Sanyo C2672R, KH2672R, XH2672R, C3672R, CH4272R User Manual

...
TECHNICAL DATA
&
SERVICE MANUAL
XH2672R / CH2672R, C2672R XH3672R / CH3672R, C3672R XH4272R / CH4272R, C4272R
TH2672R / CH2672R, C2672R TH3672R / CH3672R, C3672R TH4272R / CH4272R, C4272R THH2672R / CH2672R THH3672R / CH3672R
SPLIT SYSTEM AIR CONDITIONER
INDOOR MODEL No. PRODUCT CODE No.
XH2672R 854 028 32
XH3672R 854 028 33
XH4272R 854 031 89
TH2672R 854 028 35
TH3672R 854 028 36
TH4272R 854 031 90
THH2672R 854 028 38
THH3672R 854 028 39
KH2672R 854 028 28
KH3072R 854 028 29
KH3672R 854 028 30
KHH2672R 854 028 31
UH2672R 854 028 40
UH3672R 854 028 41
Indoor Unit Outdoor Unit
OUTDOOR MODEL No. PRODUCT CODE No.
FILE NO.
KH2672R / CH2672R, C2672R KH3072R / CH3072R, C3072R KH3672R / CH3672R, C3672R KHH2672R / CH2672R
UH2672R / CH2672R, C2672R UH3672R / CH3672R, C3672R
CH2672R 854 028 20
CH3072R 854 028 21
CH3672R 854 028 22
CH4272R 854 031 87
C2672R 854 028 24
C3072R 854 028 25
C3672R 854 028 26
C4272R 854 031 88
1
2
3
XH2672R XH3672R
XH4272R
UH2672R
85464849248002 REFERENCE NO. SM831148-2
UH3672R
KHH2672R KH2672R
TH2672R, THH2672R TH3672R, THH3672R TH4272R
KH3072R KH3672R
CH2672R, C2672R CH3072R, C3072R CH3672R, C3672R
CH4272R, C4272R
4
5
6

Important

Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must :
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or
CAUTION
unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
.............................................................................................
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidentaly injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause overheat­ing at connection points and a possible fire hazard.
When Transporting
...............................................................................................
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
.............................................................................................
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys-tems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
.............................................................................................
Ventilate the room well, in the event that refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
Keep all tubing runs as short as possible.
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either “narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
..............................................................................................
Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site when installation is finished. Check that no metal scraps or bits of wiring have been left inside the unit.
CAUTION
Ventilate any enclosed areas when installing or testing the refrigeration system. Contact of refrigerant gas with fire or heat can produce poisonous gas.
Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
SM831148
i

Contents

Section 1: SPECIFICATIONS ................................................................................................. I-1
1-1 Unit Specifications .......................................................................................... I-2
1-2 Major Component Specifications .................................................................. I-27
1-3 Other Component Specifications .................................................................. I-47
1-4 Dimensional data .......................................................................................... I-63
1-5 Refrigerant Flow Diagram ............................................................................. I-74
1-6 Operating Range .......................................................................................... I-75
1-7 Heating Capacity .......................................................................................... I-76
1-8 Noise Criterion Curves.................................................................................. I-77
1-9 Increasing the Fan Speed ............................................................................. I-82
1-10 Air throw distance chart ................................................................................ I-83
1-11 Installation Instructions.................................................................................. I-86
1-12 Electrical Wiring ............................................................................................I-98
1-13 Using Wireless Remote Controller with Wall-mounted Indoor Unit ............. I-102
Section 2: PROCESSES AND FUNCTIONS......................................................................... II-1
2-1 Room Temperature Control ............................................................................ II-2
2-2 Cold Draft Prevention (Heating Cycle) ........................................................... II-4
2-3 Automatic Fan Speed (Indoor Unit) ................................................................ II-5
2-4 Control Functions........................................................................................... II-6
2-5 Outdoor Unit Control PCB .............................................................................. II-9
2-6 Outdoor Unit Control PCB (CR-CH4272R) .................................................. II-10
Section 3: ELECTRICAL DATA ............................................................................................ III-1
3-1 Indoor Units................................................................................................... III-2
3-2 Outdoor Units .............................................................................................. III-16
Section 4: SERVICE PROCEDURES ..................................................................................IV-1
4-1 Meaning of Alarm Messages.........................................................................IV-2
4-2 Symptoms and Parts to Inspect .....................................................................IV-5
4-3 Details of Alarm Messages ........................................................................... IV-8
4-4 Table of Thermistor Characteristics .............................................................IV-14
Section 5:
Section 6: TEST RUN .......................................................................................................... VI-1
OUTDOOR UNIT MAINTENANCE REMOTE CONTROL ...............................................
