Sanyo SAP-CRV93EH, SAP-KRV93EH, SAP-CRV123EH, SAP-KRV123EH User Manual

TECHNICAL & SERVICE MANUAL
SAP-KRV93EH + SAP-CRV93EH SAP-KRV123EH + SAP-CRV123EH
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
SAP-CRV93EH SAP-CRV123EH
N
DITIONER
IMPORTANT
These air conditioners employ new refrigerant R410A.
Pay special attention when servicing the unit.
SAP-KRV93EH SAP-KRV123EH
FILE NO.
REFERENCE NO. SM700590
W
Indoor Unit Outdoor Unit
Indoor Model No. Product Code No. SAP-KRV93EH 1 852 089 81 SAP-KRV123EH 1 852 089 80
Outdoor Model No. Product Code No.
SAP-CRV93EH 1 852 089 85 SAP-CRV123EH 1 852 089 84
Destination: Europe
2
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and oper­ating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a haz­ard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tub­ing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire
hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This pre­vents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refriger­ant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
WARNING
CAUTION
WARNING
CAUTION
3
Table of Contents
Page
1. OPERATING RANGE................................................................................................................ 4
2. SPECIFICATIONS
2-1. Unit Specifications ............................................................................................................ 5
2-2. Major Component Specifications...................................................................................... 7
2-3. Other Component Specifications...................................................................................... 11
3. DIMENSIONAL DATA................................................................................................................ 12
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram................................................................................................. 14
5. PERFORMANCE DATA
5-1. Temperature Charts..........................................................................................................15
5-2. Air Throw Distance Charts................................................................................................ 17
5-3. Operating Frequency Charts ............................................................................................ 19
6. ELECTRICAL DATA
6-1. Electrical Characteristics ..................................................................................................23
6-2. Electric Wiring Diagrams .................................................................................................. 24
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection .................................................................................................26
7-2. Recommended Wire Length and Diameter ...................................................................... 28
7-3. Remote Control Unit Installation Position ......................................................................... 29
7-4. How to Test Run the Air Conditioner ................................................................................ 30
7-5. Remove the Grille to Install the Indoor Unit...................................................................... 31
8. MAINTENANCE
8-1. Address Setting of the Remote Control Unit .................................................................... 32
8-2. Disconnecting and Connecting Positive Connector for Outdoor Unit ............................... 33
9. FUNCTIONS
9-1. Operation Functions .........................................................................................................34
9-2. Protective Functions ......................................................................................................... 36
10. TROUBLESHOOTING............................................................................................................... 38
11. CHECKING ELECTRICAL COMPONENTS
11-1. Measurement of Insulation Resistance ............................................................................ 43
11-2. Checking Continuity of Fuse on PCB Ass’y ..................................................................... 44
12. REFRIGERANT R410A:
SPECIAL PRECAUTIONS WHEN SERVICING UNIT .............................................................. 45
INSTRUCTION MANUAL ...................................................................................... 52
APPENDIX
4
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
Heating
Maximum 27°C D.B. 24°C D.B. / 18°C W.B.
Minimum 16°C D.B. –20°C D.B. / –20°C W.B.
5
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B .
Outdoor air temperature 7°C D.B. / 6°C W.B.
2. SPECIFICATIONS
2-1. Unit Specifications
Indoor Unit SAP-KRV93EH Outdoor Unit SAP-CRV93EH
Power Source 220 – 240V Single-phase 50Hz
Performance Cooling Heating
Capacity kW 2.65 (0.9 – 3.2) 3.60 (0.9 – 5.0)
BTU/h 9,000 (3,100 – 10,900) 12,300 (3,100 – 17,100)
Air circulation (High) m3/h 480 530 Moisture removal (High) Liters/h 1.6
Electrical Rating Cooling Heating
Available voltage range V 198 – 264 Running amperes A 3.86 (1.28 – 5.88) 4.81 (1.21 – 6.47) Power input W 755 (250 – 1,150) 995 (250 – 1,340) Power factor % 85 90 C.O.P. W/W 3.51 3.62 Compressor locked rotor amperes A 15
Features
Controls / Temperature control Microprocessor / I.C. thermister Control unit Wireless remote control unit Timer ON / OFF 24 hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1 (Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (DC inverter) Refrigerant / Amount charged at shipment g R410A / 950 Refrigerant control Electric expansion valve Operation sound Indoor: Hi / Me / Lo dB-A 34 / 31 / 28 34 / 31 / 28
Outdoor: Hi dB-A 46 47 Refrigerant tubing connections Flare type Max allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35 (1/4) tube diameter Wide tube mm (in.) 9.52 (3/8) Refrigerant tube kit / Accessories Optional / Air clean filter
Voltage Rating 230V
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 548
Width mm 825 720
Depth mm 189 265 Package dimensions Height mm 350 600
Width mm 900 856
Depth mm 255 362 Weight Net kg 9.0 34.0
Shipping kg 11.0 36.0 Shipping volume m
3
0.080 0.186
6
Indoor Unit SAP-KRV123EH Outdoor Unit SAP-CRV123EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B .
