Rockwell Automation SA500 User Manual

Page 1
Distributed Power System SA500 DC Bus Supply
615055-2R (50 Amp) 615055-2T (50 Amp)
615055-2S (100 Amp) 615055-2V (100 Amp)
Instruction Manual
S-3017-1
Page 2
Throughout this manual, the following notes are used to alert you to safety considerations:
ATTENTION:Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
!
Important: Identifies information that is critical for successful application and understanding of the product. The thick black bar shown on the left margin of this paragraph will be used throughout this manual to signify
new or revised text or figures.
ATTENTION:Only qualified personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment.
!
Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION:DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power from the DC bus supply, wait five (5) minutes and then measure the voltage at the POS and NEG terminals of the DC bus supply and each Power Module to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION:The user is responsible for conforming with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
The information in this user’s manual is subject to change without notice.
Page 3
Chapter 1 Introduction
1.1 Related Publications........................................................................................1-2
1.2 Related Hardware............................................................................................ 1-2
Chapter 2 Mechanical/Electrical Description
2.1 Mechanical Description ...................................................................................2-1
2.1.1 LED Indicators....................................................................................... 2-2
2.1.2 Interface Connector (TB1)..................................................................... 2-2
2.2 Electrical Description .......................................................................................2-3
Chapter 3 Installation Guidelines
3.1 Selecting a DC Bus Supply .............................................................................3-2
3.2 Selecting an External Braking Resistor ........................................................... 3-3
3.3 Wiring .............................................................................................................. 3-4
3.4 Grounding........................................................................................................ 3-4
3.5 DC Bus Supply Initial Installation.....................................................................3-5
3.6 Replacing the DC Bus Supply ....................................................................... 3-10
Chapter 4 Diagnostics and Troubleshooting
4.1 DC Bus Supply Faults ..................................................................................... 4-1
4.1.1 The PHASE LOSS LED Is On............................................................... 4-1
4.1.2 The OVERTEMP LED Is On .................................................................4-1
4.1.3 The PSM READY LED Is Off ................................................................4-2
4.2 DC Bus Braking Fuse Is Blown ....................................................................... 4-2
C
ONTENTS
Appendix A Technical Specifications...........................................................................................A-1
Appendix B Block Diagram .................................................... ...... ....... ...... ....... ...... ....... ...... ....... ..B -1
Appendix C Motor Current Specifications ....................................................................................C-1
Appendix D Compliance with Electromagnetic Compatibility Standards......................................D-1
Index ........................................................................................................................... Index-1
Table of Contents
I
Page 4
II
SA500 DC Bus Supply
Page 5
List of Figures
Figure 2.1 – SA500 DC Bus Supply Faceplate......................................................... 2-1
Figure 2.2 – Circuitry of Terminals 1 and 2 of Interface Connector TB1 ..................2-3
Figure 3.1 – SA500 DC Bus Supply Mounting Dimensions......................................3-6
Figure 3.2 – Jumper W1 ........................................................................................... 3-7
Figure 3.3 – SA500 DC Bus Supply Wiring .............................................................. 3-8
Figure 4.1 – DC Bus Braking Fuse........................................................................... 4-3
Table of Contents
III
Page 6
IV
SA500 DC Bus Supply
Page 7
List of Tables
Table 1.1 – SA500 DC Bus Supplies........................................................................1-1
Table 1.2 – SA500 Documentation (Binder S-3002) ................................................ 1-2
Table 2.1 – Faceplate LED Indicators ......................................................................2-2
Table 3.1 – SA500 DC Bus Supply Motoring Current
and Internal Power Dissipation Specifications...................................... 3-2
Table 3.2 – Typical Braking Resistor Continuous Duty Power Dissipation...............3-4
Table 3.3 – Short Circuit Protection..........................................................................3-9
Table 3.4 – Minimum/Maximum Input Wire Sizes .................................................... 3-9
Table 3.5 – Internal Braking Resistor Specifications ................................................3-9
Table of Contents
V
Page 8
VI
SA500 DC Bus Supply
Page 9
C
HAPTER
1
Introduction
Distributed Power System (DPS) SA500 DC Bus Supplies rectify three-phase AC input voltage and provide constant DC voltage to the SA500 AC Power Modules. The DC bus supplies also contain circuits that permit regeneration from the SA500 AC Power Modules during motor deceleration or overhauling.
The main circuit, which supplies motoring current, consists of a full-wave bridge made from three SCRs in the upper legs and three diodes in the lower legs. The SCRs are gradually phased on to provide pre-charging and are fully turned on during normal operation.
The regenerative circuit consists of a transistor and a resistor in series across the DC bus. It is switched on when the bus voltage is higher than the AC line feeding the bridge and turned off when the bus voltage has dropped to an acceptable level.
The DC bus supplies require no programming or user tuning. These are self-contained units that provide full regulation and diagnostic capabilities.
The four DC bus supply models are listed in table 1.1.
Table 1.1 – SA500 DC Bus Supplies
Output Amps
Model Number
615055-2R 50 A DC Bus Supply with internal braking resistor 615055-2T 50 A DC Bus Supply with user-supplied, external
615055-2S 100 A DC Bus Supply with internal braking
615055-2V 100 A DC Bus Supply with internal braking
Input power for the bus supplies may be either isolated or non-isolated three-phase 230 VAC. Output power from the bus supplies is nominally 325 VDC with 230 VAC input power. A single Bus Supply can power up to six SA500 AC Power Modules. Refer to section 3.1 for more information on selecting a bus supply .
Note that throughout this manual references to a “bus supply” apply to all four bus supplies unless stated otherwise.
(DC) Description
braking resistor(s)
resistor(s)
resistor(s)
Introduction
1-1
Page 10
1.1 Related Publications
This instruction manual provides a description of the SA500 DC bus supply hardware. Installation and troubleshooting guidelines are also provided. Note that this instruction manual does not describe specific applications of the standard hardware or software.
For more information, refer to the instruction manuals contained in the SA500 drive binder, S-3002, as listed in table 1.2. It is assumed that the user is familiar with the manuals in S-3002 before installing, operating, or performing maintenance upon this equipment. Refer to these instruction manuals as needed.
