotated. Before performing any type of work on the drive
system, block the motor shaft to prevent rotation.
z AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused
conductors of the motor cable.
z Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
z Before performing work on the drive system:
z Disconnect all power, including external control power that may be present.
z Place a "Do Not Turn On" label on all power switches.
z Lock all power switches in the open position.
z Wait 15minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator
of the absence of DC bus voltage that can exceed 800 Vdc.
z Measure the voltage on the DC bus between the DC bus terminals using a properly rated voltmeter
to verify that the voltage is < 42Vdc.
z If the DC bus capacitors do not discharge properly, contact your local Schneider Electric
representative.
z Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.
DANGER
DANGER
UNINTENDED EQUIPMENT OPERATION
z Read and understand this manual before installing or operating the drive.
z Any changes made to the parameter settings must be performed by qualified personne l.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
8S1A45606 08/2014
WARNING
LOSS OF CONTROL
z The designer of any control scheme must consider the potential failure modes of control paths and,
for critical control functions, provide a means to achieve a safe state during and after a path failure.
Examples of critical control functions are emergency stop, overtravel stop, power outage, and restart.
z Separate or redundant control paths must be provided for critical control functions.System control
paths may include communication links. Consideration must be given to the implications of
unanticipated transmission delays or failures of the link.
z System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
z Observe all accident prevention regulations and local safety guidelines.(1)
z Each implementation of the product must be individually and thoroughly tested for proper operation
before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1. For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), “Safety guidelines for the
application, installation, and maintenance of solid-State control” and to NEMA ICS 7.1 (latest edition),
“Safety standards for construction and guide for selection, installation, and operation of adjustable
speed drive systems.”
CAUTION
INCOMPATIBLE LINE VOLTAGE
Before turning on and configuring the drive, ensure that the line voltage is compatible with the supply
voltage range shown on the drive nameplate. The drive may be damaged if the line voltage is not
compatible.
Failure to follow these instructions can result in injury or equipment damage.
NOTICE
RISK OF DERATED PERFORMANCE DUE TO CAPACITOR AGING
The product capacitor performances after a long time storage above 2 years can be degraded. In that
case, before using the product, apply the following procedure:
z Use a variable AC supply connected between L1 and L2 (even for ATVpppppN4 references).
z Increase AC supply voltage to have:
z 80% of rated voltage during 30 min
z 100% of rated voltage for another 30 min
Failure to follow these instructions can result in equipment damage.
S1A45606 08/20149
Qualification of personnel
Only appropriately trained persons who are familiar with and understand the contents of this manual and
all other pertinent product documentation are authorized to work on and with this product. In addition, these
persons must have received safety training to recognize and avoid hazards involved. These persons must
have sufficient technical training, knowledge and experience and be able to foresee and detect potential
hazards that may be caused by using the product, by changing the settings and by the mechanical,
electrical and electronic equipment of the entire system in which the product is used.
All persons working on and with the product must be fully familiar with all applicable standards, directives,
and accident prevention regulations when performing such work.
Intended use
The functions described in this manual are only intended for use with the basic product; you must read and
understand the appropriate product manual.The product may only be used in compliance with all
applicable safety regulations and directives, the specified requirements and the technical data.Prior to
using the product, you must perform a risk assessment in view of the planned application. Based on the
results, the appropriate safety measures must be implemented.Since the product is used as a component
in an entire system, you must ensure the safety of persons by means of the design of this entire system
(for example, machine design).
Operate the product only with the specified cables and accessories. Use only genuine accessories and
spare parts.Any use other than the use explicitly permitted is prohibited and can result in hazards.Electrical
equipment should be installed, operated, serviced, and maintained only by qualified personnel.The product
must NEVER be operated in explosive atmospheres (hazardous locations, Ex areas).
10S1A45606 08/2014
Generalities
Chapter 1
Generalities
What Is in This Chapter?
This chapter contains the following topics:
Introduction12
Standards and Terminology13
Basics14
TopicPage
S1A45606 08/201411
Introduction
Overview
The safety functions incorporated in Altivar 32 are intended to maintain the safe condition of the installation
or prevent hazardous conditions arising at the installation. In some cases, further safety-related systems
external to the drive (for example a mechanical brake) may be necessary to maintain the safe condition
when electrical power is removed.
The safety functions are configured with SoMove software.
Integrated safety functions provide the following benefits:
z Additional standards-compliant safety functions
z No need for external safety-related devices
z Reduced wiring effort and space requirements
z Reduced costs
The Altivar 32 drives are compliant with the requirements of the standards in terms of imp lementation of
safety functions.
Safety Functions as Defined by IEC 61800-5-2
Definitions
AcronymDescription
STOSafe Torque Off
No power that could cause torque or force is supplied to the motor.
SLSSafely-Limited Speed
The SLS function prevents the motor from exceeding the specified speed limit. If the motor speed exceeds
the specified speed limit value, safety function STO is triggered.
SS1Safe Stop 1
z initiates and monitors the motor deceleration rate within set limits to stop the motor
z initiates the Safe Operating Stop function when the motor speed is below the specified limit
Notation
DANGER
ELECTRIC SHOCK CAUSED BY INCORRECT USE
The safety function STO ([Safe Torque Off]) does not cause electric isolation. The DC bus voltage is
still present.
z Turn off the main voltage using an appropriate switch to achieve a voltage-free condition.
Failure to follow these instructions will result in death or serious injury.
The graphic display terminal (to be ordered separately - reference VW3A1101) menus are shown in square
brackets.
The integrated 7-segment display terminal menus are shown in ro und brackets.
Parameter names are displayed on the graphic display terminal in square brackets.
Parameter codes are displayed on the integrated 7-segment display terminal in round brackets.
12S1A45606 08/2014
Standards and Terminology
Overview
The technical terms, terminology, and the corresponding descriptions in this manual normally use the
terms or definitions in the relevant standards.
In the area of drive systems this includes, but is not limited to, terms such as safety function, safe state,
fault, fault reset, failure, error, error message, warning, warning message, and so on.
Among others, these standards include:
z IEC 61800 series: Adjustable speed electrical power drive systems
z IEC 61508 Ed.2 series: Functional safety of electrical/electronic/programmable electronic safety-related
systems
z EN 954-1 Safety of machinery - Safety related parts of control systems
z EN ISO 13849-1 & 2 Safety of machinery - Safety related parts of control systems
z IEC 61158 series: Industrial communication networks - Fie ldbus specifications
z IEC 61784 series: Industrial communication networks - Pro files
z IEC 60204-1: Safety of machinery - Electrical equipment of machines – Part 1: General requirements
EC Declaration of Conformity
The EC Declaration of Conformity for the EMC Directive can be obtained on www.schneider-electric.com.
ATEX Certification
The ATEX certificate can be obtained on www.schneider-electric.com.
Functional Safety Certification
The integrated safety functions are compatible and certified according to IEC 61800-5-2 Ed.1 Adjustable
speed electrical power drive systems - Part 5-2: Safety requirements - Functional.
IEC 61800-5-2, as a product standard, sets out safety-related considerations of Power Drive System
Safety Related PDS (SR)s in terms of the framework of the IEC 61508 Ed.2 series of standards.
Compliance with the IEC 61800-5-2 standard, for the safety functions described below, will facilitate
incorporation of a PDS (SR) (Power Drive System suitable for use in safety-related applications) into a
safety-related control system using the principles of IEC 61508, or ISO 13849, as well as IEC 62 061 for
process systems and machinery.
The defined safety functions are:
z SIL2 and SIL3 capability in compliance with IEC 61800-5-2 and the IEC 61508 Ed.2 series.
z Performance Level d and e in compliance with ISO 13849-1.
z Compliant with Category 3 and 4 of European standard ISO 13849-1 (EN 954-1).
Also refer to safety function Capability.
The safety demand operating mode is considered to be high demand or continuous mode of operation
according to the IEC 61800-5-2 standard.
The functional safety certificate is accessible on www.schneider-electric.com.
S1A45606 08/201413
Basics
Functional Safety
Automation and safety engineering are two areas that were completely separate in the past but have
recently become more and more integrated.
The engineering and installation of complex automation solutions are greatly simplified by integrated safety
functions.
Usually, the safety engineering requirements depend on the application.
The level of requirements results from the risk and the hazard potential arising from the specific application.
IEC 61508 Standard
The standard IEC 61508 Functional safety of electrical/electronic/programmable electronic safety-related
systems covers the safety-related function.
Instead of a single component, an entire function chain (for example, from a sensor through the logical
processing units to the actuator) is considered as a unit.
This function chain must meet the requirements of the specific safety integrity level as a whole.
Systems and components that can be used in various applications for safety tasks with comparable risk
levels can be developed on this basis.
SIL - Safety Integrity Level
The standard IEC 61508 defines 4 safety integrity levels (SIL) for safety functions.
SIL1 is the lowest level and SIL4 is the highest level.
A hazard and risk analysis serves as a basis for determining the required safety integrity level.
This is used to decide whether the relevant function chain is to be considered as a safety function and
which hazard potential it must cover.
PFH - Probability of a Dangerous Hardware Failure Per Hour
To maintain the safety function, the IEC 61508 standard requires various levels of measures for avoiding
and controlling detected faults, depending on the required SIL.
All components of a safety function must be subjected to a probability assessment to evaluate the
effectiveness of the measures implemented for controlling detected faults.
This assessment determined the PFH (Probability of a dangerous Failure per Hour) for a safety system.
This is the probability per hour that a safety system fails in a hazardous manner and the safety function
cannot be correctly executed.
Depending on the SIL, the PFH must not exceed certain values for the entire safety system.
The individual PFH values of a function chain are added. The result must not exceed the maximum value
specified in the standard.
Performance level Probability of a dangerous Failure per Hour (PFH) at high demand or continuous demand
4
3
2
1
14S1A45606 08/2014
PL - Performance Level
The standard IEC 13849-1 defines 5 Performance levels (PL) for safety functions.
a is the lowest level and e is the highest level.
Five levels (a, b, c, d, and e) correspond to different values of average probability of dangerous failure per
hour.
Performance levelProbability of a dangerous Hardware Failure per Hour
Depending on the SIL for the safety system, the IEC 61508 standard requires a specific hardware fault
tolerance HFT in connection with a specific proportion of safe failures SFF (Safe Failure Fraction).
The hardware fault tolerance is the ability of a system to execute the required safety function in spite of the
presence of one or more hardware faults.
The SFF of a system is defined as the ratio of the rate of safe failures to the total failure rate of the system.
According to IEC 61508, the maximum achievable SIL of a system is partly determined by the hardware
fault tolerance HFT and the safe failure fraction SFF of the system.
IEC 61508 distinguishes two types of subsystem (type A subsystem, type B subsystem).
These types are specified on the basis of criteria which the standard defines for the safety-relevant
components.
SFFHFT type A subsystemHFT type B subsystem
PFD - Probability of Failure on Demand
The standard IEC 61508 defines SIL using requirements grouped into two broad categories: hardware
safety integrity and systematic safety integrity. A device or system must meet the requirements for both
categories to achieve a given SIL.