5-1 Overview ....................................................................................................... V-2
5-2 Functions ...................................................................................................... V-2
5-3 Normal Display Operations and Functions ................................................... V-3
5-4 Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor
Temperatures ................................................................................................ V-6
5-5 Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit
Alarm History ................................................................................................ V-7
5-6 Setting Modes: Setting the Outdoor Unit EEPROM ....................................... V-7
6-1 Preparing for Test Run ................................................................................. VI-2
6-2 Caution ........................................................................................................ VI-3
6-3 Test Run Procedure ..................................................................................... VI-3
6-4 Items to Check Before the Test Run ............................................................. VI-4
6-5 Test Run Using the Remote Controller......................................................... VI-4
6-6 Precautions .................................................................................................. VI-4
6-7 Table of Self-Diagnostic Functions and Corrections (X, T, U, K Type) .......... VI-5
6-8 Examples of Wiring Diagrams ...................................................................... VI-6
V-1
1. Specifications
1. SPECIFICATIONS
1-1 Unit Specifications ......................................................................................................... I-2
1-2 Major Component Specifications ............................................................................... I-27
1-3 Other Component Specifications ............................................................................... I-47
1-4 Dimensional data ......................................................................................................... I-63
1-5 Refrigerant Flow Diagram............................................................................................ I-74
1-6 Operating Range .......................................................................................................... I-75
1-7 Heating Capacity.......................................................................................................... I-76
1-8 Noise Criterion Curves ................................................................................................ I-77
1-9 Increasing the Fan Speed ........................................................................................... I-82
1-10 Air throw distance chart .............................................................................................. I-83
1-11 Installation Instructions ............................................................................................... I-86
1-12 Electrical Wiring ........................................................................................................... I-98
1-13 Using Wireless Remote Controller with Wall-mounted Indoor Unit ........................ I-102
1
2
3
4
I-1
5
6
SM831148
1-1 Unit Specifications
Wall-Mounted Type

1. Specifications

1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 23,000 [9,500~23,000] 27,600 [8,000~27,600]
Moisture removal (High) Pints / h 7.4 Air circulation (H / M / L) 230 V CFM 540 / 460 / 380 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.9 10.3
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253
Max. Running amperes* (Without Back-up Heater)
Power input W 2,610 2,610 2,720 2,720
Back-up Heater kW 1.8 1.47
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH1UA / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 14- 9/16 (370) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 44.1 (20) 128 (58) Shipping weight lbs. (kg) 59.5 (27) 148 (67) Shipping volume cu.ft. (m 3 ) 6.4 (0.181) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit KHH2672R
Outdoor Unit CH2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 18,500
in. WG
A 14.0 15.5 14.6 16.1
(17˚F)** W 2,160 2,160
A 15 / 30
Microprocessor
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 49- 7/32 (1,250) 37 (940) Depth in. (mm) 8- 9/32 (210) 13- 3/8 (340)
Height in. (mm) 18- 7/16 (468) 34- 31/32 (888) Width in. (mm) 52- 23/32 (1,339) 39- 31/32 (1,015) Depth in. (mm) 11- 3/8 (289) 16- 3/32 (409)
dB - A 45 / 42 / 40
Electronic Expansion Valve (MOV)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-2
1-1 Unit Specifications
Wall-Mounted Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 25,200 [9,500~25,200] 29,200 [8,000~29,200]
Moisture removal (High) Pints / h 8.1 Air circulation (H / M / L) 230 V CFM 559 / 475 / 390 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.9 10.2
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253
Max. Running amperes*
