Rockwell Automation System Design User Manual

System Design for Control of Electrical Noise
Reference Manual

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
does not assume responsibility
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss.
!
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
IMPORTANT
Allen-Bradley is a registered trademark of Rockwell Automation.
Identifies information that is critical for successful application and understanding of the product.

Table of Contents

Preface
Electrical Noise Control Overview
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . P-1
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Contents of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . P-3
Conventions Used in this Manual . . . . . . . . . . . . . . . . . . . . P-3
Chapter 1
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
What is Electrical Noise?. . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Understanding the Need for Electrical Noise Control . . . . . . 1-1
CE Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Best Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Noise Control Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Noise Sources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Noise Victims . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Coupling Mechanisms . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Conducted Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Capacitance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Mutual Inductance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Electromagnetic Radiation. . . . . . . . . . . . . . . . . . . . . . . 1-6
Solutions for Reducing Noise . . . . . . . . . . . . . . . . . . . . . . . 1-6
Implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Measuring Effectiveness . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
High Frequency (HF) Bonding
Chapter 2
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Understanding the Source of Electrical Noise . . . . . . . . . . . 2-1
Noise Example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Noise Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
The Ground Plane Principle . . . . . . . . . . . . . . . . . . . . . 2-3
Extending the Ground Plane Principle. . . . . . . . . . . . . . 2-5
Grounding a PCB to the Drive Chassis . . . . . . . . . . . . . 2-5
Noise Solutions Using the Ground Plane Principle . . . . . . . 2-6
Grounding to the Component Mounting Panel. . . . . . . . 2-6
Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Adjacent Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Grid and Raised Floor. . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Mezzanine Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Machine Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
New Buildings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Existing Buildings. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Grounding (Safety Earth) . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
iPublication GMC-RM001A-EN-P — July 2001
ii Table of Contents
Segregating Sources and Victims
Shielding Wires, Cables, and Components
Chapter 3
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Understanding the Segregation Concept . . . . . . . . . . . . . . . 3-1
Noise Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Ensuring CE Compliance at Build Time . . . . . . . . . . . . . 3-2
Zone Classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Component Categories . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Routing Wires and Cables Within a Panel . . . . . . . . . . . . . . 3-4
Wire and Cable Categories . . . . . . . . . . . . . . . . . . . . . . 3-6
Routing System Wires and Cables Between Panels. . . . . . . . 3-8
Chapter 4
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Understanding the Shielding Concept . . . . . . . . . . . . . . . . . 4-1
Ferrite Sleeves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Ferrite Sleeve Limitations. . . . . . . . . . . . . . . . . . . . . . . . 4-4
Mixing Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Filtering Noise
Contact Suppression
Chapter 5
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Understanding the Filtering Concept . . . . . . . . . . . . . . . . . . 5-1
Commercial AC Line Filters for Low Voltage Circuits . . . 5-1
General Purpose 0-24V ac/dc Filters . . . . . . . . . . . . . . . 5-2
Filter Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Performance Test Set-up . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Test Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Ultrasonic Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Xenon Flashing Beacons (strobe lights). . . . . . . . . . . . . . . . 5-5
AC Line Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Earth Leakage/Ground Fault . . . . . . . . . . . . . . . . . . . . . 5-6
Chapter 6
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Understanding Contact Suppression for AC Circuits . . . . . . . 6-1
Methods of AC Contact Suppression . . . . . . . . . . . . . . . 6-2
Understanding Contact Suppression for 24V dc Circuits . . . . 6-3
Methods of DC Contact Suppression . . . . . . . . . . . . . . . 6-3
Contact Suppression Effects . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Power Distribution
Publication GMC-RM001A-EN-P — July 2001
Chapter 7
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Understanding Noise in Power Wiring . . . . . . . . . . . . . . . . 7-1
Three-Phase Power Supplies. . . . . . . . . . . . . . . . . . . . . . . . 7-1
Line Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Single Phase Power Supplies . . . . . . . . . . . . . . . . . . . . . . . 7-4
Motor Wiring
High Speed Registration Inputs
Table of Contents iii
24V dc Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
24V dc Distribution. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
24V dc PSU Zoning Methods. . . . . . . . . . . . . . . . . . . . . 7-5
Linear PSU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Special Applications for 24V dc PSUs . . . . . . . . . . . . . 7-11
Chapter 8
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Understanding Noise in Motor Power Wiring . . . . . . . . . . . 8-1
Shielding Motor Power Cables . . . . . . . . . . . . . . . . . . . . . . 8-2
Grounding Motor Power Cable Shields . . . . . . . . . . . . . . . . 8-2
Applying Ferrite Sleeves. . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Splicing Motor Power Cables . . . . . . . . . . . . . . . . . . . . . . . 8-3
Handling Excess Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Installing Long Motor Cables . . . . . . . . . . . . . . . . . . . . . . . 8-4
Chapter 9
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Understanding Registration Inputs . . . . . . . . . . . . . . . . . . . 9-1
Noise Reduction Methods. . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Shared Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Dedicated Power Supply. . . . . . . . . . . . . . . . . . . . . . . . 9-4
Detection Device Mounting. . . . . . . . . . . . . . . . . . . . . . 9-4
Proximity Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
Signal Noise Filter Options. . . . . . . . . . . . . . . . . . . . . . . . . 9-5
Single Voltage Input (24V or 5V). . . . . . . . . . . . . . . . . . 9-6
Dual Voltage Inputs (24V or 5V) . . . . . . . . . . . . . . . . . . 9-7
Registration Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-8
Error Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-9
Software Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-9
Encoders
Measuring Noise Reduction Effectiveness
Chapter 10
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
Understanding Encoders . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
Noise Reduction Methods. . . . . . . . . . . . . . . . . . . . . . . . . 10-1
Driver Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Power Supply Wiring Options . . . . . . . . . . . . . . . . . . . . . 10-3
Chapter 11
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
Understanding Noise Measurement. . . . . . . . . . . . . . . . . . 11-1
Publication GMC-RM001A-EN-P — July 2001
iv Table of Contents
Methods for Measuring Noise . . . . . . . . . . . . . . . . . . . . . . 11-1
Measuring Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
Oscilloscope Specifications . . . . . . . . . . . . . . . . . . . . . 11-2
Oscilloscope Settings for Measuring Noise Peaks . . . . . 11-2
E-Field Sniffing Method. . . . . . . . . . . . . . . . . . . . . . . . 11-3
H-Field Sniffing Method . . . . . . . . . . . . . . . . . . . . . . . 11-4
Direct Voltage Measurement Method . . . . . . . . . . . . . . 11-4
Grounding Your Probe (reference ground) . . . . . . . . . 11-6
Ground Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-7
Differential Measurements . . . . . . . . . . . . . . . . . . . . . . 11-7
Scope Probe Lead Extension . . . . . . . . . . . . . . . . . . . . 11-9
Checking Your Method for Effectiveness . . . . . . . . . . . 11-9
Identifying the Noise Source . . . . . . . . . . . . . . . . . . . 11-10
Intermittent Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-10
General Guidelines for Measuring Noise . . . . . . . . . . . . . 11-10
What are Acceptable Noise Levels? . . . . . . . . . . . . . . 11-10
Field Strength Meters . . . . . . . . . . . . . . . . . . . . . . . . 11-11
Monitoring for Noise. . . . . . . . . . . . . . . . . . . . . . . . . 11-11
Noise Control Supplement
Appendix A
Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Grounding Cable Shields . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Pigtails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Clamping at the Circular Section . . . . . . . . . . . . . . . . . . A-2
Wire Segregation Test Results . . . . . . . . . . . . . . . . . . . . . . . A-5
Test Set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Switch-Mode DC Power Supplies . . . . . . . . . . . . . . . . . . . . A-8
Background Information . . . . . . . . . . . . . . . . . . . . . . . . A-8
Grounding the Common . . . . . . . . . . . . . . . . . . . . . . . . A-9
DC Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-11
Positioning the PSU within the Panel . . . . . . . . . . . . . . A-11
AC Line Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Using Separate DC Power Supplies . . . . . . . . . . . . . . . A-12
Using a Dynamic Braking Contactor . . . . . . . . . . . . . . . . . A-13
Reducing Dynamic Braking Circuit Noise. . . . . . . . . . . A-14
Bonding Surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-15
Wire Forms an Antenna . . . . . . . . . . . . . . . . . . . . . . . A-15
Inductance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-15
Noise Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-16
EMC Product Suppliers
Publication GMC-RM001A-EN-P — July 2001
Appendix B
EMC Product Suppliers. . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

Preface

Read this preface to familiarize yourself with the rest of the manual. The preface covers the following topics:
Who should use this manual
The purpose of this manual
Contents of this manual
Related documentation
Conventions used in this manual
Allen-Bradley support

Who Should Use this Manual

Purpose of this Manual

Use this manual if you are responsible for the circuit design and layout of wiring panels or the installation and mounting of Allen-Bradley products. Specifically, the following disciplines should be included:
Circuit designers
Panel layout designers
Panel builders and electricians
Electrical technicians
In addition, you should have an understanding of:
Drive control and basic electronics
Appropriate electrical codes
This manual outlines the practices which minimize the possibility of noise-related failures and that comply with noise regulations. It gives you an overview of how electrical noise is generated (sources), how the noise interferes with routine operation of drive equipment (victims), and examples of how to effectively control noise.
This manual applies in general to Allen-Bradley drives products. For information on specific Allen-Bradley motion products refer to Noise Control Supplement - Motion Products Reference Manual (publication GMC-RM002x-EN-P).
Publication GMC-RM001A-EN-P — July 2001
P-2 Preface

Contents of this Manual

The contents of this manual are described in the table below.
Chapter Title Contents
Preface Describes the purpose, background, and
scope of this manual. Also specifies the audience for whom this manual is intended.
1 Electrical Noise Control
Overview
2 High Frequency (HF) Bonding Describes the ground plane principle and
3 Segregating Sources and
Victims
4 Shielding Wires, Cables, and
Components
5 Filtering Noise Describes how low-pass filters and ferrite
Provides a brief understanding of the need for electrical noise control, how noise affects system performance, noise coupling methods, and solutions.
provides techniques for bonding devices, panels, machines, floors, doors, and buildings.
Describes how establishing zones within your system for noise sensitive or noise generating components can reduce electrical noise coupling.
Describes how using shielded cable or steel shields can reduce electrical noise.
sleeves can reduce electrical noise.
6 Contact Suppression Describes how contact suppressors for
relays and various other switches can reduce electrical noise.
7 Power Distribution Describes bonding, segregating, shielding,
and filtering techniques for use when routing AC and DC power.
8 Motor Wiring Describes shielding, grounding, and
splicing techniques for use with motor wiring.
9 High Speed Registration
Inputs
10 Encoders Describes bonding, segregating, shielding,
11 Measuring Noise Reduction
Effectiveness
Appendix A Noise Control Supplement Provides background information on
Appendix B EMC Product Suppliers Provides a list of EMC product suppliers,
Describes how wiring sensitive to electrical noise benefits from proper noise reduction strategies.
and filtering techniques for use with encoders.
Describes the equipment, methods, and various guidelines for measuring noise levels and noise reduction effectiveness.
specific topics related to electrical noise control.
the products they offer, and internet website.
Publication GMC-RM001A-EN-P — July 2001
Preface P-3

Related Documentation

The following documents contain additional information related to electrical noise control. To obtain a copy, contact your local Allen-Bradley office or distributor.
For: Read This Document: Document Number:
Specific advice on motion products Noise Control Supplement - Motion Products GMC-RM002x-EN-P Advice specific to large systems Industrial Automation Wiring and Grounding Guidelines for Noise
Immunity
Advice specific to large systems Installing, Operating and Maintaining Engineered Drive Systems
(Reliance Electric)
Safety advice Safety Guidelines for the Application, Installation, and
Maintenance of Solid-State Control
IEEE industry standards for electrical equipment installation
A text book on noise reduction techniques Noise Reduction Techniques in Electronic Systems
A text book on grounding techniques for the control of EMI
IEEE Guide for the Installation of Electrical Equipment to Minimize Electrical Noise Inputs to Controllers from External Sources
Henry W. Ott Published by Wiley-Interscience
Grounding for the Control of EMI
Hugh W. Denny Published by Don White Consultants
1770-4.1
D2-3115-2
SGI-1.1
IEEE 518
N/A
N/A
1
A text book on solving interference problems Solving Interference Problems in Electronics
Ralph Morrison Published by Wiley-Interscience
A technical paper on EMI emissions EMI Emissions of Modern PWM ac Drives
Gary L. Skibinski, Russel J. Kerkman, & Dave Schlegel IEEE Industry Applications Magazine, Nov./Dec. 1999
A text book on EMC EMC for Product Designers
Tim Williams Published by Newnes
1
Available in future. Check with The Automation Bookstore.com or your Allen-Bradley sales representative for documentation availability.

