Sanyo KH2442, XH4242, KH3642, CH4242, UH2442 User Manual

...
INSTALLATION INSTRUCTION
— Split System Heat Pump Air Conditioner —
11
1
11
X
Model Combinations
Combine indoor and outdoor units only as listed below.
Indoor Units and Outdoor Units
Indoor Units Type
4-Way Air Discharge
11
1
11
Semi-Concealed
X
(Matching Ceiling Panel)
22
2
22
Wall-Mounted
K
33
3
33
T
44
4
44
Concealed-Duct
U
55
5
55
Outdoor Units
C
66
6
66
Wired Remote Controller
77
7
77
Wireless Remote Controller
Weekly Timer
88
8
88
99
9
99
System Controller
24
XH2442
(PNR-XH2442)
KH2442
TH2442
UH2442
CH2442
Built-in type: RCS-SH80UA.WL (Optional part ) External type: RCS-BH80UA.WL (Optional part )
36
XH3642
(PNR-XH3642)
KH3642
TH3642
UH3642
CH3642
RCS-SH80UG (Optional part )
TM-SH80UG (Optional part )
SHA-KC64UG (Optional part )
42
XH4242
(PNR-XH3642)
TH4242
CH4242
22
2
22
K
33
3
33
T
44
4
44
U
55
5
55
C
66
6
66
RC
(WD)
77
7
77
RC
(WL)
88
8
88
85464359146001 © SANYO 2001
OPERATING LIMITS
Maximum Conditions Cooling / Heating Outdoor temperature : 115°F DB / 65°F WB Room temperature : 71°F WB / 80°F DB
Minimum Conditions Outdoor temperature : 23°F (0°F)* DB / 15°F WB Room temperature : 57°F WB / 59°F DB
* When air discharge chamber is installed.
Units should be installed by licensed contractor according to local code requirements.
SANYO FISHER COMPANY
A DIVISION OF SANYO NORTH AMERICA CORPORATION 21605 Plummer Street Chatsworth, CA91311
In Canada
SANYO Canada Inc.
300 Applewood Crescent Concord, Ontario L4K 5C7, Canada
WT
99
9
99
SC
Important
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must :
Carefully read this instruction booklet before beginning.Follow each installation or repair step exactly as shown.Observe all local, state, and national electrical codes.Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a
CAUTION
hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
……………………………………………………………………
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidentaly injury or death.
Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
…………………………………………………………………… Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
……………………………………………………………………
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys­tems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
……………………………………………………………………
• Ventilate the room well, in the event that refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either “narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
……………………………………………………………………
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site when installation is finished. Check that no metal scraps or bits of wiring have been left inside the unit.
CAUTION
• Ventilate any enclosed areas when installing or testing the refrigeration system. Contact of refrigerant gas with fire or heat can produce poisonous gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
i
CONTENTS
Page
IMPORTANT Please Read Before Starting
1. GENERAL ................................................................... 4
1-1. Tools Required for Installation (Not Supplied) 1-2. Accessories Supplied with Unit 1-3. Type of Copper Tube and Insulation Material 1-4. Additional Materials Required for Installation 1-5. Tubing Length
2. SELECTING THE INSTALLATION SITE .................. 10
Indoor Unit Outdoor Unit
2-1. Air Discharge Chamber for Top Discharge 2-2. Installing the Outdoor Unit in Heavy Snow Areas 2-3. Precautions When Installing in Heavy Snow Areas 2-4. Dimensions of Snow / Wind-proof Ducting and
Refrigerant Tubing Space for Installation
3. HOW TO INSTALL THE INDOOR UNIT.................... 14
4-Way Air Discharge Semi-Concealed Type
(XH Type)................................................................... 14
3-1. Suspending the Indoor Unit 3-2. Preparation for Suspending 3-3. Placing the Unit Inside the Ceiling 3-4. Installing the Drain Piping 3-5. Checking the Drainage 3-6. Before Installing the Ceiling Panel 3-7. Installing the Ceiling Panel 3-8. When Removing the Ceiling Panel for Servicing 3-9. Duct for Fresh Air
Wall-Mounted Type (KH Type) ................................... 22
3-10. Removing the Wall Fixture from the Unit 3-11. Selecting and Making a Hole 3-12. Installing the Wall Fixture onto Wooden or
Gypsum Wall
3-13.
Removing the Casing to Install the Indoor Unit 3-14. Preparing the Indoor Side Tubing 3-15. Wiring Instructions 3-16.
Wiring Instructions for Inter-Unit Connections 3-17. Shaping the Tubing 3-18. Installing the Drain Hose
Ceiling-Mounted T ype (TH Type). .............................. 31
3-19. Suspending the Indoor Unit 3-20. Duct for Fresh Air 3-21. Installing the Drain Piping
Concealed-Duct T ype (UH Type) ............................... 35
3-22.
Required Minimum Space for Installation and Service 3-23. Suspending the Indoor Unit 3-24. Installing the Drain Piping
Page
3-25. Checking the Drainage 3-26. Increasing the Fan Speed
4. HOW TO INSTALL THE OUTDOOR UNIT ................ 40
4-1. Removing the Protective Spacer for Transportation 4-2. Installing the Outdoor Unit 4-3. Tubing Direction
5. ELECTRICAL WIRING ............................................. 41
5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Wire Diameter
for Power Supply System 5-3. Wiring System Diagrams 5-4. How to Connect Wiring to the Terminal
6.
HOW TO INSTALL THE WIRED REMOTE CONTROLLER
(OPTIONAL PART) .................................................... 45
6-1. Installation site selection 6-2. Wired Remote Controller Installation 6-3. Basic Wiring Diagram 6-4. Wiring System Diagram for Group Control 6-5. Wiring System Diagram for Multiple Remote
Control 6-6. How to Switch the Indoor Temperature Sensor 6-7. Explanation of Alarm Messages
7.
HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER
(OPTIONAL PART) .................................................... 52
7-1. Wireless Remote Controller Installation 7-2. Room Temperature Sensor Setting 7-3. Address Switches 7-4. Setting the Model Code <RCS-SH80UA. WL>
4-Way Air Discharge Semi-concealed Type
(XH Type)................................................................... 54
7-5. Indicator section Installation 7-6. Operating Controller Installation
Ceiling Mounted Type (TH Type)......................... 55
7-7. Indicator Section Installation 7-8. Operating Controller Installation 7-9. Electrical Wiring 7-10. Test Run Switch 7-11. Misoperation Alarm Indicators
<RCS-BH80UA.WA>
7-12.
Separate type Signal Receiving Unit Installation 7-13. Electrical Wiring 7-14. Test Run Switch 7-15. Misoperation Alarm Indicators 7-16. Basic Wiring Diagram 7-17. Wiring System Diagram for Group Control 7-18. Wiring System Diagram for Multiple
8. HOW TO INSTALL THE WEEKL Y TIMER
(OPTIONAL PART) ................................................... 65
8-1. Mounting Dimensions for Continuous Installation 8-2. When Using a Wall Box for Flush Mounting 8-3. Wiring Diagram 8-4. Test Run Setting 8-5. Memory Back Up Function for Power Failure
Compensation
9. HOW TO INSTALL THE SYSTEM CONTROLLER
(OPTIONAL PART) ................................................... 67
9-1. System Controller Installation 9-2. Electrical Wiring 9-3. Address Switch Setting 9-4. Mode Setting 9-5. How to Perform Zone Registration 9-6. Connection with Other Equipments 9-7. Memory Back Up Switch 9-8. Test Run
Page
10. HOW TO PROCESS TUBING .................................. 79
10-1. Use of the Flaring Method 10-2. Flaring Procedure with a Flare Tool 10-3. Precaution before Connecting Tubes Tightly 10-4. Precautions during Brazing 10-5. Connecting Tubing between Indoor and Outdoor
Units 10-6. Insulating the Refrigerant Tubing 10-7. Taping the Tubes 10-8. Finishing the Installation
11. AIR PURGING .......................................................... 82
12. TEST RUN ................................................................ 85
12-1. Preparing for Test Run 12-2. PCB Setting 12-3. R.C. Address Setting Method 12-4. Automatic Address Setting Method 12-5. Displaying Indoor / Outdoor Unit Combination
Numbers 12-6. Test Run Procedure 12-7. Items to Check Prior to Test Run 12-8. The Main Alarms of Mis-wiring & Mis-setting 12-9. The Main Alarms of Unit Troubles 12-10
. The Main Alarms of Power Supply Troubles
13. PUMP DOWN............................................................ 93
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
Check local electrical codes
CAUTION
and regulations before obtaining wire. Also, check any specified instructions or limitations.
1-4. Additional Materials Required for Installation
1-1. Tools Required for Installation (Not Supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
See Table 1-1 to 1-9.
Table Type
1-1 4-Way Air Discharge Semi-Concealed 1-2 Wall-Mounted 1-3 Ceiling-Mounted 1-4 Concealed-Duct 1-5 Outdoor Unit 1-6 Wired Remote Controller 1-7 Wireless Remote Controller 1-8 Weekly Timer 1-9 System Controller
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
1-3. Type of Copper Tube and Insulation Material
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or A/C workshop.
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2.
Foamed polyethylene insulation for copper tubes as required to precise length of tubing. Wall thick­ness of the insulation should be not less than 5/16 in..
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to Section 5. “Electrical Wiring” for details.
S4359146
4
Table 1-1 XH (4-Way Air Discharge Semi-Concealed)
Part Name Figure
Full-scale installation diagram 1 Flare insulator 2 Washer 8 Insulating tape 1 Hose band 2 Packing 1 Drain insulator 1 Drain hose 1 Drain hose adaptor 1 Sealing putty 1
Tube connector 1
Table 1-2 KH (Wall-Mounted)
Part Name Figure Q’ty Remarks
(White)
Q’ty
For determining suspension bolt pitch For wide and narrow tubes For suspending indoor unit from ceiling
For wide tube flare nuts For securing drain hose For drain joint For drain joint
For drain outlet For sealing recessed portion of power supply For sizing up of narrow tube from 1/4 in. to 3/8 in.
(only for 24 type)
Remarks
11
1
11
X
22
2
22
K
33
3
33
T
44
4
44
U
55
5
55
C
Wall fixture *1 1
Insulator *1 1
Mounting plate *1 1
Truss-head
Tapping screw *1 20
Full-scale diagram 1
Wall fixture *2 1
Rawl plug *2 10
Cover *2 1
Tapping screw *2 10
Insulator 1
Phillips 4 × 1 in.
Truss-head Phillips 4 × 5/8 in.