The SIL requirements for hard ware s af ety i ntegri ty are based on a probabilistic analysis of the device. To
achieve a given SIL, the device must meet targets for the maximum probability of dangerous failure and a
minimum Safe Failure Fraction. The concept of ’dangerous failure’ must be rigorously defined for the
system in question, normally in the form of requirement constraints whose integrity is verified throughout
system development. The actual targets required vary depending on the likelihood of a demand, the
complexity of the device(s), and types of redundancy used.
012012
SIL1SIL2SIL3----SIL1SIL2
SIL2SIL3SIL4SIL1SIL2SIL3
SIL3SIL4SIL4SIL2SIL3SIL4
SIL3SIL4SIL4SIL3SIL4SIL4
S1A45606 08/201415
The PFD (Probability of Failure on Demand) and RRF (Risk Reduction Factor) of low demand operation
for different SILs are defined in IEC 61508 are as follows:
The hazards of a control system must be identified then analyzed in a risk analysis. These risks are
gradually mitigated until their overall contribution to the hazard is deemed to be acceptable. The tolerable
level of these risks is specified as a safety requirement in the form of a target probability of a dangerous
failure over a given period, stated as a discrete SIL level.
Fault Avoidance Measures
Systematic errors in the specifications, in the hardware and the software, usage faults and maintenance
faults in the safety system must be avoided to the maximum degree possible. To meet these requirements,
IEC 61508 specifies a number of measures for fault avoidance that must be implemented depending on
the required SIL. These measures for fault avoidance must cover the entire life cycle of the safety system,
i.e. from design to decommissioning of the system.
Safety Function STO (Safe Torque Off)18
Safety Function SS1 (Safe Stop 1)20
Safety Function SLS (Safely-Limited Speed)22
TopicPage
S1A45606 08/201417
Safety Function STO (Safe Torque Off)
Overview
ELECTRIC SHOCK CAUSED BY INCORRECT USE
The safety function STO (Safe Torque Off) does not cause electric isolation. The DC bus voltage is still
present.
z Turn off the mains voltage using an appropriate switch to achieve a voltage-free condition.
Failure to follow these instructions will result in death or serious injury.
This function brings the machine safely into a no-torque state and / or prevents it from starting accidentally.
The safe torque-off (safety function STO) function can be used to effectively implement the prevention of
unexpected start-up functionality, thus making stops safe by preventing the power only to the motor, while
still maintaining power to the main drive control circuits.
The principles and requirements of the prevention of unexpected start-up are described in the standard EN
1037:1995+A1.
The logic input STO is assigned to this safety function and cannot be modified.
If a paired terminal line in 2 channels is required to trigger safety function STO, the function can also be
enabled by the safety-related logic inputs.
The safety function STO is configured with the commissioning software.
The safety function STO status can be displayed using the HMI of the drive or using the commissioning
software.
DANGER
18S1A45606 08/2014
Safety Function STO Standard Reference
The safety function STO is defined in section 4.2.2.2 of standard IEC 61800-5-2 (edition 1.0 2007.07):
Power, that can cause rotation (or motion in the case of a linear motor), is not applied to the motor.The
PDS(SR) (power drive system suitable for use in safety-related applications) will not provide energy to the
motor which can generate torque (or force in the case of a linear motor).
z NOTE 1: This safety function corresponds to an uncontrolled stop in accordance with stop category 0
of IEC 60204-1.
z NOTE 2: This safety function may be used where power removal is required to prevent an unexpected
start-up.
z NOTE 3: In circumstances where external influences (for example, falling of suspended loads) are
present, additional measures (for example, mechanical brakes) may be necessary to prevent any
hazard.
z NOTE 4: Electronic equipment and contactors do not provide adequate protection against electric
shock, and additional insulation measures may be necessary.
Safety Function (SF) Level Capability for Safety Function STO
Configuration SIL
STO with or without safety module SIL 2PL d
STO & LI3 with or without safety module SIL 3PL e
LI3 and LI4 SIL 2PL d
LI5 and LI6 SIL 2PL d
Emergency Operations
Standard IEC 60204-1 introduces 2 emergency operations:
z Emergency switching-off:
z Emergency stop:
PL
Safety Integrity Level according
to IEC 61-508
Performance Level according
to ISO-13849
This function requires external switching components, and cannot be accomplished with drive based
functions such as safe torque-off (STO).
An emergency stop must operate in such a way that, when it is activated, the hazardous movement of
the machinery is stopped and the machine is unable to start under any circumstances, even after the
emergency stop is released.
An emergency stop shall function either as a stop category 0 or as a stop category 1.
Stop category 0 means that the power to the motor is turned off immediately. Stop category 0 is
equivalent to the safe torque-off (STO) function, as defined by standard EN 61800-5-2.
In addition to the requirements for stop (see 9.2.5.3 of IEC 60204-1), the emergency stop function has
the following requirements:
z it shall override all other functions and operations in all modes.
z This reset shall be possible only by a manual action at that location where the command has been
initiated. The reset of the command shall not restart the machinery but only permit restarting.
z For the machine environment (IEC 60204-1 and machinery directive), when safety function STO is
used to manage an emergency stop category 0, the motor must not restart automatically when safety
function STO has been triggered and deactivated (with or without a power cycle). This is the reason
why an additional safety module is required if the machine restarts automatically after the safety
function STO has been deactivated.
S1A45606 08/201419
Safety Function SS1 (Safe Stop 1)
Overview
The safety function SS1 (Safe Stop 1) monitors the deceleration according to a dedicated deceleration
ramp and safely shuts off the torque once standstill has been achieved.
When the safety function SS1 is triggered, it overrides all othe r fu nctions (except STO function that has
priority) and operations in all modes.
The unit of the SS1 deceleration ramp is in Hz/s. The setting of the ramp is done with two parameters:
[SS1 ramp unit] SSrU (Hz/s) to give the unit of the ramp in 1 Hz/s, 10 Hz/s, and 100 Hz/s
[SS1RampValue] SSrt (0.1) to set the value of the ramp
Ramp calculation:
Ramp = SSrU*SSrt
Example: If SSrU = 10 Hz/s and SSrt = 5.0 the deceleration ramp is 50 Hz/s.
The safety function SS1 is configured with the commissioning software, for more information see
Commissioning (see page 75).
The safety function SS1 status can be displayed using the HMI of the drive or using the commissioning
software.
Behavior on Activation of the SS1 Function
When SS1 function is triggered, it monitors the deceleration of the motor according to the specified
monitoring ramp until standstill is reached and verifies if the motor speed is not above a monitored limit
value depending on the specified monitoring ramp and the parameter [SS1 trip threshold]SStt.
If the monitored limit value is exceeded:
z An error is triggered and the error code [Safety function fault] SAFF is displayed.
z Safety function STO is triggered.
After the [Standstill level]SSSL has been reached, the safety function STO is triggered.
SS1 function continues to be active if the request has been removed before the standstill has been
reached.
NOTE: The error detection depends on [Stator Frequency]StFr.
: SS1 trip threshold, : SS1 deceleration ramp (dV/dT), : STO function triggered, : Error and
STO function triggered
20S1A45606 08/2014
Behavior on Deactivation of the SS1 Function
After an SS1 stop, send a new run command (even if the run command is set on level command).
SS1 Standard Reference
The SS1 function is defined in section 4.2.2.2 of standard IEC 61800-5-2:
The PDS(SR) (Power drive system suitable for use in safety-related applications) either:
z Initiates and controls the motor deceleration rate within set limits to stop the motor and initiates the STO
function (see 4.2.2.2) when the motor speed is below a specified limit; or
z Initiates and monitors the motor deceleration rate within set limits to stop the motor and initiates the STO
function when the motor speed is below a specified limit; or
z Initiates the motor deceleration and initiates the STO function after an application-specific time delay.
NOTE: This safety function corresponds to a controlled stop in accordance with stop category 1 of IEC
60204-1.
Safety Function (SF) Level Capability for Safety Function SS1
FunctionConfiguration SIL
SS1 type CSTO with Preventa module SIL2PL d
SS1 type BLI3 and LI4 SIL 2PL d
Emergency Stop Category 1
An emergency stop must operate in such a way that, when it is activated, the hazardous movement of the
machinery is stopped and the machine is unable to start under any circumstances, even after the
emergency stop is released.
An emergency stop shall function either as a stop category 0 or as a stop category 1.
Stop category 1 is a controlled shut-down, whereby the energy supply to the motor is maintained to perform
the shut-down, and the energy supply is only interrupted when the shut-down has been completed.
Stop category 1 is equivalent to the [Safe Stop 1]SS1 function, as defined by standard EN 61800-5-2.
In addition to the requirements for stop (see 9.2.5.3 of IEC 60204-1), the emergency stop function has the
following requirements:
z it shall override all other functions and operations in all modes.
z This reset shall be possible only by a manual action at that location where the command has been
initiated. The reset of the command shall not restart the machinery but only permit restarting.
For the machine environment (IEC 60204-1 and machinery directive), when safety function SS1 is used to
manage an emergency stop category 1, the motor must not restart automatically when safety function SS1
has been triggered and deactivated (with or without a power cycle). This is the reason why an addition al
safety module is required if the machine restarts automatically after the safety function SS1 has been
deactivated.
PL
Safety Integrity Level
According to IEC 61-508
STO and LI3 with Preventa moduleSIL 3PL e
LI5 and LI6 SIL 2PL d
Performance Level
According to ISO-13849
S1A45606 08/201421
Safety Function SLS (Safely-Limited Speed)
Overview
This function is used to limit the speed of a motor.
There are 6 types of SLS function:
z SLS type 1: Limits the motor speed to the actual motor speed.
z SLS type 2: Limits the motor speed to a value set using a parameter.
z SLS type 3: Same as type 2 with specific behavior if the motor speed is above threshold value set using
a parameter.
z SLS type 4: Limits the motor speed to a value set using a parameter. The direction of rotation can be
changed while the safety function is active.
z SLS type 5: Same as type 4 with the specific behavior if the motor speed is above threshold value set
using a parameter.
z SLS type 6: Same as type 4 with specific behavior if the motor speed is above threshold value set using
a parameter.
NOTE: SLS types 2 and 3 use (SLwt) [SLS Wait time] parameter to allow the motor to run under the
[standstill level ] SSSL for a given time after the safety function SLS has been activated.
The safety function SLS is configured with the commissioning software, for more information see
commissioning (see page 75).
The status of the safety function SLS can be displayed using the HMI of the drive or using the
commissioning software.
Behavior on Activation of the Safety Function SLS Type 1
: Error and STO function triggered, : Reference upper limit, : STO function triggered
When the safety function is activated:
z If the [Stator Frequency]StFr is above the [SLS tolerance threshold]SLtt, the safety function
STO is triggered and an error is triggered with the error code [Safety function fault]SAFF.
z If the [Stator Frequency]StFr is under the [SLS tolerance threshold]SLtt, the stator
frequency is limited to the actual stator frequency. The reference frequency will only vary between this
value and the standstill level SSSL.
While the function is activated:
z If the[Stator Frequency]StFr decreases and reaches the [Standstill level]SSSL frequency, the
safety function STO is triggered.
z If the [Stator Frequency]StFr increases and reaches [SLS tolerance threshold]SLtt, the
safety function STO is triggered and an error is triggered with the error code [Safety function fault]SAFF.