:
Table 1.2 – SA500 Documentation (Binder S-3002)
Document Document Part Number
DPS Overview S-3005 Universal Drive Controller Module S-3007 Fiber Optic Cabling S-3009 SA500 DC Bus Supply S-3017 SA500 AC Power Modules S-3018 SA500 Diagnostics, Troubleshooting, & Start-Up
Guidelines SA500 Information Guide S-3024 SA500 Drive Configuration & Programming S-3044
S-3022
Additional information about using the SA500 Bus Supply is found in the instruction manuals, prints, and other documents shipped with each drive system. Always consult the prints shipped with the drive system for specific mounting and connecting information about your drive.
1.2 Related Hardware
Bus connection wires are normally provided with engineered drive systems. These wires connect the DC Bus Supplies to the SA500 AC Power Modules and are required for proper operation. Substitute cables should not be used.
1-2
SA500 DC Bus Supply
Page 11
Mechanical/Electrical Description
PHASE LOSS
OVER TEMP
DISABLED
PSM READY
TB1
LED Indicators
Interface Connector (TB1)
1/4 Turn Cover Fasteners
This chapter describes the DC bus supply’s faceplate and internal electronics.
2.1 Mechanical De scription
The DC bus supply consists of a phase-controlled SCR bridge, a DC bus regulator, DC bus capacitors, and cooling fan(s). The components are housed in a sheet metal enclosure.
The regulator circuit board assembly contains the LEDs and interface connector (TB1) which are visible on the bus supply’s faceplate. On-board SCR and pre-charge circuitry generate the DC bus voltage. On bus supply models 615055-2R and 615055-2S, the braking resistor(s) used to control the DC bus voltage during regeneration are included. On bus supply models 615055-2T and 615055-2V, the braking resistors must be added externally.
The faceplate cover of the DC bus supply is shown in figure 2.1. The cover is attached to the DC bus supply’s chassis by the two square 1/4-turn fasteners shown.
C
HAPTER
2
Mechanical/Electrical Description
Figure 2.1 – SA500 DC Bus Supply Faceplate
2-1
Page 12
2.1.1 LED Indicators
The four LEDs visible through the faceplate provide diagnostics information about the DC bus supply. See table 2.1.
:
7DEOH  ¤ )DFHSODWH /(' ,QGLFDWRUV
LED Name LED Color Description
PHASE LOSS Red Off: OK (normal)
OVERTEMP Red Off: OK (normal)
DISABLED Red Off: The bus supply has AC input power applied
PSM READY Green Off: No DC bus voltage
2.1.2 Interface Connector (TB1)
Terminals 1 and 2 or interface connector TB1 are used to indicate an overtemperature fault detected by the internal protective circuitry of the DC bus supply. See figure 2.2. The following signals are present on the terminals.
ON: Loss of one phase or more of the incoming
AC power
ON: The bus supply has overheated
and is enabled (normal)
ON: DC bus supply is disabled (check jumper
W1, see section 2.1.1)
ON: DC bus voltage is present (normal)
Terminal 1: – status signal
Terminal 2: + status signal
Together these terminals provide an output signal from a normally-open relay rated 24 VDC @ 0.4A, resistive load, 25° C (77° F). This signal can be monitored in an AutoMax rack through a 24V DC input module.
When the bus supply is not powered up, the relay’s contacts are open.
When the bus supply is powered up and no overtemperature fault exists, the relay’s contacts are closed.
When the bus supply is powered up and an overtemperature fault does exist, the relay’s contacts are open.
ATTENTION:DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power from the
!
If an overtemperature fault exists, the pre-charge is disabled. However, it is possible the DC bus capacitors may not discharge due to a component failure. The user should disconnect AC input power and verify that the DC bus capacitors are discharged before touching any internal components. See section 3.6.
DC bus supply, w ait five (5) minutes and then measure the voltage at the POS and NEG terminals of the DC bus supply and each Power Module to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.
2-2
SA500 DC Bus Supply
Page 13
SAMPLE EXTERNAL CONNECTIONS
INTERFACE CONNECTOR TB1
COM
1
+V
2
COM
1
+V
2
Figure 2.2 – Circuitry of Terminals 1 and 2 of Interface Connector TB1
1
2
3
4
STATUS-
STATUS+
Not Supported
Do Not Use
Not Supported
Do Not Use
Terminals 3 and 4 of interface connector TB1 are not supported at this time and must not be used.
Note that jumper W1, which is visible only when the cover is removed, must be set to position B (factory setting) for the bus supply to operate correctly. See figure 3.2 in chapter 3. With the jumper in position B, the bus supply will be on (enabled) whenever the correct three-phase AC input voltage is present.
2.2 Electrical Description
The bus supply rectifies the incoming 230 VAC and charges the DC bus capacitors using “soft charge” circuitry to reduce the inrush currents. Braking transistor circuitry is included to automatically connect a braking resistor across the DC bus whenever the motor load is regenerative and the DC bus voltage rises above the threshold level (1.47 x RMS line voltage + 5V).
Bus supply models 615055-2R and 615055-2S have internal braking resistors. Bus supply models 615055-2T and 615055-2V require external, user-supplied braking resistors. Refer to section 3.2 for more information on selecting braking resistors.
Mechanical/Electrical Description
2-3
Page 14
2-4
SA500 DC Bus Supply
Page 15
C
HAPTER
3
Installation Guidelines
This chapter provides guidelines for installing and replacing the SA500 DC bus supply . Instructions are included describing how to select a bus supply based on the bus supply’s current rating and the combined current draw of the motors attached to the bus supply through the SA500 AC Power Modules. For those installations where greater regenerative power dissipation requires the use of a bus supply with external braking resistors, a procedure is provided to assist in the selection of the proper braking resistors. Refer to the wiring diagrams supplied with your system for specific installation information.
