PowerFlex Drives with
TotalFORCE Control Built-in
EtherNet/IP Adapter
Catalog Numbers 20G, 20J, 6000T
User Manual
Original Instructions
PowerFlex Drives with TotalFORCE Control Built-in EtherNet/IP Adapter User Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANTIdentifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential
Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory
requirements for safe work practices and for Personal Protective Equipment (PPE).
2Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Rockwell Automation Publication 750COM-UM009B-EN-P - April 20215
Table of Contents
Notes:
6Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Preface
About This Publication
Conventions Used in This
Manual
Download Firmware, AOP,
EDS, and Other Files
Summary of Changes
This manual provides information about the dual-port, built-in EtherNet/IP™
adapter in PowerFlex® 755T drives and bus supplies, PowerFlex 6000T, and
how to use the adapter for network communication.
These conventions are used throughout this manual:
Parameter names are shown in the format Device Parameter xxx - [*] or Host Parameter xxx - [*]. The xxx represents the parameter number. The *
represents the parameter name—for example, Device Parameter 01 - [Operating Mode].
•Where a parameter is referenced outside of the native port, it is
referenced as Port#:Parameter# [parameter name]
(0:301 - [Net Addr Scr] or 10:350 - [Vref Source])
Download firmware, associated files (such as AOP, EDS, and DTM), and access
product release notes from the Product Compatibility and Download Center at
rok.auto/pcdc
This publication contains the following new or updated information. This list
includes substantive updates only and is not intended to reflect all changes.
.
Topic Page
Updated templatethroughout
General updatethroughout
Added information for PowerFlex 6000T drivesthroughout
Corrected PCR ID 778 on page numbering and pdf view settingthroughout
Updated Additional Resources table8
Changed all “ControlFLASH” instances to “ControlFLASH Plus”throughout
Updated Connected Component Workbench software release version to 1112, 15, 17, 75
Added information on using the Enhanced HIM Integrated Touch Screen Display with
PowerFlex 6000T drives
Revised instructions for setting IP address using a HIM page21
Updated information on establishing communication by using RSLinx Classic Software31
Updated information on AOP and corrected PCR ID 736 on broken links32
Updated information on creating Logix Controller project33
Moved Appendix A Status Indicators to topic within Chapter 6 Troubleshooting75
12, 17, 75
Rockwell Automation Publication 750COM-UM009B-EN-P - April 20217
Preface
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
PowerFlex 750-Series Products with TotalFORCE Installation Instructions,
publication 750-IN100
PowerFlex 755TM IP00 Open Type Kits Installation Instructions,
publication 750-IN101
PowerFlex Drives with TotalFORCE Control Programming Manual,
publication 750-PM100
PowerFlex 750-Series Products with TotalFORCE Control Technical Data,
publication 750-TD100
PowerFlex 755TM IP00 Open Type Kits Technical Data, publication 750-TD101
PowerFlex 750-Series Products with TotalFORCE Control Hardware Service
Manual, publication 750-TG100
.Provides declarations of conformity, certificates, and other certification details.
Provide the basic steps to install PowerFlex 755TL low harmonic drives, PowerFlex 755TR
regenerative drives, and PowerFlex 755M drive systems.
Provides instructions to install IP00 Open Type Kits in user-supplied enclosures.
Provides detailed information on:
• I/O, control, and feedback options
• Parameters and programming
• Faults, alarms, and troubleshooting
Provides detailed information on:
• Drive and bus supply specifications
• Option specifications
• Fuse and circuit breaker ratings
Provides detailed information on:
• Kit selection
• Kit ratings and specifications
• Option specifications
Provides detailed information on:
• Preventive maintenance
•Component testing
• Hardware replacement procedures
These publications provide detailed information on installation, set-up, and operation of the 750Series safety option modules.
Provides detailed information on drive features, programming parameters, and troubleshooting
faults and alarms.
Provides basic information on enclosure systems, considerations to help protect against
environmental contaminants, and power and grounding considerations for installing Pulse Width
Modulated (PWM) AC drives.
Provides basic information to wire properly and ground the following products in common bus
applications:
• PowerFlex 755TM drive system for common bus solutions
• PowerFlex 750-Series AC and DC input drive
• Kinetix® 5700 servo drives
Provides basic information to properly wire and ground PWM AC drives.
You can view or download publications at rok.auto/literature
8Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
.
Chapter 1
ItemPartDescription
1
Status
Indicator ENET
Indicates the overall status of
network communication. See
Chapter 6
, Troubleshooting on
page 75.
2
Status
indicators LNK1 and
LNK2
Indicates the status of the network
link to each of the two physical
ports. See Chapter 6
,
Troubleshooting on page 75.
3
IP address
Switches
Sets the IP address of the interface
(port 0) when not using any of
these other methods:
• Interface parameters
•BOOTP server
• DHCP server firmware
See Setting the IP Address on
page 16 for details.
4
Ethernet
Connectors
RJ45 connectors for the Ethernet
cable. The connectors are CAT-5
compliant to deliver data over a
100 Base-TX Ethernet networks.
5
DPI Port 2 and
3
Cable connection for DPI port 2
handheld and remote options. DPI
port 3 is available by using a DPI
splitter part number 1203-S03.
6Reserved
Drive Control Pod
Drive STS Indicator
Components that are shown have the HIM
bezel open and the drive cover removed
1
3
4
5
2
6
Ones
Position
Hundreds
Position
Tens
Position
Getting Started
The built-in EtherNet/IP adapter, on the main control board of the drive, is
used for network communication.