22S1A45606 08/2014
Behavior on Activation of the Safety Function SLS Type 2
: SS1 trip threshold, : Error and STO function triggered, : Reference upper limit, : STO
function triggered, : SS1 deceleration ramp (dV/dT), : Time taken fo r the [Stator Frequency ]StFr to become greater than SSSL
: [Stator Frequency]StFr is above [Set Point]SLSP
: [Stator Frequency]StFr is between [Standstill level]SSSL and [Set Point]SLSP
: [Stator Frequency]StFr is below [Standstill level]SSSL and [SLS wait time] (SLwt) ≠ 0
When the function is activated :
z If the [Stator Frequency ]StFr is above the [Set point]SLSP, the drive decelerates according
to SS1 deceleration ramp until the [Set point]SLSP is reached.(see case A)
z If the [Stator Frequency]StFr is below the SLSP the current reference is not changed but limited
to the [Set point]SLSP.(see case B)
z If the [Stator Frequency] StFr is still below the [Standstill level] SSSL frequency after [SLS
wait time] (SLwt ) has elapsed, the safety function STO will be triggered.(see case C)
While the function is activated:
z The reference frequency can only vary between the [Set point]SLSP and the standstill level SSSL.
z If the [Stator Frequency ]StFr decreases and reaches the [Standstill level]SSSL frequency,
safety function STO is triggered.
z If the [Stator Frequency ]StFr increases and reaches the [SLS tolerance threshold]SLtt, the
safety function STO is triggered and an error is triggered with the error code [Safety function fault]SAFF.
S1A45606 08/201423
Behavior on Activation of the Safety Function SLS Type 3
SLS type 3 has the same behavior as SLS type 2 except that If the [Stator Frequency]StFr is above
the [SLS tolerance threshold]SLtt, the safety function SS1 is triggered instead of decelerating to the [Set point]SLSP (see case A)
: SS1 trip threshold, : Error and STO function triggered, : Reference upper limit, : STO
function triggered, : SS1 deceleration ramp (dV/dT), : Time taken for the [Stator Frequency]StFr to become greater than SSSL
: [Stator Frequency]StFr is above [SLS tolerance threshold]SLtt
: [Stator Frequency]StFr is between [Set Point]SLSP and [SLS tolerance threshold]SLtt
: [Stator Frequency]StFr is between [Standstill level]SSSL and [Set Point]SLSP
:[Stator Frequency]StFr is below [Standstill level]SSSL and [SLS wait time] (SLwt) ≠ 0
When the function is activated :
z If the [Stator Frequency]StFr is above the [SLS tolerance threshold]SLtt, the safety function
SS1 is triggered. (see case A).
z If the [Stator Frequency] StFr is between the [SLS tolerance threshold] SLtt and the [Set
point] SLSP, the drive decelerates according to SS1 deceleration ramp until the [Set point] SLSP
has been reached.(see case B).
z If the [Stator Frequency]StFr is below the [Set point]SLSP the current reference is not changed
but limited to the [Set point]SLSP.(see case C)
z If the [Stator Frequency] StFr is still below the [Standstill level] SSSL frequency after [SLS wait
time] SLwt has elapsed, the safety function STO will be triggered.(see case D)
While the function is activated:
z The reference frequency can only vary between the [Set point] SLSP and the [Standstill level]
SSSL.
z If the [Stator Frequency ] StFr decreases and reaches the [Standstill level] SSSL frequency,
the safety function STO is triggered.
z If the [Stator Frequency ]StFr increases and reaches the [SLS tolerance threshold]SLtt, the
safety function STO is triggered and an error is triggered with the error code [Safety function fault]SAFF.
24S1A45606 08/2014
Behavior on Activation of the Safety Function SLS Type 4
Error and STO function triggered, SS1 trip threshold, SS1 deceleration ramp (dv/dt),
reference upper limit
: [Stator Frequency]StFr is above [SLS tolerance threshold]SLtt
: [Stator Frequency]StFr is between [Set Point]SLSP and [SLS tolerance threshold]SLtt
: [Stator Frequency]StFr is below [Set Point]SLSPNOTE: If the SLTT ≤ SLSP for SLS type 4, SAFF fault is triggered.
When the function is activated :
z If the [Stator Frequency]StFr is above the [SLS tolerance threshold]SLtt, the safety function
STO is triggered with the error code [Safety function fault]SAFF.(see case A)
z If the [Stator Frequency] StFr is between the [SLS tolerance threshold] SLtt and the [Set
point] SLSP, the drive decelerates according to SS1 deceleration ramp until the [Set point] SLSP
has been reached.(see case B)
z If the [Stator Frequency]StFr is below the [Set point]SLSP, the current reference is not
changed but limited to the [Set point] SLSP.(see case C).
While the function is activated:
z The reference frequency can vary between the [Set point] SLSP in both forward and reverse
directions.
z If the [Stator Frequency]StFr increases and reaches [SLS tolerance threshold]SLtt, the
safety function STO is triggered and an error is triggered with the error code [Safety function fault]SAFF.
S1A45606 08/201425
Behavior on Activation of the Safety Function SLS Type 5
: Error and STO function triggered, : SS1 trip threshold, : SS1 deceleration ramp (dv/dt), :
Reference upper limit
: [Stator Frequency]StFr is above [SLS tolerance threshold]SLtt
: [Stator Frequency]StFr is between [Set Point]SLSP and [SLS tolerance threshold]SLtt
: [Stator Frequency]StFr is below [Set Point]SLSP
When the function is activated :
z If the [Stator Frequency]StFr is above the [SLS tolerance threshold]SLtt, the drive
decelerates according to SS1 deceleration ramp until the [Set point]SLSP has been reached. (see
case A)
z If the [Stator Frequency] StFr is between the [SLS tolerance threshold] SLtt and the [Set
point] SLSP, the drive decelerates according to SS1 deceleration ramp until the [Set point] SLSP
has been reached.(see case B)
z If the [Stator Frequency]StFr is below the [Set point]SLSP, the current reference is not
changed but limited to the [Set point] SLSP.(see case C).
While the function is activated:
z The reference frequency can vary between the [Set point]SLSP in both forward and reverse
directions.
z If the [Stator Frequency]StFr increases and reaches [SLS tolerance threshold]SLtt, the
safety function STO is triggered and an error is triggered with the error code [Safety function fault]SAFF.
26S1A45606 08/2014
Behavior on Activation of the Safety Function SLS Type 6
: Error and STO function triggered, : SS1 trip threshold, : SS1 deceleration ramp (dV/dT) :
Reference upper limit, : STO function triggered.
: [Stator Frequency]StFr is above [SLS tolerance threshold]SLtt
: [Stator Frequency]StFr is between [Set Point]SLSP and [SLS tolerance threshold]SLtt
: [Stator Frequency]StFr is below [Set Point]SLSP
When the function is activated :
z If the [Stator Frequency]StFr is above the [SLS tolerance threshold]SLtt, the drive
decelerates according to SS1 deceleration ramp until 0 Hz has been reached (see case A).
z If the [Stator Frequency] StFr is between the [SLS tolerance threshold] SLtt and the [Set
point] SLSP, the drive decelerates according to SS1 deceleration ramp until the [Set point] SLSP
has been reached.(see case B)
z If the [Stator Frequency]StFr is below the [Set point]SLSP, the current reference is not
changed but limited to the [Set point] SLSP.(see case C).
While the function is activated:
z The reference frequency can vary between the [Set point] SLSP in both forward and reverse
directions.
z If the [Stator Frequency]StFr increases and reaches [SLS tolerance threshold]SLtt, the
safety function STO is triggered and an error is triggered with the error code [Safety function fault]SAFF.
S1A45606 08/201427
Behavior on Deactivation of the Safety Function SLS for All SLS Types
If...Then ...
The drive is still running when the function is deactivated The reference frequency of the active channel is applied.
Safety function STO has been triggered and the drive is
not in fault state.
The safety function SLS type 2, 3, 4 is deactivated while
the drive decelerates to the [Set point]SLSP
according to SS1 deceleration ramp.
The safety function SLS type 3 is deactivated while the
safety function SS1 has been triggered
a stop command is appliedThe safety function SLS remains active and the drive
an error is detectedThe safety function SLS remains active and the drive stops
A new run command must be applied.
The safety function SLS remains activated until the [Set point]SLSP has been reached.
STO is triggered when [Standstill level]SSSL is
reached and a new run command must be applied.
decelerates until standstill is reached.
For SLS type 1, 2, or 3 STO function is triggered when the
[Stator Frequency] StFr decreases and reaches the
[Standstill level] SSSL frequency.
according to the configured error response.
For SLS type 1, 2, or 3 STO function will be triggered after
the [Standstill level]SSSL frequency has been
reached.The drive can be reset after the cause is cleared.
SLS Standards References
The safety function SLS is defined in section 4.2.3.4 of standard IEC 61800-5-2 The SLS function helps to
prevent the motor from exceeding the specified speed limit.
Safety Function (SF) Level for Safety Function SLS
Configuration SIL
Safety Integrity Level According to IEC 61-508PLPerformance level According to ISO-13849
LI3 and LI4 SIL 2PL d
LI5 and LI6 SIL 2PL d
28S1A45606 08/2014
Calculation of Safety Related Parameters
Chapter 3
Calculation of Safety Related Parameters
What Is in This Chapter?
This chapter contains the following topics:
SLS Type 130
SLS Type 2, Type 3, Type 4, Type 5, and Type 632
SS135
TopicPage
S1A45606 08/201429
SLS Type 1
Collect Application Data
Before starting to configure the SLS function, you must collect the following data:
Code DescriptionUnitComment
FrS[Rated motor freq.]HzSee motor nameplate
nSp[Rated motorspeed]rpmSee motor nameplate
ppnMotor pole pair number–See motor nameplate
Max FrequencyMaximum motor frequency for normal
Calculate the rated motor slip frequency Fslip (Hz).:
To Configure the Function
Overview of diagram
operation
HzThis value is equal to [High speed]
HSP or lower
: Error and STO function triggered, : Reference upper limit, : STO function triggered
Standstill Level
The recommended standstill level is: SSSL = Fslip
If the application requires a different standstill level, it can be set accordingly with the SSSL parameter.
Motor Frequency Limit Threshold
The recommended value of the parameter is SLtt = 1.2 x Max Frequency + Fslip
30S1A45606 08/2014
Testing and Adjusting the Configuration
When configuration is complete, test the SLS function to verify it behaves as expected.
If an error is triggered with the error code [Safety function fault]SAFF apply the following
troubleshooting rules
ContextDrive StatusAdjustment
SLS activated and motor
running at the fixed setpoint
frequency
Example
Code DescriptionUnit
FrS[Rated motor freq.]50 Hz
nSp[Rated motorspeed]1350 rpm
ppnMotor pole pair number2
Max FrequencyMaximum motor frequency on normal operation. This value is generally
With these numerical values, the configuration of SLS type 1 is:
z SAFF error code
z SFFE.7 = 1
equal to [High speed]HSP or lower
Motor frequency has reached the motor frequency limit
threshold.
The cause of the detected error can be due to frequency
instability. Investigate and correct the cause. The value of
SLtt can be modifed to increase the tolerance threshold to
the instability of the drive system.
