Sanyo KHS1232, CH1232 Service Manual

Page 1

SERVICE MANUAL

12KHS32

FILE NO.

SPLIT SYSTEM AIR CONDITIONER

ndoor Model No. Product Code No.
KHS1232 1 852 658 14
Outdoor Model No. Product Code No.
CH1232 1 852 754 05

CH1232

KHS1232

Page 2

IMPORTANT! Please Read Before Starting

This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

  • Carefully read this instruction booklet before beginning
  • Follow each installation or repair step exactly as shown
  • Observe all local, state, and national electrical codes
  • Pay close attention to all warning and caution notices given in this manual

This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death

This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.

If Necessary, Get Help

These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.

In Case of Improper Installation

The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.

SPECIAL PRECAUTIONS

When Wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.

  • Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
  • Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental Injury or death.
  • Ground the unit following local electrical codes.
  • Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting

Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.

When Installing...
...In a Ceiling or Wall

Make sure the ceiling/wall is strong enough to hold the unit's weight. It may be necessary to construct a strong wood or metal frame to provide added support.

...In a Room

Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors.

...In Moist or Uneven Locations

Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.

...In an Area with High Winds

Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.

...In a Snowy Area (for Heat Pump-type Systems)

Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.

When Connecting Refrigerant Tubing

  • Keep all tubing runs as short as possible.
  • · Use the flare method for connecting tubing.
  • Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
  • Check carefully for leaks before starting the test run.
NOTE:

Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either "narrow" or "wide" rather than as "liquid" or "gas."

When Servicing

  • Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
  • Keep your fingers and clothing away from any moving parts.
  • Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Page 3

Table of Contents

Page

Ŭ
1. OPE 1
2. SPEC CIFICATIONS
2-1. Unit Specifications 2
2-2. Major Component Specifications 3
2-2-1. Indoor unit 3
2-2-2. Outdoor unit 4
2-3. Other Component Specifications 5
2-3-1. Indoor unit 5
2-3-2. Outdoor unit 6
2 DIME INSIONAL DATA 7
υ. Unit
4. PERF 9
5. FUN CTION
5-1. Room Temperature Control 11
5-2. Automatic Switching between Cooling and Heating 13
5-3. Heater Operation (Heating) 13
5-4. Freeze Prevention (Cooling) 13
5-5. Overload Prevention (Heating) 14
5-6. Change-over (Heating) 14
5-7. Compressor Overheating Prevention (Heating) . 15
5-8. Outdoor Fan Speed Control (Cooling) 15
5-9. Defrosting Operation (Heating) 16
5-10. Self-Diagnostic Function 18
5-10-1. Fault with serial communication -18
5-10-2. Locked compressor cut-off .18
5-10-3. Compressor winding protection 18
5-10-4. Open or short circuit of sensor (thermistor) 18
5-10-5. Combination of LED lamps on PCB Ass'y 19
5-10-6. Arrangement of LED lamps on PCB Ass'y 19
6. REF 20
7. ELEC CTRIC WIRING DIAGRAMS 21
8. TRO UBLESHOOTING
8-1. Check before and after troubleshooting 23
8-1-1. Check power supply wiring 23
. · · 8-1-2. Check inter-unit wiring 23
8-1-3. Check power supply 23
8-1-4 Check lead wires and connectors in indoor and outdoor units 23
Page 4
8-2. Trouble eshooting Flowchart 24
8-3. Checki ng and Troubleshooting 27
8-3-1. Measure insulation resistance for ground fault 27
8-3-2. Check circuit breaker 27
8-3-3. Measure resistance for short circuit 28
8-3-4. Check power supply 28
8-3-5. Check remote control unit 28
8-3-6. Check OPERATION selector switch in indoor unit 28
8-3-7. Check serial communication between indoor unit and outdoor unit 29
(a) Check transformers in indoor and outdoor units
i (b) Check fuses on PCB Ass y in indoor and outdoor units
000 (c) FCB Ass y in either indoor or outdoor unit is delective 20
0-3-0. Only compressor does not run. 30
0-3-9.
8-3-10
Function of outdoor fan speed control doos not work properly 30
0-0-10 . Function of outdoor fait speed control does not work propeny 30
9. CHE CKING ELECTRICAL COMPONENTS
9-1. Measu rement of Insulation Resistance 31
9-1-1. Power supply wires 31
9-1-2. Indoor unit 31
9-1-3. Outdoor unit 31
9-1-4. Measurement of insulation resistance for electrical parts 31
9-2. Check ing Continuity of Fuse on PCB Ass'y 32
9-3. Check ing Motor Capacitor 32
9-4. Appea rance of Electrical Parts 33
•• (a) Heater Relay
(b) Relay
(c) Thermistor
(d) Thermostat (air blowout temperature)
۱Ä PPFI INSTRUCTION MANUAL - 34
Page 5

1. OPERATING RANGE

Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling Maximum 95°F DB / 71°F WB 115°F DB
Cooling Minimum 67°F DB / 57°F WB 67°F DB
Maximum 80°F DB / 67°F WB 75°F DB / 65°F WB
Heating Minimum — DB / — WB 17°F DB / 15°F WB
Page 6

