Sage SIP, SRP, Prime SIP Series, Prime SRP Series Operation And Instruction Manual

SAGE THERMAL GAS MASS FLOW METER
Operations and
Instruction Manual
For Prime Models SIP and SRP
DOCUMENT NUMBER 100-0065
REVISION 16 - SIP/SRP (SAGE PRIME™)
Make the Wise Choice.
Choose Sage Flow Meters.
8 Harris Court, D1
Monterey, CA 93940
1-866-677-SAGE (7243)
Tel 831-242-2030
Fax 831-655-4965
www.sagemetering.com
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
3
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Table of Contents
Introduction Welcome . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SECTION A Unpacking Your Sage Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
G
etting Started
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Locating Proper Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Insertion Flow Meter Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sage Valve Assembly Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Compression Fitting Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Captive Flow Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Probe Insertion Guideline Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installation Depth Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Large Duct or Stack Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
In-line Flow Meter Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Terminal Hookup Prime Integral (Series SIP) . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
24 VDC Prime Integral Terminals Series SIP . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
AC Powered Prime and DC Powered Prime PLUS
Integral Terminals (Series SIP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Terminal Hookup Prime Remote (Series SRP). . . . . . . . . . . . . . . . . . . . . . . . . . . 21
24 VDC Prime Remote Terminals (Series SRP) . . . . . . . . . . . . . . . . . . . . . . . . . . 22
AC Powered Prime and DC Powered Prime PLUS
Remote Series Terminals (Series SRP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Junction Box Wiring Terminals for Remote Style Meters . . . . . . . . . . . . . . . . . 24
SECTION B Principle of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Specifications
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Sage PRIME Styles & Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Sage PRIME Organic (OLED) Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SECTION C SIP Series Integral Style Flow Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Drawings
SRP Series Remote Style Flow Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Remote Bracket Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Mounting Hardware:
SVA05 Series Isolation Valve Assembly for Insertion Meters . . . . . . . . . . . . 38
STCF Series Teflon Ferrule Compression Fitting . . . . . . . . . . . . . . . . . . . . . . 38
SVA05 Series Isolation Valve Assembly Detail . . . . . . . . . . . . . . . . . . . . . . . . 38
Mounting Plate for Thin Walled Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
continued on next page
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
4
REV. 16-SIP/SRP
SECTION C SVA05LP Low Pressure Isolation Valve Assembly. . . . . . . . . . . . . . . . . . . . . . . . 39
Drawings
In-Line and Insertion Flanges. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
SECTION D Common Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Diagnostics
In-Situ Calibration Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
SECTION E Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Warranties and Service Work
Cancellation/Return Policy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Returning Your Sage Flow Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Return Material Authorization Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
SECTION F Modbus Register Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Modbus
Modbus Protocol & Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Sage Register Output Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Sage Addresser Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Sage Addresser Typical Printout (Version 3.14) . . . . . . . . . . . . . . . . . . . . . . . . . 62
SECTION G Sage Prime™ Field Programmable “Dongle” . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Appendix
Correction Factors For Varying Gas Mixes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Installations Where Pipe Condensation May Develop . . . . . . . . . . . . . . . . . . . 66
J-Box and Upstream Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
What Is a Thermal Mass Flow Meter? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
5
Welcome
We are pleased that you have purchased a Sage Metering Mass Flow Meter for your requirement. We hope that you are satisfied with the performance, operation and design of our highly precise, NIST traceable Thermal Gas Mass Flow Meter.
S
age Metering is your source for monitoring, measuring and controlling the gas mass flow in your industrial process, building management system or environmental appli ­cation. Our high performance, NIST Traceable,Thermal Mass Flow Meters will help increase productivity, reduce energy costs, maximize product yields, and/ or help reduce environmental insult. Sage provides high quality In-Line and Insertion Thermal Mass Flow Meters for a wide variety of industrial, commercial, and environmental monitoring needs, including carbon credit verification for Greenhouse Gas reduction.
Sage Meters measure mass flow directly — there is no need for ancillary instrumentation such as temperature or pressure transmitters. Furthermore, our instruments have excep­tional signal sensitivity, have no moving parts, require little if any maintenance, have negligible pressure drop and have a turndown up to 100 to 1, and resolve as much as 1000 to 1. Sage Flow Meters can measure the mass flow rate and consumption of air, oxygen, natural gas, nitrogen, digester gas, biogas, flare gas, hydrogen, argon, carbon dioxide and other gases and gas mixes.
Sage Prime is the latest addition to our family of high performance Thermal Mass Flow Meters. It features a bright graphical display of Flow Rate,Total and Temperature, robust industrial enclosure, and easy to access power and output terminals. Sage Prime has a dual-compartment windowed enclosure featuring a very high contrast photo-emissive OLED display with a new photocell activated Screen Saver. The rear compartment, which is separated from the electronics, has large, easy to access and well marked ter ­minals, for ease of customer wiring. It is powered by 24 VDC (12 VDC optional, or 115/230 VAC). The power dissipation is under 2.5 watts (e.g. under 100 ma at 24 VDC for the DC version.)
Please let us know if we can assist you in any way with your Sage Meter, or if you have any questions about its installation, operation, or features. Simply phone us at 866-677-SAGE (7243), or visit our website at www.sagemetering.com to contact a factory representative in your area. (To access this manual on the website, enter in user name: sage; passcode 7243737 when prompted.)
Sincerely,
Robert Steinberg
President
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Section
GETTING STARTED
A
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
UNPACKING YOUR SAGE METER
Your Sage flow meter is a sensitive, yet rugged,
p
recision built electronic instrument. Upon delivery,
care should be taken when opening the shipping
container and removing your meter. The meter
should be inspected for any damage that may have
occurred during transit. If damage is found, please
contact the carrier immediately to place a claim for
damaged goods. The contents of the container
should be checked against the packing list for any
discrepancies. If there are any questions as to the
contents or configuration of the equipment includ-
ing calibration ranges, or, mounting hardware,
contact Sage Metering as soon as possible. Please
save shipping container and packaging materials
(including PVC tube probe protector on Sage
Insertion Flow Meters) in case the unit needs to
be returned for any reason.
MAINTENANCE
Sage thermal mass flow meters essentially require
little or no maintenance. While the sensing element
is somewhat resistant to dirt and particulate build
up, it may become necessary to clean it from time to
time if mounted in extremely dirty environments.
NOTE: ALWAYS REMOVE THE POWER PRIOR TO
ANY CLEANING OR MAINTENANCE. A detergent or
appropriate non-corrosive solvent for removing the
buildup may be required. A soft brush can be used
to gently clean the sensing element’s surface, using
caution to avoid damaging the sensor elements
(the RTDs). If any disassembly is necessary, contact
Sage Metering, Inc. for instructions. In general, it is
recommended that your Sage Thermal Mass Flow
Meter be returned to the factory if cleaning,
repair, or recalibration is needed. This is usually
the most cost-effective and reliable alternative.
CALIBRATION
Sage Prime has continuous diag nostics. The raw
cali bration milliwats (mw) is always displayed in the
upper left hand corner of the meter's display. At any
time, you can check this reading at a “no flow” con-
dition and compare the reading to the original re -
ported “zero flow” value noted on the last few lines
of your meter’s Certificate of Conformance or the
flow meter’s data tag. This diagnostic procedure not
only checks the sensor performance and the “live
zero” calibration point, but it verifies that the sensor
is clean. It essentially provides a means to validate
the meter’s performance, verifies that there is no shift
or drift, and eliminates the need for annual factory
calibrations. This simple field diagnostic procedure
also verifies that the sensor is free from contamina-
tion, even without inspection. See “In-Situ
Calibration Check” on page 46.
Getting Started
9
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
a
CAUTION cable glands shipped with unit are for shipping purposes only.
Remove shipping cable glands before installing.
a
CAUTION If installing in a Class I hazardous location the installation
must comply with appropriate electrical codes.
a
CAUTION Installer must supply proper ground and bond wire for the
transmitter and the sensor per appropriate electrical codes
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
10
INSTALLATION AND MOUNTING
Check the Certificate of Conformance included
with your Sage Thermal Mass Flow Meter for
system pressure, temperature, gas composition,
power input, and signal output.
It is recommended that the flow meter be inserted in
a location of maximum straight run. It is suggested
that there be a minimum of 15 pipe diameters of
straight run upstream, and 5 diameters downstream,
depending on the conditions. See chart on page 11.
Note, obstructions such as valves, blowers, expand -
ers and PVC and HDPE pipes will require addition-
al straight run (contact factory for assistance).
Check the orientation1: Standard calibration flow
direction is left to right when facing the flow
meter. Gas flow direction is marked with an arrow
on in-line flow meters; UPSTREAM is marked on
insertion probes.
Do not rotate probe1, or errors may occur. If enclo-
sure is facing incorrectly, rotate the enclosure 180˚,
but do not rotate the probe. The UPSTREAM mark
still needs to be facing Upstream.
Hook up the system per the wiring diagram provid-
ed with your Sage flow meter (see inside of rear
compartment cover for terminal designation).
Double check that wiring for the proper power and
signal connections are correct.
Check that all plumbing and electrical hook-ups
are in accordance with OSHA, NFPA, and all other
safety requirements.
For Remote Style Meters (SRP) be sure the Remote
Electronics is matched with the Transmitter’s
Junction Box and its attached Probe or Flow
Body. There will be Metal Serial Number Tags
on both the Transmitter as well as the Remote
Electronics enclosure. Do not mismatch the seri-
al numbers of the Remote Electronics and the
Junction Box, or calibration errors will occur.
LOCATING PROPER WIRING DIAGRAM
1) Look at the sticker on your meter. The first three
digits describe the basic model that you have.
Refer to the appropriate page numbers below for
your wiring diagram
2) SIP: see page 19
3) SRP: see page 22 for input/output terminals;
see page 24 (Junction Box Wiring Terminals
for Remote Style Meters)
WIRING
Follow the instructions below to remove the rear cap
for wiring. CAUTION: Do not open the display side!
Before removing the rear cap to access the wiring
terminals it is essential to completely remove the
screw assembly on the side of the rear enclosure to
free up the threads so the lid can be removed. Note
there is a Red Tag attached to the screw assembly
stating “Remove Screw Before Opening Lid”.
After the wiring is completed (see pages 18 to 23
for wiring details), please close the lid, and reinsert
the screw assembly in the same manner.
Note: See “Approvals” page for Hazardous Location
Approvals (DC Powered Meters Only)
REV. 16-SIP/SRP
1 The Integral Style of Sage Prime Insertion Meters have the Display oriented as shown on page 14.
If an alternate orientation of the display, or enclosure is required (ie. installation into a vertical pipe), please furnish a sketch or drawing, and specify “ROTATE” on purchase order. However, if it is later determined that the enclosure needs to be rotated, that procedure can be done in the field. However, if the display needs to be rotated, then the meter must be sent back to Sage to be modified. Do not attempt this in the field. An RMA will be required prior to returning the meter (see page 51). The procedure for rotating the enclosure is as follows: Clamp the enclosure of the Prime in a vise with the probe pointing up to the ceiling. Then take a 7/8 wrench and turn the probe to the proper orienta­tion. Lock the probe into its new position with a set screw (not provided).
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
11
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
FLOW PROFILE AND INSTALLATION
CONSIDERATIONS
Insertion Flow Meters, although generally easier to
install that In-Line Flow Meters, require proper
installation, and a well developed flow profile, in
order to perform properly. Please refer to the section
on the following pages titled PROBE INSERTION
GUIDELINE DRAWING (page 14) and INSTALLA-
TION DEPTH CHART (page 15).
SAGE VALVE ASSEMBLY OPERATION
Valve assemblies (SVA05 and SVA05LP) are an op -
tional mounting hardware for Insertion Style Flow
Meters (see pages 38 and 39). They allow the removal
of insertion-style meters for service, cleaning, recali -
bration, relocation, etc. without the need to “shut-
down” your process. The probe insertion depth is
adjustable to permit sensor to be located at center
to optimize measurement accuracy. (Refer to PROBE
IN SERTION GUIDE LINE DRAWING and CHART, pages
14 & 15.) The ball valve will seal off leaks of the
process gas at the point of insertion after the probe
assembly has been removed. The assembly includes
a valve, threadolet, compression fitting with Teflon
ferrule, a cable restraint, and two collar clamps.
A threaded half coupling (3/4" FNPT) properly sized
to accom modate the isolation valve retractor assem-
bly must be fitted to the pipe/duct to which the
insertion probe will be inserted. Avoid T-Fittings
since they will disturb the flow profile, and effec-
tively reduce the measurement area. Direct thread-
ing together (or with necessary bushings) of the
retractor assembly may be required. In other cases,
the threadolet must be welded in place and a clear-
ance hole must be drilled through the pipe/ duct to
accept the probe assembly. If the pipe/duct is under
pressure during installation, a hot tap drill (not
available through Sage Metering) may be required.
FLOW CONDITIONING AND STRAIGHT RUN
Although a minimum of 15 pipe diameters of
upstream straight run is commonly recommended,
to absolutely assure that the flow profile is well
developed at the point of measurement, either use
Flow Conditioners (standard in Sage In-Line Flow
Meters, 1/2" and larger, and also available as assem-
blies for Insertion Flow Meters, see page 13), or
consider additional straight run. The Chart below
provides examples of the amount of straight run
that would virtually assure that there are no flow
disturbances at the point of measurement.
N O T E : Detailed Drawings are shown on pages 38 & 39.
Insertion Flow Meter Application
IMPO RTANCE OF FLO W CO NDITION ING
Reco mmen ded P ipe D iameter s Ups tream
One 90˚ Elbow
Two 90˚ Elbows
in the same plane
Two 90˚ Elbows
in different planes
4:1 Area Reduction
4:1 Area Expansion
Multiple Disturbance
3
5
9
3
10
TBD
1
This column applies to In-Line Flow Meters, which come standard with built-in Flow Conditioners, as well as Insertion Meters, when provided with upstream Captive Flow Conditioners (see page 13).
