Ronan X11CA User Manual

Page 1
X11CA-IM
MASTER MODULE
(Firmware: X11-MF3 Rev. 3)
REVISION : 2.0 DOCUMENT NUMBER : DATE : EDITOR : Nana Lee Ronan Engineering Company APPROVED : Kevin Safayieh 4/23/03
Project Manager Date APPROVED : Razmik Haftvani 4/23/03 Engineering Manager Date APPROVED : Tony Gasca 4/23/03 Q.A. Date
Ronan Engineering
21200 Oxnard Street, Woodland Hills, CA 91367 TEL (818) 883-5211 FAX (818) 992-6435
Direct urgent problems to: 1-800-327-6626
X11CA-3000-IOM April 21, 2003
Copyright 2003 Ronan Engineering Company. All rights reserved. This document may not be reproduced or transmitted in any form, electronic or mechanical, including photocopying, recording, storing in an information retrieval system, or translating, in whole or in part, without the prior written permission of Ronan Engineering Company.
Page 2
Rev 2.0 : X11CA-IM MASTER MODULE
1 OVERVIEW..............................................................................................................1
1.1 Definitions ..............................................................................................................1
1.2 Revision History.....................................................................................................1
1.3 Reference Documents.............................................................................................2
2 X11-MF3 FIRMWARE.............................................................................................3
3 Cables.......................................................................................................................4
3.1.1 RS232: Laptop to X11CA-IM(P2)....................................................................... 4
3.1.2 RS232: PC to X11CA-IM(P2)............................................................................. 4
4 MODBUS COMMUNICATION PROTOCOL.........................................................5
4.1 Slave Address Setting.............................................................................................5
4.2 Data Communication Format.................................................................................5
4.3 Modbus RTU Protocol Function 3: Read the Holding Registers ...........................5
4.4 Modbus RTU Protocol Function 5: Force Single Cells ..........................................7
5 LED'S STATUS .......................................................................................................9
6 SETTING THE ALARM MODULE ADDRESSES...............................................10
7 PRGM/RUN SWITCH..............................................................................................15
7.1 Program Mode ......................................................................................................15
7.2 Run Mode .............................................................................................................15
7.2.1 Relay Outputs ..................................................................................................15
7.2.2 Functions of the Push Buttons ...........................................................................15
8 APPENDIX A: LIST OF TABLES..........................................................................17
9 APPENDIX B: LIST OF FIGURES.........................................................................18
i
Page 3
Rev 2.0 : X11CA-IM MASTER MODULE
1 OVERVIEW
The X11CA-IM Interface Module monitors alarm module activities. It also provides special features, such as Slave Modbus RTU Protocol on Port (P2), time stamped event archive, common trouble alarm, dual horn output, reflash output and system diagnostic output. All outputs are generated in the form of an open collector transistor and selectable Form C dry contact. The LEDs on the board indicate serial communication and system status.
Figure 1-1 X11CA-IM
1.1 Definitions
RS-232 A point-to-point serial connection standard. The RS-232 standard
was designed for communication over short distances (up to 50 feet).
1.2 Revision History
Revision 1.0 ECO11217 : Page 1, Definition Section, RS-232 was revised to
remove the line, ‘and at relatively slow data rates, (up to 20 kbps). However, in practice, these limits can be exceeded’
1
Page 4
Rev 2.0 : X11CA-IM MASTER MODULE
Revision 2.0 ECO11939 FIRMWARE was upgraded to Version 3 Added
MODBUS function 3& 5
1.3 Reference Documents
QA400 Design Control QA4000 Design Development Quality Assurance Plan QA4500 Project Archive
X11CA-3001-IOM X11CA Configuration Software User’s Manual
2
Page 5
Rev 2.0 : X11CA-IM MASTER MODULE
2 X11-MF3 FIRMWARE
The firmware on the X11CA-IM scans each X11CA alarm module for the following information.
