Rockwell Automation PowerFlex 755 Drive User Manual

Page 1
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter
USER MANUAL
Firmware Version 1.xxx
Page 2
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at
literature) describes some important differences between solid state equipment and
hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
http://www.rockwellautomation.com/
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
!
environment, which may lead to personal injury or death, property damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
!
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
Burn Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be at dangerous temperatures.
Allen-Bradley, PowerFlex, ControlFLASH, DPI, DriveExplorer, DriveExecutive, DriveTools SP, RSLogix, ControlLogix, PLC-5, SLC 500, and
MicroLogix 1100 are either registered trademarks or trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA and ControlNet International, Ltd. Ethernet is a trademark of Digital Equipment Corporation, Intel Corporation, and Xerox Corporation.
Windows, Microsoft, and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Page 3

Summary of Changes

This is the first release of the PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 4
soc-ii Summary of Changes
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 5
Preface About This Manual
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Chapter 1 Getting Started
Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Chapter 2 Installing the Adapter
Preparing for an Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Setting the IP Address Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Connecting the Adapter to the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Applying Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Commissioning the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6

Table of Contents

Chapter 3 Configuring the Adapter
Chapter 4 Configuring the I/O
Configuration Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Using the Enhanced PowerFlex 7-Class HIM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Using BOOTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Setting the IP Address, Subnet Mask, and Gateway Address. . . . . . . . . . . . . . . . . . . 3-5
Setting the Data Rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Selecting Master-Slave or Peer-to-Peer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Setting a Fault Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Setting Web Access Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Resetting the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Restoring Adapter Parameters to Factory Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Viewing the Adapter Status Using Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Flash Updating the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Using RSLinx Classic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
ControlLogix Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Limitations When Using PLC-5, SLC 500, and MicroLogix 1100 . . . . . . . . . . . . . 4-20
PLC-5 Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21
SLC 500 Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29
MicroLogix 1100 Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-37
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 6
ii Table of Contents
Chapter 5 Using the I/O
About I/O Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Understanding the I/O Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Using Logic Command/Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Using Reference/Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Using Datalinks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Example Ladder Logic Program Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
ControlLogix Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
PLC-5, SLC 500, and MicroLogix 1100 Example . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
Chapter 6 Using Explicit Messaging
About Explicit Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Performing Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
ControlLogix Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
PLC-5 Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
SLC 500 Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18
MicroLogix 1100 Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-32
Chapter 7 Troubleshooting
Understanding the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
ENET Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
LINK Status Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Viewing Adapter Diagnostic Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Viewing and Clearing Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
Chapter 8 Viewing the Adapter Web Pages
Accessing the Adapter Web Home Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Process Display Pop-up Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
TCP/IP Configuration Web Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Configure E-mail Notification Web Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
DPI Device Information Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Appendix A Specifications
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Regulatory Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Appendix B Adapter Parameters
About Parameter Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
How Parameters Are Organized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 7
Appendix C EtherNet/IP Objects
Identity Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2
Assembly Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
Register Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
PCCC Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-6
DPI Device Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-10
DPI Parameter Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-13
DPI Fault Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-19
DPI Alarm Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-21
DPI Diagnostic Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-23
DPI Time Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-25
Host DPI Parameter Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-28
TCP/IP Interface Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-34
Ethernet Link Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-36
Appendix D Logic Command/Status Words for PowerFlex 750-Series Drives
Logic Command Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Logic Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
Table of Contents iii
Glossary
Index
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 8
iv Table of Contents
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 9

Related Documentation

Preface

About This Manual

Topic Page
Related Documentation Rockwell Automation Support P-2 Conventions Used in This Manual P-2
For: Refer to: Publication
EtherNet/IP EtherNet/IP Planning and Installation Manual EtherNet/IP
Performance and Application Guide
DriveExplorer™ http://www.ab.com/drives/driveexplorer, and
DriveTools™ SP (includes DriveExecutive™)
Enhanced PowerFlex 7-Class HIM
PowerFlex Drives
RSLinx® Classic Getting Results with RSLinx Guide, and
RSLogix™ 5 RSLogix™ 500 RSLogix™ 5000
ControlLogix® and 1756-ENBT or 1756-EN2T
PLC-5
SLC™ 500 and 1747-L5-xxx SLC 500 Modular Hardware Style User Manual 1747-UM011 MicroLogix™ 1100 MicroLogix 1100 Programmable Controllers User Manual 1763-UM001
®
750-Series AC
®
DriveExplorer online help (installed with the software) http://www.ab.com/drives/drivetools, and DriveExecutive
online help (installed with the software) Enhanced PowerFlex 7-Class HIM User Manual 20HIM-UM001
PowerFlex 750-Series AC Drives User Manual PowerFlex 750-Series Reference Manual
online help (installed with the software) RSLogix 5 Getting Results Guide*
RSLogix 500 Getting Results Guide* RSLogix 5000 Getting Results Guide*
* And online help (installed with the software)
EtherNet/IP Modules in Logix5000 Control Systems User Manual
Enhanced and Ethernet PLC-5 Programmable Controllers User Manual
P-1
ENET-IN001 ENET-AP001
750-UM001 750-RM001
LINX-GR001
LG5-GR001 LG500-GR001 9399-RLD300GR
ENET-UM001
1785-UM012
You can view or download publications at
www.rockwellautomation.com/literature
technical documentation, contact your local Rockwell Automation distributor or sales representative.
To find your local Rockwell Automation distributor or sales representative, visit www.rockwellautomation.com/locations
For information such as firmware updates or answers to drive-related questions, go to the Drives Service & Support web site at www.ab.com/
support/abdrives and click on the “Downloads” or “Knowledgebase”
link.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
. To order paper copies of
.
Publication 750COM-UM001A-EN-P
Page 10
P-2 About This Manual