Power input W 2,840 2,840 2,620 2,620
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH1UA / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 12- 63/64 (330) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 40 (18) 128 (58) Shipping weight lbs. (kg) 44 (20) 148 (67) Shipping volume cu.ft. (m 3 ) 4.9 (0.139) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit KH2672R
Outdoor Unit CH2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 17,200
in. WG
A 15.3 16.9 14.0 15.5
(17˚F)** W 2,030 2,030
A 15 / 30
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 44- 7/8 (1,140) 37 (940) Depth in. (mm) 8- 31/32 (228) 13- 3/8 (340)
Height in. (mm) 15- 11/32 (390) 34- 31/32 (888) Width in. (mm) 47- 27/32 (1,215) 39- 31/32 (1,015) Depth in. (mm) 11- 17/32 (293) 16- 3/32 (409)
dB - A 48 / 42 / 38
Electronic Expansion Valve (MOV)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-3
6
SM831148
1-1 Unit Specifications
Wall-Mounted Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 29,800 [9,500~29,800] 34,800 [8,000~34,800]
Moisture removal (High) Pints / h 9.7 Air circulation (H / M / L) 230 V CFM 840 / 740 / 620 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.0 9.0
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253 Max. Running amperes* A 17.7 19.6 16.2 17.9 Power input W 3,690 3,690 3,390 3,390
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH1UA / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 5.73 (2.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 14- 9/16 (370) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 63.9 (29) 143 (65) Shipping weight lbs. (kg) 81.6 (37) 161 (73) Shipping volume cu.ft. (m 3 ) 8.4 (0.237) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit KH3072R
Outdoor Unit CH3072R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 20,000
in. WG
(17˚F)** W 2,460 2,460
A 15 / 35
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 59- 1/16 (1,500) 37 (940) Depth in. (mm) 9- 7/16 (240) 13- 3/8 (340)
Height in. (mm) 18- 7/16 (468) 34- 31/32 (888) Width in. (mm) 62- 9/16 (1,589) 39- 31/32 (1,015) Depth in. (mm) 12- 9/16 (319) 16- 3/32 (409)
dB - A 46 / 42 / 38
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-4
1-1 Unit Specifications
Wall-Mounted Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 31,400 [9,500~31,400] 36,400 [8,000~36,400]
Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 830 / 710 / 590 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.9 9.0
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253 Max. Running amperes* A 17.9 19.8 15.9 17.6 Power input W 3,750 3,750 3,320 3,320
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH1UA / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 14- 9/16 (370) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 72.8 (33) 143 (65) Shipping weight lbs. (kg) 90.4 (41) 161 (73) Shipping volume cu.ft. (m 3 ) 8.4 (0.237) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit KH3672R
Outdoor Unit CH3672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 20,200
in. WG
(17˚F)** W 2,450 2,450
A 15 / 35
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 59- 1/16 (1,500) 37 (940) Depth in. (mm) 9- 7/16 (240) 13- 3/8 (340)
Height in. (mm) 18- 7/16 (468) 34- 31/32 (888) Width in. (mm) 62- 9/16 (1,589) 39- 31/32 (1,015) Depth in. (mm) 12- 9/16 (319) 16- 3/32 (409)
dB - A 48 / 44 / 40
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-5
6
SM831148
1-1 Unit Specifications
Wall-Mounted Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 25,200 [9,500~25,200]
Moisture removal (High) Pints / h 8.1 Air circulation (H / M / L) 230 V CFM 559 / 475 / 390 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.9
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253
Max. Running amperes*
Power input W 2,840 2,840
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH1UA / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 12- 63/64 (330) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 40 (18) 128 (58) Shipping weight lbs. (kg) 44 (20) 148 (67) Shipping volume cu.ft. (m 3 ) 4.9 (0.139) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit KH2672R
Outdoor Unit C2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
A 15.3 16.9
(17˚F)** W
A 15 / 30
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
(20A , OD26mm)
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 44- 7/8 (1,140) 37 (940) Depth in. (mm) 8- 31/32 (228) 13- 3/8 (340)
Height in. (mm) 15- 11/32 (390) 34- 31/32 (888) Width in. (mm) 47- 27/32 (1,215) 39- 31/32 (1,015) Depth in. (mm) 11- 17/32 (293) 16- 3/32 (409)
dB - A 48 / 42 / 38
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-6
1-1 Unit Specifications
Wall-Mounted Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 29,800 [9,500~29,800]
Moisture removal (High) Pints / h 9.7 Air circulation (H / M / L) 230 V CFM 840 / 740 / 620 External Static Pressure S.E.E.R. BTU / Wh 15.0
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253 Max. Running amperes* A 17.7 19.6 Power input W 3,690 3,690