D I S T U R B A N C E
15
20
At least 40
15
At least 30
To Be Determined
WITHOUT
FLOW CONDITIONING
Minimum Industry Recommendation
WITH FLOW
CONDITIONING
1
Sage
Recommendation
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
12
REV. 16-SIP/SRP
COMPRESSION FITTING OPERATION
A bored through tube fitting, properly sized to
accommodate an insertion probe’s particular OD,
can be provided by the user or purchased as an
option from Sage Metering (see page 38). Prior to
installation, a clearance hole to accommodate the
insertion probe assembly must be drilled in the
pipe/duct. A fitting (1/2" FNPT) is then welded in
place or threaded into the half-threadolet which has
been welded to the pipe/duct. The probe insertion
depth is adjustable to permit sensor to be located at
center, to optimize measurement accuracy. (Refer to
PROBE INSERTION GUIDELINE DRAWING and
CHART, pages 14 & 15.)
Insert the probe shaft tubing into the compression fitting to the position indicated in the Probe Insertion guidelines.
While holding the fitting body steady, tighten the nut one and one-quar ter turns to the 9 o’clock position.
INSTALLATION INSTRUCTIONS
1. Insert tubing into the tube fitting.
2. Make sure that the tubing is positioned properly
per the PROBE INSERTION GUIDELINE DRAW-
ING AND CHART, pages 14 & 15.
3. Due to the variations of tubing diameters, a
common starting point is desirable. Therefore,
tighten the nut until the tubing will not turn
by hand or move axially in the fitting.
4. Scribe the nut at the 6 o’clock position.
5. While holding fitting body steady, tighten the nut
1
1
4 turns to the 9 o’clock position.
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
13
S A G E M E T E R I N G , I N C .
ANSI Class Flanges (user supplied)
Largest of the Two Perforated Plates
Flow Conditioning Assembly is inserted here.
One Pipe Diameter
FLOW
Gaskets
One Pipe
Diameter
Straight Run Requirement
from this Flange
CAPTIVE FLOW CONDITIONERS Can Be Installed in Conjunction with Insertion Style Flow Meters
NOTE: The larger of the two perforated plates of the Sage Flow Conditioning assembly is positioned between two flanges and two gaskets as shown. The smaller of the two perforated plates of the conditioner will freely slide into the application pipe, facing downstream. The probe mounting hardware will be placed one diameter downstream of the downstream plate. Probe location must be one pipe ID diameter downstream of Flow Conditioners or errors will occur.
Front View of one of the Conditioning Plates
IMPORTANT The location of the probe must be exactly one pipe ID diameter (i.e., 4” in a 4” pipe; 6” in a 6” pipe, etc.) downstream of the Captive Flow Conditioning assembly. The Captive Flow Conditioners are always designed to be separated by one pipe diameter. See drawing below. The probe location must be one pipe ID diameter downstream of Flow Conditioner, or errors will occur.
Note: See table on page 11 (last Column) for Straight Run Requirement
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
14
REV. 16-SIP/SRP
PROBE INSERTION GUIDELINE DRAWING
1
Choose the longest straight-run section of pipe avail-
able to allow a uniform, well-developed flow profile.
A
llow for a minimum of 15 pipe diameters of straight
run upstream, and 5 diameters downstream, depend-
ing on the conditions. See chart on page 11. Note,
obstructions such as valves, blowers expanders and
PVC and HDPE pipes will require additional straight
run (contact factory for assistance). Avoid, if possible,
installations immediately downstream of bends, fans,
nozzles, heaters and especially valves, or anything
else installed in the line that may cause nonuniform
flow profiles and swirls. Otherwise signal output
errors could result, unless significantly more straight
run is provided, or in the absence of sufficient straight
run, Flow Conditioners (page 13) are in stalled (con-
tact Sage for assistance if needed). Refer to page 13 to
see the benefits of incorporating Flow Conditioners.
Insertion styles are available through Sage Metering,
Inc. with a standard 1/2" OD probe support assem-
bly; 3/4" is also available. Stan dard probe lengths
are 6", 12", 15", 18", 24", 30", 36" and 48". A common
method of mounting the probe assembly through
a pipe wall or duct (if ambient air) is with a compres-
sion fitting (STCF05). A Sage valve assembly (SVA05)
is useful and highly recommended for
pressurized applications or other gases,
such as Natural Gas. Flange mounting
is optionally available.
Sage insertion style flow meters can be assembled
and calibrated for use in virtually any size pipe or
duct (as small as 1”). Sage insertion flow meters
include a probe assembly that supports the sensing
element (a self-heated flow sensor and a tempera -
ture/reference sensor); a sensor drive circuit; micro -
pro cessor meter board, and trans mitter enclosure.
The probe assembly must be inserted into the correct
position in the pro cess gas flow conduit to allow the
gas to flow through the sensor “window” across the
sensor element. The “sensing point” or active part of
the sensor (0.5" from the end of the probe) should be
positioned as per the drawing below and the
Installation Depth Chart on page 15.
Installation Depth
The center of the pipe (assuming a well developed
turbulent flow profile) is fairly flat, and easy to
locate. See “Installation Depth Chart” on next page
to determine proper insertion depth.
Z
Y
X
4" PIPE SHOWN
LESS THAN IDEAL LOCATION Contact Factory for Assistance
GOOD LOCATION
2,3
(See Installation Depth Chart for X and Y Dimension)
2. Probe should be inserted per Installation Depth Chart (see following page), so sensors are in the center of the pipe.
3. The portion of the probe that remains outside of the pipe, is simply the factory ordered probe length (i.e. “-15” = 15 inches) minus the “Y” dimension.
Center of Pipe
PRIME
84˚F
1
3546
SCFM
4
67469670
SCF
88mW
1. SIP Industrial Meter shown in drawing. Note, probe is not bi-directional.
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
15
S A G E M E T E R I N G , I N C .
I
NSTALLATION DEPTH CHART
Methods for Probe Insertion to Pipe Center
ME TH OD 1
Using charts below, select pipe size (column 1),
determine X. Insert probe until the end touches the
bottom of the pipe (ID), mark probe as it exits top
of fitting. Lift probe distance “X” and tighten com -
pression fitting.
ME TH OD 2
Using charts below1, select pipe size (column 1),
determine Y. Subtract Y from the factory supplied
probe length. That difference Z (see drawing on page
14) should be outside of the pipe, and is measured
from the bottom of the enclosure of the probe weld
to pipe OD.
PIPE SIZE OD ID XYPIPE AREA
1"
1.5" 1.900 1.500 .15" 1.56" 0.0123
2" 2.375 1.939 .35" 1.82" 0.0205
2.5" 2.875 2.323 .55" 2.07" 0.0294
3" 3.500 2.900 .80" 2.38" 0.0459
4" 4.500 3.826 1.30" 2.86" 0.0798
6" 6.625 5.761 2.25" 3.95" 0.1810
8" 8.625 7.625 3.25" 4.90" 0.3171
10" 10.750 9.750 4.25" 6.00" 0.5185
12" 12.750 11.374 5.13" 7.00" 0.7056
14" 14.000 12.500 5.70" 7.50" 0.8522
16" 16.000 14.312 6.60" 8.60" 1.1172
18" 18.000 16.124 7.50" 9.60" 1.4180
24" 24.000 21.562 10.25" 12.60" 2.5357
S C H E D U L E 4 0 P I P E
2
S C H E D U L E 8 0 P I P E
2
PIPE SIZE OD ID XYPIPE AREA
1"
1.5" 1.900 1.610 .20" 1.56" 0.0141
2" 2.375 2.067 .40" 1.82" 0.0233
2.5" 2.875 2.469 .60" 2.07" 0.0332
3" 3.500 3.068 .90" 2.38" 0.0513
4" 4.500 4.026 1.40" 2.86" 0.0884
6" 6.625 6.065 2.40" 3.95" 0.2006
8" 8.625 7.981 3.40" 4.90" 0.3474
10" 10.750 10.020 4.40" 6.00" 0.5476
12" 12.750 11.938 5.50" 7.00" 0.7773
14" 14.000 13.124 6.00" 7.50" 0.9394
16" 16.000 15.000 7.00" 8.60" 1.2272
18" 18.000 16.876 8.00" 9.60" 1.5533
24" 24.000 22.625 10.75" 12.60" 2.7919
C O N S U L T F A C T O R Y
C O N S U L T F A C T O R Y
1
For other Pipe Schedules, such as Schedule 10, contact Sage, however the Y dimension will
be the same for any Schedule Pipe
2
The 1" Pipe Size needs to have the Probe “Bottomed Out” (option “BOT"); the calibration method for the 1
1
2" Pipe is either as shown below, or with option “BOT”
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
16
REV. 16-SIP/SRP
P
RIME
84˚F
1
3546
SCFM
467469670
SCF
88mW
P
RIME
8
4
˚
F
13546 SCFM
4
67469670
SCF
88mW
PRIME
84˚F
13546 SCFM
467469670
SCF
88mW
PRIME
8
4
˚
F
1
3546
S
CFM
4
67469670
S
CF
8
8mW
CONFIGURATION FOR UTILIZING FOUR (4) SAGE INSERTION MASS FLOW METERS FOR LARGE ROUND PIPES OR DUCTS LARGER THAN 36" TO MINIMIZE EFFECTS OF VARYING FLOW PROFILES (It is recommended that Factory be contacted to assist with applications of this nature)
The outputs of the four meters will be averaged by customer’s PLC or other method to improve overall accuracy in measuring the flow rate. (For medium sized round pipes [18" to 36"], two meters, on the opposite side of the same diameter, may be sufficient [insert parallel to an upstream 90 degree bend for optimal benefit.]) Note, in this configuration, each sensor needs to be averaged.
1/2" NPT User Entry for Wiring
1/2" NPT User Entry for Wiring
3/4" NPT for
Probe Support
3/4" NPT for
Remote Cable
3/4" NPT for
Remote Cable
Large Duct or Stack Applications
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
17
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
IN-LINE FLOW METERS
In-line mounting styles are available through Sage
Metering, Inc. in sizes from 1/4" pipe through 4"
pipe. Threaded male NPT ends are standard up to
2-1/2"; ANSI 150lb flanged ends are recommended
for 3" and 4" models. Contact the factory if optional
end mounting styles are required. Pipe sizes in excess
of 4" require the insertion style mass flow meter.
The in-line style flow meter assembly flow section is
typically specified to match the user’s flow conduit
and is plumbed directly in the flow line by thread-
LENGTH “L” SAME AS NON-FLANGED METER (See table on page 27. For example, 1"x8" flow body has an 8" length. The length will be the same whether an NPT flow body, or whether flanged. If a flanged flow body, the 8" dimension will be a Face-to-Face dimension.)
FLOW CONDITIONING SCREENS FOR IN-LINE FLOW BODIES 1/2" AND UP
1
Screens shown with NPT fitting.
1 Note, Flow conditioning is also available for Insertion Meter applications (see page 13)
ing, flanging, welding, etc. DO NOT USE REDUCERS.
It includes the sensing element (a self-heated flow
sensor and a temperature/reference sensor) mounted
directly in the specified flow section for exposure to
the process gas; a sensor drive circuit; microprocessor
meter board, and transmitter enclosure.
All in-line Flow Meters, 1/2" and up have built-in
Flow Conditioners. See Table (page 10) for Upstream
Straight run requirements. Note, the 1/4" and 3/8"
do not have Flow Conditioners and thus require
more straight run.
In-Line Flow Meter Application
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
18
REV. 16-SIP/SRP
Prime Integral (Series SIP)
SEE “WIRING” ON PAGE 10 FOR INSTRUCTIONS ON HOW TO REMOVE REAR LID; SEE FOLLOWING PAGES FOR TERMINAL HOOKUP
1 RED AC1 COM 1
2
S1 AC2 B + 2
3
RED SPARE A – 3
4
WHITE
4-20mA PWR
4
5
S2 4-20mA 5
6
WHITE VDC GND 6
A B C
24 VDC P
ULSE
VDC IN
+
VDC GND
INTEGRAL
INSIDE COVER VIEW INSIDE BODY VIEW
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Probe Support
NO CUSTOMER ACCESS DO NOT OPEN THIS SIDE
DISPLAY SIDE
1/2" NPT
View Entry
(ONE ON EACH SIDE)
FLOW
TERMINAL BLOCK SIDE
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
19
S A G E M E T E R I N G , I N C .
24 VDC Prime Integral Terminals (Series SIP)
(APPROVED FOR HAZARDOUS SERVICE6)
1 RED AC1 COM 1
2
S1 AC2 B +
2
3
RED SPARE A –
3
4 WHITE
4-20mA PWR
4
5
S2 4-20mA 5
6
WHITE VDC GND
6
A B C
2
4 VDC
PULSE
VDC IN
+
VDC GND
I
NTEGRAL
INSIDE COVER VIEW
NOTE: The Sage Prime draws 2.4 watts maximum (i.e. 100ma @24VDC)
+
C
U STO ME R
R ET UR N
E
X TE RN AL LY P OW ER ED
4 –2 0 mA BY C US TO ME R
+
*
DESCRIPTION TERMINALS NOTES
DC Input Power: B5 B6 24 VDC
7,8
+ VDC – VDC GND
Internally Powered: C5 C6 Do not remove 4-20 mA
4-20 mA Return
any Jumpers
SIGNAL DRIVE
Internally Powered: C4 C6 Do not remove Pulsed Output
GND
any Jumpers
Externally Powered: C5 B4 Remove B4 & B5 4-20 mA
4-20 mA 4-20 mA
Jumper
SIGNAL DRIVE EX TERNAL SOURCE
Externally Powered9: C4 B3 Remove B4 & B5 Pulsed Output
JUNCTION FOR
Jumper and Connect
PULSE RETURN C4 Resistive Jumper
to B3
MODBUS C2 C3 C1 Modbus Ground
10
RS485(+) RS485(–) MODBUS GROUND
(REQ’D)
*B4 and B5 JUMPER Remove jumper for Externally Sourced 4-20 mA. In this mode, user supplies 9-27 Volts to externally power the 4-20 mA loop, and the 4-20 mA loop becomes optically isolated.