2. SPECIFICATIONS

2-1. Unit Specifications

Indoor unit KHS1232 Outdoor unit CH1232

Power Source 230 / 208V - Single phase - 60Hz
ġ. n - Stater - Salarin - Fala in a - Maarin - Salarin Cooling Heating
and A BTU/h 11,700 / 11,500 13,000 / 12,700
Ë Capacity kW 3.43 / 3.37 3.81 / 3.72
ore Air circulation (High) ft 3 /min. 360 / 330
مّ Moisture removal (Hig h) Pints/h 3.3 / 3.2
Voltage rating V 230 / 208 230 / 208
Available voltage rang e V 253 to 187
ţ, Running amperes ••••••••••••••••••••••••••••••••••••••• A 5.5 / 5.9 5.1 / 5.4
Ĕ Power input •••••••• W 1,210 / 1,180 1,170 / 1,120
i ca Power factor ••••••••••••••••••••••••••••••••••••••• % 95 / 96 99 / 99
ਿੱਧ S.E.E.R. (H.S.P.F.) ••••••••••••••••••••••••••••••••••••••• 10.0 / 10.0 (6.8 / 6.8)
Ē Compressor locked ro tor amperes Α 34
2 Heater element kW 1.5 / 1.23
| Controls / Temperature e control Microprocesso r / I.C. thermostat
| Control unit Wireless rem ote control unit
ļ Timer ••••• ON/OFF, 24-h ours & Program
Fan speeds Indoor 3 and Au o / 2 (Auto)
Airflow direction (Indoor) Horizontal Vertical Manual
Í Auto
l Air filter Washable e, Anti-mold
es l Compressor Rotary Hermetic)
tu Refrigerant / Amount charged at shipment lbs. (g) R22 / 2. 51 (1,140)
E E Refrigerant control Capillary tube
Indoor – Hi / Me / Lo dB-A 43 / 39 / 36
Operation sound Outdoor – Hi dB-A 49
Refrigerant tubing con nections •••••• Flar e type
Max. allowable tubing length at shipment ft. (m) 33 (10)
Refrigerant tube Narrow tube in. (mm) 1/4 (6.35)
diameter Wide tube in. (mm) 1/2 (12.7)
Refrigerant tube kit / A ccessories Optional / Hanging wall bracket
| Indoor unit Outdoor unit
Unit dimensions Heiaht in. (mm) 14-3/16 (360) 20-7/8 (530)
l H Width in. (mm) 38-31/32 (990) 29-17/32 (750)
Vei Depth in. (mm) 7-13/16 (198) 11-1/32 (280)
8 Package dimensions Height in (mm) 10-23/32 (272) 23-1/2 (597)
Suc Width in. (mm) 42-17/32 (1,080) 35-13/32 (899)
usi Depth in. (mm) 18-1/32 (458) 13-27/32 (352)
ine Weight Net lbs. (ka) 29.7 (13.5) 92.5 (42.0)
ā Shippina lbs. (ka) 37.4 (17.0) 99.1 (45.0)
Shipping volume ······································ ft 3 (m 3 ) 4.8 (0.13) 6.5 (0.18)

Remarks: Rating conditions are:

80°F DB/67°F WB
95°F DB/75°F WB
70°F DB
47°F DB/43°F WB

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Page 7

2-2. Major Component Specifications

2-2-1. Indoor unit

Indoor unit KHS1232

Remo Remote Control Unit RCS-KHS2422W
188 POW-KHS1222-A
§~ S Control circuit fuse AC 250V - 3A
Switch n Ass'y SW-KHS2412W
le le AH-KH1212
Feer 1 Input (23 0 / 208V) kW 1.5 / 1.23
ê X Protectiv e thermostat OFF 140 ± 5°F, ON 122 ± 9°F
£≤ Thermo luse Cut-off 341 + 2, -5°F, 277V - 15A
5 Туре Cross-flow
E. Number Dia. and le ength in. (mm) 1 O.D. 4 (100), L 30 (760)
Model Number UF4Q-11A6P 1
No. of po ile rpm (23 XOV, High) 4 1,330
Nominal output w 10
Coil resistance Ω
(Ambient temp. 68°F)
Ω BRN - WHT: 281.6
WHT – VLT: 45.3
6 VLT – ORG: 56.0
N S ORG - YEL: 117.0
Far YEL - PNK: 59.4
Type Internal protector
devices Operating Open °F 248 ± 9
temp. Close Automatic reclosing
Bun can acitor μF 0.8
- non cup VAC 440
Model M2EA24ZA01
20 Rating 208 to 230V, 60Hz
55 No. of po le rpm 83
Output w 2.5
Coil resis tance (at 68° F) 16.45 ± 15%
** Coil Aluminum plate fin / Copper tube
1 A D Rows Fins per inch 2 14.1
Face are a ft. 2 ' (m²) 2.08 (0.19)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Page 8

