Rockwell Automation RM 200 Reference Manual

Rockwell Automation RM 200 Reference Manual

Reference Manual

Rockwell Automation Library of Process Objects: Weigh Scale

Dosing (P_DoseWS)

Version 3.5

 

 

 

 

 

 

 

 

 

IMPORTANT

This manual applies to the Rockwell Automation Library of Process Objects version 3.5 or earlier.

 

 

 

 

 

 

For Rockwell Automation Library of Process Objects version 5.0, see

 

 

 

 

 

 

PROCES-RM200

 

 

 

 

 

 

For Rockwell Automation Library of Process Objects version 4.0 or later, use the following manuals:

 

 

 

 

 

 

PROCES-RM013 contains logic instructions

 

 

 

 

 

 

PROCES-RM014 contains display elements

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents

Preface

Weigh Scale Dosing (P_DoseWS)

Software Compatibility and Content Revision. . . . . . . . . . . . . . . . . . . . 5

Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Required Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Controller File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Visualization Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Controller Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Weigh Scale Dosing Input Structure . . . . . . . . . . . . . . . . . . . . . . . . 13

Weigh Scale Dosing Output Structure . . . . . . . . . . . . . . . . . . . . . . 18

Weigh Scale Dosing Local Configuration Tags . . . . . . . . . . . . . . . 23

Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Programming Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Display Elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Graphic Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Status/Quality Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Mode Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Maintenance Bypass Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Use Global Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Quick Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Trends Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Weigh Scale Dosing Drive Faceplate Help . . . . . . . . . . . . . . . . . . . 56

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

3

Table of Contents

Notes:

4

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

Preface

Software Compatibility and

Content Revision

Table 1 - Summary of Changes

Topic

Page

 

 

Visualization Files: Global Objects (.ggfx) - Process Diagnostic Objects

11

 

 

For the latest compatible software information and to download the Rockwell

Automation® Library of Process Objects, see the Product Compatibility and

Download Center at http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.

For general library considerations, see Rockwell Automation Library of Process Objects, publication PROCES-RM002.

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

5

Preface

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.

Resource

Description

 

 

PlantPAx® Distributed Control System Selection Guide,

Provides information to assist with equipment

publication PROCES-SG001

procurement for your PlantPAx system.

 

 

PlantPAx Distributed Control ystem Reference Manual,

Provides characterized recommendations for

publication PROCES-RM001

implementing your PlantPAx system.

 

 

Rockwell Automation Library of Process Objects,

ProvidesgeneralconsiderationsforthePlantPAxsystem

publication PROCES-RM002

library of process objects.

 

 

FactoryTalk® View Machine Edition User Manual,

Provides details on how to use this software package for

publication VIEWME-UM004

creating an automation application.

 

 

FactoryTalk View Site Edition User Manual,

Provides details on how to use this software package for

publication VIEWSE-UM006

developing and running human-machine interface

 

(HMI) applications that can involve multiple users and

 

servers, distributed over a network.

 

 

Logix5000™ Controllers Add-On Instructions Programming

Provides information for designing, configuring, and

Manual, publication 1756-PM010

programming Add-On Instructions.

 

 

Rockwell Automation Library of Process Objects: Common

Details how to monitor an input condition to raise an

Alarm Block (P_Alarm) Reference Manual, publication

alarm. Information includes acknowledging, resetting,

SYSLIB-RM002

inhibiting, and disabling an alarm. Generally the

 

P_Alarm faceplate is accessible from the Alarms tab.

 

 

Rockwell Automation Library of Process Objects: Common

Explains how to choose the Mode (owner) of an

Mode Block (P_Mode) Reference Manual, publication

instruction or control strategy. The Mode instruction is

SYSLIB-RM005

usually embedded within other instructions to extend

 

their functionality. It is possible to use a standalone

 

Mode instruction to enhance a program where modes

 

are wanted.

 

 

You can view or download publications at http:/www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or

Rockwell Automation sales representative.

6

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

Weigh Scale Dosing (P_DoseWS)

The P_DoseWS (Weigh Scale Dosing) Add-On Instruction controls an ingredient addition that uses a weigh scale to measure the quantity of ingredient added. The weigh scale can be on the receiving vessel (gain in weight) or on the sourcing vessel (loss in weight). The weigh scale can be connected via an analog input, device network, or other connection.

Global Object

Faceplate

Add-On Instruction

Guidelines

Use this instruction in these situations:

You want to control basic dosing (ingredient addition) with basic features, such as bulk/dribble rate selection, preact, automatic preact adjustment, and the ability to start, pause, and resume flow.

You are measuring the quantity of ingredient added to a destination vessel (gain in weight) or the quantity transferred from a source vessel (loss in weight) by using a weigh scale. The scale provides a weight value and can be interfaced via an analog input card, network, or other means.

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

7

Weigh Scale Dosing (P_DoseWS)

Do not use this instruction in these situations:

You want to measure the quantity of ingredients transferred with a flowmeter. Use the P_DoseFM instruction instead.

