Rockwell Automation T3404 User Manual

Page 1
ICS Regent
®
PD-6013
AC Digital Input Module
110 VAC
(T3404)
Issue 1,
The AC digital input module provides input sensing for 16 field input switches. One type of module is available for interfacing to inputs powered from 110 VAC field power supplies. The module's triplicated I/O Safetybus interface ensures that no failure in the module can affect the operation of the Regent system or other I/O modules in the system. Extensive fault detection and annunciation of critical redundant circuits help prevent the controllers from receiving erroneous data from a faulty input module.
March, 06
Features
·
Sixteen input circuits, configured as two isolated groups of eight circuits each.
·
Fault tole redundant modules of the same type.
·
Hot-replaceable.
·
Automatic self-testing of triplicated I/O Safetybus circuits and many simplex logic circuits.
·
Individual front panel indicators on each module show active and fault status and logic-side input on/off status.
·
2500 volt minimum electrical isolation between field and logic circu
·
TÜV certified, Risk Class 5.
Three AC digital input modules can be connected in parallel to obtain fault tolerant input sensing. In this triple module configuration, a failed module can be removed and replaced without interrupting the input signals.
rant operation when connected in parallel with
its.
1
Page 2
AC Digital Input Module
(T3404)

Module Operation

A block diagram of an AC digital input module is shown in Figure 1.
Optical isolation between field wiring and the module’s logic circuitry provides field-to-logic isolation — module’s logic circuits from field signal over-voltages, transients, and other electrical disturbances. It also provides a safety barrier between the primary field voltages and user accessible circuits.
pr
otecting the
2
Figure 1. Block Diagram of AC Digital Input Module.
When the field switch is closed, the input to the module is on. When the field switch opens, the input to the module turns off.
Data from the logic side of the optical isolators are bused to the I/O bus interface logic.
The processor modules send triplicated read data requests to the input module over the I/O Safetybus. The processors’ addressing data and data read requests are voted by the
Industrial Control Services
Page 3
(T3404)
module (preventing I/O Safetybus failures upstream from the module from affecting its ability to be read). The voted result is then passed to the I/O bus interface logic.
After receiving the voted data read request, the I/O bus interface logic sends its input data to the module’s three bus drivers. Each o powered and controlled by the I/O transceiver modules— preventing failures in a single driver from propagating to the other two busses.
The bus drivers transmit the data across the backplane I/O Safetybus to the I/O transceivers which, in turn, transmit the data to the processors.
f the three bus drivers is independently
AC Digital Input Module

Testing and Diagnostics

Each module’s voter circuits are periodically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine module’s voter is able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module.
Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is rem type, the processor modules will indicate I/O module errors.
Loopback logic tests periodically write data to the module and then read it back to determine whether the module’s I/O bus interface logic is functioning correctly.
oved, or is replaced with a module of a different

Front Panel Indicators

whether the
PD-6013
Mar-06
Figure 2 shows the physical features of the AC digital input module. The front panel of each module contains active and fault status indicators and field signal status indicators each circuit.
3
for
Page 4
AC Digital Input Module
(T3404)
4
Figure 2. AC Digital Input Module.
Industrial Control Services
Page 5
(T3404)
AC Digital Input Module

Application

Active and Fault Status Indicators

These green and red LEDs indicate the overall health of the module. During normal operation the green ACTIVE indicator flashes at the controller's scan rate. If a module fault is detected the red FAULT indicator turns on and the green indicator turns off.

Field Status Indicators

Input status indicators are located on the logic-side (after the signal conditioning and isolation). The field status indicators are lit when current is flowing through the input.

Simplex Configuration

Digital input modules provide a suitable interface to non critical input signals. Although many of the circuits in the digital input modules are automatically tested and annunciated, some logic circuits and all of the field-side sensing circuits are simplex and non-tested. This simplex input configuration is illustrated in Figure 3.
-
PD-6013
Mar-06
Figure 3. Simplex Digital Input Configuration.