For supporting the indoor unit
For insulation of the tubing of the indoor unit
For securing the indoor unit
For fixing the wall fixture
For determining the place where the indoor unit is installed
For supporting the indoor unit
For fixing the wall fixture
For improved tubing appearance
For fixing the wall fixture
For insulation of the tubing of the indoor unit
66
6
66
RC
(WD)
77
7
77
RC
(WL)
88
8
88
WT
99
9
99
SC
Tube connector 1
* 1 KH3642 only * 2 KH2442 only
For sizing up of narrow tube from 1/4 in. to 3/8 in. (only for 24 type)
S4359146
5
Table 1-3 TH (Ceiling-Mounted)
Part Name Figure Q’ty Remarks
Special washer
For temporarily suspending
4
indoor unit from ceiling
Drain insulator 1 Flare insulator
T5
T3
1 Set
Drain hose adaptor 1 Drain hose clamp 4
Insulating tape
Black
White (heat-resisting)
Vinyl clamp 2 Full-scale installation
diagram Sealing putty 1
Drain hose 1 Tube connector 1
Table1-4 UH (Concealed-Duct)
Part Name Figure
Flare insulator 2
(Black)
Insulating tape
(White)
For drain hose joint For wide tube joints
2
For wide tube and drain hose joint
1
For wide flare joints For ends of flare insulator
For determining suspension
1
bolt pitch For sealing recessed portion of power supply
For sizing up of narrow tube from 1/4 in. to 3/8 in. (only for 24 type)
Q’ty
Remarks
For wide and narrow tubes 2 2
For wide and narrow tubes
For wide and narrow tube flare nuts
Tapping screw TOTA4-10
14 or 20 or 24 Jumper cable* 1 Hose band 1 Packing 1 Sealing putty 1 Drain insulator 1 Drain hose 1 Drain hose adaptor 1 Clamp 9
Tube connector 1
* Jumper cable is housed inside the electrical component box.
Table 1-5 (Outdoor Unit)
Part Name Figure
Hexagonal Wrench 1
Grommet 1
Bushing 1
Q’ty
To open and shut the Narrow Tube Service Valve For protecting refrigerant pipe by attaching to the
edge of Tubing Outlet For protecting inter-unit control line by attaching to the edge of wiring outlet
Installation Instruction 1
For air intake duct connection For increasing the fan speed For securing drain hose For drain joint For sealing recessed portion of power supply For drain joint
For securing drain hose & refrigerant tubing For sizing up of narrow tube from 1/4 in. to 3/8 in.
(only for 24 type)
Remarks
Owner’s manual 1
S4359146
6
Table 1-6 (Accessories for the Wired Remote Controller)
Part Name Figure
Wired remote controller (comes with 7-7/8 in. wire)
Machine screws M4 × 1 in.
Wood screws 2
Table 1-7 (Accessories for the Wireless Remote Controller) <RCS-SH80UA.WL>
Part Name Figure
Operation controller 1 Spacers 2
Run Timer
Indicator section 1 4
Heating preparations
Q’ty
1 Spacers 2
2 Wire joints 4
Q’ty
Pan-head tapping screws 4 × 13/32 in.
Part Name Figure
Part Name Figure
Q’ty
Q’ty
11
1
11
X
22
2
22
K
33
3
33
T
44
4
44
U
55
5
55
C
Wireless remote controller 1 2
Wireless remote controller mounting cradle
Batteries 2 Wire joints 4
<RCS-BH80UA.WL>
Part Name Figure
Separate type signal receiving unit (comes with 7-7/8 in. wire)
Carrier for ceiling installation 1 Wood screws 2
Wireless remote controller 1 Spacers 4
Truss-head tapping screws 4 × 5/8 in.
Vinyl clampers
13
L 5-29/32
Q’ty
Small screws
12
M4 × 1-9/16 in.
Part Name Figure
Q’ty
66
6
66
RC
(WD)
77
7
77
RC
(WL)
88
8
88
WT
99
9
99
SC
Wireless remote controller mounting cradle
Batteries 2 Clamper 1
Machine screws M4 × 1 in.
1 Wire joints 4
Ceiling installation paper pattern
21
(
3-3/4 × 2-1/32 in.
S4359146
7
)
Table 1-8 (Accessories for the Weekly Timer)
Part Name Figure
Q’ty
Part Name Figure
Weekly timer 1 Wood screws 2
Connecting wiring length 4 ft.
Machine screws
1 Spacers 2
2 Clampers 2
M4 × 1 in.
Table 1-9 (Accessories for the System Controller)
Part Name Figure
System controller 1 1
Rubber bushing (7/8 in.)
Screws for fixture (1-3/16 in.)
Q’ty
Label (Identification label)
Label
41
(Terminal base label)
Part Name Figure
SYSTEM CONTROLLER IDENTIFICATION LABEL
ALL Central Control ALL RCU. ZONE1 Central Control
ZONE1 RCU.
ZONE2 Central Control
ZONE2 RCU.
ZONE3 Central Control
ZONE3 RCU.
ZONE4 Central Control
ZONE4 RCU.
*Please attach this label on surface of the lid after cleaning. *If need to write down some detail, use magic marker.
ALL ON
U1
INPUT
Inter-
unit control wiring
ALL OFF
U2
INPUT
COMMON
U2 Aux.
INPUT
OPERATION STATE
UNUSED
OUTPUT
ALARM OUTPUT
DC12V FROM INDOOR UNIT PCB.
COMMON OUTPUT
2
Q’ty
Q’ty
S4359146
8
1-5. T ubing Length
Refrigerant tubing between the indoor and
outdoor units should be kept as short as possible.
Select and decide the installation location so
that the length of the refrigerant tubing will be within the limits given in Table 1-10.
Table 1-10
Models
Tubing Data
Tubing size outer dia.
Limit of tubing length (ft.) 165 165
Limit of elevation difference between the 2 units
Max. allowable tubing length at shipment (ft.) 100 100 Required additional refrigerant (oz./ft.) 0.48
No additional charge of compressor oil is necessary.
*1If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.48 oz./ft.. *2If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.53 oz./ft..
Narrow tube in. (mm) 1/4 (6.35) 3/8 (9.52) Wide tube in. (mm) 3/4 (19.05) 3/4 (19.05)
Outdoor unit is higher than indoor unit (ft.)
Outdoor unit is lower than indoor unit (ft.)