Field contacts (A, B, C, D), H1 (Horn1), H2 (Horn2) and CTA (Common Trouble Alarm), Operation mode for each channel (IA, IB, IC, ID), First Out indication for each channel (FA, FB, FC, FD)
The scanned information is then stored into the holding registers, starting at the address 00, in two byte format as shown below.
Hi byte FD FC FB FA ID IC IB IA
Low byte S H2 H1 CTA D C B A
The following list has the descriptions of each data bit.
Descriptions A Status of the first input B Status of the second input C Status of the third input D Status of the forth input CTA Status of Common Trouble Alarm H1 Status of the Horn1 H2 Status of the Horn2 S Communication status bit: 0=Successful, 1=Failed to communicate with
X11CA Alarm modules.
IA Operation mode of Channel A. If IA=0, CH A is Contact Input.
If IA=1, CH A is serial input.
IB Operation mode of Channel B. If IB=0, CH B is Contact Input.
If IB=1, CH B is serial input.
IC Operation mode of Channel C. If IC=0, CH C is Contact Input.
If IC=1, CH C is serial input.
ID Operation mode of Channel D. If ID=0, CH D is Contact Input.
If ID=1, CH D is serial input.
FA If FA=1, CH A is the First Out channel withi n the group. FB If FB=1, CH B is the First Out channel within the group. FC If FC=1, CH C is the First Out channel within the group. FD If FD=1, CH D is the First Out channel within the group.
Table 2-1 Descriptions of Modbus Communication Data Format
3
Page 6
Rev 2.0 : X11CA-IM MASTER MODULE
3 CABLES
The Port 2 is communication port to host device and can be either RS232 or isolated RS485.
? The RS485 connection is a 5 pin screw terminal and the pin assignments are
marked on the cover.
? The RS232 connection is the 9 pin female connector and the pin assignments
are listed below.
3.1.1 RS232: Laptop to X11CA-IM(P2)
Figure 3-1 RS232 Cable from the Laptop to X11CA-IM Connection
3.1.2 RS232: PC to X11CA-IM(P2)
Figure 3-2 RS232 Cable from the Laptop to X11CA-IM Connection
4
Page 7
Rev 2.0 : X11CA-IM MASTER MODULE
4 MODBUS COMMUNICATION PROTOCOL
4.1 Slave Address Setting
The Slave Address switch (SW1 or SW3, depending on the revision of the PCB) on the X11CA-IM Module sets the Slave Address of the X11CA-IM Master Module for MODBUS RTU communication as shown below.
Slave
address
10 ON OFF OFF ON 11 OFF ON OFF ON 12 ON ON OFF ON 13 OFF OFF ON ON 14 ON OFF ON ON 15 OFF ON ON ON 16 ON ON ON ON
SW1-1 SW1-2 SW1-3 SW1-4
1 OFF OFF OFF OFF 2 ON OFF OFF OFF 3 OFF ON OFF OFF 4 ON ON OFF OFF 5 OFF OFF ON OFF 6 ON OFF ON OFF 7 OFF ON ON OFF 8 ON ON ON OFF 9 OFF OFF OFF ON
Table 4-1 Setting Modbus Slave Address
4.2 Data Communication Format
The data format for Modbus communication is 19200, no parity, 8 bit and 1 stop bit.
4.3 Modbus RTU Protocol Function 3: Read the Holding Registers
To read the binary contents of the holding registers on the X11CA-IM from a host device, use Modbus RTU Protocol function 3.
Query
The query message specifies the starting register and the quantity of registers to be read. Registers are addressed starting at zero: registers 1-16 are addressed as 0-15.
5
Page 8
Rev 2.0 : X11CA-IM MASTER MODULE
EXAMPLE: The following example reads registers 40108-40110 from the slave device 17.
