This document provides basic installation guidelines for the Rosemount 8732. It does not
provide instructions for detailed configuration, diagnostics, maintenance, service,
troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer
to the Rosemount 8732 reference manual (document number 00809-0100-4665) for
more instructions. The manual and this QIG are also available electronically on
www.rosemount.com.
Failure to follow these installation guidelines could result in death or serious
injury:
Installation and servicing instructions are for use by qualified personnel only. Do not
perform any servicing other than that contained in the operating instructions, unless
qualified. Verify that the operating environment of the sensor and transmitter is consistent
with the appropriate FM, CSA, ATEX, or IECEx approval.
Do not connect a Rosemount 8732 to a non-Rosemount sensor that is located in an
explosive atmosphere.
December 2012
The sensor liner is vulnerable to handling damage. Never place anything through the
sensor for the purpose of lifting or gaining leverage. Liner damage can render the sensor
useless.
To avoid possible damage to the sensor liner ends, do not use metallic or spiral-wound
gaskets. If frequent removal is anticipated, take precautions to protect the liner ends.
Short spool pieces attached to the sensor ends are often used for protection.
Correct flange bolt tightening is crucial for proper sensor operation and life. All bolts must
be tightened in the proper sequence to the specified torque limits. Failure to observe
these instructions could result in severe damage to the sensor lining and possible sensor
replacement.
Rosemount 8705 Magnetic Flowtube units ordered with non-standard paint options may
be subject to electrostatic discharge.
To avoid electrostatic charge build-up, do not rub the meter body with a dry cloth or clean
with solvents.
2
Quick Installation Guide
STEP 1: PRE-INSTALLATION
5.82
(148)
6.48 (165)
7.49 (190)
LOI Cover
4.97
(126)
8.81
(224)
3.00
(76)
3.07
(78)
4.97
(126)
1
/2”-14 NPT, CM20, (3 places)*
1
/2”-14 NPT, (2 places)*
00825-0100-4665, Rev AB
December 2012
Rosemount 8732
Before installing the Rosemount 8732 Magnetic Flowmeter Transmitter, there are several
pre-installation steps that should be completed to make the installation process easier:
• Identify the options and configurations that apply to your application
• Set the hardware switches if necessary
• Consider mechanical, electrical, and environmental requirements
Mechanical Considerations
The mounting site for the Rosemount 8732 transmitter should provide enough room for
secure mounting, easy access to conduit ports, full opening of the transmitter covers, and
easy readability of the display screen (see Figure 1).
If the Rosemount 8732 is mounted separately from the sensor, it is not subject to limitations
that might apply to the sensor.
Figure 1. Rosemount 8732 Dimensional Drawing
NOTE:
* M20 and PG 13.5 connections are available with the use of threaded conduit adapters.
3
Quick Installation Guide
00825-0100-4665, Rev AB
Rosemount 8732
December 2012
Environmental Considerations
To ensure maximum transmitter life, avoid excessive heat and vibration. Typical problem
areas include:
• High-vibration lines with integrally mounted transmitters
• Warm-climate installations in direct sunlight
• Outdoor installations in cold climates.
Remote-mounted transmitters may be installed in the control room to protect the electronics
from the harsh environment and provide easy access for configuration or service.
Both remotely and integrally mounted Rosemount 8732 transmitters require external power
so there must be access to a suitable power source.
Installation Procedures
Rosemount 8732 installation includes both detailed mechanical and electrical installation
procedures.
Mount the Transmitter
At a remote site the transmitter may be mounted on a pipe up to two inches in diameter or
against a flat surface.
Pipe Mounting
To mount the transmitter on a pipe:
1. Attach the mounting bracket to the pipe using the mounting hardware.
2. Attach the Rosemount 8732 to the mounting bracket using the mounting screws.
Hardware Jumpers/Switches
The 8732 PROFIBUS PA electronics board is equipped with two user-selectable hardware
switches. These switches do not have any functionality and should be left in the default
positions as listed below:
Simulate Enable: OFF
Transmitter Security:OFF
Changing the switch position will have no effect on the functionality of the electronics.
Electrical Considerations
Before making any electrical connections to the Rosemount 8732, consider local and plant
electrical standards and be sure to have the proper power supply, conduit, and other
accessories necessary to comply with these standards.
Rotate Transmitter Housing
The electronics housing can be rotated on the sensor in 90° increments by loosening the
four mounting bolts on the bottom of the housing, and reinstalling the bolts. When the
housing is returned to its original position, be sure the surface is clean and there is no gap
between the housing and the sensor. When rotating the housing more than 90° , be sure to
disconnect the wiring from the electronics board and reconnect once the housing is securely
tightened in the desired orientation.