You need to control precision blending. This instruction does not include capability for controlled-rate addition, such as ratio control, digital blending, or precision blending. Contact your Rockwell Automation representative for a blending solution.

You need only a totalizer (integrator). Use the built-in TOT instruction instead.

You need only to display a weigh scales’s weight or generate high and low weight alarms. Use the P_AIn Analog Input Add-On Instruction instead.

You could need additional logic in these situations:

You need more complicated sequencing, including special actions when restarting, aborting, or holding an addition. This sort of sequencing is a good candidate for an equipment phase. Equipment phase logic can drive the P_DoseWS instruction by using its Program mode commands and settings.

The material transfer equipment requires complicated startup and shutdown logic. You can provide this logic separately and use the

P_DoseWS outputs to trigger the logic for startup and shutdown of ingredient delivery.

8

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

Weigh Scale Dosing (P_DoseWS)

Functional Description

The following diagram shows the functional characteristics of the P_DoseWS Add-On Instruction.

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

9

Weigh Scale Dosing (P_DoseWS)

Required Files

The P_DoseWS instruction provides the following capabilities:

Provides linear scaling of the input weight value from raw (input card) units to engineering (display) units.

Uses a software tare of the scale to establish the zero-quantity starting point for transfer. Once the scale is tared, the instruction checks for unrequested flow, that is, an increase or decrease in scale weight before flow is actually started, and raises a tare fault alarm if such a weight change occurs.

Provides a rate of weight change calculation (differentiation with respect to time) to generate an inferred flow rate. The calculated rate is filtered and has a low cutoff, so the rate is reported as zero when the change in weight is only from noise on the input weight signal.

Provides outputs to control associated equipment, such as pumps and valves to start and stop flow. The operator or the program can start the ingredient addition, then pause and resume as needed.

Monitors the status of controlled equipment, such as pumps and valves. Flow is stopped and an alarm is raised on an equipment fault or if the equipment fails to respond as commanded.

Monitors the weight PV input quality and communication status and provides indication of uncertain or bad weight PV. Flow is stopped and an alarm is raised on a bad PV or communication loss.

Provides program or operator entry of a quantity to deliver (setpoint) and calculates the quantity remaining to deliver and percent complete during delivery.

Add-On Instructions are reusable code objects that contain encapsulated logic that can streamline implementing your system. This lets you create your own instruction set for programming logic as a supplement to the instruction set provided natively in the ControlLogix® firmware. An Add-On Instruction is defined once in each controller project, and can be instantiated multiple times in your application code as needed.

Controller File

The P_DoseWS_3_5-00_AOI.L5X Add-On Instruction must be imported into the controller project to be used in the controller configuration. The service release number (boldfaced) can change as service revisions are created.

10

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

Weigh Scale Dosing (P_DoseWS)

Visualization Files

This Add-On Instruction has associated visualization files that provide a common user interface. These files can be downloaded from the Product

Compatibility and Download Center at http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.

IMPORTANT

The visualization file dependencies require Process Library content imports to

 

occur in a specific order as reflected in the following tables:

 

Images

 

Global Objects

 

Standard Displays

 

HMI Tags

 

Macros

 

 

 

Images are external graphic files that can be used in displays. They must be imported for FactoryTalk View to make use of them.

When PNG files are imported, they are renamed by FactoryTalk View with a .bmp file extension, but retain a .png format.

Table 2 - Visualization Files: Images (.png)

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

 

 

 

All .png files in the images folder

All .png files in the images folder

These are the common icons used in the global objects and

 

 

standard displays for all Process Objects.

 

 

 

The Global Object files (.ggfx file type) in the following table are Process Library display elements that are created once and referenced multiple times on multiple displays in an application. When changes are made to a Global Object, all instances in the application are automatically updated.

Table 3 - Visualization Files: Global Objects (.ggfx)

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

 

 

 

(RA-BAS) Common Faceplate Objects

(RA-BAS-ME) Common Faceplate Objects

Global objects used on process object faceplates.

 

 

 

(RA-BAS) Process Alarm Objects

(RA-BAS-ME) Process Alarm Objects

Global objects used for managing alarms on process

 

 

object

faceplates.

 

 

 

(RA-BAS) Process Diagnostic Objects

(RA-BAS-ME) Process Diagnostic Objects

Diagnostic global objects used on process object

 

 

faceplates.

 

 

 

(RA-BAS) Process Faceplate Analog Objects

(RA-BAS-ME) Process Faceplate Analog Objects

Analog global objects used on process object faceplates.

 

 

 

(RA-BAS) Process Faceplate Misc Objects

(RA-BAS-ME) Process Faceplate Misc Objects

Miscellaneous global objects used on process object

 

 

faceplates.