11 6B
HEX
HEX
= 10001
=1101011
BIN
BIN
=17
=107
DEC
Field Name Example (Hex)
Slave Address 11 Function 03 Starting Address Hi 00 Starting Address L 6B No. of Points Hi 00 No. of Points Lo 03 Error Check (LRC or CRC) --
Table 4-2 Modbus Function 3 Example-Query
Response
The register data in the response message is packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits.
EXAMPLE: The following example is a response to the query.
Field Name Example (Hex)
Slave Address 11 Function 03 Byte Count 06 Data Hi (Register 40108) 02 Data Lo (Register 40108) 2B Data Hi (Register 40109) 00 Data Lo (Register 40109) 00 Data Hi (Register 40110) 00 Data Lo (Register 40110) 64 Error Check (LRC or CRC) --
DEC
Table 4-3 Modbus Function 3 Example-Response
The register 40108 contains two byte values of 02 2B The register 40109 contains 00 00 The register 40110 contains 00 64
6
HEX HEX
(=0
DEC).
(=100
DEC).
HEX
(=555
DEC).
Page 9
Rev 2.0 : X11CA-IM MASTER MODULE
4.4 Modbus RTU Protocol Function 5: Force Single Cells
To send alarms to X11CA-IM serially, use Modbus RTU Protocol function 5. Function 5 allows you to set a single window either to ON or OFF.
Query
The query message specifies the windows reference to be forced. Windows are addressed starting at zero. The first window is addressed as 0.
The requested ON/OFF state is specified by a constant in the query data field. A value of FF 00 hex requests the window to be ON. A value of 00 00 requests it to be OFF. All other values are illegal and will not affect the window.
EXAMPLE: The following example sets the window 173 ON in the slave device 17 (X11CA-IM).
11 AC
HEX
HEX
= 10001
BIN
=10101100
BIN
=17
=172
DEC
DEC
Field Name Example (Hex)
Slave Address 11 Function 05 Window Address Hi 00 Wi ndow Address L AC Force Data Hi FF Force Data Lo 00 Error Check (LRC or CRC) --
Table 4-4 Modbus Function 5 Example-Query
Response
The normal response is an echo of the query, returned after the window state has been forced.
EXAMPLE: The following example is a response to the query.
7
Page 10
Rev 2.0 : X11CA-IM MASTER MODULE
Field Name Example (Hex)
Slave Address 11 Function 05 Window Address Hi 00 Window Address L AC Force Data Hi FF Force Data Lo 00 Error Check (LRC or CRC) --
Table 4-5 Modbus Function 5 Example-Response
NOTE:
In order to send serial alarms to any X11CA window, its corresponding input channel must be programmed to the serial mode.
8
Page 11
Rev 2.0 : X11CA-IM MASTER MODULE
5 LED'S STATUS
? The RUN LED is a green color LED and starts flashing upon applying power to
the unit. When flashing, it indicates the power in on and the firmware is running in the unit.
? The ERROR LED is RED and when flashes ON/OFF, it indicates one or more
than one alarm boards not responding to the master module.
? The RXD1, TXD1, RXD2, TXD2 are amber color LEDs and they indicate the
transmission and reception of data from port 1 and 2.