Rockwell Automation Support

Rockwell Automation, Inc. offers support services worldwide, with over 75 sales/support offices, over 500 authorized distributors, and over 250 authorized systems integrators located through the United States alone. In addition, Rockwell Automation, Inc. representatives are in every major country in the world.
Local Product Support
Contact your local Rockwell Automation, Inc. representative for:
Sales and order support
Product technical training
Warranty support
Support service agreements
Technical Product Assistance
For technical assistance, please review the information in Chapter 7,
Troubleshooting
Allen-Bradley Technical Support web site at www.ab.com/support/
abdrives or contact Rockwell Automation, Inc.
, first. If you still have problems, then access the

Conventions Used in This Manual

The following conventions are used throughout this manual:
Parameter names are shown in the format Parameter xx - [*]. The
xx represents the parameter number. The * represents the parameter name — for example Parameter 01 - [DL From Net Cfg 01].
Menu commands are shown in bold type face and follow the format
Menu > Command. For example, if you read “Select File > Open,” you should click the File menu and then click the Open command.
The firmware release is displayed as FRN X.xxx. The “FRN”
signifies Firmware Release Number. The “X” is the major release number. The “xxx” is the minor update number.
RSLinx Classic (version 2.52), RSLogix 5 (version 7.20), RSLogix
500 (version 7.20), and RSLogix 5000 (version 16) were used for the screen shots in this manual. Different versions of the software may differ in appearance and procedures.
This manual provides information about the EtherNet/IP adapter
embedded on the Main Control Board in PowerFlex 755 drives, and using it for network communication.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 11

Chapter 1

Getting Started

The EtherNet/IP adapter, embedded on the Main Control Board in PowerFlex 755 drives, is used for network communication.
Topic Page
Components Features 1-2 Compatible Products 1-3 Required Equipment 1-3 Safety Precautions 1-4 Quick Start 1-5 Status Indicators 1-6
1-1

Components

Drive Control Pod
Figure 1.1 Components of the Embedded EtherNet/IP Adapter
(shown with HIM bezel open and drive cover removed)
Drive STS Indicator
Item Part Description
5
6
4
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
Status
Indicators
IP Address
Switches
Ethernet
Connector
DPI Port 2 Cable connection for
Two LEDs that indicate the status of the adapter and network communications. Refer to Chapter 7
Troubleshooting
Sets the IP address of the embedded adapter when not using BOOTP or adapter parameters. Refer to Setting the IP Address
Switches on page 2-2.
An RJ-45 connector for the Ethernet cable. The connector is CAT-5 compliant to ensure reliable data transfer on 100Base-TX Ethernet connections.
handheld and remote options.
,
.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 12
1-2 Getting Started

Features

The features of the embedded EtherNet/IP adapter include:
Switches to set an IP address before applying power to the drive—or
you can disable the switches and use a BOOTP server or adapter parameters to configure the IP address.
Compatibility with various configuration tools to configure the
embedded EtherNet/IP adapter and host drive. The tools include the enhanced PowerFlex 7-Class HIM (Human Interface Module) on the drive, and drive-configuration software such as DriveExplorer (version 6.01 or higher) or DriveExecutive (version 5.01 or higher).
Status indicators that report the status of the embedded EtherNet/IP
adapter and network communications. They are visible when the drive cover is open or closed.
Parameter-configurable 32-bit Datalinks in the I/O to meet
application requirements (16 for writing data from the network, and 16 for reading data to the network).
Explicit Messaging support.
Master-Slave or Peer-to-Peer hierarchy that can be configured to
transmit data to and from either a controller or another PowerFlex 750-Series drive on the network.
User-defined fault actions to determine how the embedded EtherNet/
IP adapter and its host PowerFlex 755 drive respond to:
I/O messaging communication disruptions (Comm Flt Action)Controllers in idle mode (Idle Flt Action)Peer device communication disruptions (Peer Flt Action)Explicit messaging disruptions for drive control via PCCC and
the CIP Register Object (Msg Flt Action)
Web pages, viewed using a web browser, that show information
about the embedded EtherNet/IP adapter, its host drive, and DPI devices connected to the drive.
Configurable e-mail messaging to desired addresses when selected
drive faults occur and/or are cleared, and/or when the embedded EtherNet/IP adapter takes a communication or idle fault action.
Support for DPI routing, enabling access to any networked
PowerFlex 7-Class drive using DriveExplorer (version 6.01 or higher) to monitor and configure that drive and its connected peripherals.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 13
Getting Started 1-3

Compatible Products

Required Equipment

At the time of publication, the embedded EtherNet/IP adapter is compatible with Allen-Bradley PowerFlex 750-Series drives.
Equipment Shipped with the Drive
Since the EtherNet/IP adapter is embedded on the Main Control Board in the PowerFlex 755 drive, it is always an integral part of the drive and, therefore, is not shipped with installation instructions.
User-Supplied Equipment
To configure the embedded EtherNet/IP adapter, you must supply:
A small flathead screwdriverEthernet cable (for details, refer to the EtherNet/IP Media Planning
and Installation Manual, publication ENET-IN001)
Ethernet switch (for details, refer to the EtherNet/IP Performance
Application Solution, publication ENET-AP001)
Configuration tool, such as:
– Enhanced PowerFlex 7-Class HIM (20-HIM-A6/C6S) – DriveExplorer (version 6.01 or higher) – DriveExecutive stand-alone software (version 5.01 or higher) or
bundled with the DriveTools SP suite (version 5.01 or higher)
– BOOTP Server (version 2.1 or higher) for network setup only
Controller configuration software (such as RSLogix 5/500/5000)A PC connection to the EtherNet/IP network
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 14
1-4 Getting Started