 

 

 

(RA-BAS) Process Graphics Library

(RA-BAS-ME) Process Graphics Library

Process global object device symbols used to build

 

 

process

graphics

 

 

 

(RA-BAS) Process Help Objects

(RA-BAS-ME) Process Help Objects

Global objects used for all process objects help displays.

 

 

 

(RA-BAS) Process Mode Objects

(RA-BAS-ME) Process Mode Objects

Global objects used for managing modes on process

 

 

object

faceplates.

 

 

 

 

The Standard Display files (.gfx file type) in the following table are the Process

Library displays that you see at runtime.

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

11

Weigh Scale Dosing (P_DoseWS)

Table 4 - Visualization Files: Standard Displays (.gfx)

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

 

 

 

 

(RA-BAS) Common-AnalogEdit

N/A

Faceplate used for analog input data entry.The FactoryTalk

 

 

View ME faceplates use the native analog input data entry

 

 

so no file is required.

 

 

 

(RA-BAS) P_Alarm-Faceplate

(RA-BAS-ME) P_Alarm-Faceplate

The faceplate that is used for managing alarms for

 

 

the

object.

 

 

 

 

(RA-BAS) P_Alarm-Help

(RA-BAS-ME) P_Alarm-Help

Alarm Help information that is accessed from the

 

 

P_AIarm

faceplate.

 

 

 

(RA-BAS) P_DoseWS-Faceplate

(RA-BAS-ME) P_DoseWS-Faceplate

The faceplate that is used for the object

 

 

 

(RA-BAS) P_DoseWS-Quick

(RA-BAS-ME) P_DoseWS-Quick

The Quick display that is used for the object

 

 

 

(RA-BAS) P_Mode-Config

(RA-BAS-ME) P_Mode-Config

The Configuration Display used to configure the

 

 

P_Mode

object.

 

 

 

(RA-BAS) P_Mode-Help

(RA-BAS-ME) P_Mode-Help

Mode Help information that is accessed from the

 

 

Help

faceplate.

 

 

 

(RA-BAS) Process Dose Family-Help

(RA-BAS-ME) Process Dose Family-Help

The Help display for Dose objects

 

 

 

 

(RA-BAS) P_AIChan-Faceplate

(RA-BAS-ME) P_AIChan-Faceplate

Optional

 

 

 

The Channel faceplate used for the object.

 

 

Use this file if your Analog Input has an associated

 

 

P_AIChan object and you enable navigation to its

 

 

faceplate from the Analog Input faceplate.

 

 

 

 

(RA-BAS) P_AIChan-Help

(RA-BAS-ME) P_AIChan-Help

Optional

 

 

 

Channel Help information that is accessed from the

 

 

P_AIChan Help faceplate.

 

 

Use this file if you use the Analog Input Channel faceplate.

 

 

 

 

 

HMI Tags are created in a FactoryTalk View ME application to support tab switching on Process Library faceplates. The HMI tags may be imported via the comma-separated values file (.csv file type) in the following table.

Table 5 - Visualization Files: HMI Tags (.csv)

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

 

 

 

N/A

FTVME_PlantPAxLib_Tags_3_5_xx.csv

These tags must be imported into the

 

where xx = the service release number.

FactoryTalk View ME project to support switching tabs on

 

 

any Process Object faceplate.

 

 

 

12

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

Weigh Scale Dosing (P_DoseWS)

Controller Code

This section describes the parameter references for this Add-On Instruction.

Weigh Scale Dosing Input Structure

Input parameters include the following:

Input data elements (Inp_) are typically used to connect field inputs from I/O modules or signals from other objects.

Configuration data elements (Cfg_) are used to set configurable capabilities and features of the instruction.

Command data elements (PCmd_, OCmd_, MCmd_) are used by program logic, operators, and maintenance personnel to request instruction actions.

Setting data elements (PSet_, OSet_, MSet_) are used by program logic, operators, and maintenance personnel to establish runtime setpoints, thresholds, and so forth. Set_ data elements (without a leading P, O, or M) establish runtime settings regardless of role or mode.

Table 7 - P_DoseWS Input Parameters

Input Parameter

Data

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

 

EnableIn

BOOL

 

1

Ladder Diagram:

 

 

 

 

If the rung-in condition is true, the instruction’s Logic routine executes. If the rung-

 

 

 

 

in condition is false, the instruction’s EnableInFalse routine executes.

 

 

 

 

Function Block Diagram:

 

 

 

 

If true, or not connected, the instruction’s Logic routine executes. If the parameter

 

 

 

 

is exposed as a pin and wired, and the pin is false, the instruction’s EnableInFalse

 

 

 

 

routine executes.

 

 

 

 

Structured Text:

 

 

 

 

No effect. The instruction’s Logic routine executes.

 

 

 

 

 

Inp_WeightPV

REAL

 

0.0

Weight from weigh scale (unscaled).

 

 

 

 

 

 

Inp_RunFdbk

BOOL

 

0

1

= Controlled equipment is delivering (running).