9
Page 12
Rev 2.0 : X11CA-IM MASTER MODULE
6 SETTING THE ALARM MODULE ADDRESSES
The X11-CA-IM (Master Module) Scans all the Alarm boards in the chassis continuously every 25ms/board and the number of Alarm boards to be scanned has to be set by switch SW2 or SW4 depending on the revision of the PCB used and it is shown below:
Alarm
Board#
10 ON OFF OFF ON OFF OFF OFF OFF 11 OFF ON OFF ON OFF OFF OFF OFF 12 ON ON OFF ON OFF OFF OFF OFF 13 OFF OFF ON ON OFF OFF OFF OFF 14 ON OFF ON ON OFF OFF OFF OFF 15 OFF ON ON ON OFF OFF OFF OFF 16 ON ON ON ON OFF OFF OFF OFF 17 OFF OFF OFF OFF ON OFF OFF OFF 18 ON OFF OFF OFF ON OFF OFF OFF 19 OFF ON OFF OFF ON OFF OFF OFF 20 ON ON OFF OFF ON OFF OFF OFF 21 OFF OFF ON OFF ON OFF OFF OFF 22 ON OFF ON OFF ON OFF OFF OFF 23 OFF ON ON OFF ON OFF OFF OFF 24 ON ON ON OFF ON OFF OFF OFF 25 OFF OFF OFF ON ON OFF OFF OFF 26 ON OFF OFF ON ON OFF OFF OFF 27 OFF ON OFF ON ON OFF OFF OFF 28 ON ON OFF ON ON OFF OFF OFF 29 OFF OFF ON ON ON OFF OFF OFF 30 ON OFF ON ON ON OFF OFF OFF 31 OFF ON ON ON ON OFF OFF OFF 32 ON ON ON ON ON OFF OFF OFF 33 OFF OFF OFF OFF OFF ON OFF OFF 34 ON OFF OFF OFF OFF ON OFF OFF
SW2-1 SW2-2 SW2-3 SW2-4 SW2-5 SW2-6 SW2-7 SW2-8
1 OFF OFF OFF OFF OFF OFF OFF OFF 2 ON OFF OFF OFF OFF OFF OFF OFF 3 OFF ON OFF OFF OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF OFF OFF 6 ON OFF ON OFF OFF OFF OFF OFF 7 OFF ON ON OFF OFF OFF OFF OFF 8 ON ON ON OFF OFF OFF OFF OFF 9 OFF OFF OFF ON OFF OFF OFF OFF
10
Page 13
Rev 2.0 : X11CA-IM MASTER MODULE
Alarm
Board#
35 OFF ON OFF OFF OFF ON OFF OFF 36 ON ON OFF OFF OFF ON OFF OFF 37 OFF OFF ON OFF OFF ON OFF OFF 38 ON OFF ON OFF OFF ON OFF OFF 39 OFF ON ON OFF OFF ON OFF OFF 40 ON ON ON OFF OFF ON OFF OFF 41 OFF OFF OFF ON OFF ON OFF OFF 42 ON OFF OFF ON OFF ON OFF OFF 43 OFF ON OFF ON OFF ON OFF OFF 44 ON ON OFF ON OFF ON OFF OFF 45 OFF OFF ON ON OFF ON OFF OFF 46 ON OFF ON ON OFF ON OFF OFF 47 OFF ON ON ON OFF ON OFF OFF 48 ON ON ON ON OFF ON OFF OFF 49 OFF OFF OFF OFF ON ON OFF OFF 50 ON OFF OFF OFF ON ON OFF OFF 51 OFF ON OFF OFF ON ON OFF OFF 52 ON ON OFF OFF ON ON OFF OFF 53 OFF OFF ON OFF ON ON OFF OFF 54 ON OFF ON OFF ON ON OFF OFF 55 OFF ON ON OFF ON ON OFF OFF 56 ON ON ON OFF ON ON OFF OFF 57 OFF OFF OFF ON ON ON OFF OFF 58 ON OFF OFF ON ON ON OFF OFF 59 OFF ON OFF ON ON ON OFF OFF 60 ON ON OFF ON ON ON OFF OFF 61 OFF OFF ON ON ON ON OFF OFF 62 ON OFF ON ON ON ON OFF OFF 63 OFF ON ON ON ON ON OFF OFF 64 ON ON ON ON ON ON OFF OFF