4
Quick Installation Guide
STEP 2: HANDLING
STEP 3: MOUNTING
½- through 4-in. Sensors
6-in. and Larger Sensors
5 Pipe Diameters
2 Pipe Diameters
Flow
00825-0100-4665, Rev AB
December 2012
Handle all parts carefully to prevent damage. Whenever possible, transport the system to
the installation site in the original shipping containers. PTFE-lined sensors are shipped with
end covers that protect it from both mechanical damage and normal unrestrained distortion.
Remove the end covers just before installation.
Figure 2. Rosemount 8705 Sensor Support for Handling
Rosemount 8732
Upstream/Downstream Piping
T o ensure specification accuracy over widely varying process conditions, install the sensor a
minimum of five straight pipe diameters upstream and two pipe diameters downstream from
the electrode plane (see Figure 3).
Figure 3. Upstream and Downstream StraightPipe Diameters
Installations with reduced straight runs from 0 to 5 pipe diameters are possible. In reduced
straight pipe run installations, performance will shift. Reported flow rates will still be highly
repeatable.
5
Quick Installation Guide
FLOW
FLOW
00825-0100-4665, Rev AB
Rosemount 8732
December 2012
Flow Direction
The sensor should be mounted so the FORWARD end of the flow arrow, shown on the
sensor identification tag, points in the direction of flow through the sensor.
Sensor Location
The sensor should be installed in a position that ensures the sensor remains full during
operation. Vertical installation allows upward process fluid flow and keeps the
cross-sectional area full, regardless of flow rate. Horizontal installation should be restricted
to low piping sections that are normally full.
Figure 4. Sensor Orientation
The electrodes in the sensor are properly orientated when the two measurement electrodes
are in the 3 and 9 o’clock positions or within 45° from the vertical, as shown on the right of
Figure 5. Avoid any mounting orientation that positions the top of the sensor at 90° from the
vertical position as shown on the left of Figure 5.
Figure 5. Mounting Position
Incorrect
Correct
6
Quick Installation Guide
STEP 4: INSTALLATION
00825-0100-4665, Rev AB
December 2012
Rosemount 8732
Flanged Sensors
Gaskets
The sensor requires a gasket at each of its connections to adjacent devices or piping. The
gasket material selected must be compatible with the process fluid and operating conditions.
Metallic or spiral-wound gaskets can damage the liner. Gaskets are required on each side of
a grounding ring. All other applications (including sensors with lining protectors or a
grounding electrode) require only one gasket on each end connection.
Figure 6. Flanged gasket placement
Flange Bolts
NOTE
Do not bolt one side at a time. Tighten each side simultaneously. Example:
1. Snug left
2. Snug right
3. Tighten left
4. Tighten right
Do not snug and tighten the upstream side and then snug and tighten the downstream side.
Failure to alternate between the upstream and downstream flanges when tightening bolts
may result in liner damage.
Suggested torque values by sensor line size and liner type are listed in Table 1 for ASME
B16.5 and Table 2 for EN flanges. Consult the factory if the flange rating of the sensor is not
listed. Tighten flange bolts on the upstream side of the sensor in the incremental sequence
shown in Figure 7 to 20% of the suggested torque values. Repeat the process on the
downstream side of the sensor. For sensors with more or less flange bolts, tighten the bolts
in a similar crosswise sequence. Repeat this entire tightening sequence at 40%, 60%, 80%,
and 100% of the suggested torque values or until the leak between the process and sensor
flanges stop.
7
Quick Installation Guide
1
5
3
7
8
4
6
2
8-bolt
00825-0100-4665, Rev AB
Rosemount 8732
If leakage has not stopped at the suggested torque values, the bolts can be tightened in
additional 10% increments until the joint stops leaking, or until the measured torque value
reaches the maximum torque value of the bolts. Practical consideration for the integrity of
the liner often leads the user to distinct torque values to stop leakage due to the unique
combinations of flanges, bolts, gaskets, and sensor liner material.
Check for leaks at the flanges after tightening the bolts. Failure to use the correct tightening
methods can result in severe damage. Sensors require a second tightening 24 hours after
the initial installation. Over time, sensor liner materials may deform under pressure.
Figure 7. Flange Bolt Torquing Sequence
December 2012
Table 1. Suggested Flange Bolt Torque Values for Rosemount 8705 and 8707 High-Signal Sensors
The sensor requires a gasket at each of its connections to adjacent devices or piping. The gasket
material selected must be compatible with the process fluid and operating conditions. Metallic or
spiral-wound gaskets can damage the liner. Gaskets are required on each side of a
grounding ring. See Figure 8 below.