Fault Tolerant Connection

For critical inputs, redundant input modules are used in a 2oo3 or 1oo2 fault tolerant configuration. In these configurations the redundant input modules are connected to single or multiple sensors. If redundant sensors are installed
5
Page 6
AC Digital Input Module
in the field, the redundant modules are connected so that each sensor connects to one of the redundant modules. These configurations are illustrated in Figure 4, showing triple redundant input modules. Each AC digital input module is hot replaceable. In triple redundant input configurations, if a fault occurs on one module, it can be removed and replaced while the system continues to sense the inputs from the remaining two input modules.
(T3404)
Figure 4. Fault Tolerant Digital Input Configurations.

Field Wiring

6
Field wiring terminal blocks on the I/O chassis are used to c
onnect the field input signals and the common power return signals to the module. The terminal blocks are located directly above and below the slot where the module is
Industrial Control Services
Page 7
(T3404)
AC Digital Input Module
installed. Each terminal block consists of ten #6 wire clamp screw terminals, with each terminal capable of holding two 12 AWG wires.
The module has a separate common power return terminal for each group of inputs (group 1: channels 1-8, group 2: channels 9-16). These two groups are electrically isolated from each other (2500 volts minimum connection of input signals to the input wiring terminals.
). Figure 5 shows the proper
When redundant field sensors are installed, each input module is wired as shown in Figure 5. In a fault tolerant configuration with single field sensors, the input signals are connected in parallel across all three input modules as shown in Figure 6.
PD-6013
Mar-06
7
Page 8
AC Digital Input Module
(T3404)
8
Figure 5. Module Wiring, Sin
Input Module.
gle Sensors to a Single Digital
Industrial Control Services
Page 9
(T3404)
AC Digital Input Module
PD-6013
Mar-06
Figure 6. Module Wiring, Single Sensors to Triplicated
Digital Input Modules.
9
Page 10
AC Digital Input Module
(T3404)

Keying

The I/O chassis can be physically keyed to prevent accidental damage caused by inserting a module into a slot wired for a different module type. Figure 7 illustrates how the slot keys are installed on the I/O chassis slot field wiring connectors. The slot key positions for the AC digital input module are listed in Table 1.
10
Figure 7. Installing Slot Keys.
Industrial Control Services
Page 11
(T3404)
Module
Upper
Connector
Lower
Connector
T3404
17 15
AC Digital Input Module
Table 1. Slot Key Positions.

Configuration

Each input module is configured using the
W
INTERPRET
I/O Configuration Editor. In the editor, you will perform the three steps described below to configure the input module.
1) Set the Module Type:
Position the cursor on the module slot you wish to define. Choose Set Module Type from the Edit M the appropriate digital input module from the list.
2) Edit the Module Definition:
enu and select
Choose Edit Module Definition from the Edit Menu. A dialog box will open where you can define the input point definitions.
PD-6013
Mar-06
Figure 8. Digital Input Module Definition.
3) Edit each point:
Choose Edit from the Module Definition dialog box to define a name and description for each I/O point. In the
11
Page 12
AC Digital Input Module
Digital Input Point dialog, enter a tag name (up to 12 characters) and a description (up to 40 cha
(T3404)
racters).
Figure 9. Defining a Digital Input Point.
The tag names are used in the application program to represent the input state. In addition, a module tag name can be entered to represent the combined state of all 16 inputs. This module tag name represents the 16 inputs as a signed, 16-bit integer. In this format, input point one is the least significant bit (LSB) and input point 16 is the most significant bit (MSB).