ATTENTION:Only qualified personnel familiar with the construction and operation of this equipment and the hazards involved should install,
!
adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION:DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power from the DC bus supply, w ait five (5) minutes and then measure the voltage at the POS and NEG terminals of the DC bus supply and each Power Module to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION:Ungrounded equipment presents a shock hazard. If your drive cabinet is mounted such that the cabinet is not grounded, a ground wire must be connected to the cabinet for personnel safety. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION:The user is responsible for conforming with all applicable local, national, and international codes. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
ATTENTION:Equipment must be connected to a power source for which it was designed. Verify that the available input is 230 VAC. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
Installation Guidelines
3-1
Page 16
3.1 Selecting a DC Bus Supply
The number of SA500 AC Power Modules that a single DC bus supply can power depends upon the bus supply’s current rating and the combined current draw of the attached motors.
Use the following procedure to select a bus supply based on motor current values. Refer to Appendix C for motor current information on Industrial Brushless, Brushless Servo, and Induction motors.
Step 1. Add together the continuous Idc currents of all the motors to be powered
from the bus supply. See Appendix C.
Step 2. If all of the motors can accelerate, decelerate, or overhaul (draw maximum
current) at the same time, add together the maximum Idc currents of the motors. See Appendix C.
If only some of the motors can accelerate, decelerate, or overhaul at the same time, add their maximum Idc currents to the continuous Idc currents of the other motors to obtain a total maximum Idc current.
Step 3. Select the DC bus supply based on both Idc continuous current and Idc
maximum current. See table 3.1 for bus supply ratings. Note that regardless of the total current drawn by the motors, the maximum
number of SA500 AC Power Modules that can be powered from a single DC bus supply is six.
If the motors are to be operated in the regenerative mode, the applications’s regenerative power dissipation requirements should be evaluated. The power dissipatio n ca pa b il it i es of t he bus supplies wi th i nt e rnal b r ak in g r es is t ors are shown in table 3.1. Refer to table 3.5 for the resistance values of the internal braking resistor(s).
Table 3.1 – SA500 DC Bus Supply Motoring Current and Internal Power Dissipation Specifications
Output Rating
Maximum
Current
(Idc) RMS
1
DC Bus Supply
615055-2R
Output Rating
Continuous
Current
(Idc) RMS
50A 150A
615055-2S 615055-2T
100A 450A
615055-2V
1. 10 second overload
2. Maximum continuous braking power = (continuous fuse current)
3. Maximum 0.5 second overload braking power = (maximum fuse current)2 x R, where maximum fuse current = 2 second fuse melting current.
4. V
x 1.47 + 5 volts, where VLL is 230VAC nominal.
LL
5. Snubber Fuse Limited
6. Resistor Limited
2
Internal Braking Resistor
Maximum Power Dissipation
0.5 Second3
Continuous
414W
1200W
x R, where continuous fuse current = 0.9 x fuse rating.
2
5
6
Overload
1568W
4624W
5
6
Turn-On
Voltage
343V
343V
4
If the application’s requirements exceed these values, refer to section 3.2 for information on selecting external braking resistors.
3-2
SA500 DC Bus Supply
Page 17
3.2 Selecting an External Braking Resistor
R=
(Turn-on Voltage)
2
Torque x RPM
x
6.33 ohms
τ
= Max Duty Cycle =
(0.9 x Fuse Rating)
(Turn-on Voltage)
seconds
2
x R
2
2
Max Continuous Braking Power
watts
=
(0.9 x Fuse Rating)
2
x R
DC bus supplies with external braking resistors (615055-2T or 615055-2V) allow for greater power dissipation during motor regeneration. Perform the following steps to determine the required external braking resistor specifications.
Step 1. Using the stopping time specifications, calculate the required braking torque:
Torque = J x Alpha
(lb-ft) = (N-m) =
(lb-ft-sec
(kg-meter
2
x
)
2
)
(radians/second
x
(radians/second
J is the combined total inertia of the motor and the machine (which can be either calculated or measured). Alpha is the rate of deceleration of the motor’s shaft.
Step 2. Calculate the resistance value of the external braking resistor.
2
)
2
)
Turn-on Voltage = 1.47 x V
+ 5 volts, where VLL is the RMS input
LL
line-to-line voltage. Turn-on voltage is 343 VDC for a nominal 230 VAC. Torque is in lb-ft. 1 lb-ft = 0.7376 N-m. Note that the recommended ranges of resistance values are as follows:
• 50 A DC bus supply: 8 (minimum) to 55 ohms
• 100 A DC bus supply: 4 (minimum) to 15 ohms A lower resistor value provides higher short-duration regenerative currents
but results in a reduction of the continuous power rating. A higher resistor value provides for maximum continuous power operation. Over the recommended ranges of resistance values, operation is balanced between short duration overload current conditions and continuous power conditions.
Step 3. Determine the continuous power dissipation specifications of the external
braking resistor. The continuous power rating is limited by both the fuse rating (0.9 x fuse
rating) and the resistor value. The regenerative duty cycle is limited by the internal fuse. The lower value resistors will have higher peak currents and therefore the duty cycle must be limited to prevent nuisance fuse openings.
The following equations are used to determine the typical braking resistor specifications for each power supply, as shown in table 3.2.
Installation Guidelines
3-3
Page 18
Table 3.2 – Typical Braking Resistor Continuous Duty Power Dissipation
Resistor Power Dissipation =
x (0.5 Second Overload Braking Power) watt-secs
1
2
2
50 Amp Supply 8 Amp Fuse 100 Amp Supply 30 Amp Fuse
R
(ohms)
8 0.03 414 4 0.10 2916 16 0.11 829 6 0.22 4374 24 0.25 1244 8 0.40 5832 32 0.45 1658 10 0.62 7290 40 0.71 2073 12 0.89 8748
1
47.6 48 Continuous 2451 14 Continuous 8403 55 Continuous 2139 15 Continuous 7843
1. Maximum continuous power resistor value
For intermittent duty the external braking resistor power dissipation is specified by:
0.5 Second Overload Braking Power = (Maximum Fuse Current)
Maximum Fuse Current is the level of current that will cause the braking fuse to melt in 2 seconds, as indicated on the KLK fuse rating curves. Use 14 amps for an 8 amp fuse, and 85 amps (maximum regenerative current with 4 ohms) for a 30 amp fuse.
