This air conditioning system meets strict safety and
operating standards. As the installer or service person, it
is an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must :
ⓦ Carefully read this instruction booklet before beginning.
ⓦ Follow each installation or repair step exactly as shown.
ⓦ Observe all local, state, and national electrical codes.
ⓦ Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a
hazard or unsafe practice
which can result in severe
personal injury or death.
This symbol refers to a
CAUTION
hazard or unsafe practice
which can result in personal
injury or product or property
damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
……………………………………………………………………
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and
tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidentaly injury ordeath.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire
hazard.
When Transporting
……………………………………………………………………
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
thin aluminum fins on the air conditioner can cut your
fingers.
When Installing
……………………………………………………………………
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
……………………………………………………………………
• Ventilate the room well, in the event that refrigerant gas
leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
• Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may
be either narrow or wide. Therefore, to avoid confusion the
refrigerant tubing for your particular model is specified as
either “narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
……………………………………………………………………
• Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site when installation is finished. Check
that no metal scraps or bits of wiring have been left
inside the unit.
CAUTION
• Ventilate any enclosed areas when installing or testing
the refrigeration system. Contact of refrigerant gas with
fire or heat can produce poisonous gas.
• Confirm after installation that no refrigerant gas is
leaking. If the gas comes in contact with a burning
stove, gas water heater, electric room heater or other
heat source, it can cause the generation of poisonous
gas.
i
CONTENTS
Page
IMPORTANT
Please Read Before Starting
1. GENERAL ................................................................... 4
1-1. Tools Required for Installation (Not Supplied)
1-2. Accessories Supplied with Unit
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
1-5. Tubing Length
2. SELECTING THE INSTALLATION SITE .................. 10
Indoor Unit
Outdoor Unit
2-1. Air Discharge Chamber for Top Discharge
2-2. Installing the Outdoor Unit in Heavy Snow Areas
2-3. Precautions When Installing in Heavy Snow Areas
2-4. Dimensions of Snow / Wind-proof Ducting and
Refrigerant Tubing Space for Installation
3. HOW TO INSTALL THE INDOOR UNIT.................... 14
3-1. Suspending the Indoor Unit
3-2. Preparation for Suspending
3-3. Placing the Unit Inside the Ceiling
3-4. Installing the Drain Piping
3-5. Checking the Drainage
3-6. Before Installing the Ceiling Panel
3-7. Installing the Ceiling Panel
3-8. When Removing the Ceiling Panel for Servicing
3-9. Duct for Fresh Air
■ Wall-Mounted Type (KH Type) ................................... 22
3-10. Removing the Wall Fixture from the Unit
3-11. Selecting and Making a Hole
3-12. Installing the Wall Fixture onto Wooden or
Gypsum Wall
3-13.
Removing the Casing to Install the Indoor Unit
3-14. Preparing the Indoor Side Tubing
3-15. Wiring Instructions
3-16.
Wiring Instructions for Inter-Unit Connections
3-17. Shaping the Tubing
3-18. Installing the Drain Hose
■ Ceiling-Mounted T ype (TH Type). .............................. 31
3-19. Suspending the Indoor Unit
3-20. Duct for Fresh Air
3-21. Installing the Drain Piping
■ Concealed-Duct T ype (UH Type) ............................... 35
3-22.
Required Minimum Space for Installation and Service
3-23. Suspending the Indoor Unit
3-24. Installing the Drain Piping
Page
3-25. Checking the Drainage
3-26. Increasing the Fan Speed
4. HOW TO INSTALL THE OUTDOOR UNIT ................ 40
4-1. Removing the Protective Spacer for Transportation
4-2. Installing the Outdoor Unit
4-3. Tubing Direction
6-1. Installation site selection
6-2. Wired Remote Controller Installation
6-3. Basic Wiring Diagram
6-4. Wiring System Diagram for Group Control
6-5. Wiring System Diagram for Multiple Remote
Control
6-6. How to Switch the Indoor Temperature Sensor
6-7. Explanation of Alarm Messages
■ Ceiling Mounted Type (TH Type)......................... 55
7-7. Indicator Section Installation
7-8. Operating Controller Installation
7-9. Electrical Wiring
7-10. Test Run Switch
7-11. Misoperation Alarm Indicators
<RCS-BH80UA.WA>
7-12.
Separate type Signal Receiving Unit Installation
7-13. Electrical Wiring
7-14. Test Run Switch
7-15. Misoperation Alarm Indicators
7-16. Basic Wiring Diagram
7-17. Wiring System Diagram for Group Control
7-18. Wiring System Diagram for Multiple
8-1. Mounting Dimensions for Continuous Installation
8-2. When Using a Wall Box for Flush Mounting
8-3. Wiring Diagram
8-4. Test Run Setting
8-5. Memory Back Up Function for Power Failure
9-1. System Controller Installation
9-2. Electrical Wiring
9-3. Address Switch Setting
9-4. Mode Setting
9-5. How to Perform Zone Registration
9-6. Connection with Other Equipments
9-7. Memory Back Up Switch
9-8. Test Run
Page
10. HOW TO PROCESS TUBING .................................. 79
10-1. Use of the Flaring Method
10-2. Flaring Procedure with a Flare Tool
10-3. Precaution before Connecting Tubes Tightly
10-4. Precautions during Brazing
10-5. Connecting Tubing between Indoor and Outdoor
Units
10-6. Insulating the Refrigerant Tubing
10-7. Taping the Tubes
10-8. Finishing the Installation
11. AIR PURGING .......................................................... 82
12. TEST RUN ................................................................ 85
12-1. Preparing for Test Run
12-2. PCB Setting
12-3. R.C. Address Setting Method
12-4. Automatic Address Setting Method
12-5. Displaying Indoor / Outdoor Unit Combination
Numbers
12-6. Test Run Procedure
12-7. Items to Check Prior to Test Run
12-8. The Main Alarms of Mis-wiring & Mis-setting
12-9. The Main Alarms of Unit Troubles
12-10
This booklet briefly outlines where and how to install
the air conditioning system. Please read over the entire
set of instructions for the indoor and outdoor units and
make sure all accessory parts listed are with the
system before beginning.