1 Specify the Sage Prime PLUS option in order to have the Modbus Ground (Terminal C1, COM) isolated
from the 24 VDC Sage Power Supply Ground (Terminal B6). All other features of Prime PLUS are identical to the standard Sage Prime, except other voltage available. (See footnote 8)
2 It is important to connect the Ground when using Modbus communications, or ground loop problems
may develop. Improper wiring can also damage internal circuitry
3 Note, if customer externally powers the 4-20 mA by removing the jumper, the Pulse voltage output
is also effected: The voltage output of the Pulse will follow the customer power (i.e. 24 VDC external power will result in a 24 VDC Pulse [maximum of 50 mA]; 12 VDC external power will result in a 12 VDC Pulse)
4 Pulse width 250 msec default (adjustable with Addresser software) 5 Using Sage Addresser, a Low Flow Cutoff (LFC), commonly referred to as Min Cutoff or Zero Cutoff
can be entered into the FLOW MIN Functions. In Versions 1.82 or higher, the Low Flow Cutoff and the 4-20 mA Scaling are independent of each other. For example: A Low Flow Cutoff (LFC) of 10 SCFM on a Meter with a Full Scale of 100 SCFM will report 0 on the Display and 4 mA on the output. The output will remain at 4 mA until the LFC is exceeded: (ie: 25 SCFM=8 mA). Thus the 4 mA will always be zero based
6 Class I, Div 2, Groups B,C,D,T4 and ATEX Ex na IIC T4 7 24 VDC ±10% 8 Other DC voltages (5 VDC, 12 VDC, 48 VDC) available on Prime PLUS. Contact Sage 9 Assumes the 4-20 mA is Externally Powered
10 Modbus Ground becomes isolated from the B6 Power Supply Ground only on Prime PLUS version
(specify “PLUS”)
INSIDE BODY VIEW
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Remote Cable
(on Remote Style SRP)
**
**Note, Flow Meter is supplied with a 10K (1/2 watt) metal film resistor (Resistive Jumper) connected across Terminals C4 and C6. For externally powered operation, in addition to removing B4 & B5 Jumpers, it is necessary to connect C4 Resistive Jumper to Terminal B3 instead of C6. Note, B3 must be connected to the External Sources com­mon in order to enable the optically isolated pulse output. In this mode, Pulse Output is optically isolated. Pulsed Output voltage will depend on customer source voltage. Use Sage Resistive Jumper only!
**
A1 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT) A2 – NO WIRE A3 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT) A4 – WHITE – TEMPERATURE SENSOR WIRE A5 – NO WIRE A6 – WHITE – TEMPERATURE SENSOR WIRE
B3 – JUNCTION FOR ISOLATED PULSE B4 – 4-20 mA RETURN (–) AND PULSE SOURCE B5 – VDC IN – VOLTAGE DC – POSITIVE (+) B6 – VDC GND – VOLTAGE DC – GROUND (–)
1
C1 – COM – RS485 MODBUS GROUND
1,2
C2 – B(+)–RS485_D1 C3 – A(–)–RS485_D0 C4 – 24 VDC PULSE – 0 TO 24 VDC PULSE OUTPUT
3,4
C5 – 4-20 mA – 4 TO 20 mA SIGNAL DRIVE
5
C6 – VDC GND – VOLTAGE DC – GROUND (–)
24
O
24
O
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
20
AC Powered Prime Integral Terminals (Series SIP)
6
1 RED AC1 COM 1
2
S1 AC2 B +
2
3
RED SPARE A –
3
4 WHITE
4-20mA PWR
4
5
S2 4-20mA 5
6
WHITE VDC GND
6
A B C
2
4 VDC
PULSE
VDC IN
+
VDC GND
I
NTEGRAL
INSIDE COVER VIEW
NOTE: The Sage Prime draws 2.4 watts maximum (i.e. 100ma @24VDC)
+
C US TO ME R
R ET UR N
E
X TE RN AL LY P OW ER ED
4
– 20 m A B Y CU ST OM ER
+
*B4 and B5 JUMPER Remove jumper for Externally Sourced 4-20 mA. In this mode, user supplies 9-27 Volts to externally power the 4-20 mA loop, and the 4-20 mA loop becomes optically isolated.
1 Specify the Sage Prime PLUS option in order to have the Modbus Ground (Terminal C1, COM) isolated
from the 24 VDC Sage Power Supply Ground (Terminal B6). All other features of Prime PLUS are identical to the standard Sage Prime, except other voltage available. (See footnote 8)
2 It is important to connect the Ground when using Modbus communications, or ground loop problems
may develop. Improper wiring can also damage internal circuitry
3 Note, if customer externally powers the 4-20 mA by removing the jumper, the Pulse voltage output
is also effected: The voltage output of the Pulse will follow the customer power (i.e. 24 VDC external power will result in a 24 VDC Pulse [maximum of 50 mA]; 12 VDC external power will result in a 12 VDC Pulse)
4 Pulse width 250 msec default (adjustable with Addresser software) 5 Using Sage Addresser, a Low Flow Cutoff (LFC), commonly referred to as Min Cutoff or Zero Cutoff
can be entered into the FLOW MIN Functions. In Versions 1.82 or higher, the Low Flow Cutoff and the 4-20 mA Scaling are independent of each other. For example: A Low Flow Cutoff (LFC) of 10 SCFM on a Meter with a Full Scale of 100 SCFM will report 0 on the Display and 4 mA on the output. The output will remain at 4 mA until the LFC is exceeded: (ie: 25 SCFM=8 mA). Thus the 4 mA will always be zero based
6 This version does not have Hazard Approvals 7 24 VDC ±10% 8 Other DC voltages (5 VDC, 12 VDC, 48 VDC) available on Prime PLUS. Contact Sage 9 Assumes the 4-20 mA is Externally Powered
10 Modbus Ground becomes isolated from the B6 Power Supply Ground only on Prime PLUS version
(specify “PLUS”)
INSIDE BODY VIEW
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Remote Cable
(ON REMOTE STYLE SRP)
Grounding
Lug
**
**
A1 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT) A2 – NO WIRE A3 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT) A4 – WHITE – TEMPERATURE SENSOR WIRE A5 – NO WIRE A6 – WHITE – TEMPERATURE SENSOR WIRE
B1 – AC1 – AC VOLTAGE B2 – AC2 – AC VOLTAGE B3 – JUNCTION FOR ISOLATED PULSE B4 – 4-20 mA RETURN (–) AND PULSE SOURCE B5 – VDC IN – VOLTAGE DC – POSITIVE (+) B6 – VDC GND – VOLTAGE DC – GROUND (–)
1
C1 – COM – RS485 MODBUS GROUND
1,2
C2 – B(+)–RS485_D1 C3 – A(–)–RS485_D0 C4 – 24 VDC PULSE – 0 TO 24 VDC PULSE OUTPUT
3,4
C5 – 4-20 mA – 4 TO 20 mA SIGNAL DRIVE
5
C6 – VDC GND – VOLTAGE DC – GROUND (–)
24
O
24
O
DESCRIPTION TERMINALS NOTES
AC Input Power: B1 B2 Connect Ground Wire 115 VAC/230 VAC
AC1 AC2
to Grounding Lug
DC Input Power: B5 B6 24 VDC
7,8
+ VDC – VDC GND
Internally Powered: C5 C6 Do not remove 4-20 mA
4-20 mA Return
any Jumpers
SIGNAL DRIVE
Internally Powered: C4 C6 Do not remove Pulsed Output
GND
any Jumpers
Externally Powered: C5 B4 Remove B4 & B5 4-20 mA
4-20 mA 4-20 mA
Jumper
SIGNAL DRIVE EX TERNAL SOURCE
Externally Powered9: C4 B3 Remove B4 & B5 Pulsed Output
JUNCTION FOR
Jumper and Connect
PULSE RETURN C4 Resistive Jumper
to B3
MODBUS C2 C3 C1 Modbus Ground
10
RS485(+) RS485(–) MODBUS GROUND
(REQ’D)
*
**Note, Flow Meter is supplied with a 10K (1/2 watt) metal film resistor (Resistive Jumper) connected across Terminals C4 and C6. For externally powered operation, in addition to removing B4 & B5 Jumpers, it is necessary to connect C4 Resistive Jumper to Terminal B3 instead of C6. Note, B3 must be connected to the External Sources com­mon in order to enable the optically isolated pulse output. In this mode, Pulse Output is optically isolated. Pulsed Output voltage will depend on customer source voltage. Use Sage Resistive Jumper only!
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
21
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Prime Remote (Series SRP)
SEE “WIRING” ON PAGE 10 FOR INSTRUCTIONS ON HOW TO REMOVE REAR LID; SEE FOLLOWING PAGES FOR TERMINAL HOOKUP
REMOTE
1
RED AC1 COM
1
2
GREEN AC2 B +
2
3
BLUE SPARE A –
3
4
WHITE
4-20mA PWR 24 VDC PULSE
4
5
BLACK VDC IN 4-20mA
5
6
ORANGE VDC GND VDC GND
6
A B C
1
2
3
4
5
6
1
2
3
4
5
6
A B C
INSIDE COVER VIEW INSIDE BODY VIEW
DISPLAY SIDE
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Remote Cable
(ON REMOTE STYLE SRP)
3/4" NPT for
Remote Cable
3/4" NPT for
Probe Support
Junction Box contains no electronics, just terminals
1/2" NPT
User Entry for Wiring
(ONE ON EACH SIDE)
FLOW
TERMINAL
BLOCK SIDE
3/4" NPT for
Remote Cable
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
22
24 VDC Prime Remote Terminals (Series SRP)
(APPROVED FOR HAZARDOUS SERVICE6)
R
EMOTE
1
RED AC1 COM
1
2
GREEN AC2 B +
2
3
B
LUE SPARE A –
3
4
W
HITE 4-20mA PWR
2
4 VDC PULSE
4
5
B
LACK VDC IN 4-20mA
5
6
O
RANGE VDC GND VDC GND
6
A B C
A1 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT) A2 – GREEN – SENSE WIRE A3 – BLUE – VELOCITY SENSOR WIRE (HEATED ELEMENT) A4 – WHITE – TEMPERATURE SENSOR WIRE A5 – BLACK – SENSE WIRE A6 – ORANGE – TEMPERATURE SENSOR WIRE
B3 – JUNCTION FOR ISOLATED PULSE B4 – 4-20 mA RETURN (–) AND PULSE SOURCE B5 – VDC IN – VOLTAGE DC – POSITIVE (+) B6 – VDC GND – VOLTAGE DC – GROUND (–)
1
C1 – COM – RS485 MODBUS GROUND
1,2
C2 – B(+)–RS485_D1 C3 – A(–)–RS485_D0 C4 – 24 VDC PULSE – 0 TO 24 VDC PULSE OUTPUT
3,4
C5 – 4-20 mA – 4 TO 20 mA SIGNAL DRIVE
5
C6 – VDC GND – VOLTAGE DC – GROUND (–)
INSIDE COVER VIEW
NOTE: The Sage Prime draws 2.4 watts maximum (i.e. 100ma @24VDC)
+
C US TO ME R
R ET UR N
E
X TE RN AL LY P OW ER ED
4
– 20 m A B Y CU ST OM ER
+
*
DESCRIPTION TERMINALS NOTES
DC Input Power: B5 B6 24 VDC
7,8
+ VDC – VDC GND
Internally Powered: C5 C6 Do not remove 4-20 mA
4-20 mA Return
any Jumpers
SIGNAL DRIVE
Internally Powered: C4 C6 Do not remove Pulsed Output
GND
any Jumpers
Externally Powered: C5 B4 Remove B4 & B5 4-20 mA
4-20 mA 4-20 mA
Jumper
SIGNAL DRIVE EX TERNAL SOURCE
Externally Powered9: C4 B3 Remove B4 & B5 Pulsed Output
JUNCTION FOR
Jumpers and Connect
PULSE RETURN C4 Resistive Jumper
to B3
MODBUS C2 C3 C1 Modbus Ground
10
RS485(+) RS485(–) MODBUS GROUND
REQ’D)
*B4 and B5 JUMPER Remove jumper for Externally Sourced 4-20 mA. In this mode, user supplies 9-27 Volts to externally power the 4-20 mA loop, and the 4-20 mA loop becomes optically isolated.
1 Specify the Sage Prime PLUS option in order to have the Modbus Ground (Terminal C1, COM) isolated
from the 24 VDC Sage Power Supply Ground (Terminal B6). All other features of Prime PLUS are identical to the standard Sage Prime, except other voltage available. (See footnote 8)
2 It is important to connect the Ground when using Modbus communications, or ground loop problems
may develop. Improper wiring can also damage internal circuitry
3 Note, if customer externally powers the 4-20 mA by removing the jumper, the Pulse voltage output
is also effected: The voltage output of the Pulse will follow the customer power (i.e. 24 VDC external power will result in a 24 VDC Pulse [maximum of 50 mA]; 12 VDC external power will result in a 12 VDC Pulse)
4 Pulse width 250 msec default (adjustable with Addresser software) 5 Using Sage Addresser, a Low Flow Cutoff (LFC), commonly referred to as Min Cutoff or Zero Cutoff
can be entered into the FLOW MIN Functions. In Versions 1.82 or higher, the Low Flow Cutoff and the 4-20 mA Scaling are independent of each other. For example: A Low Flow Cutoff (LFC) of 10 SCFM on a Meter with a Full Scale of 100 SCFM will report 0 on the Display and 4 mA on the output. The output will remain at 4 mA until the LFC is exceeded: (ie: 25 SCFM=8 mA). Thus the 4 mA will always be zero based
6 Class I, Div 2, Groups B,C,D,T4 and ATEX Ex na IIC T4 7 24 VDC ±10% 8 Other DC voltages (5 VDC, 12 VDC, 48 VDC) available on Prime PLUS. Contact Sage 9 Assumes the 4-20 mA is Externally Powered
10 Modbus Ground becomes isolated from the B6 Power Supply Ground only on Prime PLUS version
(specify “PLUS”)
INSIDE BODY VIEW
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Remote Cable
(ON REMOTE STYLE SRP)
**
**
24
O
24
O
**Note, Flow Meter is supplied with a 10K (1/2 watt) metal film resistor (Resistive Jumper) connected across Terminals C4 and C6. For externally powered operation, in addition to removing B4 & B5 Jumpers, it is necessary to connect C4 Resistive Jumper to Terminal B3 instead of C6. Note, B3 must be connected to the External Sources com­mon in order to enable the optically isolated pulse output. In this mode, Pulse Output is optically isolated. Pulsed Output voltage will depend on customer source voltage. Use Sage Resistive Jumper only!
