This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
For safe installation and trouble-free operation, you must :
● Carefully read this instruction booklet before beginning.
● Follow each installation or repair step exactly as shown.
● Observe all local, state, and national electrical codes.
● Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
CAUTION
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites
and maintenance conditions. If you require help for a special
problem, contact our sales/service outlet or your certified
dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow
the instructions in this document.
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
●
Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked.
●
Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions
when wiring. Improper connections and inadequate
grounding can cause accidentaly injury or death.
●
Ground the unit following local electrical codes.
●
Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum
fins on the air conditioner can cut your fingers.
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to walls
and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents water
damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys-tems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.
Ventilate the room well, in the event that refrigerant gas
leaks during the installation. Be careful not to allow contact
of the refrigerant gas with a flame as this will cause the
generation of poisonous gas.
●
Keep all tubing runs as short as possible.
●
Use the flare method for connecting tubing.
●
Apply refrigerant lubricant to the matching surfaces of the
flare and union tubes before connecting them, then tighten
the nut with a torque wrench for a leak-free connection.
●
Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be
either narrow or wide. Therefore, to avoid confusion the
refrigerant tubing for your particular model is specified as either
“narrow” or “wide” rather than as “liquid” or “gas”.
Turn the power OFF at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
●
Keep your fingers and clothing away from any moving parts.
●
Clean up the site when installation is finished. Check that no
metal scraps or bits of wiring have been left inside the unit.
CAUTION
●
Ventilate any enclosed areas when installing or testing the
refrigeration system. Contact of refrigerant gas with fire or
heat can produce poisonous gas.
●
Confirm after installation that no refrigerant gas is leaking. If
the gas comes in contact with a burning stove, gas water
heater, electric room heater or other heat source, it can
cause the generation of poisonous gas.
Moisture removal (High) Pints / h7.4
Air circulation (H / M / L) 230 V CFM540 / 460 / 380
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh15.910.3
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes* (Without Back-up Heater)
Power inputW2,6102,6102,7202,720
Back-up HeaterkW1.81.47
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-SH1UA / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filterWashable
Drain pump (Drain connection) (20A , OD26mm)
CompressorRotary(SANYO)
Operation sound
Refrigerant control
REFRIGERANT TUBING
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)14- 9/16 (370)30- 23/32 (780)
Moisture removal (High) Pints / h8.1
Air circulation (H / M / L) 230 V CFM559 / 475 / 390
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh14.910.2
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes*
Power inputW2,8402,8402,6202,620
Back-up HeaterkW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
ControlsMicroprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-SH1UA / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filterWashable
Drain pump (Drain connection) (20A , OD26mm)
CompressorRotary(SANYO)
Operation sound
Refrigerant control
REFRIGERANT TUBING
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)12- 63/64 (330)30- 23/32 (780)
Moisture removal (High) Pints / h9.7
Air circulation (H / M / L) 230 V CFM840 / 740 / 620
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh15.09.0
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes*A17.719.616.217.9
Power inputW3,6903,6903,3903,390
Back-up HeaterkW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
ControlsMicroprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-SH1UA / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filterWashable
Drain pump (Drain connection) (20A , OD26mm)
CompressorRotary(SANYO)
Operation sound
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 5.73 (2.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)14- 9/16 (370)30- 23/32 (780)
Moisture removal (High) Pints / h10.0
Air circulation (H / M / L) 230 V CFM830 / 710 / 590
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh15.99.0
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes*A17.919.815.917.6
Power inputW3,7503,7503,3203,320
Back-up HeaterkW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
ControlsMicroprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-SH1UA / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filterWashable
Drain pump (Drain connection) (20A , OD26mm)
CompressorRotary(SANYO)
Operation sound
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)14- 9/16 (370)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)12- 63/64 (330)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 5.73 (2.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)14- 9/16 (370)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)14- 9/16 (370)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)13-5/16 (338)30- 23/32 (780)
