Sanyo CH0922 CH0921, KHS1222, KHS0922, KHS0921 Service Manual

Page 1

SERVICE MANUAL (Basic Information)

KHS0921 / CH0921 KHS0922 / CH0922 KHS1222 / CH1222

SPLIT SYSTEM AIR CONDITIONER

REVISED

Indoor Unit

Outdoor Unit

CH0921 / CH0922 / CH1222

KHS1222

Page 2

SERVICE MANUAL

KHS0921 / CH0921 KHS0922 / CH0922 KHS1222 / CH1222

(Basic Information)

Page 3

IMPORTANT! Please Read Before Starting

This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

  • Carefully read this instruction booklet before beginning
  • Follow each installation or repair step exactly as shown
  • Observe all local, state, and national electrical codes
  • Pay close attention to all warning and caution notices given in this manual

This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.

If Necessary, Get Help

These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.

In Case of Improper Installation

The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.

SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PER-SONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.

  • Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
  • Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death .
  • Ground the unit following local electrical codes.
  • Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting

Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.

When Installing...
... In a Ceiling or Wall

Make sure the ceiling/wall is strong enough to hold the unit's weight. It may be necessary to construct a strong wood or metal frame to provide added support.

...In a Room

Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water damage to walls and floors.

... In Moist or Uneven Locations

Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.

...In an Area with High Winds

Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.

...In a Snowy Area (for Heat Pump-type Systems)

Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.

When Connecting Refrigerant Tubing

  • Keep all tubing runs as short as possible.
  • Use the flare method for connecting tubing.
  • Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
  • Check carefully for leaks before starting the test run.
NOTE:

Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either "narrow" or "wide" rather than as "liquid" or "gas."

When Servicing

  • Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
  • Keep your fingers and clothing away from any moving parts.
  • Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Page 4

Table of Contents

Page
1. OPERATING RANGE 1
н., с
1
2
2. SPECIFICATIONS
Unit Specifications
••••••• •••••• 2
3. DIMENSIONAL DATA ••••• ••••••• . 5
4. COOLING CAPACITY •••••• . 7
5. HEATING CAPACITY ••••• ••••••• . 12
6. REFRIGERANT FLOW DIAGRAM M •••••• •••••• . 17
7. ELECTRICAL DATA ••••• . 19
Electrical Characteristics . 19
20
. 20
Page 5

1. OPERATING RANGE

Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp
O alling Maximum 95°F DB / 71°F WB 115°F DB
Cooling - Minimum 67°F DB / 57°F WB 67°F DB
These Maximum 80°F DB / 67°F WB 75°F DB / 65°F WB
Heating - Minimum — DB / — WB 17°F DB / 15°F WB
KHS0921 / CH0921, KHS0922 / CH0922 and KHS1222 / CH1222
Page 6