Figure 8. Wafer gasket placement
Spacer Installation
Horizontal meters
Alignment
1. On 1.5 through 8-inch (40 through 200 mm) line sizes. Rosemount strongly recommends
installing the alignment spacers provided to insure proper centering of the wafer sensor
between the process flanges. Sensor sizes of 0.15, 0.30, 0.5 and 1 in. (4 through 25
mm), do not require alignment spacers.
2. Insert studs for the bottom side of the sensor between the pipe flanges and center the
alignment spacer in the middle of the stud. See Figure 8 for the bolt hole locations
recommended for the spacers provided. Stud specifications are listed in Table 3.
3. Place the sensor between the flanges. Make sure that the alignment spacers are
properly centered on the studs. For vertical flow installations slide the oring over the stud
to keep the spacer in place. See Figure 8. To ensure the spacers match the flange size
and class rating for the process flanges see Table 4.
4. Insert the remaining studs, washers, and nuts.
5. Tighten to the torque specifications shown in Table 5. Do not overtighten the bolts or the
liner may be damaged.
Table 3. Stud Specifications
Nominal Sensor SizeStud Specifications
0.15 – 1 inch (4 – 25 mm)316 SST ASTM A193, Grade B8M Class 1 threaded mounted stu ds
1.5 – 8 inch (40 – 200 mm)CS, ASTM A193, Grade B7, thread ed mounting studs
NOTE
Sensor sizes of 0.15, 0.30, and 0.5 in. mount between AMSE 1/2-inch flanges. Using carbon
steel bolts on sensor sizes of 0.15, 0.30, 0.5 and 1 in. (15 and 25 mm), rather than the
required stainless steel bolts, will degrade the flow sensor measurement.
To order an Alignment Spacer Kit (qty 3 spacers) use p/n 08711-3211-xxxx along with the
Dash No. above.
12
Quick Installation Guide
00825-0100-4665, Rev AB
December 2012
Rosemount 8732
Flange Bolts
Wafer sensors require threaded studs. See Figure 7 for torque sequence. Always check for
leaks at the flanges after tightening the flange bolts. All sensors require a second torquing
24 hours after initial flange bolt tightening.
Table 5. Rosemount 8711 Torque Specifications
Size CodeLine SizePound-feetNewton-meter
15F0.15 inch (4 mm)57
30F0.30 inch (8 mm)57
0050.5 inch (15 mm)57
0101 inch (25 mm)1014
0151.5 inch (40 mm)1520
0202 inch (50 mm)2534
0303 inch (80 mm)4054
0404 inch (100 mm)3041
0606 inch (150 mm)5068
0808 inch (200 mm)7095
13
Quick Installation Guide
User supplied clamp
User supplied gasket
00825-0100-4665, Rev AB
Rosemount 8732
December 2012
Sanitary Sensors
Gaskets
The sensor requires a gasket at each of its connections to adjacent devices or piping. The
gasket material selected must be compatible with the process fluid and operating conditions.
Gaskets are supplied between the IDF fitting and the process connection fitting, such as a
Tri-Clamp fitting, on all Rosemount 8721 Sanitary sensors except when the process
connection fittings are not supplied and the only connection type is an IDF fitting.
Alignment and Bolting
Standard plant practices should be followed when installing a magmeter with sanitary
fittings. Unique torque values and bolting techniques are not required.
Figure 9. Rosemount 8721 Sanitary Installation
14
Quick Installation Guide
STEP 5: GROUNDING
Grounding Rings or Lining
Protectors
00825-0100-4665, Rev AB
December 2012
Use Table 6 to determine which process grounding option to follow for proper installation.
The sensor case should be earth grounded in accordance with national and local electrical
codes. Failure to do so may impair the protection provided by the equipment.