65 OFF OFF OFF OFF OFF OFF ON OFF 66 ON OFF OFF OFF OFF OFF ON OFF 67 OFF ON OFF OFF OFF OFF ON OFF 68 ON ON OFF OFF OFF OFF ON OFF 69 OFF OFF ON OFF OFF OFF ON OFF 70 ON OFF ON OFF OFF OFF ON OFF 71 OFF ON ON OFF OFF OFF ON OFF 72 ON ON ON OFF OFF OFF ON OFF 73 OFF OFF OFF ON OFF OFF ON OFF 74 ON OFF OFF ON OFF OFF ON OFF 75 OFF ON OFF ON OFF OFF ON OFF 76 ON ON OFF ON OFF OFF ON OFF
SW2-1 SW2-2 SW2-3 SW2-4 SW2-5 SW2-6 SW2-7 SW2-8
11
Page 14
Rev 2.0 : X11CA-IM MASTER MODULE
Alarm
Board#
77 OFF OFF ON ON OFF OFF ON OFF 78 ON OFF ON ON OFF OFF ON OFF 79 OFF ON ON ON OFF OFF ON OFF 80 ON ON ON ON OFF OFF ON OFF 81 OFF OFF OFF OFF ON OFF ON OFF 82 ON OFF OFF OFF ON OFF ON OFF 83 OFF ON OFF OFF ON OFF ON OFF 84 ON ON OFF OFF ON OFF ON OFF 85 OFF OFF ON OFF ON OFF ON OFF 86 ON OFF ON OFF ON OFF ON OFF 87 OFF ON ON OFF ON OFF ON OFF 88 ON ON ON OFF ON OFF ON OFF 89 OFF OFF OFF ON ON OFF ON OFF 90 ON OFF OFF ON ON OFF ON OFF 91 OFF ON OFF ON ON OFF ON OFF 92 ON ON OFF ON ON OFF ON OFF 93 OFF OFF ON ON ON OFF ON OFF 94 ON OFF ON ON ON OFF ON OFF 95 OFF ON ON ON ON OFF ON OFF 96 ON ON ON ON ON OFF ON OFF
97 OFF OFF OFF OFF OFF ON ON OFF 98 ON OFF OFF OFF OFF ON ON OFF
99 OFF ON OFF OFF OFF ON ON OFF 100 ON ON OFF OFF OFF ON ON OFF 101 OFF OFF ON OFF OFF ON ON OFF 102 ON OFF ON OFF OFF ON ON OFF 103 OFF ON ON OFF OFF ON ON OFF 104 ON ON ON OFF OFF ON ON OFF 105 OFF OFF OFF ON OFF ON ON OFF 106 ON OFF OFF ON OFF ON ON OFF 107 OFF ON OFF ON OFF ON ON OFF 108 ON ON OFF ON OFF ON ON OFF 109 OFF OFF ON ON OFF ON ON OFF 110 ON OFF ON ON OFF ON ON OFF 111 OFF ON ON ON OFF ON ON OFF 112 ON ON ON ON OFF ON ON OFF 113 OFF OFF OFF OFF ON ON ON OFF 114 ON OFF OFF OFF ON ON ON OFF 115 OFF ON OFF OFF ON ON ON OFF 116 ON ON OFF OFF ON ON ON OFF 117 OFF OFF ON OFF ON ON ON OFF 118 ON OFF ON OFF ON ON ON OFF
SW2-1 SW2-2 SW2-3 SW2-4 SW2-5 SW2-6 SW2-7 SW2-8
12
Page 15
Rev 2.0 : X11CA-IM MASTER MODULE
Alarm
Board#
119 OFF ON ON OFF ON ON ON OFF 120 ON ON ON OFF ON ON ON OFF 121 OFF OFF OFF ON ON ON ON OFF 122 ON OFF OFF ON ON ON ON OFF 123 OFF ON OFF ON ON ON ON OFF 124 ON ON OFF ON ON ON ON OFF 125 OFF OFF ON ON ON ON ON OFF 126 ON OFF ON ON ON ON ON OFF 127 OFF ON ON ON ON ON ON OFF 128 ON ON ON ON ON ON ON OFF 129 OFF OFF OFF OFF OFF OFF OFF ON