2. SPECIFICATIONS

Unit Specifications

Model No. Outdoor unit CH0921 0 BTU/h 9,000 10,800 Capacity kW 2,64 3,16 Air circulation (High) cu. fr/min. 220 Moisture removal (High) Pints/h 2,7 Phase, Frequency Hz Single, 60 Voltage rating V 115 115 Voltage rating V 103 to 127 103 to 1 Running amperes A 8,2 8,8 Power factor % 99 59 Starting amperes A 449 10,010 Power factor % 99 59 Starting amperes A 449 10,010 Starting amperes A 449 10,010 Starting amperes A 449 10,010 Starting amperes A 449 10,010 Starting amperes A 449 10,010 Starting amperes A 449 10,010 Starti Indoor unit KHS 0921
Open control Cooling Heating Air circulation (High) cu. fl/min. 220 Moisture removal (High) cu. fl/min. 220 Moisture removal (High) cu. fl/min. 220 Voltage rating V 115 115 Voltage rating V 103 to 127 103 to 12 Running amperes A 8.2 8.8 Power input W 930 1,010 Prover factor % 99 99 S. E. E. R. BTU/Wh 10.0 10.0 Heater element kW – HSPF Model 1 No. Outdoor unit CH 0921
BTU/h 9,000 10,80 Capacity kW 2.64 3.16 Air circulation (High) cu. f/min. 220 Moisture removal (High) Pints/h 2.7 Phase, Frequency Hz Single, 60 Voltage rating V 115 115 Available voltage range V 013 to 127 103 to 1 Available voltage range V 103 to 127 103 to 1 Available voltage range V 115 115 Available voltage range V 103 to 127 103 to 1 Renning amperes A 8.2 8.8 Power factor % 99 99 Starting amperes A 8.2 8.8 Fower factor % 99 99 Starting amperes A 8.2 8.8 Controls BTU/Wh 10.0 Heater element kW-HSPF Controls Indoor / Outdoor 3 and Auto / 1 Fan speeds 4) Cooling Heating
Expectivy kW 2.64 3.16 Air circulation (High) cu. ft/min. 220 Moisture removal (High) Pints/h 2.7 Moisture removal (High) Pints/h 2.7 Voltage rating V 115 115 Available voltage range V 103 to 127 103 to 1 Running amperes A 8.2 8.8 Power input W 930 1.010 Power factor % 99 99 S. E. E. R. BTU/Wh 10.0 Heater element kW − HSPF — Controls Microprocessor Control unit Wireless remote control unit Temperature control IC thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor 3 and Auto / 1 Air deflector Horizontal / Vertical Manual / Manual Air filter Washable, easy access Compressor Compressor sound In-Hi / Me / Lo B-A 49 Op BTU/h 9,000 10,800
Yet Air circulation (High) cu. fr/min. 220 Moisture removal (High) Pints/h 2.7 Phase, Frequency Hz Single, 60 Voltage rating V 115 115 Available voltage rating V 103 to 127 103 to 1 Running amperes A 8.2 8.8 Power input W 930 1,010 Power factor % 99 99 S. E. E. R. BTU/Wh 10.0 Heater element kW - HSPF Ë, Capacity kW 2.64 3.16
L Moissure removal (High) Pints/h 2.7 Phase, Frequency Hz Single, 60 Voltage rating V 115 115 Available voltage range V 103 to 127 103 to 1 Running amperes A 8.2 8.8 Power input W 930 1.010 Power factor % 99 99 Starting amperes A 49 3.2 Starting amperes A 49 3.2 Starting amperes A 49 3.4 Starting amperes A 49 3.2 Starting amperes A 49 3.2 Starting amperes A 49 3.3 Starting amperes A 49 3.3 Starting amperes A 49 3.3 Starting amperes A 49 3.3 Starting amperes Indoor / Outdoor 3 and Auto / 1 Timer ON/OFF, 24-hours & Program Timer erfo Air circulation (High) cu. ft/min. 2 20
Phase, Frequency Hz Single, 60 Voltage rating V 115 115 Available voltage range V 103 to 127 103 to 1 Running amperes A 8.2 8.8 Power input W 930 1,010 Power input W 930 1,010 Power factor % 99 99 Starting amperes A 449 S. E. E. R. BTU/Wh 10.0 Heater element kW – HSPF — Controls Microprocessor Control unit Wireless remote control unit Temperature control Ic thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor 3 and Auto / 1 Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment bs. (kg) R22: 2.84 (1.29) Refrigerant ubing connections Flare type 104/10 / 35 / 30 Operation sound In-Hi / Me / Lo dB-A Ч Moisture removal (Hig h) Pints/h 2 .7
Voltage rating V 115 115 Available voltage range V 103 to 127 103 to 1 Running amperes A 8.2 8.8 Power input W 930 1,010 Power factor % 99 99 Starting amperes A 49 S. E. E. R. BTU/Wh 10.0 Heater element kW – HSPF — Controls Microprocessor Controls Microprocessor Controls Indoor / Outdoor Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor Air deflector Horizontal / Vertical Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment bs. (kg) R22: 2.84 (1.29) Refrigerant tubing connections Flare type Refrigerant tubing length ft. (m) 33 (10) Limit of tubing length ft. (m) 0utdoor unit is higher than indoor unit: 23 Refrigerant tube od. Phase, Frequency Hz Sing le, 60
Perform Available voltage range V 103 to 127 103 to 1 Running amperes A 8.2 8.8 Power input W 930 1,010 Power factor % 99 99 S.E.E.R. BTU/Wh 100.0 Heater element kW – HSPF — Controls Microprocessor Control unit Wireless remote control unit Temperature control Ic thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor 3 and Auto / 1 Air deflector Horizontal / Vertical Manual / Manual Air filter Washable, casy access Compressor Compressor Refrigerant amount charged at shipment Ibs. (kg) R22: 2.84 (1.29) Refrigerant tubing connections Flare type In-Hi / Me / Lo dB-A 40/35 / 30 Operation sound In-Hi / Me / Lo dB-A 40/35 / 30 Outdoor unit is higher than indoor unit: 23 Refrigerant tubing length ft. (m) 33 (10) 11 Limit of tubing length ft. (m) Outdoor unit is higher than indoor unit: 23 Voltage rating V 115 115
Participant A 8.2 8.8 Power input W 930 1,010 Power factor % 99 99 Starting amperes A 49 S. E. E. R. BTU/Wh 10.0 Heater element kW – HSPF — Controls Microprocessor Control unit Wireless remote control unit Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor Air deflector Horizontal / Vertical Air deflector Horizontal / Vertical Air difference Rotary Refrigerant amount charged at shipment Ibs. (kg) Refrigerant amount charged at shipment Ibs. (kg) Refrigerant control Capillary tube Refrigerant and the length ft. (m) Operation sound In-Hi / Me / Lo Max. allowable tubing length ft. (m) Limit of tubing length ft. (m) Limit of tubing length ft. (m) Limit of tubing length ft. (m) Veide tube in. (mm) Refrigerant tube od. Narrow ŝ Available voltage range e V 103 to 127 103 to 127