τ
(seconds)
1.0/Cont 2468
Max CBP
(watts)
R
(ohms)
1
12.7
/
2
τ
(seconds)
1.0/Cont 9258
Max CBP
(watts)
x R watts
Note:
Instantaneous Maximum Braking Power =
3.3 Wiring
To reduce the possibility of electrical noise interfering with the proper operation of the drive system, exercise care when installing the wiring between the system and external devices. For detailed recommendations, refer to IEEE 518.
3.4 Grounding
ATTENTION:
drive cabinet is mounted such that the cabinet is not grounded, a ground
!
The grounding stud (GND) on the DC bus supply must be connected externally to earth ground (PE) as shown in figure 3.3 on page 3-8 and checked with an ohmmeter before power is applied. Use a star washer (toothed lock washer) on the grounding stud to ensure continuity.
wire must be connected to the cabinet for personnel safety. Failure to observe this precaution could result in severe bodily injury or loss of life.
(Maximum DC Bus Voltage)
R
Ungrounded equipment presents a shock hazard. If your
watts
3-4
SA500 DC Bus Supply
Page 19
3.5 DC Bus Supply Initial Installation
The following procedure is intended to be only a guide to assist you in installing the DC bus supply. Refer to the wiring diagrams supplied with you system for more specific information.
Step 1. Mount the DC bus supply. DC bus supplies are designed to be mounted on a
flat surface using M5 or #10 screws. The holes in the top flange are key-hole shaped and the lower holes are U-shaped to facilitate mounting. The bus supply should be mounted in a location with good air flow and in close proximity to the SA500 AC Power Modules (3 mm (1/8 in) to 13 mm (1/2 in) spacing between units). See figure 3.1. Provide at least 85 mm (3.3 in) of clearance above and below the bus supply for ventilation.
Ambient air around the bus supply must be clean, dry, and free of flammable or combustible vapors, chemical fumes, oil vapor, steam, and excessive moisture and dirt.
The highest current AC Power Module should be placed closest to the bus supply. Note that the SA500 AC Power Modules (6 maximum) should be evenly distributed on each side of the bus supply. If two Power Modules are being used, one should be wired from the left of the bus supply and one should be wired from the right. If four Power Modules are being used, two should be wired from the left of the bus supply and two from the right. If an odd number of Power Modules is being used, they should be distributed as evenly as possible on each side of the bus supply. This method of Power Module placement minimizes wire length which reduces wire inductance. The continuous DC bus current for all SA500 AC Power Modules connected to the bus supply is limited to either 50A or 100A.
Installation Guidelines
3-5
Page 20
(17.5")
445 mm
(9.5")
243 mm
Side View
2
Air Exhaust
(16.88")
12 mm
(0.47")
7 mm
(0.27)
429 mm
411 mm
(16.18")
A
SA500
SA500
Air Intake
A
Minimum Recommended
Panel Space Requirement
Module
Module
AC Power AC Power
3-6
1/4 Turn Cover
Fasteners
SA500
Supply
DC Bus
Front View
r
#10 (M5)
Mounting Screws
SA500
Module
AC Powe
B B B B C
35 mm
(1.38")
C
35 mm
(1.38")
SA500
AC Power
Module
Figure 3.1 – SA500 DC Bus Supply Mounting Dimensions
1
(4.5")
Typical
115 mm
Mounting Screw Head Diameter is 10 mm (0.39") maximum
Covers are removed by pulling them straight out as indicated by arrow
A = 102 mm (4") minimum
B = 118 mm (4.62") minimum, 127 mm (5") maximum
1
C = 13 mm (0.5") minimum
2
SA500 DC Bus Supply
Page 21
Step 2. Rotate the quarter-turn cover fasteners and remove the bus supply’s front
1
4
A B
Jumper W1
DC Bus Supply
PC Board
(Component Side)
LEDs
A B
1 2 3 4
Fault Contact Output Not Supported}
}
Interface Connector (TB1)
cover. Check the bus supply’s nameplate to ensure that the bus supply has the proper power rating (50A or 100A).
Examine jumper W1 on the printed circuit board (see figure 3.2). The jumper must be set to position B for the bus supply to operate properly. This is the factory setting. When the jumper is set to position B, the bus supply will be enabled whenever the correct three-phase input voltage is present.
Installation Guidelines
Figure 3.2 – Jumper W1
Step 3. Connect the input power wiring per the NEC and local wiring codes as shown
in figure 3.3. A fuse disconnecting switch must be placed in the AC line that feeds the DC bus supply. Select the proper value of short circuit protection fuse from table 3.3. Minimum/maximum input wire sizes are given in table
3.4. The phasing of the three-phase input lines (L1, L2, L3) is not critical. The proper DC bus polarity, however, must be observed. Be sure to connect the grounding stud (GND) to earth ground (PE) as shown in figure 3.3.
Wires for connecting the DC bus and the Power Module are normally provided with engineered systems. Do not substitute other wires for those supplied. The wires are 225 mm (8.8 in) in length.
Do not over-tighten the nuts on the DC bus terminals. Use a nut-driver only and limit the torque to 4.0 Nm (36 lb-in).
ATTENTION:Fuse disconnecting switches are not designed to be opened under load. Turn off the drive before opening the switch. Failure to observe this precaution could result in damage to, or destruction of,
!
the equipment.