TopicPage
Components9
Fea tur es10
Dual Ethernet Ports10
Required Equipment12
Equipment Shipped with the Drive12
User-supplied Equipment12
Choose an Ethernet Switch13
Safety Precautions13
Components
Rockwell Automation Publication 750COM-UM009B-EN-P - April 20219
Chapter 1 Getting Started
FeaturesThe features of the built-in EtherNet/IP adapter include the following:
•Switches are used to set an IP address before power is applied to the
drive. Other methods are also available to configure the IP address:
- Interface parameters
- BOOTP (Bootstrap Protocol) server
- DHCP (Dynamic Host Configuration Protocol) server
•Indicators that report the status of the built-in EtherNet/IP adapter and
network communication. They are visible when the drive cover is open or
closed.
•Controller hierarchy that can be configured to transmit data to and from
a controller.
•Parameter-configured 32-bit datalinks in the I/O to meet application
requirements: 16 datalinks to write data from the network to the drive,
and 16 datalinks to read data to the network from the drive.
•Explicit Messaging support.
•User-defined fault actions to determine how the built-in
EtherNet/IP adapter and its host drive respond to the following:
- I/O messaging communication disruptions (Comm Flt Action)
- Controllers in Program mode (Idle Flt Action)
- Message (MSG) instructions for drive control via PCCC or the
Common Industrial Protocol (CIP™) based network Assembly Object
(Msg Flt Action)
•Automatic Device Configuration (ADC) and Studio 5000 Logix
Designer® application feature, which supports the automatic download
of configuration data.
Dual Ethernet Ports
Dual Ethernet ports provide connection for star, linear, or Device Level Ring
(DLR) network topologies.
Examples of different EtherNet/IP network topologies are shown in Figure 1
Figure 2
applicable to PowerFlex drives with TotalFORCE® technology with the built-in
Ethernet/IP adapter. For information about linear and Device Level Ring
(DLR) topologies, see EtherNet/IP built-in Switch Technology,
publication ENET-AP005
, and Figure 3. These examples show a PowerFlex 755T drive, but are
.
IMPORTANT
The adapter has EtherNet/IP built-in switch technology, and ENET1 and
ENET2 network ports to connect to a linear or Device Level Ring (DLR)
network in a subnet.
You cannot use the ENET1 and ENET2 network ports as two network
interfaces that are connected to two different Internet Protocol (IP)
subnets.
,
10Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Figure 1 - Connecting the Ethernet Cable in a Star Topology Network
Controller
PowerFlex 755T drives
(1)
External
Ethernet
Switch
Computer with Ethernet
Connection
To other
EtherNet/IP
networks
(1)
The Ethernet cable can be connected to the adapters ENET1 or ENET2 network port.
Controller
PowerFlex 755T drives
(1)
External
Ethernet Switch
Computer with Ethernet
Connection
To other
EtherNet/IP
networks
(1)
The adapters ENET1 and ENET2 network ports are both used.
Controller
PowerFlex 755T drives
(1)
Computer with Ethernet
Connection
To other
EtherNet/IP
networks
Ethernet Tap
1783-ETAP
((1)
The adapters ENET1 and ENET2 network ports are both used.
Ethernet Tap
1783-ETAP
Figure 2 - Connecting the Ethernet Cable in a Linear Topology Network
Chapter 1 Getting Started
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202111
Figure 3 - Connecting the Ethernet Cable in a DLR Topology Network
Chapter 1 Getting Started
Required EquipmentSome required equipment that is used with the built-in EtherNet/IP adapter is
shipped with the drive. The sections that follow describe some of the other
user-supplied equipment that is also required.
Equipment Shipped with the Drive
Because the EtherNet/IP adapter is built in the main control board in the drive,
it is always a part of the drive. There are no separate physical installation
instructions for the interface.
User-supplied Equipment
To configure the built-in EtherNet/IP adapter, you must supply the following:
•A small screwdriver for setting the network address switches.
•An Ethernet cable.
•An Ethernet switch (see Choose an Ethernet Switch
•A computer connection to the EtherNet/IP network.
on page 13).
See the EtherNet/IP Media Planning and Installation Manual, available from the
Open DeviceNet® Vendor Association (ODVA) at https://www.odva.org
details on how to use the required media components and how to plan for
install, verify, troubleshoot, and certify your EtherNet/IP network.
for
Configuration Tool Options
Any of the following configuration tools can be used:
•20-HIM-A6 and 20-HIM-C6S for PowerFlex 755T drives
•Integrated touch screen display (eHIM) or standard HIM (20-750-CS6)
for PowerFlex 6000T drives
•Connected Components Workbench™ software release 11 or later
Connected Components Workbench software is the recommended
standalone software tool for use with PowerFlex drives. Download it for
free from the Product Compatibility and Download Center (PCDC) at
rok.auto/pcdc
•Controller configuration software, such as RSLogix 5000® software,
version 20, or Studio 5000 Logix Designer application, version 21 and
later, which also supports Automatic Device Configuration (ADC).
For versions earlier than version 30, you must install the Add-on Profile
(AOP) available from the PCDC at rok.auto/pcdc
.
.
12Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Chapter 1 Getting Started
Choose an Ethernet Switch
If the built-in EtherNet/IP adapter is used to communicate with a controller
that has multicast connections, a managed switch that supports IGMP
snooping is suggested. EtherNet/IP implicit (I/O) messaging can be
configured to use IP multicast to distribute I/O control data, which is
consistent with the CIP-based network Producer/Consumer model. If multiple
built-in EtherNet/IP adapters are connected to the switch in a redundant
configuration, a managed switch is required. A managed switch also provides
useful diagnostic features such as port mirroring.