2-2-2. Outdoor unit

Outdoor unit CH1232

POW-C CH1232
불문 Control ci rcuit fuse •••••• AC 250 DV - 3A
- Type Rotary (h nermetic)
Model Number •••••• C-R95H6E 1
No. of cv rom ••••••• •••••• 1 3,500
Nominal outout •••••••••••••••••••••••••••••••••• W 9 50
Compres sor lubricant ••••• CC 60 00
Coil resis tance ••••• Ω C – R 1: 1.89
ō (Ambient temp. 77°F) C – S 6: 4.90
ess Type •••••• Internal External
dr. Overload re lay models MST00AKU-9200
ō Safety Operating Open °F 275±9
- devices temp. Close °F | 156 ± 27
Operating a
(Ambient te
amp.
mp. 77°F)
Trip in 6 to 16 sec.
at 21.0A
μF 2 20
Run capacitor VAC VAC 400
Crank case heater 230V - 20W
c Type Propeller
Fa Number Dia. in. (mm) 1 15-3/4 (400)
Model UE6S -21L6P
No. of po ole rpm (23 30V, High) 6 . 840
Nominal output W 20
••••••••••••••••••••••••••••••••••••••• Ω BRN – V NHT: 201.7
ō Coil resistance WHT - YEL: 156.1
Ŵ (Ambien t temp. 68°F) YEL – PNK: 27.1
an Туре ••••••• Internal protector
L Safety Operating Open °F 24 8±9
devices temp. Close ••••••••••••••••••••••••••••••••••••••• Automat ic reclosing
_ $ μF 2.5
Run cap Run capacitor VAC 440
Coil Aluminum plate e fin / Copper tube
eat
(ch.
Rows . Fins per incl h 2 15.9
Ξŵ Face ar ft. 2 (m 2 ) 3.29 (0.30)
Exter nal Finish Acrylic baked -on enamel finish

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Page 9

2-3. Other Component Specifications

2-3-1. Indoor unit

Indoor unit KHS1232

Transformer ATR-H85U
Rated Primary AC 220V, 60Hz
Secondary 11V, 0.727A
Capacity 8VA
Coil resistance Ω (at 77°F) Primary (WHT – WHT): 294.0 ± 15%
Secondary (BRN – BRN): 1.0 ± 15%
Thermal cut-off temp 259°F, 2A, 250V
Heater Relay G4E-2123T-US
Coil rating DC 12V
Coil resistance Ω (at 73°F) 133.5 ± 10%
Contact rating AC 250V, 15A
Thermistor (Coil sensor) PB C-41E-S4
Resistance 14ºF 23.7 ± 5% 77°F 5.3 ± 5%
32°F 15.0 ± 5% 86°F 4.4 ±5%
50°F 9.7 ± 5% 104°F 3.1 ± 5%
68°F 6.5 ± 5%
Thermistor (Room sensor) SDT-50 0B6-2
Resistance 50°F 10.3 ± 4% 86°F 4.0 ± 4%
59°F 8.0 ± 4% 104°F 2.6 ± 4%
68°F 6.3 ± 4% 122°F 1.8 ± 4%
77°F 5.0 ± 4%
Thermostat (air blowout temp.) CT-7L
Operating temp. °F OFF 131±5
ON 113±5
Contact rating DC 24V, 0.2A
Page 10

2-3-2. Outdoor unit

Outdoor unit CH1232

Transformer ATR-H85U
Rated Primary AC 220V, 60Hz
Secondary 11V, 0.727A
Capacity 8VA
Coil resistance Ω (at 77°F) Primary (WHT – WHT): 294.0 ± 15%
Secondary (BRN – BRN): 1.0 ± 15%
Thermal cut-off temp . 259°F, 2A, 250V
Power Relay G4F-11123T-US
Coil rating DC 12V
Coil resistance Ω (at 68°F) 160 ± 10%
Contact rating AC 240V, 20A
Thermistor (Coll ser sor, Air temp. sensor) PBC-41E-S15
Resistance 14°F 23.7 ± 59 % 77°F 5.3 ± 5%
32°F 15.0 ± 5% 6 86°F 4.4 ± 5%
50°F 9.7 ± 5% 6 104°F 3.1 ± 5%
68°F 6.5 ± 59 6
Thermistor (Discharge sensor) DTN-TK DTN-TKS101B
Resistance 32°F 185.5 ± 5% 86°F 45.1 ± 5%
50°F 112.2 ± 5% 104°F 29.7 ± 5%
68°F 70.1 ± 5% 122°F 20.0 ± 5%
Thermistor (PTC) TDK 101YV
Max. voltage AC 400V
Max. ampere 11.5A
Resistance Ω (at 77°F) 100 ± 25%
Solenoid Valve (4-way valve) LB59005 (Coil), V26 9100 (Valve)
Coil rating AC 208 to 240V, 60Hz, 5W
Coil resistance Ω (at 68°F) 1,770
Page 11

3. DIMENSIONAL DATA

Indoor unit KHS1232

Page 12

Page 13

4. PERFORMANCE CHARTS

Cooling characteristics

Indoor unit KHS1232 Outdoor unit CH1232

Outdoor intake air D.B. temp. °F (°C)

NOTE

.....Points of rating condition

Black dots in above charts indicate the following rating conditions.