 

 

 

 

 

 

Inp_DribbleFdbk

BOOL

 

0

1

= Controlled equipment is delivering at dribble.

 

 

 

 

 

 

Inp_StopFdbk

BOOL

 

0

1

= Controlled equipment is confirmed stopped.

 

 

 

 

 

Inp_PVBad

BOOL

 

0

Bad Signal Quality/Communication Status for Inputs (1 = Bad, 0 = OK). If PV is

 

 

 

 

read from an analog input, then this is normally read from the analog input

 

 

 

 

channel fault status.

 

 

 

 

 

Inp_PVUncertain

BOOL

 

0

Uncertain Quality for Inputs (1 = Uncertain, 0 = OK). This is optional status for the

 

 

 

 

input that can be used to drive the status of the output (Sts_PVUncertain).

 

 

 

 

 

Inp_CtrldEqpFault

BOOL

 

0

Controlled equipment device or I/O status:

 

 

 

 

0

= OK

 

 

 

 

1

= Fail

 

 

 

 

 

Inp_Sim

BOOL

 

0

Simulation input.When set to 1, the instruction simulates a working dosing action.

 

 

 

 

When set to 0, the instruction controls dosing normally.

 

 

 

 

 

Inp_Reset

BOOL

 

0

Input parameter used to programmatically reset alarms. When set to 1, all alarms

 

 

 

 

requiring reset are reset.

 

 

 

 

 

 

Cfg_LossInWeight

BOOL

 

0

1

= Running reduces weight (Transfer Out).

 

 

 

 

0

= Running increases weight (Transfer In).

 

 

 

 

 

 

Cfg_HasDribble

BOOL

 

0

1

= Slow to dribble before complete.

 

 

 

 

0

= Run full flow until complete.

 

 

 

 

 

 

Cfg_HasEqpFdbk

BOOL

 

0

1

= Controlled Equipment provides Run, Dribble (if used), and Stop Feedback.

 

 

 

 

 

 

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

13

Weigh Scale Dosing (P_DoseWS)

Table 7 - P_DoseWS Input Parameters

Input Parameter

Data

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

Cfg_UseEqpFdbk

BOOL

 

0

1 = Use run/dribble/stop feedback.

 

 

 

 

0 = Assume equipment state.

 

 

 

 

 

Cfg_AutoAdjPreact

BOOL

 

0

1 = Enable automatic adjustment of preact after each tolerance check.

 

 

 

 

 

Cfg_SetTrack

BOOL

 

1

This parameter is used to set up bumpless behavior of setting parameters when

 

 

 

 

switching modes. When this parameter is 1, in Program mode the operator

 

 

 

 

settings track the program settings; in Operator mode the program settings track

 

 

 

 

the operator settings; and the simulation inputs match the output values

 

 

 

 

(transitions are bumpless).

 

 

 

 

When this parameter is 0, the operator settings and program settings are not

 

 

 

 

modified by this instruction. In this case, when the mode is changed, the effective

 

 

 

 

value of the setting can change depending on the program-set and operator-set

 

 

 

 

values.

 

 

 

 

 

Cfg_HasChanObj

BOOL

 

0

1 = Tells HMI a Channel object (P_AIChan, etc.) is used for Inp_WeightPV.

 

 

 

 

IMPORTANT: The name of the Channel object in the controller must be this

 

 

 

 

object's name with the suffix ‘_Chan’. For example, if your P_DoseWS object has

 

 

 

 

the name ‘DoseWS123’, then its Channel object must be named

 

 

 

 

‘DoseWS123_Chan’.

 

 

 

 

 

Cfg_PCmdClear

BOOL

Mode.Cfg_PCmdClear

1

When this parameter is 1, program commands are cleared once they are acted

 

 

 

 

upon. When set to 0, program commands remain set until cleared by the

 

 

 

 

application program logic.

 

 

 

 

IMPORTANT: Clearing this parameter online can cause unintended program

 

 

 

 

command execution.

 

 

 

 

 

Cfg_ProgDefault

BOOL

Mode.Cfg_ProgDefault

0

This parameter defines the default mode. When this parameter is 1, the mode

 

 

 

 

defaults to Program if no mode is being requested. When this parameter is 0, the

 

 

 

 

mode defaults to Operator if no mode is being requested.

 

 

 

 

IMPORTANT: Changing this parameter online can cause unintended mode

 

 

 

 

changes.

 

 

 

 

 

Cfg_ShedOnEqpFault

BOOL

 

0

1 = Stop delivery and alarm on equipment fault.

 

 

 

 

0 = Alarm only on Equipment fault.

 

 

 

 

 

Cfg_HasOverTolAlm

BOOL

OverTol.Cfg_Exists

0

These parameters determine whether the corresponding alarm exists and is

 

 

 

 

checked or if the alarm does not exist and is not used. When these parameters are

Cfg_HasUnderTolAlm

 

UnderTol.Cfg_Exists

 

 

 

1, the corresponding alarm exists.