Conventions Used in this Manual

The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not procedural
steps.
Numbered lists provide sequential steps or hierarchical
information.
Words that you type or select appear in bold.
When we refer you to another location, the section or chapter
name appears in italics.
N/A
N/A
N/A
Publication GMC-RM001A-EN-P — July 2001
P-4 Preface
Publication GMC-RM001A-EN-P — July 2001
Electrical Noise Control Overview
Chapter
1

Chapter Objectives

What is Electrical Noise?

This chapter provides a brief understanding of the need for electrical noise control, how noise affects system performance, noise coupling methods and solutions. This chapter covers the following topics:
What is electrical noise

Understanding the need for electrical noise control

Noise control basics
Coupling mechanisms
Solutions for reducing noise
Implementation
Measuring effectiveness
Electrical noise is voltage spikes, generated by the routine operation of selected system components (sources), that interfere (due to a coupling mechanism) with the routine operation of other selected system components (victims).
Understanding the Need for
In Europe, a system must satisfy EMC regulations. It must also work reliably without suffering from noise-induced failures.
Electrical Noise Control

CE Compliance

Most equipment is CE marked. This means it is certified to be compliant with European Directives which comprise two main requirements:
Potential noise sources must be limited in noise output to a
Potential victims of noise must be hardened to withstand a higher
specified level.
noise level.
Publication GMC-RM001A-EN-P — July 2001
1-2 Electrical Noise Control Overview
In both cases, equipment must be installed to manufacturers recommendations to achieve compliance. The frequency range covered is 150kHz to 1GHz, though the upper limit is likely to be raised as operation frequencies increase.
Despite this, a CE compliant industrial drive system may still suffer functional failures due to electrical noise. Additional measures are often necessary to prevent noise from being coupled between source and victim. The frequency range involved in system failures is generally confined between 200kHz and 10MHz.

Best Practices

Most industrial control products do not utilize high frequencies directly, but they can generate them in the form of noise. Logic circuits are affected by this noise, so you need to be able to control it.

Noise Control Basics

Because it is far less expensive to apply noise control measures during system installation than it is to redesign and fix a malfunctioning system, we recommend you implement the best-practice procedures described in this document.
If basic measures are implemented rigorously, a reliable system should result. However, if just one wire is routed incorrectly or a filter is missed, it may be enough to cause problems. Experience shows that it is very difficult to ensure that these measures are applied 100% of the time. If all possible measures are taken (incorporating redundancy), the system is likely to be more tolerant of minor mistakes in implementation.
A typical industrial control system will contain a mixture of noise sources and potential victims. Problems are caused when a coupling mechanism is introduced.

Noise Sources

Publication GMC-RM001A-EN-P — July 2001
Typical noise sources include:
Mechanically switched inductive loads create intense intermittent
noise.
PWM drive power outputs create intense continuous noise.
Switch-mode DC power supplies can create continuous noise.
Electrical Noise Control Overview 1-3
Microprocessor clocks can generate high levels of noise at the
clock frequency and its harmonics.
Contact switching.
Of the noise sources listed above, only contact switching noise can be reduced at the source by the system builder.
Refer to the figure below for an example of a typical noise source.
Figure 1.1 Switch-Mode Power Supply Noise Measurement
AC
Line
Filter
+24V
24V dc PSU
DC common
Ground Plane - conductive metal panel
No load connected
Noise voltage measured here
Refer to Figure 1.2 for an example of six volt noise spikes from a typical 24V dc power supply. The spikes usually contain frequencies above 10 MHz.
Figure 1.2 Switch-Mode Power Supply Noise
10V
8
6
4
2
0
-2
-4
-6
6.0V pk
-8
-10V
-10123456789
Sitop Power 20 with 3 phase input - no load
Common Mode Noise +24 Volts to Backplane
ms
Publication GMC-RM001A-EN-P — July 2001
1-4 Electrical Noise Control Overview

Noise Victims

Typical noise victims include the following:
Microprocessor controlled devices
Analog devices
Encoder and registration interfaces
Refer to Figure 1.3 for an example of a typical victim.
Figure 1.3 A victim TTL gate is easily triggered
Noisy circuit carrying 6V spikes
comprising mainly 10 MHz
5V TTL gate

Coupling Mechanisms

100 pF = 200
50
Signal Source (zero impedance)
1
Refer to the section Capacitance below for an explanation of the 200 ohm impedance. Generally, most potential victims are better protected than this.
@ 10 MHz
Victim TTL gate receives 1.2V spikes
1
The source noise level and the victim’s sensitivity are normally outside the control of the system designer so that it is necessary to concentrate on the transmission of noise between them.
The coupling mechanism is the means by which electrical noise interferes with the routine operation of equipment. This section describes the four common coupling mechanisms for electrical noise transmission.
Publication GMC-RM001A-EN-P July 2001

Conducted Noise

Noise is conducted directly by system power wiring. A common route for conducted noise is the 24V dc distribution wiring.
Electrical Noise Control Overview 1-5

Capacitance

At radio frequencies (RF) the capacitance between two adjacent wires is significant. Two insulated wires touching each other and only 1.0 meter (39.0 in.) long form a capacitance of approximately 100 pF (Pico Farads). At 10 MHz the impedance is only 200 ohms.
Fortunately, the effect reduces as the square of the separation distance. Refer to Figure 1.4 for an example of capacitive coupling.
Figure 1.4 Capacitive Coupling
Stray
capacitance
Circuit A
Separation distance
Circuit B

Mutual Inductance

At radio frequencies (RF) the inductance of a straight wire is significant. A length of wire 1.0 meter (39 in.) has an inductance of
µ
approximately 1.0 ohms.
Two adjacent wires have mutual inductance forming a transformer. Fortunately, the effect reduces as the square of the separation distance. Refer to Figure 1.5 for an example of inductive coupling.
Figure 1.5 Inductive Coupling
H (Micro Henry). At 10 MHz the impedance is 60
Stray
inductance
Circuit A
Magnetic coupling
Circuit B
Separation distance
Publication GMC-RM001A-EN-P July 2001
1-6 Electrical Noise Control Overview

Electromagnetic Radiation

An example of electromagnetic radiation is radio transmission. Industrial control wiring systems are large, wideband antenna which radiate noise signals to the world. These signals (together with conducted noise) are the primary target of the European regulations, but rarely cause system malfunctions.

Solutions for Reducing Noise

This method: In this
category:
HF (high frequency) Bonding
Segregation Coupling
Shielding Coupling
Filtering Coupling
Coupling Reduction
Reduction
Reduction
Reduction
Noise reduction solutions are categorized as coupling reduction and source reduction. There are four main methods used to reduce the coupling of noise between source and victim. However, contact suppression is the only source reduction technique that can be directly applied by the system builder. Refer to the table below for a summary.
Is defined as: For more
information refer to:
Maintaining all
metalwork at the same electrical potential. This method is low cost and the basis for all other methods. It works by ensuring all equipment chassis are at the same potential at all
The chapter High
Frequency (HF) Bonding.
frequencies. If different potentials exist the voltage difference is seen as common-mode noise on all interconnecting wiring.
Separating sources and victims of electrical noise into zones. Noise coupling reduces with the square of separation distance. Zoning is zero cost (within limits).
Using shielded cable and steel barriers (Faraday cage effect) to reduce electrical noise. Because of its relatively high cost, shielding is used with discretion.
Using low-pass filters to attenuate RF noise. Relatively low cost but impractical for every wire.
The chapter
Segregating Sources and Victims.
The chapter Shielding Wires, Cables, and Components.
The chapter Filtering Noise.
Contact Suppression
Source Reduction
Adding contact suppression to mechanical switches to reduce noise. Generally, the one noise source directly influenced by the system builder.
Publication GMC-RM001A-EN-P July 2001
The chapter Contact Suppression.
Electrical Noise Control Overview 1-7

Implementation

This application: Is defined as: For more
Routing AC and DC power
Routing motor power cables
Wiring high speed registration inputs
Routing encoder power cables
Applying bonding, segregating, shielding, and filtering techniques to AC and DC power supplies and the associated wiring.
Applying shielding, grounding, and splicing techniques to motor power cable installation.
Applying all the noise reduction methods available to improve the performance of noise sensitive wiring.
Applying bonding, segregating, shielding, and filtering techniques to encoder installation.

Measuring Effectiveness

Implementation involves applying the methods summarized in the table on page 1-6 to the applications as shown in the table below.
information refer to:
The chapter Power Distribution.
The chapter Motor Wiring.
The chapter High Speed Registration Inputs.
The chapter Encoders.
Measuring noise reduction effectiveness involves using an oscilloscope to test for noise during implementation. It also involves monitoring for noise after implementation should updates to the system affect system performance.
This application: Is defined as: For more
information refer to:
Measuring effectiveness
Testing for electrical noise during implementation, identifying the sources of noise, determining acceptable noise levels, and monitoring for noise on an on-going basis.
The chapter
Measuring Noise Reduction Effectiveness.
Publication GMC-RM001A-EN-P July 2001
1-8 Electrical Noise Control Overview
Publication GMC-RM001A-EN-P July 2001
High Frequency (HF) Bonding
Chapter
2

Chapter Objectives

Understanding the Source of Electrical Noise

This chapter describes the ground plane principle and techniques to extend the ground plane to devices, panels, machines, floors, doors, and buildings. This chapter covers the following topics:
Understanding the source of electrical noise
Noise solutions using a ground plane
Grounding (safety earth)
The most common source of electrical noise is due to switching of PWM output stages.
Two examples of how noise is generated by a drive system are given on the following pages.
Publication GMC-RM001A-EN-P July 2001
2-2 High Frequency (HF) Bonding

Noise Example 1

The transistors impose a 600V step change in the wire B (typically less than 200nS). Stray capacitance A charges very rapidly causing a current spike. This is the dominant noise source in PWM (Pulse Width Modulated) drive systems.
The current circulates through stray capacitance C, bonding impedance D, bonding impedance E, bonding impedance F, and back to stray capacitance A. A voltage spike will appear between motor frame and machine structure (Vd), between machine structure and the panel (Ve) and between the panel and drive chassis (Vf).
The circuit of an encoder mounted on the motor will then have a voltage spike of amplitude Vd + Ve relative to the panel and to any input circuit on the panel, potentially a noise victim.
The noise voltages are proportional to the impedance of the bonds (voltage = current x impedance). If these are reduced to zero, no voltage will appear between encoder and panel.
Figure 2.1 Switching noise affecting encoder signal
Drive
Heatsink (connected to chassis)
F
IMPORTANT
Panel
The quality of bonding techniques applied during installation directly affects the noise voltages
+600V dc
Stray
capacitance
A
B
Transistor block
DC common
Impedance due to
poor bonding
between system components.
Motor
Windings
C
Encoder
D
E
Machine Structure
Publication GMC-RM001A-EN-P July 2001
High Frequency (HF) Bonding 2-3

Noise Example 2

Stray capacitance I charges very rapidly. Current circulates via stray capacitances H, bond G, bond F, and A. In this way, a voltage Vf + Vg is developed between the drive chassis and true-ground.
Any remote equipment grounded to this true-ground and wired to the drive will have this noise voltage imposed upon its incoming signal.
Figure 2.2 Switching noise affecting incoming power
AC line
Stray capacitance
to ground
H
G
F
Drive
Heatsink (connected to chassis)
Impedance due to poor bonding
Panel
I
A
+600V dc
Stray capacitance
Transistor block
DC common
Many other noise sources exist in a typical system and the advantage of good bonding holds true for all.