Cooling: Indoor air temperature 80°F DB/67°F WB Outdoor air temperature 95°F DB

Page 14

Heating characteristics

Outdoor intake air D.B. temp. °F (°C)

NOTE

Overload prevention operates to protect the air conditioner when the outdoor ambient temperature reaches an abnormally high level while in heating mode. (Refer to 5-5. Overload prevention)

........Points of rating condition

Black dots in above charts indicate the following rating conditions.

Heating: Indoor air temperature 70°F DB Outdoor air temperature 47°F DB/43°F WB

Page 15

5. FUNCTION

5-1. Room Temperature Control

  • Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit.
  • The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit.

  • The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
  • As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor operation.
  • Thermo ON : When the room temperature is above T + 2°F (T°F is set temperature). Compressor \rightarrow ON
  • Thermo OFF : When the room temperature is equal to or below set temperature T°F. Compressor \rightarrow OFF
Page 16
Heating

  • Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit.
  • The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit.

*1: Cold draft prevention

  • The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 5 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.
  • As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor operation.
  • Thermo ON : When the room temperature is below T 2°F (T°F is set temperature). Compressor \rightarrow ON
  • Thermo OFF : When the room temperature is equal to or above set temperature T°F. Compressor \rightarrow OFF
Page 17

5-2. Automatic Switching between Cooling and Heating

• When AUTO mode is selected, the microprocessor calculates the difference between the set temperature and the room temperature, and automatically switches to COOLING or HEATING mode to maintain the desired temperature.

Room temp. ≥ Set temp. → COOL Room temp. < Set temp. → HEAT

This means that if the room temperature is higher than or equal to the set temperature, COOLING operation begins. If the room temperature is lower than the set temperature. HEATING operation begins.

5-3. Heater Operation (Heating)

  • The electric heater operates in Thermo ON at the time of initial start or when the room temperature is 4°F lower than the set temperature.
  • When the air conditioner is thermo OFF, the heater is OFF at the same time.
  • When the indoor outlet air temperature rises above 131°F, heater operation stops. It resumes operation when the indoor outlet air temperature falls below 113°F.
  • When the outdoor temperature falls to around 10°F, the compressor stops but the electric heater continues to operate.

5-4. Freeze Prevention (Cooling)

  • This function prevents freezing of the indoor heat exchange coil.
  • When the compressor has been running for 10 minutes or more and the temperature of the indoor heat exchange coil falls below 30°F, the control circuit stops the compressor for at least 6 minutes.

Page 18

5-5. Overload Prevention (Heating)

  • This function prevents overheating of the indoor heat exchange coil.
  • When the temperature of the indoor heat exchange coil rises above 135°F, and if the indoor fan is L (low speed), then the fan speed changes from L (low speed) to M (medium speed).
  • When the temperature of the indoor heat exchange coil rises above 138°F, the outdoor fan stops.

5-6. Change-over (Heating)

  • This function protects the compressor from being damaged due to liquid back-flow.
  • Low ambient operation during heating can cause the outdoor heat exchanger to become super-cooled which may result in liquid back-flow. To protect the compressor from this condition, the compressor stops if the outdoor temperature drops below 10°F. However, the indoor fan and the heater continue to operate even after the compressor has stopped.

Page 19

5-7. Compressor Overheating Prevention (Heating)

• This function protects the compressor from overheating using the outdoor fan.

5-8. Outdoor Fan Speed Control (Cooling)

  • The outdoor fan speed switches automatically to LOW to prevent the indoor heat exchange coil from freezing due to low ambient temperature.
  • If the outdoor air temperature falls below 74°F, the fan speed switches to LOW.
  • If the outdoor air temperature rises above 80°F for 5 minutes or longer, the fan speed switches to HIGH.

Page 20

5-9. Defrosting Operation (Heating)

Defrosting Flowchart

Page 21

Defrosting Mode Timing Chart

Defrosting Zone

Zones

Page 22

5-10. Self-Diagnostic Function

• When the following problems occur in the air conditioner, operation stops and the operation lamp in the indoor unit flashes.

At the same time, LED lamps on the PCB Ass'y in the indoor and outdoor units also flash. The combination of flashing LED lamps indicates the cause of the problem.

5-10-1. Fault with serial communication

  • Fault in transmission between indoor and outdoor units.
  • Error message appears on the PCB Ass'y after 3 minutes.
  • To release this error, push the operation ON-OFF button again.
5-10-2. Locked compressor cut-off

  • This function prevents the compressor from being damaged by overcurrent.
  • The air conditioner stops when the current exceeds 17A for 2 seconds, repeating 3 times.
  • To release this error, push the operation ON-OFF button again.
5-10-3. Compressor winding protection

• The air conditioner stops if the compressor discharge temperature rises above 239°F, repeating 2 times within 1 hour.

• To release this error, wait 15 minutes and push the operation ON-OFF button.