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
23
S A G E M E T E R I N G , I N C .
AC Powered Prime Remote Terminals (Series SRP)
6
R
EMOTE
1
RED AC1 COM
1
2
GREEN AC2 B +
2
3
B
LUE SPARE A –
3
4
W
HITE 4-20mA PWR
2
4 VDC PULSE
4
5
B
LACK VDC IN 4-20mA
5
6
O
RANGE VDC GND VDC GND
6
A B C
INSIDE COVER VIEW
NOTE: The Sage Prime draws 2.4 watts maximum (i.e. 100ma @24VDC)
+
C US TO ME R
R ET UR N
E
X TE RN AL LY P OW ER ED
4 –2 0 mA BY C US TO ME R
+
*
DESCRIPTION TERMINALS NOTES
AC Input Power: B1 B2 Connect Ground Wire 115 VAC/230 VAC
AC1 AC2
to Grounding Lug
DC Input Power: B5 B6 24 VDC
7
,8
+ VDC – VDC GND
Internally Powered: C5 C6 Do not remove 4-20 mA
4-20 mA Return
any Jumpers
SIGNAL DRIVE
Internally Powered: C4 C6 Do not remove Pulsed Output
GND
any Jumpers
Externally Powered: C5 B4 Remove B4 & B5 4-20 mA
4-20 mA 4-20 mA
Jumper
SIGNAL DRIVE EX TERNAL SOURCE
Externally Powered9: C4 B3 Remove B4 & B5 Pulsed Output
JUNCTION FOR
Jumpers and Connect
PULSE RETURN C4 Resistive Jumper
to B3
MODBUS C2 C3 C1 Modbus Ground
10
RS485(+) RS485(–) MODBUS GROUND
(REQ’D)
*B4 and B5 JUMPER Remove jumper for Externally Sourced 4-20 mA. In this mode, user supplies 9-27 Volts to externally power the 4-20 mA loop, and the 4-20 mA loop becomes optically isolated.
1 Specify the Sage Prime PLUS option in order to have the Modbus Ground (Terminal C1, COM) isolated
from the 24 VDC Sage Power Supply Ground (Terminal B6). All other features of Prime PLUS are identical to the standard Sage Prime, except other voltage available. (See footnote 8)
2 It is important to connect the Ground when using Modbus communications, or ground loop problems
may develop. Improper wiring can also damage internal circuitry
3 Note, if customer externally powers the 4-20 mA by removing the jumper, the Pulse voltage output
is also effected: The voltage output of the Pulse will follow the customer power (i.e. 24 VDC external power will result in a 24 VDC Pulse [maximum of 50 mA]; 12 VDC external power will result in a 12 VDC Pulse)
4 Pulse width 250 msec default (adjustable with Addresser software) 5 Using Sage Addresser, a Low Flow Cutoff (LFC), commonly referred to as Min Cutoff or Zero Cutoff
can be entered into the FLOW MIN Functions. In Versions 1.82 or higher, the Low Flow Cutoff and the 4-20 mA Scaling are independent of each other. For example: A Low Flow Cutoff (LFC) of 10 SCFM on a Meter with a Full Scale of 100 SCFM will report 0 on the Display and 4 mA on the output. The output will remain at 4 mA until the LFC is exceeded: (ie: 25 SCFM=8 mA). Thus the 4 mA will always be zero based
6 This version does not have Hazard Approvals 7 24 VDC ±10% 8 Other DC voltages (5 VDC, 12 VDC, 48 VDC) available on Prime PLUS. Contact Sage 9 Assumes the 4-20 mA is Externally Powered
10 Modbus Ground becomes isolated from the B6 Power Supply Ground only on Prime PLUS version
(specify “PLUS”)
1
2
3
4
5
6
1
2
3
4
5
6
A B C
INSIDE BODY VIEW
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Remote Cable
(ON REMOTE STYLE SRP)
Grounding
Lug
**
**
A1 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT) A2 – GREEN – SENSE WIRE A3 – BLUE – VELOCITY SENSOR WIRE (HEATED ELEMENT) A4 – WHITE – TEMPERATURE SENSOR WIRE A5 – BLACK – SENSE WIRE A6 – ORANGE – TEMPERATURE SENSOR WIRE
B1 – AC1 – AC VOLTAGE B2 – AC2 – AC VOLTAGE B3 – JUNCTION FOR ISOLATED PULSE B4 – 4-20 mA RETURN (–) AND PULSE SOURCE B5 – VDC IN – VOLTAGE DC – POSITIVE (+) B6 – VDC GND – VOLTAGE DC – GROUND (–)
1
C1 – COM – RS485 MODBUS GROUND
1,2
C2 – B(+)–RS485_D1 C3 – A(–)–RS485_D0 C4 – 24 VDC PULSE – 0 TO 24 VDC PULSE OUTPUT
3,4
C5 – 4-20 mA – 4 TO 20 mA SIGNAL DRIVE
5
C6 – VDC GND – VOLTAGE DC – GROUND (–)
24
O
24
O
**Note, Flow Meter is supplied with a 10K (1/2 watt) metal film resistor (Resistive Jumper) connected across Terminals C4 and C6. For externally powered operation, in addition to removing B4 & B5 Jumpers, it is necessary to connect C4 Resistive Jumper to Terminal B3 instead of C6. Note, B3 must be connected to the External Sources com­mon in order to enable the optically isolated pulse output. In this mode, Pulse Output is optically isolated. Pulsed Output voltage will depend on customer source voltage. Use Sage Resistive Jumper only!
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
24
REV. 16-SIP/SRP
Junction Box Wiring Terminals for Remote Style Meters (Series SRP)
(THERE ARE NO ELECTRONICS INSIDE JUNCTION BOX)
CUSTOMER SIDE
1
(Wired at Installation Site)
FACTORY SIDE
(Wired at Factory)
Red
Red White
W
hite
Blue
Green
Red
Orange
Black
White
CAUTION: Strip wires 3/8" and d
o not crimp insulation.
4.37
3/4” FNPT
Conduit Receptacle
Grounding Screw
GROUNDING SCREW NOT USED (The shield [drain wire] is only connected on the other end [the electronics end]).
Metal Conduit is recommended with appropriate grounding to minimize effects from external noise sources.
Interconnect Cable
2
To Terminal A1 to A6
(see page 21–23)
SEE THE PREVIOUS PAGE FOR THE OTHER END OF THE REMOTE WIRING HOOKUP (the electronics side).
NOTE: The Sensor Junction Box will have a serial number tag. It is important to match this serial number with the serial number of the Remote electronics. Mixing components from different meters can result in significant errors.
a
CAUTION: Cable and cable glands are not for use in hazardous area
environments. Power, ground, outputs, shielded cable, seal fittings
and conduits are to be supplied by customer.
1 NOTE: There are hidden jumpers (underneath the terminal strip) that short together the Blue
and Green wires, and also short together the Black and Orange wires. These extra wires are part of the meter's Lead Length Compensation circuitry, allowing the user to change the length of the interconnect cable (from 0 to 1000 feet) without effecting the accuracy. 25 feet of cable are ini­tially supplied (for cabling longer than 1000 feet, contact Sage).
2 Sage supplies 25 feet of cable for the interconnect wires between the Junction Box and the Remote
Enclosures: Carroll (manufacturer), Part #C0783, 20 gauge, 6 conductor, foil shielded, grey PVC jacket.
Section
STYLES AND FEATURES
B
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
27
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Sage Thermal Mass Flow Meters have two sensors
constructed of reference grade platinum windings
(RTDs). The two RTDs are clad in a protective 316SS
sheath and are driven by a proprietary sensor drive
circuit. One of the sensors is self-heated (flow sen-
sor), and the other sensor (temperature/reference
sensor) measures the gas temperature. The pair is
referred to as the sensing element, and is either
installed in a probe as an Insertion style, or inserted
into a pipe section as an In-Line style flow meter.
As gas flows by the flow sensor, the gas molecules
carry heat away from the surface, and the sensor
cools down as it loses energy. The sensor drive
circuit replenishes the lost energy by heating the
flow sensor until it is a constant temperature differ-
ential above the reference sensor. The electrical
power required to maintain a constant temperature
differential is directly proportional to the gas mass
flow rate and is linearized to be the output signal
of the meter.
Principle of Operation of the Thermal Mass Flow Meter
It is essential that this constant temperature differ -
ential be maintained, even if there are wide fluctua-
tions in gas temperature. It is the function of the
Sage hybrid-digital proprietary sensor drive circuit to
maintain the differential, whether or not the gas
temperature changes, or however quickly molecules
cool off the flow sensor. It is also necessary to proper-
ly calibrate the device with the actual gas (or close
equivalent with certain gases), in the Sage National
Institute of Standards certified (NIST) calibration
facility. By accomplishing these two critical objec-
tives, the Sage meters provide an extremely repeat-
able (0.2% of Full Scale) and accurate output directly
proportional to the mass flow rate of the gas being
measured.
FLOW SENSOR (Self Heated)
TEMPERATURE SENSOR (Reference Sensor)
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
28
REV. 16-SIP/SRP
Features and Benefits
MAJOR BENEFITS OF THERMAL MASS FLOW METERS
Direct Mass Flow – No need for separate temperature or pressure transmitters
High Accuracy and Repeatability – Precision measurement and extraordinary repeatability
Turndown of 100 to 1 and resolution as much as 1000 to 1
Low-End Sensitivity – Measures as low as 5 SFPM (e.g., 1 SCFM in a 6" pipe)
Negligible Pressure Drop – Will not impede the flow or waste energy
No Moving Parts – Eliminates costly bearing replacements, and prevents undetected accuracy shifts
Dirt Insensitive – Provides sustained performance
Low cost-of-ownership
Ease of installation and convenient mounting hardware
SPECIFIC BENEFITS OF THE SAGE PRIME
High contrast photo-emissive OLED display with numerical Flow Rate, Total and Temperature, as well as Graphical Flow Indicator
Photocell activated Screen Saver to extend display life
Calibration milliwatts (mw) is continuously displayed, providing for ongoing diagnostics, and in-situ calibration check
Modbus® compliant RS485 RTU communications
Isolated 4-20 ma output
Rugged, user-friendly packaging with easy terminal access
Option for Solar Energy use (12VDC models)
Low power dissipation, under 2.5 Watts (e.g. under 100 ma at 24 VDC)
Powerful state-of-the-art microprocessor technology for high per­formance mass flow measurement and low cost-of-ownership
Proprietary digital sensor drive circuit provides enhanced signal stability and unaffected by process temperature & pressure changes
Remote Style has Lead-Length Compensation. Allows remote elec­tronics up to 1000 feet from probe; Explosion Proof Junction Box has no circuitry, just terminals
Field reconfigurability via Sage ADDRESSER or Sage DONGLE
Flow conditioning built into In-Line flow meters (1/2" and up)
Captive Flow Conditioners for Insertion Meter applications, if required
SAGE PRIME™ THERMAL MASS FLOW METER FOR GASES
Sage Prime is the top selling meter in our Product Line. The Sage Prime Thermal Mass Flow Meter features a bright, high contrast, photo-emissive OLED display of Flow Rate, Total and Temper ature in a robust, yet lightweight, dual-compartment industrial enclosure. The flow rate is also displayed graphically in a horizontal bar graph format. The rear compartment is completely separated from the electronics, and has large, easy-to-access, well marked terminals, for ease of customer wiring (see photo below). It is powered by 24 VDC (12 VDC optional, or 115/230 VAC). The power dissipation is under
2.5 watts (e.g. under 100 ma at 24 VDC). The Sage Prime Flow Meter is offered in Integral or Remote Style
(which has lead-length compensation up to 1000 feet as well as an Explosion Proof Junction Box). Specify any standard probe length or flow body size. It has a 4-20 ma output as well as a Pulsed Output of Totalized Flow (solid state transistor drive). In addition, Sage Prime supports full Modbus® compliant RS485 RTU communi cations (IEEE 32 Bit Floating Point).
Sage Prime is CE approved, and CSA and UL approved for
Hazardous Service2(see Approvals tab on the website).
CONTINUOUS DIAGNOSTICS & FIELD CONFIGURABILITY
Sage Prime has continuous diagnostics. The raw calibration milli­watts (mw) is always displayed in the upper left hand corner of the meter’s display. At any time, you can check this reading at a “no flow” condition, and compare the reading to the original re ported “zero flow” value noted on the last few lines of your meter’s Certificate of Con formance or the flow meter’s data tag. This in-situ diagnostic pro ­cedure not only checks the sensor performance and the “live zero” calibration point, but it also verifies that the sensor is clean. It essen­tially provides a means to validate that the meter is oper ating prop-
erly, verifies that there is no shift or drift, and eliminates the need for annual fac tory calibrations. This simple field diagnostic procedure,
in addition, verifies that the sensor is free from
contamination, even without inspection.
Although Sage Prime is fully configured
upon shipment, for the pipe and process
con ditions requested, there are three
strategies if changes are needed: Sage
DONGLE; the Sage ADDRESSER software
program; or the Sage ADDRESSER advanced pro-
gram. Contact Sage for details.
1 Note, a built-in photocell continuously monitors the ambient light, and adjusts the display brightness for
optimum long-term life, and also senses motion which automatically switches display from Screen Saver mode to Normal mode
2 Only available with 24VDC powered meters
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
29
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Sage PRIME™ Styles and Specifications
S I P S E R I E S – I N T E G R A L
Mou ntin g
H
ardw are
(in clud ed)
Flow Element is In-Line Style consisting of a choice of 316 Stainless Steel Schedule 40 Flow Bodies sized from 1/4” x 6” long to 4” x 12” long
Flow Element is Insertion Style, consisting of a 1/2” OD probe (3/4” optional) with lengths up to 36” long (typically 15” long) suitable for insertion into the center of a process pipe
Electronics is Remote Style, with rugged windowed dual compartment NEMA 4 enclosure with display. The display is a high contrast photo­emissive OLED display with Screen Saver, and it displays Mass Flow Rate, Totalized Flow and Temperature as well as a graphical representation of Flow Rate in a horizontal bar graph format. In addition, the calibration milliwatts (mw) is continuously displayed, providing ongoing diagnos­tics. Includes Remote Mounting Hardware.