The Ground Plane Principle

The purpose of High Frequency (HF) bonding is to present a defined low impedance path for HF noise currents returning to their source.
IMPORTANT
Most textbooks on radio frequency (RF) techniques describe the ground plane (GP) as the ultimate ground reference and an absolute requirement for controlling RF current paths.
Noise current must and will return to source. If a safe path is not provided, it may return via victim wiring and cause circuits to malfunction.
Publication GMC-RM001A-EN-P July 2001
2-4 High Frequency (HF) Bonding
The ground plane principle was originally developed by printed circuit board (PCB) designers for high frequency circuits. In multi-layer PCBs a minimum of two copper layers are used with one being designated the ground or common. This layer covers as large an area as possible and each IC common is tied directly to it. In addition, each IC Vss (+5V) pin is decoupled by a 0.1
µ
F capacitor to the ground plane as close as possible to the pin. The capacitor presents a very low impedance at RF hence any induced noise current generates minimal voltage.
The fundamental property of a ground plane is that every point on its surface is at the same potential (and zero impedance) at all frequencies. At high frequencies this is more effective than the use of single point grounding schemes. This is because wire has significant inductance at RF and just a few inches can create an unacceptable voltage drop. Refer to the section Bonding Surfaces in Appendix A for more information.
Figure 2.3 Ground plane layer in a double-sided printed circuit board
Vss pin
Vdd pin
(common)
Ground plane
layer
Insulation
layer
Integrated Circuit
Interconnect
layer
(+5V)
Decoupling Capacitor
(Vss to ground)
Ground plane construction has proved so successful that it is now universal in PCB design for all but the most price-sensitive and low frequency circuits. Single-sided PCBs are not generally used for RF or TTL circuits.
Publication GMC-RM001A-EN-P July 2001
High Frequency (HF) Bonding 2-5

Extending the Ground Plane Principle

The same theory holds true regardless of scale, (the earth being the ultimate and literal ground plane) and can be used at control cabinet level or even building level, but requires rigorous implementation.
A ground plane does not have to be flat, but gentle curves prove more effective than sharp corners. Area is what matters. Even the outer surface of a machine structure can be used.

Grounding a PCB to the Drive Chassis

In the figure below, a PCB ground plane is extended by bonding it to the drive chassis.
Figure 2.4 PCB ground plane extended to the drive chassis
Drive
chassis
Printed circuit
board (PCB)
Guidelines for the system builder include:
PCB copper interconnection layer
PCB copper ground plane layer bonded to drive chassis
When permitted, the control circuit common should be grounded.
Some products do not permit grounding of the control common,
µ
but may allow grounding to chassis via a 1.0
F, 50V ceramic
capacitor. Check your installation manual for details.
Publication GMC-RM001A-EN-P July 2001
2-6 High Frequency (HF) Bonding

Noise Solutions Using the Ground Plane Principle

In this section, examples of how to apply the ground plane principle are described.

Grounding to the Component Mounting Panel

In the example below, the drive chassis ground plane is extended to the mounting panel. The panel is made of zinc plated steel to ensure a proper bond between chassis and panel.
Figure 2.5 Drive chassis ground plane extended to the panel
Drive ground plane (chassis) bonded to panel
Publication GMC-RM001A-EN-P July 2001
Note: Where TE and PE terminals are provided, ground each
separately to the nearest point on the panel using flat braid.
Plated vs. Painted Panels
In an industrial control cabinet, the equivalent to the copper ground layer of a PCB is the mounting panel. To make use of the panel as a ground plane it must be made of zinc plated mild steel or if painted, the paint must be removed at each mounting point of every piece of metal-clad equipment (including DIN rails).
Zinc plated steel is strongly recommended due to its inherent ability to bond with the drive chassis and resist corrosion. The disadvantage with painted panels, apart from the cost in labor time to remove the
High Frequency (HF) Bonding 2-7
paint, is the difficulty in making quality control checks to verify if paint has been properly removed, and any future corrosion of the unprotected mild steel will compromise noise performance.
Plain stainless steel panels are also acceptable but are inferior to zinc plated mild steel due to their higher ohms-per-square resistance.
Though not always available, a plated cabinet frame is also highly desirable since it makes HF bonding between panel and cabinet sections more reliable.
Painted Components
Mating surfaces must be cleaned of paint and the exposed surfaces protected against corrosion with conductive paint or petroleum jelly.
Anodized Aluminum Components
Mating surfaces must be cleaned of anodizing and the exposed surfaces protected against corrosion.
EMC Filters
Filter performance depends entirely on close coupling between the filter case and the drive chassis (or other load chassis). They should be mounted as close as possible to the load and on the same panel. If a painted panel is used, short braid straps should be used to tie the two chassis together. As a temporary remedy, an effective means of coupling filter case and drive chassis is to lay a single piece of aluminum foil beneath the two chassis.

Doors

For doors 2 m (78 in.) in height, bond with two or three (three is preferred) braided straps (top, bottom, and center).
EMC seals are not normally required for industrial systems.
Publication GMC-RM001A-EN-P July 2001
2-8 High Frequency (HF) Bonding

Adjacent Panels

Bond adjacent panels by mounting multiple flat straps between the panels. As an alternative, mount a filler plate between the panels using multiple fasteners along the edges of the plate.
Figure 2.6 Panel ground plane extended to adjacent panels
Adjacent panels
bonded to extend
the ground plane
Cabinet ground plane (component mounting panel)
Ground plane extended to side panel by bonding to main panel
Publication GMC-RM001A-EN-P July 2001
High Frequency (HF) Bonding 2-9

Grid and Raised Floor

Bonding cabinet panels and machine chassis to a ground grid below a raised floor is the best possible grounding scheme and commonly used in computer mainframe installations, but rarely used in industrial environments.
Ideally the grid squares should be 1 m (39 in.) or less.
Figure 2.7 Panel ground plane extended to a grid beneath a raised floor
Machine structure used as ground plane
Cabinet ground plane (panel) bonded to floor ground plane
Copper strip laid on the floor,
(also bonded to machine structure).
Grid ground plane.
covered by a false floor
Publication GMC-RM001A-EN-P July 2001
2-10 High Frequency (HF) Bonding

Mezzanine Floor

A mezzanine floor makes a very effective ground plane if the floor panels are aluminum or galvanized steel and bonded at their edges every 1 m (39 in.) minimum. Machine structure, floor, and both panels form one large ground plane.
Figure 2.8 Panel ground plane extended to a mezzanine floor
Mezzanine floor ground plane
Cabinet ground plane (panel) bonded to Mezzanine floor ground plane
Machine structure
bonded to floor
Machine structure used as ground plane
Machine structure
bonded to floor
Publication GMC-RM001A-EN-P July 2001
High Frequency (HF) Bonding 2-11

Machine Structure

If the machine structure covers a large portion of the system area and is constructed of a conductive material with all sections closely bonded, then it too will form an excellent ground plane. Care should be taken to ensure paint is removed at the bonds and the connections protected against corrosion.
Figure 2.9 Panel ground plane extended to the machine structure
Machine structure used as ground plane
bonded to structure ground plane by
Panel ground plane
clean and dirty wireways
Bond the panel(s) to the machine structure as tight as possible, but if this proves difficult, construct a low impedance path using the following guidelines:
Use a zinc-plated tray, as wide as practical, and join sections by
overlapping with several fasteners across the width. The perforations will not reduce performance (refer to Figure 2.10).
EMC trunking (plated at joint surfaces with conductive gaskets)
also makes a good bond.
Short and wide is the requirement for any HF bonding material.
Panel(s) should be located as close to the machine structure as practical and the bond should be firmly attached at both the machine structure and the control panel (not the cabinet outer panels).
Multiple trays/trunking are better.
Note that copper wire safety earth bonding is still required. Refer to the section Grounding (Safety Earth) at the end of this chapter for more information.
Publication GMC-RM001A-EN-P July 2001
2-12 High Frequency (HF) Bonding
Figure 2.10 Extending the panel ground plane using cable tray
Multiple
fasteners
Zinc plated
steel main
panel
Same width
Note: A ground plane does not have to be flat.
Must be directly bonded here and at the machine structure
Zinc plated
steel cable tray
(wider is better)

New Buildings

In new installations it is possible to specify that the structural steel columns are bonded together beneath the floor. This is similar in concept to the special floor grid shown earlier (refer to Figure 2.7), but inferior due to the large grid squares.
Cabinet ground plane (panel)
Publication GMC-RM001A-EN-P July 2001
The panels are bonded by a flat strip or braid to the nearest steel column. The floor, machine structure, and panels form a large, but relatively ill-defined ground plane.
Figure 2.11 Panel ground plane extended to the building
Machine structure used as ground plane Steel Column
Steel Column
bonded to nearest
building steel
Building ground plane.
Copper strip laid into the floor
bonding columns together.
High Frequency (HF) Bonding 2-13

Existing Buildings

The nearest building steel structures between the machine and control cabinets may be used to bond to.
If there is more than 20 m (65 ft) between the building structural steel closest to the motor and the building structural steel closest to the control panel, the ground between these two structural points should be checked and enhanced, if necessary, using at least 25 mm (1 in.) wide wire braid.

Limits

A ground plane sub-panel may only be considered part of a larger ground plane when bonded sufficiently well at RF. For this purpose wide thin strips are more effective than wire. Refer to the section Bonding Surfaces in Appendix A for more information.
Length
Shorter = better
Wider = better
Thickness is not an issue. Thin is acceptable (even foil is very
effective, but fragile).
The building example shown in Figure 2.11 normally falls outside these requirements.
In cases where the maximum 10:1 bonding aspect ratio limit cannot be satisfied, a differential noise voltage must be assumed to exist between each semi-isolated ground plane. All wiring entering a ground plane will carry this noise voltage and must be dealt with at the point of entry.
A ground plane is just as effective if it is perforated or made up of a matrix of flat conductors, provided that the apertures are smaller than one quarter of the wavelength of the highest troublesome frequency.
width x 10 is the generally accepted maximum ratio.
Publication GMC-RM001A-EN-P July 2001
2-14 High Frequency (HF) Bonding

Grounding (Safety Earth)

Grounding refers to safety grounding and although the safety ground circuit and the noise current return circuit may sometimes share the same path and components, they should be considered as totally different circuits with different requirements. The object of safety grounding/bonding is to ensure that all metalwork is at the same, ground (or Earth) potential at power frequencies.
The copper wire typically specified by regulatory bodies has little effect at the high frequencies involved in noise problems.
ATTENTION
Safety ground circuits are extremely important and all relevant local and international regulations must be adhered to and take precedence over any guidance given in this document.
!
Generally, safety dictates that all metal parts are connected to safety earth with separate copper wire of appropriate gauge.
Most equipment has specific provisions to connect a safety ground or PE (protective earth) directly to it.
These ground wires should be terminated directly to a bonded PE ground bar, but lengths are not important provided the ground plane strategy is followed (refer to the section The Ground Plane Principle).
Publication GMC-RM001A-EN-P July 2001
Segregating Sources and Victims
Chapter
3

Chapter Objectives

Understanding the Segregation Concept

This chapter describes how establishing zones within your panel for noise sensitive or noise generating components can reduce coupling of electrical noise. This chapter covers the following topics:
Understanding the segregation concept
Zone classification
Routing wires and cables within a panel
Routing system wires and cables between panels
You can avoid many of the problems caused by noise by grouping sources and victims (along with their associated wiring) in zones according to their noise performance rather than arranging for neatness, tradition, or convenience.