Moisture removal (High) Pints / h10.6
Air circulation (H / M / L) 230 V CFM1050 / 840 / 720
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh14.69.1
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes*A18.720.715.917.6
Power inputW3,9503,9503,3503,350
Back-up HeaterkW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
ControlsMicroprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-SH80UA. WL / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filterWashable, long life (2,500 hr)
Drain pump (Drain connection)
CompressorRotary(SANYO)
Operation sound
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)14-31/64 (368)30- 23/32 (780)
Moisture removal (High) Pints / h12.6
Air circulation (H / M / L) 230 V CFM1050 / 840 / 720
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh14.610.4
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes*A23.025.422.424.8
Power inputW4,5204,5204,3604,360
Back-up HeaterkW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
ControlsMicroprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-SH80UA. WL / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filterWashable, long life (2,500 hr)
Drain pump (Drain connection)
CompressorRotary(SANYO)
Operation sound
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 7.94 (3.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)14-31/64 (368)48-7/16 (1,230 )
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)13-5/16 (338)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)14-31/64 (368)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 7.94 (3.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)14-31/64 (368)48-7/16 (1,230 )
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)12-7/32 (310)30- 23/32 (780)
Moisture removal (High) Pints / h10.0
Air circulation (H / M / L) 230 V CFM670 / 530 / 460
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh13.98.7
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes*A18.620.615.917.6
Power inputW3,9203,9203,3403,340
Back-up HeaterkW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
ControlsMicroprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filter
Drain pump (Drain connection)
CompressorRotary(SANYO)
Operation sound
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)12-7/32 (310)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)12-7/32 (310)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)12-7/32 (310)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)7-17/32 (190)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)7-17/32 (190)30- 23/32 (780)
Moisture removal (High) Pints / h10.0
Air circulation (H / M / L) 230 V CFM1100 / 930 / 750
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh15.19.6
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes*A18.220.115.617.3
Power inputW3,8403,8403,2503,250
Back-up HeaterkW2.41.95
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
Controls MicroprocessorMicroprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-SH80UA. WL / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filterWashable, long life (2,500 hr)
Drain pump (Drain connection) (20A , OD26mm)
CompressorRotary(SANYO)
Operation sound
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)9-7/16 (240)30- 23/32 (780)
Moisture removal (High) Pints / h10.0
Air circulation (H / M / L) 230 V CFM1100 / 930 / 750
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh15.19.6
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes*A18.220.115.617.3
Power inputW3,8403,8403,2503,250
Back-up HeaterkW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
ControlsMicroprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-SH80UA. WL / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filterWashable, long life (2,500 hr)
Drain pump (Drain connection) (20A , OD26mm)
CompressorRotary(SANYO)
Operation sound
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)9-7/16 (240)30- 23/32 (780)
Moisture removal (High) Pints / h12.6
Air circulation (H / M / L) 230 V CFM1100 / 930 / 750
External Static Pressure
S.E.E.R. / H.S.P.F. (Region 4)BTU / Wh15.610.2
ELECTRICAL RATINGS
Voltage ratingV230208230208
Available voltage rangeVVAC 187 - 253VAC 187 - 253
Max. Running amperes*A21.123.318.620.6
Power inputW4,1404,1403,6303,630
Back-up HeaterkW
Maximum overcurrent protection (Indoor/Outdoor)
FEATURES
ControlsMicroprocessor
Low ambient control Built-in 0˚F
Fan speeds Indoor / Outdoor3 and Automatic control / Variable
Optional Wired Remote Controller
Optional Wireless Remote ControllerRCS-SH80UA. WL / RCS-BH80UA. WL
Air deflection (Horizontal / Vertical )
Air filterWashable, long life (2,500 hr)
Drain pump (Drain connection) (20A , OD26mm)
CompressorRotary(SANYO)
Operation sound
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 7.94 (3.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)9-7/16 (240)48-7/16 (1,230 )
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 4.19 (1.9) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)7-17/32 (190)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 6.17 (2.8) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)9-7/16 (240)30- 23/32 (780)
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)10~100 (3~30)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit : 100 (30)
between the two unitsft. (m)Outdoor unit is lower than indoor unit : 50 (15)
Refrigerant tubeNarrow tubein. (mm) 3 / 8 (6.35)
outer diameterWide tubein. (mm) 5 / 8 (15.88)
Refrigerant amount at shipmentlbs. (kg) 7.94 (3.6) - R410A
DIMENSIONS & WEIGHT
Unit dimensionsHeightin. (mm)9-7/16 (240)48-7/16 (1,230 )