The built-in EtherNet/IP adapter supports unicast connections. Unicast is the
default setting when adding the drive to the I/O controller. When all built-in
EtherNet/IP adapters are installed as unicast devices, then an IGMP snooping
(managed) switch is not needed.
The choice of a switch involves many factors. See Ethernet Reference Manual
publication ENET-RM002
switches from Rockwell Automation, see the Stratix® Industrial Networks
Infrastructure At-a-Glance, publication ENET-QR001
for details. For more information about industrial
.
Safety PrecautionsRead the following safety precautions carefully.
ATTENTION: Risk of injury or equipment damage exists.
• Only personnel familiar with drive and power products and the associated
machinery can plan or implement the installation, start up, configuration. Only
qualified personnel can perform subsequent maintenance of the drive by using
this built-in interface. Failure to comply can result in injury and/or equipment
damage.
• The built-in adapter contains electrostatic discharge (ESD) sensitive parts that
can be damaged if you do not follow ESD control procedures. ESD control
precautions are required when handling the interface. If you are unfamiliar with
ESD control procedures, see Guarding Against Electrostatic Damage,
publication 8000-SB001
• When a system is configured for the first time, unintended or incorrect machine
motion can occur. Disconnect the motor from the machine or process during
initial system testing.
.
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202113
Chapter 1 Getting Started
Notes:
14Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Chapter 2
Configure the Adapter
This chapter provides instructions and information for setting the parameters
to configure the built-in EtherNet/IP adapter.
TopicPage
Configuration Tools15
Setting the IP Address16
Connecting the Interface to the Network17
Apply Power18
Start-up Status Indications18
Configuring and Verifying Key Drive Parameters20
Use Interface Parameters to Set the IP Address21
Using a HIM to Access Parameters21
Using a BOOTP or DHCP Server23
Setting the Data Rate24
Setting Communication Hierarchy25
Setting a Controller Hierarchy25
Setting a Fault Action27
Changing the Fault Action27
Resetting the Adapter28
Restore Interface Parameters to Default Configurations28
Viewing the Interface Status Using Parameters29
Updating the Interface Firmware30
For a list of parameters, see Appendix B
definitions of terms in this chapter, see the Glossary
, Interface Parameters on page 85. For
.
Configuration ToolsThe built-in EtherNet/IP adapter stores parameters and other information in
nonvolatile storage (NVS). The following tools can be used to access the
interface parameters.
ToolSee
PowerFlex 20-HIM-A6 or 20-HIM-C6S HIMpage 21
BOOTP serverpage 23
DHCP server page 23
Connected Components Workbench software,
release 11 or later
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202115
rok.auto/pcdc, or online help (installed with the software)
Chapter 2 Configure the Adapter
Ones
Position
Hundreds
Position
Tens
Position
Setting the IP AddressThere are four ways to configure the built-in EtherNet/IP adapter IP address:
•Interface Rotary Switches — Use the switches when working on a
simple, isolated network (with IP addresses in the range, 192.168.1.xxx),
and you prefer a simplified node addressing method that has other
products with switches to set their IP addresses. See Use Switches to Set
the IP Address on page 16.
•Interface Parameters — Use interface parameters for more flexibility
when configuring the IP address. To use parameters as the source for the
IP address, set the rotary switches to 999. Set 0:300 - [Net Addr Sel] to ‘1’
(Parameters). The IP address, subnet mask, and gateway address come
from the values set using the associated interface 0:302...313. See Use
Interface Parameters to Set the IP Address on page 21.
•BOOTP — Use BOOTP when you want to configure an IP address, subnet
mask, and gateway address for the interface by using a BOOTP server. To
use BOOTP as the source for the IP address, set the rotary switches to
999. Set 0:300 - [Net Addr Sel] to ‘2’ (BOOTP).
See Using a BOOTP or DHCP Server
•DHCP (Dynamic Host Configuration Protocol) Use DHCP when you
want to configure an IP address, subnet mask, and gateway address for
the interface by using a DHCP server. To use DHCP as the source for the
IP address, set the rotary switches to 999.
Set 0:300 - [Net Addr Sel] to ‘3’ (DHCP).
See Using a BOOTP or DHCP Server
on page 23 for details.
on page 23 for details.
IMPORTANT
Regardless of the method that is used to set the interface IP address, each
node on the EtherNet/IP network must have a unique IP address. To
change an IP address, you must set the new value and then remove and
reapply power to (or reset) the interface.
Use Switches to Set the IP Address
Figure 4 - Setting the IP Address Switches
The three interface switches are grouped near the middle of the drive. These
switches are read when the drive powers up, and represent three decimal
digits from top to bottom. If set to a valid address (001…254), the interface uses
that value as the last octet of its IP address (192.168.1.xxx, where xxx = the
16Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Chapter 2 Configure the Adapter
rotary switch settings), along with a subnet mask of 255.255.255.0 and a
gateway address of 192.168.1.1. Also, the setting for interface 0:300 - [Net Addr Sel] is automatically ignored.
Table 1 - IP Address Switches Settings
SettingsDescription
001…254
888
999
Any other setting Reserved.
The adapter uses the rotary switch settings for the IP address (192.168.1.xxx, where xxx = the rotary
switch settings). The value that is stored in 0: 300 - [Net Addr Sel] is automatically ignored.
Resets the adapter IP address and other EtherNet/IP communication settings to factory defaults.