Noise Zones

The three noise zones are defined in the table below.
This noise zone: Has this relative noise level:
Very-Dirty High Dirty Moderate Clean Low
This descriptive terminology (very-dirty, dirty, and clean) is chosen for maximum clarity. Most noise documents assign numbers to the zones, but there is no consistent numbering scheme. The descriptive approach allows you to see the true meaning of a zone at a glance, without having to remember a code.
Publication GMC-RM001A-EN-P July 2001
3-2 Segregating Sources and Victims
Figure 3.1 shows how you can create three zones in a standard panel or cabinet enclosure. The very-dirty items are placed in the right/front section. The dirty items are placed behind them in the right/rear section and the least noisy (clean) items are placed in the left/rear section.
Figure 3.1 Relative position of noise zones on the panel
Main Panel or Cabinet
(top view)
Clean wireway and component
mounting section
Dirty wireway and component
mounting section
Right side divider panel
Left side and front panels (if cabinet)
Very-Dirty cable tray and component mounting
A side panel is fitted on the right to support the power cable shield clamps and any very-dirty wires, cables, or components. This leaves the main panel free for the clean and dirty zones.
Note: It is preferable to mount PLC and motion control equipment in a
separate cabinet away from power control equipment (motor starters, etc.).

Ensuring CE Compliance at Build Time

Ensuring CE compliance is aided by the use of detailed physical panel layouts, together with wiring schedules to specify precise wire routing and zone categories. Periodic checks during installation are recommended to achieve full CE compliance.
As an aid to the technicians wiring the panel, the use of grey wireways for the clean zone and black wireways for the dirty zone helps ensure proper segregation of cables. For example, this makes a communication cable running in a dirty wireway easier to see.

Zone Classification

Publication GMC-RM001A-EN-P July 2001
You can classify each cable or device based on these two factors:
How much noise does the cable/device generate/radiate?
How sensitive is the device connected via the cable to electrical
noise?
Segregating Sources and Victims 3-3

Component Categories

The table below indicates which noise zone components fall into as a general reference for component segregation
Note: An X in multiple zones indicates that the component straddles
the two zones. Under these circumstances it is important to position the component in the correct orientation.
Component Very-
Dirty Clean
Dirty
PWM Drives/Amplifiers
1
XXX
Dynamic braking components X External Dump Resistor (unshielded) X
External Dump Resistor (shielded)
2
X
AC Line Filter X X
Dump Resistor module (metal-clad)
2
X
Switch-mode DC power supply X
Ultrasonic Transducer
3
X
Contactors X MCB X
Switched 24V dc loads
4
X
(e.g., E-stop/Piltz circuit, solenoids, relays, etc.) Encoder buffer board X PLC X Registration 24V dc supply filter X Dirty to Clean filter X X Linear DC power supply X Other 24V dc none-switched loads X Data/Communication devices X Analog devices X
1
The connector/terminal block locations on the drive will normally dictate the zone geometry since it normally has connections in all categories. Design zones around the drive(s).
2
Bond chassis to the main panel or drive chassis. Refer to the chapter High Frequency (HF) Bonding for more information.
3
Refer to the chapter Filtering Noise for more information.
4
All inductive switched loads must be suppressed. Refer to the chapter Contact Suppression for more information.
Publication GMC-RM001A-EN-P July 2001
3-4 Segregating Sources and Victims

Routing Wires and Cables Within a Panel

The following figures provide examples of how to route clean, dirty, and very-dirty wireways or cable trays within a panel.
Figure 3.2 Routing clean and dirty cables
Main Panel
(front view)
Power
distribution
Barrier
Sensitive
equipment
PLC
C
C
A
PSU
Dirty Zone (black wireway)
PWM Drive
PWM Drive
Clean Zone
(grey wireway)
Clean
B
Dirty
Relays
Observe the following guidelines when planning your panel layout for clean and dirty cables:
The plated steel barrier between clean and dirty wireways allow
them to run close together.
If dirty power is required at A, then run it via wireway B using
shielded cable. Refer to the chapter Shielding Wires, Cables, and Components for more information.
The vertical wireway at C is not good practice as it encourages the
creation of loops. Refer to the section Minimizing Loops later in this chapter.
The use of different colored wireways (e.g., grey for clean and
black for dirty) encourages good segregation.
Publication GMC-RM001A-EN-P July 2001
Figure 3.3 Routing very-dirty cables
Segregating Sources and Victims 3-5
Dirty Zone
(black wireway)
Clean Zone
(grey wireway)
Main Panel (front view)
PWM
Drive
PWM
Drive
Right Side Panel
(inside view)
PWM
Drive
PWM Drive
Segregation from clean/dirty zone
Zinc plated cable tray
Drive power connections (forming bridge to cable tray)
Very-Dirty Zone (white cable tray)
Divider panel
Divider panel bonded with braided strap
to main panel (three places)
Observe the following guidelines when planning your panel layout for very-dirty cables:
Power cables bridge across to the drive terminals from the cable
tray on the right.
The cable tray is bonded to the divider panel using braided strap.
If no divider panel is used, then bond cable tray to main panel.
A divider panel is used on the right to segregate very-dirty wiring
from the clean zone of the next panel to the right.
The divider panel is bonded with braided straps to the main panel
at top, center, and bottom.
Clean and Dirty Zone
Cable tray bonded with braided strap to main/ divider panel
Use 25.4 mm (1.0 in.) wide braided strap for bonding (preferred
method). Braided strap 12.7 mm (0.5 in.) wide is acceptable.
Publication GMC-RM001A-EN-P July 2001
3-6 Segregating Sources and Victims

Wire and Cable Categories

The table below indicates the best zone for running cables and wires. The table also shows how the use of ferrite sleeves and shielded cable can reduce the noise effects of dirty and very-dirty wires and cables.
Note: Some items have two entries (one shielded and one not
shielded).
Zone Method
Cable and Wire Category
Very­Dirty
Dirty Clean Ferrite
Sleeve
1
Shielded
2
Cable
Three Phase between Line Filter and Drive
Three Phase between Line Filter and Drive
Extended DC bus X Extended DC bus X X
PWM Drive/Inverter to Motor Power PWM Drive/Inverter to Motor Power X X PWM Drive/Inverter to Sine Wave
Filter Sine Wave Filter to Motor X CM Choke to Motor Power X CM Choke to Motor Power X X Line Terminator - Motor Power X Line Terminator - Motor Power X X External Dump Shunt Resistor X External Dump Shunt Resistor X X Contactor to AC Motor X Contactor to AC Motor X X
X
XX
3
X
X
Publication GMC-RM001A-EN-P July 2001
Three Phase Supply Power X Single Phase Supply Power X 24V Hydraulic/Pneumatic - solenoids X Motor Feedback Resolver X X PLC digital I/O X Dedicated Drive Inputs (except
registration) Limit Switches X Push buttons X
X
Cable and Wire Category
Segregating Sources and Victims 3-7
Zone Method
Very­Dirty
Dirty Clean Ferrite
Sleeve
1
Shielded
2
Cable
Proximity Switches (except
X
registration) Photoelectric Cell X 24V dc Relay X Transformer Indicator Lamp X
Data/Communications
4
XX X
Encoder/Resolver X X Logic circuit power X X
High Speed Registration inputs
5
XX
PLC Analog I/O X X PLC High Speed Counter input X X
1
An X in this column indicates a ferrite sleeve fitted to the wire is recommended.
2
An X in this column indicates a shielded cable is recommended.
3
Keep unshielded conductors as short as possible and separated from dirty and clean cables as far as possible.
4
Refer to the section Data/Communications Cables below for more information.
5
Refer to the chapter High Speed Registration Inputs for more information.
Note: Grounding power cable shields at entry to the cabinet is recommended.
Data/Communications Cables
Data and communication cables that come from a remote structure (refer to the chapter High Frequency (HF) Bonding) will carry noise on their shields. Follow the guidelines listed below when installing data or communication cables.
Follow the product manual recommendations for termination
resistors, minimum and maximum length, etc.
Carefully segregate data and communication cables from dirty and
especially very-dirty cables.
Ground shields to the panel at the point of entry when permitted.
Check your manual for the recommended procedure. Connecting to the 360° shield is preferable to the use of pigtails. If pigtails must be used, they should be kept short. Refer to the section Grounding Cable Shields in Appendix A for more information on grounding cable shields.
Refer to the chapter Filtering Noise for more information.
Publication GMC-RM001A-EN-P July 2001
3-8 Segregating Sources and Victims
Minimizing Loops
Wires that form a loop make an efficient antennae. Run feed and return wires together rather than allowing a loop to form. Twisting the pair together further reduces the antennae effects. Refer to the figure below for an illustration.
Note: This applies to potential victim wiring too. Antennae work
equally well in both receive and transmit modes.
Figure 3.4 Avoiding loops in wiring designs
Not Recommended

Routing System Wires and Cables Between Panels

Switch
Switch
Good Solution
Better Solution
Switch
Follow the same segregation guidelines when wiring between panels and machine devices.
Maintain clean, dirty, and very-dirty noise zones.
Always use separate, grounded, metal wireways.
Publication GMC-RM001A-EN-P July 2001
Chapter
Shielding Wires, Cables, and Components
4

Chapter Objectives

Understanding the Shielding Concept

This chapter describes how using shielded cable or steel shields can reduce electrical noise coupling. This chapter covers the following topics:
Understanding the shielding concept
Ferrite sleeves
Mixing categories
You can avoid many of the problems caused by noise by shielding sources and victims (along with their associated wiring) with the use of shielded cable or a supplementary steel shield.
If sources and victims cannot be sufficiently segregated it may be possible to prevent noise coupling by shielding as shown in the figure below.
Figure 4.1 Wire segregation vs. shield
Minimum segregation is
150 mm (6.0 in.) within a panel
Clean Zone
Dirty Zone
Grounded steel shield allows minimal segregation distance.
Publication GMC-RM001A-EN-P July 2001
4-2 Shielding Wires, Cables, and Components
In the shielding example below the grey plastic wireway (front) is shielded by 0.7 mm (0.03 in.) thick perforated and plated sheet steel. The perforated steel is easy to cut and bend. You can safely route very-dirty wires in the other (black) wireway behind the shield.
Note: By using grey colored wireway for clean zones and black for
dirty and very-dirty zones you will see more clearly when shielding is necessary.
Figure 4.2 Shielding example

Ferrite Sleeves

Shielded data cables grounded at both ends (important at high frequencies) may carry noise current due to voltage differences between the two ends. Because the shields have a low impedance, currents may be quite high even though voltage is low. These currents can cause spurious data reception.
By installing ferrite sleeves, the common-mode impedance of the cable is greatly increased at HF thus blocking the noise currents without affecting the signal currents.
In Figure 4.3 the capacitor grounding is very effective and avoids no-grounding rules, but it’s awkward to implement.
Publication GMC-RM001A-EN-P July 2001
Shielding Wires, Cables, and Components 4-3
Figure 4.3 Ferrite sleeves increase common mode impedance
Ferrite sleeve greatly
increases impedance at RF
Signal
Source
Optional capacitor
V
Panel A
Differential noise voltage
Figure 4.4 Common mode rejection in shielded cable
Panel B
In this physical circuit, the core and shield are effectively connected together at the transmit end.
Vn is the noise voltage.
In this equivalent circuit, the core and shield form two windings of a 1:1 transformer.
The ferrite sleeve (more turns are better) forms a core increasing the magnetic coupling. The signal is unaffected.
This is known as a common-mode choke.
Tra n sm it
Core
Transmit Shield
Plane
Tra n sm it
Core
Transmit Shield
Plane
Vn
Vn
1:1
Vn
Receive Shield
Receive
0V
Receive Shield
Ferrite Sleeve
Receive
Plane
Core
Secondary voltage matches the primary voltage.
Plane
The following implementation guidelines apply to ferrite sleeves:
Always install ferrite sleeves to data cables where specified.
Always use ferrite sleeves when cable length is greater than 10 m
(30 ft).
Core
If power frequency ground currents are expected, or measured by
current clamp, one shield/ground connection could be made via a 1uF, 50V capacitor.
Publication GMC-RM001A-EN-P July 2001
4-4 Shielding Wires, Cables, and Components

Ferrite Sleeve Limitations

After implementing all the guidelines presented in this manual, a properly built system should perform well without ferrite sleeves. However, by including sleeves in your installation, the system will avoid problems caused during future modifications.
System installations can benefit from ferrite sleeves, but you should also realize that ferrite sleeves alone are not a substitute for proper noise coupling reduction techniques.
As a rule, include sleeves as standard to obtain the most effective overall system.
For more information about ferrite sleeves, refer to Appendix B.