* Flashing of LED lamps on the PCB Ass'y

5-10-4. Open or short circuit of sensor (thermistor)

  • The following sensors are provided in the outdoor unit.
    • TH1: Outdoor heat exchange coil temperature sensor
    • TH2: Outdoor air temperature sensor
    • TH3: Compressor discharge gas temperature sensor
  • For checking the sensor fault, measure the sensor resistance.
Page 23

5-10-5. Combination of LED lamps on PCB Ass'y

Indoo r unit Outdoor unit
Type of problem LED lamp combination LED lamp combination
24 25 26 27 2 4 6
Fault with serial communication
Locked compressor cut-off
Compressor winding protection
Open or short circuit of sensor $

☆: Flashing lamps

5-10-6. Arrangement of LED lamps on PCB Ass'y

• KHS1232

• CH1232

Page 24

6. REFRIGERANT FLOW DIAGRAM

Indoor unit KHS1232

Outdoor unit CH1232

Insulation of Refrigerant Tubing

IMPORTANT

To prevent heat loss and wet floors due to dripping of condensation, both the wide and narrow tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 5/16 in.

After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.

Page 25

7. ELECTRIC WIRING DIAGRAMS

Indoor unit KHS1232

To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.

Page 26

Outdoor unit CH1232

To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.

Page 27

8. TROUBLESHOOTING

8-1. Check before and after troubleshooting

Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing.

8-1-1. Check power supply wiring.

• Check that power supply wires are correctly connected to terminals No. 5 and No. 6 on the terminal plate in the outdoor unit.

8-1-2. Check inter-unit wiring.

• Check that inter-unit wiring is correctly connected to the indoor unit from the outdoor unit.

8-1-3. Check power supply.

  • Check that voltage is in specified range (±10% of the rating).
  • Check that power is being supplied.
8-1-4. Check lead wires and connectors in indoor and outdoor units.

  • Check that coating of lead wires is not damaged.
  • Check that lead wires and connectors are firmly connected.
  • Check that wiring is correct.
Page 28

8-2. Troubleshooting Flowchart

Page 29
Troubleshooting Flowchart (cont'd)

Page 30
Troubleshooting Flowchart (cont'd)

Page 31

8-3. Checking and Troubleshooting

8-3-1. Measure insulation resistance for ground fault.

If resistance value is 1MΩ or less, insulation is defective ("NO").

8-3-2. Check circuit breaker.

Page 32

8-3-3. Measure resistance for short circuit.

Measure resistance of compressor motor winding.

8-3-4. Check power supply.

8-3-5. Check remote control unit.

8-3-6. Check OPERATION selector switch in indoor unit.

Page 33

8-3-7. Check serial communication between indoor unit and outdoor unit.

• Check cause of fault.
(a) Check transformers in indoor and outdoor units.

Measure resistance of transformer windings.

(b) Check fuses on PCB Ass'y in indoor and outdoor units.

(c) PCB Ass'y in either indoor or outdoor unit is defective.
Page 34

8-3-8. Only compressor does not run.

8-3-10. Function of outdoor fan speed control does not work properly.

Refer to 5-8. Outdoor Fan Speed Control.

winding.

Page 35

9 CHECKING ELECTRICAL COMPONENTS

9.1 Measurement of Insulation Resistance

• The insulation is in good condition if the resistance exceeds 1MO

9-1-1. Power supply wires

Clamp the ground wire of the power supply wires with the lead clin of the insulation resistance tester and measure the resistance by placing a probe on either of the power wires. (Fig. 1)

Then measure the resistance between the ground wire and the other power wire. (Fig. 1)

9-1-2 Indoor unit

Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw except where the ground line is connected on the terminal plate. (Fig. 2)

9-1-3. Outdoor unit

Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate, (Fig. 2)

9-1-4 Measurement of insulation resistance for electrical parts

Disconnect the lead wires of the desired electric part from terminal plate, PCB Ass'y, capacitor, etc. Similarly disconnect the connector. Then measure the insulation resistance. (Figs. 1 to 4)

Refer to Electric Wiring Diagram.

NOTE If the probe cannot enter the poles because the hole is too narrow then use a probe with a thinner pin.

Page 36

9-2. Checking Continuity of Fuse on PCB Ass'y

Check for continuity using a multimeter as shown in Fig. 5.

NOTE

Method Used to Replace Fuse on PCB Ass'y

  • 1. Remove the PCB Ass'y from the electrical component box.
  • Pull the fuse from the metal clasp using pliers while heating the soldered leads on the back side of the PCB Ass'y with a soldering iron (30W or 60W). (Fig. 6)
  • Remove the fuse ends one at a time. For replacement, insert a fuse of the same rating and solder it. (Allow time to radiate heat during soldering so that the fuse does not melt.)

When replacing the fuse, be sure not to break down the varistor.

9-3. Checking Motor Capacitor

Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 7. Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value.

The capacitor is "good" if the pointer bounces to a great extent and then gradually returns to its original position.

The range of deflection and deflection time differ according to the capacity of the capacitor.