Programming

Inputs are referenced in the application program through the tag names defined in the I/O Configuration Editor. When current flows through the input (field switch closed) the input is said to be on, or have a value of one. In ladder logic, the on state would produce power flow in a normally open (N.O.) contact.
To program fault tolerant configurations using triplicated digital input modules, a voter element can be used as shown in Figure 10.
12
Figure 10. Programming Fault Tolerant Digital Inputs.
Industrial Control Services
Page 13
(T3404)
In this illustration, VOTE_A_NAME, VOTE_B_NAME, and VOTE_C_NAME represent the three digital inputs to be two out-of-three voted. ERROR_A_NAME, ERROR_B_NAME and ERROR_C_NAME are the error bits for the digital inputs. RESULT_NAME is the result of the voter instruction. The field Msec is the time, in milliseconds, an input can be incorrect before signaling an error. RESET_NAME is the reset bit used to reset the latched error bits.
The voter instruction can be used to vote digital input points or ent modules, the tag names VOTE_A_NAME, VOTE_B_NAME, and VOTE_C_NAME would be the names of the digital input modules and RESULT_NAME would be a shared variable register. After voting the modules, a block move instruction should be used to move the contents of the register RESULT_NAME into individual shared variable control relays. Refer to the information about the block move instruction and shared variable definitions.
ire digital input modules. When voting digital input
W
INTERPRET
AC Digital Input Module
Help files for more
-
Maint
enance
No periodic maintenance or calibration is required for the AC digital input module. There are no user replaceable parts inside the module. In safety critical input applications, the inputs should be dynamically transitioned at a period not greater than six months.

Safety Considerations

The AC voltage digital input module is TÜV certified as non
interfering and when properly configured is also certified for Risk Class 5 safety critical inputs. Safety critical configura
In safety critical input applications using a single sensor, it is important that the sensor failure modes be predictable and well understood, so there is little probability of a failed sensor not responding to a critical process condition. In such a configuration, it is important that the sensor be tested
tions include 2oo3 and 1oo2 voting methods.
-
PD-6013
Mar-06
13
Page 14
AC Digital Input Module
regularly, either by dynamic process conditions that are verified in the Regent, or by manual intervention testing.
(T3404)
Redundant sensors can be used with redundan
t input modules to eliminate any single points of failure and extend fault tolerance to include the sensors.
In all safety critical configurations and applications, the AC voltage digital input module can be used for de-energized to trip inputs, a period not greater than six months.
only
if the inputs are dynamically transitioned at
For additional safety considerations, please refer to the Safety Considerations section of the Regent User’s Guide.
14
Industrial Control Services
Page 15
(T3404)
Safetybus Power
1.15 load units
Number of In
puts
16 circuits divided into two groups of eight
Voltage Range
90 to 130 VAC
Frequency Range
47 to 63 Hz
Turn-On Voltage
89 VAC, minimum
Turn-Off Voltage
30 VAC, maximum
Input Current
3.9 mA, typical
Turn-On Delay
minimum maximum
3.5 msec 20 msec
Turn-Off Delay
minimum maximum
3.5 msec 15 msec
Over Voltage Protection
continuous: burst:
160 VAC 260 VAC, for 5 sec
Heat Dissipation
14 Watts, 48 BTUs/hour
Fusing
None, fuse external if required
Isolation
2500 volts minimum (field wiring to c
ontrol logic) 2500 volts minimum (input group 1-8 to input group 9-16)
Operating Temperature
0°
to 60° C
(32° to 140° F)
Storage Temperature
-40°
to 85° C
(-40°
to 185° F)
Operating Humidity
0 to 95% relative humidity, non-condensing
Vibration
10 to 55 Hz:
±0.15mm
AC Digital Input Module

Specifications

PD-6013
Mar-06
15
Page 16
Shock
Operating:
15 g, ½ sine wave, 11 msec
E
lectromagnetic
Interference
IEC 801 Part 2 - Electrostatic Discharges
IEC 801 Part 3 - Radiated Electromagnetic Fields
ANSI/IEEE C37.90 - Surge Withstand Capability
Level 3: Contact discharge of 6 kV Level 3: 10 V/M, 27 MHz ­500 MHz
2.5 kV damped 1 MHz sine wave
Safety
Certified to DIN V VDE 0801 for Risk Class 5. Also designed to meet UL 508 and CSA 22.2, No. 142-M1981
Dime
nsions
Height: Width: Depth:
12.6" (320 mm)
1.27" (32 mm)
10.12" (257 mm)
Weight
3.0 lbs (1.4 kg)
AC Digital Input Module
(T3404)
16
Industrial Control Services
Loading...