Mixing Categories

It is often difficult to segregate effectively in a confined space. When strict segregation isn’t practical, minimize overlap and cross cables at right angles. Test results in Appendix A show that even a close parallel run of 0.5 m (20.0 in.) will allow significant noise coupling (refer to the section Wire Segregation Test Results).
You can convert wiring designated dirty or very-dirty to the next lower category by means of shielding using either shielded cable or conduit where required. Figure 4.5 and Figure 4.6 show how this technique may be used to mix categories without breaking the segregation rules.
Publication GMC-RM001A-EN-P July 2001
EMC
filter to drive
Very-Dirty Zone
Shielding Wires, Cables, and Components 4-5
In Figure 4.5 the cable is locally shielded to cross another zone. Each shield is grounded at each boundary and the cable is run close to the panel. The outer shield A is a thick walled steel conduit.
Figure 4.5 Very-dirty cable in clean zone
Dirty Zone
24V dc I/O
cable
Dirty Zone
Clean Zone
Dirty Zone
Very-Dirty Zone
Motor power
cable
Analog device
cable
Clean Zone
A
Minimum 150 mm (6.0 in.) segregation
The principle works both ways. In Figure 4.6 the clean cable passes through a very-dirty zone.
Figure 4.6 Clean cable in very-dirty zone
Dirty Zone
24V dc I/O
cable
Dirty Zone
Very-Dirty
Zone
Dirty Zone
Clean Zone
Encoder
cable
A
Minimum 150 mm (6.0 in.) segregation
Publication GMC-RM001A-EN-P July 2001
4-6 Shielding Wires, Cables, and Components
Publication GMC-RM001A-EN-P July 2001
Filtering Noise
Chapter
5

Chapter Objectives

Understanding the Filtering Concept

This chapter describes how low-pass filters and ferrite sleeves can reduce electrical noise coupling. This chapter covers the following topics:
Understanding the filtering concept
Filter performance
Ultrasonic transducers
AC line filters
If sources and victims are connected by wiring, you can prevent noise coupling by filtering. Low-pass filters attenuate high frequency noise without affecting the low frequency signals.

Commercial AC Line Filters for Low Voltage Circuits

Provided that motor cable lengths are short, less than 20 m (60 ft), commercial AC line filters work well in low voltage circuits. Two-stage types are preferred.
If motor cable lengths are long, the natural ringing frequency is typically at too low a frequency (below 300k Hz) to be attenuated by commercial AC line filters. To determine if your cables are long, refer to the section Installing Long Motor Cables in Appendix A.
Publication GMC-RM001A-EN-P July 2001
5-2 Filtering Noise

General Purpose 0-24V ac/dc Filters

The filter diagram shown below forms a classic LC low-pass filter.
Figure 5.1 Filter applied to 24V dc power circuit
Grounded
Common
+24V
Com/Neutral
IMPORTANT
The effectiveness of the LC low-pass filter depends on a perfect bond between the DIN rail and the ground plane panel.
Figure 5.2 Universal 0-24V ac/dc grounded common filter
Clean side
Floating
Common
Segregation
DIN rail
Publication GMC-RM001A-EN-P July 2001
Capacitor
Ferrite Sleeve
(choke)
Dirty side
Figure 5.3 Floating-Common filter
Filtering Noise 5-3
Clean side
Dirty side
Forming capacitor leads
DIN rail
Capacitors
Ferrite Sleeve
(choke)
The table below lists the part description and part numbers for the filters shown in Figure 5.2 and Figure 5.3.
Part Description RS Components
Part Number
Newark Part Number

Filter Performance

Ground Terminal (1 in, 2 out type) 225-4372 N/A Insulated Terminal (1 in, 2 out type) 426-193 N/A
1 µF, 50V Ceramic Capacitor
Small Ferrite Sleeve
1
Capacitor value is not critical, but it must be a ceramic type.
2
The ferrite specification is not critical, but choose a low frequency type if possible.
3
Alternative ferrite sleeve part numbers: Palomar (FB-102-43) or Schafner (2644665702)
Note: For more information regarding part vendors refer to Appendix B.
1
2
211-5558 29F025
239-056
3
91F6484
The theoretical attenuation of one stage and two stage filters is shown in the table below.
With this filter: Attenuation @ 1M Hz is:
1 stage (2.8k Hz) 55 dB 2 stage (1.2k Hz 110 dB
Publication GMC-RM001A-EN-P July 2001
5-4 Filtering Noise
M

Performance Test Set-up

The filter performance test included the following components:
24V dc power supply with grounded common filter
Filter mounted to DIN rail
Relay coil to simulate an inductive load
100M Hz sampling digital storage oscilloscope
Test components mounted on a large zinc plated steel panel
Figure 5.4 Filter test block diagram
easurement point
1 m (39 in.) wire
Switched load
Filter
Filter under
test
24V dc
PSU
Ground Plane - conductive metal panel

Test Results

This test condition: With
No filter:
No Suppression 200V pk 5.5V pk 674mV pk R/C
5.5V pk 932mV pk 168mV pk Across coil 100R/0.1uF
R/C
2.5V pk 103mV pk 70mV pk Across switch 100R/0.1uF
Transorb
14.9V pk 1.8V pk 658mV pk Across coil
Transorb
8.1V pk 1.4V pk 1.2V pk Across switch
With Capacitor only:
With Capacitor and ferrite sleeve:
Suppression
Publication GMC-RM001A-EN-P July 2001
Diode 12V pk 63mV pk 63mV pk
Note: Voltages were measured between the measurement point and the ground plane (refer to Figure 5.4 for
exact location.
Filtering Noise 5-5

Ultrasonic Transducers

Xenon Flashing Beacons (strobe lights)

Ultrasonic transducers often induce high noise levels onto their DC supply and signal lines. To reduce noise using ultrasonic transducers:
1. Mount two DC filters close to the device with ferrite sleeves
between the capacitors and the sensor.
2. Feed the DC power supply through one sleeve.
3. Bring out the analog signal via the other sleeve.
Note: Use shielded cable for the analog signal.
The filter ground should be close coupled to the machine metalwork close to the sensor.
Strobe lights can generate high voltage transients on their 24V dc supply lines. To reduce this source of noise, try using one of these two alternatives.
Mount a DC filter close to the lamp (ferrite sleeve on the lamp
side) with its common attached to chassis ground.

AC Line Filters

Use shielded cable between lamp and control panel, with DC filter
at the point where the cable leaves the panel.
AC line filters contain capacitors connected between phase and the filter chassis. Line voltage is with respect to ground. The capacitor allows a small but potentially dangerous amount of current to flow to ground.
ATTENTION
To avoid personal injury and/or damage to equipment, ensure AC line filter capacitors are properly connected to safety (PE) ground.
!
Publication GMC-RM001A-EN-P July 2001
5-6 Filtering Noise
Figure 5.5 Line filter earth leakage path
L
Line
N
Leakage current
E
Load
Three phase filters are theoretically balanced so the net ground current should be zero. However, a failure of any one capacitor or severe unbalance would cause ground current to flow and trip a circuit breaker.

Earth Leakage/Ground Fault

Earth Leakage Circuit Breakers (ELCB) and Ground Fault Interrupters (GFI) are typical European and US terms for the same device.
The ground/earth current may cause nuisance tripping of Earth Leakage Breakers. Uprated units may help in some cases.
Three phase filters, being balanced, are much less likely to give problems than single phase types.
Publication GMC-RM001A-EN-P July 2001
Contact Suppression
Chapter
6

Chapter Objectives

Understanding Contact Suppression for AC Circuits

This chapter describes how contact suppressors for solenoids, relays, and various other switches can reduce electrical noise. This chapter covers the following topics:
Understanding contact suppression for AC circuits
Understanding contact suppression for 24V dc circuits
Contact suppression effects
The one potential noise source that the you can reduce directly is a contact switched load. Even circuits feeding resistive loads will produce significant switching noise. This is because the wiring both upstream and downstream of the contact is inductive. Thus, any switch contact will benefit from suppression.
IMPORTANT
Examples of AC devices requiring contact suppression include:
All switched, inductive loads in the system must be suppressed. This is standard practice in any PLC based control system.
Contactor controlled motors
Solenoid coils
Contactor coils
Relay coils
Transformer primaries
Transformer driven indicator lamps
Fluorescent cabinet lights (also require line filters close to the
lamp)
Line filters (often present an inductive load)
The only exception is a load driven by a Zero-Crossing Detector circuit such as Allen Bradley solid-state (Triac) output modules. Zero-crossing switches reduce noise generation virtually to zero. Preferred for frequent operation or close to clean zones.
Publication GMC-RM001A-EN-P July 2001
6-2 Contact Suppression
Note: Sometimes the supply to a group of zero-crossing Triac outputs
is switched by a mechanical contact for safety purposes. Suppress at the contact in this case.

Methods of AC Contact Suppression

The typical RC suppressor circuit (shown below) consists of a 0.1 µF capacitor in series with a 100 ohm resistor. These components are readily available from many suppliers.
Figure 6.1 RC suppressor circuit
0.1 µF
100 ohms
The typical RC plus transient absorber circuit (shown below) consists of the RC network shown in Figure 6.1 in parallel with a transient absorber. These are used in high current, high energy applications such as motor starters. A three-phase contactor requires three suppressors.
Figure 6.2 RC plus transient absorber circuit
Transient absorber
0.1 µF
100 ohms
Publication GMC-RM001A-EN-P July 2001
Contact Suppression 6-3
The suppressor across the contact (as shown below, lower) reduces the noise from the wiring inductance as well as the coil inductance.
Figure 6.3 RC suppressor in circuit
L
Good Solution
Line
Load

Understanding Contact Suppression for 24V dc Circuits

N
L
Line
N
RC suppressor
Better Solution
Load
Examples of DC devices requiring contact suppression include:
Solenoid coils
Contactor coils
Relay coils

Methods of DC Contact Suppression

First choice for DC circuit suppression is a flywheel diode (shown in the figure below), but this does increase the release time which may not be acceptable in all applications. For the transient absorber method, refer to Figure 6.5.
Figure 6.4 Flywheel diode
+24V dc
Common
+24V dc
Common
Good Solution
Flywheel diode
Better Solution
Flywheel diode
Publication GMC-RM001A-EN-P July 2001
6-4 Contact Suppression
Figure 6.5 Transient absorber
+24V dc
Good Solution

Contact Suppression Effects

Common
+24V dc
Common
Transient absorber
Better Solution
Transient absorber
The waveform below displays 7.2V peaks across the AC terminals of a +24V dc power supply. Noise is due to load on the DC circuit being switched.
Figure 6.6 Unsuppressed inductive load on the DC circuit
10V
8
7.2V pk
6
4
2
0
-2
-4
-6
-8
-10V
-10123456789 Source Omron PSU AC Neutral
DC floating, Unsuppressed Relay
µs
Publication GMC-RM001A-EN-P July 2001
Contact Suppression 6-5
The waveform below displays the effects of an RC suppressor added across the coil on the noise shown in Figure 6.6. Peaks are reduced to
6.4V with significant reduction in duration. Refer to Figure 6.3 (upper) for example of RC suppressor across a coil.
Figure 6.7 Effects of RC suppressor mounted at the load
10V
8
6.4 mV pk
6
4
2
0
-2
-4
-6
-8
-10V
-10123456789 Source Omron PSU AC Neutral
DC floating, RC suppressor at Relay coil
(No difference at contact)
µs
The waveform below displays the effects of a flywheel diode across the coil (refer to Figure 6.4, upper). The peak voltage is reduced to
0.9V.
Figure 6.8 Effects of Flywheel Diode at the load
10V
8
6
4
2
930 mV pk
0
-2
-4
-6
-8
-10V
-10123456789
Source Omron PSU AC Neutral DC floating, Diode at Relay coil
µs
Publication GMC-RM001A-EN-P July 2001
6-6 Contact Suppression
The waveform below displays the effects of a flywheel diode across the switch (refer to Figure 6.4, lower). The peak voltage is reduced to
0.3V.
Figure 6.9 Effects of Flywheel Diode at the switch
10V
8
6
4
2
340 mV pk
0
-2
-4
-6
-8
-10V
-10123456789 Source Omron PSU AC Neutral
DC floating, Diode at Switch
µs
The small additional noise reduction, when the suppressor is fitted across the switch, is because the wiring between switch and load is also inductive and creates the same inductive spike.
Publication GMC-RM001A-EN-P July 2001
Power Distribution
Chapter
7

Chapter Objectives

Understanding Noise in Power Wiring

Three-Phase Power Supplies

This chapter describes bonding, segregating, shielding, and filtering techniques when routing AC and DC power. This chapter covers the following topics:
Understanding noise in power wiring
Three-phase power supplies
Single-phase power supplies
24V dc power supplies
AC and DC power wiring usually extends to all parts of a system. Without precautions, noise coupled into any power wiring conductor is distributed throughout the entire system.
To avoid noise related problems caused by three-phase power supplies, observe the following guidelines.
Treat three-phase wiring as dirty.
Include line filters for loads that create noise, such as PWM
devices.