Check local electrical codes
CAUTION
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.
1-4. Additional Materials Required for Installation
1-1. Tools Required for Installation (Not Supplied)
1.Standard screwdriver
2.Phillips head screwdriver
3.Knife or wire stripper
4.Tape measure
5.Level
6.Sabre saw or key hole saw
7.Hacksaw
8.Core bits
9.Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
See Table 1-1 to 1-9.
TableType
1-14-Way Air Discharge Semi-Concealed
1-2Wall-Mounted
1-3Ceiling-Mounted
1-4Concealed-Duct
1-5Outdoor Unit
1-6Wired Remote Controller
1-7Wireless Remote Controller
1-8Weekly Timer
1-9System Controller
1.Refrigeration (armored) tape
2.Insulated staples or clamps for connecting wire
(See your local codes.)
3.Putty
4.Refrigeration tubing lubricant
5.Clamps or saddles to secure refrigerant tubing
6.Scale for weighing
1-3. Type of Copper Tube and Insulation Material
Copper tubing for connecting the outdoor unit to the
indoor unit is available in kits which contain the narrow
and wide tubing, fittings and insulation. Consult your
nearest sales outlet or A/C workshop.
If you wish to purchase these materials separately
from a local source, you will need:
1.Deoxidized annealed copper tube for refrigerant
tubing.
2.
Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16 in..
3.Use insulated copper wire for field wiring. Wire
size varies with the total length of wiring. Refer to
Section 5. “Electrical Wiring” for details.
For determining suspension bolt pitch
For wide and narrow tubes
For suspending indoor unit from ceiling
For wide tube flare nuts
For securing drain hose
For drain joint
For drain joint
For drain outlet
For sealing recessed portion of power supply
For sizing up of narrow tube from 1/4 in. to 3/8 in.
(only for 24 type)
Remarks
11
1
11
X
22
2
22
K
33
3
33
T
44
4
44
U
55
5
55
C
Wall fixture *11
Insulator *11
Mounting plate *11
Truss-head
Tapping screw *120
Full-scale diagram1
Wall fixture *21
Rawl plug *210
Cover *21
Tapping screw *210
Insulator1
Phillips
4 × 1 in.
Truss-head
Phillips
4 × 5/8 in.
For supporting the indoor unit
For insulation of the tubing of the indoor unit
For securing the indoor unit
For fixing the wall fixture
For determining the place where the indoor unit is
installed
For supporting the indoor unit
For fixing the wall fixture
For improved tubing appearance
For fixing the wall fixture
For insulation of the tubing of the indoor unit
66
6
66
RC
(WD)
77
7
77
RC
(WL)
88
8
88
WT
99
9
99
SC
Tube connector1
* 1 KH3642 only
* 2 KH2442 only
For sizing up of narrow tube from 1/4 in. to 3/8 in.
(only for 24 type)
S4359146
5
Table 1-3TH (Ceiling-Mounted)
Part NameFigureQ’tyRemarks
Special washer
For temporarily suspending
4
indoor unit from ceiling
Drain insulator1
Flare insulator
T5
T3
1 Set
Drain hose adaptor1
Drain hose clamp4
Insulating tape
Black
White
(heat-resisting)
Vinyl clamp2
Full-scale installation
diagram
Sealing putty1
Drain hose1
Tube connector1
Table1-4 UH (Concealed-Duct)
Part NameFigure
Flare insulator2
(Black)
Insulating tape
(White)
For drain hose joint
For wide tube joints
2
For wide tube and drain hose joint
1
For wide flare joints
For ends of flare insulator
For determining suspension
1
bolt pitch
For sealing recessed portion of power supply
For sizing up of narrow tube from 1/4 in. to 3/8 in.
(only for 24 type)
Q’ty
Remarks
For wide and narrow tubes
2
2
For wide and narrow tubes
For wide and narrow tube flare nuts
Tapping screw TOTA4-10
14 or 20 or 24
Jumper cable*1
Hose band1
Packing1
Sealing putty1
Drain insulator1
Drain hose1
Drain hose adaptor1
Clamp9
Tube connector1
* Jumper cable is housed inside the electrical component box.