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH1UA / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 5.73 (2.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 14- 9/16 (370) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 63.9 (29) 143 (65) Shipping weight lbs. (kg) 81.6 (37) 161 (73) Shipping volume cu.ft. (m 3 ) 8.4 (0.237) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit KH3072R
Outdoor Unit C3072R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
(17˚F)** W
A 15 / 35
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 59- 1/16 (1,500) 37 (940) Depth in. (mm) 9- 7/16 (240) 13- 3/8 (340)
Height in. (mm) 18- 7/16 (468) 34- 31/32 (888) Width in. (mm) 62- 9/16 (1,589) 39- 31/32 (1,015) Depth in. (mm) 12- 9/16 (319) 16- 3/32 (409)
dB - A 46 / 42 / 38
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-7
6
SM831148
1-1 Unit Specifications
Wall-Mounted Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 31,400 [9,500~31,400]
Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 830 / 710 / 590 External Static Pressure S.E.E.R. BTU / Wh 15.9
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253 Max. Running amperes* A 17.9 19.8 Power input W 3,750 3,750
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH1UA / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 14- 9/16 (370) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 72.8 (33) 143 (65) Shipping weight lbs. (kg) 90.4 (41) 161 (73) Shipping volume cu.ft. (m 3 ) 8.4 (0.237) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit KH3672R
Outdoor Unit C3672R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
(17˚F)** W
A 15 / 35
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 59- 1/16 (1,500) 37 (940) Depth in. (mm) 9- 7/16 (240) 13- 3/8 (340)
Height in. (mm) 18- 7/16 (468) 34- 31/32 (888) Width in. (mm) 62- 9/16 (1,589) 39- 31/32 (1,015) Depth in. (mm) 12- 9/16 (319) 16- 3/32 (409)
dB - A 48 / 44 / 40
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-8
1-1 Unit Specifications
4-Way Air Discharge Semi-Concealed Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 24,800 [9,500~24,800] 29,800 [8,000~29,800]
Moisture removal (High) Pints / h 8.1 Air circulation (H / M / L) 230 V CFM 710 / 530 / 450 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.1 10.5
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253
Max. Running amperes*
Power input W 2,920 2,920 2,790 2,790
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller Air deflection (Horizontal / Vertical ) / Automatic (Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 13-5/16 (338) 30- 23/32 (780)
Package dimensions Body Panel Outdoor unit
Net weight lbs. (kg) 49 (22) 11 (5) 128 (58) Shipping weight lbs. (kg) 57 (26) 18 (8) 148 (67) Shipping volume cu.ft. (m 3 ) 7.1 (0.200) 3.6 (0.100) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit XH2672R
Outdoor Unit CH2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 18,300
in. WG
A 15.6 17.3 14.8 16.4
(17˚F)** W 2,200 2,200
A 15 / 30
RCS-SH80UG / RCS-TM80BG
RCS-SH80UA.WL / RCS-BH80UA. WL
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 33-55/64 (860) 37 (940) Depth in. (mm) 33-55/64 (860) 13- 3/8 (340)
Height in. (mm) 11-9/64 (283) 4-3/32 (104) 34- 31/32 (888) Width in. (mm) 32-7/8 (835) 37-61/64 (964) 39- 31/32 (1,015) Depth in. (mm) 33-9/32 (845) 39-21/64 (999) 16- 3/32 (409)
dB - A 38 / 35 / 31
Indoor unit (Include panel) Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-9
6
SM831148
1-1 Unit Specifications
4-Way Air Discharge Semi-Concealed Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 32,600 [9,500~32,600] 37,600 [8,000~37,600]
Moisture removal (High) Pints / h 10.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.6 9.1
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253 Max. Running amperes* A 18.7 20.7 15.9 17.6 Power input W 3,950 3,950 3,350 3,350
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 14-31/64 (368) 30- 23/32 (780)
Package dimensions Body Panel Outdoor unit
Net weight lbs. (kg) 60 (27) 16 (7) 143 (65) Shipping weight lbs. (kg) 71 (32) 22 (10) 161 (73) Shipping volume cu.ft. (m 3 ) 10.6 (0.299) 4.6 (0.131) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit XH3672R
Outdoor Unit CH3672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 20,000
in. WG
(17˚F)** W 2,450 2,450
A 15 / 35
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 45-9/32 (1,150) 37 (940) Depth in. (mm) 33-55/64 (860) 13- 3/8 (340)
Height in. (mm) 12-13/32 (315) 4-3/32 (104) 34- 31/32 (888) Width in. (mm) 44-19/64 (1,125) 49-31/64 (1,257) 39- 31/32 (1,015) Depth in. (mm) 33-9/32 (845) 39-21/64 (999) 16- 3/32 (409)
dB - A 44 / 37 / 33
Indoor unit (Include panel) Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-10
1-1 Unit Specifications
4-Way Air Discharge Semi-Concealed Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 39,500 [9,500~39,500] 48,000 [8,000~48,000]
Moisture removal (High) Pints / h 12.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.6 10.4
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253 Max. Running amperes* A 23.0 25.4 22.4 24.8 Power input W 4,520 4,520 4,360 4,360
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 7.94 (3.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 14-31/64 (368) 48-7/16 (1,230 )