Line Filters

Observe the following guidelines when installing line filters.
Install an individual filter as close as possible to each PWM load
(this is the preferred configuration).
Install the filter and PWM device on the same panel.
Treat wiring between filter and drive as very-dirty (provide
shielding as required).
Segregate input and output wiring as far as possible.
Publication GMC-RM001A-EN-P July 2001
7-2 Power Distribution
IMPORTANT
The effectiveness of the line filter depends solely on the HF bond between filter case and drive chassis.
Commercial filters are tested, as shown in the figure below, with all devices properly bonded to a conductive metal ground plane. Proper bonding techniques are essential to achieve the published attenuation figures. Refer to the chapter High Frequency (HF) Bonding for more information on bonding.
Figure 7.1 Filter test set-up
Signal
Generator
Filter under test
Ground Plane - conductive metal panel
Measuring Instrument
In the example below, noise couples directly from the filter input wires to the filter output wires and bypasses the filter. You can avoid this common mistake by shielding and/or segregating the cables and reducing the cable length.
Figure 7.2 Improper line filter installation example
AC Line
PWM Drive
ATTENTION
!
AC
Close spacing
Unshielded cable
Long distance
Line Filter
To avoid personal injury and/or damage to equipment, ensure AC line filter capacitors are properly connected to safety (PE) ground.
Publication GMC-RM001A-EN-P July 2001
Power Distribution 7-3

Transformers

An isolation transformer is frequently assumed to give good noise isolation. In fact, this only applies if the transformer is equipped with one or more electrostatic (ES) shields, as shown in the figure below.
Figure 7.3 Electrostatically shielded transformer
Primary
Ground Plane
Shield(s) bonded to
ground plane
Secondary
Frame bonded to ground plane
This technique is very effective, though generally EMC filters are required to meet European regulation standards. Observe the following guidelines when installing transformers.
Install the transformer to the same panel as the rest of your system
(or HF bond from panel-to-panel).
Treat wiring between transformer and drive as very-dirty (provide
shielding as required).
Bond shield, if used, with braid directly to the panel. The
transformer mounting bolts are useful for this purpose.
Segregate input and output wiring as far as possible.
IMPORTANT
The effectiveness of the transformer depends solely on the HF bond between shields and drive chassis.
Publication GMC-RM001A-EN-P July 2001
7-4 Power Distribution

Single Phase Power Supplies

24V dc Power Supplies

To avoid noise related problems caused by single-phase power supplies, observe the following guidelines:
Treat single-phase wiring as dirty.
Include line filters for loads that create noise, such as PWM
devices with DC switch-mode power supplies and fluorescent cabinet lights.
Include line filters for potentially sensitive loads, such as PLC logic
power.
Mount the line filter as close to the load as possible.
Switch-mode power supplies do not isolate noise and may generate common-mode noise on both AC and DC lines. Refer to the section Switch-Mode DC Power Supplies in Appendix A for more information.
Linear power supplies normally generate very little noise, but AC line filters or DC output filters are required to attenuate incoming line noise to achieve a clean category.
To avoid noise related problems caused by 24V dc power supplies, observe the following guidelines.
Connect the common through a ground terminal.
Decouple the +24V dc line to the same ground terminal with a
1 µ
F, 50V ceramic capacitor to achieve the clean category.
The simplest method for making the ground connection is to use a ground terminal installed on the DIN rail fastened to a zinc plated panel. Refer to Figure 7.4 for an example of the symbol used in diagrams.
Figure 7.4 Ground Plane Symbol
This symbol indicates direct connection to a ground plane.
Publication GMC-RM001A-EN-P July 2001
Power Distribution 7-5

24V dc Distribution

Route power wiring according to clean/dirty zones. Segregate the following load classifications:
Clean loads that are potentially sensitive to noise and which do
not create significant noise, e.g. controller logic supplies.
Dirty loads that are insensitive to noise but may emit moderate
levels of noise, e.g. relay circuits.
Note: Refer to the chapter Segregating Sources and Victims for a
detailed listing of categories.
Note: Refer to the chapter High Speed Registration Inputs for special
treatments of registration input devices.

24V dc PSU Zoning Methods

The following two methods of 24V dc power supply zoning are described in this chapter.
Single 24 volt power supply with filtering between zones.
Dual 24 volt power supplies.
Publication GMC-RM001A-EN-P July 2001
7-6 Power Distribution
Single 24V dc Switch-Mode PSU Zoning Example
In the figure below, a 24V dc supply is mounted in the dirty zone, because it may create noise. But, the noise is reduced by filtering before the output enters the clean zone.
Figure 7.5 24V dc power distribution with single PSU
24V com
Dirty Load
Clean Load
AC
+24V
24V dc PSU
Filter
Dirty Zone
Segregation
Clean Zone
Filter
De-coupling
capacitor
Grounded, de-coupling capacitors are used at each clean load (refer to the chapter High Frequency (HF) Bonding for details). Provided the system is correctly bonded, the multiple common/ground connections are not a problem. The copper becomes a backup conductor. No segregation or filtering is necessary for the load in the dirty zone.
Publication GMC-RM001A-EN-P July 2001
Power Distribution 7-7
In the figure below, a filter is pictured between the clean zone (grey wireway) and the dirty zone (black wireway). Refer to the chapter Filtering Noise for details regarding filters.
Figure 7.6 Filter between zones
Publication GMC-RM001A-EN-P July 2001
7-8 Power Distribution
Dual Switch-Mode 24V dc PSU Example
In the figure below, dirty and clean zone loads have dedicated power supplies. Segregation and filtering are used (as in Figure 7.5) to reduce the noise in the power supply for clean zone needs.
Figure 7.7 24V dc power distribution with dual PSU
24V com
Dirty Load
Clean Load
24V com
AC
AC
Dirty Zone
Clean Zone
Filter
Filter
+24V
24V dc PSU
24V dc PSU
Segregation
Filter
De-coupling
capacitor
+24V
Note: Clean PSU is mounted in the dirty zone because it typically
generates noise in the switching process.
Publication GMC-RM001A-EN-P July 2001
Power Distribution 7-9

Linear PSU

The linear PSU does not generate noise on its AC terminals, as does a switch-mode supply, however, some noise reduction provisions are still recommended.
Linear PSU Mounted in Clean Zone
In the figure below, the linear power supply is mounted in the clean zone, but the AC line feeding it requires filtering. The AC line filter is positioned between zones and attenuates line noise which may otherwise be passed through to the DC circuit.
Figure 7.8 Linear PSU mounted in Clean Zone
AC
Dirty Zone
Filter
24V dc Linear PSU
De-coupling
capacitor
+24V
Segregation
Clean Zone
Clean Load
24V com
Publication GMC-RM001A-EN-P July 2001
7-10 Power Distribution
Linear PSU Mounted in Dirty Zone
In the figure below no AC line filter is required because the linear PSU does not generate noise and the AC line noise is filtered by the DC filter.
Figure 7.9 PSU mounted in Dirty Zone
AC
Dirty Zone
Clean Zone
24V dc
Linear PSU
Segregation
Filter
De-coupling
capacitor
+24V
Clean Load
24V com
Publication GMC-RM001A-EN-P July 2001
Power Distribution 7-11

Special Applications for 24V dc PSUs

This section contains information considered application specific and does not apply to all installations.
Floating Requirement
If it is necessary to maintain a floating common, a modified filter may be used to ground the common at HF frequencies only. Refer to the chapter Filtering Noise for details regarding filters.
Figure 7.10 Floating Common
AC
Dirty Zone
Clean Zone
24V dc PSU
Filter
Segregation
Filter
De-coupling
capacitor
+24V
24V com
Dirty Load
Clean Load
Publication GMC-RM001A-EN-P July 2001
7-12 Power Distribution
Segregation and Filtering Variations
Once the principles of segregation and filtering are understood it is possible to vary the strategy to suit special requirements.
For example, the clean zone does not have to be a single entity. As shown in the figure below, you can create separate local clean zones. Refer to the chapter Segregating Sources and Victims for guidelines on crossing zones.
Figure 7.11 Separate Clean Zones
+24V
24V com
Dirty Zone
Filter
Clean Zone
A
Segregation
Filter
Clean Zone
B
Publication GMC-RM001A-EN-P July 2001
Power Distribution 7-13
Long Power Cable Runs
The 24V dc lines entering or leaving panels that cannot be bonded together by flat strips (no longer than 10 times the width) should have filters at the point of entry.
Figure 7.12 Long cable runs between panels
Panel A
+24V
24V com
Panel B
Note: If heavy circulating currents at power frequency are likely, the
floating filter technique or separate, local PSUs, may be safer to use.
Publication GMC-RM001A-EN-P July 2001
7-14 Power Distribution
Publication GMC-RM001A-EN-P July 2001
Motor Wiring
Chapter
8

Chapter Objectives

Understanding Noise in Motor Power Wiring

This chapter describes shielding, grounding, and splicing techniques for use with motor wiring. This chapter covers the following topics:
Understanding noise in motor power wiring
Shielding motor power cables
Grounding motor power cable shields
Applying ferrite sleeves
Splicing motor power cables
Handling excess cable
Installing long motor cables
The PWM Drive to motor power conductors are typically the most intense noise source in a system. Proper implementation of shielding, grounding, splicing, and treatment of excess cable is essential to reducing noise in your system. In the figure below:
The unshielded conductors radiate an electric noise field that
couples capacitively with adjacent wiring.
Stray capacitance at A & C cause ground currents to flow creating
a magnetic noise field that couples inductively with adjacent wiring.
Figure 8.1 Motor power cable noise
Drive
Heatsink
(connected
to chassis)
Panel
A
DC+
DC-
Radiation by E (electric) field
Unshielded motor cable
both conducts and
radiates noise
Publication GMC-RM001A-EN-P July 2001
Windings
C
Radiation by
H (magnetic)
field from this
Machine Structure
Motor
loop
8-2 Motor Wiring

Shielding Motor Power Cables

The benefits of using shielded cable are listed below (also refer to Figure 8.2).
The shield strongly attenuates the electric field (E field) noise.
Core to shield capacitance is added to the stray capacitance at A &
C increasing ground currents in the loop A, C, D, E, and F.
These currents generate a magnetic field (H field).
It is important to minimize the area of this loop as far as possible by routing the cable close to grounded metalwork.
Figure 8.2 Shielded motor power cable
Drive Motor
Heatsink
(connected to
chassis)
DC+
A
Cable shield
introduces more stray
capacitance to ground
Windings
C

Grounding Motor Power Cable Shields

Cable shield
grounded both
ends
F
Panel
DC-
E
D
Machine Structure
Observe the following guidelines when bonding the motor power cable shield to ground. Bond motor power cable shields:
At the motor frame.
To the panel at entry to the cabinet (optional).
To the drive (amplifier) chassis. If a connection point is not
provided, bond to the adjacent panel.
These connections must be made at the circular section, not by creating pigtails. Refer to the section Grounding Cable Shields in Appendix A for examples of grounding at the circular section.
Publication GMC-RM001A-EN-P July 2001
Motor Wiring 8-3