 

 

 

 

 

Cfg_HasTareFaultAlm

 

TareFault.Cfg_Exists

 

 

 

 

 

 

 

Cfg_HasEqpFaultAlm

 

EqpFault.Cfg_Exists

 

 

 

 

 

 

 

Cfg_OverTolResetReqd

BOOL

OverTol.Cfg_ResetReqd

0

These parameters determine whether a reset is required to clear the alarm status.

 

 

 

 

When these parameters are 1, the alarm is latched ON when the alarm occurs. After

Cfg_UnderTolResetReqd

 

UnderTol.Cfg_ResetReqd

 

 

 

the alarm condition returns to normal, a reset is required to clear the alarm status

 

 

 

 

(for example, OCmd_Reset, Inp_Reset, or EqpFault.OCmd_Reset are required to

Cfg_TareFaultResetReqd

 

TareFault.Cfg_ResetReqd

 

 

 

clear Alm_EqpFault alarm after the alarm is set and the equipment returns to

 

 

 

 

 

 

 

 

normal). When these parameters are 0, no reset is required and the alarm status is

Cfg_EqpFaultResetReqd

 

EqpFault.Cfg_ResetReqd

 

 

 

cleared when the alarm condition returns to normal.

 

 

 

 

 

 

 

 

IMPORTANT: If the reset clears the alarm, it also acknowledges the alarm.

 

 

 

 

 

Cfg_OverTolAckReqd

BOOL

OverTol.Cfg_AckReqd

1

These parameters determine whether an acknowledgement is required for an

 

 

 

 

alarm. When these parameters are 1, the acknowledge (ack) bit is cleared when

Cfg_UnderTolAckReqd

 

UnderTol.Cfg_AckReqd

 

 

 

the alarm occurs. An acknowledge command (for example, PCmd_EqpFaultAck or

 

 

 

 

EqpFault.OCmd_Ack) is required to acknowledge the alarm. When set to 0, the

Cfg_TareFaultAckReqd

 

TareFault.Cfg_AckReqd

 

 

 

Acknowledge bit is set when an alarm occurs indicating an acknowledged alarm

 

 

 

 

 

 

 

 

and no acknowledge command is required.

Cfg_EqpFaultAckReqd

 

EqpFault.Cfg_AckReqd

 

 

 

 

 

 

 

 

 

14

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

 

 

 

 

 

Weigh Scale Dosing (P_DoseWS)

 

 

 

 

 

 

Table 7 - P_DoseWS Input Parameters

 

 

 

 

 

 

 

 

 

Input Parameter

Data

 

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

 

 

Cfg_OverTolSeverity

INT

 

OverTol.Cfg_Severity

750

These parameters determine the severity of each alarm. This drives the colors and

 

 

 

 

 

symbols that are used to indicate alarm status on the faceplate and global object.

Cfg_UnderTolSeverity

 

 

UnderTol.Cfg_Severity

500

 

 

The following are valid values:

 

 

 

 

 

Cfg_TareFaultSeverity

 

 

TareFault.Cfg_Severity

1000

1…250 = Low

 

 

 

 

 

251…500 = Medium

Cfg_EqpFaultSeverity

 

 

EqpFault.Cfg_Severity

1000

 

 

501…750 = High

 

 

 

 

 

 

 

 

 

 

751…1000 = Urgent

 

 

 

 

 

IMPORTANT: For FactoryTalk View software version 7.0, these severity parameters

 

 

 

 

 

drive only the indication on the global object and faceplate. The Alarms and Events

 

 

 

 

 

definition of severity drives the color and symbol that is used on the alarm banner

 

 

 

 

 

and alarm summary as well as the value returned by FactoryTalk Alarms and Events

 

 

 

 

 

display commands.

 

 

 

 

 

 

Cfg_InpRawMin

REAL

 

 

0.0

Minimum unscaled weight input.

 

 

 

 

 

 

Cfg_InpRawMax

REAL

 

 

10000.0

Maximum unscaled weight input.

 

 

 

 

 

 

Cfg_PVEUMin

REAL

 

 

0.0

Minimum scaled weight PV input (engineering units).

 

 

 

 

 

 

Cfg_PVEUMax

REAL

 

 

10000.0

PV (Output) maximum for scaling to engineering units.

 

 

 

 

 

IMPORTANT: The P_DoseWS instruction supports reverse scaling; either the raw

 

 

 

 

 

(Input) or engineering (Scaled) range can be reversed (maximum less than

 

 

 

 

 

minimum).

 

 

 

 

 

 

Cfg_MaxQty

REAL

 

 

1.0E+38

Maximum allowed quantity to deliver (setpoint) (engineering units).

 

 

 

 

 

 

Cfg_RateTime

REAL

 

 

1.0

Time factor for rate (60 for /min, 3600 for /hr) (seconds).