50 Hz
SSSL = Fslip = 5 Hz
SLtt = 1.2 x Max Frequency + Fslip = 1.2 x 50 + 5 = 65 Hz
S1A45606 08/201431
SLS Type 2, Type 3, Type 4, Type 5, and Type 6
Collect Application Data
Before starting to configure the SLS function, you must collect the following data:
Code DescriptionUnitComment
FrS[Rated motor freq.]HzSee motor nameplate
nSp[Rated motor speed]rpmSee motor nameplate
ppnMotor pole pair number–See motor nameplate
Max FrequencyMaximum motor frequency
on normal operation
SS1 deceleration
ramp
Calculate the rated motor slip frequency Fslip (Hz).
Deceleration ramp to apply
when SS1 ramp is triggered
HzThis value is equal to [High speed]HSP or lower.
Hz–
Fslip = FrS -
To Configure the Function
Overview of diagram
Nsp x ppn
60
: SS1 trip threshold, : Error and STO function triggered, : Reference upper limit, : STO
function triggered, : SS1 deceleration ramp (dV/dT), : Time taken for the [Stator Frequency ]StFr to become greater than SSSL
: [Stator Frequency]StFr is above [Set Point]SLSP
: [Stator Frequency]StFr is between [Standstill level]SSSL and [Set Point]SLSP
: [Stator Frequency]StFr is below [Standstill level]SSSL and [SLS wait time] (SLwt) ≠ 0
Standstill Level
The recommended standstill level is: SSSL = Fslip
If the application requires a different standstill level, it can be set accordingly with the SSSL parameter.
Ramp Value and Ramp Unit
32S1A45606 08/2014
Set SSrt (ramp value) and SSrU (ramp unit) parameters according to the deceleration ramp to apply when
the safety function SS1 is triggered.
Ramp calculation: Ramp = SSrU*SSrt
Example 1: If SSrU = 1 Hz/s and SSrt = 500.0 the deceleration ramp is 500.0 Hz/s and the accuracy is
0.1 Hz
Example 2: If SSrU = 10 Hz/s and SS rt = 50.0 the deceleration ramp is 500 Hz/s and the accuracy is 1 Hz
Use the table to set the correct accuracy according to the deceleration ramp to apply when the safety
Set the SLS setpoint parameter (SLSP) to: SLSP= Fsetpoint (SLS)
Motor Frequency and ramp Limit Threshol d
The recommended motor frequency limit threshold is SLtt = 1.2 x SLSP + Fslip and the recommended SS1
ramp limit threshold is: SStt = 0.2 x Max Frequency
SLS Wait time
Set the [SLS wait time] (SLwt) greater than 0 ms to to allow the motor to run under the [standstill level]
SSSL for a given time after the safety function SLS has been activated.
NOTE: When SLS Type 4 is configured, [SLS wait time] (SLwt) must be set to 0 otherwise an error is
triggered and the error code [Safety function fault]SAFF is displayed
Testing and Adjusting the Configuration
When configuration is complete, test the SLS function to verify that it behaves as expected.
If an error is triggered with the error code [Safety function fault]SAFF, apply the following
troubleshooting rules
ContextDrive StatusAdjustment
SLS activated and
deceleration ramp in
progress
z SAFF error code
z SFFE.3 = 1
Motor frequency has reached the motor frequency limit threshold.
The cause of the detected error can be due to frequency instability.
Investigate and correct the cause. The value of SLtt can be modified to
increase the tolerance threshold to the instability of the drive system.
S1A45606 08/201433
ContextDrive StatusAdjustment
SLS activated and end
of ramp at SLSP
frequency
z SAFF error code
z SFFE.3 = 1
or
z SFFE.7 = 1
Motor frequency stabilization at SLSP takes too long and has reached
the safety function error detection condition.
: Safety function error detection, Tosc: T oscillation, F: Frequency
The oscillations must be lower than SLtt before the time T(oscillation)
elapses.
If the condition is not followed, an error is triggered and the error code
[Safety function fault]SAFF is displayed
The relationship between SStt and T(oscillation) is:
Motor frequency has reached the motor frequency limit threshold.
The cause of the detected error can be due to frequency instability.
Investigate and correct the cause. The value of SStt can be modified to
increase the tolerance threshold to the oscillations of the drive system.
SLS activated and
motor running at SLSP
frequency
z SAFF error code
z SFFE.7 = 1
Motor frequency has reached the motor frequency limit threshold.
The cause of the detected error can be due to frequency instability.
Investigate and correct the cause. The value of SLtt can be modified to
increase the tolerance threshold to the instability of the drive system.
Example
Code DescriptionUnit
FrSRated motor frequency50 Hz
nSpRated motor speed1350 rpm
ppnMotor pole pair number2
Max FrequencyMaximum motor frequency on normal operation. This value is equal to
50 Hz
[High speed]HSP or lower
Fsetpoint(SLS)Motor frequency setpoint15 Hz
SS1 deceleration ramp Deceleration ramp to apply when SS1 is triggered20 Hz/s
With these numerical values, the configuration of SLS type 2, 3, and 4 is:
Fslip = 50 -=5 Hz
1350 x 2
60
SSSL = Fslip = 5Hz
SSrU = 1 Hz/s and SSrt = 20.0 for SS1 deceleration ramp = 20 Hz/s (accuracy is 0.1 Hz)
SLSP = Fsetpoint(SLS) = 15 Hz
SLtt = 1.2 x SLSP + Fslip = 1.2 x 15 + 5 = 23 Hz
SStt = 0.2 x Max Frequency = 0.2 * 50 = 10 Hz
In this example, the frequency oscillations are allowed to be higher than SLtt for 350 ms.
34S1A45606 08/2014
SS1
Collect Application Data
Before configuring the SS1 function, you must collect the following data:
Code DescriptionUnitComment
FrSRated motor frequencyHzFrom motor
nSpRated motor speedrpmFrom motor
ppnMotor pole pair number–From motor
Max FrequencyMaximum motor
Calculate the rated motor slip frequency Fslip (Hz).
To Configure the Function
Overview of diagram
HzThis value is equal to [High speed]HSP or lower
frequency on normal
operation
: SS1 trip threshold, : SS1 deceleration ramp (dV/dT), : STO function triggered, : Error and
STO function triggered
Standstill Level
The recommended standstill level is: SSSL = Fslip
If the application requires a different standstill level, it can be set accordingly with the SSSL parameter.
Ramp Value and Ramp Unit
Set SSrt (ramp value) and SSrU (ramp unit) parameters according to the deceleration ramp to apply when
the safety function SS1 is triggered.
Ramp Calculation: Ramp = SSrU*SSrt
Example 1: If SSrU = 1 Hz/s and SSrt = 500.0 the deceleration ramp is 500.0 Hz/s and the accuracy is
0.1 Hz
Example 2: If SSrU = 10 Hz/s and SS rt = 50.0 the deceleration ramp is 500 Hz/s and the accuracy is 1 Hz
S1A45606 08/201435
Use the table to set the correct accuracy according to the deceleration ramp to apply when the safety
function SS1 is triggered:
The SS1 ramp trip threshold is calculated by: SStt = 0.2 x Max Frequency
This value is equal to [High speed]HSP or lower
Testing and Adjusting the Configuration
When configuration is complete, test the safety function SS1 to verify that it behaves as expected.
If an error is triggered with the error code [Safety function fault]SAFF, apply the following
troubleshooting rules
ContextDrive StatusAdjustment
SS1 activated and the
[Standstill level]SSSL
has not yet been reached
z SAFF error code
z SFFE.3 = 1
Motor frequency has reached the motor frequency limit
threshold.
The cause of the detected error can be due to frequency
instability. Investigate and correct the cause. The value of
SStt can be modified to increase the tolerance threshold
to the instability of the drive system.
Example
Code DescriptionUnit
FrSRated motor frequency50 Hz
nSpRated motor speed1350 rpm
ppnMotor pole pair number2
Max FrequencyMaximum motor frequency on normal operation50 Hz
SS1 deceleration rampDeceleration ramp to apply when SS1 is triggered20 Hz/s
With these numerical values, the configuration of SS1 is:
SSSL = Fslip = 5Hz
SSrU = 1 Hz/s and SSrt = 20.0 for SS1 deceleration ramp = 20 Hz/s (accuracy is 0.1 Hz)
SStt = 0.2 x Max Frequency =0.2x50=10Hz
36S1A45606 08/2014
Behavior of Safety Functions
Chapter 4
Behavior of Safety Functions
What Is in This Chapter?
This chapter contains the following topics:
Limitations38
Detected Fault Inhibition39
Priority Between Safety Functions40
Factory Settings41
Configuration Download42
Priority Between Safety Functions and No Safety-Related Functions43
TopicPage
S1A45606 08/201437
Limitations
Type Of Motor
The safety functions SLS and SS1 on ATV32 are only applicable for asynchronous motors with openloop control profile.
The safety function STO can be used with synchronous and asynchronous motors.
Prerequisites for Using Safety Functions
Following conditions have to be fulfilled for correct operation:
z The motor size is adequate for the application and is not at the limit of its capacity.
z The drive size has been correctly chosen for the line supply, sequence, motor, and application and is
not at the limit of their capacities as stated in the catalog.
z If required, the appropriate options are used.
Example: dynamic braking resistor or motor choke.
z The drive is correctly set up with the correct speed loop and torque characteristics for the application;
the reference frequency profile applied to the drive control loop is followed.
Requirements on Logical Inputs
z Sink mode must not been used with the safety function. If you use the safety function, you need to wire
the logic inputs in source mode.
z PTC on LI6 is incompatible with the safety function set on this input. If you are using the safety function
on LI6, do not set the PTC switch to PTC
z If you are using the pulse input, you cannot set the safety function on LI5 at the same time.
38S1A45606 08/2014
Detected Fault Inhibition
When a safety function has been configured, the error [Safety Function Fault]SAFF cannot be
inhibited by the function [Fault Inhibit assign.]InH
S1A45606 08/201439
Priority Between Safety Functions
1. The safety function STO has the highest priority. If the safety function STO is triggered, a Safe Torque
Off is performed regardless of which other functions are active.
2. The safety function SS1 has medium priority in relation to the other safety functions.
3. The safety function SLS has the lowest priority.
40S1A45606 08/2014
Factory Settings
If the safety functions are configured and you restore the factory settings, only the parameters which are
not safety-related will be reset to the factory setting. The settings of safety-related parameters can only be
reset using the commissioning software, for more information see Commissioning (see page 75).
S1A45606 08/201441
Configuration Download
You can transfer a configuration in all situations. If a safety function has been configured, the functions
using these same logic inputs will not be configured.
For example: If the downloaded configuration has functions (Preset speed,...) on LI3-4-5-6 and if the drive
has a safety function configured on these logic inputs, safety function will not be erased. It is the functions
that have the same logic input as safety functions that are not transferred. Multiconfiguration/multimotor
and macro configuration obey the same rules.
42S1A45606 08/2014
Priority Between Safety Functions and No Safety-Related Functions
Priority Table
o: Compatible functions
x: Incompatible functions
: The function indicated by the arrow has priority over the other.
[REF. OPERATIONS] OAI-o
[2 wire] 2Co: Run command on transition
[PTC MANAGEMENT] PtC-o: inactive if the safety function
[FORCED LOCAL] LCF-o
StFr is above the frequency
limit threshold, the error SAFF is
triggered.
detected by the safety function
StFr is above the Frequency
limit threshold, the error SAFF is
triggered.