Page 37

9-4. Appearance of Electrical Parts

(a) Heater Relay

G4E-2123T-US

Fia. 8

(b) Power Relay

Fig. 9

(c) Thermistor (PTC)

TDK 101YV

Fig. 10

(d) Thermostat (air blowout temperature)

CT-7L

Page 38

APPENDIX INSTRUCTION MANUAL

Table of Contents

F > age
Installation Location 3
Electrical Requirements 3
Safety Instructions 3
Names of Parts 4
Using the Remote Control Unit 8
Operation with the Remote Control Unit 9
1. Cooling 9
2. Adjusting the Fan Speed 10
3. Fan Only 11
4. Heating 12
Operation without the Remote Control Unit 13
Setting the Timer 14
Adjusting the Airflow Direction 15
Care and Cleaning 16
Troubleshooting 17
Tips for Energy Saving 17
Page 39

Installation Location

  • properly by a qualified installation technician in accordance with the Installation Instructions provided with the unit.
  • Before installation, check that the voltage of the electric supply in your home or office is the same as the voltage shown on the nameplate.
  • Do not install this air conditioner where there are fumes or flammable gases, or in an extremely humid space such as a green house.
  • Do not install the air conditioner where excessively high heatgenerating objects are places.
  • To protect the air conditioner from heavy corrosion, avoid installing the outdoor unit where salty sea water can splash directly onto it or in sulphurous air near a spa.

Electrical Requirements

  • 1. All wiring must conform to the local electrical codes. Consult your dealer or a qualified electrician for details.
  • 2. Each unit must be properly grounded with a ground (or earth) wire or through supply wiring.
  • 3. Wiring must be done by a qualified electrician.
Power mains

To warm up the system, power mains must be turned on at least five (5) hours before operation. Leave the power mains ON unless you will not be using this appliance for an extended period.

Power supply: 60 Hz, single-phase 230/208 VOLT

Safety Instructions

  • Read this booklet carefully before using this air conditioner. If you still have any difficulties or problems, consult your dealer for help.
  • This air conditioner is designed to give you comfortable room conditioners. Use this only for its intended purpose as described in these Instruction Manual.
  • Never use or store gasoline or other flammable vapor or liquid near the air conditioner — it is very dangerous.
  • This air conditioner has no ventilator for intaking fresh air from outdoors. You must open doors or windows frequently when you use gas or oil heating appliances in the same room, which consume a lot of oxygen from the air. Otherwise there is a risk of suffocation in an extreme case.
  • Do not turn the air conditioner on and off from the power mains switch. Use the operation ON/OFF button.
  • Do not stick anything into the air outlet of the air conditioner. This is dangerous because the fan is rotating at high speed.
  • Do not let children play with the air conditioner.
  • Do not cool or heat the room too much if babies or invalids are present.

Page 40

Names of Parts

This air conditioner consists of an indoor unit and an outdoor unit. You can control the air conditioner with the remote control unit.

Air Intake

NOTE:

Air Outlet Remote Control Unit

Refrigerant Tubes

Drain Hose Outdoor (Condensing) Unit

1

Air from the room is drawn into this section and passes through air filters which remove dust.

Conditioned air is blown out of the air conditioner through the air outlet. The wireless remote control unit controls power ON/OFF, operation mode selection, temperature, fan speed, timer setting, and air sweeping. The indoor and outdoor units are connected by copper tubes through which refrigerant gas flows.

Moisture in the room condenses and drains off through this hose. The outdoor unit contains the compressor, fan motor, heat exchanger coil, and other electrical components.

Page 41

Unit Display and Operation Selector

INDOOR UNIT

REMOTE CONTROL receiver OPERATION lamp STANDBY lamp

TIMER lamp Operation selector ON position

OFF position

TEST position

This section picks up infrared signals from the remote control unit (transmitter).

This lights when the system is in the continuous COOL or FAN mode.

This lamp lights during warm up period for heating and when the system is defrosting. To keep a constant room temperature, the air conditioner continues to supply a gentle breeze during warm up or when the heating operation is paused by the thermostat.

This lamp lights when the system is being controlled by the timer.

This position is for operating the air conditioner with the wireless remote control unit. Set the selector normally in this position. Switch the selector to the OFF position if you are not going to use the air conditioner for a few days or longer.

The OFF position does not disconnect the power. Use the main power switch to turn off power completely.

This position is used only when servicing the air conditioner, so don't leave the selector in this position.

Page 42

Remote Control Unit

Page 43

Remote Control Unit (continued)

SWEEP button When you press this button, the (SWEEP) mark will appear at the lower left of
the display, and the flap in the air outlet starts moving up and down to
deliver air over the sweep range set. To stop sweeping, just press the
SWEEP button again.
MODE selector switch FAN:
COOL:
HEAT:
AUTO:
The air conditioner works only as a circulation fan.
The air conditioner makes the room cooler.
The air conditioner makes the room warmer.
When this setting is selected, the air conditioner calculates the
difference between the thermostat setting and the room
temperature and automatically switches to the "cool" or
"heat" mode as appropriate.
Timer selector switch NORM.:
OFF:
ON:
PROGRAM:
The timer does not operate.
The air conditioner stops at the set time.
The air conditioner starts at the set time.
The air conditioner stops and starts, or starts and stops, at the
set times every day.
Fan speed selector switch AUTO:
HIGH:
MED.:
LOW:
The air conditioner automatically decides the fan speeds.
High speed for fast cooling
Medium speed
Low speed
SENSOR A temperature temperature. e sensor inside the remote control unit senses the room
Page 44

Installation Position

The indoor remote unit may be operated either from a non-fixed position or from a wall-mounted position. To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places:

  • In direct sunlight
  • Behind a curtain or other places where it is covered
  • More than 26 ft. away from the air conditioner
  • In the path of the air conditioner's airstream
  • Where it may become extremely hot or cold
  • Where it may be subject to electrical or magnetic noise
1. If Non-fixed Position

Raise the rear plate of the remote control unit mounting cradle and insert the remote control unit. The unit can be used either in that position (placed on a table, for instance) or held in the hand.