3-7
Page 22
SA500 AC
SA500 AC
UVW
Power Module
NEG GND
Motor
Connecting Lugs
M6 Nut
M6 Terminal Post
POS
GND
round Terminals
G
UVW
Power Module
NEG
POS
GND
L3
47
48
External
Braking Resistor
SA500
SA500 AC
Power Module
L1 L2
Supply
DC Bus
NEG
POS
GND
NEG
POS
VW U
Flat Washers
Lock Washers
Fuse
Fuse
Fuse
Drive or Power
Supply Bus Bar
Positive and Negative Terminals
Fuse Disconnecting Switch
SA500 AC
GND
UVW
Voltage
AC Input
Power Module
NEG
POS
(3-Phase)
Short Circuit Capacity
PE
5000 Amps o r Less
M6 Nut
M6 Terminal Post
Connecting Lugs
Terminal Post Base
3-8
Red Wire*
Black Wire*
Green Wire*
To Grounding Rod
*Wires are 225 mm (8.8") long
or Building Steel
Figure 3.3 – SA500 DC Bus Supply Wiring
SA500 DC Bus Supply
Page 23
7DEOH  ¤ 6KRUW &LUFXLW 3URWHFWLRQ
DC Bus Supply
50A (615055-2R) (615055-2T)
100A (615055-2S) (615055-2V)
Maximum Input Fuse
UL Class
RK5 250 VAC
40 Amp
90 Amp
Table 3.4 – Minimum/Maximum Input Wire Sizes
DC Bus Supply
Current Rating Terminals
50A
100A
L1, L2, L3 L1, L2, L3
Minimum/Maximum Wire Sizes
(mm2 / gauge)
4.8 to 21.6 mm
13.6 to 35 mm
2
(10 - 4 AWG)
2
(6 - 2AWG)
Step 4. DC bus supplies 615055-2R and 615055-2S are supplied with built-in braking
resistors to dissipate power that is regenerated by the motor. The 50A bus supply has one braking resistor, while the 100A bus supply has two. See table 3.5. for internal resistor specifications.
Table 3.5 – Internal Braking Resistor Specifications
Resistor Specifications 50A Bus Supply 100A Bus Supply
Trigger Voltage 1.47 RMS input line voltage (V
) + 5 volts
LL
Ohms 8 4 Ω Watts 600 W 1200 W
Continuous
Braking Power
0.5 Second Overload Braking Power
414 W 1200 W
1568 W 4624 W
Installation Guidelines
Instantaneous Overload
Braking Power
19,500 W 39,000 W
If the motor is to be operated in the regenerative mode, the application’s regenerative power dissipation requirements should be evaluated. A DC bus supply using external braking resistors (615055-2T or 615055-2V) may be needed to increase the bus supply’s power dissipation capacity. To calculate the proper resistor values, refer to the procedures in section 3.2.
3-9
Page 24
If external resistors are to be used, connect the wires from the resistors to the terminal block at the top of the bus supply. A notch in the front cover allows the wires to be routed from the terminal block even when the front cover is installed.
Step 5. Apply power to the input wiring and check that the voltages are within
operating parameters. Voltage specifications are given in Appendix A.
Step 6. Re-attach the bus supply’s front cover.
3.6 Replacing the DC Bus Supply
Use the following procedure to replace a DC bus supply: Step 1. Turn off and lock out AC input power to the bus supply.
ATTENTION:
power has been disconnected. After disconnecting input power from the
!
Step 2. Wait five minutes to allow the DC bus voltage to dissipate. Step 3. Measure the DC bus potential across the POS and NEG terminals of the DC
Step 4. Disconnect the input power wires from the L1, L2, and L3 terminals. Step 5. Disconnect the DC bus wires from the POS, NEG, and GND terminals. Step 6. Disconnect the external braking resistor (if used) from the terminal block at
Step 7. Remove the screws that attach the bus supply to its mounting surface.
DC bus supply, w ait five (5) minutes and then measure the voltage at the POS and NEG terminals of the DC bus supply and each Power Module to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.
bus supply and at each Power Module before working on the unit. When the DC bus potential is down to less than 5V, touch a 50 Ω, 50 W or
larger resistor across the POS and NEG terminals for 20 seconds to allow any remaining DC bus voltage to dissipate.
Remove the resistor and re-measure the DC bus potential to ensure the DC bus capacitors are completely discharged before touching any internal components.
the top of the DC bus supply.
DC bus capacitors retain hazardous voltages after input
3-10
Step 8. Install the replacement bus supply by following steps 3 through 7 in reverse
order.
SA500 DC Bus Supply
Page 25
C
HAPTER
4
Diagnostics and Troubleshooting
ATTENTION:
power has been disconnected. After disconnecting input power from the
!
Use the procedures described in the following section to diagnose and troubleshoot DC bus supply faults. If the problem cannot be corrected by following these instructions, the DC bus supply is not user-serviceable.
DC bus supply, w ait five (5) minutes and then measure the voltage at the POS and NEG terminals of the DC bus supply and each Power Module to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.
DC bus capacitors retain hazardous voltages after input
4.1 DC Bus Supply Faults
Bus supply faults are indicated by the LEDs visible on the faceplate.
4.1.1 The PHASE LOSS LED Is On
Problem: At least one phase of the three-phase AC input power is missing. Use the following procedure to correct the problem:
Step 1. Cycle the AC input power to the bus supply. If the PHASE LOSS LED
remains on, proceed to step 2. Note that this LED may light when low AC line voltage is detected or when
line notching occurs. The LED will remain on until power is cycled.
Step 2. Using a voltmeter, verify that AC input power is reaching the DC bus supply
Step 3. If AC power is not reaching the bus supply, check the incoming AC power
4.1.2 The OVERTEMP LED Is On
Problem: The bus supply has overheated and shut down. Allow the bus supply to cool down. Then cycle power and try running it again. The
LED will remain on until power is cycled. Typically, if the ambient temperature is above the rated value, fan failure or air flow blockage may be the cause. If the bus supply overheats repeatedly, it may be overloaded and should be replaced with a larger unit.
Diagnostics and Troubleshooting
input terminals (L1, L2, L3).
lines and fuses. If AC power is reaching the bus supply and the PHASE LOSS LED remains
on, replace the DC bus supply.
4-1
Page 26
4.1.3 The PSM READY LED Is Off
Problem: The DC bus voltage is different from what is expected. During normal operation, the PSM READY LED is on when AC power is applied and
there are no bus supply faults. If this LED turns off, use the following procedure to isolate the problem:
Step 1. Using a voltmeter, verify that the DC bus supply is receiving the correct AC
input voltage (terminals L1, L2, L3).