Run command on level is not
compatible
is not assigned to LI6
x: Motor output
phase loss is
detected by the
safety function
o :If the [Stator Frequency]StFr
is above the
Frequency limit
threshold, the error
SAFF is triggered.
o: Run command on
transition
Run command on
level is not
compatible
o: inactive if the
safety function is not
assigned to LI6
o
o: Run command on
transition
Run command on
level is not
compatible
o: inactive if the
safety function is not
assigned to LI6
[LI CONFIGURATION]o: inactive if the safety function
[MULTIMOTORS/CONFIG].
MMC-
[FAULT INHIBITION] InHxxx
[Profile] CHCFLogic input used by safety
[Macro configuration] CFG
[RAMP] rPt-
[Motor short circuit] SCF1o
44S1A45606 08/2014
is assigned to logic input
o: except safety-related
parameters
function cannot be switched
: Macro configuration could be
overlapped if safety function use
a logical input requested by the
macro configuration
: SLS ramp
B : SLS steady
o: inactive if the
safety function is
assigned to logic
input
o: except safetyrelated parameters
Logic input used by
safety function
cannot be switched
: Macro
configuration could
be overlapped if
safety function use a
logical input
requested by the
macro configuration
o:inactive if the
safety function is
assigned to logic
input
o: except safetyrelated parameters
Logic input used by
safety function
cannot be switched
: Macro
configuration could
be overlapped if
safety function use a
logical input
requested by the
macro configuration
o
Drive FunctionSLSSS1STO
[Ground short circuit] SCF3o
[Overspeed] SOFo
[Sync. mot.] SYnxxo
[Configuration Transfer]o: except safety-related
parameters
o: except safetyrelated parameters
o: except safetyrelated parameters
[Energy Sav.]nLdxxo
For more information about these functions, see ATV32 Programming manual.
S1A45606 08/201445
46S1A45606 08/2014
Safety Functions Visualization by HMI
Chapter 5
Safety Functions Visualization by HMI
What Is in This Chapter?
This chapter contains the following topics:
Status of Safety Functions48
Dedicated HMI49
Error Code Description50
TopicPage
S1A45606 08/201447
Status of Safety Functions
Description
The status of the safety functions can be displayed using the HMI of the drive or using the commissioning
software. HMI of the drive can be the local HMI on the product or the graphic display terminal or the remote
display terminal. There is one register for each safety function. See introduction (see page 12) for more
information about the safety functions.
To access these registers with an HMI: [2 MONITORING]MOn- --> [MONIT. SAFETY]SAF-
z [STO status]StOS: Status of the safety function STO (Safe Torque Off)
z [SLS status]SLSS: Status of the safety function SLS (Safely-Limited Speed)
z [SS1 status]SS1S: Status of the safety function SS1 (Safe Stop 1)
The status registers are not approved for any type of safety-related use.
For more information about these registers, see ATV32 Visualization and Status of Safety Functions
(see page 81) on www.schneider-electric.com.
48S1A45606 08/2014
Dedicated HMI
Description
When a safety function has been triggered, some information is displayed.
Example with the local HMI of the product when the safety function SS1 has been triggered:
: Display alternately the name of the safety function SS1 and the current display parameter as long as
the motor decelerates according to the specified monitoring ramp until standstill is reached, After the
[Standstill level]SSSL has been reached, the safety function STO is triggered and displayed
S1A45606 08/201449
Error Code Description
Description
When an error is detected by the safety function, the drive displays [Safety function fault] (SAFF). This
detected error can only be reset after powering the drive OFF/ON.
for more information, you can access to the registers to find out the possible reasons for triggeri ng.
These registers can be displayed using the graphic display terminal or the commissioning software:
[DRIVE MENU] --> [MONITORING] --> [DIAGNOSTICS] --> [MORE FAULT INFO]
SFFE [Safety Function Error Register]
BitDescription
Bit0=1Logic inputs debounce time-out (verify value of debounce time LIDT according to the application)
Bit1Reserved
Bit2=1Motor speed sign has changed during SS1 ramp
Bit3=1Motor speed has reached the frequency limit threshold during SS1 ramp.
Bit4Reserved
Bit5Reserved
Bit6=1Motor speed sign has changed during SLS limitation
Bit7=1Motor speed has reached the frequency limit threshold during SS1 ramp.
Bit8Reserved
Bit9Reserved
Bit10Reserved
Bit11Reserved
Bit12Reserved
Bit13=1Not possible to measure the motor speed (verify the motor wiring connection)
Bit14=1Motor ground short-circuit detected (verify the motor wiring connection)
Bit15=1Motor phase to phase short-circuit detected (verify the motor wiring connection)
This register is reset after powering OFF/ON.
This register can also be accessed from [DRIVE MENU] --> [MONITORING] --> [MONIT. SAFETY]
SAF1 [Safety Fault Register 1]
This is an application control error register.
BitDescription
Bit0=1PWRM consistency detected error
Bit1=1Safety functions parameters detected error
Bit2=1Application auto test has detected an error
Bit3=1Diagnostic verification of safety function has detected an error
Bit4=1Logical input diagnostic has detected an error
Bit5=1Application hardware watchdog active
Bit6=1Application watchdog management active
Bit7=1Motor control detected error
Bit8=1Internal serial link core detected error
Bit9=1Logical input activation detected error
Bit10=1Safe Torque Off function has triggered an error
Bit11=1Application interface has detected an error of the safety functions
Bit12=1Safe Stop 1 function has detected an error of the safety functions
Bit13=1Safely Limited Speed function has triggered an error
Bit14=1Motor data is corrupted
Bit15=1Internal serial link data flow detected error
50S1A45606 08/2014
This register is reset after powering OFF/ON.
SAF2 [Safety Fault Register 2]
This is a motor control error register.
BitDescription
Bit0=1Consistency stator frequency verification has detected an error
Bit1=1Stator frequency estimation detected error
Bit2=1Motor control watchdog management is active
Bit3=1Motor control hardware watchdog is active
Bit4=1Motor control auto test has detected an error
Bit5=1Chain testing detected error
Bit6=1Internal serial link core detected error
Bit7=1Direct short-circuit detected error
Bit8=1PWM driver detected error
Bit9Reserved
Bit10Reserved
Bit11=1Application interface has detected an error of the safety functions
Bit12Reserved
Bit13Reserved
Bit14=1Motor data is corrupted
Bit15=1Internal serial link data flow detected error
This register is reset after powering OFF/ON.
SF00 [Safety Fault Subregister 00]
This is an application auto test error register.
BitDescription
Bit0Reserved
Bit1=1Ram stack overflow
Bit2=1Ram address integrity detected error
Bit3=1Ram data access detected error
Bit4=1Flash checksum detected error
Bit5Reserved
Bit6Reserved
Bit7Reserved
Bit8Reserved
Bit9=1Fast task overflow
Bit10=1Slow task overflow
Bit11=1Application task overflow
Bit12Reserved
Bit13Reserved
Bit14=1PWRM line is not activated during initialization phase
Bit15=1Application hardware watchdog is not running after initialization
This register is reset after powering OFF/ON.
S1A45606 08/201451
SF01 [Safety Fault Subregister 01]
This is a logical input diagnostics error register
BitDescription
Bit0=1Management - state machine detected error
Bit1=1Data required for test management are corrupted
Bit2=1Channel selection detected error
Bit3=1Testing - state machine detected error
Bit4=1Test request is corrupted
Bit5=1Pointer to test method is corrupted
Bit6=1Incorrect test action provided
Bit7=1Detected error in results collecting
Bit8=1LI3 detected error.Cannot activate safety function
Bit9=1LI4 detected error. Cannot activate safety function
Bit10=1LI5 detected error. Cannot activate safety function
Bit11=1LI6 is detected error. Cannot activate safety function
Bit12=1Test sequence updated while a diagnostic is in progress
Bit13=1Detected error in test pattern management
Bit14Reserved
Bit15Reserved
This register is reset after powering OFF/ON.
SF02 [Safety Fault Subregister 02]
This is an application watchdog manag ement detected error register.
BitDescription
Bit0=1Fast task detected error
Bit1=1Slow task detected error
Bit2=1Application task detected error
Bit3=1Background task detected error
Bit4=1Safety function fast task/input detected error
Bit5=1Safety function slow task/input detected error
Bit6=1Safety function application task/inputs detected error
Bit7=1Safety function application task/treatment detected error
Bit8=1Safety function background task detected error
Bit9Reserved
Bit10Reserved
Bit11Reserved
Bit12Reserved
Bit13Reserved
Bit14Reserved
Bit15Reserved
This register is reset after powering OFF/ON.
52S1A45606 08/2014
SF03 [Safety Fault Subregister 03]
BitDescription
Bit0=1Debounce time out
Bit1=1Input not consistent
Bit2=1Consistency verification - state machine detected error
Bit3=1Consistency verification - debounce timeout corrupted
Bit4=1Response time data detected error
Bit5=1Response time corrupted
Bit6=1Undefined consumer queried
Bit7=1Configuration detected error
Bit8=1Inputs are not in nominal mode
Bit9Reserved
Bit10Reserved
Bit11Reserved
Bit12Reserved
Bit13Reserved
Bit14Reserved
Bit15Reserved
This register is reset after powering OFF/ON.
SF04 [Safety Fault Subregister 04]
This is a [Safe Torque Off] STO detected error register
This is a motor control auto test detected error register.
BitDescription
Bit0Reserved
Bit1=1Ram stack overflow
Bit2=1Ram address integrity detected error
Bit3=1Ram data access detected error
Bit4=1Flash checksum error
Bit5Reserved
Bit6Reserved
Bit7Reserved
Bit8Reserved
Bit9=11 ms task overflow
Bit10=1PWM task overflow
Bit11=1Fixed task overflow
Bit12Reserved
Bit13Reserved
Bit14=1Unwanted interruption
Bit15=1Hardware WD is not running after initialization
This register is reset after powering OFF/ON.
SF10 [Safety Fault Subregister 10]
This is a motor control direct short-circuit detected error register
BitDescription
Bit0=1Ground short circuit - configuration detected error
Bit1=1Phase to phase short circuit - configuration detected error
Bit2=1Ground short circuit
Bit3=1Phase to phase short circuit
Bit4Reserved
Bit5Reserved
Bit6Reserved
Bit7Reserved
Bit8Reserved
Bit9Reserved
Bit10Reserved
Bit11Reserved
Bit12Reserved
Bit13Reserved
Bit14Reserved
Bit15Reserved
This register is reset after powering OFF/ON.
56S1A45606 08/2014
SF11 [Safety Fault Subregister 11]
This is a motor control dynamic verification of activity detected error register
BitDescription
Bit0=1Application requested a diagnostic of direct short-circuit
Bit1=1Application requested consistency verification of stator frequency estimation (voltage and current)
Bit2=1Application requested diagnostic of SpdStat provided by motor control
Bit3Reserved
Bit4Reserved
Bit5Reserved
Bit6Reserved
Bit7Reserved
Bit8=1Motor control diagnostic of direct short circuit is enabled
Bit9=1Motor control consistency verification of stator frequency estimation is enabled
Bit10=1 Motor control diagnostic of SpdStat provided by motor control is enabled
Bit11Reserved
Bit12Reserved
Bit13Reserved
Bit14Reserved
Bit15Reserved
This register is reset after powering OFF/ON.