The Flow Element’s Junction Box is Explosion Proof (Class 1, Div 1, Groups B, C, D), and does not have any electronics – only a wiring terminal block. The Junction Box is connected to the Remote Electronics by 25 feet of lead-length compensated cable. The cable (6-conductor) can be lengthened or shortened without affec ting accuracy (max loop resistance 10 ohms, over 1000 feet), if grounded properly.
REMOTE STYLE ELECTRONICS
X
SRP In-Line
1,3,5
SRP Insertion
2
ENGINEERING SPECIFICATIONS OF OPTIONAL SAGE PRIME PLUS
T
his is an optional version of Sage Prime offering a separate ground for the 24VDC
Power Supply (optional 5 VDC or 12 VDC Power Supplies) which isolates the Modbus
ground from the power supply ground. All other features of Prime PLUS are identical to the standard Sage Prime, except Approvals do not apply at this time.
Flow Element is In-Line Style consisting of a choice of 316 Stainless Steel Schedule 40 Flow Bodies sized from 1/4" x 6” long to 4" x 12" long
Flow Element is Insertion Style, consisting of a 1/2" OD probe (3/4" optional) with lengths up to 36" lo ng (typically 15" long) suitable for inser tion into the center of a process pipe
INTEGRA L STYLE EL ECTRO NICS
Electronics is Integral Style, with rugged windowed dual compart­ment NEMA 4 enclosure with local display. The display is a high con­trast photo-emissive OLED display with Screen Saver, and it displays Mass Flow Rate, Totalized Flow and Temperature as well as a graphi­cal representation of Flow Rate in a horizontal bar graph format. In addition, the calibration milliwatts (mw) is continuously displayed, providing ongoing diagnostics.
X
SIP In-Line
1,3,5
SIP Insertion
2
1 Male NPT ends are standard, with flanged ends, tube, or butt weld optionally available 2 Mounting hardware such as Isolation Valve Assemblies, Compression Fittings, and Flanges, are optional 3 Chart of Flow Body length “X” is on Application Data Sheet on website as well as in the Prime O&M 4 Enhanced accuracy available upon request, especially if turndown limited. Contact Sage 5 Flow Conditioners are built into In-Line Style Flow Bodies from 1⁄2" to 4"
Sage Metering is your source for monitoring, measuring and controlling the gas mass flow in your industrial process, building management system or environmental appli­cation. Our high performance, NIST Traceable, Thermal Mass Flow Meters will help in ­c
rease productivity, reduce energy costs, maximize product yields, and/or help reduce environmental insult. Sage provides high quality In-Line and Insertion Thermal Mass Flow Meters for a wide variety of industrial, commercial, and environmental moni­toring needs, including carbon credit verification for Greenhouse Gas reduction.
Our experienced application engineers, many of whom have worked in the Thermal Mass Flow marketplace since its inception, will assist you in choosing the proper gas Flow Meter for your application – and they will be pleased to offer i
nstallation guidance to assure that the meter(s) selected will perform as accurately as possible. Additionally, our Service Staff stand ready to support you with any after-sale assistance that you may require.
S R P S E R I E S – R E M O T E
PRIME SIP/SRP
Standard accuracy is +/– 0.5% of Full Scale +/– 1% of reading with a turn­down of 100 to 1 and resolution as much as 1000 to 1. Repeatability is 0.2%. NOTE: Enhanced accuracy optionally available with limited turn-down4.
The electronics has an isolated 4 to 20 mA output proportional to Mass Flow Rate as well as pulsed outputs of Totalized Flow (24 VDC solid state transistor drive). In addition, Modbus RS485 RTU communications is standard (IEEE 32 Bit Floating Pt).
O
pti onal SVA 05 Iso lati on V alve As semb ly
®
®
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
30
REV. 16-SIP/SRP
1 Upon start-up, the Revision No., Serial No., and Modbus ID will display for a few seconds.
Also the output configurations symbol is momentarily displayed
2 Note, a built-in photocell continuously monitors the ambient light, and adjusts the display
brightness for optimum long-term life, and also senses motion which automatically switches display from Screen Saver mode to Normal mode
3 To view display, wave hand over display or use a flashlight. The Flow Meter displays for one
minute, then the Screen Saver resumes
1
Raw Calibration milliwatts (mw) for Diagnostics and Periodic “Zero Flow” Calibration Check
2 Graphical Indication of Percentage of Full Scale
Flow Rate
3 Flow Rate 4 Totalized Flow (Consumption)
(Value is Retained during Power Outage or Power Cycling)
5 Flashes with each pulsed output of consumption 6 Engineering Units of Flow Rate (the last digit
can be S(seconds), M(minute), H(hour), D(day)
7 Engineering Units of Consumption 8 Photocell activated Screen Saver extends display life
M E T E R I N G , I N C .
1 - 8 6 6 - 6 7 7 - S A G E
PRIME
COM M
PWR
. . .
N8˚'
4$'.
 4$'
1
2
3
4
5
6
7
Sage PRIME Organic (OLED) Display
1,2,3
8
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
31
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
HAZARDOUS LOCATION APPROVALS
All 24 VDC Powered Sage Prime Meters (SIP Integral
I
nsertion, SIP In-Line, SRP Remote Insertion, SRP
Remote In-Line) are approved for Class 1, Div 2,
Groups B, C, D, T4 and ATEX: Ex nA IIC T4.
AC Powered Meters are not approved.
Testing is in accordance with the following Safety
Standards:
• UL1604, Third Edition, Electrical Equipment for
Use in Class I and II, Division 2, and Class III
Hazardous (Classified) Locations
• CSA C22.2 No. 213-M1987 (R1999), First Edition,
Non-incendive Electrical Equipment for Use in
Class I, Division 2 Hazardous Locations
• UL/CSA 61010-1, Second Edition, Safety Require -
ments for Electrical Equipment for Measurement,
Control, and Laboratory Use – Part 1: General
Requirements
The following is required to comply with the above
mentioned Approvals
1) Repair of the product (or replacement of compo-
nents) is not possible by the user
2) As noted on the following label (see below) it will
contain the following markings: Ex symbol, nA
symbol IIC, temperature class
3) All Prime DC meters will be marked with “X”
which means that these Special Conditions of
Use will apply:
a) The completed meter must be installed with a
rigid or flexible metal conduit in order to satis-
fy approval conditions.
b) The meter has been approved for use with the
electronics enclosure in an ambient tempera-
ture from –20˚C < Ta < 65˚C.
4) Sage Metering considers a linear correction suit-
able for temperatures exceeding the temp code
rating of 40C (104F) thus no customer correction
is needed.
CONFORMANCE
All AC & DC Powered Sage Metering, Inc. Series
SIP (Sage Prime-Integral) and Series SRP (Sage Prime-
Remote) are CE Compliant for the following CE
directives:
• EN61000-6-4 for Electromagnetic compatibility;
• EN61000-3-2 for Harmonics;
• EN61000-3-3 for Flicker;
• EN61000-6-2 for Electromagnetic Compatibility
(Immunity for Industrial Environments), which
includes EN61000-4-2 for ESD;
• EN61000-4-3 for Radiated Immunity;
• EN61000-4-4 for EFT/B; EN61000-4-5 for Surge;
• EN61000 for Conducted Immunity;
• EN61000-4-8 for Magnetic Immunity;
• EN61000-4-11 for Voltage Interruptions
MEDICAL CONFORMANCE
Contact Sage Metering if Medical CE Conformance
is required. (AC Powered Sage Prime Meters only.)
The Standard is to IEC 60601-1-2:2007 Edition 3
Approvals
S
AGE METERING, INC.-MTRY, CA 93940/ PRIME THERMAL MFM
Class I, Div 2, Groups B,C,D T4 ATEX: Ex nA IIC T4 X
MODEL #
SERIAL # mW0 =
FOR USE IN HAZARDOUS LOCATIONS–CAUTION–DISCONNECT FROM POWER
S
UPPLY BEFORE OPERATING. KEEP COVER TIGHT WHILE CIRCUITS ARE ALIVE.
CONDUIT SEALS MUST BE INSTALLED WITHIN 18˚ OF THE ENCLOSURE.
ATTENTION–OUVRIR LE CIRCUIT AVANT
D’ENLEVER LE COUVERCLE GARDER
L
E COUVERCLE BIEN FERME TANT QUE LES CIRCUITS SONT SOUS TENSION.
UN SCELLEMENT DOIT ETR INSTALLE A MOINS DE 45CM DU BOITER.
Section
DRAWINGS
C
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
35
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
INSERTION STYLE
2
150#, 300#, or 600# flanged mounting is optionally avail­able. Available probe lengths are 6", 12", 15", 18", 24", 30", 36" or 48". Standard probe is 1/2" diameter (3/4" optional – recommended for 36" or 48")
4.50
4.60
Probe Length
FLOW
SIP Series Integral Style Mass Flow Meters
IN-LINE STYLE
1,3
150#, 300#, or 600# flanged ends are optionally available. (150# flanges recommended on 3" and 4" Flow Bodies)
5.38
2-3/4” Nominal
See Chart
FLOW
4.61
1 NPT Fittings standard 2 Flanged Mounting available for high pressure operation 3 Flow Conditioning built in to Flow Meter Pipe Sizes 1/2" and up. Contact Sage for optional
1/4" tube flow body.
Depth: DC Enclosure depth is 4.35"
AC Enclosure depth is 5.35"
1/2" NPT
User Entry
for Wiring
1/2" NPT
User Entry
for Wiring
CAUTION: Do not rotate the Enclosure of In-Line Style Meters relative to the Flow Tube, or the calibration may be effected since the sensors may become misaligned.
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
36
REV. 16-SIP/SRP
SRP Series Remote Style Mass Flow Meters
INSERTION STYLE
2
150#, 300#, or 600# flanged mounting is optionally avail­able. Available probe lengths (C) are 6", 12", 15", 18", 24", 30", 36" or 48".
See Chart
on Page 35
IN-LINE STYLE
1,3,4
150#, 300#, or 600# flanged ends are optionally available. (150# flange recommended on 3" and 4" Flow Bodies)
1 NPT Fittings standard 2 Flanged Mounting available for high pressure operation 3 Flow Conditioning built in to Flow Meter Pipe Sizes 1/2" and up. Contact Sage for optional
1/4" tube flow body.
4 See Chart on page 35. 5 Junction Box has the following certifications: Class I, Groups B,C,D; Class II, Groups E,F,G; Class III;
4X, 7BCD, 9EFG; FM Standard 3615; UL Standard 1203; CSA Standard C22.2 No. 30; and NEMA Compliance
4.60
4.50
3.50
Junction Box is Explosion Proof, Class 1, Div. 1 & 2, Group B, C, D
(
NO ELECTRONICS)
3/4" NPT for Remote Cable
1/2" NPT User Entry for Wiring
3/4" NPT for Remote Cable
3/4" NPT for
Remote Cable
1/2" CORD GRIP SUPPLIED ON ELECTRONICS
END
25' CABLE SUPPLIED Can be shortened or lengthened in the field by up to 1000 ft. without affecting calibration.
Junction Box is Explosion Proof, Class 1, Division 1 & 2, Group B, C, D
(NO ELECTRONICS)
5
CAUTION: Do not rotate the Junction Box of In-Line Style Meters relative to the Flow Tube, or the calibration may be effected since the sensors may become misaligned.
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
37
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Sage Prime Remote Bracket Layout
MOUNTING OPTIONS
1
. Overhead with U-bolts (customer supplied) across
pipe on each leg
2. Vertically, as shown
3
. Horizontally
4.61
7.38
2.00
CORD GRIP or
NPT PLUG (as req’d)
BOTH SIDES
WAVE WASHER
WAVE
WASHER
.266 DIA
HOLES
1/2" NPT User Entry for Wiring (2)
3/4" NPT for Remote Cable
1/2" NPT User Entry for Wiring (2)
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
38
REV. 16-SIP/SRP
11. 0 0
Mounting Hardware
3
STCF SERIES TEFLON FERRULE COMPRESSION FITTING
1/2" tube x 1/2" pipe fitting (shown, not to scale), is used for low pressure insertion applications to 125 psig (Stainless Steel Ferrule optional for higher pres­sure applications – up to 225 psig). Also available in 3/4" tube x 3/4" pipe size.
1. 9 2
1 At 250 psig, force exerted on 1/2" diameter probe is 50 lbs 2 Safety chain is designed to prevent probe from accidentally escaping from assembly during removal from pressurized pipe 3 Insertion meters can have optional flanged mounting (generally used for high pressure or very hot gases). This adaptation is not
shown. Consult factory for details.
4 Maximum gas temperature, 200F, unless high temperature models ordered. 5 Hot Tapping is feasible by removing Weldment (upper portion of assembly temporarily removed) 6 See page 46. SVA05 can be utilized for Sensor Functionality and Zero Self Check. 7 The allen wrench for SVA05 is
9
64 (it is 3⁄16 for SVA07).
1/2" BORE SINGLE PIECE COLLAR CLAMPS
7
3/4"x1.5" PIPE NIPPLES
3/4"x3" BALL VALVE
SVA05 SERIES ISOLATION VALVE ASSEMBLY DETAIL
5,6
Cut away view of probe inserted through isolation b
all valve assembly.
1/2"–3/4" BALL VALVE WELDMENT WITH 1/2" TUBE TO PIPE COMPRESSION FITTING
3/4"x1"
HALF COUPLING
(THREADOLET)
MOUNTING PLATE FOR THIN WALLED DUCTS (INCLUDES STCF05 COMPRESSION FITTING)
4"
4"
NOTE: User needs to weld a 3/4" female threadolet (of appropriate radius) to mate with existing pipe after a 3/4" hole has been drilled in pipe. The 3/4" Male Coupling of the Sage Isolation Valve Assembly will thread into the user’s 3/4" threadolet.