CH2442
165 165
100 100
*1
INDOOR UNIT
Elevation difference (H)
CH3642, CH4242
*2
0.53
Tubing length (L)
OUTDOOR UNIT
Fig. 1-1
0711_M_I
11
1
11
X
22
2
22
K
33
3
33
T
44
4
44
U
55
5
55
C
66
6
66
RC
(WD)
77
7
77
RC
(WL)
88
8
88
WT
99
9
99
SC
S4359146
9
2. SELECTING THE INSTALLATION SITE
Indoor Unit
AVOID:
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near inverter lamps which may affect
performance of the unit.
locations near heat sources which may affect performance of the unit.
locations where external air may enter the room directly. This may cause “sweating” on the air discharge ports, causing them to spray or drip.
locations where the remote control unit will be splashed with water or affected by dampness or humidity.
installing the remote control unit behind curtains or furniture.
locations where the receiver in the indoor unit is exposed to the inver ter lamp light. Faulty operation of the unit occurs.
DO:
Ceiling-Mounted Type
Ceiling
Wall
Min.10 inch
Front view
Min.10 inch
NOTE
The rear of the indoor unit can be installed flush against the wall.
Air discharge
Min.2 ft.
Side view
Ceiling
Air intake
1091_T_I
4-Way Air Discharge Type
Concealed-Duct Type
3 ft.
3 ft.
select an appropriate position from which every corner of the room can be uniformly cooled.
select a location where the ceiling is strong enough to support the weight of the unit.
select a location where tubing and drain pipe have the shortest run to the outdoor unit.
allow room for operation and maintenance as well as unrestricted air flow around the unit.
install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length from the outdoor unit as detailed in Table 1-10.
allow room for mounting the remote control unit about 3 ft. off the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from the floor to the ceiling is greater than 10 ft..
3 ft.
Min. 6 inch
3 ft.
3 ft.
1960_X_I
Wall-Mounted T ype
Min. 6 inch
Min. 12 inch
0930_K_I
10
S4359146
Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 2-1)
damp, humid or uneven locations.
DO:
Hot air
Out­door unit
Exhaust fan
Heat source
0591_C_I
11
1
11
X
22
2
22
K
choose a place as cool as possible.
choose a place that is well ventilated and outside
air temperature does not exceed maximum 115°F constantly.
allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 2-2)
provide a solid base; about 6 inch above ground level to reduce humidity and possib le water damage in the unit and decreased service life. (Fig. 2-3)
use lug bolts or equivalent to bolt down unit, reducing vibration and noise.
In case of multiple installations
Unit spacing if air discharge chamber is not used. Unit spacing when air discharge chamber is used.
Min. 4 ft. Min. 4 ft.Min. 5 ft.
Min. 1 ft.
Min. 12 ft.
Min. 8 inch
Min. 1 inch
Min. 4 ft.
Min. 1 ft. 2 inch
Min. 1 ft. 2 inch
4 in.
Min. 2 ft.
Min. 8 inch
Fig. 2-1
Min. 1 inch
0931_C_I
Fig. 2-2
Min. 1 ft.
Obstacle above
Min. 7 ft.
Air dis­charge
Ground
Min. 4 ft.
Air discharge chamber
Min. 1 ft.
0932_C_I
33
3
33
T
44
4
44
U
55
5
55
C
66
6
66
RC
(WD)
77
7
77
RC
(WL)
88
8
88
WT
If you would like to make the separation smaller on the air discharge side, use an air discharge chamber. You can install any number of units side-by -side.
Only up to 3 units can be installed side-by-side under the above conditions. The next group must be spaced at least 1 ft. away from the first group.
11
Air in
Air discharge
Concrete block 4 inch × 1 ft. 4 inch beams or equal
Anchor bolts (4 pieces)
Fig. 2-3
S4359146
Air in
Min. 6 inch
0934_C_I
0933_C_S
99
9
99
SC
Air discharge
0426_C_I
2-1. Air Discharge Chamber for Top Discharge
I
Install the air-discharge chamber in the field when:
it is difficult to keep a space of minimum 2 ft. between the air-discharge outlet and the obstacle.
the air-discharge outlet is facing the sidewalk and discharge hot air can annoy the passers-by. Refer to Fig. 2-4.
8-ø1/4" hole
22-5/16"
23-5/16"
3-ø2-3/8" hole
11-13/16"
43-15/16"
9-7/8"9-7/8" 17-3/4" 3-15/16"
5-3/16"
5-5/32"
1352_C_
Recommended outer dimensions of wind shield (field supply)
21-13/16"
21-13/16"
CH3642 CH2442
Fig. 2-4
3 - ø1-9/16" hole
9-27/32"21-5/8"15/16"
6 - ø15/64" hole
22-7/16"1/2"
23-15/32"
5-3/16"
5-5/32"9-27/32"9-27/32"1-7/32"
0936_C_I
2-2.
Installing the Outdoor Unit in Heavy Snow Areas
In locations subject to strong winds, snow-proof ducting should be fitted and direct exposure to the wind should be avoided as much as possible.
The following problems may occur when the outdoor unit is not provided with a platform and snow-proof ducting.
a) The outdoor fan may not run and there may be
damage to the unit b) There may be no air flow. c) The tubing may freeze and burst. d) The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
12
S4359146
I
2-3. Precautions When Installing in Heavy Snow
Areas
(1) The platform should be higher than the maximum.
snow depth. (Fig. 2-5)
(2) The two anchoring feet of the outdoor unit should
be attached to the platform, and the platform should be installed beneath the air-intake side of the outdoor unit.
(3) The platform foundation must be solid and the
unit must be secured with anchor bolts.
(4) When installing on a roof subject to strong wind,
countermeasures must be taken to prevent the unit from being overturned.