Table 1-5 (Outdoor Unit)
Part NameFigure
Hexagonal Wrench1
Grommet1
Bushing1
Q’ty
To open and shut the Narrow Tube Service Valve
For protecting refrigerant pipe by attaching to the
edge of Tubing Outlet
For protecting inter-unit control line by attaching to
the edge of wiring outlet
Installation Instruction1
For air intake duct connection
For increasing the fan speed
For securing drain hose
For drain joint
For sealing recessed portion of power supply
For drain joint
For securing drain hose & refrigerant tubing
For sizing up of narrow tube from 1/4 in. to 3/8 in.
(only for 24 type)
Remarks
Owner’s manual1
S4359146
6
Table 1-6 (Accessories for the Wired Remote Controller)
Part NameFigure
Wired remote controller
(comes with 7-7/8 in. wire)
Machine screws
M4 × 1 in.
Wood screws2
Table 1-7 (Accessories for the Wireless Remote Controller)
<RCS-SH80UA.WL>
Part NameFigure
Operation controller1Spacers2
Run Timer
Indicator section14
Heating preparations
Q’ty
1Spacers2
2Wire joints4
Q’ty
Pan-head tapping screws
4 × 13/32 in.
Part NameFigure
Part NameFigure
Q’ty
Q’ty
11
1
11
X
22
2
22
K
33
3
33
T
44
4
44
U
55
5
55
C
Wireless remote controller12
Wireless remote controller
mounting cradle
Batteries2Wire joints4
<RCS-BH80UA.WL>
Part NameFigure
Separate type signal receiving unit
(comes with 7-7/8 in. wire)
Carrier for ceiling installation1Wood screws2
Wireless remote controller1Spacers4
Truss-head tapping screws
4 × 5/8 in.
Vinyl clampers
13
L 5-29/32
Q’ty
Small screws
12
M4 × 1-9/16 in.
Part NameFigure
Q’ty
66
6
66
RC
(WD)
77
7
77
RC
(WL)
88
8
88
WT
99
9
99
SC
Wireless remote controller
mounting cradle
Batteries2Clamper1
Machine screws
M4 × 1 in.
1Wire joints4
Ceiling installation paper pattern
21
(
3-3/4 × 2-1/32 in.
S4359146
7
)
Table 1-8 (Accessories for the Weekly Timer)
Part NameFigure
Q’ty
Part NameFigure
Weekly timer1Wood screws2
Connecting wiring
length 4 ft.
Machine screws
1Spacers2
2Clampers2
M4 × 1 in.
Table 1-9 (Accessories for the System Controller)
Part NameFigure
System controller11
Rubber bushing
(7/8 in.)
Screws for fixture
(1-3/16 in.)
Q’ty
Label
(Identification label)
Label
41
(Terminal base label)
Part NameFigure
SYSTEM CONTROLLER IDENTIFICATION LABEL
ALL Central Control ALL RCU.
ZONE1 Central Control
ZONE1 RCU.
ZONE2 Central Control
ZONE2 RCU.
ZONE3 Central Control
ZONE3 RCU.
ZONE4 Central Control
ZONE4 RCU.
*Please attach this label on surface of the lid after cleaning.
*If need to write down some detail, use magic marker.
ALL ON
U1
INPUT
Inter-
unit
control
wiring
ALL OFF
U2
INPUT
COMMON
U2 Aux.
INPUT
OPERATION
STATE
UNUSED
OUTPUT
ALARM
OUTPUT
DC12V
FROM
INDOOR
UNIT PCB.
COMMON
OUTPUT
2
Q’ty
Q’ty
S4359146
8
1-5.T ubing Length
● Refrigerant tubing between the indoor and
outdoor units should be kept as short as
possible.
● Select and decide the installation location so
that the length of the refrigerant tubing will be
within the limits given in Table 1-10.
Table 1-10
Models
Tubing Data
Tubing size
outer dia.
Limit of tubing length(ft.)165165
Limit of elevation
difference between
the 2 units
Max. allowable tubing length at shipment (ft.)100100
Required additional refrigerant(oz./ft.)0.48
No additional charge of compressor oil is necessary.
*1If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.48 oz./ft..
*2If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.53 oz./ft..
● areas where leakage of flammable gas may be
expected.
● places where large amounts of oil mist exist.
● direct sunlight.
● locations near inverter lamps which may affect
performance of the unit.
● locations near heat sources which may affect
performance of the unit.
● locations where external air may enter the room
directly. This may cause “sweating” on the air
discharge ports, causing them to spray or drip.
● locations where the remote control unit will be
splashed with water or affected by dampness or
humidity.
● installing the remote control unit behind curtains or
furniture.
● locations where the receiver in the indoor unit is
exposed to the inver ter lamp light. Faulty operation
of the unit occurs.
DO:
Ceiling-Mounted Type
Ceiling
Wall
Min.10 inch
Front view
Min.10 inch
NOTE
The rear of the indoor unit can be installed flush
against the wall.
Air
discharge
Min.2 ft.
Side view
Ceiling
Air intake
1091_T_I
4-Way Air Discharge Type
Concealed-Duct Type
3 ft.
3 ft.
● select an appropriate position from which every
corner of the room can be uniformly cooled.
● select a location where the ceiling is strong enough
to support the weight of the unit.
● select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
● allow room for operation and maintenance as well
as unrestricted air flow around the unit.
● install the unit within the maximum elevation
difference above or below the outdoor unit and
within a total tubing length from the outdoor unit as
detailed in Table 1-10.