Outdoor air temperature 7°C D.B. / 6°C W.B.
Power Source 220 – 240V Single-phase 50Hz
Performance Cooling Heating
Capacity kW 3.50 (0.9 – 3.8) 4.20 (0.9 – 5.8)
BTU/h 11,900 (3,100 – 13,000) 14,300 (3,100 – 19,800) Air circulation (High) m3/h 500 530 Moisture removal (High) Liters/h 2.0
Electrical Rating Cooling Heating
Available voltage range V 198 – 264 Running amperes A 5.21 (1.19 – 6.21) 5.48 (1.18 – 7.09) Power input W 1,090 (250 – 1,300) 1,165 (250 – 1,500) Power factor % 91 92 C.O.P. W/W 3.21 3.61 Compressor locked rotor amperes A 15
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON / OFF 24 hours & Daily program, 1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto / 1 (Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (DC inverter) Refrigerant / Amount charged at shipment g R410A / 1,100 Refrigerant control Electric expansion valve Operation sound Indoor: Hi / Me / Lo dB-A 36 / 33 / 29 34 / 31 / 29
Outdoor: Hi dB-A 47 49 Refrigerant tubing connections Flare type Max allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35 (1/4) tube diameter Wide tube mm (in.) 9.52 (3/8) Refrigerant tube kit / Accessories Optional / Air clean filter
Voltage Rating 230V
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 285 548
Width mm 825 720
Depth mm 189 265 Package dimensions Height mm 350 600
Width mm 900 856
Depth mm 255 362 Weight Net kg 9.0 35.0
Shipping kg 11.0 37.0 Shipping volume m
3
0.080 0.186
7
2-2. Major Component Specifications
2-2-1. Indoor Unit
Indoor Unit SAP–KRV93EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Control PCB
Part No. CB-KRV93EH (POW-KRV93GJH) Controls Microprocessor Control circuit fuse 250V 3.15A
Flap Motor and Louver Motor
Type Stepping motor Model MP24Z3-12V Rating DC 12V
Coil resistance (Ambient temp. 25°C) Each pair of terminals: 400 ± 7%
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m
2
0.188
Fan & Fan Motor
Type Fan / Fan motor Cross-flow / AC motor Q’ty … Dia. and lengthmm1 … D92 / L634 Fan motor model … Q’ty IBH-884-066 … 1 No. of poles … Rough measure rpm (Cool / Heat) 4 … 1,200 / 1,250 Nominal output W 30
Coil resistance (Ambient temp. 20°C) BRN – WHT: 234
PNK (RED) – WHT: 209
— :
Safety devices Type Thermal fuse
Operating temp. Open °C 130
Close
Run capacitor µF 1.2
VAC 440
Remote Control Unit RCS-3HVPSS4E
8
Indoor Unit SAP–KRV123EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Control PCB
Part No. CB-KRV123EH (POW-KRV93GJH) Controls Microprocessor Control circuit fuse 250V 3.15A
Flap Motor and Louver Motor
Type Stepping motor Model MP24Z3-12V Rating DC 12V
Coil resistance (Ambient temp. 25°C) Each pair of terminals: 400 ± 7%
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.3 Face area m
2
0.188
Fan & Fan Motor
Type Fan / Fan motor Cross-flow / AC motor Q’ty … Dia. and lengthmm1 … D92 / L634 Fan motor model … Q’ty IBH-884-066 … 1 No. of poles … Rough measure rpm (Cool / Heat) 4 … 1,250 / 1,250 Nominal output W 30
Coil resistance (Ambient temp. 20°C) BRN – WHT: 234
PNK (RED) – WHT: 209
— :
Safety devices Type Thermal fuse
Operating temp. Open °C 130
Close
Run capacitor µF 1.2
VAC 440
Remote Control Unit RCS-3HVPSS4E
9
2-2-2. Outdoor Unit
Outdoor Unit SAP–CRV93EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Compressor
Type DC Rotary (Hermetic) Compressor model / Nominal output G4C090LU1ER / 600W Compressor oil … Amount cc FV50S … 320
Coil resistance (Ambient temp. 20°C) U – V: 0.81
V – W: 0.81 W – U: 0.81
Safety devices
CT (Peak current cut-off control) YES Compressor discharge temp. control YES Operation cut-off control in abnormal ambient temp.