Safety Precautions

Please read the following safety precautions carefully.
ATTENTION: Risk of injury or equipment damage exists. Only personnel familiar with drive and power products and the
!
associated machinery should plan or implement the installation, start up, configuration, and subsequent maintenance of the drive using this embedded adapter. Failure to comply may result in injury and/or equipment damage.
ATTENTION: Risk of equipment damage exists. The embedded adapter contains ESD (Electrostatic Discharge)
!
sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the adapter. If you are unfamiliar with static control procedures, refer to Guarding Against Electrostatic Damage (publication 8000-4.5.2).
ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting control I/O to the drive, the drive
!
may fault when you reset the adapter. Determine how your drive will respond before resetting the adapter.
ATTENTION: Risk of injury or equipment damage exists. Embedded adapter Parameters 54 - [Comm Flt Action], 55
!
- [Idle Flt Action], 56 - [Peer Flt Action], and 57 - [Msg Flt Action] let you determine the action of the adapter and drive
if I/O communication is disrupted, the controller is idle, Peer I/O is disrupted, or explicit messaging for drive control is disrupted. By default, these parameters fault the drive. You can set these parameters so that the drive continues to run. Precautions should be taken to ensure that the settings of these parameters do not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable or a controller in idle state).
ATTENTION: Risk of injury or equipment damage exists. When a system is configured for the first time, there may be
!
unintended or incorrect machine motion. Disconnect the motor from the machine or process during initial system testing.
ATTENTION: Risk of injury or equipment damage exists. The examples in this publication are intended solely for
!
purposes of example. There are many variables and requirements with any application. Rockwell Automation, Inc. does not assume responsibility or liability (to include intellectual property liability) for actual use of the examples shown in this publication.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 15
Getting Started 1-5

Quick Start

This section is provided to help experienced users quickly start using the embedded EtherNet/IP adapter. If you are unsure how to complete a step, refer to the referenced chapter.
Step Action Refer to…
1 Review the safety precautions for the adapter. Throughout This Manual 2 Verify that the PowerFlex drive is properly installed. PowerFlex 750-Series
AC Drive Installation Instructions
3 Set the adapter IP address.
A. When using the adapter switches, set the IP address.
When using a BOOTP server or adapter parameters to set the IP address, first perform Step 3B and all of Step 4. Then proceed with Step 5.
B. Verify that the PowerFlex drive is not powered. Then,
connect the embedded EtherNet/IP adapter to the network using an Ethernet cable.
4 Apply power to the drive.
A. Replace the drive cover or close the drive door.
B. The embedded EtherNet/IP adapter receives power from
the drive. Apply power to the drive. The status indicators should be green. If they flash red, there is a problem. Refer to Chapter 7
C. Configure/verify key drive parameters.
5 Configure the adapter for your application.
Set embedded EtherNet/IP adapter parameters for the following functions as required by your application:
IP address, subnet mask, and gateway address (only
when not using adapter switches)
Data rate
I/O configuration
Master-Slave or Peer-to-Peer hierarchy
Fault actions
Web enable/features
6 Configure the controller to communicate with the
adapter.
Use a controller configuration tool such as RSLogix to configure the master on the EtherNet/IP network to recognize the embedded EtherNet/IP adapter and drive.
7 Create a ladder logic program.
Use a controller configuration tool such as RSLogix to create a ladder logic program that enables you to:
Control the embedded EtherNet/IP adapter and drive
using I/O.
Monitor or configure the drive using Explicit messages.
, Troubleshooting.
Chapter 2 Installing the Adapter
Chapter 2 Installing the Adapter
Chapter 3 Configuring the Adapter
Chapter 4, Configuring the I/O
Chapter 5 Using the I/O
Chapter 6, Using Explicit Messaging
,
,
,
,
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 16
1-6 Getting Started

Status Indicators

Embedded EtherNet/IP adapter status indicators
on main control board in drive control pod.
The embedded EtherNet/IP adapter uses two status indicators to report its operating status. They can be viewed with the HIM cradle closed or open (Figure 1.2
Figure 1.2 Status Indicators
).
Indicators shown with HIM bezel closed and drive cover installed.
Item Name
ENET
LINK
After connecting the embedded EtherNet/IP adapter to the network and applying power to the drive, refer to Start-Up Status Indications
page 2-5 for possible start-up status indications and their descriptions.
on
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 17

Chapter 2

Installing the Adapter

Since the EtherNet/IP adapter is embedded on the Main Control Board in the PowerFlex 755 drive, the only required adapter installation is setting its IP address and connecting it to the network.
Topic Page
Preparing for an Installation Setting the IP Address Switches 2-2 Connecting the Adapter to the Network 2-4 Applying Power 2-4 Commissioning the Adapter 2-6
2-1

Preparing for an Installation

Before installing the embedded EtherNet/IP adapter:
Read the EtherNet/IP Performance and Application Guide
(publication ENET-AP001) and EtherNet/IP Media Planning and Installation Manual (publication ENET-IN001).
Understand IGMP Snooping/Ethernet Switches
Much of EtherNet/IP implicit (I/O) messaging uses IP multicast (including this embedded EtherNet/IP adapter) to distribute I/O control data, which is consistent with the CIP producer/consumer model. Historically, most switches have treated multicast packets the same as broadcast packets. That is, all multicast packets are re-transmitted to all ports.
IGMP snooping constrains the flooding of multicast traffic by dynamically configuring switch ports so that multicast traffic is forwarded only to ports associated with a particular IP multicast group.
Switches that support IGMP snooping “learn” which ports have devices that are part of a particular multicast group and only forward the multicast packets to the ports that are part of the multicast group.
Be careful as to what level of support a switch has of IGMP snooping. Some layer 2 switches that support IGMP snooping require a router (which could be a layer 3 switch) to send out IGMP polls to learn what devices are part of the multicast group. Some layer 2 switches can use IGMP snooping without a router sending polls. If your control system is a stand-alone network or is required to continue performing if the router is out of service, make sure the switch you are using supports IGMP snooping without a router being present.
Verify that you have all required equipment. Refer to Required
Equipment on page 1-3.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 18
2-2 Installing the Adapter