Step 2. If the bus supply is not receiving the correct input voltage, check the AC input
power lines. If the bus supply is receiving the correct voltage, proceed to step 3.
Step 3. Check the other fault LEDs. the PHASE LOSS and OVERTEMP LEDs should
be off. If either LED is on, refer to the appropriate troubleshooting section in this chapter.
Step 4. If the PSM READY LED remains off, replace the DC bus supply.
4.2 DC Bus Braking Fuse Is Blown
Problem: SA500 AC Power Module regeneration does not work properly (i.e., braking is slower than expected) and the Power Module experiences frequent DC bus overvoltage faults.
These problems may be caused by a blown braking fuse. Use the following procedure to determine if the braking fuse is blown:
Step 1. Turn off and lock out AC input power to the bus supply.
ATTENTION:
power has been disconnected. After disconnecting input power from the
!
Step 2. Wait five minutes to allow the DC bus voltage to dissipate. Step 3. Measure the DC bus potential across the POS and NEG terminals of the DC
Step 4. Rotate the quarter-turn cover fasteners to the open position and remove the
DC bus supply, w ait five (5) minutes and then measure the voltage at the POS and NEG terminals of the DC bus supply and each Power Module to ensure the DC bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in severe bodily injury or loss of life.
bus supply and each Power Module before working on the unit. When the DC bus potential is down to less than 5V, touch a 50 Ω, 50 W or
larger resistor across the POS and NEG terminals for 20 seconds to allow any remaining DC bus voltage to dissipate.
Remove the resistor and re-measure the DC bus potential to ensure the DC bus capacitors are completely discharged before touching any internal components.
bus supply’s front cover.
DC bus capacitors retain hazardous voltages after input
4-2
Step 5. Remove the fuse (see figure 4.1). Use an ohmmeter to check if the fuse is
SA500 DC Bus Supply
Page 27
open. If the fuse is blown, install a replacement that has the proper ratings.
Replaceable DC Bus Braking Fuse (with cover removed)
Fuse specifications are provided in Appendix A.
Step 6. Re-install the bus supply’s front cover. Rotate the quarter-turn cover screws
to the closed position.
Step 7. Re-apply AC input power and test the bus supply for proper operation.
If the DC bus overvoltage condition continues to occur, check the braking resistor to see if it is open or shorted.
Diagnostics and Troubleshooting
Figure 4.1 – DC Bus Braking Fuse
4-3
Page 28
4-4
SA500 DC Bus Supply
Page 29
A
PPENDIX
Technical Specifications
Ambient Conditions
Operating Temperature: 0 to 50° C (32 to 122° F)
Relative Humidity: 5 to 95% (non-condensing)
Dimensions
Height: 445 mm (17.5 in)
Width: 115 mm (4.5 in)
Depth: 250 mm (9.8 in)
Weight: 11.9 kg (26.2 lbs)
Input Voltage
230 VAC RMS (+15%, -5%) three-phase
5000 Amps Maximum Symmetrical Available Fault Current Source
A
Output Voltage
310 to 375 VDC
Continuous Output DC Amperes
50A units: 50A
100A units: 100A
Maximum Output DC Amperes (10 Second Overload)
50A units: 150A
100A units: 450A
Internal Braking Resistor Continuous Power Dissipation
50A units: 414W
100A units: 1200W
Internal Braking Resistor 0.5 Second Overload Power Diss ipation
50A units: 1568W
100A units: 4624W
Technical Specifications
A-1
Page 30
Internal Braking Resistor Instantaneous Overload Power Dissipation
50A units: 19,500W
100A units: 39,000W
DC Bus Braking Fuse
DC Bus Supply (50A) with Internal Braking Resistor: Littelfuse KLK D8, Fast Acting, 600V, 8A or Bussman KLM-8
DC Bus Supply (50A) with External Braking Resistor: Littelfuse KLK D8, Fast Acting, 600V, 8A or Bussman KLM-8
DC Bus Supply (100A) with Internal Braking Resistor: Littelfuse KLK D20, Fast Acting, 600V, 20A or Bussman KLM-20
DC Bus Supply (100A) with External Braking Resistor: Littelfuse KLK D30, Fast Acting, 600V, 30A or Bussman KLM-30
Maximum Power Losses
50A units: 110W + intermittent watts from braking circuit
100A units: 240W + intermittent watts from braking circuit
1. Typical power losses are one-half of these values
1
A-2
SA500 DC Bus Supply
Page 31
A
PPENDIX
Block Diagram
B
230 VAC
Input
Voltage
DC-to-DC
Power Supply
Pre-charge
SCR
Driver
LEDs
Resistor
Voltage Braking
Feedback Transistor
Driver
Fuse
Resistor
DC Bus
Output
Voltage
to SA500 AC
Power Module
Block Diagram
B-1
Page 32
B-2
SA500 DC Bus Supply
Page 33
Motor Current Specifications
Table C.1 – Industrial Brushless Motors
A
PPENDIX
C
Max
Speed
Model No. HP
B14H3050 1 2000 TENV 3.3 4.2 6.5 8.2 B14H3060 2 2000 TENV 6.5 8.2 13.1 16.5 B18H3070 3 2000 TENV 9.8 12.4 19.6 24.7 B18H3080 4 2000 TENV 13.1 16.5 26.3 33.2 P21M0309 7.5 1750 TENV 24.0 30.3 48.0 60.5 P21M0310 10 1750 TENV 32.0 40.3 64.0 80.7 P21M0311 15 1750 TENV 48.0 60.2 96.0 121.0
1. Minimum bus supply: 615055-2R or 615055-2T. Output continuous current (Idc) = 50A.
2. Minimum bus supply: 615055-2S or 615055-2V. Output continuous current (Idc) = 100A.
Refer to the DPS SA500 Power Modules instruction manual (S-3018) for Iac current overload rating information (speed-torque charts).