Power input W 930 1,010 Power factor % 99 Starting amperes A 49 99 99 S. E. E. R. BTU/Wh 10.0 00 Heater element kW – HSPF — — Controls Microprocessor Microprocessor Control unit Wireless remote control unit Temperature control and the function of the set of Rati Running amperes Α 8.2 8.8
Bower factor % 99 Starting amperes A 49 S. E. E. R. BTU/Wh 10.0 Heater element kW – HSPF — Controls Microprocessor Control unit Wireless remote control unit Temperature control IC thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment Ibs. (kg) Refrigerant control In-Hi / Me / Lo Max. allowable tubing length ft. (m) Max. allowable tubing length ft. (m) Limit of tubing length ft. (m) Limit of tubing length ft. (m) Refrigerant tube od. Narrow tube in. (mm) Refrigerant tube od. Narrow tube in. (mm) Refrigerant tube kit Optional cal Power input W 930 1,010
Starting amperes A 49 S. E. E. R. BTU/Wh 10.0 Heater element kW – HSPF — Controls Microprocessor Control unit Wireless remote control unit Temperature control IC thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor Air deflector Horizontal / Vertical Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment Ibs. (kg) Refrigerant control En-Hi / Me / Lo Refrigerant control In-Hi / Me / Lo Max. allowable tubing length at shipment ft. (m) Max. allowable tubing length at shipment ft. (m) Limit of tubing length ft. (m) Limit of tubing length at shipment ft. (m) Limit of tubing length at shipment ft. (m) Refrigerant tube od. Narrow tube in. (mm) Refrigerant tube od. Narrow tube in. (mm) Refrigerant tube od. Narrow tube in. (mm) Refrigerant tube od. Narrow tube i Ë Power factor % 99 99
S. E. E. R. BTU/Wh 10.0 Heater element kW – HSPF — Controls Microprocessor Control unit Wireless remote control unit Temperature control IC thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor 3 and Auto / 1 Air deflector Horizontal / Vertical Manual / Manual Air deflector Horizontal / Vertical Manual / Manual Air deflector Horizontal / Vertical Manual / Manual Air deflector Horizontal / Vertical Manual / Manual Air deflector Horizontal / Vertical Manual / Manual Air filter Vashable, easy access Compressor Compressor Rotary Rotary Refrigerant control Capillary tube Refrigerant tubing connections Refrigerant tubing connections Flare type Flare type Max. allowable tubing length ft. (m) 33 (10) 100 Limit of tubing length ft. (m) Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Refrigerant tube out Narrow tube Ele Starting amperes Α 1 19
Heater element kW – HSPF — Controls Microprocessor Control unit Wireless remote control unit Temperature control IC thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor Air deflector Horizontal / Vertical Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment Ibs. (kg) Refrigerant control Capillary tube Refrigerant tubing connections Flare type Max. allowable tubing length at shipment fl. (m) Juint of tubing length fl. (m) Limit of elevation difference fl. (m) Detween the 2 units Narrow tube in. (mm) Refrigerant tube od. Narrow tube in. (mm) Refrigerant tube kit Optional S. E. E. R. BTU/Wh 1 0.0
Controls Microprocessor Control unit Wireless remote control unit Temperature control IC thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor Air deflector Horizontal / Vertical Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment Ibs. (kg) Refrigerant control Capillary tube Refrigerant tubing connections Flare type Operation sound In-Hi / Me / Lo dB-A Max. allowable tubing length ft. (m) 33 (10) Limit of tubing length ft. (m) S0 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 Refrigerant tube o.d. Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube kit Optional Optional Heater element kW – HSPF -
Second control unit Wireless remote control unit Temperature control IC thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor Air deflector Horizontal / Vertical Air deflector Horizontal / Vertical Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment Ibs. (kg) Refrigerant control Capillary tube Refrigerant control Capillary tube Refrigerant subing connections Flare type Operation sound In-Hi / Me / Lo dB-A 40 / 35 / 30 Out-Hi dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) Outdoor unit is ligher than indoor unit: 23 Detween the 2 units Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube o.d. Narrow tube in. (mm) 3/8 (9.52) Refrigerant tube kit Optional Optional Controls Містор rocessor
Temperature control IC thermostat Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor 3 and Auto / 1 Air deflector Horizontal / Vertical Manual / Manual Air deflector Horizontal / Vertical Manual / Manual Air deflector Horizontal / Vertical Manual / Manual Air deflector Horizontal / Vertical Manual / Manual Air deflector Refrigerant / Washable, easy access Compressor Compressor Rotary Refrigerant amount charged at shipment Ibs. (kg) R22: 2.84 (1.29) Refrigerant control Capillary tube Refrigerant control Capillary tube Refrigerant ubing connections Flare type In-Hi / Me / Lo dB-A 40 / 35 / 30 Operation sound In-Hi / Me / Lo dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of nubing length ft. (m) S0 (15) Outdoor unit is higher than indoor unit: 23 Detween the 2 units Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube o.d. Narrow tube in. (mm) 3/8 (9.52) Refrigerant Control unit Wireless rem ote control unit
Timer ON/OFF, 24-hours & Program Fan speeds Indoor / Outdoor 3 and Auto / 1 Air deflector Horizontal / Vertical Manual / Manual Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment Ibs. (kg) R22: 2.84 (1.29) Refrigerant control Capillary tube Refrigerant tubing connections Flare type Operation sound In-Hi / Me / Lo dB-A 40 / 35 / 30 Operation sound In-Hi / Me / Lo dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 22 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Refrigerant tube o.d. Narrow tube in. (mm) 3/8 (9.52) Refrigerant tube kit Optional Temperature control IC the rmostat