Setting the IP Address Switches

There are three methods for configuring the embedded EtherNet/IP adapter’s IP address:
Adapter Rotary Switches — Use the switches when working on a
simple, isolated network (for example, 192.168.1.xxx) that has other products with switches to set their IP addresses, does not need to be accessed from outside the network, and you prefer a simplified node addressing method. The three adapter switches are read when the drive powers up, and represent three decimal digits from top to bottom (see Figure 2.1 adapter will use that value as the lower octet of its IP address (192.168.1.xxx, where xxx = rotary switch settings), along with a subnet mask of 255.255.255.0 and there will be no gateway configured. Also, the setting for adapter Parameter 36 - [BOOTP] is automatically ignored.
See Figure 2.1 settings and their related descriptions.
Important:When using the adapter rotary switches, set the IP
BOOTP Server — Use BOOTP if you prefer to control the IP
addresses of devices using a server. The IP address, subnet mask, and gateway addresses will then be provided by the BOOTP server.
and its accompanying table for all possible switch
address before power is applied because the adapter uses the IP address it detects when it first receives power.
). If set to a valid address (001-254), the
Adapter Parameters — Use adapter parameters when you want
more flexibility in setting up the IP address, or need to communicate outside the control network using a gateway. The IP address, subnet mask, and gateway addresses will then come from the adapter parameters you set.
Important:Regardless of the method used to set the adapter’s IP
address, each node on the EtherNet/IP network must have a unique IP address. To change an IP address, you must set the new value and then remove and reapply power to (or reset) the adapter.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 19
Installing the Adapter 2-3
Figure 2.1 Setting the IP Address Switches
5
6
4
Hundreds
Position
Te n s
Position
Ones
Position
Possible Settings Description
000 Adapter will use, depending on Parameter 36 - [BOOTP], the BOOTP
001 - 254 Adapter will use the rotary switch settings for the IP address
255 - 887 Adapter will use, depending on Parameter 36 - [BOOTP], the BOOTP
888 Resets the adapter IP address function to factory defaults. Thereafter, the
889 - 998 Adapter will use, depending on Parameter 36 - [BOOTP], the BOOTP
999 (default settings)
setting or the adapter parameter settings for the IP address.
(192.168.1.xxx, where xxx = rotary switch settings).
setting or the adapter parameter settings for the IP address.
drive must be powered down, the switches set to a setting other than 888, and then the drive must be powered up again to accept the new address.
setting or the adapter parameter settings for the IP address. Disables the rotary switches. Adapter will use, depending on Parameter
36 - [BOOTP], the BOOTP setting or the adapter parameter settings for the IP address.
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 20
2-4 Installing the Adapter

Connecting the Adapter to the Network

ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause
!
injury or death. Remove power from the drive, and then verify power has been discharged before connecting the embedded EtherNet/IP adapter to the network.
1. Remove power from the drive.
2. Remove the drive cover.
3. Use static control precautions.
4. Connect an Ethernet cable to the EtherNet/IP network. See
Figure 2.2
Figure 2.2 Connecting the Ethernet Cable to the Network
Router
(optional)
for an example of wiring to an EtherNet/IP network.
PowerFlex 755 Drives
Controller
(ControlLogix shown with
1756-ENBT Bridge)
(each with embedded
EtherNet/IP adapter)

Applying Power

EtherNet/IP
Switch
5. Route the Ethernet cable through the bottom of the PowerFlex 755
drive, and insert the cable’s plug into the embedded EtherNet/IP adapter’s mating socket (item 3 in Figure 1.1
ATTENTION: Risk of equipment damage, injury, or death exists. Unpredictable operation may occur if you fail to verify
!
that parameter settings are compatible with your application. Verify that settings are compatible with your application before applying power to the drive.
Install the drive cover, and apply power to the drive. The embedded EtherNet/IP adapter receives its power from the drive. When you apply power to the embedded EtherNet/IP adapter for the first time, its “ENET” status indicator should be solid or flashing green after an initialization. If it is red, there is a problem. Refer to Chapter 7
Troubleshooting
.
).
,
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 21
Installing the Adapter 2-5
Start-Up Status Indications
After power has been applied, status indicators for the PowerFlex 755 drive and embedded EtherNet/IP adapter can be viewed on the front of the drive (Figure 2.3
Table 2.A
Figure 2.3 Drive and Adapter Status Indicators
.
). Possible start-up status indications are shown in
Table 2.A Drive and Adapter Start-Up Status Indications
Item Name Color State Description
Drive STS Indicator
STS
(Status)
ENET Unlit Off Adapter and/or network is not powered, adapter is not properly connected to the network,
LINK Unlit Off Adapter is not powered or is not transmitting on the network.
Green Flashing Drive ready but not running, and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing When running, a type 2 (non-configurable) alarm condition exists – drive continues to run.
When stopped, a start inhibit condition exists and the drive cannot be started (see drive parameter 933 - [Start Inhibit]).
Steady A type 1 (user configurable) alarm condition exists, but the drive continues to run.
Red Flashing A major fault has occurred. Drive will stop. Drive cannot be started until fault condition is
cleared.
Steady A non-resettable fault has occurred.
Red/Yellow Flashing Alternately A minor fault has occurred. Use drive parameter 950 - [Minor Flt Config] to enable. If not
Yellow/Green Flashing Alternately When running, a type 1 alarm exists. Green/Red Flashing Alternately Drive is flash updating.
Red Flashing An EtherNet/IP connection has timed out.
Red/Green Flashing Alternately Adapter is performing a self-test. Green Flashing Adapter is properly connected, but is not communicating with any devices on the network.
Green Flashing Adapter is properly connected and transmitting data packets on the network.
Steady Adapter failed the duplicate IP address detection test.
Steady Adapter is properly connected and communicating on the network.
Steady Adapter is properly connected, but is not transmitting on the network.
enabled, acts like a major fault. When running, the drive continues to run. System is brought to a stop under system control. The fault must be cleared to continue.
Embedded EtherNet/IP Adapter Status Indicators
or adapter needs an IP address.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 22
2-6 Installing the Adapter
Configuring/Verifying Key Drive Parameters
The PowerFlex 755 drive can be separately configured for the control and Reference functions in various combinations. For example, you could set the drive to have its control come from a peripheral or terminal block with the Reference coming from the network. Or you could set the drive to have its control come from the network with the Reference coming from another peripheral or terminal block. Or you could set the drive to have both its control and Reference come from the network.
The following steps in this section assume that the drive will receive the Logic Command and Reference from the network.
1. Use drive Parameter 545 - [Speed Ref A Sel] to set the drive speed
Reference to “Port 13 Reference” (the drive port dedicated to the embedded EtherNet/IP adapter).
2. Verify that drive Parameter 930 - [Speed Ref Source] is reporting
that the source of the Reference to the drive is “Port 13 Reference.” This ensures that any Reference commanded from the network can be monitored by using drive Parameter 002 - [Commanded SpdRef]. If a problem occurs, this verification step provides the diagnostic capability to determine whether the drive/adapter or the network is the cause.