Model No. HP
S2005-K-R 5.9 4000 TENV 3.0 3.8 6.5 8.2 S3007-N-R 7.6 3000 TENV 2.0 2.5 6.3 7.9 S3016-N-R 20 3000 TENV 5.7 7.2 14.3 18.0 S4030-P-R 30 3000 TENV 4.8 6.1 13.6 17.1 S4050-P-R 60 3000 TENV 9.6 12.1 30.4 38.3 S4075-R-R 90 2500 TENV 9.5 12.0 28.4 35.8 S6100-Q-R 100 2000 TENV 11.8 14.9 26.8 33.8 S6200-Q-R 200 2000 TENV 24.2 30.5 58.1 73.3 S6300-Q-R 320 2000 TENV 36.0 45.4 77.6 97.8 S8353-S-R 350 2000 TENV 32.5 41.0 57.6 72.6 S8500-S-R 480 2000 TENV 39.1 49.3 95.6 120.5
RPM Encl
Max
Speed
RPM Encl
Cont
Iac RMS
Amps
Table C.2 – Brushless Servo Motors
Cont Iac
RMS
Amps
Cont Idc Amps
(Bus Supply
Requirement)
Cont Idc Amps
(Bus Supply
Requirement)
Max Iac
RMS
Amps
Max Iac
RMS
Amps
Max Idc Amps
(Bus Supply
Requirement)
Max Idc Amps
(Bus Supply
Requirement)
Min DC
Bus
Supply
1 1 1 1 1 1 2
Min DC
Bus
Supply
1 1 1 1 1 1 1 1 1 1 1
1. Minimum bus supply: 615055-2R or 615055-2T. Output continuous current (Idc) = 50A.
Refer to the DPS SA500 Power Modules instruction manual (S-3018) for Iac current overload rating information (speed-torque charts). I/M S-3018 also contains horsepower ratings for the brushless servo motors.
Motor Current Specifications
C-1
Page 34
Table C.3 – Induction Motors
Model No. HP
Max
Speed
RPM Encl
Cont Iac
RMS
Amps
Cont Idc Amps
(Bus Supply
Requirement)
Max Iac
RMS
Amps
Max Idc Amps
(Bus Supply
Requirement)
P14A5810 1 1757 TENV 3.0 3.8 4.5 5.7 P14A5804 1.5 1756 TENV 4.4 5.5 6.6 8.3 P14A5813 2 1764 TENV 5.8 7.3 8.7 11.0 P18A6111 3 1758 TENV 9.0 11.3 13.5 17.0 P18A6113 5 1737 TENV 14.4 18.2 21.6 27.2
P21L0212 5 1781 TENV 15.3 19.3 23.0 28.9 P21L0213 5 1180 TENV 14.8 18.7 22.2 28.0 P21L0214 5 880 TENV 14.8 18.7 22.2 28.0 P21L0215 7.5 1780 TENV 21.5 27.1 32.3 40.7 P21L0216 7.5 1177 TENV 20.6 26.0 30.9 39.0 P21L0217 7.5 866 TEAO 21.8 27.5 32.7 41.2 P21L0218 10 1779 TENV 27.8 35.1 41.7 52.6 P21L0219 10 1171 TEAO 27.3 34.4 41.0 51.6 P21L0220 10 868 TEAO 28.0 35.3 42.0 53.0 P21L0221 15 1768 TEAO 42.0 53.0 63.0 79.4 P21L0222 15 1172 TEAO 42.0 53.0 63.0 79.4 P21L0223 15 872 TEAO 41.1 51.8 61.7 77.7
Min DC
Bus
Supply
1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2
1. Minimum bus supply: 615055-2R or 615055-2T. Output continuous current (Idc) = 50A.
2. Minimum bus supply: 615055-2S or 615055-2V. Output continuous current (Idc) = 100A.
Induction motor Iac current values are rated at 150% overload for 1 minute.
C-2
SA500 DC Bus Supply
Page 35
Compliance with Electromagnetic
D.1 Introduction
This appendix provides information on the SA500 DC Bus Supplies and AC Power Modules’ compliance with European Community electromagnetic compatibility (EMC) standards and covers the following:
requirements for standards compliance
guidelines on installing the equipment
instructions on how the drive must be wired.
The SA500 DC Bus Supplies and AC Power Modules listed on the Declaration of Conformity (DOC) (Ref: Drawing 422802-201) have been tested and are in compliance with the following standards when installed as described in this manual and amended herein:
A
PPENDIX
D
Compatibility Standards
EN55011 (1991) Limits and methods of measurement of radio disturbance characteristics of industrial, scientific, and medical (ISM) radio-frequency equipment.
EN50082-2 (1995) Electromagnetic Compatibility - Generic Immunity Standard Part 2: Industrial Environment
Note that the conformity of the SA500 DC Bus Supplies and AC Pow er Modules to the above standards does not guarantee that the entire installation will be in conformance.
For a copy of the Declaration of Conformity, contact your local Rockwell Automation sales office.
D.2 Compliance Requirements
In order for the SA500 DC Bus Supplies and AC Power Modules to conform to the standards listed in section D.1, the equipment must:
be accompanied by the DOC (Ref: Drawing 422802-201).
have a CE mark. This mark is found on the product.
be mounted inside a cabinet.
be powered through a EMI line filter.
be installed in accordance with the instructions in this appendix.
If these conditions are not met and CE conformity is desired, contact your local Rockwell Automation Drive Systems Sales Representative.
Compliance with Electromagnetic Compatibility Standards
D-1
Page 36
D.3 Installing the Equipment
The equipment must be mounted inside a steel cabinet. The cabinet door must be grounded to the main cabinet. Any accessory plates attached to the cabinet door must be grounded to the same point on the cabinet as the door. The cabinet must also have floor pans with the cutouts for cable entries kept to an absolute minimum.
The SA500 DC Bus Supplies and AC Power Modules and EMI Filter should be mounted to the panel in accordance with the installation instructions provided in chapter 3 of this manual.
D.4 Wiring Practices
This section describes how the SA500 drive must be wired to conform to the standards listed in section D.1. Figure D.1 shows an SA500 wiring example.
D.5 AC Input Power
A 110 Amp three-phase line filter (M/N 612421-2A) must be installed in the power lines. The leads between the filter and the DC Bus Supply should be as short as possible and must be routed away from the leads to the input of the filter. Both ground connections must be used and the ground leads should be kept as short as possible.(£ 6.0”). This filter may be mounted to a separate bracket and placed on edge to reduce the panel footprint so long as the bracket is properly grounded to the control panel.