Thereafter, the drive must be powered down, the switches set to a correct value (001…254 or 999),
and then the drive must be powered up again to accept the new address.
Disables the rotary switches, and requires using one of the following:
• 0:300 - [Net Addr Sel] selects the source for the interface IP address, which is one of the
following:
–Adapter Parameters
– BOOTP server (default)
– DHCP server firmware
Connecting the Interface to
the Network
IMPORTANT
When using the interface rotary switches, set the IP address before power
is applied because the interface uses the switch settings that it detects
when it first receives power.
The switch settings can be verified by viewing Port 0 Diagnostic Item number
68, see Table 21 on page 78
with any of the following drive configuration tools:
•20-HIM-A6 and 20-HIM-C6S for PowerFlex 755T drives
•Integrated touch screen display (eHIM) or standard HIM (20-750-CS6)
for PowerFlex 6000T drives.
•Connected Components Workbench software, release 11 or later.
Also, you can use 0:301 - [Net Addr Src], a read-only parameter, to verify the
active setting for 0:300 - [Net Addr Sel].
ATTE NT IO N: Risk of injury or death exists. The PowerFlex drive can contain high
voltages that can cause injury or death. Remove power from the drive, and then
verify that power has been discharged before connecting the built-in EtherNet/IP
adapter to the network. Verify that the DC bus has been discharged.
1. Remove power from the drive and discharge any stored power.
2. To access the drive control pod, open the drive door.
3. Use electrostatic discharge (ESD) control precautions.
4. Connect one end of an Ethernet cable to the network.
See Figure 5
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202117
for an example of wiring to an EtherNet/IP network.
Chapter 2 Configure the Adapter
Ethernet Switch
Controller
PowerFlex 755T drives
(each with built-in EtherNet/IP adapter)
Apply Power
Figure 5 - Connecting the Ethernet Cable to the Network
5. Route the other end of the Ethernet cable through the bottom plate of the
drive to either of the Ethernet connectors on the bottom edge of the control
board. See item 4 in Components on page 9.
ATTENTION: Risk of equipment damage, injury, or death exists.
• Unpredictable operation can occur if you fail to verify that parameter settings are
compatible with your application. Verify that settings are compatible with your
application before power is applied to the drive.
• Wear personal protective equipment (PPE) to avoid death or injury when applying
power with the drive door open.
1. Close the cabinet door for the drive.
2. Apply power to the drive.
The built-in EtherNet/IP adapter receives its power from the drive.
ATTENTION: Risk of injury or equipment damage exists. When a system is
configured for the first time, there can be unintended or incorrect machine
motion. Disconnect the motor from the machine or process during initial
system testing.
3. Check the status indicators either by using status parameters, HIM
status, or the software tool status.
When you apply power to the built-in EtherNet/IP adapter for the first
time, its EtherNet/IP status indicator is steady green or flashes green
after an initialization.
If it is red or remains off, see Start-up Status Indications on page 18
.
Start-up Status Indications
18Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
After power is applied, the drive STS (status) indicator and the built-in
EtherNet/IP adapter ENET, LNK1, and LNK2 status indicators can be
monitored via status parameters, HIM status, and the software tool status. If
personal protective equipment is worn, you can also view status indicators on
the front of the drive (Figure 6
status indications.
). See Table 2 on page 19 for possible startup
Chapter 2 Configure the Adapter
1
2
3
Figure 6 shows an example of the drive status indicator location near a HIM
under the drive cover. Your HIM may appear differently or in another location.
Figure 6 - Drive and Interface Status Indicators
Table 2 - Drive and Interface Start-up Status Indications
ItemNameColorStateDescription
Drive STS Indicator
Green
Yellow
1STS (Status)
Red
Red/
Yellow
Yellow/
Green
Green/Red
Built-in EtherNet/IP adapter Status Indicators
UnlitOff
Red
2ENET
Red/Green
Green
FlashingDrive ready but is not running, and no faults are present.
SteadyDrive is running and no faults are present.
When running, a type 2 (non-configurable) alarm condition exists –
Flashing
the drive continues to run. When stopped, a start inhibit condition
exists and the drive cannot be started (see drive 0:603 - [Start Inhibit]).
Steady
Flashing
A type 1 (configurable) alarm condition exists, but the drive
continues to run.
A major fault has occurred. The drive stops. it cannot be started
until the fault condition is cleared.
SteadyA non-resettable fault has occurred.
A minor fault has occurred. If not enabled a minor fault, acts like a
Flashing
Alternately
major fault. If minor faults are enabled and the drive is running, the
drive continues to run. The system is brought to a stop under
system control. The fault must be cleared to continue.
Flashing
Alternately
Flashing
Alternately
When running, a type 1 (configurable) alarm exists and the drive
continues to run.
The drive is updating firmware.
The interface and/or network is not powered, the interface is not
properly connected to the network, or the interface needs an IP
address.
A network connection has timed out, the rotary switches have been
changed since power-up, or the network configuration is invalid.
The interface failed the duplicate IP address detection test or its
DCHP lease has expired.
The interface is performing a self-test.
The interface is properly connected, but the drive is not controlled
by the network.
The interface is properly connected, and the drive is controlled by
the network.
Flashing
Steady
Flashing
Alternately
Flashing
Steady
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202119
Chapter 2 Configure the Adapter
Table 2 - Drive and Interface Start-up Status Indications (Continued)
ItemNameColorStateDescription
UnlitOffThe interface does not have an Ethernet link.