Run capacitor µF
VAC
Crankcase heater
Fan & Fan Motor
Type … Fan / Fan motor Propeller / AC motor Q’ty … Dia. mm 1 … 370 Fan motor model … Q’ty IB-976-501 … 1 No. of poles … Rough measure rpm (Cool / Heat) 6 … 700 / 700 Nominal output W 20
Coil resistance (Ambient temp. 20°C) WHT – BRN: 213
RED (PNK) – WHT: 168
— : —
Safety devices Type Thermal fuse
Operating temp. Open °C 150
Close °C
Run capacitor on control PCB (A) µF 2.0
VAC 440
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.288
External Finish Acrylic baked-on enamel finish
Control PCB (A) / Control PCB (B)
Part No. CB-CRV93EH (POW-CRV93GJH) Controls Microprocessor Control circuit fuse 250V, 20A
10
Outdoor Unit SAP–CRV123EH
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Fan & Fan Motor
Type … Fan / Fan Motor Propeller / DC Motor Q’ty … Dia. mm 1 … 370 Fan motor model … Q’ty DAJ12-55J71-C … 1 No. of poles … Rough measure rpm (Cool / Heat) 8 … 750 / 750 Nominal output W 50
Coil resistance (Ambient temp. 20°C)
— —
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor on control PCB (A) µF
VAC
Heat Exchanger Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.367
External Finish Acrylic baked-on enamel finish
Control PCB (A) / Control PCB (B)
Part No. CB-CRV123EH (POW-CRV123GJH) Controls Microprocessor Control circuit fuse 250V, 20A
Compressor
Type DC Rotary (Hermetic) Compressor model / Nominal output G4C090LU1ER / 600W Compressor oil … Amount cc FV50S … 320
Coil resistance (Ambient temp. 20°C) U – V: 0.81
V – W: 0.81 W – U: 0.81
Safety devices
CT (Peak current cut-off control) YES Compressor discharge temp. control YES Operation cut-off control in abnormal ambient temp.
Run capacitor µF
VAC
Crankcase heater
11
2-3. Other Component Specifications
Indoor Unit SAP–KRV93EH
SAP–KRV123EH
Outdoor Unit SAP–CRV93EH
SAP–CRV123EH
• Indoor air temp sensor
• Indoor heat exchanger sensor
• Compressor temp sensor
10
9
8
7
6
5
Resistance (k)
4
3
2
1
15 20 25 30 35 40
10
Temperature (°C)
Resistance (k)
200
180
160
140
120
100
80
60
40
20
0
0 102030405060708090
Temperature (°C)
• Outdoor air temp sensor
• Outdoor heat exchanger sensor
40
35
30
25
20
Resistance (k)
15
10
5
0
–20 –15 –10 –5 0 5 10 15 20
Temperature (°C)
12
5 5815
3. DIMENSIONAL DATA
Indoor Unit SAP-KRV93EH
SAP-KRV123EH
Unit: mm
40
24.5 56
196
825
815
70
56 79.5
52 23
32
133.8
285
40
45
189 3
567
285
86.5
45
(ø65)
40
178.9
Wide tube ø9.52(3/8")
Narrow tube ø6.35(1/4")
70
360
450187.5
825 450
308
187.5
86.5 45
178.9
Drain hose ø18
187.5187.5
24.5
92.5122.5
(ø65)
40
46.5 27.4
13
Outdoor Unit SAP-CRV93EH
SAP-CRV123EH
Unit: mm
AIR INTAKE
(12 class only)
275
AIR INTAKE
AIR DISCHARGE
538
ID:ø18
ID:2-ø23.6
720 72
91 12
2-ø12 holes
26591290
316
Wide tube service valve
ø9.52 (3/8")
Narrow tube service valve
ø6.35 (1/4")
16
548
109 55
2
155
14
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
Indoor Unit SAP-KRV93EH Outdoor Unit SAP-CRV93EH
SAP-CRV123EH SAP-CRV123EH
Indoor unit Outdoor unit
O.D. ø9.52 mm (3/8 ")
Heat exchanger
Narrow tube
O.D. ø6.35 mm (1/4")
Wide tube
Wide tube service valve
Muffler
Narrow tube service valve
Strainer
Modulator
(12 class only)
Muffler
(12 class only)
Accumulator
4-way valve
Electric
expansion
valve
M
Capillary tube for split flow
Compressor
Heat exchanger
Cooling cycle
(Defrosting cycle)
Heating cycle
Insulation of Refrigerant Tubing
IMPORTANT
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation should be a min. 8 mm.