S1A45606 08/201457
58S1A45606 08/2014
Technical Data
Chapter 6
Technical Data
What Is in This Chapter?
This chapter contains the following topics:
Electrical Data58
Getting and Operating the Safety Function59
Safety Function Capability60
Debounce Time and Response Time62
TopicPage
S1A45606 08/201457
Electrical Data
Logic Type
Cabling Label
The drive logic inputs and logic outputs can be wired for logic type 1 or logic type 2.
Logic TypeActive State
1The output draws current (Sink)
Current flows to the input
2The output supply flows from the input current
Current (Source)
Safety functions must only be used in source mode.
Signal inputs are protected against reverse polarity, outputs are protected against short-circuits. The inputs
and outputs are galvanically isolated.
58S1A45606 08/2014
Getting and Operating the Safety Function
Logic Input
General-purpose logic inputs can be used to trigger a safety function. Logic inputs have to be combined in
pairs to obtain a redundant request. There are only 4 general-purpose logic inputs that can be linked to
safety functions (LI3, LI4, LI5, LI6).The pairs of logic inputs are fixed and are:
z LI3 and LI4
z LI5 and LI6
z Another combination is only possible for the STO function: LI3 and STO
Pairs of logic inputs can only be assigned once when they are linked to a safety function. When you set a
safety function on an logic input you cannot set another function (safety or other) on this logic input. If you
set a non-safety function on an logic input you cannot set a safety function on this logic input.
The SISTEMA Software
The SISTEMA software allows machine developers and testers of safety-related machine controls to
evaluate the safety standard or level of their machine in the context of ISO 13849-1. The tool allows you
to model the structure of safety-related control components based on the designated architectures,
allowing automated calculation of the reliability standards with various levels of detail, including that of the
Performance Level (PL).
The Altivar 32 Libraries are available from www.schneider-electric.com.
Preventa Safety Relays
Used for the creation of complex safety functions in machines, allowing management of the I/O, and also
for protecting both the operator and the machine.
The Preventa range of products feature microprocessor-based technology using the redundancy principle,
and are essential to ensure safe operation of dangerous machinery.
S1A45606 08/201459
Safety Function Capability
PDS (SR) safety functions are part of an overall system
If the qualitative and quantitative safety objectives determined by the final application require some
adjustments to ensure safe use of the safety functions, the integrator of the BDM (Basic Drive Module) is
responsible for these additional changes (for example, managing the mechanical brake on the motor).
Also, the output data generated by the use of safety functions (fault relay activation, error codes or
information on the display, etc.) is not considered to be safety-related data.
Machine Application Function Configuration
STOSS1 type C (5)SLS/STO/SS
STOSTO and LI3STO with Preventa
IEC 61800-5-2 /
IEC 61508 /
IEC 62061 (1)SIL2SIL3 CLSIL2 CLSIL3 CLSIL2 CL
EN 954-1 (2)Category 3Category 4Category 3Category 4Category 3
ISO 13849-1 (3)Category 3
(1) Because the IEC 62061 standard concerns integration, this standard distinguishes the overall safety
function (which is classified SIL2 or SIL3 for ATV32 according to the diagrams Process system SF - Case 1
and Process system SF - Case 2 from components which constitute the safety function (which is classified
SIL2 CL or SIL3 CL for ATV32).
(2) According to table 6 of IEC 62061 (2005).
(3) According to table 4 of EN 13849-1 (2008).
(4) If protection against supply interruption or voltage reduction and subsequent restora tio n is needed
according to IEC 60204-1, a safety module type Preventa XPS AF or equivalent must be used.
(5) SS1 type C: the power drive initiates the motor deceleration and initiates the STO function after an
application specific time delay.
(6) SS1 type B: the power drive initiates and monitors the moto r deceleration rate within set limits to stop
the motor and initiates the STO function when the motor speed is below a specified limit.
Process Application Function Configurati on
STOSS1 type C (2)SLS / STO / SS1 type B
STOSTO and LI3STO with Preventa
IEC 61800-5-2
IEC 61508
IEC 62061 (1)SIL2 CLSIL3 CLSIL2 CLSIL3 CLSIL2 CL
Standard
SIL2SIL3SIL2SIL3SIL2
XPS ATE or XPS AV
or equivalent
STO and LI3
with Preventa
XPS AV or
equivalent
(3)
LI3 LI4LI5 LI6
(1) Because the IEC 62061 standard concerns integration, this standard distinguishes the overall safety
function (which is classified SIL2 or SIL3 for ATV32 according to diagrams CASE 1 and CASE 2 from
components which constitute the safety function (which is classified SIL2 CL or SIL3 CL for ATV32).
(2) SS1 type C: the power drive initiates the motor deceleration and initiates the STO function after an
application specific time delay.
(3) SS1 type B: the power drive initiates and monitors the moto r deceleration rate within set limits to stop
the motor and initiates the STO function when the motor speed is below a specified limit.
60S1A45606 08/2014
Input Signal Safety Functions
Input signals safety functionsUnitsValue for LI3 to LI6Value for STO
PFD10y7.26.10-44.00.10-42.44.10-3
PFD1y7.18.10-53.92.10-52.33.10-4
PFHequ_1y8.20 FIT (1)4.47 FIT (1)26.6 FIT (1)
TypeBBB
HFT110
DC93.1%91.5%90%
SIL capability232
IEC 62061 (1)SIL CL capability232
EN 954-1 (2)Category343
ISO 13849-1 (3)PLded
Category343
MTTFd in years13900L1 3850L2 293004290
IEC 61508 Ed.2SFF93.3%
PFD10y2.72.10-3
PFHequ_10y31.1 FIT (1)
TypeB
HFT0
DC78.7%
SIL capability2
IEC 62061 (2)SIL CL capability2
EN 954-1 (3)Category3
ISO 13849-1 (4)PLd
Category3
MTTFd in years3670
(1) FIT: Failure In Time = Failure/10-9 hours.
(2) Because the IEC 62061 standard concerns integration, this standard distinguishes the overall safety
function (which is classified SIL2 or SIL3 for ATV32 according to diagrams Process system SF - Case 1
and Process system SF - Case 2, from components which constitute the safety function (which is classified
SIL2 CL or SIL3 CL for ATV32).
(3) According to table 6 of IEC 62061 (2005).
(4) According to table 4 of EN 13849-1 (2008).
Preventive annual activation of the safety function is recommended.
However, the safety levels can be obtained (with lower margins) without annual activation.
For the machine environment, a safety module is required for the STO function.
To avoid the use of a safety module, the Restart function parameters must be part of the safety function.
Please refer to the description of advantages of the safety module.
NOTE: The table above is not sufficient to evaluate the PL of a PDS. The PL evaluation has to be done at
the system level. The fitter or the integrator of the BDM (Basic Drive Module) has to do the system PL
evaluation by including sensors data with numbers from the table above.
S1A45606 08/201461
Debounce Time and Response Time
Description
On the ATV32 there are 2 parameters to configure logic inputs for safety function (LI3, LI4, LI5, LI6).
The consistency of each pair of logical input is verified continuously.
[LI debounce time]LIdt: A logical state difference between LI3/LI4 or LI5/LI6 is allowed during
debounce time, otherwise a detected error is activated.
[LI response time]LIrt: The logic input response time manages the safety function activation shift.
: Logic input Response Time
c
: Logic input Debounce Time
62S1A45606 08/2014
Certified Architectures
Chapter 7
Certified Architectures
What Is in This Chapter?
This chapter contains the following topics:
Introduction64
Multi-drive with the Safety Module Type Preventa XPS AF - Case 165
Multi-drive with the Safety Module Type Preventa XPS AF - Case 266
Multi-drive Without the Safety Module67
Single Drive with the Safety Module Type Preventa XPS AV - Case 168
Single Drive with the Safety Module Type Preventa XPS AV - Case 269
Single Drive with the Safety Module Type Preventa XPS AF - Case 170
Single Drive with the Safety Module Type Preventa XPS AF - Case 271
Single Drive According to IEC 61508 and IEC 60204-1 - Case 172
Single Drive According to IEC 61508 and IEC 60204-1 - Case 273
TopicPage
S1A45606 08/201463
Introduction
Certified Architectures
NOTE: For certification relating to functional aspects, only the PDS(SR) (Power Drive System suitable for
use in safety-related applications) will be considered, not the complete system into which it is integrated to
help to ensure the functional safety of a machine or a system/process.
These are the certified architectures:
z Multi-drive with the Safety module type Preventa XPS AF - Case 1
z Multi-drive with the Safety module type Preventa XPS AF - Case 2
z Multi-drive without the Safety module
z Single drive with the Safety module type Preventa XPS AV - Case 1
z Single drive with the Safety module type Preventa XPS AV - Case 2
z Single drive with the Safety module type Preventa XPS AF - Case 1
z Single drive with the Safety module type Preventa XPS AF - Case 2
z Single drive according to IEC 61508 and IEC 60204-1 - Case 1
z Single drive according to IEC 61508 and IEC 60204-1 - Case 2
The safety functions of a PDS(SR) (Power Drive System suitable for use in safety-related applications) are
part of an overall system.
If the qualitative and quantitative safety-related objectives determined by the final application require some
adjustments to ensure safe use of the safety functions, the integrator of the BDM (Basic Drive Module) is
responsible for these additional changes (for example, managing the mechanical brake on the motor).
Also, the output data generated by the use of safety functions (fault relay activation, error codes or
information on the display, etc.) is not considered to be a safety-related data.
64S1A45606 08/2014
Multi-drive with the Safety Module Type Preventa XPS AF - Case 1
Multi-drive with the Safety Module Type Preventa XPS AF According to EN 954-1, ISO 13849-1 and IEC 60204-1
(Machine)
The following configurations apply to the diagram:
z STO category 4, PL e/SIL3 Machine with Safety module type Preventa XPS AF or equivalent and LI3
set to STO
z SLS category 3, PL d/SIL2 or SS1 type B category 3 on LI5/LI6
Or
z STO category 4, PL e/SIL3 Machine with Safety module type Preventa XPS AF or equivalent and LI3
set to STO
z LI4 and LI5/LI6 not set to a safety function
(1) Braking resistor, if used, (2) Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B
according to NF C 93-550, external diameter 2.54 mm /0.09 in., maximum length 15 m / 49.21 ft. The cable
shielding must be earthed, (3) Line choke, if used, (4) Multi-drives is possible with another drive (Example:
ATV71 with PWR connection or Lexium servo drives)
NOTE: For more information about the control terminal characteristics, please refer to the installation
manual.
S1A45606 08/201465
Multi-drive with the Safety Module Type Preventa XPS AF - Case 2
Multi-drive with the Safety Module Type Preventa XPS AF According to EN 954-1, ISO 13849-1 and IEC 60204-1
(Machine)
The following configurations apply to the diagram below:
z STO category 3, PL d/SIL2 Machine with Safety module type Preventa XPS AF or equivalent
z SLS category 3, PL d/SIL2 or SS1 type B category 3 on LI3/LI4 or LI5/LI6
(1) Braking resistor, if used, (2) Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B
according to NF C 93-550, external diameter 2.54 mm /0.09 in., maximum length 15 m / 49.21 ft. The cable
shielding must be earthed, (3) Line choke, if used, (4) Multi-drives is possible with another drive (Example:
ATV71 with PWR connection or Lexium servo drives).