● allow room for mounting the remote control unit
about 3 ft. off the floor, in an area that is not in
direct sunlight nor in the flow of cool air from the
indoor unit.
NOTE
● Air delivery will be degraded if the distance from the
floor to the ceiling is greater than 10 ft..
3 ft.
Min.
6 inch
3 ft.
3 ft.
1960_X_I
Wall-Mounted T ype
Min.
6 inch
Min.
12 inch
0930_K_I
10
S4359146
Outdoor Unit
AVOID:
● heat sources, exhaust fans, etc. (Fig. 2-1)
● damp, humid or uneven locations.
DO:
Hot air
Outdoor
unit
Exhaust fan
Heat source
0591_C_I
11
1
11
X
22
2
22
K
● choose a place as cool as possible.
● choose a place that is well ventilated and outside
air temperature does not exceed maximum 115°F
constantly.
● allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 2-2)
● provide a solid base; about 6 inch above ground
level to reduce humidity and possib le water damage
in the unit and decreased service life. (Fig. 2-3)
● use lug bolts or equivalent to bolt down unit,
reducing vibration and noise.
In case of multiple installations
Unit spacing if air discharge chamber is not used.Unit spacing when air discharge chamber is used.
Min. 4 ft.Min. 4 ft.Min. 5 ft.
Min. 1 ft.
Min. 12 ft.
Min. 8 inch
Min.
1 inch
Min. 4 ft.
Min. 1 ft. 2 inch
Min. 1 ft. 2 inch
4 in.
Min. 2 ft.
Min. 8 inch
Fig. 2-1
Min.
1 inch
0931_C_I
Fig. 2-2
Min. 1 ft.
Obstacle above
Min.
7 ft.
Air
discharge
Ground
Min. 4 ft.
Air
discharge
chamber
Min. 1 ft.
0932_C_I
33
3
33
T
44
4
44
U
55
5
55
C
66
6
66
RC
(WD)
77
7
77
RC
(WL)
88
8
88
WT
If you would like to make the separation smaller on the air
discharge side, use an air discharge chamber.
You can install any number of units side-by -side.
Only up to 3 units can be installed side-by-side under the above
conditions. The next group must be spaced at least 1 ft. away
from the first group.
11
Air in
Air
discharge
Concrete block
4 inch × 1 ft. 4 inch
beams or equal
Anchor bolts
(4 pieces)
Fig. 2-3
S4359146
Air in
Min. 6 inch
0934_C_I
0933_C_S
99
9
99
SC
Air discharge
0426_C_I
2-1.Air Discharge Chamber for Top Discharge
I
Install the air-discharge chamber in the field when:
● it is difficult to keep a space of minimum 2 ft.
between the air-discharge outlet and the obstacle.
● the air-discharge outlet is facing the sidewalk and
discharge hot air can annoy the passers-by.
Refer to Fig. 2-4.
8-ø1/4" hole
22-5/16"
23-5/16"
3-ø2-3/8" hole
11-13/16"
43-15/16"
9-7/8"9-7/8"17-3/4"3-15/16"
5-3/16"
5-5/32"
1352_C_
Recommended outer dimensions of wind shield
(field supply)
21-13/16"
21-13/16"
CH3642CH2442
Fig. 2-4
3 - ø1-9/16" hole
9-27/32"21-5/8"15/16"
6 - ø15/64" hole
22-7/16"1/2"
23-15/32"
5-3/16"
5-5/32"9-27/32"9-27/32"1-7/32"
0936_C_I
2-2.
Installing the Outdoor Unit in Heavy Snow
Areas
In locations subject to strong winds, snow-proof
ducting should be fitted and direct exposure to the
wind should be avoided as much as possible.
The following problems may occur when the outdoor
unit is not provided with a platform and snow-proof
ducting.
a)The outdoor fan may not run and there may be
damage to the unit
b)There may be no air flow.
c)The tubing may freeze and burst.
d)The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
12
S4359146
I
2-3.Precautions When Installing in Heavy Snow
Areas
(1) The platform should be higher than the maximum.
snow depth. (Fig. 2-5)
(2) The two anchoring feet of the outdoor unit should
be attached to the platform, and the platform
should be installed beneath the air-intake side of
the outdoor unit.
(3) The platform foundation must be solid and the
unit must be secured with anchor bolts.
(4) When installing on a roof subject to strong wind,
countermeasures must be taken to prevent the
unit from being overturned.
2-4.Dimensions of Snow / Wind-proof Ducting
and Refrigerant Tubing Space for Installation
Min. 4"
Duct
Duct
Min. 4"12"Unit: inch
Outdoor Unit
12"
1117_C_I
In regions with snow fall, the outdoor unit should be
provided with a platform and snow-proof duct.
Without snowproof ducting
(Low platform)
Fig. 2-5Fig. 2-6
Outdoor
Unit
Duct
Snow-proof
ducting
(High platform)
0937_C_I
Duct
11
1
11
X
22
2
22
K
33
3
33
T
44
4
44
U
55
5
55
C
66
6
66
RC
(WD)
Air
Intake
About 1/2 of the
unit height
Platform (foundation)
Fig. 2-7
Example of Installation
Fig. 2-8
Higher than the
maximum
snow depth
Air
Intake
0488_C_
0490_C_I
77
7
77
RC
(WL)
88
8
88
WT
99
9
99
SC
S4359146
13
11
1
11
3. HOW TO INSTALL THE INDOOR UNIT
■
4-Way Air Discharge Semi-Concealed Type
(XH Type)
X
3-1. Suspending the Indoor Unit
Hole-in-anchor
Hole-in-plug
ConcreteInsert
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.