Package dimensions Body Panel Outdoor unit
Net weight lbs. (kg) 60 (27) 16 (7) 220 (100) Shipping weight lbs. (kg) 71 (32) 22 (10) 240 (109 ) Shipping volume cu.ft. (m 3 ) 10.6 (0.299) 4.6 (0.131) 19.5 (0.552 )
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit XH4272R
Outdoor Unit CH4272R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 31,800
in. WG
(17˚F)** W 3,540 3,540
A 15 / 40
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 53
Width in. (mm) 45-9/32 (1,150) 37 (940) Depth in. (mm) 33-55/64 (860) 13- 3/8 (340)
Height in. (mm) 12-13/32 (315) 4-3/32 (104) 52-3/8 (1,330 ) Width in. (mm) 44-19/64 (1,125) 49-31/64 (1,257) 39- 31/32 (1,015) Depth in. (mm) 33-9/32 (845) 39-21/64 (999) 16- 3/32 (409)
dB - A 45 / 38 / 34
Indoor unit (Include panel) Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-11
6
SM831148
1-1 Unit Specifications
4-Way Air Discharge Semi-Concealed Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 24,800 [9,500~24,800]
Moisture removal (High) Pints / h 8.1 Air circulation (H / M / L) 230 V CFM 710 / 530 / 450 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.1
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253
Max. Running amperes*
Power input W 2,920 2,920
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller Air deflection (Horizontal / Vertical ) / Automatic (Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 13-5/16 (338) 30- 23/32 (780)
Package dimensions Body Panel Outdoor unit
Net weight lbs. (kg) 49 (22) 11 (5) 128 (58) Shipping weight lbs. (kg) 57 (26) 18 (8) 148 (67) Shipping volume cu.ft. (m 3 ) 7.1 (0.200) 3.6 (0.100) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit XH2672R
Outdoor Unit C2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
A 15.6 17.3
(17˚F)** W
A 15 / 30
RCS-SH80UG / RCS-TM80BG
RCS-SH80UA. WL / RCS-BH80UA. WL
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 33-55/64 (860) 37 (940) Depth in. (mm) 33-55/64 (860) 13- 3/8 (340)
Height in. (mm) 11-9/64 (283) 4-3/32 (104) 34- 31/32 (888) Width in. (mm) 32-7/8 (835) 37-61/64 (964) 39- 31/32 (1,015) Depth in. (mm) 33-9/32 (845) 39-21/64 (999) 16- 3/32 (409)
dB - A 38 / 35 / 31
Indoor unit (Include panel) Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-12
1-1 Unit Specifications
4-Way Air Discharge Semi-Concealed Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 32,600 [9,500~32,600]
Moisture removal (High) Pints / h 10.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.6
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253 Max. Running amperes* A 18.7 20.7 Power input W 3,950 3,950
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 14-31/64 (368) 30- 23/32 (780)
Package dimensions Body Panel Outdoor unit
Net weight lbs. (kg) 60 (27) 16 (7) 143 (65) Shipping weight lbs. (kg) 71 (32) 22 (10) 161 (73) Shipping volume cu.ft. (m 3 ) 10.6 (0.299) 4.6 (0.131) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit XH3672R
Outdoor Unit C3672R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
(17˚F)** W
A 15 / 35
Microprocessor
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 45-9/32 (1,150) 37 (940) Depth in. (mm) 33-55/64 (860) 13- 3/8 (340)
Height in. (mm) 12-13/32 (315) 4-3/32 (104) 34- 31/32 (888) Width in. (mm) 44-19/64 (1,125) 49-31/64 (1,257) 39- 31/32 (1,015) Depth in. (mm) 33-9/32 (845) 39-21/64 (999) 16- 3/32 (409)
dB - A 44 / 37 / 33
Indoor unit (Include panel) Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-13
6
SM831148
1-1 Unit Specifications
4-Way Air Discharge Semi-Concealed Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 39,500 [9,500~39,500]
Moisture removal (High) Pints / h 12.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.6
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253 Max. Running amperes* A 23.0 25.4 Power input W 4,520 4,520
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 7.94 (3.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 14-31/64 (368) 48-7/16 (1,230 )
Package dimensions Body Panel Outdoor unit
Net weight lbs. (kg) 60 (27) 16 (7) 220 (100) Shipping weight lbs. (kg) 71 (32) 22 (10) 240 (109 ) Shipping volume cu.ft. (m 3 ) 10.6 (0.299) 4.6 (0.131) 19.5 (0.552 )
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit XH4272R
Outdoor Unit C4272R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
(17˚F)** W
A 15 / 40
Microprocessor
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 53
Width in. (mm) 45-9/32 (1,150) 37 (940) Depth in. (mm) 33-55/64 (860) 13- 3/8 (340)
Height in. (mm) 12-13/32 (315) 4-3/32 (104) 52-3/8 (1,330 ) Width in. (mm) 44-19/64 (1,125) 49-31/64 (1,257) 39- 31/32 (1,015) Depth in. (mm) 33-9/32 (845) 39-21/64 (999) 16- 3/32 (409)
dB - A 45 / 38 / 34
Indoor unit (Include panel) Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-14
1-1 Unit Specifications
Concealed-Duct Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 24,000 [9,500~24,000] 28,600 [8,000~28,600]
Moisture removal (High) Pints / h 7.7 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.0 9.7
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253
