Rosemount 3051SMV, 3051S, 3051SF Series Quick Installation Manual

Quick Installation Guide
Step 1: Mount the Transmitter Step 2: Consider Housing Rotation Step 3: Set Switches Step 4: Connect Wiring and Power Up Step 5: Flow Configuration Step 6: Verify Device Configuration Step 7: Trim the Transmitter Product Certifications
Start
End
00825-0100-4803, Rev BA April 2011
Rosemount 3051SMV
Rosemount 3051S MultiVariable™ Transmitter
Rosemount 3051SF Series Flowmeter MultiVariable Transmitter
¢00825-0100-4801J¤
www.rosemount.com
Quick Installation Guide
IMPORTANT NOTICE
WARNING
00825-0100-4803, Rev BA
Rosemount 3051SMV
© 2011 Rosemount Inc. All rights reserved. All marks property of owner. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
Rosemount Inc.
8200 Market Boulevar d Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-888 8 F (952) 949-7001
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947/65 6777 0743
This installation guide provides basic guidelines for the Rosemount 3051S MultiVariable transmitter (reference manual document number 00809-0100-4803). It also provides the basic 3051S MultiVariable transmitter configuration guidelines for the 3051SFA (reference manual document number 00809-0100-4 809), 3051SFC (reference manual docume nt number 00809- 0100-4810), and 3051SFP (refere nce manual document number 00809-0100-468 6). It does not provide ins tructions for diagno stics, mainten ance, service , or troubleshooting. Refer to the 3051S MultiVariable transmitter reference manual for more instruction. All documents are available electronically at www.emersonprocess.com/rosemount.
Emerson Process Management GmbH & Co. OHG
Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390 , F49 (8153) 939172
Beijing Rosemount Far East Instrument Co., Limited
No. 6 North Street, Hepingli, Dong Cheng District Beijing 100013, China T (86) (10) 6428 2233 F (86) (10) 6422 8586
April 2011
Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, na tional, and internati onal sta ndards, codes, a nd practices. P lease review the approvals sec tion of the 3051S MultiVariable transmitter reference manual (00809-0100-4803) for any restrictions associated with a safe installation.
• Before connecting a Field communica tor in an explosive atmosphere, ensure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
2
Quick Installation Guide
STEP 1: MOUNT THE TRANSMITTER
00825-0100-4803, Rev BA April 2011
Liquid Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented upward.
Gas Flow Applications
1. Place taps in the top or side of
Rosemount 3051SMV
the line.
2. Mount beside or above the taps.
Steam Flow Applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
3
Quick Installation Guide
Pipe MountPanel Mount
Pipe Mount
Panel Mount
00825-0100-4803, Rev BA
Rosemount 3051SMV
Mounting Brackets
Coplanar™ Flange
Tr aditional Flange
April 2011
4
Quick Installation Guide
4 x 1.75-in.
(44 mm)
4 x 2.88-in.
(73 mm)
A. Transmitter with Coplanar Flange
B. Transmitter with Coplanar Flange and Optional Flange Adapters
C. Transmitter with Traditional Flange and Optional Flange Adapters
D. Transmitter with Coplanar Flange and Optional Manifold and Flange Adapters
4 x 1.75-in.
(44 mm)
4 x 1.50-in.
(38 mm)
4 x 1.75-in.
(44 mm)
4 x 2.25-in.
(57 mm)
00825-0100-4803, Rev BA April 2011
Rosemount 3051SMV
Bolting Considerations
If the transmitter installation requires assembly of a process flange, manifold, or flange adaptors, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitter. Only use bolts supplied with the transmitter or sold by Emerson Process Management as spare parts. Figure 1 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
Figure 1. Common Transmit ter Assemblies
5
Quick Installation Guide
Module Isolator Plate
Bolt
B7M
316
316
316
SW
316
STM
316
R
B8M
00825-0100-4803, Rev BA
Rosemount 3051SMV
April 2011
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Figure 3. If bolt material is not shown in Figure 3, contact the local Emerson Process Management representative for more information.
Use the following bolt installation procedure:
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing p attern. See Figure 3 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing pattern. See Figure 3 for final torque value.
5. Verify that the flange bolts are protruding through the module isolator plate before applying pressure.
Figure 2. Module Isolator Plate
Figure 3. Torque Values for the Flange and Flange Adap ter Bolts
Bolt Material Head Markings Initial T orque Final Torque
Carbon Steel (CS)
Stainless Steel (SST)
300 in.-lbs. 650 in.-lbs.
150 in.-lbs. 300 in.-lbs.
6
Quick Installation Guide
WARNING
Rosemount 3051S / 3051 / 2051 / 3095
Rosemount 1151
Flange Adapter
O-ring
Flange Adapter
O-ring
PTFE Based
Elastomer
PTFE
Elastomer
00825-0100-4803, Rev BA April 2011
Rosemount 3051SMV
O-rings with Flange Adaptors
Failure to install proper flange adapter O-rings may cause process leaks, which
can result in death or serious injury. The two flange adapters are distinguished
by unique O-ring grooves. Only use the O-ring that is designed for its specific
flange adapter, as shown below.
Whenever the flange or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or cuts. If the o-rings are replaced, re-torque the flange bolts and alignment screws after installation to compensate for seating of the o-rings.
7
Quick Installation Guide
STEP 2: CONSIDER HOUSING ROTATION
Housing Rotation Set Screw
(3/32-in.)