3-2. Preparation for Suspending
(1) Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs.
3-1 and 3-2), by attaching them to the ceiling
support structure, or by any other method that
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-1
0038_T_I
ensures that the unit will be securely and safely
suspended.
X
(2) Follow Fig. 3-2 and Table 3-1 to make the holes
in the ceiling.
Table 3-1Unit: inch (mm)
Type
Length
XH1242, XH1842 , XH2442
(PNR-XH2442)
XH3642, XH4242
(PNR-XH3642)
AB
32-9/32 (820) 22-9/32 (566)
43-11/16 (1,110) 33-11/16 (856)
A (Ceiling opening)
B
(Suspention bolt pitch)
Drain hose
side
Grille center
32-9/32 (Ceiling opening)
29-13/16 (Suspention bolt pitch)
(3) Determine the pitch of the suspension bolts using
(1) When placing the unit inside the ceiling, deter-
mine the pitch of the suspension bolts using the
supplied full-scale installation diagram. (Fig. 3-4)
The size of the opening for the indoor unit can be
confirmed by attaching the full-scale installation
diagram beneath the unit. (Fig. 3-4)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position for connection to the unit before placing the
unit inside the ceiling.
(2) The length of suspension bolt must be appropri-
ate for a distance between the bottom of the bolt
and the bottom of the ceiling of 19/32 in. or more
as shown in Fig. 3-4.
(3) Thread the 2 hexagonal nuts (field supply) and
washers onto the 4 suspension bolts as shown in
Fig. 3-5.
Use 2 sets of nuts and washers (upper and
lower), so that the unit will not fall off the suspension lugs.
(4) Remove the protective cardboard used to protect
the fan parts during transport.
(5) Adjust the distance between the unit and surface
of the ceiling. (1-7/8 in.) (Fig. 3-4)
Full-scale installation diagram
(printed on a cardboard packing)
19/32 inch or more
Nuts and washers
(Use above and below)
Double nuts
Fig. 3-4
Suspension bolt
Upper
Lower
1-7/8 inch
Fig. 3-5
Full-scale installation
diagram
2040_X_I
Suspension lug
Notch
1-7/8 inch
1971_X_
11
1
11
X
S4359146
15
11
I
I
1
11
X
3-4. Installing the Drain Piping
(1) Prepare standard hard PVC pipe for the drain and
use the supplied drain hose and hose band to
prevent water leaks.
The PVC pipe must be purchased separately.
The transparent part allows you to check drain-
age. (Fig. 3-6)
Tighten the hose clamps
CAUTION
so their locking nuts face
upward. (Fig. 3-6)
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe.
(Fig. 3-7)
NOTE
Ensure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.
Transparent part for
checking drainage
Packing
(supplied)
Drain hose
(supplied)
Drain insulator (supplied)
Hose band
(supplied)
Fig. 3-6
Fig. 3-7
Hard PVC pipe
(not supplied)
Drain hose
adapter
(supplied)
0197_X_I
0964_X_I
● Do not install an air
CAUTION
bleeder tubes, as this
may cause water to spray
from the drain tube outlet.
(Fig. 3-8)
● If it is necessary to increase the height
of the drain pipe, the section directly
after the connection port can be raised
a maximum of 19-11/16 in. Do not raise
it any higher than 19-11/16 in., as this
could result in water leaks.
(Fig. 3-9)
● Do not install the pipe with an upward
gradient from the connection port. It
will cause the drain water to flow
backwards and leak when the unit is
stopped. (Fig. 3-10)
● Do not apply force to the piping on the
unit side when connecting the drain
pipe. The pipe should not be allowed
to hang unsupported from its connection to the unit. Fasten the pipe to a
wall, frame, or other support as close
to the unit as possible. (Fig. 3-11)
Air bleeder
0047_X_I
Fig. 3-8
11-3/4 in. or less (as short as possible)
19-11/16 in. or less
1972_X_I
Fig. 3-9
Upward gradient
0049_X_
Fig. 3-10
● Provide insulation for any drain pipes
that are installed indoors.
16
Support
pieces
0050_X_
Fig. 3-11
S4359146
3-5. Checking the Drainage
After wiring and piping are completed, use the following procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth
ready to catch and wipe up spilled water.
Do not supply power to the
unit until the tubing and
wiring to the outdoor unit
are completed.
(1) Take off the tube cover and through the opening,
slowly pour about 43 oz. of water into the drain
pan to check drainage.
(2) Do Test Run to check the drainage after complet-
ing installation. When performing Test Run, be
sure to observe the Test Run procedure.
Refer to page 89.
11
1
11
X
CAUTION
(3) After drain checking is finished, return the
Operation Selector switch to the RUN position
(ON position ) and remount the tube cover.
CAUTION
Be careful since the fan will
start turning when checking
the drainage.
To mount the tube cover,
use 5/16" (4
screws. Do not use long
screws as they may puncture the drain pan and cause
water leakage.