 

 

 

 

 

 

Cfg_RateFiltTC

REAL

 

 

0.1

Filter time constant (seconds) for calculated rate.

 

 

 

 

 

 

Cfg_TareFaultLim

REAL

 

 

1.0

Amount (engineering units) scale can drift after tare before starting flow without

 

 

 

 

 

faulting.

 

 

 

 

 

 

Cfg_SettleT

REAL

 

 

1.0

Time to allow scale to settle before allowing tolerance check (seconds).

 

 

 

 

 

 

Cfg_BumpT

REAL

 

 

0.0

Bump (manual top-off) Time (seconds), 0.0 = use Bump command as a ‘jog’.

 

 

 

 

 

 

Cfg_AutoAdjPct

REAL

 

 

10.0

Percentage of delivery error to auto-adjust preact (%).

 

 

 

 

 

 

Cfg_SimStartWt

REAL

 

 

0.0

Weight to start from (tare to) in simulation (engineering units).

 

 

 

 

 

 

Cfg_SimRate

REAL

 

 

1.0

Rate at which to deliver when running in simulation (engineering units/rate time).

 

 

 

 

 

 

Cfg_SimDribbleRate

REAL

 

 

0.1

Rate at which to dribble when running in simulation (engineering units/rate time).

 

 

 

 

 

 

Cfg_FaultT

DINT

 

 

10

Time for equipment feedback to follow output before fault (seconds).

 

 

 

 

 

 

Cfg_OperKeep

SINT

 

 

2#0000_0000

Operator keeps control in Program mode:

 

 

 

 

 

Bit .0 = 1 operator keeps Start/Stop

 

 

 

 

 

Bit .1 = 1 Operator keeps SP

 

 

 

 

 

Bit .2 = 1 Operator keeps Dribble/preact

 

 

 

 

 

Bit .3 = 1 Operator keeps Tolerances

 

 

 

 

 

 

Cfg_ProgKeep

SINT

 

 

2#0000_0000

Program keeps control in Operator mode:

 

 

 

 

 

Bit .0 = 1 Program keeps Start/Stop

 

 

 

 

 

Bit .1 = 1 Program keeps SP

 

 

 

 

 

Bit .2 = 1 Program keeps Dribble/preact

 

 

 

 

 

Bit .3 = 1 Program keeps Tolerances

 

 

 

 

 

 

PSet_SP

REAL

 

 

0.0

Program setting of total quantity to deliver (engineering units).

 

 

 

 

 

 

PSet_DribbleQty

 

 

 

 

Program setting of quantity to dribble (engineering units).

 

 

 

 

 

 

PSet_Preact

 

 

 

 

Program setting of quantity before total to stop flow (engineering units).

 

 

 

 

 

 

PSet_TolHi

 

 

 

 

Program setting of high (excess) tolerance limit.

 

 

 

 

 

 

PSet_TolLo

 

 

 

 

Program setting of low (shortage) tolerance limit.

 

 

 

 

 

 

PSet_Owner

DINT

 

 

0

Program owner request ID (nonzero) or Release (zero).

 

 

 

 

 

 

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

15

Weigh Scale Dosing (P_DoseWS)

Table 7 - P_DoseWS Input Parameters

Input Parameter

Data

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

OSet_SP

REAL

 

0.0

Operator setting of total quantity to deliver (engineering units).

 

 

 

 

 

OSet_DribbleQty

 

 

 

Operator setting of quantity to dribble (engineering units).

 

 

 

 

 

OSet_Preact

 

 

 

Operator setting of quantity before total to stop flow (engineering units).

 

 

 

 

 

OSet_TolHi

 

 

 

Operator setting of high (excess) tolerance limit.

 

 

 

 

 

OSet_TolLo

 

 

 

Operator setting of low (shortage) tolerance limit.

 

 

 

 

 

PCmd_Tare

BOOL

 

0

When Cfg_PCmdClear is 1:

 

 

 

 

Set PCmd_Tare to 1 to reset the delivered quantity to 0

 

 

 

 

This parameter is reset automatically

 

 

 

 

When Cfg_PCmdClear is set to 0:

 

 

 

 

Set PCmd_Tare to 1 to reset the delivered quantity to 0

 

 

 

 

This parameter is not reset automatically

 

 

 

 

 

PCmd_StartFlow

BOOL

 

0

When Cfg_PCmdClear is 1:

 

 

 

 

Set PCmd_StartFlow to 1 to start delivery

PCmd_StopFlow

 

 

 

 

 

 

Set PCmd_StopFlow to 1 to stop delivery

 

 

 

 

PCmd_CheckTol

 

 

 

Set PCmd_CheckTolerances to 1 to check tolerances

 

 

 

 

These parameters reset automatically

 

 

 

 

When Cfg_PCmdClear is 0:

 

 

 

 

Set PCmd_StartFlow to 1 to start delivery

 