SAFETY CHAIN
PROBE LENGTH SAFETY
(with sensor)2CHAIN LENGTH
2
12" 8.25" 15" 11.25" 18" 14.25" 24" 20.25"
SVA05 SERIES ISOLATION VALVE ASSEMBLY FOR INSERTION METERS
4
(for Low Pressure SVA05 see page 39)
U
sed for pressures to 250 psig
1
(
shown for use with 1/2" diameter insertion meters). 150# or 300# flanged mounting is op tionally available. Available sizes are 1/2" x 3/4" NPT (SVA05 shown), and 3/4" x 1" NPT for use with 3/4" diameter insertion meters (SVA07).
SENSOR ASSEMBLY
EXTENDS 2.25" L
BELOW THE
LOWER EDGE OF
THE WELDED
COLLAR CLAMP
WITH CHAIN TAUT
3/4" THREADOLET (User Supplied)
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
39
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Teflon Ferrule 3
16SS Compression Fitting
316SS 3/4"x 1-1/2" Pipe Nipple
8.00" with
threadolet
7.00" with
threadolet
HANDLE IN CLOSED POSITION HANDLE IN OPEN POSITION
3/4" Brass Full Port Ball Valve
1/2"-3/4" Brass Adaptor
5.5"
without
threadolet
6.5" with
threadolet
Valve Handle
Customer
Supplied Threadolet
SVA05LP Low Pressure Isolation Valve Assembly
NOTES AND CAUTIONS
• Suitable for low pressure Air or Natural Gas applications (maximum 50 PSIG)
• Assumes 1⁄2" Insertion Probe inserted to center of a Pipe (see Sage Probe Insertion Guidelines)
• Teflon Ferrule permits ease of Probe insertion or removal
• Exercise caution when loosening Ferrule nut during insertion and removal of Probe, since this model has no Safety Chain
• Note, maximum upward force is 20% of pipe pressure (i.e., 10 Lbs with 50 PSIG)
• The Assembly will be shipped with a plastic sleeve that protects the 3/4" pipe nipple
• It is the Customer’s responsibility to weld a Female Threadolet with correct diameter to pipe
UPSTREAM
F
L
O
W
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
40
REV. 16-SIP/SRP
Flanged Ends for In-Line Meter (OPTIONAL)
Flanges for 31⁄2" pipe sizes and up, have 8 bolt holes
Flanges for 3" pipe sizes and smaller have 4 bolt holes
Flanged Mounting for Insertion Meter (OPTIONAL)
Section
DIAGNOSTICS
D
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
43
S A G E M E T E R I N G , I N C .
Common Diagnostics
SYMPTOM: Display failure, or pixels extremely dim. CORRECTIVE ACTION: Contact Factory. Certain types
of failures are under long term warranty. Please note that the 4-20 ma will still function normally.
SYMPTOM: Display fading, or partially fading. CORRECTIVE ACTION:
a) Some fading, particularly with those characters that
are lit up most frequently, is normal. The flow meter will continue to function properly, and flow meter accuracy and outputs will not be effected.
b) In extreme cases, contact the factory for display
replacement.
c) Note, in late 2009, the Sage Prime was modified
to incorporate a built-in photocell. The purpose of the photocell is to adjust the display brightness with ambient lighting. The brighter the surround­ing lighting conditions, the brighter the display. Lower ambient lighting conditions, such as a fac­tory environment, will dim the display. The dis­play will be dimmest if operated in low ambient lighting, or at night. The photocell circuit is designed to extend the life of the display, and to minimize fading.
d) Note, in early 2010, a further enhancement was
added to further extend the life of the display. The above mentioned built-in photocell also senses motion which automatically switches dis­play from Screen Saver mode to Normal mode.
SYMPTOM: Erratic Readings. POSSIBLE CAUSES: If a large Motor or Generator or
Variable Fre quen cy Drive (VFD) is nearby the enclo­sure, it may be inducing sufficient analog noise into the circuitry to temporarily corrupt the data.
SUGGESTED CORRECTIVE ACTION:
a) If a Power-Restart temporarily solves the problem,
than it is likely that the source of the noise was the problem.
b) To prevent subsequent problems, if a Remote
Style Meter, move the enclosure as far away as possible from the source (the Motor or VFD).
c) If an Integral Style Meter, mount the meter in
a different location (further from the source) or move the source further from the meter.
SYMPTOM: Erratic Readings on a Remote Meter. POSSIBLE CAUSE: In some cases, analog noise is
induced into the Remote cable causing erratic, or climbing readings.
SUGGESTED CORRECTIVE ACTION:
a) Be sure the remote cable is installed in metal con-
duit and grounded on one end (in some cases, grounding both ends may be required).
b) Also, avoid coiled cable, especially if not in metal
conduit.
c) Also, if extra cable exists, move the extra cable as
far away as possible from any source of analog noise, such as large motors or VFDs.
SYMPTOM: Meter reading zero continuously, or Full Scale continuously, or temperature reading is abnor­mally low (hundreds of degrees below zero).
POSSIBLE CAUSES/SUGGESTED CORRECTIVE ACTION:
a) It is likely that a wire is loose. But in rare cases,
a sensor could fail (i.e., if a standard sensor, HT01 or HT02 sensor exceeds a process temperature of 450˚F.)
b) Check for continuity to be sure the wiring is
making good contact at the terminals of the Junction Box.
c) Also, to verify that the electronics and the sensor
serial number are the same, note the following: The sensor’s serial number will come up upon power up, right after Initializing on the Display. If the serial number doesn't agree with the Junction Box labels, that would affect cali bration (in other words, sensors and electronics are a matched pair—mixing them up will cause false readings). Also metal Serial Number Tags are fastened to both the electronics and the Junction Box. They must have identical Serial numbers.
d) To check if a sensor has failed on a remote style
meter, it is easy to use the Junction Box to do so. You must Power Down (shut off power), but you do not need to remove the probe from the pipe. Refer to page 24.
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
44
REV. 16-SIP/SRP
e) An Ohm Meter is required to check across the sen-
sor leads of the Flow Sensor. Look at the drawing of the Junction Box. Disconnect the red wires on the Factory Side to isolate and measure the resist­ance. If the reading is infinity or a short, it means that sensor has failed.
f) Now check the Temperature Sensor. Disconnect the
white wires on the Factory Side to isolate and meas­ure the resistance. If you have infinity or a short, it means that sensor is burned out. Note: Normally the
sensors will read approximately 110 ohms at 70˚ F. At higher temperatures they should read a higher resist­ance, but both sensors should have a similar value.
g) On integral style meters (SIP), there is no Junction
Box. In that case, refer to the Prime Integral Terminals on page 19 and check the sensor wires. Remove the appro priate wires first (red pair for flow, then white pair for temperature). Measure their resistance. If reading infinity or short, it means that sensor has failed.
SYMPTOM: Meter Railing (Pegging) or Reading High POSSIBLE CAUSES/SUGGESTED CORRECTIVE ACTION:
a) Insufficient straight run (i.e. flow profile is dis-
turbed, causing errors).
b) Possible jet effect if upstream pipe is smaller than
meter flow body or if valve is too close upstream to meter.
c) Not following Probe Insertion Guideline.
d) If sensor is inserted in reverse (“Upstream” mark
is facing downstream) Meter may over-report (or under-report) by as much as 30%.
e) If sensor is not aligned properly, with “Upstream”
mark facing upstream, a rotation greater than ± 5 degrees may cause change in reading (greater than ± 5 degrees and less than ± 20 degrees causes meter to over-report; a greater rotation actually blocks the sensor, and causes
meter to under-report).
f) A downstream valve too close to the meter (flow
may be reflecting back).
g) Possibly caused by water droplets condensing out
of gas stream (which generally causes output to spike; but if droplets are near continuous, output may rail).
h) Meter is miswired, especially in Remote Style
application.
i) Possibly caused by water droplets condensing on
inside of pipe wall, which roll down or hit sensor causing output to spike; but if droplets are near continuous, output may rail.
Note: Recommend in -
stallation 45˚ from vertical (see drawing on page 68).
j) Possibly caused by water droplets condensing out
of gas stream and filling the cavity containing the sensing elements (usually due to probes mounted below horizontal in saturated pipes).
k) Sensor may be contaminated. Remove probe,
wipe off or clean with a solvent. Reinsert.
l) Using a different gas or gas mix than the meter
was specified and calibrated for.
m) If a Remote Style Meter (SRP), be sure Serial
Numbers of Junction Box and Remote Electronics are identical (if not, errors in calibration are in ­evi table). To confirm, verify that Junction Box Serial Number Tag has identical Serial Numbers to Tag on Remote Enclosure.
n) Meter may appear to be reading high if user is
comparing Sage flow meter readings (SCFM) to an uncorrected volumetric device (ACFM). For example, at constant volume, a decrease in gas temperature will increase the mass flow (SCFM). That is completely normal.
SYMPTOM: Reading Low POSSIBLE CAUSES:
a) Insufficient straight run (i.e. flow profile is
disturbed, causing errors).
b) Poor flow profile Upstream (insufficient upstream
straight run).
c) Not following Probe Insertion Guideline.
d) If sensor is inserted in reverse (“Upstream” mark
is facing downstream) Meter may over-report (or under-report) by as much as 30%.
e) If sensor is not aligned properly, with “Upstream”
mark facing upstream, a rotation greater than ± 5 degrees may cause change in reading (greater than ± 5 degrees and less than ± 20 degrees causes meter to over-report; a greater rotation actually blocks the sensor, and causes meter to under-report).
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
45
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
f) Sensor may be contaminated. Remove probe, wipe
o
ff or clean with a solvent. Reinsert.
g
) Using a different gas or gas mix than the meter
was specified and calibrated for.
h) If a Remote Style Meter (SRP), be sure Serial
Numbers of Junction Box and Remote Electronics are identical (if not, errors in calibration are in ­evita ble). To confirm, verify that Junction Box Serial Number Tag has identical Serial Numbers to Tag on Remote Enclosure.
i) Meter may appear to be reading low if user is
comparing Sage flow meter readings (SCFM) to an uncorrected volumetric device (ACFM). For example, at constant volume, an increase in gas temperature will lower the mass flow (SCFM). That is completely normal.
j) On most models, the Totalizer will not start count-
ing for 10 seconds after power up so any flow data will not be accumu lated during this time.
k) Insufficient power supply—most products require
minimum 100 ma.
l) Excessive load on the 4-20 ma. (To check if prob-
lem is due to 4-20 ma output device, temporarily remove device, and observe if display reads as expected).
SYMPTOM: Totalizer can take up to 10 seconds to update its reading when flow meter is first powered up, or a channel is changed. CORRECTIVE ACTION: None. This slight delay is com­pletely normal.
SYMPTOM: Display does not have power POSSIBLE CAUSE: Mis-wiring
SYMPTOM: 4-20 mA output not tracking the flow rate
display
POSSIBLE CAUSE:
a) In normal operation (Self Powered) B4 and B5
must be jumpered to supply power to loop. See pages 19 and 22.
b) In Externally Powered mode, the jumper must be
removed. Verify that 9 to 27 Volts DC is supplied to externally power the loop as per page 19 or 22.
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
46
REV. 16-SIP/SRP
In-Situ Calibration Check
RECOMMENDED ON A QUARTERLY BASIS FOR EPA 40 CFR 98 PERIODIC
CALIBRATION VERIFICATION, CAR1PROTOCOLS, AND CDM2PROTOCOLS
Sage Prime has continuous diagnostics. The raw cali­bration milliwatts (mw) is always displayed in the upper left hand corner of the meter’s display allow­ing the user to conduct an “in-situ” calibration. At any time, you can check this reading at a “no flow” condition and compare the reading to the original re ported “zero flow” value noted on the last few lines of your meter’s Certificate of Conformance or the flow meter's data tag. This diagnostic procedure not only checks the sensor performance and the “live zero” calibration point, but it verifies that the sensor is clean. It essentially provides a means to validate that the meter is operating properly, verifies that there is no shift or drift, and eliminates the need for annual factory calibrations. This simple field diagnos­tic procedure also verifies that the sensor is free from contamination, even without inspection.
1. Verify that meter has no gas flow
3
Close appropriate valves in the process to have a “no flow” condition so you can check the “live zero” mw output of the actual gas (it should be checked at the same pressure as noted on Certificate of Conformance).
If it is not possible to close valves in the process (e.g. natural gas supply must be kept flow­ing), a user with a Sage SVA05 or SVA07 Isolation Valve Assembly can check “zero” of the actual gas and pressure without shutting off the gas supply. Refer to SVA SERIES ISOLATION VALVE ASSEMBLY DETAILS ON PAGE 38. a) Loosen lower Collar Clamp completely
4
b) Slightly loosen compression fitting until Probe
can be lifted c) Lift Probe until Safety Chain is taut d) Tighten compression fitting e) Close Valve f) Check zero mw as per “2” below
Optionally, do an ambient air check by re ­moving probe and covering up sensor by capping the sensor with a plastic bag, empty plastic water bottle or other means of preventing flow (see 8).
2. Observe the raw mw on the top of the meter’s display. After one to three minutes of “no flow” stabilization, check the observed reading against the flow meter’s data tag or last line(s) of your Meter’s Certificate of Conformance.
3. A value within 5 milliwatts of the original Factory value (assuming the same gas is checked at same pressure) indicates that meter is still in calibration.
4. A value greater than 5 mw, but less than or equal to 10 mw, also indicates that the meter is still in
calibration, but this reading may have been influ­enced by one or more of the following factors: gas composition, pressure, dirt, non-zero conditions, and sensor orientation. Any of these factors can have an effect on mWo. It is a very sensitive data point; that is why it is such a good check.
5. Note, if all of the above factors were remedied, it would be expected that the mW zero would report less than or equal to 5 milliwatts.