Applying Ferrite Sleeves

Splicing Motor Power Cables

A ferrite sleeve around the three power conductors as they leave the drive will help to reduce common-mode noise current. Take all three conductors two or three times through the core. If it runs hot reduce the number of turns.
Note: Not all drives allow the use of a ferrite sleeve around power
conductors. Refer to your manual for specific applications.
Avoid splicing motor power cables when ever possible. Ideally, motor power cables should run continuous between the drive and motor terminals. The most common reason for splicing is to incorporate high-flex cable for continuous flexing applications.
If necessary, the preferred method of splicing is to use a fully shielded bulkhead connector. Splicing can also be accomplished using a grounded and shielded junction box, as shown in the figure below.
Figure 8.3 Spliced cable using junction box
Observe the following guidelines when installing a junction box:
Shield drain wire must be spliced only to mating shield drain
wires and not grounded at the junction box.
Feedback shields must be passed through pin for pin.
Separate junction boxes for power and feedback are required.
Publication GMC-RM001A-EN-P July 2001
8-4 Motor Wiring

Handling Excess Cable

Observe the following guidelines when handling excess cable:
Do not coil excess cable of different types (i.e. motor power and
feedback) together. An efficient transformer is formed at HF.
Cable lengths should ideally be trimmed to fit the application.
If excess cable cannot be trimmed, it should be laid in an 'S' or
figure eight pattern (refer to the figure below).
Figure 8.4 Excess cable treatment
Preferred Methods
Poor Method

Installing Long Motor Cables

Motor cables are defined as long when the motor frame is not bonded close enough to the drive panel to be considered a single ground plane. To be considered a single ground plane, the parts must be connected by a surface which is no longer than ten times its width. Refer to the chapter High Frequency (HF) Bonding for methods of achieving a single ground plane.
Observe the following guidelines when installing long motor cables:
Bonding should be by the widest practical means. Wide cable tray
is effective when it is made of zinc plated steel and carefully bonded at the ends to control panel and motor frame.
Zinc plated sheet steel channel is also effective. The fact that the
width is folded into a U shape does not matter. A closing lid helps.
Solid steel conduit bonded at both ends is effective.
The spiral construction of flexible conduit makes it less attractive
for RF shielding because the spiral shape forms an inductor, even with partially shorted turns.
Publication GMC-RM001A-EN-P July 2001
High Speed Registration Inputs
Chapter
9

Chapter Objectives

Understanding Registration Inputs

This chapter describes how wiring, sensitive to electrical noise, benefits from proper noise reduction strategies. This chapter covers the following topics:
Understanding registration inputs
Noise reduction methods
Power supply wiring options
Signal noise filter options
Registration error
High speed registration inputs are potentially sensitive to noise by design. Typically, the specification states that the input responds within 1 microsecond of the signal going high, while in practice, the response is often even faster. Noise pulses of this duration are common in a typical drive system.
IMPORTANT
Coupling is usually capacitive if unshielded cable is run near noisy cables or if voltage differentials exist between the detector mounting and the equipment carrying the registration input. For these reasons, treat high speed registration input circuits with special care.
Publication GMC-RM001A-EN-P July 2001
9-2 High Speed Registration Inputs

Noise Reduction Methods

This section provides installation guidelines for reducing noise coupling into high speed registration inputs.

Wiring

Follow these guidelines to reduce noise coupling in wiring:
Always use shielded cable.
Connect shields at both ends and at the circular section.
Always run the cable in a clean zone.
Segregate the cable as far as practical from dirty and (especially)
very-dirty wiring.
Always make cable runs as short as possible.

Power

Follow these guidelines to reduce noise coupling in power supplies:
The power supply should be as clean as possible.
Use a filter if a switch-mode supply is used (refer to the chapter
Filtering Noise for more information).
Obtain +24V dc power from a clean supply and provide a filter
(refer to the chapter Filtering Noise for more information).
Always ground the common.

Shared Power Supply

Observe the following guidelines when sharing power between the registration input and other clean loads. Refer to Figure 9.1 for a shared power wiring diagram.
Provide a filter just prior to the registration input, even if the +24V
dc supply has a clean rating.
Mount the filter on a separate DIN rail, especially if a painted
panel is used.
Publication GMC-RM001A-EN-P July 2001
Figure 9.1 Shared registration power supply
High Speed Registration Inputs 9-3
Dirty Zone
Segregation
Clean Zone
Insulated mounting (preferred)
Detector
+
com
+24V
+24V com
Clean Load
Registration Input
In figure below a pigtail shield connection is used for the short cable run to the input and a clamp connection for the long run from the sensor. Refer to Appendix A for more information on grounding cable shields.
Figure 9.2 Registration power filter
From sensor
24V dc supply
To registration input
Publication GMC-RM001A-EN-P July 2001
9-4 High Speed Registration Inputs

Dedicated Power Supply

In the figure below, the registration input has a dedicated linear power supply.
Figure 9.3 Dedicated registration power supply
AC
Dirty Zone
Filter
24V dc Linear PSU
Insulated mounting (preferred)
+
Detector
com
Segregation
Clean Zone
Keep short or shield (ground shield on both ends)
Registration Input

Detection Device Mounting

A line driver or push-pull output is preferred, but not widely available except in specialized photoelectric sensors for mark detection.
Publication GMC-RM001A-EN-P July 2001
Ideally, the device body should be insulated from the machine structure and connected to the cable shield.
If the sensor cannot be insulated, ground the shield to the structure or sensor mounting.
High Speed Registration Inputs 9-5

Proximity Switches

Proximity switches are especially vulnerable in the off state since the signal line is disconnected at the switch, forming an efficient antenna. Observe the following guidelines when using proximity switches:
Insulate the mounting, if possible, and connect the body to the
cable shield.
Arrange to be normally on (i.e. hole-operated instead of
target-operated).
Register on the falling edge. With the line effectively disconnected
(off condition) stray capacitance causes the signal voltage to fall slowly. Even low levels of noise may then cause false triggering of inputs without hysteresis.
When the proximity switch is supplied with unshielded cable,
keep the unshielded length to a minimum by joining to shielded cable inside a shielded terminal box mounted close to the switch. Bond the terminal box to the sensor body.

Signal Noise Filter Options

Most registration inputs have a response time of 1 microsecond or less. In practice, such speed is rarely required. A simple, low-pass filter will slow the response time but will increase the noise immunity. Observe the following guidelines for best results in all configurations.
Keep the length of cable between filter and control to a minimum.
Bond the filter common securely to the controller chassis.
Publication GMC-RM001A-EN-P July 2001
9-6 High Speed Registration Inputs

Single Voltage Input (24V or 5V)

The figure below illustrates a typical registration filter circuit.
Figure 9.4 Registration filter circuit
R2
R1
C
R1 lowers the circuit impedance which improves noise immunity.
It also ensures that the signal voltage falls rapidly when the detector turns off. A lower R value is better, but is limited by the drive capability of the detector and the dissipation in the resistor. A 470 ohm resistor will dissipate 1.2W at 24V dc if on continuously, hence it should be rated at 2W.
The maximum value of R2 depends on the impedance of the
registration input (a volt drop to 10% of nominal is ideal). If input impedance is less than 4.7k ohms, then R2 will require a lower value (i.e., 10% of input impedance). If R2 is changed, use this
µ
formula for the on-delay: Delay (uS) = R2 (ohm) x C (
F). A value
of 470 ohms should be acceptable for most cases.
Capacitor C, together with R2, determines the on-delay. Capacitor
C, together with R1 + R2, determines the off-delay (as shown in the table below).
Publication GMC-RM001A-EN-P July 2001
R1
k ohm
0.47 0.47 4.7 2 4 14 23
0.47 0.47 10 5 9 30 29
0.47 0.47 22 10 21 65 36
0.47 0.47 47 22 44 139 43
0.47 0.47 100 47 94 295 49
0.47 0.47 220 100 207 649 56
R2
k ohm
C
nF
Delay On
µs
Delay Off
µs
Noise Attenuation factor
@ 1MHz
Noise Attenuation
@1MHz dB
High Speed Registration Inputs 9-7

Dual Voltage Inputs (24V or 5V)

Where the input is split into 5V and 24V, with inputs sharing the same common, it is important that the 5V input is not left floating. In the figure below, the 24V and 5V inputs are shorted together and fed at 5V.
Figure 9.5 Registration filter circuit (24V/5V)
+24V
From Detector
Common
+24V
R2
R1
C
+5V
To Registration Inputs
Common
The on-delay and off-delay times are shown in the table below.
R1
k ohmR2k ohm
0.100 0.390 220 22 2 14 23
0.100 0.390 220 22 5 30 29
0.100 0.390 220 22 10 65 36
0.100 0.390 220 22 22 139 43
0.100 0.390 470 47 47 295 49
C
nF
Delay On
µs
Delay Off
µs
Noise Attenuation factor
@ 1MHz
Noise Attenuation
@1MHz dB
0.100 0.390 1000 100 100 649 56
Publication GMC-RM001A-EN-P July 2001
9-8 High Speed Registration Inputs

Registration Error

The following charts help to estimate the error due to time delays. The detector delay may be much greater than the filter delay, so it is important to add the two together.
Figure 9.6 Registration Error vs. Delay (metric units)
10
1
0.1
Error mm
0.01
0.001
0.0001 10 20 50 100 200 500 1000
Li near V elocit y m/ min
1 uS 2 uS 5 uS 10 uS 20 uS 50 uS 100 uS
Figure 9.7 Registration Error vs. Delay (British units)
1
0.1
0.01
0.001
Error ins
0.0001
0.00001
0.000001 20 50 100 200 500 1000 2000
Linear Velocity ft/min
Publication GMC-RM001A-EN-P July 2001
1 uS 2 uS 5 uS 10 uS 20 uS 50 uS 100 uS
Figure 9.8
g
Registration Error vs. Delay (rotary units)
10
1
0.1
Error de
0.01
0.001
0.0001 20 50 100 200 500 1000 2000
High Speed Registration Inputs 9-9
Velocity RPM
1 uS 2 uS 5 uS 10 uS 20 uS 50 uS 100 uS

Error Compensation

If the registration signal delay is constant, it will have the effect of applying a position error proportional to velocity. In this case it may be possible to apply a software correction.

Software Solutions

It is possible to increase noise resistance with your software, especially if the problem is false triggering on the falling edge (which is usually much slower than the rising edge).
Try one of the following techniques before re-arming or looking for the next registration event.
Add wait-for-registration-input-low.
Add a timer after a registration event (to allow the switch signal to
go low).
Add wait-for-position-greater-than-x (to allow the switch signal to
go low).
Publication GMC-RM001A-EN-P July 2001
9-10 High Speed Registration Inputs
Publication GMC-RM001A-EN-P July 2001
Encoders
Chapter
10

Chapter Objectives

Understanding Encoders

This chapter describes bonding, segregating, shielding, and filtering techniques for use with encoders. This chapter covers the following topics:
Understanding encoders
Noise reduction methods
Power supply wiring options
Encoder input circuits are, by their nature, potentially sensitive to noise. The signal is typically a square wave of about 500kHz at maximum speed. In order to preserve a reasonable square pulse, the circuit must handle at least ten times higher frequencies. Unfortunately, a response of 5MHz is ideally suited to detecting the noise spikes in a drive system.
The internal encoder circuitry should be relatively immune if it is well designed but there is often a long cable run to the control input circuitry. Coupling is usually due to voltage differentials between the encoder mounting and the drive input.

Noise Reduction Methods

This section provides installation guidelines for reducing noise sources near encoder input circuits.

Driver Type

IMPORTANT
Driver type is generally dictated by the drive product but A quad B, differential, or line driver outputs are preferred.
Publication GMC-RM001A-EN-P July 2001
10-2 Encoders

Wiring

Always use shielded cable (manufacturers usually specify
appropriate cable).
Segregate the cable as far as practical from dirty and especially
very-dirty wiring.