Commissioning the Adapter

3. If hard-wired discrete digital inputs are not used to control the
drive, verify that all unused digital input parameters are set to “Not Used.”
To commission the embedded EtherNet/IP adapter, you must set a unique IP address. See the Glossary When using the adapter switches, refer to Setting the IP Address
Switches on page 2-2. When not using the adapter switches, use either a
BOOTP server or adapter parameters to set the IP address after connecting the adapter to the network and applying power to the drive.
By default, the adapter is configured so that you must set the IP address using a BOOTP server. For details, see Using BOOTP set the IP address using adapter parameters, refer to Setting the IP
Address, Subnet Mask, and Gateway Address on page 3-5.
Important:New settings for some adapter parameters (for example,
Parameters 38 - [IP Addr Cfg 1] through 41 - [IP Addr Cfg 4]) are recognized only when power is applied to the
adapter or it is reset. After you change parameter settings, cycle power or reset the adapter.
for details about IP addresses.
on page 3-2. To
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 23

Chapter 3

Configuring the Adapter

This chapter provides instructions and information for setting the parameters to configure the embedded EtherNet/IP adapter.
Topic Page
Configuration Tools Using the Enhanced PowerFlex 7-Class HIM 3-1 Using BOOTP 3-2 Setting the IP Address, Subnet Mask, and Gateway Address 3-5 Setting the Data Rate 3-7 Selecting Master-Slave or Peer-to-Peer 3-8 Setting a Fault Action 3-14 Setting Web Access Control 3-16 Resetting the Adapter 3-17 Restoring Adapter Parameters to Factory Defaults 3-17 Viewing the Adapter Status Using Parameters 3-18 Flash Updating the Adapter 3-18
3-1

Configuration Tools

Using the Enhanced PowerFlex 7-Class HIM

For a list of parameters, refer to Appendix B, Adapter Parameters. For definitions of terms in this chapter, refer to the Glossary
The embedded EtherNet/IP adapter stores parameters and other information in its own non-volatile memory. You must, therefore, access the adapter to view and edit its parameters. The following tools can be used to access the adapter parameters:
Tool Refer to…
Enhanced PowerFlex 7-Class HIM Enhanced PowerFlex 7-Class HIM User Manual BOOTP Server page 3-2 DriveExplorer Software
(version 6.01 or higher) DriveExecutive Software
(version 5.01 or higher)
If your drive has an enhanced PowerFlex 7-Class HIM, it can be used to access parameters in the adapter. For details on viewing and editing parameters, refer to the Enhanced PowerFlex 7-Class HIM User Manual (publication 20HIM-UM001).
http://www.ab.com/drives/driveexplorer, or DriveExplorer online help (installed with the software)
http://www.ab.com/drives/drivetools, or DriveExecutive online help (installed with the software)
.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 24
3-2 Configuring the Adapter

Using BOOTP

By default, the embedded EtherNet/IP adapter is configured to set its IP address, subnet mask, and gateway address by using a BOOTP utility. You can select from a variety of BOOTP utilities. These instructions use Rockwell’s BOOTP Server (version 2.3 or higher), a stand-alone program that incorporates the functionality of standard BOOTP utilities with a graphical interface. It is available from www.ab.com/networks/
bootp.html. Refer to the Readme file and online Help for detailed
directions and information.
TIP: If desired, you can disable BOOTP and configure the IP address, subnet mask, and gateway address by setting adapter parameters. For details, see Setting the IP Address, Subnet Mask, and Gateway
Address on page 3-5.
Configuring the Adapter Using BOOTP Server
1. Verify and note the adapter’s hardware Ethernet Address (MAC),
which will be used in Step 6. There are two ways to do this:
– Use the HIM to scroll to Port 13 and access the embedded
EtherNet/IP adapter’s DIAGNOSTIC folder screen. Then scroll to Diagnostic Items 43 (HW Addr 1) through 48 (HW Addr 6) to view the adapter’s hardware Ethernet Address (MAC).
– Remove the drive cover and locate the adapter’s hardware
Ethernet Address (MAC) label on the drive’s Main Control Board (Figure 3.1
).
Figure 3.1 Adapter Hardware Address Label Location
8
2
9
1
0
Ethernet Address
(MAC) label location
Ethernet
Connector
Drive Control Pod
2. On a computer connected to the EtherNet/IP network, start the
BOOTP software. The BOOTP Server window (Figure 3.2
) appears.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 25
Configuring the Adapter 3-3
Figure 3.2 BOOTP Server Window
3. To properly configure devices on your EtherNet/IP network, you
must configure settings in the BOOTP software to match the network. Select Tools > Network Settings to display the Network Settings window (Figure 3.3
).
Figure 3.3 Network Settings Window
4. Edit the following:
Box Type
Subnet Mask Gateway Primary DNS The address of the primary DNS server to be used on the local end of
Secondary DNS Optional—the address of the secondary DNS server to be used on the
Domain Name The text name corresponding to the numeric IP address that was
(1)
For definitions of these terms, refer to the Glossary.
(1)
(1)
The subnet mask for the embedded EtherNet/IP adapter’s network. The IP address of the gateway device on the adapter’s network.
the link for negotiating with remote devices.
local end of the link for negotiating with remote devices when the primary DNS server is unavailable.
assigned to the server that controls the network.
5. Click OK to apply the settings. Devices on the network issuing
BOOTP requests appear in the BOOTP Request History list.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 26
3-4 Configuring the Adapter
6. In the BOOTP Request History list, either double-click the adapter’s Ethernet Address (MAC) noted in Step 1A or Step 1B, or click New in the Relation List. The New Entry dialog box (Figure 3.4 In the first case, the Ethernet Address (MAC) is automatically entered. In the latter case, you must manually enter it.
Figure 3.4 New Entry Dialog Box
7. Edit the following:
) appears.
Box Type
IP Address Host Name Optional Description Optional
(1)
8. Click OK to apply the settings. The adapter appears in the Relation List (Figure 3.5
Figure 3.5 BOOTP Server Window with Adapter in the Relation List
(1)
A unique IP address for the adapter
For definitions of these terms, refer to the Glossary.
) with the new settings.
9. To assign this configuration to the adapter permanently, select the
10. To save the Relation List, select File > Save.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
device in the Relation List and click Disable BOOTP/DHCP. When power is cycled on the adapter, it will use the configuration you assigned it and not issue new BOOTP requests.
TIP: To enable BOOTP for an embedded adapter that has had BOOTP disabled, first select the adapter in the Relation List, then click Enable BOOTP, and finally reset the adapter or power cycle the drive.
Page 27
Configuring the Adapter 3-5