LNK1 and
3
LNK2
Green
(100 Mbps)
or
Yellow
(10 Mbps)
Flashing
Steady
The interface is properly connected and is transmitting or receiving
data packets on the network.
The interface is properly connected, but is not transmitting or
receiving on the network.
After verifying correct operation, place the drive HIM bezel to its closed
position if necessary and install the drive cover. See Drive Status Indicator
Descriptions on page 80 for more details.
Configuring and Verifying Key Drive Parameters
The drive can be separately configured for the command logic and reference
functions in various combinations. For example, you could set the drive to
have the logic command come from a peripheral or terminal block but have the
reference come from the network. Or you could set the drive to have its control
come from the network with the reference that comes from another peripheral
or terminal block. Or you could set the drive to have both its logic command
and reference come from the network.
The following steps in this section assume that the drive receives the logic
command and reference from the network.
1. To access the required parameters in this procedure, verify that drive
parameter 0:30 - [Access Level] is set to ‘1’ (Advanced) or ‘2’ (Expert).
2. To set the drive velocity reference, use drive 10:1800 - [VRef A Sel].
a. Set the Port field to ‘10 - Pri MtrSideCtrl’ as shown.
b. Set the Parameter field to point to Port 0, which contains the
EtherNet/IP adapter.
c. Then choose Parameter 211 [Emb Enet Ref].
3. Verify that drive 10:350 - [VRef Source] matches your entry to 10:1800 [VRef A Sel].
Any velocity reference that is commanded from the network can be
monitored by using 0:1914 - [VRef Command]. If a problem occurs, this
verification step provides the diagnostic capability to determine whether
the drive, interface, or the network is the cause.
4. If hard-wired discrete digital inputs are not used to control the drive,
verify that all unused digital input drive parameters are set to ‘0’ (Not
Used). These parameters are located in Port 0, in the file Feedback and I/
O, group Command.
20Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Chapter 2 Configure the Adapter
Default = 0.0.0.0255.255.255.255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
Use Interface Parameters to
Set the IP Address
By default, the interface is configured to use a DHCP server as the source for
the IP address interface, subnet mask, and gateway address. To use interface
parameters instead, you must first change the source for the node address to Parameters by using 0:300 - [Net Addr Sel]. Set the associated interface
parameters as described in the following subsections.
Using a HIM to Access Parameters
If your drive has a HIM, it can be used to access parameters in the interface.
From the Status screen (20-HIM-A6 or 20-HIM-C6S) or the Dashboard
Parameters tab (eHIM), navigate to Port 0 where the built-in EtherNet/IP
adapter resides.
From the Port 0, you can set the source for the network address, set the
IP address, subnet mask, and gateway address.
For details on how to view and edit parameters, see PowerFlex 20-HIM-A6/C6S HIM (Human Interface Module) User Manual,
publication 20HIM-UM001
.
Change the Source for the Network Address
1. Verify that the IP address switches, see Table 1 on page 17 are set to 999.
2. Set the value of 0:300 - [Net Addr Sel] to ‘1’ (Parameters).
3. Reset the interface by cycling power or by using the HIM as described in
Resetting the Adapter
on page 28.
4. Set the IP address, subnet mask, and gateway address by using interface
parameters by performing the steps in the following subsections.
Set the IP Address
1. Verify 0:300 - [Net Addr Sel] is set to ‘1’ (Parameters).
2. Set the value of 0:302 - [IP Addr Cfg 1] … 305 - [IP Addr Cfg 4] to a unique
IP address.
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202121
Chapter 2 Configure the Adapter
Default = 0.0.0.0255.255.255.255
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
Default = 0.0.0.0255.255.255.255
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
Set the Subnet Mask
1. Verify 0:300 - [Net Addr Sel] is set to ‘1’ (Parameters).
2. Set the value of 0:306 - [Subnet Cfg 1] … 309 - [Subnet Cfg 4] to the desired
value for the subnet mask.
•The subnet mask cannot be 0.0.0.0.
•The gate way address can be 0.0.0.0. If the gateway address is 0.0.0.0, the
drive can only communicate with devices on the same subnet as the
drive. It is not able to communicate with devices on other subnets.
•If the gateway address is not set to 0.0.0.0, then it must be set to an
address that is on the same subnet as the IP address of the drive.
Set the Gateway Address
1. Verify 0:300 - [Net Addr Sel] is set to ‘1’ (Parameters).
2. Set the value of 0:310 - [Gateway Cfg 1] … 313 - [Gateway Cfg 4] to the IP
address of the gateway device.
•The subnet mask cannot be 0.0.0.0.
•The gateway address can be 0.0.0.0. If the gateway address is 0.0.0.0, the
PowerFlex 755T can only communicate with devices on the same subnet
as the drive. It is not able to communicate with devices on other subnets.
•If the gateway address is not set to 0.0.0.0, then it must be set to an
address that is on the same subnet as the IP address of the drive.
3. Reset the interface by cycling power or by using the HIM as described in
Resetting the Adapter
on page 28.
22Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Chapter 2 Configure the Adapter
ValueSetting
1Parameters
2BOOTP
3DHCP (default)
Ethernet
Address
(MAC) Label
Location
Drive Control Pod
Ethernet Connectors
Front View - Main Control Board
Using a BOOTP or DHCP
Server
There are various BOOTP and DHCP servers available. The following
instructions use the Rockwell Automation BOOTP/DHCP Server. This is a free
standalone program that incorporates the functionality of standard BOOTP
and DHCP utilities with a graphical interface page installed automatically as
part of the RSLinx® software. It is available at the Product Compatibility and
Download Center (PCDC) at rok.auto/pcdc
. From the website, choose the ‘Find
Downloads’ link and search for the word ‘BOOTP’). See the Read-me file and
online Help for directions and more information.