Feature Board
00825-0100-4803, Rev BA
Rosemount 3051SMV
To improve field access to wiring or to better view the optional LCD display:
Figure 4. T ransmitter Housing Set Screw
April 2011
1. Loosen the housing rotation set screw.
2. Turn the housing up to 180° left or right of its original (as shipped) position.
3. Retighten the housing rotation set screw.
NOTE
Do not rotate the housing more than 180° wit hout first performing a disassembly procedure (see Section 4 of the 3051S MultiVariable transmitter reference manual (00809-0100-4803) for more information). Over-rotation may sever the electrical connection between the sensor module and the feature board electronics.
8
Quick Installation Guide
STEP 3: SET SWITCHES
Alarm
Security
00825-0100-4803, Rev BA April 2011
The transmitter’s default configuration sets the alarm condition to high (HI) and the security to off.
1. If the transmitter is installed, secure the loop and remove power.
2. Remove the housing cover opposite the field terminals side. Do not remove the housing cover in explosive environments.
3. Slide the security and alarm switches into the preferred position by using a small screwdriver.
4. Reinstall the housing cover so that metal contacts metal to meet explosion-proof requirements.
Figure 5. Transmitter Switch Configuration
Rosemount 3051SMV
9
Quick Installation Guide
STEP 4: CONNECT WIRING AND POWER UP
IMPORTANT NOTICE
00825-0100-4803, Rev BA
Rosemount 3051SMV
NOTE
Do not connect the power across the test terminals. Power could damage the test diode in the test connection. Twisted pa irs yield best result s. Use 24 A WG to 14 AWG wire and do not exceed 5,000 feet (1500 meters).
Use the following steps to wire the transmitter:
1. Remove the cover on the field terminals side of the housing.
2. Connect the positive lead to the “PWR/COMM +” terminal, and the negative lead to the “PWR/COMM –” terminal.
3. If the optional process temperature input is not installed, plug and seal the unused conduit connection. If the optional process temperature input is being utilized, see “Install Optional Process Temperature Input (Pt 100 RTD Sensor)” on page 13 for more
April 2011
information.
When the enclosed pipe plug is utilized in the conduit opening, it must be installed with a minimum engagement of five threads in order to comply with explosion-proof requirements. Refer to the 3051S MultiVariable transmitter reference manual (document number 00809-0100-4803) for more information.
4. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
5. Reinstall the housing cover and tighten so that metal contacts metal to meet explosion-proof requirements.
10
Quick Installation Guide
RL 250
Power Supply
Power Supply
RL 250
00825-0100-4803, Rev BA April 2011
Rosemount 3051SMV
Figure 6 shows the wiring connections necessary to power a 3051S MultiV ariable transmitter and enable communications with a hand-held Field Communicator.
Figure 6. Transmitter Wiring
3051SMV without Optional Process
Temper at u r e C o nn e c t io n
3051SMV with Optional Process
Temperature Connection
NOTE
Installation of the tran sient protectio n terminal block does no t provide transient protection unless the 3051S MultiVariable transmitter housing is properly grounded.
Conduit Electrical Connector Wiring (Option GE or GM)
For 3051S MultiV ariable transmitters with conduit electrical connectors GE or GM, refer to the cordset manufacturer’s installation instructions for wiring details. For FM Intrinsically Safe, Division 2 hazardous locations, install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA 4X and IP66.) See Appendix B of the 3051S MultiVariable transmitter reference manual (00809-0100-4803).
11
Quick Installation Guide
Voltage (Vdc)
Load (Ohms)
Operating
Region
1322
1000
500
0
12.0 20 30
42.4
00825-0100-4803, Rev BA
Rosemount 3051SMV
April 2011
Power Supply
The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator , intrinsic safety barriers, and related components.
Figure 7. Load Limitation
3051S MultiVariable Transmitter
Maximum Loop Resistance = 43.5 x (Power Supply Voltage – 12.0)
HART communication requires a minimum
12
loop resistance of 250.
Quick Installation Guide
RTD Cable Assembly
Wires
Red
White
Pt 100
RTD
Sensor
Ground Lug
00825-0100-4803, Rev BA April 2011
Rosemount 3051SMV
Install Optional Process Temperature Input (Pt 100 RTD Sensor)
NOTE
To meet ATEX/IECEx Flameproof certification, only ATEX/IECEx Flameproof Cables (Temperature Input Code C30, C32, C33, or C34) may be used.
1. Mount the Pt 100 RTD Sensor in the appropriate location.
NOTE
Use shielded four-wire cable for the process temperature connection.
2. Connect the RTD cable to the 3051S MultiVariable transmitter by inserting the cable wires through the unused housing conduit and connect to the four screws on the transmitter terminal block. An appropriate cable gland should be used to seal the conduit opening around the cable.
3. Connect the RTD cable shield wire to the ground lug in the housing.
Figure 8. 3051S MultiVariable Transmitter RTD Wiring Connection
13
Quick Installation Guide
STEP 5: FLOW CONFIGURATION
00825-0100-4803, Rev BA
Rosemount 3051SMV
April 2011
Engineering Assistant 6.1 or Later
The 3051SMV Engineering Assistant 6.1 or later is PC-based software that performs configuration, maintenance, diagnostic functions, and serves as the primary communication interface to the 3051S MultiVariable transmitter with the Fully Compensated Mass and Energy Flow Feature Board.
The 3051SMV Engineering Assistant software is required to complete the flow configuration.
Installation and Initial Setup
The following are the minimum system requirements to install the 3051SMV Engineering Assistant software:
• Pentium-grade Processor: 500 MHz or faster
• Operating System: Windows 2000(32-bit), Windows XP Professional (32-bit), or Windows 7 (32-bit)
• 256 MB RAM
• 100 MB free hard disk space
• RS232 serial port or USB port (for use with HART modem)
• CD-ROM
14
Loading...
+ 32 hidden pages