6. Note, in some cases, contamination of the sensor is the only cause of the additional heat transfer during the “no flow” test. Remove probe, and clean the sensor (use an appropriate non-corrosive sol­vent to remove build up). A soft brush can be used to gently clean the sensing surface, using caution to avoid damaging the sensor elements (the RTD’s).
7. In summary, if a technician in the field were able to simulate Sage calibration conditions, he too would find that the mWo would be within one mW or very close to that. Since this is not always possible, we are finding that after considering all of the field variables, a mWo in the field that is within 10 mW is an acceptable value (see 9). This would allow for a check to be done in the pipe under application conditions.
8. Note, if desired, a second check can be conducted as well but using ambient air: This validation method requires that the sensor be removed from the pipe and inserted in a container such as an empty plastic water bottle.
9. For CAR
1
compliance Sage recommends a quar terly
In-Situ Calibration Check for the following Protocols:
U.S. Landfill Protocol, Version 4.0, Par. 6.2 Mexico Landfill Protocol, Version 1.1, Par. 6.2 U.S. Livestock Protocol, Version 3.0, Par. 6.2 U.S. Livestock Protocol, Version 4.0, Par. 6.3 Mexico Livestock Protocol, Version 2.0, Par. 6.2
As per the protocols, the maximum allowable drift is 5%. Percent drift can be determined by multi­plying the mW change from factory value (see 2) by 1.0% (i.e. each mW change equals 1% drift).
1 CAR is the Climate Action Reserve. The Climate Action Reserve is a national offsets program working
to ensure integrity, transparency and financial value in the U.S. carbon market. It does this by estab­lishing regulatory-quality standards for the development, quantification and verification of green­house gas (GHG) emissions reduction projects in North America. The Climate Action Reserve operates alongside its sister program, the California Climate Action Registry (California Registry), which was created by the State of California in 2001 to address climate change through voluntary calculation and public reporting of emissions.
2 CDM Methodologies, ACM 0001, “Methodological tool to determine the mass flow of a greenhouse
gas in gaseous stream” (EB61 Report, Annex 11, Page 1).
3 Sage "zeros" the meter in a horizontal pipe. If you have a vertical pipe, mW will be slightly lower
at zero (also see note 4).
4 The allen wrench to loosen collar clamp is
9
64 on the SVA05 (it is 3⁄16 on the SVA07).
Section
WARRANTIES AND
SERVICE WORK
E
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
49
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Warranties and Service Work
LIMITED WARRANTY
Sage Metering’s products are warranted against faulty
materials or workmanship for one year from the date
of shipment from the factory. Sage’s obligation is
limited to repair, or at its sole option, replacement of
products and components which, upon verification
by Sage at our factory in Monterey, California, prove
to be defective. Sage shall not be liable for installa-
tion charges, for expenses of Buyer for repairs or
replacement, for damages from delay or loss of use,
or other indirect or consequential damages of any
kind. This warranty is extended only to Sage prod-
ucts properly used and properly installed for the par-
ticular application for which intended and quoted;
and does not cover water damage due to improper
use of cord grips or removal of protective caps; and
does not cover Sage products which have been
altered without Sage authorization or which have
been subjected to unusual physical or electrical
stress. Sage makes no other warranty, express or
implied, and assumes no liability that goods sold to
any purchaser are fit for any particular purpose.
Transportation charges for materials shipped to the
factory for warranty repair are to be paid by the ship-
per. Sage will return items repaired or replaced under
warranty, prepaid. NOTE: No items will be returned
for warranty repair without prior written authoriza-
tion from Sage Metering, Inc. Sage does not warranty
damage due to corrosion.
GENERAL TERMS AND CONDITIONS
Detailed General Terms and Conditions can be found
on the Sage website (www.sagemetering.com) on a
link “General Terms” on the Footer of any page on
the website.
CANCELLATION / RETURN POLICY
Cancellation or Return: After issuance of a purchase
order (by phone, mail, e-mail or fax) or a credit card
order (by phone, mail, e-mail or fax), there will be a
cancellation fee for any cancelled order. Can cella -
tions must be in writing (by mail, e-mail or fax):
1) If credit card order or non-credit card order is
cancelled within 7 days of issuance of purchase
order or date order was placed (which ever is
earlier), there will be a 10% cancellation fee.
2) If credit card order or non-credit card order is
cancelled after 7 days, but prior to shipment,
there will be a 20% cancellation fee. (If order is
cancelled due to late delivery, the cancellation
fee will be waived. Late delivery is defined as
shipping a meter 7 days or later than the delivery
date acknowledged by Sage Metering at time of
placing order).
3) If a credit card customer decides to return the
equipment after shipment for credit, credit will
not be issued if equipment is damaged or if equip-
ment is returned after four (4) months of ship-
ment. If equipment is not damaged, then equip-
ment can be returned after issuance of a Return
Meter Authorization (RMA) by Sage. Returned
package must be insured by customer and must
reference proper RMA# on outside of package,
or package may be rejected (i.e., package will be
returned unopened). Credit Card customers will
be charged a 30% re-stocking fee (70% balance
will be credited back). Customer is responsible for
return shipping charges and any damage if
improperly packaged.
continued on next page
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
50
4) If a non-credit card customer decides to return
the equipment after shipment for credit, credit
will not be issued if equipment is damaged or if
equipment is returned after 1 month of ship-
ment, unless authorized by a representative at
Sage Metering, Inc. The Sage representative will
issue a Return Material Authorization (RMA) at
that time and will advise of the restocking fee.
Returned package must be insured by cus-
tomer and must reference proper RMA# on
outside of package, or package may be rejected
(i.e., package will be returned unopened).
Customer is responsible for return shipping
charges and any damage if improperly packaged.
REV. 16-SIP/SRP
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
51
RETURNING YOUR SAGE METER
A Return Material Authorization Number (RMA#)
must be obtained prior to returning any equipment
to Sage Metering for any reason. RMA#s may be
obtained by calling Sage Metering at 866-677-7243
or 831-242-2030 between 8:00 am and 5:00 pm
Monday through Friday.
A Sage RMA Form (see page 52) must be filled out
and included with the meter being returned to
Sage Metering. RMA Form is also accessible by
clicking the “Contact” tab of the Sage website
(www.sagemetering.com).
Take special care when packaging your meter for
return to the factory. The sensor in particular may
easily be damaged if not prevented from shifting
around within the package and if the sensor itself is
not covered to keep it from contacting other pack-
age contents. Any damage resulting from improper
packaging is the responsibility of the shipper.
A purchase order is required prior to an RMA being
issued. Most repairs or recalibrations can be quoted
over the phone. For equipment that must be evaluat-
ed, an Evaluation purchase order in the amount of
$150 is required. Once an evaluation is completed
and a quote has been issued, you can choose to pro-
ceed with the work or have the unit returned with
only the evaluation and freight fee billed.
In accordance with the “Right to Know Act” and
applicable US Department of Transportation (DOT)
regulations, Sage Metering will not accept delivery of
equipment that has been contaminated without writ-
ten evidence of decontamination, and has instituted
the following Return/Repair conditions. Strict adher-
ence to these conditions is required. Returned equip-
ment that does not conform to the requirements list-
ed below will not be processed. If Sage Metering finds
evidence of contamination, we may, at our option,
have the unit returned at your expense. For your ref-
erence, the requirements for packaging and labeling
hazardous substances are listed in DOT regulations
49 CFR 172, 178, and 179.
1. The equipment must be completely cleaned and
decontaminated prior to shipment to Sage
Metering. This decontamination includes the sen-
sor, probe, electronics and enclosures internally
and externally. All packaging must be clean and
free from contamination.
2. A Material Safety Data Sheet (MSDS) is required
for all process fluids and gases that have been in
contact with the equipment. This includes fluids
or gases used in cleaning the equipment. A
Decontamination Statement is also required for
each meter returned using a different gas or fluid.
Both the MSDS and the Decontamination
Statement are to be attached to the OUTSIDE of
the shipping container. If both documents are not
attached, you will be called, and the equipment
sent back to you at your expense.
3. The decontamination Statement must include
the following required information
A. A list of all chemicals and process fluids used
in the equipment, including decontamination
fluids or gases.
B. The model and serial number of the equip-
ment being returned.
C. A company officer or other authorized person’s
signature on the statement.
Return Shipping Address:
Sage Metering, Inc.
8 Harris Court, Building D1
Monterey, CA 93940
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
52
REV. 16-SIP/SRP
RETURN MATERIAL AUTHORIZATION R
MA #
Date
R
ETURN CUSTOMER INFORMATION
Customer’s Name Fax #
Customer’s Contact Name Phone #
Email Address
CUSTOMER’S RETURN ADDRESS
Bill to: Ship to:
RETURN PRODUCT INFORMATION
Model No. Serial No(s).
FLOW: MIN NORMAL MAX
TEMP: MIN NORMAL MAX
PRESSURE: MIN NORMAL MAX
GAS LINE SIZE
REASON FOR RETURN / DESCRIPTION OF SYMPTOMS
(All non-warranty repairs could be subject to a minimum evaluation charge)
Recommended steps to be used to duplicate problem/symptoms
Sage Metering Technical Contact
Take special care when packaging your meter for return to the factory. The sensor in particular may easily be damaged if not prevented from shifting around within the package and if the sensor itself is not cov­ered to keep it from contacting other package contents. Any damage resulting from improper packaging is the responsibility of the shipper.
SAGE METERING, INC.
8 Harris Court, Building D-1 / Monterey, California 93940
PHONE: 831-242-2030 / FAX: 831-655-4965
Section
MODBUS
F
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
55
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Modbus Register Listing
SAGE PRIME REV. 1.80–2.07
*SCALED INT32 register contents form INT32 values by multiplying the IEEE FLOAT x 1000 ex. FLOAT –> 112.768 = SCALED INT32 –> 112768
2
56
256
257
257
257
257
257
257
257
257
257
TEMP
TEMP
TEMP
TEMP
FLOW
FLOW
FLOW
FLOW
FLOW
FLOW
514
516
518
520
522
524
526
528
530
532
534
536
538
540
542
544
546
548
770
772
774
776
778
780
782
784
786
788
790
792
794
796
798
800
802
804
UINT8
UINT8
UINT8
UINT8
UINT1
UINT1
UINT1
UINT1
UINT1
UINT1
UINT1
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
UINT32 IEEE Float SCALED INT32*
Reg Reg Reg Reg
Offset O ffset Type Offset Type Description
format flag
modbus_unit_id
output mode sel
fix_pt selection
bRun
bTotal
bEEProm
bReset
bLeadEn
bDACIo
bDAChi
CAL_VAL
K-FACTOR
VREF
LOAD-RES
COEFF A
COEFF B
COEFF C
COEFF D
DISP A
DISP B
DISP C
DISP D
COEFF A
COEFF B
COEFF C
COEFF D
COEFF E
COEFF F
302
304
306
308
310
312
314
316
318
320
550
552
554
556
558
578
580
582
584
586
588
590
592
594
596
598
600
602
806
808
810
812
814
834
836
838
840
842
844
846
848
850
852
854
856
858
FLOAT
F
LOAT
FLOAT
FLOAT
FLOAT
UINT16
UINT16
UINT32
ASCII
ASCII
UINT32
UINT32
UINT32
UINT32
UINT32
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
FLOAT
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
UINT32 IEEE Float SCALED INT32*
Reg Reg Reg Reg
Offset O ffset Type Offset Type Description
iir filter coeff
ow_min
flow_max
PULSE COUNT
temp_max
dac1_min
dac1_max
serial number
RATE string
TOTAL string
current totalizer
ADC0
ADC1
ADC2
ADC3
current flow
current temp
rtd_mWatts
rtd_res
ref_res_r
ref_res_d
dac_smooth
lead
oheat
bv
fv
tv
lv
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
56
REV. 16-SIP/SRP
Sage Prime Meters support communication with
other devices via MODBUS® protocol using RTU
transmission mode. The Modbus protocol defines a
message structure that controllers will recognize and
use, regardless of the type of networks over which
they communicate. It establishes a common format
for the layout and contents of message fields.
Transactions use a master-slave technique, in which
only one device (the master) can initiate transactions
(called queries). The other devices (the slaves)
respond by supplying the requested data to the
master and by taking the action requested in the
query. Sage Meters operate as slaves to other Modbus
devices and default to 19200-8-E-1, however, the
following modes may also be software selectable:
9600-8-N-1 (Baud-Bits-Parity-Stop) 9600-8-E-1 9600-8-O-1 19200-8-N-1
1
19200-8-E-1 (Default) 19200-8-O-1
MESSAGE FRAMING
Messages start with a silent interval of at least 3.5
character times followed by 4 fields and then fol-
lowed by another silent interval of at least 3.5 char-
acter times. The first field contains the device
address. The second field contains the function code.
The third field contains the data and byte counts.
The fourth field contains the CRC value.
ADDRESS FIELD
T
he address field contains one byte. Sage Prime
Meters will transmit response packets to addresses
which are between 1 to 240 decimal (inclusive).
M
odbus packet writes may be sent to broadcast
address 00, however the Prime will not reply with a
response packet.
FUNCTION CODE FIELD
The function code field contains one byte. See the
section titled Function Codes Supported by Sage Prime.
DATA FIELD
The data field contains four or more bytes. This
information is used by the Meter to take the action
defined by the function code, or to read or write data
to one or many registers.
CRC FIELD
The CRC-16 (cyclical redundancy check) field is two
bytes, containing a 16-bit binary value. The CRC
value is calculated by the transmitting device, which
appends the CRC to the message. The receiving
device recalculates a CRC during receipt of the mes-
sage, and compares the calculated value to the actual
value it received in the CRC field. If the two values
are not equal, the message will be discarded.
Sage Metering Modbus Protocol Rev. 1.80–Rev. 2.07
1 Parity on the Wireless Devices manufactured by Obvius is “None” rather than “Even”. The Sage
default is 19200-8-E-1. Change to 19200-8-N-1 for the Obvius Modhoppers and related wireless devices.
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
57
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
03 (0X03) READ HOLDING REGISTERS
Identical operation as code 04 READ INPUT REGIS-
T
ERS described below, except READ only.