2. If Wall-mounted Fixed Position

Install the remote control unit at a convenient location on a nearby wall. However, before attaching the remote control unit mounting cradle, check that the remote control unit can operate from the desired wall position.

Page 45

Operation with the Remote Control Unit

  • NOTE:
    • 1. Cooling

Check that the circuit breaker on the power panel is turned on and the operation selector of the indoor unit is in the ON position.

  • STEP 1: Set the MODE selector switch to COOL.
  • STEP 2: Set the timer selector switch to NORM.
  • STEP 3: Press the ON/OFF operation button.
  • STEP 4: Press the COOLER or WARMER button to set a cooler or warmer temperature.

Each time you press these buttons, the set temperature varies by 2° F.

84° F max.
64° F min.

STEP 5: Set the fan speed selector switch to the setting you want.

To stop the air conditioner, press the ON/OFF operation button again.

  • Choose the best position in the room for the remote control unit, which also acts as the sensor for room comfort and transmits the operating instructions. Once you've found this best position, always keep the remote control unit there.
  • This appliance has a built-in 3-minute time delay circuit to ensure reliable operation. If the operation button is pressed, the compressor will start running after three minutes. In the event of power failure, the unit will stop. When the power is applied, the unit will re-start automatically after 3 minutes.
  • To prevent the appliance from malfunctioning, do not set any selector switch between two indicated positions. Make sure that it clicks into position.

Page 46

Night Setback Mode in Cooling

STEP 1: Press the NIGHT SETBACK button in cooling. The _____ mark appears at the lower left of the display. Press the NIGHT SETBACK button again to release the night setback function. This button has no effect in the FAN mode.

What does the Night Setback mode mean?

In this mode, the air conditioner will cool the room to the set temperature, and then the thermostat will make the unit pause. After about 30 minutes, the air conditioner will automatically raise the set temperature by 2° F. When the room temperature reaches the newly set value, the thermostat will cause the unit to pause. After about 30 minutes the temperature will again be raised by 2° F. This enables you to save energy without sacrificing comfort. This function is convenient when gentle cooling is needed.

2. Adjusting the Fan Speed

A. Automatic

STEP 1: Simply set the FAN SPEED selector to the "AUTO" position.

A microcomputer in the air conditioner automatically controls the fan speed when the AUTO mode is selected. When the air conditioner starts operating, the difference between the room temperature and the set temperature is detected by the microcomputer which then automatically switches the fan speed to the most suitable level.

Page 47

Cooling mode:

When difference between room temperature and set temperature is FAN SPEED
4°F and over High
Between 4° F and 2° F Medium
Below 2°F Low
Heating mode:
When difference between FAN SPEED
room temperature and set
temperature is
2°F and over High
Below 2° F Medium
B. Manual

If you want to adjust fan speed manually during cooling, just set the FAN SPEED selector as desired. [HIGH. MED., or LOW]

3. Fan Only

If you want to circulate air without any temperature control, follow these steps:

  • STEP 1: Set the MODE selector switch to FAN.
  • STEP 2: Press the ON/OFF operation button.
Page 48

4. Heating
STEFT. Set the MODE selector switch to hEAT. STEP 1: Set the MODE selector switch to HEAT.

  • STEP 2: Set the timer selector switch to NORM.
  • STEP 3: Press the ON/OFF operation button.
  • STEP 4: Press the COOLER or WARMER button to set a cooler or warmer temperature.

Each time you press these buttons, the set temperature varies by 2° F.

84° F max.
64" F min.

STEP 5: Set the fan speed selector switch to the setting you want. To stop the air conditioner, press the ON/OFF operation button again.

  • Choose the best position in the room for the remote control unit, which also acts as the sensor for room comfort and transmits the operating instructions. Once you've found this best position, always keep the remote control unit there.
  • This appliance has a built-in 3-minute time delay circuit to ensure reliable operation. If the operation button is pressed, the compressor will start running after three minutes. In the event of power failure, the unit will stop. When the power is applied, the unit will re-start automatically after 3 minutes.
  • To prevent the appliance from malfunctioning, do not set any selector switch between two indicated positions. Make sure that it clicks into position.

Page 49

If the outdoor temperature is extremely low, it is recommended to use another heating appliance:

When the outdoor temperature falls to around 10° F, the compressor stops. In this case, to prevent room from freezing, use another heating appliance.

Night Setback Mode in Heating

STEP 1: Press the NIGHT SETBACK button in cooling. The _____ mark appears at the lower left of the display. Press the NIGHT SETBACK button again to release the night setback function. This button has no effect in the FAN mode.

What does the Night Setback mode mean?

In this mode, the air conditioner will heat the room to the set temperature, and then the thermostat will make the unit pause. After about 30 minutes, the air conditioner will automatically lower the set temperature by 4° F. When the room temperature reaches the newly set value, the thermostat will cause the unit to pause. After about 30 minutes the temperature will again lowered by 4° F. This enables you to save energy without sacrificing comfort. This function is convenient when gentle heating is needed.