Max. Running amperes*
Power input W 2,600 2,600 2,400 2,400
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 12-7/32 (310) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 71 (32) 128 (58) Shipping weight lbs. (kg) 82 (37) 148 (67) Shipping volume cu.ft. (m 3 ) 11.8 (0.334) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit UH2672R
Outdoor Unit CH2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 17,100
in.WG
A 13.6 15.0 12.5 13.8
(17˚F)** W 1,980 1,980
A 15 / 30
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 39-3/8 (1,000) 37 (940) Depth in. (mm) 24-13/16 (630) 13- 3/8 (340)
Height in. (mm) 14-3/32 (358) 34- 31/32 (888) Width in. (mm) 46-7/8 (1,191) 39- 31/32 (1,015) Depth in. (mm) 30-13/16 (783) 16- 3/32 (409)
dB - A 34 / 30 / 27
0.2:at shipment / 0.4:using jumper cable
RCS-SH80UG / RCS-TM80BG
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-15
6
SM831148
1-1 Unit Specifications
Concealed-Duct Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200] 36,200 [8,000~36,200]
Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 13.9 8.7
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253 Max. Running amperes* A 18.6 20.6 15.9 17.6 Power input W 3,920 3,920 3,340 3,340
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 12-7/32 (310) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 104 (47) 143 (65) Shipping weight lbs. (kg) 115 (52) 161 (73) Shipping volume cu.ft. (m 3 ) 16.5 0.468) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit UH3672R
Outdoor Unit CH3672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 20,200
in. WG
(17˚F)** W 2,570 2,570
A 15 / 35
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 58-9/32 (1,480) 37 (940) Depth in. (mm) 24-13/16 (630) 13- 3/8 (340)
Height in. (mm) 14-3/32 (358) 34- 31/32 (888) Width in. (mm) 65-25/32 (1,671) 39- 31/32 (1,015) Depth in. (mm) 30-13/16 (783) 16- 3/32 (409)
dB - A 38 / 33 / 31
0.24:at shipment / 0.4:using jumper cable
RCS-SH80UG / RCS-TM80BG
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-16
1-1 Unit Specifications
Concealed-Duct Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 24,000 [9,500~24,000]
Moisture removal (High) Pints / h 7.7 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.0
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253
Max. Running amperes*
Power input W 2,600 2,600
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 12-7/32 (310) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 71 (32) 128 (58) Shipping weight lbs. (kg) 82 (37) 148 (67) Shipping volume cu.ft. (m 3 ) 11.8 (0.334) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit UH2672R
Outdoor Unit C2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
A 13.6 15.0
(17˚F)** W
A 15 / 30
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 39-3/8 (1,000) 37 (940) Depth in. (mm) 24-13/16 (630) 13- 3/8 (340)
Height in. (mm) 14-3/32 (358) 34- 31/32 (888) Width in. (mm) 46-7/8 (1,191) 39- 31/32 (1,015) Depth in. (mm) 30-13/16 (783) 16- 3/32 (409)
dB - A 34 / 30 / 27
0.2:at shipment / 0.4:using jumper cable
RCS-SH80UG / RCS-TM80BG
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
— —
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-17
6
SM831148
1-1 Unit Specifications
Concealed-Duct Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200]
Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 13.9
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253 Max. Running amperes* A 18.6 20.6 Power input W 3,920 3,920
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH1UA / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Drain pump (Drain connection) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 12-7/32 (310) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 104 (47) 143 (65) Shipping weight lbs. (kg) 115 (52) 161 (73) Shipping volume cu.ft. (m 3 ) 16.5 0.468) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit UH3672R
Outdoor Unit C3672R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
(17˚F)** W
A 15 / 35
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 58-9/32 (1,480) 37 (940) Depth in. (mm) 24-13/16 (630) 13- 3/8 (340)
Height in. (mm) 14-3/32 (358) 34- 31/32 (888) Width in. (mm) 65-25/32 (1,671) 39- 31/32 (1,015) Depth in. (mm) 30-13/16 (783) 16- 3/32 (409)
dB - A 38 / 33 / 31
0.24:at shipment / 0.4:using jumper cable
RCS-SH80UG / RCS-TM80BG
Max.head 2-33/64 in. above drain connection (25A , OD32mm)
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
— —
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-18
1-1 Unit Specifications
Ceiling-Mounted Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 24,400 [9,500~24,400] 30,800 [8,000~30,800]
Moisture removal (High) Pints / h 7.7 Air circulation (H / M / L) 230 V CFM 550 / 490 / 460 External Static Pressure in. WG S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.5 10.3
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253
Max. Running amperes* (Without Back-up Heater)
Power input W 2,880 2,880 3,000 3,000
Back-up Heater kW 1.8 1.47