After a tube has been insulated,
CAUTION
never try to bend it into a narrow curve because it can cause the tube to break or crack.
Thickness: Min. 8 mm
Wide tube
Insulation
Thickness: Min. 8 mm
Narrow tube
15
5. PERFORMANCE DATA
5-1. Temperature Charts
Indoor Unit SAP-KRV93EH Outdoor Unit SAP-CRV93EH
Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to “9-2. Overload prevention during heating.”)
Points of rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B. / 24°C W.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
Cooling Characteristics Heating Characteristics
G)
2
1.3
(12.2)
1.2
MPa (kgf/cm
(11.2)
1.1
(10.2)
1.0
Low pressure at wide tube service valve
(9.2)
25 30 35 40
Indoor Air Temp.30°C
Outdoor inlet air D.B. temp.( C)
5
4
3
Operating current (A)
Indoor Air Temp.30°C
27
24
27
24
3.5
G)
(34.7)
2
3.0
(29.6)
MPa (kgf/cm
°C
°C
2.5
(24.5)
2.0
(19.4)
High pressure at wide tube service valve
–5 0 5 10 15 20 25
Indoor Air Temp.23°C
20
17
°C
°C
Outdoor inlet air D.B. temp.( C)
9
8
7
°C
°C
6
5
4
Operating current (A)
3
Indoor Air Temp.23°C
°C
20
°C
17
2
25 30 35 40
2
–5 0 5 10 15 20 25
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
17
16
15
14
13
12
11
Indoor discharge air temperature ( C)
10
25 30 35 40
Indoor Air Temp.30°C
27
24
°C
°C
60
55
50
45
40
35
30
Indoor discharge air temperature ( C)
25
–5 0 5 10 15 20 25
Indoor Air Temp.23°C
17
20
°C
°C
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
NOTE
16
Indoor Unit SAP-KRV123EH Outdoor Unit SAP-CRV123EH
Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to “9-2. Overload prevention during heating.”)
Points of rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B. / 24°C W.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
Cooling Characteristics Heating Characteristics
G)
(12.2)
2
1.3
Outdoor fan speed
HighLow
1.2
(11.2)
MPa (kgf/cm
Indoor Air Temp.30°C
1.1
(10.2)
1.0
(9.2)
Low pressure at wide tube service valve
25
30 35 40
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
9
8
Outdoor fan speed
HighLow
7
6
5
4
Operating current (A)
3
27
24
27
24
°C
°C
30°C
°C
°C
G)
2
3.5
(34.7)
MPa (kgf/cm
3.0
Indoor Air Temp.23°C
(29.6)
2.5
(24.5)
2.0
High pressure at wide tube service valve
(19.4)
50 5 10152025
9
8
7
6
Indoor Air Temp.23°C
5
4
Operating current (A)
3
20
20
17
17
°C
°C
°C
°C
2
25
30 35 40
2
50 5
10 15 20 25
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
20
18
Outdoor fan speed
HighLow
16
14
Indoor Air Temp.30
12
10
8
Indoor discharge air temperature ( C)
6
25
30 35 40
27
24
°C
°C
°C
60
55
50
45
40
35
30
Indoor discharge air temperature ( C)
25
50 5 10
23°C
°C
20
°C
17
15 20 25
Outdoor inlet air D.B. temp.( C) Outdoor inlet air D.B. temp.( C)
NOTE
17
5-2. Air Throw Distance Charts
Indoor Unit SAP–KRV93EH
Cooling
Room air temp. : 27°C Fan speed : High
123456789
1
2
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
3
4
Heating
Room air temp. : 20°C Fan speed : High
1
: Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°
Horizontal distance (m)
123456789
2
Axis air velocity (m/s)
Vertical distance (m)
3