2-4. Dimensions of Snow / Wind-proof Ducting
and Refrigerant Tubing Space for Installation
Min. 4"
Duct
Duct
Min. 4" 12" Unit: inch
Outdoor Unit
12"
1117_C_I
In regions with snow fall, the outdoor unit should be provided with a platform and snow-proof duct.
Without snow­proof ducting (Low platform)
Fig. 2-5 Fig. 2-6
Outdoor Unit
Duct
Snow-proof ducting (High platform)
0937_C_I
Duct
11
1
11
X
22
2
22
K
33
3
33
T
44
4
44
U
55
5
55
C
66
6
66
RC
(WD)
Air Intake
About 1/2 of the unit height
Platform (foundation)
Fig. 2-7
Example of Installation
Fig. 2-8
Higher than the maximum snow depth
Air Intake
0488_C_
0490_C_I
77
7
77
RC
(WL)
88
8
88
WT
99
9
99
SC
S4359146
13
11
1
11
3. HOW TO INSTALL THE INDOOR UNIT
4-Way Air Discharge Semi-Concealed Type (XH Type)
X
3-1. Suspending the Indoor Unit
Hole-in-anchor Hole-in-plug
Concrete Insert
This unit uses a drain pump. Use a carpenter’s level to check that the unit is level.
3-2. Preparation for Suspending
(1) Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs.
3-1 and 3-2), by attaching them to the ceiling
support structure, or by any other method that
Suspension bolt (M10 or 3/8") (field supply)
Fig. 3-1
0038_T_I
ensures that the unit will be securely and safely
suspended.
X
(2) Follow Fig. 3-2 and Table 3-1 to make the holes
in the ceiling.
Table 3-1 Unit: inch (mm)
Type
Length
XH1242, XH1842 , XH2442
(PNR-XH2442)
XH3642, XH4242
(PNR-XH3642)
AB
32-9/32 (820) 22-9/32 (566)
43-11/16 (1,110) 33-11/16 (856)
A (Ceiling opening)
B
(Suspention bolt pitch)
Drain hose side
Grille center
32-9/32 (Ceiling opening)
29-13/16 (Suspention bolt pitch)
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The
diagram and table (Fig. 3-3 and Table 3-2) show
the relationship between the positions of the
suspension fitting, the unit, and the panel.
Refrigerant tubing joint (wide tube side)
Suspension lug
E
Fig. 3-3
Table 3-2 Unit : inch (mm)
Type
Length
ABCDE
XH1242, XH1842, XH2442 6-3/16 7-5/32 10-9/32 12-1/8 4-7/8
(PNR-XH2442) (157) (182) (261) (308) (124)
XH3642, XH4242 6-3/16 7-5/32 11-15/32 13-1/16 4-7/8
(PNR-XH3632) (157) (182) (291) (338) (124)
Fig. 3-2
Refrigerant tubing side
1969_X_S
Drain connection (another side) (VP25)
Refrigerant tubing joint (narrow tube side)
D
C
B
A
1-3/16
1970_X_S
14
S4359146
3-3. Placing the Unit Inside the Ceiling
I
(1) When placing the unit inside the ceiling, deter-
mine the pitch of the suspension bolts using the supplied full-scale installation diagram. (Fig. 3-4) The size of the opening for the indoor unit can be confirmed by attaching the full-scale installation diagram beneath the unit. (Fig. 3-4) Tubing and wiring must be laid inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing and wiring into posi­tion for connection to the unit before placing the unit inside the ceiling.
(2) The length of suspension bolt must be appropri-
ate for a distance between the bottom of the bolt and the bottom of the ceiling of 19/32 in. or more as shown in Fig. 3-4.
(3) Thread the 2 hexagonal nuts (field supply) and
washers onto the 4 suspension bolts as shown in Fig. 3-5.
Use 2 sets of nuts and washers (upper and lower), so that the unit will not fall off the suspen­sion lugs.
(4) Remove the protective cardboard used to protect
the fan parts during transport.
(5) Adjust the distance between the unit and surface
of the ceiling. (1-7/8 in.) (Fig. 3-4)
Full-scale installation diagram (printed on a cardboard packing)
19/32 inch or more
Nuts and washers
(Use above and below)
Double nuts
Fig. 3-4
Suspension bolt
Upper
Lower
1-7/8 inch
Fig. 3-5
Full-scale installation
diagram
2040_X_I
Suspension lug
Notch
1-7/8 inch
1971_X_
11
1
11
X
S4359146
15
11
I
I
1
11
X
3-4. Installing the Drain Piping
(1) Prepare standard hard PVC pipe for the drain and
use the supplied drain hose and hose band to
prevent water leaks.
The PVC pipe must be purchased separately.
The transparent part allows you to check drain-
age. (Fig. 3-6)
Tighten the hose clamps
CAUTION
so their locking nuts face upward. (Fig. 3-6)
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe.
(Fig. 3-7)
NOTE
Ensure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
Transparent part for checking drainage
Packing (supplied)
Drain hose (supplied)
Drain insulator (supplied)
Hose band (supplied)
Fig. 3-6
Fig. 3-7
Hard PVC pipe (not supplied)
Drain hose adapter (supplied)
0197_X_I
0964_X_I
Do not install an air
CAUTION
bleeder tubes, as this may cause water to spray from the drain tube outlet. (Fig. 3-8)
If it is necessary to increase the height
of the drain pipe, the section directly after the connection port can be raised a maximum of 19-11/16 in. Do not raise it any higher than 19-11/16 in., as this could result in water leaks. (Fig. 3-9)
Do not install the pipe with an upward
gradient from the connection port. It will cause the drain water to flow backwards and leak when the unit is stopped. (Fig. 3-10)
Do not apply force to the piping on the
unit side when connecting the drain pipe. The pipe should not be allowed to hang unsupported from its connec­tion to the unit. Fasten the pipe to a wall, frame, or other support as close to the unit as possible. (Fig. 3-11)
Air bleeder
0047_X_I
Fig. 3-8
11-3/4 in. or less (as short as possible)
19-11/16 in. or less
1972_X_I
Fig. 3-9
Upward gradient
0049_X_
Fig. 3-10
Provide insulation for any drain pipes
that are installed indoors.