A three-phase input power surge protector (M/N 600686-45A) must be installed on the 230 VAC lines at the line input to the EMI Filter. The leads on the surge protector should be kept as short as possible.
The 115 VAC source voltage used to power the digital I/O must be supplied through a 1 kV A control transformer (M/N 417155-V) with a MOV (M/N 411026-X) mounted across transformer terminals X1 and X2. The X2 terminal of the control transformer must also be grounded to the control panel.
D.6 Motor Output
The motor leads (three phases and ground) must be installed in conduit. The conduit should be terminated at the cabinet.
D.6.1 Grounding
The incoming 230 VAC three-phase power must be connected to the grounding stud on the DC Bus Supply.
The DC Bus Supply and AC Power Module must be grounded in accordance with the guidelines provided in section 3.4 of this manual. The ground lead from the motor must be connected to the AC Power Module and then connected to the DC Bus Supply via the jumper supplied with the AC Power Module.
D-2
SA500 DC Bus Supply
Page 37
D.6.2 Rail Ports
The two rail Rail Ports must not be used for CE applications. As an alternative, digital I/O can be configured using either the digital I/O on the Resolver and Drive I/O Module or the Allen-Bradley Remote I/O Interface Module (M/N 57C443) and Allen-Bradley I/O.
D.6.3 Resolver and Analog Input Wiring
Resolver cable M/N 417900-207CG is recommended. This specific cable was chosen per instruction manual D2-3115-2, (Installing, Operating, and Maintaining Engineered Drive Systems), as the only cable not required to be installed in conduit. Conduit is not required for CE purposes, but it may be required for a specific application.
Use shielded 2-conductor cable for analog input wiring. The shield drain wire is to be grounded to the cable terminal board and left open at the opposite end.
D.6.4 Digital I/O Wiring
The 115 V A C source voltage f or the digital I/O must be supplied from the secondary of the isolation transformer. When a main contactor is used, an RC suppressor (M/N 600686-33A or equivalent) must be installed across the coil contacts.
Compliance with Electromagnetic Compatibility Standards
D-3
Page 38
SA500 AC
SA500 AC
UVW
Power Module
NEG GND
Motor
Connecting Lugs
M6 Nut
M6 Terminal Post
POS
GND
round Terminals
G
UVW
Power Module
NEG
POS
GND
L3
47
48
External
Braking Resistor
SA500
SA500 AC
Power Module
L1 L2
Supply
DC Bus
NEG
POS
GND
NEG
POS
VW U
Flat Washers
Lock Washers
Fuse
Fuse
Fuse
Drive or Power
Supply Bus Bar
Positive and Negative Terminals
Fuse Disconnecting Switch
SA500 AC
GND
UVW
Voltage
AC Input
Power Module
NEG
POS
(3-Phase)
Short Circuit Capacity
PE
5000 Amps o r Less
M6 Nut
M6 Terminal Post
Connecting Lugs
Terminal Post Base
D-4
Red Wire*
Black Wire*
Green Wire*
To Grounding Rod
*Wires are 225 mm (8.8") long
or Building Steel
Figure D.1 – Typical SA500 Wiring Example for CE Compliance
SA500 DC Bus Supply
Page 39
I
NDEX
B
Block diagram, B-1 Braking fuse
checking for a blown fuse, 4-2 to 4-3 fuse location, 4-3
Braking resistor
external braking resistor, 3-3 to 3-4 internal braking resistor specifications, 3-9
C
Compliance with electromagnetic compatibility
standards, D-1 to D-4
D
DC bus supply motoring current, 3-2 Diagnostics and troubleshooting, 4-1 to 4-3 Documentation, 1-2
E
Electrical description, 2-3
selecting a DC bus supply, 3-2 selecting an external braking resistor, 3-3 to 3-4 short circuit protection, 3-9 wiring, 3-4, 3-8
Interface connector TB1, 2-2 to 2-3
circuitry of terminals 1 & 2, 2-3 Internal power dissipation specifications, 3-2 Introduction, 1-1 to 1-2
L
LED indicators, 2-2, 4-1 to 4-2
Overtemp LED on, 4-1
Phase loss LED on, 4-1
PSM ready LED off, 4-2
M
Mechanical description, 2-1 to 2-3 Model numbers, 1-1 Motor current specifications, C-1 to C-2 Mounting dimensions, 3-6
R
F
Faceplate of bus supply, 2-1 Faults, 4-1 to 4-2
over temperature, 4-1 phase loss, 4-1 PSM not ready, 4-2
Fuses, 3-9
G
Grounding, 3-4
I
Installation guidelines, 3-1 to 3-10
grounding, 3-4 initial installation, 3-5 to 3-10 mounting dimensions, 3-6
Index
Related hardware, 1-2 Related publications, 1-2 Replacing the DC bus supply, 3-10
S
Selecting a DC bus supply
guidelines Selecting an external braking resistor
Installation guidelines
See
Installation
T
Technical specifications, A-1 to A-2
W
Wiring, 3-4, 3-8, D-4
See
Index-1
Page 40
Index-2
SA500 DC Bus Supply
Page 41
DIF
Documentation
Impro vement Form
Use this form to give us your comments concerning this publication or to report an error that you have found. For convenience, y ou may attach copies of the pages with your comments. After you have completed this form, please return it to:
Rockwell Automation RGA (Technical Publications) 25001 Tungsten Road Cleveland, Ohio 44117
Fax: 216.266.7120
Publication Name: Publication Number: Publication Date:
Comments:
Your Name: Date: Company Name: Phone: ( ) Address:
Thank you for your comments.
Technical Writing Internal Use
Date: DIF Number: Follow-Up Action:
Page 42
Page 43
Page 44
Rockwell Automation
Printed in U.S.A. S-3017-1 September 1998
/ 24703 Euclid Avenue / Cleveland, Ohio 44117 / (216) 266-7000
Loading...