NOTE: For more information about the control terminal characteristics, please refer to the installation
manual.
66S1A45606 08/2014
Multi-drive Without the Safety Module
Multi-drive Without the Safety Module Type Preventa XPS AF According to IEC 61508
The following configurations apply to the diagram below:
z STO SIL2 on STO
z SLS SIL2 or SS1 type B SIL2 on LI3/LI4 or LI5/LI6
Or
z STO SIL2 on STO
z SLS or SS1 type B on LI3/LI4
z LI5/LI6 not set to a safety function
Or
z STO SIL2 on STO
z LI3/LI4 and LI5/LI6 not set to a safety function
Or
z STO SIL3 on STO and LI3
z SLS SIL2 or SS1 type B SIL2 on LI5/LI6
z LI4 not set to a safety function
Or
z STO SIL3 on STO and LI3
z LI4 and LI5/LI6 not set to a safety function
(1) Braking resistor, if used, (2) Line chokes, if used.
NOTE: For more information about the control terminal characteristics, please refer to the installation
manual.
S1A45606 08/201467
Single Drive with the Safety Module Type Preventa XPS AV - Case 1
Single Drive with the Safety Module Type Preventa XPS AV According to EN 954-1, ISO 13849-1 and IEC 60204-1
(Machine)
The following configurations apply to the diagram below:
z SS1 type C category 3, PL d/SIL2 on STO with Safety module type Preventa XPS AV or equivalent
Or
z SS1 type C category 3, PL d/SIL2 on STO with Safety module type Preventa XPS AV or equivalent
z SLS category 3, PL d/SIL2 or SS1 type B category 3 on LI3/LI4
z LI5/LI6 not set to a safety function
Or
z SS1 type C category 3, PL d/SIL2 on STO and LI3 with Safety module type Preventa XPS AV or
equivalent
z LI3/LI4 and LI5/LI6 not set to a safety function
(1) Channel 1 logic, (2) Channel 2 logic, (3) Output 1, (4) Output 2, (5) Emergency stop, (6) Start, (7) Time
delay stop, (8) Braking resistor, if used, (9) Line chokes, if used
NOTE: For more information about the control terminal characteristics, please refer to the installation
manual.
68S1A45606 08/2014
Single Drive with the Safety Module Type Preventa XPS AV - Case 2
Single Drive with the Safety Module Type Preventa XPS AV According to EN 954-1, ISO 13849-1 and IEC 60204-1
(Machine)
The following configurations apply to the diagram below:
z SS1 type C category 4, PL e/SIL3 on STO and LI3 with Safety module type Preventa XPS AV or
equivalent
z SLS category 3, PL d/SIL2 or SS1 type B category 3 PL d/SIL2 on LI5/LI6
z LI4 not set to a safety function
(1) Channel 1 logic, (2) Channel 2 logic, (3) Output 1, (4) Output 2, (5) Emergency stop, (6) Time delay
stop, (7) Braking resistor, if used, (8) Line chokes, if used.
NOTE: For more information about the control terminal characteristics, please refer to the installation
manual.
S1A45606 08/201469
Single Drive with the Safety Module Type Preventa XPS AF - Case 1
Single Drive with the Safety Module Type Preventa XPS AF According to EN 954-1, ISO 13849-1, IEC 62061 and 602041 (Machine)
The following configurations apply to the diagram below:
z STO category 3, PL d/SIL2 on STO with Safety module type Preventa XPS AF or equivalent
z SLS category 3, PL d/SIL2 or SS1 type B category 3 on LI3/LI4 or LI5/LI6
Or
z STO category 3, PL d/SIL2 on STO with Safety module type Preventa XPS AF or equivalent
z SLS category 3, PL d/SIL2 or SS1 type B category 3 on LI3/LI4
z LI5/LI6 not set to a safety function
Or
z STO category 3, PL d/SIL2 on STO with Safety module type Preventa XPS AF or equivalent
z LI3/LI4 and LI5/LI6 not set to a safety function
(1) Braking resistor, if used, (2) Line chokes, if used.
NOTE: For more information about the control terminal characteristics, please refer to the installation
manual.
70S1A45606 08/2014
Single Drive with the Safety Module Type Preventa XPS AF - Case 2
Single Drive with the Safety Module Type Preventa XPS AF According to EN 954-1, ISO 13849-1, IEC 62061 and 602041 (Machine)
The following configurations apply to the diagram below:
z STO category 4, PL e/SIL3 on STO with Safety module type Preventa XPS AF or equivalent and LI3
set to STO
z SLS category 3, PL d/SIL2 or SS1 type B category 3 on LI5/LI6
z LI4 not set to a safety function
(1) Start, (2) Braking resistor, if used, (3) Line chokes if used.
NOTE: For more information about the control terminal characteristics, please refer to the installation
manual.
S1A45606 08/201471
Single Drive According to IEC 61508 and IEC 60204-1 - Case 1
Single Drive According to IEC 61508 and IEC 60204-1 Withou t Protection Against Supply Interruption or Voltage
Reduction and Subsequent Rotation
The following configurations apply to the diagram below:
z STO SIL2 on STO
z STO or SLS SIL2 or SS1 type B SIL2 on LI3/LI4 or LI5/LI6
Or
z STO SIL2 on STO
z STO or SLS or SS1 type B on LI3/LI4
z LI5/LI6 not set to a safety function
Or
z STO SIL2 on STO
z LI3/LI4 and LI5/LI6 not set to a safety function
Or
z STO SIL3 on STO and LI3
z SLS SIL2 or SS1 type B SIL2 on LI5/LI6
z LI4 not set to a safety function
Or
z STO SIL3 on STO and LI3
z LI4 and LI5/LI6 not set to a safety function
(1) Braking resistor, if used, (2) Line chokes if used.
NOTE: For more information about the control terminal characteristics, please refer to the installation
manual.
72S1A45606 08/2014
Single Drive According to IEC 61508 and IEC 60204-1 - Case 2
Single Drive According to IEC 61508 and IEC 60204-1 Withou t Protection Against Supply Interruption or Voltage
Reduction and Subsequent Rotation
The following configurations apply to the diagram below:
z STO SIL2 on LI3 and LI4
z SLS SIL2 or SS1 type B SIL2 on LI5/LI6
Or
z STO SIL2 on LI3 and LI4
z LI5/LI6 not set to a safety function
Wiring Diagram
(1) Braking resistor, if used, (2) Line chokes, if used.
NOTE: For more information about the control terminal characteristics, please refer to the installation
manual.
S1A45606 08/201473
74S1A45606 08/2014
Commissioning
Chapter 8
Commissioning
What Is in This Chapter?
This chapter contains the following topics:
Safety Functions Tab76
Configure Safety Functions Panel77
Visualization and Status of Safety Functions81
Copying Safety Related Configuration from Device to PC and from PC to Device82
Machine Signature85
TopicPage
S1A45606 08/201475
Safety Functions Tab
Introduction
To access the safety function configuration, click the Safety Functions tab. This screen is read-only,
allowing you to see all current safety function configurations.
The Safety Functions tab provides access to:
z an outline of the safety function features available on the ATV32 (accessible online/offline)
z the status of all I/O in connected mode
z general information about the machine (online/offline).
It also provides access to the following dialog boxes:
z Configuration
z Configure (only available in connected mode)
z Reset Configuration
z Copy from DEVICE to PC
z Copy from PC to DEVICE
z Password Configuration
z Modify Password
z Reset Password
Steps to Configure the Safety Functions
If...Then ...
you are not in online mode In the menu bar, click Communication → Connect to Device or click the
you are online modeClick the Configure button in the Safety Functions tab.
Connect to Device icon
Once connected:
StepActionComment
1 Click the Configure button in the
Safety Functions tab.
If...Then ...
you have already defined
the password
type your safety function configuration password in Enter Configuration
Password box, click Ok.
Result: Opens the Configuration of Safety Functions window.
A Define Configuration Password dialog box appears:
z Type the new configuration password in Enter New
Password box
z Retype the new configuration password in Confirm New
Password box.
z Click Ok
NOTE:
Your password:
z Should have only numeric value, choose the value
between 1...9999.
z Should not exceed more than 4 digits.
z Should not have the value 0.
Result: Opens the Configuration of Safety Functions
window.
76S1A45606 08/2014
Configure Safety Functions Panel
Overview
The Configuration of Safety Functions panel includes the Information, STO, SLS, SS1 and
Input/Output tabs.
Information Tab
The information tab allows you to define and display product system information
Information filled in automatically by SoMove:
z Date (format depends on the PC local and linguistic options)
z Device Type
z Drive Reference
Information filled in manually:
z Device Serial No (number)
z Machine Name
z Company Name
z End-User Name
z Comments
Safe Torque Off (STO) Tab
For more information about STO function, see STO description (see page 18).
For this function, only the associated set of inputs should be selected in the box. The parameter to be
managed is: STOA.
CodeName/DescriptionFactory
StO[Safe Torque Off]
StOA[STO function activation][No]
L3PW
[No: Not assigned]
nO
[LI3 and LI4]: logic input 3/4 low state
L34
[LI5 and LI6]: logic input 5/6 low state
L56
[LI3 and STO]: logic input 3/STO low state
This parameter is used to configure the channel used to trigger the STO function. If you set STOA=No,
STO function is always active but just on STO input
Setting
S1A45606 08/201477
Safely Limited Speed (SLS) Tab
For more information about SLS function, see SLS description (see page 22).
[LI3 and LI4]: logic input 3/4 low state
[LI5 and LI6]: logic input 5/6 low state
This parameter is used to configure the channel used to trigger the SLS function.
This parameter is used to select the SLS type.
[Type1] : SLS type 1
[Type2] : SLS type 2
[Type3] : SLS type 3
[Type4]: SLS type 4
Refer to function description to have information about behavior of different type.
This parameter is only visible if SLT = Type2 or SLT = Type3 or SLT = Type 4
SLSP is used to set the maximum speed
The behavior of this parameter depends on the value of SLT, see above
This parameter is used to set the maximum time for StFr to be greater than SSSL.
When SLwt is reached, STO function is triggered.
Unit of this parameter is 1 ms.
For example
If the value is set to 2000 units, then the SLS wait time in second is:
2000*1 ms = 2 s
This parameter can be modified only if SLT = Type 2 or SLT = Type 3
For SLS type 1 and SLS type 4, SLwt is always set to 0
The unit depends on the SSRU parameter. Use this parameter to set the value of the SS1 deceleration
ramp.
SS1 ramp = SSRT*SSRU example: If SSRT = 250 and SSRU = 1 Hz/s then the deceleration ramp = 25
Hz/s.
This parameter is similar to the SS1 safety function, for more information see SS1 (see page 35).
[SS1 ramp unit] parameter[1 Hz/s]
[1 Hz/s]
[10 Hz/s]
[100 Hz/s]
This parameter is used to set the SSrt unit.
This parameter is similar to the SS1 safety function configured, for more information see SS1
(see page 35).
This parameter sets the tolerance zone around the deceleration ramp in which the frequency may vary.
This parameter is similar to the SS1 safety function configured in another tab.
This parameter adjusts the frequency at which the drive should go into STO state at the end of the SS1
ramp.
This parameter is similar to the SS1 safety function configured in another tab.