Fan speeds Indoor / Outdoor 3 and Auto / 1 Air deflector Horizontal / Vertical Manual / Manual Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment Ibs. (kg) R22: 2.84 (1.29) Refrigerant control Capillary tube Refrigerant tubing connections Flare type Operation sound In-Hi / Me / Lo dB-A 40 / 35 / 30 Operation sound In-Hi / Me / Lo dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 Refrigerant tube o.d. Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube kit Optional Accessories Mounting bracket Timer ON/OFF, 24-h ours & Program
Air deflector Horizontal / Vertical Manual / Manual Air filter Washable, casy access Compressor Rotary Refrigerant amount charged at shipment lbs. (kg) R22: 2.84 (1.29) Refrigerant control Capillary tube Refrigerant nubing connections Flare type Operation sound In-Hi / Me / Lo dB-A Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 23 Outdoor unit is lower than indoor unit: 24 Optional Accessories Maunting bracket Fan speeds Indoor / Outdoor 3 and . Auto / 1
Air filter Washable, easy access Compressor Rotary Refrigerant amount charged at shipment lbs. (kg) R22: 2.84 (1.29) Refrigerant control Capillary tube Refrigerant tubing connections Flare type Operation sound In-Hi / Me / Lo dB-A 40 / 35 / 30 Operation sound In-Hi / Me / Lo dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 Refrigerant tube o.d. Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube o.d. Narrow tube in. (mm) 3/8 (9.52) Refrigerant tube kit Optional Air deflector Horizontal / Vertical Manual / Manual
Compressor Rotary Refrigerant amount charged at shipment lbs. (kg) R22: 2.84 (1.29) Refrigerant control Capillary tube Refrigerant tubing connections Flare type Operation sound In-Hi / Me / Lo dB-A 40 / 35 / 30 Operation sound In-Hi / Me / Lo dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 Refrigerant tube o.d. Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube kit Optional Accessories Mounting bracket Air filter Washable, easy access
Refrigerant amount charged at shipment lbs. (kg) R22: 2.84 (1.29) Refrigerant control Capillary tube Refrigerant control Capillary tube Refrigerant tubing connections Flare type Operation sound In-Hi / Me / Lo dB-A 40 / 35 / 30 Operation sound In-Hi / Me / Lo dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 Detween the 2 units Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube o.d. Narrow tube in. (mm) 3/8 (9.52) Refrigerant tube kit Optional Compressor Ro tary
Refrigerant control Capillary tube Refrigerant tubing connections Flare type Operation sound In-Hi / Me / Lo dB-A 40 / 35 / 30 Operation sound In-Hi / Me / Lo dB-A 40 / 35 / 30 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 Detween the 2 units Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube o.d. Narrow tube in. (mm) 3/8 (9.52) Refrigerant tube kit Optional Refrigerant amount cha arged at shipment lbs. (kg) R22: 2. 84 (1.29)
Refrigerant tubing connections Flare type Operation sound In-Hi / Me / Lo dB-A 40 / 35 / 30 Operation sound Out-Hi dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 Detween the 2 units Narrow tube in. (mm) Refrigerant tube o.d. Narrow tube in. (mm) Refrigerant tube kit Optional ŝ Refrigerant control Capill ary tube
P In-Hi / Me / Lo dB-A 40 / 35 / 30 Operation sound Out-Hi dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 22 between the 2 units Outdoor unit is lower than indoor unit: 23 Refrigerant tube o.d. Narrow tube in. (mm) Refrigerant tube kit Optional Accessories Mounting bracket atu Refrigerant tubing con nections Flar e type
Operation sound Out-Hi dB-A 49 Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 23 between the 2 units Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube o.d. Narrow tube in. (mm) 3/8 (9.52) Refrigerant tube kit Optional Accessories Mounting bracket щ A In-Hi / Me / Lo dB-A 40/: 35 / 30
Max. allowable tubing length at shipment ft. (m) 33 (10) Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 25 between the 2 units Outdoor unit is lower than indoor unit: 23 Refrigerant tube o.d. Narrow tube in. (mm) Refrigerant tube kit Optional Accessories Mounting bracket Operation sound Out-Hi dB-A 19
Limit of tubing length ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 22 between the 2 units Outdoor unit is lower than indoor unit: 23 Refrigerant tube o.d. Narrow tube in. (mm) Refrigerant tube kit Optional Accessories Mounting bracket Max. allowable tubing length at shipment ft. (m) 33 (10)
Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 2: between the 2 units Outdoor unit is lower than indoor unit: 23 Refrigerant tube o.d. Narrow tube in. (mm) Refrigerant tube o.d. Wide tube in. (mm) Refrigerant tube kit Optional Accessories Mounting bracket Limit of tubing length ft. (m) 50 (15)
Narrow tube in. (mm) 1/4 (6.35) Refrigerant tube o.d. Wide tube in. (mm) 3/8 (9.52) Refrigerant tube kit Optional Limit of elevation diffe erence ft. (m) Outdoor unit is higher than indoor unit: 23 (7)
than indoor unit: 23 (7)
Refrigerant tube o.d. Wide tube in. (mm) 3/8 (9.52) Refrigerant tube kit Optional Accessories Mounting bracket Narrow tube in. (mm) 1/4 (6.35)
Refrigerant tube kit Optional Refrigerant tube o.d. Wide tube in (mm) 3/8 (9.52)
Refrigerant tube kit ΙσΟ ional
Accessories Mountir ng bracket
Indoor unit Outdoor Indoor unit Outdoor unit
in. (mm) 13-19/32 (345) 20-7/8 (5 cigh Height in. (mm) 13-19/32 (345) 20-7/8 (530)
Width in. (mm) 31-1/2 (800) 29-17/32 Ň Width in. (mm) 31-1/2 (800) 29-17/32 (750)
2 Depth in. (mm) 7-3/32 (180) 11-1/32 ( IS & Depth in. (mm) 7-3/32 (180) 11-1/32 (280)
B Net weight Ibs. (kg) 24.3 (11) 90.4 (4) sior Net weight lbs. (kg) 24.3 (11) 90.4 (41.0)
Shipping volume cu. ft. (cu. m) 3.3 (0.10) 6.7 (0.1) nen Shipping volume cu. ft. (cu. m) 3.3 (0.10) 6.7 (0.19)
A Shipping weight (Approx.) Ibs. (kg) 28.7 (13) 97.1 (4) D. Shipping weight (App rox.) lbs. (kg) 28.7 (13) 97.1 (44)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