Setting the IP Address, Subnet Mask, and Gateway Address

By default, the adapter is configured to set its IP address, subnet mask, and gateway address using a BOOTP server. If you want to set these attributes using the adapter parameters instead, you must first disable BOOTP and then set these network address parameters in the adapter.
Accessing Parameters in the Adapter
1. Display the Status screen, which is shown on HIM power up.
2. Use the or key to scroll to Port 13, which is the port
always dedicated to the embedded EtherNet/IP adapter.
3. Press the PAR# soft key to display the Jump to Param # entry pop-up box.
4. Use the numeric keys to enter the desired parameter number, or use the S or T soft key to scroll to the desired parameter number.
Disabling the BOOTP Feature
1. Set the value of Parameter 36 - [BOOTP] to “0” (Disabled).
Figure 3.6 Edit BOOTP HIM Screen
Value Setting
0 Disabled 1 Enabled (Default)
AUTO
ENTER
F
Stopped
0.00 Hz
Edit BOOTP
Disabled 0
0<<1
▲▼
ESC
2. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
After disabling the BOOTP feature, you can then configure the IP address, subnet mask, and gateway address using adapter parameters.
Setting an IP Address Using Parameters
1. Verify that Parameter 36 - [BOOTP] is set to “0” (Disabled). This parameter must be set to Disabled to configure the IP address using the adapter parameters.
2. Set the value of Parameters 38 - [IP Addr Cfg 1] through 41 - [IP Addr Cfg 4] to a unique IP address.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 28
3-6 Configuring the Adapter
Figure 3.7 Edit IP Addr Cfg 1 HIM Screen
Default = 0.0.0.0 255 . 255 . 255 . 255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
AUTO
F
0
ENTER
Stopped
0.00 Hz
Edit IP Addr Cfg 1
0 << 255
ESC
3. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
The ENET status indicator will be solid green or flashing green if the IP address is correctly configured.
Setting a Subnet Mask Using Parameters
1. Verify that Parameter 36 - [BOOTP] is set to “0” (Disabled). This parameter must be set to Disabled to configure the subnet mask using the adapter parameters.
2. Set the value of Parameters 42 - [Subnet Cfg 1] through 45 - [Subnet Cfg 4] to the desired value for the subnet mask.
Figure 3.8 Edit Subnet Cfg 1 HIM Screen
Default = 0.0.0.0 255 . 255 . 255 . 255
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
0
AUTO
ENTER
F
Stopped
0.00 Hz
Edit Subnet Cfg 1
0 << 255
ESC
3. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
Setting a Gateway Address for the Adapter Using Parameters
1. Verify that Parameter 36 - [BOOTP] is set to “0” (Disabled). This parameter must be set to Disabled to configure the gateway address using the adapter parameters.
2. Set the value of Parameters 46 - [Gateway Cfg 1] through 49 - [Gateway Cfg 4] to the IP address of the gateway device.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 29
Figure 3.9 Edit Gateway Cfg 1 HIM Screen
Configuring the Adapter 3-7

Setting the Data Rate

Default = 0.0.0.0 255 . 255 . 255 . 255
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
AUTO
F
0
ENTER
.
Stopped
0.00 Hz
Edit Gateway Cfg 1
0<<255
ESC
3. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
By default, the adapter is set to autodetect, so it automatically detects the data rate and duplex setting used on the network. If you need to set a specific data rate and duplex setting, the value of Parameter 50 - [Net Rate Cfg] determines the Ethernet data rate and duplex setting that the adapter will use to communicate. For definitions of data rate and duplex, refer to the Glossary
1. Set the value of Parameter 50 - [Net Rate Cfg] to the data rate at which your network is operating.
Figure 3.10 Edit Net Rate Cfg HIM Screen
Value Data Rate
0 Autodetect (default) 1 10Mbps Full 2 10Mbps Half 3 100Mbps Full 4 100Mbps Half
AUTO
ENTER
F
Stopped
0.00 Hz
Edit Net Rate Cfg
Autodetect 0
0<<4
▲▼
ESC
TIP: Auto detection of baud rate and duplex works properly only if the device (usually a switch) on the other end of the cable is also set to automatically detect the baud rate/duplex. If one device has the baud rate/duplex hard-coded, the other device must be hard-coded to the same settings.
2. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 30
3-8 Configuring the Adapter