Table 6. Process Grounding Installation
Type of Pipe
Conductive Unlined
Pipe
Conductive Lined
Pipe
Non-Conductive
Pipe
Figure 10. Grounding Straps or Grounding Electrode in Lined Pipe
Grounding
Straps
See Figure 10Not RequiredNot RequiredSee Figure 11
Insufficient
Grounding
Insufficient
Grounding
Process Grounding Options
Grounding
Rings
See Figure 11See Figure 10See Figure 11
See Figure 12See Figure 13See Figure 12
Grounding
Electrode
Rosemount 8732
Lining
Protectors
Figure 11. Grounding with Grounding Rings or Lining Protectors
15
Rosemount 8732
Grounding Rings or Lining
Protectors
Figure 12. Grounding with Grounding Rings or Lining Protectors
Figure 13. Grounding with Grounding Electrode
Quick Installation Guide
00825-0100-4665, Rev AB
December 2012
16
Quick Installation Guide
STEP 6: WIRING
Coil Drive
and
Electrode
Cables
Power
Outputs
Power
Outputs
Coil Drive
and
Electrode
Cables
Power
Outputs
Power
Outputs
00825-0100-4665, Rev AB
December 2012
Rosemount 8732
This wiring section covers the connection between the transmitter and sensor, the
PROFIBUS PA fieldbus segment, and supplying power to the transmitter . Follow the conduit
information, cable requirements, and disconnect requirements in the sections below.
Conduit Ports and Connections
Both the sensor and transmitter junction boxes have ports for 1/2-inch NPT conduit
connections with optional CM20 or PG 13.5 connections available. These connections
should be made in accordance with national, local, and plant electrical codes. Unused ports
should be sealed with metal plugs. Proper electrical installation is necessary to prevent
errors due to electrical noise and interference. Separate conduits are not necessary for the
coil drive and signal cables, but a dedicated conduit line between each transmitter and
sensor is required. Shielded cable must be used for best results in electrically noisy
environments. When preparing all wire connections, remove only the insulation required to
fit the wire completely under the terminal connection. Removal of excessive insulation may
result in an unwanted electrical short to the transmitter housing or other wire connections.
For flanged sensors installed into an application requiring IP68 protection, sealed cable
glands, conduit, and conduit plugs that meet IP68 ratings are required.
Conduit Requirements
A single dedicated conduit run for the coil drive and signal cable is needed between the
sensor and the remote transmitter. See Figure 14. Bundled cables in a single conduit are
likely to create interference and noise problems in the system. Use one set of cables per
conduit run.
Figure 14. Conduit Preparation
WrongCorrect
17
Quick Installation Guide
STEP 6 CONTINUED...
Cable Shield
1.00
(26)
NOTE
Dimensions are in inches (millimeters).
00825-0100-4665, Rev AB
Rosemount 8732
December 2012
Run the appropriate size cable through the conduit connections in your magnetic flowmeter
system. Run the power cable from the power source to the transmitter. Run the coil drive
and signal cables between the flowmeter sensor and transmitter.
• Installed signal wiring should not be run together and should not be in the same cable
tray as AC or DC power wiring.
• Device must be properly grounded or earthed according to local electric codes.
• Rosemount combination cable part number 08732-0753-1003 (ft.) or 08732-0753-2004
(m) is required to be used to meet EMC requirements.
Transmitter to Sensor Wiring
The transmitter can be integral to the sensor or remotely mounted following the wiring
instructions.
Remote Mount Cable Requirements and Preparation
For installations using the individual coil drive and signal cable, lengths should be limited to
less than 1,000 feet (300 meters). Equal length cable is required for each. See Table 7.
For installations using the combination coil drive and signal cable, lengths should be limited
to less than 330 feet (100 meters). See Table 7.
Prepare the ends of the coil drive and signal cables as shown in Figure 15. Limit the
unshielded wire length to 1-inch on both the coil drive and signal cables. Any unsheathed
wire should be wrapped with proper insulation. Excessive lead length or failure to connect
cable shields can create electrical noise resulting in unstable meter readings.
Figure 15. Cable Preparation Detail
18
Quick Installation Guide
WARNING
00825-0100-4665, Rev AB
December 2012
Table 7. Cable Requirements
To order cable specify length as quantity desired. 25 feet = Qty (25) 08732-0753-1003
DescriptionLengthPart Number
Signal Cable (20 AWG)
Belden 8762, Alpha 2411
or equivalent
Combination Cable
Coil Drive Cable (18 AWG) and
Signal Cable (20 AWG)
ft
m
ft
m
ft
m
Rosemount 8732
08712-0060-0001
08712-0060-2013
08712-0061-0001
08712-0061-2003
08732-0753-1003
08732-0753-2004
Potential Shock Hazard Across Terminals 1 & 2 (40 Vac).
Wiring the Transmitter to the Sensor
When using individual cables for coil drive and signal refer to Table 8. If using the
combination coil drive and signal cable refer to Table9. See Figure16 for transmitter
specific wiring diagram.