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 7-17/32 (190) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 64 (29) 128 (58) Shipping weight lbs. (kg) 75 (34) 148 (67) Shipping volume cu.ft. (m 3 ) 8.9 (0.253) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit THH2672R
Outdoor Unit CH2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 17,900
A 15.6 17.3 16.4 18.1
(17˚F)** W 2,190 2,190
A 15 / 30
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 51-3/16 (1,300) 37 (940) Depth in. (mm) 26-3/8 (670) 13- 3/8 (340)
Height in. (mm) 9-7/16 (240) 34- 31/32 (888) Width in. (mm) 54-19/32 (1,387) 39- 31/32 (1,015) Depth in. (mm) 31-1/16 (789) 16- 3/32 (409)
dB - A 39 / 37 / 33
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-19
6
SM831148
1-1 Unit Specifications
Ceiling-Mounted Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 24,400 [9,500~24,400] 30,800 [8,000~30,800]
Moisture removal (High) Pints / h 7.7 Air circulation (H / M / L) 230 V CFM 550 / 490 / 460 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.5 10.3
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253
Max. Running amperes* (Without Back-up Heater)
Power input W 2,880 2,880 3,000 3,000
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 7-17/32 (190) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 57 (26) 128 (58) Shipping weight lbs. (kg) 68 (31) 148 (67) Shipping volume cu.ft. (m 3 ) 8.9 (0.253) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit TH2672R
Outdoor Unit CH2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 17,900
in. WG
A 15.6 17.3 16.4 18.1
(17˚F)** W 2,190 2,190
A 15 / 30
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 51-3/16 (1,300) 37 (940) Depth in. (mm) 26-3/8 (670) 13- 3/8 (340)
Height in. (mm) 9-7/16 (240) 34- 31/32 (888) Width in. (mm) 54-19/32 (1,387) 39- 31/32 (1,015) Depth in. (mm) 31-1/16 (789) 16- 3/32 (409)
dB - A 39 / 37 / 33
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-20
1-1 Unit Specifications
Ceiling-Mounted Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200] 37,400 [8,000~37,400]
Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 1100 / 930 / 750 External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.1 9.6
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253 Max. Running amperes* A 18.2 20.1 15.6 17.3 Power input W 3,840 3,840 3,250 3,250
Back-up Heater kW 2.4 1.95
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 9-7/16 (240) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 90 (41) 143 (65) Shipping weight lbs. (kg) 104 (47) 161 (73) Shipping volume cu.ft. (m 3 ) 14.8 (0.420) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit THH3672R
Outdoor Unit CH3672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 21,000
in. WG
(17˚F)** W 2,470 2,470
A 15 / 35
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 62-1/32 (1,575) 37 (940) Depth in. (mm) 26-3/8 (670) 13- 3/8 (340)
Height in. (mm) 12-15/32 (317) 34- 31/32 (888) Width in. (mm) 66-1/16 (1,678) 39- 31/32 (1,015) Depth in. (mm) 31-1/16 (789) 16- 3/32 (409)
dB - A 42 / 40 / 35
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-21
6
SM831148
1-1 Unit Specifications
Ceiling-Mounted Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200] 37,400 [8,000~37,400]
Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 1100 / 930 / 750 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.1 9.6
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253 Max. Running amperes* A 18.2 20.1 15.6 17.3 Power input W 3,840 3,840 3,250 3,250
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 9-7/16 (240) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 84 (38) 143 (65) Shipping weight lbs. (kg) 97 (44) 161 (73) Shipping volume cu.ft. (m 3 ) 14.8 (0.420) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit TH3672R
Outdoor Unit CH3672R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 21,000
in. WG
(17˚F)** W 2,470 2,470
A 15 / 35
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 62-1/32 (1,575) 37 (940) Depth in. (mm) 26-3/8 (670) 13- 3/8 (340)
Height in. (mm) 12-15/32 (317) 34- 31/32 (888) Width in. (mm) 66-1/16 (1,678) 39- 31/32 (1,015) Depth in. (mm) 31-1/16 (789) 16- 3/32 (409)
dB - A 42 / 40 / 35
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-22
1-1 Unit Specifications
Ceiling-Mounted Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 39,000 [9,500~39,000] 44,500 [8,000~44,500]
Moisture removal (High) Pints / h 12.6 Air circulation (H / M / L) 230 V CFM 1100 / 930 / 750 External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.6 10.2
ELECTRICAL RATINGS Voltage rating V 230 208 230 208 Available voltage range V VAC 187 - 253 VAC 187 - 253 Max. Running amperes* A 21.1 23.3 18.6 20.6 Power input W 4,140 4,140 3,630 3,630
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 7.94 (3.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 9-7/16 (240) 48-7/16 (1,230 )
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 84 (38) 220 (100) Shipping weight lbs. (kg) 97 (44) 240 (109 ) Shipping volume cu.ft. (m 3 ) 14.8 (0.420) 19.5 (0.552 )
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit TH4272R
Outdoor Unit CH4272R
230 - 208 V / 1 Phase / 60 Hz