16
Support pieces
0050_X_
Fig. 3-11
S4359146
3-5. Checking the Drainage
After wiring and piping are completed, use the follow­ing procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth ready to catch and wipe up spilled water.
Do not supply power to the unit until the tubing and wiring to the outdoor unit are completed.
(1) Take off the tube cover and through the opening,
slowly pour about 43 oz. of water into the drain pan to check drainage.
(2) Do Test Run to check the drainage after complet-
ing installation. When performing Test Run, be sure to observe the Test Run procedure. Refer to page 89.
11
1
11
X
CAUTION
(3) After drain checking is finished, return the
Operation Selector switch to the RUN position (ON position ) and remount the tube cover.
CAUTION
Be careful since the fan will start turning when checking the drainage.
To mount the tube cover, use 5/16" (4 screws. Do not use long screws as they may punc­ture the drain pan and cause water leakage.
××
× 8 mm) tapping
××
5/16"(4 × 8 mm) tapping screw
Tube cover
Siphon
0966_X_I
Fig. 3-12
17
S4359146
11
1
11
X
Ceiling Panel
Never touch or attempt to
CAUTION
move the air direction louver by hand or you may damage the unit. Instead, use the remote control unit if you want to change the direction or air flow.
3-6. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 3-13 and 3-14)
(a) Remove the 2 screws on the latch of the air-
intake grille. (Fig. 3-13)
(b) Press on the 2 latches of the air-intake grille
with your thumb in the direction of the arrow to open the grille. (Fig. 3-13)
(c) With the air-intake grille open about 45˚,
remove the safety string (hook on the grille side). (Fig. 3-14)
(d) Pull the air-intake grille towards you to
remove it from the ceiling panel.
Latch
Screw
Air intake grille
(2) Pull down the two panel catches on the body of
the indoor unit body. (Fig. 3-15)
Ceiling panel
0149_X_I
Fig. 3-13
Air filter
45°
Safety string
18
0150_X_I
Fig. 3-14
S4359146
3-7. Installing the Ceiling Panel
(1) Lift the ceiling panel and position it to align the
panel hook with the panel catch of the indoor unit.
NOTE
The ceiling panel must be mounted in the correct direction. Note that the 2 catches of the panel differ in size. Confirm that the catches are correctly matched be­tween the ceiling panel and the indoor unit body.
(2) Next, check to see that the ceiling panel is prop-
erly aligned with the seamline of the ceiling. If it is not, remove the ceiling panel and slightly readjust the indoor unit body to the proper suspension point.
(3) When the ceiling panel has been properly
aligned, use the supplied 4 mounting screws (M5) with washers to permanently fasten the ceiling panel.
(4) Install the wiring connector from the ceiling panel
to the connector in the electrical component box of the indoor unit. After installing the connector, use the clamp on the body of the indoor unit to secure the wiring.
(5) Install the air filter and air-intake grille by perform-
ing the steps in section 3-6 in reverse.
NOTE
Rehook the safety string before closing the air-intake grille.
3-8. When Removing the Ceiling Panel for
Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the wiring connector inside the electrical component box, and then remove the 4 mounting screws.
11
1
11
X
Ceiling panel
Clamp
Ceiling panel wiring connector
Electrical component box
Panel catch Electrical
component box
Unit body
Panel catch (arrange facing downwards)
(2 locations)
Screws M5 with washer
(supplied)
Air filter
Fig. 3-15
19
Air-intake grille
1973_X_I
S4359146
11
1
11
X
3-9. Duct for Fresh Air
There is a duct connection part on sideface of the indoor unit. (Fig. 3-16)
Optional air-intake plenum (including duct connection box and flange) can be attached to the indoor unit.
Air-intake plenum Type
CMB-GSJ80U
CMB-GSJ140U
PNR-XH2442
(XH1242, XH1842, XH2442)
PNR-XH3642
(XH3642, XH4242)
For fresh air intake
2-3/8
2-5/32
4-ø1/8 hole
ø4-13/32
(1) Accessories
Check that the following parts are in the box when unpacking.
NAME QT’Y REMARKS
Cord with socket (9P) intaking fresh air.
Screw (M5 × L5 in.) (for fastening)
Screw (M4 × L1/2 in.) (for fastening)
Duct connection box 1 (for fresh air) Duct connection flange 1
Connecting line. Not necessary for
1
Air-intake filter
4
Duct connection flange/ box
7
(for connecting fresh air duct
(2) Installation
Installation steps (a) to (e) are the same for both the CMB-GSJ80U and the GSJ140U. The drawing illustrates installation of air-intake plenum to the CMB-GSJ80U.
Installation screws
(a) Installing the air-intake plenum
Set the air-intake plenum to the indoor unit taking care not to set the incorrect direction. (Fig. 3-17)
Fasten the air-intake plenum with the accessory screws. (M5 × L5 in., 4pcs) (Fig. 3-17)
Detail of fresh air intake
Fig. 3-16
)
Socket cover
1974_X_S
Panel lead wire (8P)
(b) Installing the duct connection box
Fasten the duct connection flange to the duct connection box with the accessory screws. (M4 × L1/2 in., 4pcs) (Fig. 3-18)
Put the duct connection box into the rectangular hole of the air-intake plenum and fasten it to the both sides of the indoor unit and plenum with the accessory screws. (M4 × L1/2 in., 3pcs) (Fig. 3-18)
(c) Installing the indoor unit
Install the indoor unit to the ceiling. (Install the indoor unit according to items 3-1 to 3-6.)