 

 

 

Set PCmd_StopFlow to 1 to stop delivery

 

 

 

 

Set PCmd_CheckTolerances to 1 to check tolerances

 

 

 

 

These parameters do not reset automatically

 

 

 

 

 

PCmd_Bump

BOOL

 

0

When PCmd_Bump is set to 1:

 

 

 

 

If the configured bump time (Cfg_BumpT) is nonzero, then bump delivery for

 

 

 

 

the configured bump time

 

 

 

 

PCmd_Bump is cleared automatically

 

 

 

 

If the configured bump time (Cfg_BumpT) is zero, then bump delivery until

 

 

 

 

PCmd_Bump is returned to 0

 

 

 

 

PCmd_Bump is not cleared automatically

 

 

 

 

Cfg_PCmdClear does not affect this parameter

 

 

 

 

 

PCmd_Acq

BOOL

Mode.PCmd_Acq

0

When Cfg_PCmdClear is 1:

 

 

 

 

Set PCmd_Acq to 1 to Acquire

PCmd_Rel

 

Mode.PCmd_Rel

 

 

 

Set PCmd_Rel to 1 to Release

 

 

 

 

These parameters reset automatically

 

 

 

 

When Cfg_PCmdClear is 0:

 

 

 

 

Set PCmd_Acq to 1 to Acquire

 

 

 

 

Set PCmd_Acq to 0 to Release

 

 

 

 

PCmd_Rel is not used

 

 

 

 

These parameters do not reset automatically

 

 

 

 

 

PCmd_Lock

BOOL

Mode.PCmd_Lock

0

When Cfg_PCmdClear is 1:

 

 

 

 

Set PCmd_Lock to 1 to Lock

PCmd_Unlock

 

Mode.PCmd_Unlock

 

 

 

Set PCmd_Unlock to 1 to Unlock

 

 

 

 

These parameters reset automatically

 

 

 

 

When Cfg_PCmdClear is 0:

 

 

 

 

Set PCmd_Lock to 1 to Lock

 

 

 

 

Set PCmd_Lock to 0 to Unlock

 

 

 

 

PCmd_Unlock is not used

 

 

 

 

These parameters do not reset automatically

 

 

 

 

 

PCmd_Reset

BOOL

 

0

Set PCmd_Reset to 1 to reset all alarms requiring reset

 

 

 

 

This parameter is always reset automatically

 

 

 

 

 

PCmd_OverTolAck

BOOL

OverTol.PCmd_Ack

0

Set PCmd_<Alarm>Ack to 1 to Acknowledge alarm

 

 

 

 

The parameter is reset automatically

PCmd_UnderTolAck

 

UnderTol.PCmd_Ack

 

 

 

 

 

 

 

 

 

PCmd_TareFaultAck

 

TareFault.PCmd_Ack

 

 

 

 

 

 

 

PCmd_EqpFaultAck

 

EqpFault.PCmd_Ack

 

 

 

 

 

 

 

16

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

Weigh Scale Dosing (P_DoseWS)

Table 7 - P_DoseWS Input Parameters

Input Parameter

Data

Alias For

Default

Description

 

Type

 

 

 

 

 

 

 

 

PCmd_OverTolSuppress

BOOL

OverTol.PCmd_Suppress

0

When Cfg_PCmdClear is 1:

 

 

 

 

Set PCmd_<Alarm>Suppress to 1 to suppress alarm

PCmd_UnderTolSuppress

 

UnderTol.PCmd_Suppress

 

 

 

Set PCmd_<Alarm>Unsuppress to 1 to unsuppress alarm

 

 

 

 

PCmd_TareFaultSuppress

 

TareFault.PCmd_Suppress

 

These parameters reset automatically

 

 

 

 

When Cfg_PCmdClear is 0:

PCmd_EqpFaultSuppress

 

EqpFault.PCmd_Suppress

 

 

 

Set PCmd_<Alarm>Suppress to 1 to suppress alarm

 

 

 

 

PCmd_OverTolUnsuppress

BOOL

OverTol.PCmd_Unsuppress

0

Set PCmd_<Alarm>Suppress to 0 to unsuppress alarm

 

 

 

 

PCmd_<Alarm>Unsuppress is not used

PCmd_UnderTolUnsuppress

 

UnderTol.PCmd_Unsuppress

 

 

 

These Parameters do not reset automatically

 

 

 

 

PCmd_TareFaultUnsuppress

 

TareFault.PCmd_Unsuppress

 

 

 

 

 

 

 

PCmd_EqpFaultUnsuppress

 

EqpFault.PCmd_Unsuppress

 

 

 

 

 

 

 

PCmd_OverTolUnshelve

BOOL

OverTol.PCmd_Unshelve

0

Set PCmd_<Alarm>Unshelve to 1 to Unshelve alarm

 

 

 

 

The parameter is reset automatically

PCmd_UnderTolUnshelve

 

UnderTol.PCmd_Unshelve

 

 

 

 

 

 

 

 

 

PCmd_TareFaultUnshelve

 

TareFault.PCmd_Unshelve

 

 

 

 

 

 

 

PCmd_EqpFaultUnshelve

 

EqpFault.PCmd_Unshelve

 

 

 

 

 

 

 

OCmd_Tare

BOOL

 

0

Operator command to tare (reset delivered quantity to 0).