Cooling Heating
(17˚F)** BTU / h 28,800
in. WG
(17˚F)** W 3,110 3,110
A 15 / 40
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 53
Width in. (mm) 62-1/32 (1,575) 37 (940) Depth in. (mm) 26-3/8 (670) 13- 3/8 (340)
Height in. (mm) 12-15/32 (317) 52-3/8 (1,330 ) Width in. (mm) 66-1/16 (1,678) 39- 31/32 (1,015) Depth in. (mm) 31-1/16 (789) 16- 3/32 (409)
dB - A 44 / 41 / 37
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-23
6
SM831148
1-1 Unit Specifications
Ceiling-Mounted Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 24,400 [9,500~24,400]
Moisture removal (High) Pints / h 7.7 Air circulation (H / M / L) 230 V CFM 550 / 490 / 460 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.5
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253
Max. Running amperes* (Without Back-up Heater)
Power input W 2,880 2,880
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 7-17/32 (190) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 57 (26) 128 (58) Shipping weight lbs. (kg) 68 (31) 148 (67) Shipping volume cu.ft. (m 3 ) 8.9 (0.253) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit TH2672R
Outdoor Unit C2672R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
A 15.6 17.3
(17˚F)** W
A 15 / 30
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 49
Width in. (mm) 51-3/16 (1,300) 37 (940) Depth in. (mm) 26-3/8 (670) 13- 3/8 (340)
Height in. (mm) 9-7/16 (240) 34- 31/32 (888) Width in. (mm) 54-19/32 (1,387) 39- 31/32 (1,015) Depth in. (mm) 31-1/16 (789) 16- 3/32 (409)
dB - A 39 / 37 / 33
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-24
1-1 Unit Specifications
Ceiling-Mounted Type
1. Specifications
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200]
Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 1100 / 930 / 750 External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.1
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253 Max. Running amperes* A 18.2 20.1 Power input W 3,840 3,840
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 9-7/16 (240) 30- 23/32 (780)
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 84 (38) 143 (65) Shipping weight lbs. (kg) 97 (44) 161 (73) Shipping volume cu.ft. (m 3 ) 14.8 (0.420) 13.0 (0.369)
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit TH3672R
Outdoor Unit C3672R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
(17˚F)** W
A 15 / 35
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 52
Width in. (mm) 62-1/32 (1,575) 37 (940) Depth in. (mm) 26-3/8 (670) 13- 3/8 (340)
Height in. (mm) 12-15/32 (317) 34- 31/32 (888) Width in. (mm) 66-1/16 (1,678) 39- 31/32 (1,015) Depth in. (mm) 31-1/16 (789) 16- 3/32 (409)
dB - A 42 / 40 / 35
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
1
2
3
4
5
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
I-25
6
SM831148
1-1 Unit Specifications
Ceiling-Mounted Type
1. Specifications
1
2
3
4
5
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity * [minimum~muximum] BTU / h 39,000 [9,500~39,000]
Moisture removal (High) Pints / h 12.6 Air circulation (H / M / L) 230 V CFM 1100 / 930 / 750 External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 15.6
ELECTRICAL RATINGS Voltage rating V 230 208 Available voltage range V VAC 187 - 253 Max. Running amperes* A 21.1 23.3 Power input W 4,140 4,140
Back-up Heater kW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls Microprocessor Low ambient control Built-in 0˚F Fan speeds Indoor / Outdoor 3 and Automatic control / Variable Optional Wired Remote Controller Optional Wireless Remote Controller RCS-SH80UA. WL / RCS-BH80UA. WL Air deflection (Horizontal / Vertical ) Air filter Washable, long life (2,500 hr) Drain pump (Drain connection) (20A , OD26mm) Compressor Rotary(SANYO) Operation sound
Refrigerant control Electronic Expansion Valve (MOV)
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 10~100 (3~30) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit : 100 (30) between the two units ft. (m) Outdoor unit is lower than indoor unit : 50 (15) Refrigerant tube Narrow tube in. (mm) 3 / 8 (6.35) outer diameter Wide tube in. (mm) 5 / 8 (15.88) Refrigerant amount at shipment lbs. (kg) 7.94 (3.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensions Height in. (mm) 9-7/16 (240) 48-7/16 (1,230 )
Package dimensions Indoor unit Outdoor unit
Net weight lbs. (kg) 84 (38) 220 (100) Shipping weight lbs. (kg) 97 (44) 240 (109 ) Shipping volume cu.ft. (m 3 ) 14.8 (0.420) 19.5 (0.552 )
Cooling:
Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB
Indoor Unit TH4272R
Outdoor Unit C4272R
230 - 208 V / 1 Phase / 60 Hz
Cooling
(17˚F)** BTU / h
in. WG
(17˚F)**
Indoor - Hi/Me/Lo
Outdoor - Hi dB - A 53
Width in. (mm) 62-1/32 (1,575) 37 (940) Depth in. (mm) 26-3/8 (670) 13- 3/8 (340)
Height in. (mm) 12-15/32 (317) 52-3/8 (1,330 ) Width in. (mm) 66-1/16 (1,678) 39- 31/32 (1,015) Depth in. (mm) 31-1/16 (789) 16- 3/32 (409)
W
A 15 / 40
RCS-SH80UG / RCS-TM80BG
/ Automatic (Vertical )
dB - A 44 / 41 / 37
Indoor unit Outdoor unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Heating:
Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB
SM831148
I-26