When installing in a pre-
CAUTION
existing location, install the indoor unit before installing the duct connection box.
Air-intake plenum
Indoor unit
S4359146
20
Clamper
8P socket (red) (electrical component box)
8P socket (red) (ceiling panel side)
1975_X_S
Fig. 3-17
(e) Installing the ceiling panel
Attach the ceiling panel to the chamber. Drawing the panel downwards sets the panel in position temporarily with the panel catch (at 2 locations).
Remove the socket cover of the air-intake plenum and pass the 8P sockets through it. (Fix the panel lead wire to chamber side clamper.) (Fig. 3-17)
Connect the 8P socket (electrical component box side) to the 8P socket (ceiling panel side) of the indoor unit electrical component box.
Reattach the socket cover.
Duct connection flange
Installation screws
(M4 × 1/2 in.)
Panel catch
Ceiling panel
Fig. 3-18
Duct connection box
1976_X_S
11
1
11
X
21
S4359146
I
I
Wall-Mounted Type (KH Type)
3-10. Removing the Wall Fixture from the Unit
22
2
22
K
KH2442
Remove and discard the set screws and take off the wall fixture. (Fig. 3-19)
3-11. Selecting and Making a Hole
KH2442
(1) Tape the full-scale installation diagram on the
wall at the location selected. Make sure the unit is horizontal, using a level or tape measure to measure down from the ceiling. (Fig. 3-20)
(2) Before drilling a hole, check that there are no
studs or pipes behind the determined location.
Avoid area where electrical
CAUTION
(3) Using a sabre saw, key hole saw or 3-5/32 in.
hole-cutting drill attachment, make a hole in the wall. The required minimum hole diameter for these models is 3-3/16 in. (Fig. 3-21)
(4) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a slight angle 1/4 in. shorter than the thickness of the wall. (Fig. 3-22)
(5) Place the plastic cover over the end of the pipe,
(for indoor side only) and insert in the wall. (Fig. 3-23)
wiring or conduit is located. Also take this precaution if the tubing goes through a wall at any other location.
Wall fixture
Set screws only for transportation
1390_T_I
Fig. 3-19
Tape
Full-scale installation diagram
0940_T_I
Fig. 3-20
NOTE
Hole should be made at a slight downward slant to the outdoor side.
Indoor side
Outdoor side
0066_T_
Fig. 3-21
PVC pipe (locally purchased)
Cut at slight angle
0941_T_I
Fig. 3-22
OUTSIDE
PVC pipe
Slight angle
0942_K_
Plastic cover
INSIDE
Wall
Fig. 3-23
S4359146
22
I
I
KH3642
One hole is required for the air conditioner tubing, and may be either on the left or right side. (Also see sec­tion 3-14. Preparing the Indoor Side Tubing.)
(1) Tape the full-scale installation diagram on the
wall at the location selected. Make sure the unit is horizontal, using a level or tape measure to measure down from the ceiling. (Fig. 3-24)
(2) Determine if the hole is to be drilled at the left or
right hole location.
(3) Before drilling a hole, check that there are no
studs or pipes behind the determined location.
Avoid area where electrical
CAUTION
wiring or conduit is located. Also take this precaution if the tubing goes through a wall at any other location.
(4) Using a sabre saw, key hole saw or 3-5/32 in.
hole-cutting drill attachment, make a hole in the wall. The required minimum hole diameter for these models is 3-3/16 in. (Fig. 3-25)
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a slight angle 1/4 in. shorter than the thickness of the wall. (Fig. 3-26)
Tape
Full scale installation diagram
1354_T_I
Fig. 3-24
NOTE
Hole should be made at a slight downward slant to the outdoor side.
Indoor side
Outdoor side
22
2
22
K
(6) Place the plastic cover over the end of the pipe,
(for indoor side only) and insert in the wall. (Fig. 3-27)
Fig. 3-25
PVC pipe (locally purchased)
Cut at slight angle
Fig. 3-26
INSIDE
Plastic cover
Wall
0066_T_
0941_T_I
OUTSIDE
PVC pipe
Slight angle
0942_K_
Fig. 3-27
S4359146
23
3-12. Installing the Wall Fixture onto Wooden or
Gypsum Wall
KH2442
Confirm that the wall is strong enough to support the unit.
a) If the Wall is Wooden
wall fixture
22
2
22
K
(1) Attach the wall fixture to the wall with the 9
screws provided. (Fig. 3-28) If you are not able to line up the holes in the wall fixture with the beam locations marked on the wall, use rawl plugs or toggle bolts to go through the holes on the panel or drill 13/64 in. dia. holes in the panel over the stud locations and then mount the wall fixture.
(2) Check with a tape measure or carpenter’s level.
This is important so that the unit is correctly installed.
(3) Make sure the wall fixture is flush against the
wall. Any space between the wall and unit will cause noise and vibration.
b) If the Wall is Brick, Concrete or Similar
Drill 3/16 in. dia. holes in the wall. Insert rawl plugs for appropriate mounting screws. (Fig. 3-29)
KH3642
Confirm that the wall is strong enough to support the unit.
0943_T_I
Fig. 3-28
3/16 in. dia. hole
Rawl plug
0944_T_I
Fig. 3-29
a) If the Wall is Wooden
(1) Attach the wall fixture to the wall with the 12
screws provided. (Fig. 3-30) If you are not able to line up the holes in the wall fixture with the beam locations marked on the wall, use rawl plugs or toggle bolts to go through the holes on the panel or drill 3/16 in. dia. holes in the wall fixture over the stud locations.