If the PowerFlex 6000T, 755TM, 755TR, or 755TL drive is connected to a
Stratix 6000 or Stratix 8000 managed Ethernet switch and the drive is set
for BOOTP or DHCP mode, the ‘dynamic IP address assignment by port’
(Stratix 6000) or ‘DHCP persistence’ (Stratix 8000) feature can be used to
set the IP address for the drive. For more details, see the Stratix 6000
Ethernet-Managed Switch User Manual, publication 1783-UM001
, or the
Stratix 8000 and Stratix 8300 Ethernet Managed Switches User Manual,
.
IMPORTANT
publication 1783-UM003
When the DHCP lease expires, the adapter stops communicating on the
network. A power cycle or option module reset is required.
1. Depending on the type of server (BOOTP or DHCP) being used, set 0:300
- [Net Addr Sel] to either ‘2’ (BOOTP) or ‘3’ (DHCP) respectively.
2. Make note of the Ethernet Address (MAC) of the interface hardware,
which is used in step 5
.
There are two ways to find the media access control (MAC) address:
• Remove the drive cover and locate the hardware Ethernet Address
label on the main control board of the drive (Figure 7
Figure 7 - Location of the Interface Hardware Address Label
).
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202123
Chapter 2 Configure the Adapter
• Use the HIM to access drive Port 0 and access the built-in EtherNet/IP
adapter DIAGNOSTIC folder screen. Then scroll to Diagnostic Items
43…48 (HW Addr 1…6) to view the hardware Ethernet Address (MAC) of
the interface. Finally, convert these decimal values to hex values.
The eHIM uses local subnet to detect the drive connected to the Stratix
switch. You are able to view the drive profile and change the IP address
in the Device Definition page within the overview tab.
3. On a computer that is connected to the EtherNet/IP network, start the
BOOTP/DHCP software.
4. Edit the Network Settings to match your network.
BoxType
Subnet MaskThe subnet mask for the built-in EtherNet/IP of the interface network.
GatewayThe IP address of the gateway device on the network of the interface.
Primary DNS
Secondary DNS
Domain Name
Optional - the address of the primary Domain Name Service (DNS) server that is used to
locate devices on the network by name instead of by IP address.
Optional - the address of the secondary DNS server to be used on the local end of the link
for negotiating with remote devices when the primary DNS server is unavailable.
Optional - The text name that corresponds to the network containing the BOOTP/DHCP
server and the drive being configured.
5. In the BOOTP/DHCP Request History list, either double-click the
Ethernet Address (MAC) of the interface noted in step 2
, or click New in
the Relation List.
6. Edit the following:
BoxType
IP address A unique IP address for the interface
Host NameOptional - a text name for the drive being configured
DescriptionOptional - text to describe the device that is saved only in the BOOTP/DHCP software
7. After the BOOTP/DHCP Server has provided an IP address, to assign this
configuration permanently to the interface, select the device in the
Relation List, and click Disable BOOTP/DHCP.
When power is cycled on the interface, it uses the configuration that you
assigned it and does not issue new BOOTP or DHCP requests.
8. From the File menu, choose Save to save the Relation List.
Setting the Data RateBy default, the interface is set to autodetect, so it automatically detects the data
rate and duplex setting that is used on the network. If you must set a specific
data rate and duplex setting, use the 0:314 - [Net Rate Cfg 1] and 0:316 - [Net Rate Cfg 2] values. These values determine the Ethernet data rate and duplex
settings that the interface uses to communicate.
1. Verify that the Ethernet cable is connected to Ethernet port 1 or port 2 to
change the data rate or duplex setting. Port 1 is the connector closest to
the front edge of the control board.
2. Set the value of 0:314 - [Net Rate Cfg 1] or 0:316 - [Net Rate Cfg 2] to the
data rate at which your network is operating.
ValueData Rate
0Autodetect (default)
110 Mbps Full
210 Mbps Half
3100 Mbps Full
4100 Mbps Half
24Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Chapter 2 Configure the Adapter
Auto detection of the data rate and duplex works only if the device (usually
a switch) on the other end of the cable is also set to detect the rate/duplex.
If one device is using fixed data rate/duplex, the other device must use the
same fixed settings.
3. Reset the interface by cycling power or by using the HIM as described in
Resetting the Adapter on page 28.
Setting Communication
Hierarchy
A hierarchy determines the type of device with which the interface exchanges
data. In a controller hierarchy, the interface exchanges data with the
ControlLogix® controller or another communication bridge.
When a multicast I/O connection is used or when the interface does not have a
valid gateway address, the controller must be on the same IP subnet as the
interface to establish an I/O connection.
Setting a Controller Hierarchy
To set the Controller hierarchy, follow the instructions in this section to enable
datalinks to read and write data.
When using the ControlLogix controller, there is no need to configure
datalink parameters. They are assigned when configuring the drive Addon Profile, see Configure Input and Output Data on page 36
Enable Datalinks to Write Data
The controller output image (controller outputs-to-drive) always contains the
logic command and reference fields. It can also have 0...16 additional 32-bit
parameters (datalinks). They are configured using 0:321 - [DL From Net 01] … 336 - [DL From Net 16]. The output connection size in the controller determines
the number of datalinks that are actively used. See the respective controller
example sections in Chapter 3
page 31 for more information on setting the connection size.