130 ON OFF OFF OFF OFF OFF OFF ON 131 OFF ON OFF OFF OFF OFF OFF ON 132 ON ON OFF OFF OFF OFF OFF ON 133 OFF OFF ON OFF OFF OFF OFF ON 134 ON OFF ON OFF OFF OFF OFF ON 135 OFF ON ON OFF OFF OFF OFF ON 136 ON ON ON OFF OFF OFF OFF ON 137 OFF OFF OFF ON OFF OFF OFF ON 138 ON OFF OFF ON OFF OFF OFF ON 139 OFF ON OFF ON OFF OFF OFF ON 140 ON ON OFF ON OFF OFF OFF ON 141 OFF OFF ON ON OFF OFF OFF ON 142 ON OFF ON ON OFF OFF OFF ON 143 OFF ON ON ON OFF OFF OFF ON 144 ON ON ON ON OFF OFF OFF ON 145 OFF OFF OFF OFF ON OFF OFF ON 146 ON OFF OFF OFF ON OFF OFF ON 147 OFF ON OFF OFF ON OFF OFF ON 148 ON ON OFF OFF ON OFF OFF ON 149 OFF OFF ON OFF ON OFF OFF ON 150 ON OFF ON OFF ON OFF OFF ON 151 OFF ON ON OFF ON OFF OFF ON 152 ON ON ON OFF ON OFF OFF ON 153 OFF OFF OFF ON ON OFF OFF ON 154 ON OFF OFF ON ON OFF OFF ON 155 OFF ON OFF ON ON OFF OFF ON 156 ON ON OFF ON ON OFF OFF ON 157 OFF OFF ON ON ON OFF OFF ON 158 ON OFF ON ON ON OFF OFF ON 159 OFF ON ON ON ON OFF OFF ON
SW2-1 SW2-2 SW2-3 SW2-4 SW2-5 SW2-6 SW2-7 SW2-8
160 ON ON ON ON ON OFF OFF ON
13
Page 16
Rev 2.0 : X11CA-IM MASTER MODULE
Alarm
Board#
161 OFF OFF OFF OFF OFF ON OFF ON 162 ON OFF OFF OFF OFF ON OFF ON 163 OFF ON OFF OFF OFF ON OFF ON 164 ON ON OFF OFF OFF ON OFF ON 165 OFF OFF ON OFF OFF ON OFF ON 166 ON OFF ON OFF OFF ON OFF ON 167 OFF ON ON OFF OFF ON OFF ON 168 ON ON ON OFF OFF ON OFF ON 169 OFF OFF OFF ON OFF ON OFF ON 170 ON OFF OFF ON OFF ON OFF ON 171 OFF ON OFF ON OFF ON OFF ON 172 ON ON OFF ON OFF ON OFF ON 173 OFF OFF ON ON OFF ON OFF ON 174 ON OFF ON ON OFF ON OFF ON 175 OFF ON ON ON OFF ON OFF ON 176 ON ON ON ON OFF ON OFF ON 177 OFF OFF OFF OFF ON ON OFF ON 178 ON OFF OFF OFF ON ON OFF ON 179 OFF ON OFF OFF ON ON OFF ON 180 ON ON OFF OFF ON ON OFF ON 181 OFF OFF ON OFF ON ON OFF ON 182 ON OFF ON OFF ON ON OFF ON 183 OFF ON ON OFF ON ON OFF ON 184 ON ON ON OFF ON ON OFF ON 185 OFF OFF OFF ON ON ON OFF ON 186 ON OFF OFF ON ON ON OFF ON 187 OFF ON OFF ON ON ON OFF ON 188 ON ON OFF ON ON ON OFF ON 189 OFF OFF ON ON ON ON OFF ON 190 ON OFF ON ON ON ON OFF ON 191 OFF ON ON ON ON ON OFF ON 192 ON ON ON ON ON ON OFF ON
193 OFF OFF OFF OFF OFF OFF ON ON 194 ON OFF OFF OFF OFF OFF ON ON 195 OFF ON OFF OFF OFF OFF ON ON 196 ON ON OFF OFF OFF OFF ON ON 197 OFF OFF ON OFF OFF OFF ON ON 198 ON OFF ON OFF OFF OFF ON ON 199 OFF ON ON OFF OFF OFF ON ON 200 ON ON ON OFF OFF OFF ON ON
SW2-1 SW2-2 SW2-3 SW2-4 SW2-5 SW2-6 SW2-7 SW2-8
Table 6-1 Setting Alarm Module Addresses
14
Page 17
Rev 2.0 : X11CA-IM MASTER MODULE
7 PRGM/RUN SWITCH
Use the PRGM/RUN switch on the X11CA-IM to set the mode to either program mode or run mode.