(2) Check with a tape measure or carpenter’s level
that the wall fixture is level. This is important so that the unit is correctly installed.
(3) Make sure the wall fixture is flush against the
wall. Any space between the wall and unit will cause noise and vibration.
b) If the Wall is Brick, Concrete or Similar
Drill 3/16 in. dia. holes in the wall. Insert rawl plugs for appropriate mounting screws. (Fig. 3-29)
Wall fixture
1355_M_I
Fig. 3-30
24
S4359146
3-13.
Removing the Casing to Install the Indoor Unit
KH2442
How to Remove the Casing
(1) Remove the plastic cover. (Fig. 3-31) (2) Remove the clamp for the wiring connector.
(Fig. 3-32) (3) Disconnect the wiring connector. (Fig. 3-33) (4) Set the flap in the horizontal position. (Fig. 3-34)
Plastic cover
Screw
22
2
22
K
(5) Remove the 3 screws. (Fig. 3-34) (6) Remove the casing. (Fig. 3-34)
NOTE
When replacing the casing, be careful not to crush the lead wires between the casing and the frame. (Fig. 3-34)
Casing
Frame
Flap
Clamp
Screw
0945_T_I
Fig. 3-31
Fig. 3-32
2023_T_I
Wiring connector
Screws
Fig. 3-34
0947_T_I
Fig. 3-33
2024_T_I
25
S4359146
22
1358_T_I
Hack saw
2
22
K
3-14. Preparing the Indoor Side Tubing
KH2442
Tubing can be extended in 4 directions as shown in Fig. 3-35.
Arrangement for Left Tubing
(a) Cut out the left tubing outlet. (Fig. 3-36)
Arrangement for Right Tubing
(a) Cut out the right tubing outlet using a hacksaw.
(Fig. 3-37)
Arrangement for Left-rear and Right-rear Tubing.
(a) It is not necessary to cut a hole.
KH3642
Tubing can be extended in 4 directions as shown in Fig. 3-35.
Left tubing
Left tubing outlet
Fig. 3-36
Left-rear tubing
0950_T_I
Fig. 3-35
Right-rear tubing (Recommended)
Right tubing
0949_T_I
Right tubing outlet
0951_T_I
Fig. 3-37
Arrangement for Right-rear Tubing
(a) Remove the 2 screws and slide out the side
cover. (Fig. 3-38)
(b) Extend the wide tube from the outdoor side and
connect it directly to the mating tube inside the indoor unit. Use a flare nut. (Fig. 3-39)
Arrangement for Right Tubing
(a) Remove the 2 screws and take off the side cover.
(Fig. 3-38)
(b) Cut out the L-shaped tubing outlet using a hacksaw.
(Fig. 3-40)
(c) Using the L-shaped tube (field supply), connect
tubing between the indoor and outdoor units. (Fig. 3-42)
Arrangement for Left and Left-rear Tubing.
(a) Remove the 4 screws (2 on each side) and take
off both left and right side cover. (Fig. 3-41) (b) Remove 4 screws to remove the bottom cover. (c) Using the L-shaped tube (field supply), connect
tubing as in Fig. 3-43.
Fig. 3-38
1356_T_I
Tubing from the outdoor unit
1357_T_I
Fig. 3-39
Left side cover
Indoor unit
Bottom cover
Fig. 3-41
Right side cover
1361_T_I
L-shaped tube
Fig. 3-42
26
Fig. 3-40
L-shaped tube
1359_T_I
1360_T_I
Fig. 3-43
S4359146
3-15. Wiring Instructions General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the
unit as shown on its name plate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.
(3) To prevent possible hazards from insulation
failure, the unit must be grounded. (4) All wiring must be connected tightly. (5) Do not allow wiring to touch refrigerant tubing,
compressor, or any moving parts of the fan.
Unauthorized changes in the internal wiring can be very dangerous. The manufac­turer will accept no respon­sibility for any damage or misoperation that occurs as a result of such unautho­rized changes.
22
2
22
K
27
S4359146
22
I
2
22
K
3-16.
Wiring Instructions for Inter-Unit Connections
(a) Insert the inter-unit wiring (according to local
codes) into the through-the-wall PVC pipe. Run the wiring toward the indoor side allowing approx. 5". to extend from the wall face. (Fig. 3-44)
Never fix the wiring by any
CAUTION
means before the indoor unit is fully seated on the rear panel.
(b) Remove the side cover and the metallic cover.
(Fig. 3-45 or 3-46, depending on model.)
(c) Secure the conduit connector to the chassis with
a lock nut. (Fig. 3-45 or 3-46)
(d) Give some play to the inter-unit wiring from the
outdoor unit to the corresponding terminals on the terminal plate.
Be sure to refer to the
CAUTION
wiring system diagram label inside the metallic cover and carry out the correct field wiring. Wrong wiring can cause the unit to malfunction.
Check local electrical
codes and any specified wiring instructions or limitations.
(e) Secure the metallic cover with its screw. Then
replace the side cover.
KH2442
Rear panel
Wiring
KH3642
Connector Wiring
Wall
Plastic cover
5"
1362_T_I
Wall fixture
Wall
5"
KH2442
Lock nut
Power line
Look nut
Elbow conduit
Grounding line
Fig. 3-45
Metallic cover
Plastic cover
Screw
0968_T_I
KH3642
Lock nut
Connector
Fig. 3-44
Metallic cover
Fig. 3-46
Side cover
1363_T_
1395_T_I
S4359146
28
Loading...
+ 65 hidden pages