Configuring the Drive in a Logix System on
.
IMPORTANT
When using a ControlLogix controller, configure the datalink parameters now
as described in this section.
0:321 - [DL From Net 01] …336 - [DL From Net 16] control which parameters
receive the values from the network. These parameters apply to the drive,
option module, or any other connected peripheral. You can use a HIM, or
another drive configuration tool, such as Connected Components Workbench
software, to select the drive or peripheral by port number and the parameter by
name. As an alternate method, set the parameter value manually by number by
using this formula:
From Net Parameter Value = (10000 * Port Number) + (Destination Parameter Number)
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202125
Always use the datalink parameters in consecutive numerical order. Start
with the first parameter. For example, use 0:321… 323 to configure three
datalinks to write data. Otherwise, the network I/O connection size is larger
than necessary, which needlessly increases controller response time and
memory usage.
Chapter 2 Configure the Adapter
For example, if you want to use 0:321 - [DL From Net 01] to write to Parameter
3 of an optional encoder card plugged into drive Port 5. By using the formula,
the value for 0:321- [DL From Net 01] would be (10000 * 5) + (3) = 50003.
Follow these steps to enable datalinks to write data.
1. Set the values of only the required number of contiguous controller-todrive datalinks that write data to the drive and are included in the
network I/O connection.
2. Reset the drive by cycling power to the drive or by using the Reset Device
function of the HIM located in the DIAGNOSTIC folder for the drive. See
Resetting the Adapter
on page 28.
3. Because the logic command and reference are always used in the
interface, configure the parameters in the drive to accept the logic
command and reference from the interface.
When using the controller for speed reference via the interface, set two
fields in drive 10:1800 - [VRef A Sel].
a. Set the Port field for the drive.
b. Set the Parameter field to point to the parameter containing the
reference value received from the parameter containing the reference
value that is received from the embedded EtherNet/IP adapter 0:211 -[Emb Enet Ref].
Also, verify that the mask parameters in the drive, (for example,
0:41 - [Logic Mask]) are configured to receive the desired logic
command from the interface. See the drive documentation for details.
The interface is ready to receive input data and transfer control data
from the controller.
Next, configure the controller to recognize and transmit I/O to the interface.
See Chapter 3
Configuring the Drive in a Logix System on page 31.
Enable Datalinks to Read Data
The controller input image (drive-to-controller inputs) always contains the
logic status and feedback fields. It can also have 0...16 additional 32-bit
parameters (datalinks). They are configured using 0:340 - [DL To Net 01] … 355 - [DL To Net 16]. The input connection size in the controller determines the
number of datalinks that are actively used. See the respective controller
example sections in Chapter 3
page 31 for more information on setting the connection size.
IMPORTANT
Always use the datalink parameters in consecutive numerical order. Start
with the first parameter. For example, use 0:340…344 to configure five
datalinks to read data. Otherwise, the network I/O connection size is larger
than necessary, which needlessly increases controller response time and
memory usage.
Configuring the Drive in a Logix System on
When using a ControlLogix controller, configure the datalink parameters now
as described in this section.
0:340 - [DL To Net 01] … 355 - [DL To Net 16] configure which parameters in the
drive, interface, or any other connected peripheral send the values to the
26Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Chapter 2 Configure the Adapter
network. Select the drive or peripheral by port number and the parameter by
name. Use the HIM, or another drive configuration tool such as Connected
Components Workbench software. As an alternate method, use this formula to
set the parameter value manually by number:
To Net Parameter Value = (10000 * Port Number) + (Origination Parameter Number)
For example, suppose that you want to use 0:340 - [DL To Net 01] to read
Parameter 2 of an optional I/O card plugged into drive Port 6. By using the
formula, the value for 0:340 - [DL To Net 01] would be (10000 * 6) + (2) = 60002.
Follow these steps to enable datalinks to read data.
1. Set the values of only the required number of contiguous drive-tocontroller datalinks that read data from the drive and are included in the
network I/O connection.
2. Reset the interface by cycling power or by using the HIM described in
Resetting the Adapter
on page 28.
The interface is configured to send output data to the controller. Configure the
controller to recognize and transmit I/O to the interface. See Chapter 3
Configuring the Drive in a Logix System on page 31
.
Setting a Fault ActionBy default, when the drive is controlled by the network or receives information
from the network; communication is disrupted. The drive responds by
faulting, if it is using I/O from the network. Possible causes include that the
network cable is disconnected, the controller is idle (in Program mode or
faulted), or an MSG instruction that is used for drive control is disrupted. You
can configure another response to these faults:
•Disrupted I/O communication by using 0:360 - [Comm Flt Action]
•An idle controller by using 0:361 - [Idle Flt Action]
•Disrupted Explicit Messaging for drive control via PCCC or the CIPbased network Assembly Object by using 0:363 - [Msg Flt Action]
ATTE NT IO N: Risk of injury or equipment damage exists. By default, these
parameters fault the drive:
• 0:360 - [Comm Flt Action]
• 0:361 - [Idle Action]
• 0:363 - [Msg Flt Action]
You can configure these parameters so that the drive continues to run. However,
verify that the settings of these parameters do not create a risk of injury or
equipment damage. When commissioning the drive, verify that your system
responds correctly to various situations.
Changing the Fault Action
Set the values of 0:360 - [Comm Flt Action], 361 - [Idle Flt Action], and 363 [Msg Flt Action] to an action that meets your application requirements.