1. Connect the coil drive cable using terminals 1, 2, and 3 (ground).
2. Connect the signal cable using terminals 17, 18, and 19.
Table 8. Individual Coil and Signal Cables
Transmitter TerminalSensor Terminal Wire GaugeWire Color
1114Clear
2214Black
3 or Ground3 or Ground14Shield
171720Shield
181820Black
191920Clear
Table 9. Combination Coil and Signal Cable
Transmitter TerminalSensor Terminal Wire GaugeWire Color
1118Red
2218Green
3 or Ground3 or Ground18Shield
171720Shield
181820Black
191920White
19
Quick Installation Guide
Sensors
00825-0100-4665, Rev AB
Rosemount 8732
Figure 16. Remote Mount Wiring Diagram
NOTE
When using the Rosemount supplied combination cable, the signal wires for terminals 18
and 19 contain an additional shield wire. These two shield wires should be tied with the main
shield wire at terminal 17 at the sensor terminal block and cut back to the insulation in the
transmitter junction box. See Figure 17.
Figure 17. Combination Coil and Signal Cable Wiring Diagram
Coil Drive Cable
Signal Cable
December 2012
Transsmiter
Cut Shield
1 Red 2 Green 3 Shield17 Shield 18 Black 19 White
Tube
17 Shield 18 Black 19 White1 Red 2 Green 3 Shield
20
Quick Installation Guide
00825-0100-4665, Rev AB
December 2012
Rosemount 8732
Integral Mount Transmitters
The interconnecting wire harness for an integral mount transmitter is installed at the factory.
See Figure 18. Do not use cable other than that supplied by Emerson Process
Management, Rosemount, Inc.
Figure 18. 8732EST Integral Mount Wiring Diagram
21
Quick Installation Guide
Control Room
00825-0100-4665, Rev AB
Rosemount 8732
December 2012
PROFIBUS PA Fieldbus Connection Wiring
Transmitter Communication Input
The PROFIBUS PA fieldbus communication requires a minimum of 9 V dc and a maximum
of 32 V dc at the transmitter communication terminals. Do not exceed 32 V dc at the
transmitter communication terminals. Do not apply ac line voltage to the transmitter
communication terminals. Improper supply voltage can damage the transmitter.
Field Wiring
Power independent of the transmitter power supply must be supplied for PROFIBUS PA
fieldbus communications. Use shielded, twisted pair for best results. In order to get
maximum performance in new applications, twisted pair cable specifically designed for
fieldbus communications should be used. The number of devices on a fieldbus segment is
limited by the power supply voltage, the resistance of the cable, and the amount of current
drawn by each device. See Table10 for cable specifications.
Table 10. Ideal Cable Specifications for Fieldbus Wiring
Each fieldbus power supply requires a power conditioner to decouple the power supply
output from the fieldbus wiring segment.
Figure 19. Power Connections
22
Quick Installation Guide
–PA signal
+PA signal
00825-0100-4665, Rev AB
December 2012
Transmitter Wiring Connection
Follow the steps listed below to wire the model 8732E PROFIBUS PA Fieldbus transmitter:
1. Ensure Power Conditioner and cable meet the requirements shown above in 'Field
Wiring'
2. Ensure the transmitter is not powered
3. Route Fieldbus wire through appropriate conduit entry
4. Connect one Fieldbus wire to terminal 1 and the other Fieldbus wire to terminal 2.The
8732E Fieldbus transmitter is polarity insensitive. See Figure 20.
When wiring to screw terminals, crimped lugs are recommended. Tighten the terminals to
ensure adequate contact. Both transmitter covers must be fully engaged to meet explosion
proof requirements. Do not remove the transmitter covers in an explosive atmosphere when
the transmitter is powered.
Figure 20. 8732E PROFIBUS PA Fieldbus Wiring Diagram
Rosemount 8732
23
Quick Installation Guide
12
18
24
30
36
42
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Power Supply (Volts)
I = Supply current requirement (Amps)
V = Power supply voltage (Volts)
Supply Current (Amps)
00825-0100-4665, Rev AB
Rosemount 8732
December 2012
Powering the Transmitter
The 8732E transmitter is designed to be powered by 90-250 Vac, 50–60 Hz or 12–42 Vdc.
Before connecting power to the Rosemount 8732E, consider the following standards and be
sure to have the proper power supply, conduit, and other accessories. Wire the transmitter
according to national, local, and plant electrical requirements for the supply voltage. See
Figure 21.
Figure 21. DC Power Supply Current Requirements
Supply Wire Requirements
Use 12 to 18 AWG wire rated for the proper temperature of the application. For connections
in ambient temperatures above 140 °F (60 °C), use a wire rated for 176 °F (80 °C). For
ambient temperatures greater than 176 °F (80 °C), use a wire rated for 230 °F (110 °C). For
DC powered transmitters with extended cable lengths, verify that there is a minimum of 12 V
DC at the terminals of the transmitter.