 

 

 

 

 

OCmd_StartFlow

BOOL

 

0

Operator commands to start delivery, stop/pause delivery, or check tolerances.

 

 

 

 

 

OCmd_StopFlow

 

 

 

 

 

 

 

 

 

OCmd_CheckTol

 

 

 

 

 

 

 

 

 

OCmd_Bump

BOOL

 

0

Operator command to bump delivery for under tolerance.

 

 

 

 

 

MCmd_Acq

BOOL

Mode.MCmd_Acq

0

Maintenance command to acquire ownership (Operator/Program/Override to

 

 

 

 

Maintenance).

 

 

 

 

 

MCmd_Rel

BOOL

Mode.MCmd_Rel

0

Maintenance command to release ownership (Maintenance to Operator/Program/

 

 

 

 

Override)

 

 

 

 

 

OCmd_AcqLock

BOOL

Mode.OCmd_AcqLock

0

Operator command to acquire (Program to Operator)/lock ownership.

 

 

 

 

 

OCmd_Unlock

BOOL

Mode.OCmd_UnlockRel

0

Operator command to unlock/release (Operator to Program) ownership.

 

 

 

 

 

OCmd_Reset

BOOL

 

0

Operator command to reset all alarms requiring reset.

 

 

 

 

 

OCmd_ResetAckAll

BOOL

 

0

Operator command to acknowledge and reset all alarms and latched shed

 

 

 

 

conditions.

 

 

 

 

 

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

17

Weigh Scale Dosing (P_DoseWS)

Weigh Scale Dosing Output Structure

Output parameters include the following:

Output data elements (Out_) are the primary outputs of the instruction, typically used by hardware output modules; however, they can be used by other application logic.

Value data elements (Val_) are numeric outputs of the instruction for use by the HMI. Values can also be used by other application logic or software packages.

Source and Quality data elements (SrcQ_) are outputs of the instruction used by the HMI to indicate PV source and quality.

Status data elements (Sts_) are bit outputs of the instruction for use by the

HMI. Status bits can also be used by other application logic.

Error data elements (Err_) are outputs of the instruction that indicate a particular configuration error. If any Err_ bit is set, then the Sts_Err configuration error summary status is set and the Invalid Configuration indicator is displayed on the HMI.

Not Ready data elements (Nrdy_) are bit outputs of the instruction for use by the HMI for displaying the Device Not Ready indicator. Not Ready bits can also be used by other application logic.

Alarm data elements (Alm_) are outputs of the instruction that indicate a particular alarm has occurred.

Acknowledge data elements (Ack_) are outputs of the instruction that indicate the corresponding alarm has been acknowledged.

Ready data elements (Rdy_) are bit outputs of the instruction used by the HMI to enable or disable command buttons and setting entry fields.

Table 8 - P_DoseWS Output Parameters

Output Parameter

Data Type

Alias For

Description

 

 

 

 

EnableOut

BOOL

 

Enable output: The EnableOut signal is not manipulated by this instruction. Its output state

 

 

 

always reflects

 

 

 

EnableIn input state.

 

 

 

 

Out_RunFlow

BOOL

 

1 = Deliver at full (fast) flow.

 

 

 

 

Out_DribbleFlow

BOOL

 

1 = Deliver at dribble (slow) flow.

 

 

 

 

Out_StopFlow

BOOL

 

1 = Stop delivery equipment.

 

 

 

 

Val_PV

REAL

 

Weight on scale (engineering units).

 

 

 

 

Val_Tare

REAL

 

Weight on scale when tare command received (engineering units).

 

 

 

 

Val_Qty

REAL

 

Quantity actually delivered (change in weight) (engineering units).

 

 

 

 

Val_Rate

REAL

 

Current delivery rate (engineering units/time).

 

 

 

 

Val_SP

REAL

 

Quantity to be delivered (setpoint) (engineering units).

 

 

 

 

Val_Remain

REAL

 

Quantity yet to deliver to reach setpoint (engineering units).

 

 

 

 

Val_PctComplete

REAL

 

Percent complete (for progress bar on HMI) 0.0…100.0%.

 

 

 

 

Val_DribbleQty

REAL

 

Quantity to be delivered at slow rate (engineering units).

 

 

 

 

Val_Preact

REAL

 

Quantity before SP when flow is stopped (engineering units).

 

 

 

 

18

Rockwell Automation Publication SYSLIB-RM021G-EN-E - February 2017

Loading...
+ 42 hidden pages