INDOOR UNIT

Operation without the Remote Control Unit

If you have lost the remote control unit or it has trouble, follow the steps below.

1. When the air conditioner is stopped.

If you want to turn on the air conditioner, switch the operation selector to the OFF position, and then to the ON position.

The set temp. and fan speed are automatically set at the latest selection before stopping.

2. When the air conditioner is running.

If you want to turn off the air conditioner, switch the operation selector to the OFF position.

Page 50
1) How to set the present time

2) How to set the OFF time

3) How to set the ON time

Setting the Timer

(Example) To set to 9:10 p.m.

Operation Indication
1. Press the PROGRAM button three times.
The time indication alone flashes.
Flashing
  • 2.
  • Press the HH button until 9 and PB are displayed.
  • Press the MM button until 10 is displayed. The display will automatically stop flashing except for the ":" symbol after 10 sec.
Flashing
(Example) To stop the air conditioner at 11:30 p.m.
1. Press the PROGRAM button once. The timer OFF and time indications flash. Flashing
  1. Press the HH button until 11 is displayed.
  2. Press the MM button until 30 is displayed. The display will change automatically back to show the present time after 10 sec.
  3. Set the timer switch(es) to OFF.
  4. Press the ON/OFF button to start the air conditioner.
Flashing
(Example) To start operation at 7:10.
  1. Press the PROGRAM button twice. The
    timer ON and time indications flash.
Flashing
  • Press the HH button until 7 and (A) are displayed.
  • Press the MM button until 10 is displayed.
  • The display will change automatically back to show the present time after 10 sec.
  • Set the timer switch(es) to ON.
  • Press the ON/OFF button to start the air conditioner.
Flashing

(Example) To start operation at 7:10 and stop the air conditioner at 11:30 p.m.

  1. Set the timer ON/OFF times as shown in
    2) and 3).
  1. Set the timer switch(es) to PROGRAM.
  2. Press the ON/OFF button to start the air conditioner.
Page 51

Power failure during timer operation

If power failure occurs, the time counted up to that point will become void. After the power is applied, the timer newly starts counting at the set time.

Adjusting the Airflow Direction

Page 52

Casing and Grille (Indoor Unit)

Care and Cleaning

For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning. Do not pour water on the indoor unit to clean it. This will damage

2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.

Clean the casing and grille of the indoor unit with a vacuum cleaner brush, or wipe them with a clean, soft cloth.

If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When cleaning the grille, be careful not to force the vanes out of place.

  • 1. Never use solvents, or harsh chemicals when cleaning the indoor unit. Do not wipe the plastic casing using very hot water.
  • Some metal edges and the fins are sharp and may cause injury if handled improperly; be especially careful when you clean these parts.
  • The internal coil and other components of the outdoor unit must be cleaned every year. Consult your dealer or service centre.

Air Filter

The air filter behind the air intake grille should be checked and cleaned at least once every two weeks.

How to remove the filter

  • 1. Move the flap on the air outlet grille to its lowest position.
  • 2. Hold the air filter by the tab at the bottom, and pull downward.

Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter, wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it. When replacing the filter, make sure that the FRONT mark is facing you.

Page 53

Troubleshooting

If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or service centre.

Trouble Possible Cause Remedy
Air conditioner does not
run at all
1. Power failure 1. Restore power
2. Leakage breaker tripped 2. Contact service centre
3. Line voltage too low 3. Consult with electrician or dealer
4. Operation button is OFF 4. Press the button again
5. Batteries in remote control unit have run down 5. Replace batteries
Compressor runs but soon stops 1. Obstruction in front of condenser coil 1. Remove obstruction
Poor cooling (or heating)
performance
1. Dirty or clogged air filter 1. Clean air filter to improve airflow
2. Heat source or many people in room 2. Eliminate heat source if possible
3. Doors and/or windows are open 3. Shut them to keep the heat out
4. Obstacle near air intake or air discharge port 4. Remove it to ensure good airflow
5. Thermostat is set too high for cooling (or too low for heating) 5. Set the temperature lower
6. (Outdoor temperature is too low) 6. (Try to use any back-up heater)
7. (Defrosting system does not work) 7. (Consult your dealer)

  • Tips for Energy Saving
  • Block the air intake and outlet of the unit. If it is obstructed, the unit will not work well, and may be damaged. Let direct sunlight into the room. Use sunshades, blind or curtains. If the
  • ✔ Do:
  • to cool the room. Always try to keep the air filter clean. (Refer to "Care and Cleaning"). A clogged filter will impair the performance of the unit.

walls and ceiling of the room are warmed by the sun, it will take longer

To prevent conditioned air from escaping, keep windows, doors and any other openings closed.

Page 54

For Parts or Service Contact SANYO FISHER SERVICE CORPORATION 1200 West Artesia Blvd., Compton, California, 90220, USA 50 Beth Nealson Drive, Toronto, Ontario, M4H 1M6, CANADA

Nov. / '95 / 1350 Printed in the U.S.A.

Loading...