Disconnects
Connect the device through an external disconnect or circuit breaker. Clearly label the
disconnect or circuit breaker and locate it near the transmitter and per local electrical
control.
Installation Category
The installation category for the 8732E is (Overvoltage) Category II.
Overcurrent Protection
The Rosemount 8732E flowmeter transmitter requires overcurrent protection of the supply
lines. Maximum ratings of overcurrent devices are shown in Table 11.
Table 11. Overcurrent Limits
Power SystemFuse RatingManufacturer
95-250 V AC2 Amp, Quick ActingBussman AGC2 or Equivalent
12-42 V DC3 Amp, Quick ActingBussman AGC3 or Equivalent
24
Quick Installation Guide
00825-0100-4665, Rev AB
December 2012
8732E Power Supply
For AC power applications (90-250 VAC, 50-60 Hz) connect AC Neutral to terminal 9 (AC
N/L2) and connect AC Line to terminal 10 (AC/L1). For DC power applications connect
negative to terminal 9 (DC -) and positive to terminal 10 (DC +). Units powered by 12-42 V
DC power supply may draw up to 1 amp of current. See Figure 22 for terminal block
connections.
Figure 22. 8732E Transmitter Power Connections
Rosemount 8732
Cover Jam Screw
For transmitter housings shipped with a cover jam screw, the screw should be properly
installed once the transmitter has been wired and powered up. Follow these steps to install
the cover jam screw:
1. Verify that the cover jam screw is completely threaded into the housing.
2. Install the transmitter housing cover and verify that the cover is tight against the housing.
3. Using an M4 hex wrench, loosen the jam screw until it contacts the transmitter cover.
4. Turn the jam screw an additional
(Note: Application of excessive torque may strip the threads.)
5. Verify that the cover cannot be removed.
1
/2 turn counterclockwise to secure the cover.
25
Quick Installation Guide
00825-0100-4665, Rev AB
Rosemount 8732
December 2012
Step 7: Basic Configuration
Quick Start-Up
Once the magnetic flowmeter system is installed and communication is established,
configuration of the transmitter must be completed. The standard transmitter configuration,
without Option Code C1, Custom Configuration, is shipped with the following parameters:
The 8732E Magnetic Flowmeter Transmitter with PROFIBUS PA fieldbus is shipped with a
temporary address. T o change the Node Address and Ident Number , use the features of the
Local Operator Interface (LOI) or a configuration tool. The tools do the following:
• Change the Node Address to a user specified address on the network.
• Change the Ident Number to determine if the device will operate in Generic mode or
Manufacturer Specific mode. This setting affects the GSD file required by the host
system.
Flow-Specific Block Configuration
AI Block
The Analog Input (AI) function block provides the primary interface of the measurement to
the control and/or monitoring systems. To properly configure the device, the following
parameters should be reviewed and configured to ensure that the device is correctly
configured.
1. The first parameter is CHANNEL. The CHANNEL parameter defines which transducer
block measurement is used by the AI block. In the 8732E Magnetic Flowmeter
Transmitter, the channel will always be set to Flow. There is no other option for this
variable.
2. The second parameter is the LINEARIZATION TYPE. This parameter defines the
relationship between the block input and the block output. Since the 8732E Magnetic
Flowmeter Transmitter does not require linearization, this parameter will always be set to
No Linearization. This means that the AI block will only apply scaling, filtering, and limit
checking to the input value.
3. The third parameter is PV_SCALE. The Transducer Block VOLUME_FLOW_UNITS
define the unit of measure of the primary variable input and are directly related to the
choice of the PV_SCALE UPPER RANGE and LOWER RANGE values.
4. The fourth parameter is OUT_SCALE. The output from the AI Block is scaled according
to the relationship of the PV_SCALE and OUT_SCALE UPPER RANGE and LOWER
RANGE values.
5. The fifth group of parameters are the alarm limits. The High and Low warning and Fault
Alarm limits should be configured relative to the OUT_SCALE UPPER RANGE and
LOWER RANGE values to set the control limits for the primary variable.