78S1A45606 08/2014
Safe Stop 1 (SS1) Tab
For more information about SS1 function, see SS1 description (seepage20).
[LI5 and LI6]: logic input 5/6 low state
This parameter is used to configure the channel used to trigger the SS1 function.
The unit depends on the SSRU parameter. Use this parameter to set the value of the SS1 deceleration
ramp.
SS1 ramp = SSRT*SSRU example: If SSRT = 250 and SSRU = 1 Hz/s then the deceleration ramp =
25 Hz/s.
This parameter is similar to the SLS safety function configured in another tab.
[1 Hz/s]
1H
[10 Hz/s]
10H
[100 Hz/s]
This parameter is used to set the SSRT unit.
This parameter is similar to the SLS safety function configured in another tab.
This parameter sets the tolerance zone around the deceleration ramp in which the frequency may vary.
This parameter is similar to the SLS safety function configured,
This parameter adjusts the frequency at which the drive should go into STO state at the end of the SS1
ramp.
This parameter is similar to the SLS safety function configured in another tab.
Input/Output Configuration
The figure shows the Input/Output tab:
S1A45606 08/201479
CodeName/DescriptionAdj. RangeFactory
IO[Input/Output]
LIdt[LI debounce time] 0...2000 ms50
In most cases, the 2 logic inputs in a pair used for a safety function (LI3-LI4 or LI5-LI6 or STO-LI3) will
not be 100% synchronized. They will not change state at the same time. There is a small delta between
the 2 logic input transitions.
LIdt is the parameter used to set this delta. If the 2 logic inputs change state with a delta lasting less
than LIdt it is considered to be simultaneous transition of the logic inputs. If the delta lasts longer
than LIdt, the drive considers the logic Inputs are no longer synchronized and detected error is
triggered.
LIrt[LI response time] 0...50 ms0
This parameter is used to filter short impulses on the logic input (only for LI3-LI4 or LI5-LI6, STO not
concerned). Some applications send short impulses on the line to test it. This parameter is used to filter
these short impulses. Commands are only taken into account if the duration is longer than LIrt.
If the duration is shorter the drive considers that there is no command: the command is filtered.
Password Configuration - Modify Password
This function allows you to modify the configuration password in the drive.
To modify the configuration password
StepAction
1In Safety Functions tab, click the Modify Password button
Result: opens the Modify Configuration Password dialog box.
2In the Modify Configuration Password dialog box:
z Type the existing configuration password in Enter Current Password box
z Type the new configuration password in Enter New Password box
z Retype the new configuration password in Confirm New Password box
z Click Ok
NOTE: The password typed in Enter New Password box and Confirm New Password box should be
same.
NOTE:
Your password:
z Should contain only numeric value, choose the value between 1...9999.
z Should not exceed more than 4 digits.
z Should not have the value 0.
Result: modifies the configuration password.
Setting
Password Configuration - Reset Password
If you cannot remember the configuration password defined in the drive, you need to know the universal
password to reset the drive. To obtain this password, contact your Schneider Electric contact.
After this operation, the device reverts to no defined configuration password and the session is
automatically closed.
However, the function configuration remains unchanged.
Reset Configuration
This function is used to reset the configuration of the safety function to the factory settings.
To access the function, click the Reset Configuration button in the Safety Functions tab.
First enter the password, then confirm your choice.
After this action, all safety-related parameters are set to factory settings.
80S1A45606 08/2014
Visualization and Status of Safety Functions
CodeName/Description
SAF-[MONIT. SAFETY] menu - Visible on SoMove and keypad
StFr[Stator Frequency]
Displays the estimated stator frequency in Hz
StOS[STO status]
Status of the Safe Torque Off safety function
IdLE
SLSS[SLS status]
IdLE
WAIt
Strt
SS1S[SS1 status]
IdLE
SAF-[MONIT. SAFETY] menu - Visible ONLY on SoMove
SFtY[Safety drive status]
IStd
SAFE
[IdLE]: STO not in progress
[Safe torque off]: STO in progress
StO
[Fault]: STO in detected error
FLt
Status of the Safely limited speed safety function
[Not config]: SLS not configured
nO
[IdLE]: SLS not in progress
[Safe stop 1]: SLS ramp in progress
SSI
[Safe torque off]: SLS safe torque off request in progress
StO
[Fault]: SLS in detected error
FLt
[wAIT]: SLS waiting for activation
[Started]: SLS in transient state
Status of the Safe Stop 1 safety function
[Not config]: SS1 not configured
nO
[IdLE]: SS1 not in progress
[Safe stop 1]: SS1 ramp in progress
SSI
[Safe torque off]: SS1 safe torque off request in progress
StO
[Fault]: SS1 in detected error
FLt
Safety function status of the drive
[Standard drive]: Standard product without safety function configured
[Safety drive]: product with at least 1 safety function configured
S1A45606 08/201481
Copying Safety Related Configuration from Device to PC and from PC to Device
Overview
This feature is used to copy/paste the tested safety-related configuration in several ATV32 drives.
This feature allows you to:
z identify unique safety-related configuration on the drive
z copy the safety-related configuration file from ATV32 drive to PC.
z copy the safety-related configuration file from PC to ATV32 drives
Architecture
The figure shows the architecture for copying the safety-related configuration from device to PC and PC to
device:
82S1A45606 08/2014
Identify Unique Safety Related Configuration
The identification of the safety-related configuration is done by using CRC, calculated using all safetyrelated parameters
You can get the CRC value from My Device tab. Note down the CRC value after the drive is fully tested.
Copy from Device to PC
To copy a configuration file from device to PC:
StepAction
1In the Safety Functions tab, click the Copy from DEVICE to PC button
Result: opens the Copy from Device to PC dialog box.
2Type the configuration password in Enter configuration Password box, click Ok.
Result: Displays the CRC1 value
3Note the CRC1 value, click Save.
Result: opens the Save File... window.
4In the Save File.. Window:
z Select/create the folder
z Type the name of the file in File name box.
z Click Save,
Result: Safety-related Parameters Successfully saved message appears on the screen,
which confirms that the file has been saved successfully in the desired path.
NOTE:
You cannot copy the configuration from device to PC if:
z the motor is powered.
z a function block is in Run state.
z the function Forced Local is active.
z a safety function is triggered.
S1A45606 08/201483
Copy from PC to Device
UNEXPECTED EQUIPMENT OPERATION
z Connect the PC using point-to-point connection.
z Copy from PC to Device operation should be performed only by qualified IEC61800-5-2 personnel
z Test the safety function configuration after copying the configuration from PC to device.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
To copy a file from PC to device:
StepAction
WARNING
1In the Safety Functions tab, click the Copy from PC to DEVICE button
Result: Warning box appears, read the following instruction before proceeding with copy from
PC to device operation.
2
Click OkResult: Opens the Open File... window.
3In the Open File... Window
z Select .sfty file.
z Click Open
Result: Displays the CRC1 value
4Verify whether the CRC1 value is same as the CRC1 value noted while copying the configuration
from device to PC if both CRC1 values are same then click Continue.Result: Opens the Copy from PC to Device dialog box.
5Type the password (49157) in the Enter copy password box, click Ok.
Result: Configuration is successfully copied from PC to device. A commisoning test must be
done on the safety function.
NOTE:
You cannot copy the cofiguration from PC to device if:
z the motor is powered.
z a function block is in Run state.
z the function Forced Local is active.
z the configuration of the safety function is already present in the device
84S1A45606 08/2014
Machine Signature
Overview
The purpose of the test is to verify proper configuration of the defined safety functions and test mechanisms
and to examine the response of dedicated monitoring functions to explicit input of values outside the
tolerance limits.
The test must cover all drive-specific Safety configured monitoring functions and global Safety integrated
functionality in ATV32.
Condition Prior to Acceptance Test
z The machine is wired up correctly.
z All safety-related devices such as protective door monitoring devices, light barriers, and emergency
stop switches are connected and ready for operation.
z All motor parameters and command parameters must be correctly set on the drive.
Acceptance Test Process
The acceptance test is configured with SoMove software.
StepActionComment
1 Select the Device → Safety Function → Machine
Signature menu and follow the five steps below
2 General Information
To add this step to the final report select Add to the
machine signature
Click Next.
3 Function Summary
To add a function to the final report select Add to the
machine signature
Click Next
4 I/O Summary
To add a function to the final report select Add to the
machine signature
Click Next
5 Test
To add a function to the final report select Add to the
machine signature
Click Next
6 Key
Click Finish to create the report
The information displayed here corresponds to the
Identification section in the Safety Functions tab.
This step is composed of sub-steps.
Each sub-step relates to one of the following safety
functions:
z STO
z SLS
z SS1
In a function, sub-step the function diagram and
parameters values are displayed.
A text box allows you to enter additional text in this
step.
The information displayed here corresponds to the
Logic Input summary folder of the Safety
Functions tab:
z The logic input that is assigned to a safety
function are displayed in red and show the related
safety function
z The logic input that is not assigned to a safety
function do not show any assignment and are
displayed in green
In this step, you tick the box when you have tested
the safety functions to confirm that you have verified
the correct behavior of the functions for all devices.
The checksum of the safety-related configuration is
displayed as it is calculated for transmission to the
connected device when you click Apply.
This allows you to compare the checksum value with
the one displayed in the identification menu on the
graphic display terminal
S1A45606 08/201485
Acceptance Report
SoMove creates the acceptance report.
This function provides a final report when one or several safety functions have been configured and
verified.This report is deemed to be a machine signature and certifies that all the safety functi ons are
operational.The acceptance report has been added as an optional document to be printed to a printer or
to a PDF file.
If the drive configuration is modified (not only applicable on the safety related parameters), you
must repeat the acceptance test.
86S1A45606 08/2014
Services and Maintenance
Chapter 9
Services and Maintenance
What Is in This Chapter?
This chapter contains the following topics:
Maintenance90
Power and MCU Replacement91
Changing Machine Equipment92
TopicPage
S1A45606 08/201489
Maintenance
Overview
By way of preventive maintenance, the Safety functions must be activated at least once a year. The drive
power supply must be turned off and then on again before carrying out this preventive maintenance. The
drive logic output signals cannot be considered to be safety-related signals. Install interference
suppressors on all inductive circuits near the drive or coupled to the same circuit (relays, contactors,
solenoid, valves, etc.).
NOTE: For more product information, see the installation manual and programming manual on
www.schneider-electric.com.
90S1A45606 08/2014
Power and MCU Replacement
Overview
You can replace the MCU (Motor Control Unit) part (APP + HMI card) and the power part.
Depending on the drive configuration (safety function active or not), the drive response will differ.
If you replace the power and you keep your MCU, you won’t lose the configuration of the safety functions
but you need to repeat the Acceptance Test to avoid incorrect wiring or incorrect behavior of the safety
function.
If you replace the MCU you will lose your safety-related configuration. You need to reinstall your
Configuration on the new MCU and then repeat the Acceptance Test.
NOTE: For more product information, see the installation manual and programming manual
www.schneider-electric.com.
S1A45606 08/201491
Changing Machine Equipment
Overview
If you need to change any part of the drive system (Motor, Emergency stop, etc.) you must repeat the
Acceptance Test.
NOTE: For more product information, see the installation manual and programming manual
www.schneider-electric.com.
92S1A45606 08/2014
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.