××
× 8 mm) tapping
××
5/16"(4 × 8 mm)
tapping screw
Tube cover
Siphon
0966_X_I
Fig. 3-12
17
S4359146
11
1
11
X
■Ceiling Panel
Never touch or attempt to
CAUTION
move the air direction louver
by hand or you may damage
the unit. Instead, use the
remote control unit if you
want to change the direction
or air flow.
3-6. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 3-13 and 3-14)
(a) Remove the 2 screws on the latch of the air-
intake grille. (Fig. 3-13)
(b) Press on the 2 latches of the air-intake grille
with your thumb in the direction of the arrow
to open the grille. (Fig. 3-13)
(c)With the air-intake grille open about 45˚,
remove the safety string (hook on the grille
side). (Fig. 3-14)
(d) Pull the air-intake grille towards you to
remove it from the ceiling panel.
Latch
Screw
Air intake grille
(2) Pull down the two panel catches on the body of
the indoor unit body. (Fig. 3-15)
Ceiling panel
0149_X_I
Fig. 3-13
Air filter
45°
Safety string
18
0150_X_I
Fig. 3-14
S4359146
3-7. Installing the Ceiling Panel
(1) Lift the ceiling panel and position it to align the
panel hook with the panel catch of the indoor unit.
NOTE
The ceiling panel must be mounted in the correct
direction. Note that the 2 catches of the panel differ in
size.
Confirm that the catches are correctly matched between the ceiling panel and the indoor unit body.
(2) Next, check to see that the ceiling panel is prop-
erly aligned with the seamline of the ceiling. If it is
not, remove the ceiling panel and slightly readjust
the indoor unit body to the proper suspension
point.
(3) When the ceiling panel has been properly
aligned, use the supplied 4 mounting screws (M5)
with washers to permanently fasten the ceiling
panel.
(4) Install the wiring connector from the ceiling panel
to the connector in the electrical component box
of the indoor unit. After installing the connector,
use the clamp on the body of the indoor unit to
secure the wiring.
(5) Install the air filter and air-intake grille by perform-
ing the steps in section 3-6 in reverse.
NOTE
Rehook the safety string before closing the air-intake
grille.
3-8. When Removing the Ceiling Panel for
Servicing
When removing the ceiling panel for servicing, remove
the air-intake grille and air filter, disconnect the wiring
connector inside the electrical component box, and
then remove the 4 mounting screws.
11
1
11
X
Ceiling panel
Clamp
Ceiling panel wiring
connector
Electrical
component box
Panel catch
Electrical
component box
Unit body
Panel catch
(arrange facing downwards)
(2 locations)
Screws M5 with washer
(supplied)
Air filter
Fig. 3-15
19
Air-intake grille
1973_X_I
S4359146
11
1
11
X
3-9. Duct for Fresh Air
● There is a duct connection part on sideface of the
indoor unit. (Fig. 3-16)
● Optional air-intake plenum (including duct connection
box and flange) can be attached to the indoor unit.
Air-intake plenumType
CMB-GSJ80U
CMB-GSJ140U
PNR-XH2442
(XH1242, XH1842, XH2442)
PNR-XH3642
(XH3642, XH4242)
For fresh air intake
2-3/8
2-5/32
4-ø1/8 hole
ø4-13/32
(1) Accessories
● Check that the following parts are in the box when unpacking.
Installation steps (a) to (e) are the same for both the
CMB-GSJ80U and the GSJ140U. The drawing
illustrates installation of air-intake plenum to the
CMB-GSJ80U.
Installation
screws
(a) Installing the air-intake plenum
● Set the air-intake plenum to the indoor unit taking
care not to set the incorrect direction. (Fig. 3-17)
● Fasten the air-intake plenum with the accessory
screws. (M5 × L5 in., 4pcs) (Fig. 3-17)
Detail of fresh air intake
Fig. 3-16
)
Socket cover
1974_X_S
Panel lead wire (8P)
(b) Installing the duct connection box
● Fasten the duct connection flange to the duct
connection box with the accessory screws.
(M4 × L1/2 in., 4pcs) (Fig. 3-18)
● Put the duct connection box into the rectangular
hole of the air-intake plenum and fasten it to the
both sides of the indoor unit and plenum with the
accessory screws. (M4 × L1/2 in., 3pcs) (Fig. 3-18)
(c) Installing the indoor unit
● Install the indoor unit to the ceiling.
(Install the indoor unit according to items 3-1 to 3-6.)
When installing in a pre-
CAUTION
existing location, install the
indoor unit before installing
the duct connection box.
Air-intake
plenum
Indoor unit
S4359146
20
Clamper
8P socket (red)
(electrical
component box)
8P socket (red)
(ceiling panel side)
1975_X_S
Fig. 3-17
(e) Installing the ceiling panel
● Attach the ceiling panel to the chamber.
Drawing the panel downwards sets the panel in
position temporarily with the panel catch (at 2
locations).
● Remove the socket cover of the air-intake plenum
and pass the 8P sockets through it. (Fix the panel
lead wire to chamber side clamper.) (Fig. 3-17)
● Connect the 8P socket (electrical component box
side) to the 8P socket (ceiling panel side) of the
indoor unit electrical component box.
● Reattach the socket cover.
Duct
connection
flange
Installation screws
(M4 × 1/2 in.)