Table 3 - Fault Action Parameters
ValueActionDescription
0FaultThe drive is faulted and stopped (default).
1StopThe drive is stopped, but not faulted.
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202127
Chapter 2 Configure the Adapter
Table 3 - Fault Action Parameters (Continued)
ValueActionDescription
2Zero DataThe drive is sent ‘0’ values for data. This value does not command a stop.
3Hold LastThe drive continues in its present state.
The drive is sent the data that you set in the fault configuration parameters:
• 0:364 - [Flt Cfg Logic] - A 32-bit value that is sent to the drive for logic
command
4Send Flt Cfg
• 0:365 - [Flt Cfg Ref] - A 32-bit REAL (Floating Point) value that is sent to
the drive for reference
• 0:366 - [Flt Cfg DL 01] … 381 - [Flt Cfg DL 16]) - A 32-bit Integer value that
is sent to the drive for a datalink. If the destination of the datalink is a
REAL (Floating Point) parameter, you must convert the desired value
to the binary representation of the REAL value.
Changes to these parameters take effect immediately. A reset is not required.
If communication is disrupted and then re-established, the drive automatically
receives commands over the network again.
Resetting the AdapterChanges to rotary switch settings and some interface parameters require that
you reset the adapter before the new settings take effect. You can reset the
interface by cycling power or by using the Reset Device function of the HIM
located in the DIAGNOSTIC folder for the drive.
Restore Interface
Parameters to Default
Configurations
ATT EN TI ON : Risk of injury or equipment damage exists. If the adapter is transmitting
control I/O to the drive, the drive can be faulted when you reset the adapter. Determine
how your drive responds before resetting the adapter.
Interface parameters can be restored in two ways:
•ALL—restores ALL parameters on the port to their default configuration
values.
•MOST—restores MOST parameters on the port —except the following,
which are used for network setup Port 0:
• 0:300 - [Net Addr Sel]
• 0:302…305 - [IP Addr Cfg 1…4]
• 0:306…309 - [Subnet Cfg 1…4]
• 0:310…313 - [Gateway Cfg 1…4]
• 0:314 - [Net Rate Cfg 1]
• 0:316 - [Net Rate Cfg 2]
IMPORTANT
Because the built-in EtherNet/IP adapter is part of Port 0, restoring the
port defaults also resets other drive configuration settings that are
made in Port 0.
Using a 20-HIM-A6 or 20-HIM-C6S HIM
Follow these steps to restore interface parameters to their default
configuration values.
1. From the Status screen, scroll to Port 0, which is the drive
port contains the built-in EtherNet/IP interface.
2. Use the key to scroll to Port 0, which is the drive port contains
the built-in EtherNet/IP interface.
28Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Chapter 2 Configure the Adapter
3. Display the last viewed folder, select the key.
4. To scroll to the MEMORY folder, use the keys.
5. To select Set Defaults, use the or key.
6. Press the (Enter) key.
The Set Defaults popup box appears.
7. Press the (Enter) key again.
The warning popup box appears.
8. Reset parameters to their default configuration values by selecting the
appropriate option:
• To restore MOST parameters to default configurations, press the
MOST soft key.
• To restore ALL parameters, press the ALL soft key.
• To cancel, press the ESC soft key.
Viewing the Interface Status
Using Parameters
IMPORTANT
When performing a Set Defaults, the drive can detect a conflict and then
not allow this function to occur. If a conflict happens, first resolve the
conflict and then repeat this Set Defaults procedure. Common reasons for
a conflict include a drive that is running or a controller in Run mode.
9. Reset the interface by cycling power or by using the HIM as described in
Resetting the Adapter
on page 28.
Using enhanced HIM
Reset parameters to their default configuration by navigating to the
Parameters tab (enhanced HIM) and click the Reset to Defaults button.
The following parameters provide information about the status of the
interface. You can view these parameters at any time.
Table 4 - Interface Status Parameters
Interface ParameterDescription
0:356 - [DLs From Net Act]
0:357 - [DLs To Net Act]
0:301 - [Net Addr Src]
0:315 - [Net Rate Act 1]The data rate/duplex used by the ENET1 network port on the interface.
0:317 - [Net Rate Act 2]The data rate/duplex used by the ENET2 network port on the interface.
The number of controller-to-drive datalinks that are included in the network I/O
connection (controller outputs).
The number of drive-to-controller datalinks that are included in the network I/O
connection (controller inputs).
Displays the active source for the interface node address, subnet mask, and
gateway address.
‘Switches’ (0) – The address comes from the rotary switches on the main control
board.
‘Parameters’ (1) – The addresses come from 0:302 [IP Addr Cfg 1]…313 [Gateway
Cfg 4].
‘BOOTP’ (2) – The address comes from a BOOTP server on the network.
‘DHCP’ (3) – The address comes from a DHCP server on the network and could be a
Stratix switch.
Rockwell Automation Publication 750COM-UM009B-EN-P - April 202129
Chapter 2 Configure the Adapter
Updating the Interface
Firmware
The interface firmware is contained within the drive firmware. The interface
firmware can be updated over the network.
When updating firmware over the network, you can use the Allen-Bradley®
ControlFLASH Plus™ software tool.
To obtain a firmware update for this interface, go to rok.auto/pcdc
website contains all firmware update files and associated Release Notes that
describe the following items:
•Firmware update enhancements and anomalies
•How to determine the existing firmware revision
•How to update the firmware using ControlFLASH Plus software
. This
30Rockwell Automation Publication 750COM-UM009B-EN-P - April 2021
Loading...
+ 104 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.