4
: Flap angle 45° , : Axis air velocity 45° : Flap angle 60° , : Axis air velocity 60°
18
Indoor Unit SAP–KRV123EH
Cooling
Room air temp. : 27°C Fan speed : High
1
2
Axis air velocity (m/s)
Vertical distance (m)
3
4
Heating
Room air temp. : 20°C Fan speed : High
123456789
Horizontal distance (m)
: Flap angle 0° , : Axis air velocity 0° : Flap angle 30°, : Axis air velocity 30°
123456789
1
2
Axis air velocity (m/s)
Vertical distance (m)
3
4
Horizontal distance (m)
: Flap angle 45° , : Axis air velocity 45° : Flap angle 60° , : Axis air velocity 60°
19
5-3. Operating Frequency Charts
Indoor Unit SAP–KRV93EH Outdoor Unit SAP–CRV93EH
230V Single-phase 50Hz
Cooling
5
4
3
2.65
2
Cooling Capacity (kW)
1
Min.
Max.
Center
0
0 1020304050607080
Operating Freqency (Hz)
1200
1000
800
755
600
Power Input (W)
400
Min.
200
0
0 1020304050607080
Operating Freqency (Hz)
54
Max.
Center
54
NOTE
1) Rating conditions in cooling are:
Indoor: 27°C D.B. / 19°C W.B. Outdoor: 35°C D.B. / 24°C W.B.
2) Fan speed: High
20
230V Single-phase 50Hz
Heating
5
4
3.6
3
2
Heating Capacity (kW)
1
0
0 20 40 60 80 100 120
1400
1200
Min.
Operating Freqency (Hz)
Center
75
Max.
Max.
1000
995
800
600
Power Input (W)
400
Min.
200
0
0 20 40 60 80 100 120
NOTE
1) Rating conditions in heating are:
Indoor: 20°C D.B. Outdoor: 7°C D.B. / 6°C W.B.
2) Fan speed: High
Center
75
Operating Freqency (Hz)
21
Indoor Unit SAP–KRV123EH Outdoor Unit SAP–CRV123EH
230V Single-phase 50Hz
Cooling
5
4
3.5
3
2
Cooling Capacity (kW)
1
0
0 102030405060708090
1400
1200
1090 1000
Min.
Operating Freqency (Hz)
Center
78
Center
Max.
Max.
800
600
Power Input (W)
400
Min.
200
0
0 102030405060708090
NOTE
1) Rating conditions in cooling are:
Indoor: 27°C D.B. / 19°C W.B. Outdoor: 35°C D.B. / 24°C W.B.
2) Fan speed: High
78
Operating Freqency (Hz)
22
230V Single-phase 50Hz
Heating
6
5
4.2
4
3
2
Heating Capacity (kW)
1
0
0 20 40 60 80 100 120
1600
1400
Min.
Operating Freqency (Hz)
Center
81
Max.
Max.
1200
1165
1000
800
600
Power Input (W)
400
200
0
0 20 40 60 80 100 120
Min.
NOTE
1) Rating conditions in heating are:
Indoor: 20°C D.B. Outdoor: 7°C D.B. / 6°C W.B.
2) Fan speed: High
Center
81
Operating Freqency (Hz)
23
6. ELECTRICAL DATA
6-1. Electrical Characteristics
Indoor Unit SAP-KRV93EH Outdoor Unit SAP-CRV93EH
Cooling
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V Single-phase 50Hz Rating conditions Running amp. A 0.17
Power input kW 0.033
Rating conditions: Indoor air temperature: 27°C D.B. / 19°C W.B.
Outdoor air temperature: 35°C D.B.
Heating
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V Single-phase 50Hz Rating conditions Running amp. A 0.17
Power input kW 0.035
0.21
0.048
0.21
0.048
3.48
0.674
4.43
0.912
3.86
0.755
4.81
0.995
Rating conditions: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
Indoor Unit SAP-KRV123EH Outdoor Unit SAP-CRV123EH
Cooling
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V Single-phase 50Hz Rating conditions Running amp. A 0.17
Power input kW 0.035
Rating conditions: Indoor air temperature: 27°C D.B. / 19°C W.B.