Panel catch
Ceiling panel
Fig. 3-18
Duct connection box
1976_X_S
11
1
11
X
21
S4359146
I
I
■ Wall-Mounted Type (KH Type)
3-10. Removing the Wall Fixture from the Unit
22
2
22
K
KH2442
Remove and discard the set screws and take off the
wall fixture. (Fig. 3-19)
3-11. Selecting and Making a Hole
KH2442
(1) Tape the full-scale installation diagram on the
wall at the location selected. Make sure the unit is
horizontal, using a level or tape measure to
measure down from the ceiling. (Fig. 3-20)
(2) Before drilling a hole, check that there are no
studs or pipes behind the determined location.
Avoid area where electrical
CAUTION
(3) Using a sabre saw, key hole saw or 3-5/32 in.
hole-cutting drill attachment, make a hole in the
wall. The required minimum hole diameter for
these models is 3-3/16 in. (Fig. 3-21)
(4) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a
slight angle 1/4 in. shorter than the thickness of
the wall. (Fig. 3-22)
(5) Place the plastic cover over the end of the pipe,
(for indoor side only) and insert in the wall.
(Fig. 3-23)
wiring or conduit is located.
Also take this precaution if
the tubing goes through a
wall at any other location.
Wall fixture
Set screws only for transportation
1390_T_I
Fig. 3-19
Tape
Full-scale installation diagram
0940_T_I
Fig. 3-20
NOTE
Hole should be made at a slight downward slant to the
outdoor side.
Indoor
side
Outdoor
side
0066_T_
Fig. 3-21
PVC pipe (locally purchased)
Cut at slight angle
0941_T_I
Fig. 3-22
OUTSIDE
PVC pipe
Slight
angle
0942_K_
Plastic
cover
INSIDE
Wall
Fig. 3-23
S4359146
22
I
I
KH3642
One hole is required for the air conditioner tubing, and
may be either on the left or right side. (Also see section 3-14. Preparing the Indoor Side Tubing.)
(1) Tape the full-scale installation diagram on the
wall at the location selected. Make sure the unit is
horizontal, using a level or tape measure to
measure down from the ceiling. (Fig. 3-24)
(2) Determine if the hole is to be drilled at the left or
right hole location.
(3) Before drilling a hole, check that there are no
studs or pipes behind the determined location.
Avoid area where electrical
CAUTION
wiring or conduit is located.
Also take this precaution if
the tubing goes through a
wall at any other location.
(4) Using a sabre saw, key hole saw or 3-5/32 in.
hole-cutting drill attachment, make a hole in the
wall. The required minimum hole diameter for
these models is 3-3/16 in. (Fig. 3-25)
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a
slight angle 1/4 in. shorter than the thickness of
the wall. (Fig. 3-26)
Tape
Full scale
installation diagram
1354_T_I
Fig. 3-24
NOTE
Hole should be made at a slight downward slant to the
outdoor side.
Indoor
side
Outdoor
side
22
2
22
K
(6) Place the plastic cover over the end of the pipe,
(for indoor side only) and insert in the wall.
(Fig. 3-27)
Fig. 3-25
PVC pipe (locally purchased)
Cut at slight angle
Fig. 3-26
INSIDE
Plastic
cover
Wall
0066_T_
0941_T_I
OUTSIDE
PVC pipe
Slight
angle
0942_K_
Fig. 3-27
S4359146
23
3-12. Installing the Wall Fixture onto Wooden or
Gypsum Wall
KH2442
Confirm that the wall is strong enough to support the unit.
a) If the Wall is Wooden
wall fixture
22
2
22
K
(1) Attach the wall fixture to the wall with the 9
screws provided. (Fig. 3-28)
If you are not able to line up the holes in the wall
fixture with the beam locations marked on the
wall, use rawl plugs or toggle bolts to go through
the holes on the panel or drill 13/64 in. dia. holes
in the panel over the stud locations and then
mount the wall fixture.
(2) Check with a tape measure or carpenter’s level.
This is important so that the unit is correctly
installed.
(3) Make sure the wall fixture is flush against the
wall. Any space between the wall and unit will
cause noise and vibration.
b) If the Wall is Brick, Concrete or Similar
Drill 3/16 in. dia. holes in the wall. Insert rawl plugs for
appropriate mounting screws. (Fig. 3-29)
KH3642
Confirm that the wall is strong enough to support the unit.
0943_T_I
Fig. 3-28
3/16 in.
dia. hole
Rawl plug
0944_T_I
Fig. 3-29
a) If the Wall is Wooden
(1) Attach the wall fixture to the wall with the 12
screws provided. (Fig. 3-30) If you are not able to
line up the holes in the wall fixture with the beam
locations marked on the wall, use rawl plugs or
toggle bolts to go through the holes on the panel
or drill 3/16 in. dia. holes in the wall fixture over
the stud locations.
(2) Check with a tape measure or carpenter’s level
that the wall fixture is level. This is important so
that the unit is correctly installed.
(3) Make sure the wall fixture is flush against the
wall. Any space between the wall and unit will
cause noise and vibration.
b) If the Wall is Brick, Concrete or Similar
Drill 3/16 in. dia. holes in the wall. Insert rawl plugs for
appropriate mounting screws. (Fig. 3-29)
Wall fixture
1355_M_I
Fig. 3-30
24
S4359146
3-13.