Cooling: Outside air temperature 95°F DB/75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Heating: Outside air temperature 47°F DB/43°F WB

Indoor unit entering air temperature 70°F WB

WM-700698

Page 7

Unit Specifications

Mode 1 No Indoor unit KI 180922
mout Outdoor unit C H0922
8 Cooling Heating
Jano Canacity BTU/h 9,000 / 8,800 10,900 / 10,700
Eo Capacity kW 2.64 / 2.59 3.19/3.14
Fer Air circulation (High) cu. ft/min. 220
Moisture removal (Hig h) Pints/h 2.7
3 Phase, Frequency ••••••••••••••••••••••••••••••••••••••• Hz Single, 60
Voltage rating V 230 / 208 230 / 208
ting Available voltage range 9 V 187 to 253 187 to 253
Rat Running amperes Α 4.5 / 4.6 4.7 / 4.8
ical Power input W 950 / 930 1,030 / 980
, E Power factor % 92 / 98 96 / 99
Ē Starting amperes Α ••••••••••••••••••••••••••••••••••••••• 30
S. E. E. R. BTU/Wh 10.0 0/10.0
Heat element kW – HSPF 1.0/0.82-6.8/6.8
Controls Micro processor
Control unit Wireless ren note control unit
Temperature control IC th ermostat
Timer ON/OFF, 24- hours & Program
Fan speeds Ind oor / Outdoor 3 and Auto / 1
Air deflector Horizo ntal / Vertical Manua l / Manual
Air filter Washable e, easy access
Compressor R otary
Refrigerant amount cha rged at shipment lbs. (kg) R22: 2 .91 (1.32)
Sources Refrigerant control Capil lary tube
catu Refrigerant tubing conr ections Fla re type
Ц Operation sound In-Hi / Me / Lo dB-A 40 / 35/30
Operation sound Out-Hi dB-A 49
Max. allowable tubing length at shipment ft. (m) 33 (10)
Limit of tubing length ft. (m) 5( ) (15)
Limit of elevation diffe rence ft. (m) Outdoor unit is highe r than indoor unit: 23 (7)
between the 2 units ••••••••••••••••••••••••••••••••••••••• ••••• Outdoor unit is lower than indoor unit: 23 (7)
Refrigerant tube o d Narrow tube in. (mm) (6.35)
Kenigerant tube 0.u. Wide tube in. (mm) 3/8 (9.52)
Refrigerant tube kit Op tional
Accessories Mounti ng bracket
äht Indoor unit Outdoor unit
Vei Height in. (mm) 13-19/32 (345) 20-7/8 (530)
& V Width in. (mm) 31-1/2 (800) 29-17/32 (750)
Suc Depth in. (mm) 7-3/32 (180) 11-1/32 (280)
'nsić Net weight lbs. (kg) 24.3 (11) 90.4 (41)
lime Shipping volume cu. ft. (cu. m) 3.3 (0.10) 6.7 (0.19)
Shipping weight (Appro ox.) lbs. (kg) 28.7 (13) 97.1 (44)

Remarks: Rating conditions are:

Cooling: Outside air temperature 95°F DB/75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Heating: Outside air temperature 47°F DB/43°F WB Indoor unit entering air temperature 70°F WB

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Page 8
Unit Specifications
Indoor unit КН S1222
Model No. Outdoor unit 11222
- Cooling Heating
ance i BTU/h 11,400 / 11,200 13,300 / 12,700
Ĩ Capacity kW 3.34 / 3.28 3.90 / 3.72
erfo Air circulation (High) cu. ft/min. 360 0/330
4 Moisture removal (High ) Pints/h 4.0
Phase, Frequency Hz Sin gle, 60
Voltage rating V V 230 / 208 230 / 208
ng
B
Available voltage range v 187 to 253 187 to 253
Rati Running amperes Α 5.6/5.9 5.2 / 5.5
[]E Power input W 1,210 / 1,180 1,190 / 1,140
ij Power factor % 94 / 97 99 / 99
E Starting amperes Α 32
S. E. E. R. BTU/Wh 10.0 0 / 10.0
Heat element kW – HSPF 1.5 / 1.23 - 6.8 / 6.8
· Controls Micro processor
Control unit Wireless ren note control unit
Temperature control IC th ermostat
Timer ON/OFF, 24- hours & Program
Fan speeds Indoor / Outdoor 3 and Auto / 1
Air deflector Horizontal / Vertical Manual / Automatic
Air filter ••••••••••••••••••••••••••••••••••••••• Washable e, easy access
Compressor R lotary
Refrigerant amount cha rged at shipment lbs. (kg) R22: 2 .96 / (1.34)
S Refrigerant control Capi llary tube
atur Refrigerant tubing conr ections Fla re type
н
Н
In-Hi/Me/Lo dB-A 43 / / 39 / 36
Operation sound Out-Hi dB-A 49
Max. allowable tubing length at shipment ft. (m) 3 3 (10)
Limit of tubing length ft. (m) 6 5 (20)
Limit of elevation diffe
between the 2 units
rence ft. (m) Outdoor unit is highe
Outdoor unit is lowe
er than indoor unit: 23 (7)
er than indoor unit: 23 (7)
Narrow tube in. (mm) 1/4 (6.35)
Refrigerant tube o.d. Wide tube in. (mm) 1/2 2 (12.7)
Refrigerant tube kit Ο ptional
Accessories Mount ing bracket
Ħ Indoor unit Outdoor unit
eigł Height in. (mm) 14-3/16 (360) 20-7/8 (530)
Ň Width in. (mm) 39-0 (990) 29-17/32 (750)
ls & Depth in. (mm) 7-13/16 (198) 11-1/32 (280)
sion Net weight lbs. (kg) 29.8 (13.5) 92.6 (42)
nen Shipping volume cu. ft. (cu. m) 4.8 (0.14) 6.5 (0.19)
ă | Shipping weight (Appr ox.) lbs. (kg) 37.5 (17) 99.3 (45)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks: Rating conditions are:

Cooling: Outside air temperature 95°F DB/75°F WB

Indoor unit entering air temperature 80°F DB/67°F WB

Heating: Outside air temperature 47°F DB/43°F WB

Indoor unit entering air temperature 70°F WB

Page 9

3. DIMENSIONAL DATA

Indoor Unit: KHS0921, KHS0922

Indoor Unit: KHS1222

Page 10

Outdoor Unit: CH1222

Page 11

4. COOLING CAPACITY

115V

KHS0921 / CH0921
Rating g Capacity: 9,000 BTU/H ' Air Flow v Rate: 220 CFM
Eva porator Cone lenser
Ent. Tem p. °F/(°C) Ambient Te mp. °F/(' °C)
WB DB 75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
TC
kW
8,910
0.67
8,510
0.73
8,100
0.80
7,640
0.87
7,020
0.95
59
(15.0)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
SHC
SHC
SHC
SHC
6,310
7,050
7,830
8 570
6,090
6,830
7,610
8 350
5,880
6,620
7,400
8,100
5,650
6,390
7,160
7,640
5,340
6,080
6,850
7,020
88 (31.1) SHC 8,910
9,220
8,510
8,930
8,100
8,580
7,640 7,020
63
(17 2)
72 (22.2)
76 (24 4)
kW
SHC
SHC
0.68
5,360
6,100
0.74
5,220
5,960
0.81
5,050
5,790
0.88
4,830
5,570
0.97
4,530
5,270
(11.2) 80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
6,880
7,620
8,360
6,740
7,480
8,220
6,570
7,310
8,050
6,340
7,090
7,830
6,050
6,790
7,470
TC
kW
9,470
0.68
9,320
0.75
*9,000
0.82
8,510
0.89
7,920
0.99
67
(19.4)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
SHC
4,380
5,120
5,890
6,630
7,380
4,310
5,050
5,820
6,570
7,310
4,170
4,910
5,690
6,430
7,170
3,950
4,700
5,470
6,210
6,950
3,710
4,450
5,220
5,960
6,710
TC
kW
9,770
0.69
9,600
0.76
9,360
0.83
8,940
0.92
8,420
1.01
71
(21.7)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
SHC
3,370
4,110
4,880
5,630
6,370
3,300
4,040
4,820
5,560
6,300
3,200
3,950
4,720
5,460
6,200
3,040
3,780
4,550
5,300
6,040
2,840
3,580
4,350
5,090
5,840
TC
kW
9,950
0.71
9,850
0.77
9,630
0.84
9,290
0.94
8,910
1.04
75
(23.9)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
3,100
3,870
4,620
5,360
3,060
3,830
4,580
5,320
2,980
3,760
4,500
5,240
2,860
3,640
4,380
5,120
2,730
3,500
4,240
4,990

TC: Total Cooling Capacity (BTU/H) SHC: Sensible Heat Capacity (BTU/H) kW: Compressor Input (kW)

Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB/67°F WB

Page 12
KHS0922 / CH0922

230V

Rating Capacity: 9,000 BTU/H · : · Air Flov v Rate: 220 CFM
Evar orator Conc lenser
Ent. Temp •. °F/(°C) Ambient Te mp. °F/(° °C)
WD DB 75 85 95 105 115
WB (23.9) (29.4) (35.0) (40.6) (46.1)
TC 8,910 8,510 8,100 7,640 7,020
••••••••••••••••••••••••••••••••••••••• kW 0.67 0.73 0.80 0.87 0.95
59 72 (22.2) SHC 6,310 6,090 5,880 5,650 5,340
(15.0) 76 (24.4) SHC 7,050 6,830 6,620 6,390 6,080
80 (26.7) SHC 7,830 7,610 7,400 7,160 6,850
84 (28.9) SHC 8,570 8,350 8,100 7,640 7,020
88 (31.1) SHC 8,910 8,510 8,100 7,640 7,020
ТС 9,220 8,930 8,580 8,110 7,470
kW 0.68 0.74 0.81 0.88 0.97
63 72 (22.2) SHC 5,360 5,220 5,050 4,830 4,530
(17.2) 76 (24.4) SHC 6,100 5,960 5,790 5,570 5,270
80 (26.7) SHC 6,880 6,740 6,570 6,340 6,050
84 (28.9) SHC 7,620 7,480 7,310 7,090 6,790
88 (31.1) SHC 8,360 8,220 8,050 7,830 7,470
тс 9,470 9,320 *9,000 8,510 7,920
kW 0.68 0.75 0.82 0.89 0.99
67 72 (22.2) SHC 4,380 4,310 4,170 3,950 3,710
(19.4) 76 (24.4) SHC 5.120 5,050 4,910 4,700 4,450
80 (26.7) SHC 5,890 5,820 5,690 5,470 5,220
84 (28.9) SHC 6,630 6,570 6,430 6,210 5,960
88 (31.1) SHC 7,380 7,310 7,170 6,950 6,710
ТС 9,770 9,600 9,360 8,940 8,420
kW 0.69 0.76 0.83 0.92 1.01
71 72 (22.2) SHC 3,370 3,300 3,200 3,040 2,840
(21.7) 76 (24.4) SHC 4,110 4,040 3,950 3,780 3,580
80 (26.7) SHC 4,880 4,820 4,720 4,550 4,350
84 (28.9) SHC 5,630 5,560 5,460 5,300 5,090
88 (31.1) SHC 6,370 6,300 6,200 6,040 5,840
TC 9,950 9,850 9,630 9,290 8,910
kW 0.71 0.77 0.84 0.94 1.04
75 76 (24.4) SHC 3,100 3,060 2,980 2,860 2,730
(23.9) 80 (26.7) SHC 3,870 3,830 3,760 3,640 3,500
84 (28.9) SHC 4,620 4,580 4,500 4,380 4,240
88 (31.1) SHC 5,360 5,320 5,240 5,120 4,990

TC: Total Cooling Capacity (BTU/H) SHC: Sensible Heat Capacity (BTU/H) kW: Compressor Input (kW)

Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB/67°F WB

Page 13
KHS0922 / CH0922

208V

Rati ng Capacity: 8,80 0 BTU/H Air Flo w Rate: 210 CFM
Ev aporator ` Con denser
Ent. Ter np. °F/(°C) Ambient To emp. °F/ (°C)
WB DB 75
(23.9)
85
(29.4)
95
(35.0)
105 115
тс 8,710 8,320 7.920 7.470 6 860
kW 0.67 0.73 0.80 0.87 0.95
59 72 (22.2) SHC 6,140 5,930 5,720 5,490 5,190
(15.0) 76 (24.4) SHC 6,860 6,640 6,440 6,200 5,900
80 (26.7) SHC 7,600 7,390 7,180 6,950 6,650
04 (20.9)
98 (21.1)
SHC 8,320 8,100 7,890 7,470 6,860
00 (31.1) SIL 8,710 8,320 7,920 7,470 6,860
9,010 8,730 8,390 7,930 7,300
(2) 20 (00 0) KW 0.08 0.74 0.81 0.88 0.97
03
(17-2)
SHC 5,230 5,090 4,920 4,700 4,410
(17.2) 70 (24.4)
80 (26 7)
SHC 5,940 5,800 5,630 5,420 5,130
84 (28 9) SHC 0,090 7 260 0,380 6,160 5,870
88 (31.1) SHC 8,110 7,200 7,090 0,880 7 300
тс 9 260 0 110 *8 800 8 220 7,500
kW 0.68 0.75 0.82 0,520 0.99
67 72 (22.2) SHC 4.280 4.210 4 070 3 860 3 610
(19.4) 76 (24.4) SHC 4,990 4,920 4,780 4,570 4,330
80 (26.7) SHC 5,730 5,670 5,530 5,320 5,070
84 (28.9) SHC 6,450 6,380 6,240 6,030 5,790
88 (31.1) SHC 7,160 7,090 6,960 6,750 6,500
1. A. A. TC 9,550 9,390 9,150 8,740 8,230
kW 0.69 0.76 0.83 0.92 1.01
71 72 (22.2) SHC 3,300 3,230 3,140 2,970 2,780
(21.7) 76 (24.4) SHC 4,010 3,950 3,850 3,690 3,490
80 (26.7) SHC 4,760 4,690 4,600 4,430 4,240
84 (28.9) SHC 5,470 5,410 5,310 5,150 4,950
88 (31.1) SHC 6,190 6,120 6,030 5,860 5,660
TC 9,730 9,630 9,420 9,080 8,710
kW 0.71 0.77 0.84 0.94 1.04
75 76 (24.4) SHC 3,040 3,000 2,920 2,800 2,670
(23.9) 80 (26.7) SHC 3,780 3,740 3,670 3,550 3,420
84 (28.9) SHC 4,490 4,460 4,380 4,260 4,130
88 (31.1) SHC 5,210 5,170 5,090 4,970 4,840

TC: Total Cooling Capacity (BTU/H) SHC: Sensible Heat Capacity (BTU/H) kW: Compressor Input (kW)

Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB/67°F WB

Page 14
KHS1222 / CH1222

230V

Ratin g Capacity: 11,40 0 BTU/H Air Flov v Rate: 360 CFM
Eva porator Conc ienser
Ent. Tem p. °F/(°C) 1 Ambient Te mp. °F/(° °C)
WB DB 75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
12 TC
kW
11,290
0.89
10,770
0.97
10,260
1.05
9,680
1.14
8,890
1.25
59
(15.0)
72 (22.2)
76 (24.4)
80 (26.7)
SHC
SHC
SHC
8,520
9,690
10,910
8,270
9,440
10,650
8,020
9,190
10,260
7,750
8,910
9,680
7,380
8,540
8,890
84 (28.9)
88 (31.1)
SHC
SHC
11,290
11,290
10,770
10,770
10,260
10,260
9,680
9,680
8,890
8,890
TC
kW
11,670
0.89
11,310
0.98
10,860
1.07
10,270
1.16
9,460
1.28
63
(17.2)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
SHC
7,110
8,270
9,490
10,650
11,670
6,940
8,110
9,320
10,490
11,310
6,740
7,910
9,130
10,290
10,860
6,480
7,650
8,870
10,030
10,270
6,130
7,300
8,520
9,460
9,460
TC
kW
11,990
0.90
11,800
0.99
*11,400
1.08
10,770
1.18
10,030
1.31
67
(19.4)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
SHC
5,650
6,810
8,030
9,200
10,360
5,570
6,730
7,950
9,120
10,280
5,400
6,570
7,790
8,950
10,120
5,150
6,320
7,530
8,700
9,860
4,860
6,020
7,240
8,410
9,570
88 (51.17 TC
kW
12,370
0.91
12,160
1.00
11,860
1.10
11,320
1.21
10,660
1.33
71
(21.7)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
SHC
4,150
5,310
6,530
7,700
8,860
4,070
5,240
6,450
7,620
8,780
3,960
5,120
6,340
7,500
8,670
3,760
4,930
6,140
7,310
8,470
3,520
4,690
5,900
7,070
8,230
TC
kW
12,610
0.93
12,470
1.02
12,200
1.11
11,760
1.24
11,290
1.37
75
(23.9)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
3,820
5,040
6,210
7,370
3,780
5,000
6,160
7,330
3,690
4,900
6,070
7,230
3,540
4,760
5,930
7,090
3,390
4,600
5,770
6,930

TC: Total Cooling Capacity (BTU/H) SHC: Sensible Heat Capacity (BTU/H) kW: Compressor Input (kW)

Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB/67°F WB

Page 15
KHS1222 / CH1222

208V

Ratir ng Capacity: 11,20 0 BTU/H Air Flo w Rate: 330 CFM
Ev aporator . Con denser 7
Ent. Ten np. °F/(°C) Ambient Te mp. °F/( °C)
WB DB 75
(23.9)
85
(29.4)
95
(35.0)
105
(40.6)
115
(46.1)
TC
kW
11,090
0.88
10,580
0.96
10,080
1.04
9,510
1.13
8,740
1.24
59
(15.0)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
SHC
8,220
9,300
10,440
11,090
11,090
7,970
9,050
10,190
10,580
10,580
7,720
8,800
9,940
10,080
10,080
7,440
8,530
9,510
9,510
9,510
7,080
8,160
8,740
8,740
8,740
8,740
TC
kW
11,470
0.89
11,110
0.97
10,670
1.06
10,090
1.15
9,300
1.27
63
(17.2)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
SHC
6,890
7,970
9,100
10,190
11,270
6,720
7,810
8,940
10,020
11,110
6,520
7,610
8,740
9,820
10,670
6,260
7,350
8,480
9,560
10,090
5,910
7,000
8,130
9,220
9,300
TC
kW
11,780
0.89
11,590
0.98
*11,200
1.07
10,580
1.17
9,860
1.29
67
(19.4)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
SHC
5,510
6,590
7,730
8,810
9,900
5,430
6,510
7,650
8,730
9,820
5,270
6,350
7,490
8,570
9,6 5 0
5,010
6,100
7,230
8,320
9,400
4,720
5,810
6,940
8,020
9,110
TC
kW
12,150
0.90
11,950
0.99
11,650
1.09
11,120
1.20
10,470
1.32
71
(21.7)
72 (22.2)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
SHC
4,100
5,180
6,310
7,400
8,480
4,020
5,100
6,240
7,320
8,410
3,900
4,990
6,120
7,210
8,290
3,710
4,790
5,930
7,010
8,100
3,470
4,550
5,690
6,770
7,860
TC
kW
12,390
0.92
12,250
1.01
11,980
1.10
11,560
1.23
11,090
1.35
75
(23.9)
76 (24.4)
80 (26.7)
84 (28.9)
88 (31.1)
SHC
SHC
SHC
SHC
3,770
4,910
5,990
7,080
3,730
4,860
5,950
7,030
3,640
4,770
5,860
6,940
3,490
4,630
5,710
6,800
3,340
4,470
5,550
6,640

TC: Total Cooling Capacity (BTU/H) SHC: Sensible Heat Capacity (BTU/H) kW: Compressor Input (kW)

Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB

Indoor unit entering air temperature 80°F DB/67°F WB

WM-700698

Page 16

5. HEATING CAPACITY

1 Phase 60Hz 115V Model Name: KHS0921

Temperature Air Entering Outdoor Coil (°F DB at 75% RH)

Page 17

Indoor Entering Air Temperature 70°F

(°F DB at 75% RH)

Page 18

(°F DB at 75% BH)

Page 19

Page 20

(°F DB at 75% RH)

Page 21

6. REFRIGERANT FLOW DIAGRAM

Cooling Cycle

Models: KHS0921 / CH0921, KHS0922 / CH0922

Heating Cycle

Models: KHS0921 / CH0921, KHS0922 / CH0922

Page 22

Cooling Cycle

Models: KHS1222 / CH1222

Heating Cycle

Models: KHS1222 / CH1222

WM-700698

Page 23

7. ELECTRICAL DATA

• Electrical Characteristics
KHS0921 / CH0921
Performance at Indoo r Unit Outdo or Unit Complete Unit
115V – 1ø – 60Hz Fan Motor Max. Heat Fan Motor Compressor Heat-pump Max. Heat
Casting Rating A 0.26 *** 0.69 7.25 8.2
Cooling Conditions W 28 · . 79 823 930
Hasting Rating A 0.26 ! 0.69 7.85 8.8
Heating Conditions W 28 79 903 1,010
Locked-I Rotor Amperes A 0.31 0.87 49

Remarks: Rating conditions are:

Cooling: Outside air temperature 95°F DB/75°F WB

Indoor unit entering air temperature 80°F DB/67°F WB

Heating: Outside air temperature 47°F DB/43°F WB

Indoor unit entering air temperature 70°F WB

KHS0922 / CH0922
Perfo Performance at Indoo r Unit Outdo or Unit Complete Unit
230/208V – 1ø – 60Hz Fan Motor Max. Heat Fan Motor Compressor Heat-pump Max. Heat
Cooling Rating A 0.15/0.14 0.42 / 0.39 3.93 / 4.07 4.5/4.6
Cooling Conditions W 34/29 95 / 80 821/821 950/930
Uasting Rating A 0.15/0.14 4.35 / 3.93 0.42 / 0.39 4.13 / 4.27 4.7 / 4.8 9.05 / 8.73
neating Conditions W 34/29 1,000/818 95 / 80 901/871 1,030 / 980 2,030 / 1,798
Locked-l Rotor Amperes A 0.18/0.17 0.45 / 0.41 30 *

Remarks: Rating conditions are:

Cooling: Outside air temperature 95°F DB/75°F WB

Indoor unit entering air temperature 80°F DB/67°F WB

Heating: Outside air temperature 47°F DB/43°F WB

Indoor unit entering air temperature 70°F WB

KHS1222 / CH1222
Perfo Performance at Indoo r Unit Outdo or Unit Complete Unit
230/208V – 1ø – 60Hz Fan Motor Max. Heat Fan Motor Compressor Heat-pump Max. Heat
Casting Rating A 0.18 / 0.17 0.42 / 0.39 5.0/5.34 5.6/5.9
Cooling Conditions W 40/35 95 / 80 1,075 / 1,065 1,210/1,180 _
Heating Rating A 0.18/0.17 6.52 / 5.90 0.42 / 0.39 .4.6/4.94 5.2/5.5 11.7 / 11.4
neating Conditions W 40/35 1,500 / 1,227 95 / 80 1,055 / 1,025 1,190/1,140 2,690 / 2,367
Locked-I Rotor Amperes A 0.21 / 0.18 0.45 / 0.41 32

Remarks: Rating conditions are:

Cooling: Outside air temperature 95°F DB/75°F WB

Indoor unit entering air temperature 80°F DB/67°F WB

Heating: Outside air temperature 47°F DB/43°F WB

Indoor unit entering air temperature 70°F WB

Page 24
• Electric Wiring Diagram

Indoor Unit: KHS0921

To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.

Page 25

To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.

W/M __ 7006

Page 26

Indoor Unit: KHS1222

To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.

Page 27

To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.

Page 28

Outdoor Unit: CH0922

To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.

Downloaded from www.Manualslib.com manuals search engine

WM -- 700698

Page 29

To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts.

Page 30

For parts or service contact

SFS Corporation: 1200 West Artesia Bivd., Compton, California 90220

In Canada SANYO Canada Inc.: Toronto, Ont. M4H 1M6

H408/12M

Printed in U.S.A. WM-700698