Power

Always use the internal power supply when available.
Ensure the power supply has a clean rating (refer to Figure 10.1
and Figure 10.2 for linear and switch-mode power supply examples).
Use a filter if a switch-mode supply is used (refer to the chapter
Filtering Noise for more information).
Always ground the common.

Mounting

Insulate the encoder body from the machine structure and connect
it to the cable shield.
Note: This strategy also requires an insulated shaft coupling.
If the encoder cannot be insulated, connect the cable shield to
ground at the encoder case and drive chassis (or dedicated termination).
Publication GMC-RM001A-EN-P July 2001
Encoders 10-3

Power Supply Wiring Options

This section provides filtering options of power supply configurations for your encoder. For more information regarding filters, refer to the chapter Filtering Noise.
Figure 10.1 Linear power supply example
AC
Dirty Zone
Filter
5/12V dc Linear PSU
Insulated mounting and coupling preferred
Encoder
+
com
Segregation
Clean Zone
Keep short or shield (ground shield on both ends)
Encoder Input
Figure 10.2 Switch-mode power supply example
Filter
Dirty Zone
Clean Zone
Insulated mounting and coupling preferred
Encoder
5/12V dc PSU
Segregation
+
com
Keep short or shield
Encoder Input
Publication GMC-RM001A-EN-P July 2001
10-4 Encoders
Publication GMC-RM001A-EN-P July 2001
Chapter
11
Measuring Noise Reduction Effectiveness

Chapter Objectives

Understanding Noise Measurement

Methods for Measuring Noise

This chapter describes the equipment, methods, and various guidelines for measuring noise reduction effectiveness. This chapter covers the following topics:
Understanding noise measurement
Methods for measuring noise
Measuring noise
General guidelines for measuring noise
The ability to measure the effectiveness of noise reduction efforts and to determine if a system is within tolerance is important. However, it can be very difficult to obtain meaningful and repeatable results.
European EMC regulations are based on spectrum analysis (displaying amplitude vs. frequency). An RF spectrum analyzer is an expensive specialist tool, but necessary for pre-compliance testing if this is the requirement. Usually, a specialist EMC testing company is hired to perform such tests and the subject is beyond the scope of this document.
For troubleshooting drive systems, an oscilloscope (displaying amplitude vs. time) is more practical. You can determine the effectiveness of your noise reduction efforts by measuring the amplitude of the largest noise spikes at various points in the system.
There are three primary methods of measuring noise:
E-field sniffing (electric field)
H-field sniffing (magnetic field)
Direct voltage measurements
The first two methods (E-field and H-field sniffing) are best used to quickly check for intense noise sources, however direct voltage measurements along the system wiring is the most reliable indicator of noise performance. Conducted noise (via capacitance and system wiring) is the most common cause of functional problems.
Publication GMC-RM001A-EN-P July 2001
11-2 Measuring Noise Reduction Effectiveness
Professional probes are available in each category and would be mandatory for testing to EMC regulations but simple methods are sufficient for this purpose and are described below (refer to Appendix B for EMC suppliers).

Measuring Noise

This section describes the tools and methods used to measure noise.

Oscilloscope Specifications

When measuring noise, choose an oscilloscope with the following features:
Digital storage
At least 100 MHz sampling rate
Trigger that is easily set to a known voltage
Standard voltage probes
Differential-mode function (differential voltage probe is a good
alternative, but an additional cost)
Probe bandwidth of at least 20 MHz.
Battery power (optional)
Publication GMC-RM001A-EN-P July 2001

Oscilloscope Settings for Measuring Noise Peaks

Measuring noise peaks is often difficult since PWM induced peaks are short and typically vary in amplitude widely with time.
To set up your system and oscilloscope for measuring noise peaks:
1. Set the timebase to 1 microsecond per division.
2. Set the trigger so that peaks are captured.
3. Gradually increase the trigger level until triggering just stops.
4. Measure the maximum peak voltage displayed.
Measuring Noise Reduction Effectiveness 11-3

E-Field Sniffing Method

The E-field is the electric field capacitively coupled to the probe. To use the E-field sniffing method:
1. Attach a 150 mm (6 in.) length of stiff insulated wire to the probe
tip to form an antenna.
2. Remove the probe ground clip or attach it to the scope cable to
ensure it does not contact anything.
3. Hold the wire parallel to and touching potential victim wiring and
measure the voltage spikes.
Note: The signal observed is with respect to the scope ground. Check
the method by holding the wire against the panel. There should be little noise observed (refer to the section Ground Loops for more information).
Figure 11.1 Simple E-field probe
Publication GMC-RM001A-EN-P July 2001
11-4 Measuring Noise Reduction Effectiveness

H-Field Sniffing Method

The H-field is the magnetic field inductively coupled to the probe. Connect the scope probe ground clip to the probe tip forming a small loop. Hold the loop close to potential victim wiring. The loop antenna is sensitive to orientation, so test all three axes to determine the maximum reading at each location.
Figure 11.2 Simple H-field probe
Publication GMC-RM001A-EN-P July 2001

Direct Voltage Measurement Method

Direct voltage measurement methods exist for both AC and DC circuits. Each category are described in the paragraphs below.
Measuring DC Circuits
Direct voltage measurements with respect to a known good ground are made at chosen points in your DC circuit using a standard 1x scope probe. Set signal coupling to AC.
Measuring Noise Reduction Effectiveness 11-5
Measuring AC Circuits
Line voltage AC circuits are more difficult to measure since 50/60Hz AC waveforms will swamp the noise signals if a standard 10x or 100x scope probe is used.
Professional noise probes include a 150kHz high-pass filter to attenuate power frequency signals, but such a filter is easily built (refer to Figure 11.3).
Figure 11.3 High-pass filter circuit, 150kHz, 1 pole
Shielded enclosure
BNC socket from probe
ATTENTION
1000 pF
2 kV
1000
0.25 W
To avoid personal injury or damage to equipment, the capacitor must be rated at 2 kV or higher.
BNC plug to scope
!
With this filter installed between a 1x scope lead and the scope input, AC lines may be examined for noise. The 50/60 Hz waveform will be reduced to around 200 mV peak.
Note: Note that a 10x probe will attenuate far more than 10x in this
situation and should not be used.
Publication GMC-RM001A-EN-P July 2001
11-6 Measuring Noise Reduction Effectiveness
For BNC cases (as shown in Figure 11.4) refer to the following list of suppliers:
Pomona Electronics, Part # 3752
RS Components, Part # 189-0258
For more information on these and other suppliers, refer to Appendix B.
Figure 11.4 High-pass filter construction, 150 kHz, 1 pole (signal flow is left to right)
ATTENTION
To avoid personal injury or damage to equipment, always connect the probe ground clip to reference ground. Connecting the ground clip to line voltage may cause the scope chassis and controls to reach potentially lethal line voltage.
!

Grounding Your Probe (reference ground)

If the panel is plated and everything is bonded to it then the nearest point on the panel is the best reference ground point. With proper bonding the whole panel is a ground plane and the ideal reference. With a painted panel it is almost impossible to define a good ground because all the components are at different RF potentials. However, because a properly bonded panel (even one thats painted) maintains the same electrical potential at all points, it is still the best reference ground.
Publication GMC-RM001A-EN-P July 2001
Measuring Noise Reduction Effectiveness 11-7

Ground Loops

A line-powered oscilloscope may introduce noise via the ground loop formed by the separate line supply and the connection of the probe to system ground. Methods to reduce this type of noise are listed below.
Connect a braided strap between the scope chassis and the panel.
Most scopes have a ground terminal provided for this purpose.
Pass the scope lead through a ferrite sleeve several times.
Use a battery powered scope and place it inside the control
cabinet close to the panel.
Use a scope with differential inputs. Refer to the section
Differential Measurements for more information.
Extend the scope probe lead. Refer to Figure 11.6 for an
illustration.

Differential Measurements

Differential measurements eliminate ground loops and allow the scope to be grounded to its own supply ground. Two methods to reduce this type of noise are given below.
Differential Voltage Probes
Differential voltage probes, as shown in Figure 11.5, use only one scope input. Since they cancel common-mode voltage between the measured circuit and the scope common, ground loop problems are greatly reduced.
The main limitation is that of limited common-mode rejection. To avoid saturating the amplifier when measuring noise at line voltage the attenuation must be set to 1/100 or 1/200. This way the noise signal of interest is attenuated by the same amount. Increasing the scope sensitivity to compensate amplifies any internal probe or scope noise. Tips for using differential scope probes are listed below.
Connect both probe tips to the same point in the circuit under test.
No signal should be seen if the differential function is working correctly. Refer to the section Checking Your Method for Effectiveness for details. For best results, use the method as described.
Publication GMC-RM001A-EN-P July 2001
11-8 Measuring Noise Reduction Effectiveness
Use a high-pass filter between the probe and the scope input
when checking AC circuits. Refer to Figure 11.4 for filter construction details.
Note: Before installing the high-pass filter, check that the signal
Figure 11.5 Typical differential voltage probe
does not overload the voltage probe at the chosen division ratio.
Publication GMC-RM001A-EN-P July 2001
Differential Scope Inputs
Refer to these guidelines using an oscilloscope with two inputs in differential mode.
The trigger must also operate in differential mode. Check your
user manual for compatibility and instructions.
Use two matched high-pass filters (one for each probe) for AC line
checks as described above. Refer to Figure 11.4 for filter construction details.
Connect both probe tips to the same point in the circuit under test.
The residual noise signal should be much smaller than the measured value if the differential function is working. Refer to the section Checking Your Method for Effectiveness for details.
Avoid forming large loops with your probes by twisting the two
leads together as far as possible.
Measuring Noise Reduction Effectiveness 11-9

Scope Probe Lead Extension

Refer to these guidelines, and the figure below, when extending the scope probe.
Keep the extension cable as short as possible.
Make several turns through the ferrite sleeve.
Only use 1x probes (10x probes will attenuate HF signals by more
than ten times).
Figure 11.6 Extending the scope lead
Scope
BNC / BNC
extension
cable
BNC bulkhead
socket
Ferrite sleeve
Component mounting panel
1x Scope probe

Checking Your Method for Effectiveness

Connect the probe ground clip to the chosen ground reference and then connect the probe to the same point. It would be reasonable to expect zero signal, but it is common to see significant levels of noise. The main sources of such noise are given below.
Poor ground reference. Refer to the section Grounding Your Probe
(reference ground) for guidelines.
Scope power supply introducing noise. Refer to the section
Ground Loops for guidelines.
Local magnetic noise field. Refer to the section H-Field Sniffing
Method for details.
Note: It can be seen from this why extending the scope probe
ground wire is not recommended.
Without constant checking, it difficult to know when the observed noise waveform is real or a measurement artifact.
Publication GMC-RM001A-EN-P July 2001
11-10 Measuring Noise Reduction Effectiveness

Identifying the Noise Source

Two methods for identifying the source of a noise spike are listed below.
Disable each potential source in turn until the spike disappears.
Correlate the noise signal with PWM sources by displaying the
PWM waveform on a second channel. If the PWM source is the culprit, the noise signal will remain synchronized to the edges of the PWM waveform. Use a differential probe (phase to phase) or high-pass filter (phase to ground), connected to the suspect drive terminals, to display the PWM edges.

Intermittent Noise

If noise from mechanical contacts (e.g., a motor contactor) is suspected, the technique is a little different. Because of the variable nature of the peak amplitude, the best method is to operate the suspect device (for example) ten times in quick succession by overriding the control system. If this is not practical, monitor the device long enough to observe a number of operations. Progressively increase the trigger level as before.

General Guidelines for Measuring Noise

This section contains general guidelines for measuring noise. Tips on understanding acceptable noise levels, noise measurement methods that dont work, and system monitoring methods are discussed.

What are Acceptable Noise Levels?

No national or international standards for instantaneous peak voltage levels are known, but a very conservative approach would be to assume that a TTL gate may be closely coupled to a nominally clean circuit. Then, the noise immunity of a TTL gate (around 1.0V) becomes the critical level. This implies an allowable maximum of (for example) 500mV to allow for some margin of safety.
Publication GMC-RM001A-EN-P July 2001
Loading...