26
Quick Installation Guide
Totalizers
Basic Setup
Detailed Setup
Totalizer 1
Totalizer 2
Totalizer 3
Flow Units
Sensor Size
Cal Number
Damping
Coil Frequency
PROFIBUS
AI Block Conf
LOI Config
Trims
8714i
Total 3 Value
Total 3 Conf ig
Tota l 3 Set
Tota l 3 Mode
Tota l 3 Units
Total 3 Preset
Device Address
Ident Selector
AI PV Scale
AI Out Scale
Total 1Va lue
Total 1 C onfig
Tota l 2 Val ue
Total 2 Config
Total 1 Set
Total 1 Mode
Total 1 Unit s
Total 1 Preset
Total 2 Set
Total 2 Mode
Total 2 Unit s
Total 2 Preset
PV Scale URV
Out Scale LRV
Out Scale Unit
Out Scale URV
Out Scale LRV
Run 8714i
View Results
TubeSignature
Measurements
Display Timing
Language
Write Lock
Auto Zero Trim
Universal Trim
Values
Re-signature
Recall Values
Coil Resist
Coil Signature
Electrode Res
PV
Totaliz er 1
Totaliz er 2
Totaliz er 3
Coil Resist
Coil Signature
Electrode Res
00825-0100-4665, Rev AB
December 2012
Rosemount 8732
Slot Configuration
The 8732E has 4 slots that must be configured. If a slot is not going to be used, it must be
configured as an empty slot.
Figure 23 shows an example of a basic slot configuration for the Primary Variable (PV or
Flow), and the totalized flow value.
Figure 23. Basic Slot Configuration
Consult the GSD file for more details on what each slot can be configured for.
Figure 24. 8732E PROFIBUS P A LOI Menu Tree
27
Quick Installation Guide
00825-0100-4665, Rev AB
Rosemount 8732
December 2012
Product Certifications
Approved Manufacturing Locations
Rosemount Inc. — Eden Prairie, Minnesota, USA
Fisher-Rosemount Technologias de Flujo, S.A. de C.V. — Chihuahua, Mexico
Emerson Process Management Flow — Ede, The Netherlands
Asia Flow Technology Center — Nanjing, China
EUROPEAN DIRECTIVE INFORMATION
The EC declaration of conformity can be found on page 35. The most recent revision can be
found at www.rosemount.com.
Type n protection type in accordance with EN50021
• The installation of external connections and the plugging of any unused entries must be
carried out using appropriate Ex e or Ex n cable glands and blanking plugs, component
certified by an approved Certification Body.
CE Marking
Complies with EN 61326-1 : 2006
For Rosemount 8732E transmitters:
Complies with Essential Health and Safety Requirements:
EN 60079-0: 2006
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-11: 2007
EN 60079-15: 2005
EN 61241-0: 2004
EN 61241-1: 2006
International Certificates
C-Tick Marking
Rosemount Inc. complies with the following IEC Requirements.
For Rosemount 8732E transmitters:
For the 8732E transmitters with a local operator interface (LOI), the lower ambient
temperature limit is -20 °C.
NOTE
For intrinsically safe (IS) outputs on the 8732E output option code F must be selected.
IS outputs for Class I, Division 1, Groups A, B, C, D. Temp Code – T4 at 60 °C
IS outputs for Ex de [ia] IIB or IIC T6
NOTE
For the 8732E transmitters with a local operator interface (LOI), the lower ambient
temperature limit is -20 °C.
North American Certifications
FM Approvals
N0 Non-incendive for Class I, Division 2
Groups A, B, C, and D non-flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T5 at 60 °C)
Hazardous Locations; Enclosure Type 4X
N5 Non-incendive for Class I, Division 2,
Groups A, B, C, and D flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T5 at 60 °C)
Hazardous Locations; Enclosure Type 4X
Requires sensors with N5 Approval
Rosemount 8732
E5 Explosion proof for Class I, Division 1
Groups C and D (T6 at 60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T5 at 60 °C),
Non-incendive for Class I, Division 2
Groups A, B, C, and D flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Hazardous Locations; Enclosure Type 4X
Canadian Standards Association (CSA)
N0 Non-incendive for Class I, Division 2
Groups A, B, C, and D non-flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T4 at 60 °C)
Hazardous Locations; Enclosure Type 4X
29
Rosemount 8732
European Certifications
E1ATEX Flameproof
Certificate No: KEMA 07ATEX0073 X
II 2G Ex de IIC T6 or
II 2G Ex de [ia] IIC T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
0575
EDATEX Flameproof
Certificate No.: KEMA 07ATEX0073 X II 2G
Ex de IIB or Ex de [ia] IIB T6 (-50°C Ta +60 °C)
with LOI (-20°C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
0575
ND ATEX Dust
Certificate No: KEMA 07ATEX0073 X
II 1D Ex tD A20 IP66 T100 °C or
with I.S. outputs
II G [Ex ia] IIC
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
IP 66
0575
Quick Installation Guide
00825-0100-4665, Rev AB
December 2012
Special conditions for safe use (KEMA 07ATEX0073 X):
Contact Rosemount Inc. for information on the dimensions of the flameproof joints. The
property class of the security screws which attach the flowtube or junction box to the
transmitter is SST A2-70, or SST A4-70.