Outdoor air temperature: 35°C D.B.
0.14
0.030
4.90
1.025
Heating
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor Performance at 230V Single-phase 50Hz Rating conditions Running amp. A 0.17
Power input kW 0.035
0.14
0.030
5.17
1.100
5.21
1.090
5.48
1.165
Rating conditions: Indoor air temperature: 20°C D.B.
Outdoor air temperature: 7°C D.B. / 6°C W.B.
24
6-2. Electric Wiring Diagrams
Indoor Unit SAP-KRV93EH
Outdoor Unit SAP-CRV93EH
EVAPORATOR
GRN/YEL
FLAP
FLAP MOTOR
FAN MOTOR
FM
GRN/YEL
FAN MOTOR CAPACITOR
11 22 33 44 55
(RED)
PNK BRN WHT
RED
BLK
YEL
RED
PNK BLU
BRN
YEL
BLU
PNK
RY01
1
1 2
2
FLAP
3
3
5P(WHT)
4
4
5
5
CONTROLLER
11
FAN
33
5P(WHT)
55
11
HALL IC
22
3P(WHT)
33
FMC1
FMC2
AC IN SI1 SI
4
3
POWER RELAY
ROOM/COIL
GRY
GRY
LAMP
9P(WHT)
4P(WHT)
HA
JEM-A
4P(WHT)
TERMINAL BASE
BRN
GRN/YEL
RED
BRN BLU
GRN/YEL
1 1 2 2 3 3 4 4 55 6 6 7 7 88 9 9
1 1 2 2 3 3 4 4
1 2 3 4
1
2
4
L
N
EARTH
RED
11
WHT
22
WHT
33
WHT
44
WHT
55
WHT
66
WHT
77
WHT
8
8
WHT
99
THERMISTOR
(ROOM)
BLK
BLK BLK(ORG) BLK(ORG)
THERMISTOR
(COIL)
8FA-2-5257-143XX-1
Outdoor Unit : SAP-CRV93EHIndoor Unit : SAP-KRV93EH
L2L1IN+IN–OUT–OUT+IN1IN2S1
(WHT)
1
BLK
BLK
THERMISTOR
MAGNETIC COILREACTANCE
MV
1
3
5
2
6
443
1
5
6
2
YEL
BLK
RED
WHT
W
221
BLK
BLK
GRY
ORG
1
2
1
2
MV
(BLK)
(WHT)
COIL/COMP
1
YEL
WHT
433
5
6
4
5
6
W
W
BLU
W
V
WHT
U
RED
W
1
322 3
1
VL3P
CONNECTOR
WARNING
YEL
4433221
BLK
BLK
FERRITE CORE
RED
WHT
BLU
COMPRESSOR
COIL
THERMISTOR
THERMISTOR
GRN/YEL
(PNK)
R
/
V
S/U C/W
CM
COMPRESSOR MOTOR
8FA-2-5257-145XX-0
To avoid electrical shock hazard, be sure to
disconnect power before checking, servicing
and/or cleaning any electrical parts.
1
BLK
2
WHT
GRN/YEL
4
RED
TERMINAL BASE
POWER
SUPPLY
1
T-RUN/TEST
2 3
IND LAMP ASSY
CORE
FERRITE
W W W W W W
W W
W
BLU
RED
CAPACITOR
GRN/YEL
FAN MOTOR
ORG
CONTROLLER
CE
FM FM H
BRN
32211 3
BRN
RED
(PNK)
FM
BLK
WHT
YL3P
CONNECTOR
WHT
4-WAY VALVE
RV
WHT
OUTDOORRV1RV2
WWWWW
BLU
BLU
122 1
YL2P
CONNECTOR
BLU
OUTDOOR
BLU
Meaning of Abbreviations
ABBREV.
1 BLK BLACK
2 BLU
3 BRN
4 GRN/YEL
5 GRY
6 ORG
7 PNK
8 RED
9 VLT
10 WHT WHITE
11 YEL
MEANING
BLUE
BROWN
GREEN/YELLOW
GREY
ORANGE
PINK
RED
VIOLET
YELLOW