Removing the Casing to Install the Indoor Unit
KH2442
How to Remove the Casing
(1) Remove the plastic cover. (Fig. 3-31)
(2) Remove the clamp for the wiring connector.
(Fig. 3-32)
(3) Disconnect the wiring connector. (Fig. 3-33)
(4) Set the flap in the horizontal position. (Fig. 3-34)
Plastic cover
Screw
22
2
22
K
(5) Remove the 3 screws. (Fig. 3-34)
(6) Remove the casing. (Fig. 3-34)
NOTE
When replacing the casing, be careful not to crush
the lead wires between the casing and the frame.
(Fig. 3-34)
Casing
Frame
Flap
Clamp
Screw
0945_T_I
Fig. 3-31
Fig. 3-32
2023_T_I
Wiring
connector
Screws
Fig. 3-34
0947_T_I
Fig. 3-33
2024_T_I
25
S4359146
22
1358_T_I
Hack
saw
2
22
K
3-14. Preparing the Indoor Side Tubing
KH2442
Tubing can be extended in 4 directions as shown in
Fig. 3-35.
Arrangement for Left Tubing
(a) Cut out the left tubing outlet. (Fig. 3-36)
Arrangement for Right Tubing
(a) Cut out the right tubing outlet using a hacksaw.
(Fig. 3-37)
Arrangement for Left-rear and Right-rear Tubing.
(a) It is not necessary to cut a hole.
KH3642
Tubing can be extended in 4 directions as shown in
Fig. 3-35.
Left
tubing
Left tubing
outlet
Fig. 3-36
Left-rear
tubing
0950_T_I
Fig. 3-35
Right-rear
tubing
(Recommended)
Right tubing
0949_T_I
Right tubing
outlet
0951_T_I
Fig. 3-37
Arrangement for Right-rear Tubing
(a) Remove the 2 screws and slide out the side
cover. (Fig. 3-38)
(b) Extend the wide tube from the outdoor side and
connect it directly to the mating tube inside the
indoor unit. Use a flare nut. (Fig. 3-39)
Arrangement for Right Tubing
(a) Remove the 2 screws and take off the side cover.
(Fig. 3-38)
(b)Cut out the L-shaped tubing outlet using a hacksaw.
(Fig. 3-40)
(c)Using the L-shaped tube (field supply), connect
tubing between the indoor and outdoor units.
(Fig. 3-42)
Arrangement for Left and Left-rear Tubing.
(a) Remove the 4 screws (2 on each side) and take
off both left and right side cover. (Fig. 3-41)
(b) Remove 4 screws to remove the bottom cover.
(c)Using the L-shaped tube (field supply), connect
tubing as in Fig. 3-43.
Fig. 3-38
1356_T_I
Tubing
from the
outdoor
unit
1357_T_I
Fig. 3-39
Left
side
cover
Indoor unit
Bottom
cover
Fig. 3-41
Right
side
cover
1361_T_I
L-shaped tube
Fig. 3-42
26
Fig. 3-40
L-shaped
tube
1359_T_I
1360_T_I
Fig. 3-43
S4359146
3-15. Wiring Instructions
General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the
unit as shown on its name plate, then carry out
the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit a power supply disconnect and circuit
breaker for overcurrent protection should be
provided in the exclusive line.
(3) To prevent possible hazards from insulation
failure, the unit must be grounded.
(4) All wiring must be connected tightly.
(5) Do not allow wiring to touch refrigerant tubing,
compressor, or any moving parts of the fan.
Unauthorized changes in the
internal wiring can be very
dangerous. The manufacturer will accept no responsibility for any damage or
misoperation that occurs as
a result of such unauthorized changes.
22
2
22
K
27
S4359146
22
I
2
22
K
3-16.
Wiring Instructions for Inter-Unit Connections
(a) Insert the inter-unit wiring (according to local
codes) into the through-the-wall PVC pipe. Run
the wiring toward the indoor side allowing approx.
5". to extend from the wall face. (Fig. 3-44)
Never fix the wiring by any
CAUTION
means before the indoor
unit is fully seated on the
rear panel.
(b) Remove the side cover and the metallic cover.
(Fig. 3-45 or 3-46, depending on model.)
(c)Secure the conduit connector to the chassis with
a lock nut. (Fig. 3-45 or 3-46)
(d) Give some play to the inter-unit wiring from the
outdoor unit to the corresponding terminals on the
terminal plate.
● Be sure to refer to the
CAUTION
wiring system diagram
label inside the metallic
cover and carry out the
correct field wiring.
Wrong wiring can cause
the unit to malfunction.
● Check local electrical
codes and any specified
wiring instructions or
limitations.
(e) Secure the metallic cover with its screw. Then
replace the side cover.
KH2442
Rear
panel
Wiring
KH3642
ConnectorWiring
Wall
Plastic
cover
5"
1362_T_I
Wall fixture
Wall
5"
KH2442
Lock
nut
Power line
Look nut
Elbow
conduit
Grounding
line
Fig. 3-45
Metallic cover
Plastic cover
Screw
0968_T_I
KH3642
Lock
nut
Connector
Fig. 3-44
Metallic cover
Fig. 3-46
Side cover
1363_T_
1395_T_I
S4359146
28
Loading...
+ 65 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.