Installation Instructions:
The cable and conduit entry devices and blanking elements shall be of a certified
flameproof or increased safety type, suitable for the conditions of use and correctly
installed. With the use of conduit, a certified stopping box shall be provided immediately
to the entrance of the enclosure.
30
Quick Installation Guide
00825-0100-4665, Rev AB
December 2012
N1 ATEX Type n
Certificate No: Baseefa 07ATEX0203X
II 3G Ex nA nL IIC T4
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 42 V DC
max
IP 66
0575
Special conditions for safe use (x):
The apparatus is not capable of withstanding the 500V insulation test required by
Clause 6.8.1 of EN 60079-15: 2005. This must be taken into account when installing the
apparatus.
International Certifications
IECEx
E7 IECEx Flameproof
Certificate No: KEM 07.0038X
Ex IIC or Ex de [ia] IIC T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
Rosemount 8732
EF IECEx Flameproof
Certificate No: KEM 07.0038X
Ex de IIB or Ex de [ia] IIB T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
NF IIECEx Dust
Certificate No: KEM 07.0038X
Ex tD A20 IP66 T 100 °C
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
Special conditions for safe use (KEM 07.0038X):
Contact Rosemount Inc. for information on the dimensions of the flameproof joints. The
property class of the security screws which attach the flowtube or junction box to the
transmitter is SST A2-70, or SST A4-70.
Installation Instructions:
The cable and conduit entry devices and blanking elements shall be of a certified
flameproof or increased safety type, suitable for the conditions of use and correctly
installed. With the use of conduit, a certified stopping box shall be provided immediately
to the entrance of the enclosure.
31
Quick Installation Guide
00825-0100-4665, Rev AB
Rosemount 8732
N7 IECEx Type n
Certificate No: IECEx BAS 07.0062X
Ex nA nL IIC T4
with FISCO / FNICO output
Ex nA nL [ia] IIC T4
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 42 V DC
max
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500V insulation test required by
Clause 6.8.1 of IEC 60079-15: 2005. This must be taken into account when installing
the apparatus.
NEPSI - China
E3 NEPSI Flameproof
Certificate No: GYJ071438X
Ex de IIC T6 or Ex de [ia] IIC T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
EP NEPSI Flameproof
Certificate No: GYJ071438X
Ex de IIB T6 or Ex de [ia] IIB T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
December 2012
InMetro - Brazil
E2 InMetro Flameproof
Certificate No: NCC 12.1177 X
Ex de IIC T6 Gb IP66 or
Ex de [ia IIC Ga] IIC T6 Gb IP66
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
EB InMetro Flameproof
Certificate No: NCC 12.1177 X
Ex de IIB T6 Gb IP66 or
Ex de [ia IIC Ga] IIB T6 Gb IP66
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
32
Quick Installation Guide
00825-0100-4665, Rev AB
December 2012
KOSHA - Korea
E9 KOSHA Flameproof
Certificate No: 2008-2094-Q1X
Ex de IIC or Ex de [ia] IIC T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
EK KOSHA Flameproof
Certificate No: 2008-2094-Q1X
Ex de IIB or Ex de [ia] IIB T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
V
= 250 V AC or 42 V DC
max
GOST - Russia
E8 GOST Flameproof
Ex de IIC T6 or Ex de [ia] IIC T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
IP67
EM GOST Flameproof
Ex de IIB T6 or Ex de [ia] IIB T6
without LOI (-50 °C Ta +60 °C)
with LOI (-20 °C Ta +60 °C)
IP67
Rosemount 8732
33
Quick Installation Guide
00825-0100-4665, Rev AB
Rosemount 8732
December 2012
Sensor Approval Information
For
(1)
Rosemount 8707
Sensor
For Non-
flammable
Fluids
Flammable
For
Fluids
Rosemount 8711
Sensor
For Non-
flammable
Fluids
Flammable
For
Fluids
Table 12. Sensor Option Codes
Rosemount 8705
Sensor
For Non-
Approval
Codes
E5
(1) CE Marking is standard on Rosemount 8705, 8711, and 8721.
(2) Available in line sizes up to 8 in. (200 mm) only.