04 (0X04) READ INPUT REGISTERS
Reads the binary contents of the specified register.
This is READ/WRITE register. Sage Prime values are
typically 32 bits wide (4 bytes) and contain a single
IEEE754 floating point value. Modbus registers are
16 bits wide (2 bytes) so a minimum of 2 Modbus
registers are required to transfer all floating point
bits to the master. See section titled Sage Floating
Point Format.
Query
The query message specifies the starting register
address and the quantity of registers to be read.
0x03 READ MULTIPLE HOLDING REGISTERS or 0x04 READ MULTIPLE INPUT REGISTERS
–QUERY– –RESPONSE– SA – SLAVE ADRESS SA 04 – FUNC CODE 04 RH – REG ADDR HI BC – # of data bytes to follow RL – REG ADDR LO DATA0 00 – # OF REGS HI DATA1 CT – # OF REGS LO DATAn CH – CRC MSB CH CRC MSB CL – CRC LSB CL CRC LSB
REG ADDR HI (RH) is set to:
01 for INTEGER access of integral values 02 for IEEE754 floating point 03 for Scaled (x1000) long integer of floating point value
REG ADDR LO (RL) is the starting address index into the register structure. See section titled Sage Register Index Values.
CT is the register count needed to transfer data. Typically this byte is set to 02 to request 1 full IEEE754 floating point value. (Modbus single registers are 16 bits wide, Sage floating point values are 32 bits wide.)
DATA0-DATAn are bytes in binary format returned from the slave device
representing the contents of the selected register(s).
NOTE: values indicated with 0x prefix are in hexadeci-
mal, otherwise in decimal notation.
Function Codes Supported by SAGE Prime
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
58
REV. 16-SIP/SRP
16 (0x10) WRITE REGISTERS
W
rites the binary contents of the specified register
into the meter. Sage Prime values are typically 32 bits
wide (4 bytes) and contain a single IEEE754 floating
p
oint value. Modbus registers are 16 bits wide (2
bytes) so a minimum of 2 Modbus registers are
required to transfer all floating point bits into the
meter. See section titled Sage Floating Point Format.
Query
The query message specifies the starting register
address and the quantity of registers to be written.
16 (0x10) WRITE MULTIPLE REGISTERS
–QUERY– –RESPONSE– SA – SLAVE ADRESS SA 0x10 – FUNC CODE 0x10 – 16 FUNC CODE RH – REG ADDR HI RH – REG ADDR HI RL – REG ADDR LO RL – REG ADDR LO 00 – # OF REGS HI 00 – # REGS HI CT – # OF REGS LO CT – # REGS LO BC – BYTES COUNT CH – CRC MSB DATA0 CL – CRC LSB DATA1 DATAn CH – CRC MSB CL – CRC LSB
REG ADDR HI (RH) is set to:
01 for INTEGER access of integral values 02 for IEEE754 floating point 03 for Scaled (x1000) long integer of floating point value
REG ADDR LO (RL) is the starting address index into the register structure. See section titled Sage Register Index Values.
CT is the register count needed to transfer data. Typically this byte is set to 02 to request 1 full IEEE754 floating point value.
BC is the actual number of bytes that follow.
DATA0-DATAn are bytes in binary format transmitted to the slave device representing the contents of the selected register(s).
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
59
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
17 (0x11) REPORT SLAVE IDENTIFICATION*
This query requests from the specified slave address
a detailed identification packet with a run status, and
Sage Prime and firmware revision response. (Prime
will not respond to broadcast slave address 00.)
Query
The query message specifies the slave address, func-
tion code, and CRC check words.
17 (0x11) REPORT SLAVE ID
–QUERY– –RESPONSE– SA – SLAVE ADRESS SA 11 – FUNC CODE 11 CL – CRC LSB BC – BYTES COUNT, 19 CH – CRC MSB SD – SLAVE ID (DEVICE SPECIFIC), 0x5A
RS – RUN STATUS INDICATOR, 0xFF ASCII Text – SAGE PRIME v1.81x CH
CL Response The Sage Prime will respond with an echo of the slave address and function code. The byte count will be 19 (0x13) to allow the master to account for all the remaining bytes that follow.
REPORT SLAVE ID Example: (Slave Address = 0x30 = 48, default) Master Query –> 30 11 D5 BC Prime Response –> 30 11 13 5A FF 53 61 67 65 20 50 72 69 6D 65 20
76 31 2E 38 31 20 F1 2B
ASCII translation–> Sage Prime v1.81
NOTE: THIS PAGE APPLIES TO REV. 1.81–1.83
ILLEGAL FUNCTION CODES*
The Sage Prime will respond to other Modbus func-
tion codes not documented in this revision, these
codes are considered unsupported by Sage Metering.
Unsupported function codes will cause the Prime to
reply with Modbus ILLEGAL FUNCTION status.
*Not implemented in revision 1.80
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
60
REV. 16-SIP/SRP
SAGE REGISTER INDEX VALUES
D
ATA ADDRESS
TYPE VALUE SIZE INDEX DESCRIPTION Byte slave_ad 1 BYTE 1 Modbus Slave Address* fl
oat flow_rate; 1 IEEE754 578 actual flow rate
oat flow_temp; 1 IEEE754 580 process temperature float rtd_mWatts; 1 IEEE754 582 sensor power reading float rtd_res; 1 IEEE754 584 actual sensor probe resistance fl
oat ref_res_r; 1 IEEE754 586 actual temperature probe resistance integ totalizer; 1 uLONG 312 actual displayed total
*
NOTE: Sage Prime Meters are factory programmed with the MODBUS slave address = 48 (0x30). It may be extremely useful to be able to write to an unknown slave address with a simple broadcast command. Be sure only one Sage Prime is connected during any broadcast writes using slave a
ddress = 0.
Writing into unspecified registers (not defined above)
can render the unit non-functional or overwrite fac-
tory calibration data yielding incorrect operation.
EXAMPLE MODBUS PACKET
Query
This packet will request of the addressed slave to
respond by sending back the contents of registers
578 to 582 (inclusive). Three registers: flow rate
through RTD mWatts in IEEE754 floating point
format.
0x31 – SAGE PRIME SLAVE ADDRESS (0x31 Hex = 49 Decimal default) 0x04 – READ INPUT REGS FUNCTION CODE 0x02 – STARTING REGISTER HI BYTE (0x01 = 256, 0x02 = 512, 0x03 = 768) 0x42 – STARTING REGISTER LO BYTE (512 + 66 = register access = 578) 0x00 – COUNT MSB (ALWAYS ZERO) 0x06 – COUNT OF ALL DESIRED REGISTERS 0xD5 – CRC HI BYTE 0x85 – CRC LO BYTE
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
61
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
INTEGER REPRESENTATION
Computer systems hosting a MODBUS network
t
ypically store integer values to represent non-
fractional quantities.
All registers addressed above 256 (0x0100-0x1FF) will
transfer 16 bit integral quantities in response to all
master queries. MODBUS requires that the register
count reflects each 16 bit registers transmitted to
ensure that no bytes are missing in the transfer of
integer quantities. (Note: Most Sage Prime registers
are IEEE754 quantities; integer representations of
these registers will require significant translation.)
IEEE754 FLOATING POINT
Computer systems hosting a MODBUS network typi-
cally store single precision floating point data in the
standard IEEE754 format.
All registers addressed above 512 (0x0200-0x02FF)
will transfer full 32 bit single precision quantities
in response to all master queries. MODBUS requires
that two 16 bit registers are transmitted to ensure
that no bytes are missing in the transmission of
32 bit quantities.
SCALED DECIMAL REPRESENTATION
Computer systems hosting a MODBUS network may
choose represent single precision floating point val-
ues as scaled long integers (32 bit values). The Sage
Prime will convert floating point registers to integral
units by multiplying the value by 1000.
Ex. Floating point value 1234.567 will be converted
to integral value 1234567
All registers addressed above 768 (0x0300-0x03FF)
will transfer full 32 bit scaled integer quantities in
Sage Register Output Format
response to all master queries. MODBUS requires
that two 16 bit registers are transmitted to ensure
that no bytes are missing in the transmission of
32 bit quantities.
For more information on the MODBUS protocol, see:
http://www.modbus.org/tech.php
SAGE ADDRESSER SOFTWARE
Addresser is a convenient software kit that includes
Addresser software, as well as an optically isolated
ULINX RS485 to USB converter. The Addresser is a
READ/WRITE Program with drop-down menus for
convenient user interface between your PC or laptop
and the Modbus Terminals of the Sage Prime. Con -
tact Sage for ordering information and instructions.
SAGE ADDRESSER TECHNICAL ASSISTANCE
Visit our website at www.sagemetering.com and
navigate to the Manuals/Download section
(http://www.sagemetering.com/manual.htm).
Click on the “Instructional Manuals & Technical
Data” button. User name: sage; password: 7243737.
Click on link “Click to View ADDRESSER
Procedures” and/or “Click to View MODBUS
Poll/PRIME Communications Setup Instructions”.
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
62
REV. 16-SIP/SRP
Sage Addresser Typical Printout (Version 3.14)
Units: SCFM Modbus:
0x31
Copyright 2011, Sage Metering Inc. 1 of 1
G
Section
APPENDIX
G
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
65
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
Sage Prime™ Field Programmable “Dongle”
Although virtually any setting on Sage Prime can
be changed by users who have Modbus® capability
(see pages 19 and 22 for terminal connections), not
all customers have that capability to communicate
with the Prime using its Modbus Compliant RS485
Communications. However, users do not need to
have a Modbus host or any special skill, since they
can also change configurations in the field by using
the patent pending Sage “Dongle”.
The Sage Prime device known as a “Dongle”, was
developed to facilitate making changes on Sage
Prime Flow Meter settings in the field. Simply con-
tact Sage and specify your requirement (such as the
new Full Scale, new Pipe Area, etc), and the device
will be programmed at Sage and sent directly to you
within a few days (there is a slight fee for this serv-
ice). The patent-pending Dongle can also be config-
ured as a Reset Totalizer device (i.e. it can be used
repeatedly, with any Sage Prime to easily reset the
Totalizer). The Dongle can also be programmed to
change Engineering Units, Filter Response and
numerous other parameters.
In fact, Dongles can also be used to provide multiple
gas calibrations. In this case, the requirements must
be specified at the time of ordering. For example, one
meter can be calibrated for four different gases with
totally different calibration ranges, by providing four
Dongles with the Flow Meter. When a different gas
calibration is needed, simply upload the data from
the appropriate Dongle. It only takes a few seconds
to do so.
Dongles come with a convenient well marked cable
that is connected to the RS485 terminals. Simply
remove the rear cover, connect the Dongle, and push
the button on the Dongle. An LED will illuminate,
and within 3 seconds the light will go out signaling
that the data transfer is complete.
1
Remove the
Dongle, close the cover, and you will notice that the
new settings have been uploaded (or in the case of a
Totalizer-Reset Dongle, you will notice that the
Totalizer has zeroed).
1 If the light does not go out, it will be necessary to repeat procedure. Remove finger for a few seconds
and then push button again.
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
66
REV. 16-SIP/SRP
TILT ENCLOSURE 45º (forward or backward) FOR APPLICATIONS WHERE CONDENSATION MAY DEVELOP ON INSIDE WALL OF PIPES
Correction Factors For Variation From Original Digester Gas Calibration
Sage can calibrate for any Digester Gas, Bio Gas or
Landfill Gas Mix. However, it may be helpful to have
correction factors for a typical calibration, in the
event that the composition changes after delivery.
The following examples assume that the initial cali-
bration was set up for 60% CH4 and 40% CO2.
a) 65% CH4 and 35% CO2: Multiply reading by
0.982 to correct it for new composition
b) 70% CH4 and 30% CO2: Multiply reading by
0.965 to correct it for new composition
c) 55% CH4 and 45% CO2: Multiply reading by
1.0185 to correct it for new composition
For smaller changes, the corrections are linear in
between
d) Also, if 100% saturated with H2O vapor (non-
condensing), multiply readings by 1.042
e) If 50% saturated with water, multiply reading by
1.021
(Water vapor correction is linear in between)
Also, use the 45 degree mounting method in order to
avoid droplets from hitting the sensor and causing
spikes (see above right)
Installations Where Pipe Condensation May Develop
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
67
S A G E M E T E R I N G , I N C .
REV. 16-SIP/SRP
J-Box and Upstream Orientation
5
.0
4.40
5
.0
2.72 2.72
FLOW DIRECTION
FLOW DIRECTION
F
RONT VIEW LOOKING DOWNSTREAM LOOKING UPSTREAM
FLOW DIRECTION
S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
68
REV. 16-SIP/SRP
What is a Thermal Mass Flow Meter?
FLOW SENSOR (Self Heated)
TEMPERATURE SENSOR (Reference Sensor)
• What is a Thermal Mass Flow Meter? It is a meter
that directly measures the gas mass flow based
on the principle of conductive and convective
heat transfer.
• All Meters have probes (Insertion Style) or Flow
Bodies (In-Line Style) that support a pair of
sensors, which are in contact with the gas.
• The sensors are RTDs, which are resistance tem -
perature detectors. They consist of highly stable
reference-grade platinum windings. In fact, we
use the same material that is used as Platinum
Resistance Standards at the NIST.
• The RTDs are clad in a protective 316 SS sheath
for industrial environments.
• One of the RTDs [See Diagram below] is self-heated
by the circuitry and serves as the flow sensor. The
other RTD acts as a reference sensor, and measures
the gas temperature. Essen tial ly it is used for tem-
perature compensation.
• The Sage proprietary hybrid-digital sensor drive
circuitry maintains a constant overheat between
the flow sensor and the reference sensor. As gas
flows by the heated sensor (flow sensor), the
molecules of flowing gas carry heat away from
this sensor, and the sensor cools down as it loses
energy. The circuit equilibrium is disturbed, and
momentarily the temperature difference between
the heated sensor and the reference sensor has
changed. The circuit will automatically (within
1 second) replace this lost energy by heating
up the flow sensor so the overheat temperature
is restored.
• The current required to maintain this overheat
represents the mass flow signal. There is no need
for external temperature or pressure devices.
Loading...