7.1 Program Mode
In the program mode, you can configure or change the configuration of the alarm modules with the Configuration software running on the host computer.
To set X11CA-IM to program mode, set the switch to PRGM and make sure that the cable is connected from the Modbus communication port (P2) on the X11CA­IM to the serial port of the host computer. Verify that the RUN and ERROR LEDs flash simultaneously.
Ref er to X11CA Configuration Software User’s Manual (Doc # :X11CA-3001- IOM) for detail.
7.2 Run Mode
In the run mode, the X11CA-IM scans all the activities of the alarm modules and activates the relay outputs and its push button functions.
7.2.1 Relay Outputs
There are five Relays on the X11-CA-IM as follows:
? RUN Relay indicates the power on condition and is normally energized ? REFLASH Relay is not used in this revision of the firmware. ? CTA Relay is a Common Trouble Alarm and will be energized if one or more
than one input in any Alarm card is on.
? Relay A1 is HORN1 relay and will be energized according to the sequence
programmed in the ALARM card.
? Relay A2 is HORN2 relay and will be energized according to the sequence
programmed in the ALARM card.
7.2.2 Functions of the Push Buttons
The following is the summary of the push button functions.
15
Page 18
Rev 2.0 : X11CA-IM MASTER MODULE
Button
Name
TEST Test SIL Silence Stops the sound of the audio devices.
ACK Acknowledge Acknowledges the alarms. RST Reset Resets inputs according to the sequence type. FRST First Out Reset Resets the first out alarm in the group . GF1 General
GF2 General
Full Name Description
Tests properties of alarm modules.
Function 1
Function 2
Inhibits the GF1 inhibit signals while the button is being pressed.
Inhibits the GF2 inhibit signals while the button is being pressed.
Table 7-1 Push Button Functions
16
Page 19
Rev 2.0 : X11CA-IM MASTER MODULE
8 APPENDIX A: LIST OF TABLES
TABLE 2-1 DESCRIPTIONS OF MODBUS COMMUNICATION DATA FORMAT..........................3
TABLE 4-1 SETTING MODBUS SLAVE ADDRESS ..................................................................5
TABLE 4-2 MODBUS FUNCTION 3 EXAMPLE-QUERY...........................................................6
TABLE 4-3 MODBUS FUNCTION 3 EXAMPLE-RESPONSE......................................................6
TABLE 4-4 MODBUS FUNCTION 5 EXAMPLE-QUERY...........................................................7
TABLE 4-5 MODBUS FUNCTION 5 EXAMPLE-RESPONSE......................................................8
TABLE 6-1 SETTING ALARM MODULE ADDRESSES ...........................................................14
TABLE 7-1 PUSH BUTTON FUNCTIONS...............................................................................16
17
Page 20
Rev 2.0 : X11CA-IM MASTER MODULE
9 APPENDIX B: LIST OF FIGURES
FIGURE 1-1 X11CA-IM.......................................................................................................1
FIGURE 3-1 RS232 CABLE FROM THE LAPTOP TO X11CA-IM CONNECTION.......................4
FIGURE 3-2 RS232 CABLE FROM THE LAPTOP TO X11CA-IM CONNECTION......................4
18
Loading...