Selecting Master-Slave or Peer-to-Peer

A hierarchy determines the type of device with which the adapter exchanges data. In a Master-Slave hierarchy, the adapter exchanges data with a master, such as a bridge or controller. In a Peer-to-Peer hierarchy, the adapter exchanges data with one or more EtherNet/IP adapters in other PowerFlex 750-Series drives. (The drives must have compatible Logic Command/Status words).
For both Master-Slave and Peer-to-Peer hierarchies, the devices exchanging data must be on the same IP subnet. See “IP Addresses” in the Glossary
Setting a Master-Slave Hierarchy
Enabling Datalinks To Write Data
The controller output image (controller outputs-to-drive) can have anywhere from 0 to 16 additional 32-bit parameters (Datalinks). They are configured using Parameters 01 - [DL From Net 01] through 16 - [DL From Net 16]. The number of Datalinks actively used is controlled by the connection size in the controller. See the respective controller example sections in Chapter connection sizes.
for information about IP subnets.
4 for more information on setting the
Important:Always use the Datalink parameters in consecutive
numerical order, starting with the first parameter. For example, use Parameters 01, 02, and 03 to configure 3 Datalinks to write data. Otherwise, the network I/O connection will be larger than necessary, which needlessly increases controller response time and memory usage.
TIP: When using a ControlLogix controller and an RSLogix 5000 Add-On Drive Profile (v16 or higher), there is no need to configure Datalink parameters at this time. They will be assigned when configuring the RSLogix 5000 Add-On Drive Profile (see Adding the
Drive/Adapter to the I/O Configuration on page 4-5).
When using a ControlLogix controller and the Generic Profile, or a PLC-5, SLC 500 or MicroLogix 1100 controller, configure the Datalink parameters now as described in this section.
Parameters 01 - [DL From Net 01] through 16 - [DL From Net 16] control which parameters in the drive, adapter, or any other connected peripheral receive the values from the network. The enhanced PowerFlex 7-Class HIM, DriveExplorer, and DriveExecutive provide user-friendly screens to help select the drive or peripheral by port number and the parameter by name. As an alternate method, the parameter value can be set manually by number using this formula:
From Net Parameter Value = (10000 * Port Number) + (Destination Parameter Number)
For example, suppose you want to use Parameter 01 - [DL From Net 01] to write to Parameter 03 of an optional encoder card plugged into
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 31
Configuring the Adapter 3-9
drive Port 5. Using the formula, the value for Parameter 01 - [DL From Net 01] would be (10000 * 5) + (3) = 50003.
1. Set the values of only the required number of contiguous Datalink
parameters needed to write data to the drive and that are to be included in the network I/O connection.
2. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
3. Since the Logic Command and Reference are always used in the adapter, configure the parameters in the drive to accept the Logic Command and Reference from the adapter. If the controller is going to be used for speed reference via the adapter, set Parameter 545 ­[Speed Ref A Sel] in a PowerFlex 755 drive to “Port 13 Reference” (the drive port dedicated to the embedded EtherNet/IP adapter). Also, verify that the mask parameters in the drive (for example, Parameter 324 - [Logic Mask]) are configured to receive the desired logic from the adapter. Refer to the documentation for your drive for details.
The adapter is ready to receive input data from the master (controller). You must now configure the controller to recognize and transmit I/O to the adapter. Refer to Chapter
Enabling Datalinks To Read Data
The controller input image (drive-to-controller inputs) can have anywhere from 0 to 16 additional 32-bit parameters (Datalinks). They are configured using Parameters 17 - [DL To Net 01] through 32 - [DL To Net 16]. The number of Datalinks actively used is controlled by the connection size in the controller. See the respective controller example sections in Chapter connection sizes.
Important:Always use the Datalink parameters in consecutive
numerical order, starting with the first parameter. For example, use Parameters 17, 18, 19, 20, and 21 to configure 5 Datalinks to read data. Otherwise, the network I/O connection will be larger than necessary, which needlessly increases controller response time and memory usage.
TIP: When using a ControlLogix controller and an RSLogix 5000 Add-On Drive Profile (v16 or higher), there is no need to configure Datalink parameters at this time. They will be assigned when configuring the RSLogix 5000 Add-On Drive Profile (see Adding the
Drive/Adapter to the I/O Configuration on page 4-5).
4, Configuring the I/O.
4 for more information on setting the
When using a ControlLogix controller and the Generic Profile, or a PLC-5, SLC 500 or MicroLogix 1100 controller, configure the Datalink parameters now as described in this section.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 32
3-10 Configuring the Adapter
Parameters 17 - [DL To Net 01] through 32 - [DL To Net 16] control which parameters in the drive, adapter, or any other connected peripheral send the values to the network. The enhanced PowerFlex 7-Class HIM, DriveExplorer, and DriveExecutive provide user-friendly screens to help select the drive or peripheral by port number and the parameter by name. As an alternate method, the parameter value can be set manually by number using this formula:
To Net Parameter Value = (10000 * Port Number) + (Origination Parameter Number)
For example, suppose you want to use Parameter 17 - [DL To Net 01] to read Parameter 2 of an optional I/O card plugged into drive Port 4. Using the formula, the value for Parameter 17 - [DL To Net 01] would be (10000 * 4) + (2) = 40002.
1. Set the values of only the required number of contiguous Datalink parameters needed to read data from the drive and that are to be included in the network I/O connection.
2. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
The adapter is ready to send output data to the master (controller). You must now configure the controller to recognize and transmit I/O to the adapter. Refer to Chapter
Setting the Adapter to Transmit Peer-to-Peer Data
Simple Peer I/O Configuration
The most common use of Peer I/O is to take the Logic Command and Reference from one drive and repeat it over Ethernet to one or more other drives. If scaling of the Reference is needed to enable drives to run at different but related speeds, use drive Parameter 609 - [TrmPct RefA Stpt]. The embedded EtherNet/IP adapter provides a simplified configuration method for simple Peer I/O.
Important:Because of the 32-bit REAL (floating point) Reference, the
following method works only if the drives transmitting and receiving are PowerFlex 750-Series drives.
To set up the master (broadcast) side of simple Peer I/O:
1. Set Parameters 89 - [To Peer Period] and 90 - [To Peer Skip] as desired for your application. Parameter 89 controls how frequently the adapter will transmit present data. Parameter 90 controls how many transmit opportunities can be skipped if the data to be transmitted has not changed.
4, Configuring the I/O.
2. Set Parameter 91 - [To Peer Enable] to a value of “1” (Cmd/Ref).
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 33
Figure 3.11 Edit To Peer Enable HIM Screen
Configuring the Adapter 3-11
Value Se ttin g
0 Off (Default) 1Cmd/Ref 2Custom
AUTO
ENTER
F
Stopped
0.00 Hz
Edit To Peer Enable
Off 0
0<<2
▲▼
ESC
To set up the slave (receiver) side of simple Peer I/O:
1. Set Parameter 80 - [Fr Peer Timeout] to a suitable timeout value for your application. This value should be greater than the product of Parameter 89 - [To Peer Period] and Parameter 90 - [To Peer
Skip] in the transmitting drive.
2. Set Parameters 81 - [Fr Peer Addr 1] through 84 - [Fr Peer Addr 4] to the IP address of the drive transmitting Peer I/O.
3. In each PowerFlex 750-Series slave drive, set drive parameter 308 -
[Direction Mode] to “1” (Bipolar) to ensure that it properly follows the master drive’s speed reference and commanded direction.
4. Set Parameter 85 - [Fr Peer Enable] to a value of “1” (Cmd/Ref).
Custom Peer I/O Configuration
Peer I/O also allows more flexibility in sending custom data over the network, but requires more configuration.
Important:Because of the 32-bit REAL (floating point) Reference, the
following method works only if the drives transmitting and receiving are PowerFlex 750-Series drives.
To set up the master (broadcast) side of custom Peer I/O:
1. Decide how many Datalink parameters you want to transmit. Set Parameter 87 - [DLs To Peer Cfg] to that value.
2. Determine how the Datalinks are allocated. The highest numbered
of the 16 Datalinks are allocated to Peer I/O. For example, if Parameter 87 - [DLs To Peer Cfg] is set to “3,” then Datalinks 14, 15, and 16 are allocated to Peer I/O. To avoid an overlap between Master-Slave and Peer I/O, make sure that Parameter 35 - [DLs To Net Act] plus Parameter 87 - [DLs To Peer Cfg] does not total more than 16.
3. Set Parameters 17 through 32 - [DL To Net 01-16] to the parameters you want to transmit, based on the allocation in Step 2.
4. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder so that changes to Parameter 87 - [DLs To Peer Cfg] take effect.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 34
3-12 Configuring the Adapter
5. Set Parameters 89 - [To Peer Period] and 90 - [To Peer Skip] as required for your application. Parameter 89 controls how frequently the adapter will transmit present data. Parameter 90 controls how many transmit opportunities can be skipped if the data to be transmitted has not changed.
6. Set Parameter 91 - [To Peer Enable] to a value of “2” (Custom).
To set up the slave (receiver) side of custom Peer I/O:
1. Decide how many pieces of data (Logic Command, Reference, and Datalink parameters) you want to receive. This must match the number of parameters transmitted by the master. Set Parameter 76
- [DLs Fr Peer Cfg] to that value.
2. Determine how the Datalinks are allocated. The highest numbered
of the 16 Datalinks are allocated to Peer I/O. For example, if Parameter 76 - [DLs Fr Peer Cfg] is set to “3,” Datalinks 14, 15, and 16 are allocated to Peer I/O. To avoid an overlap between Master-Slave and Peer I/O, make sure that Parameter 34 - [DLs From Net Act] plus Parameter 76 - [DLs Fr Peer Cfg] does not total more than 16.
3. Set Parameters 1 through 16 - [DL From Net 01-16] to the parameters you want to receive, based on the allocation in Step 2.
4. Set Parameter 80 - [Fr Peer Timeout] to a suitable timeout value for your application. This value should be greater than the product of Parameter 89 - [To Peer Period] and Parameter 90 - [To Peer Skip] in the transmitting drive.
Figure 3.12 Edit Fr Peer Timeout HIM Screen
AUTO
ENTER
F
Stopped
0.00 Hz
Edit Fr Peer Timeout
ESC
5. Set Parameter 56 - [Peer Flt Action] to the desired action if Peer I/O data is not received before the timeout is reached.
ATTENTION: Risk of injury or equipment damage exists. Parameter 56 - [Peer Flt Action] lets you determine the
!
action of the adapter and connected drive if the adapter is unable to communicate with the designated peer. By default, this parameter faults the drive. You can set this parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does not create a hazard of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable).
10.00 Secs
0.01 << 10.00
.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 35
Figure 3.13 Edit Peer Flt Action HIM Screen
Configuring the Adapter 3-13
Stopped
0.00 Hz
Edit Peer Flt Action
Fault 0
0<<4
▲▼
ESC
AUTO
ENTER
F
Value Description
0 Fault (Default) 1Stop 2 Zero Data 3 Hold Last 4 Send Flt Cfg
For more details about fault action, see Setting a Fault Action on
page 3-14.
6. Set Parameters 81 - [Fr Peer Addr 1] through 84 - [Fr Peer Addr 4] to the IP address of the drive transmitting the custom Peer I/O.
Figure 3.14 Edit Fr Peer Addr 1 Screen on the HIM
IP Address of Node Transmitting Custom Peer I/O
AUTO
F
0
ENTER
Default = 0.0.0.0
[Peer Inp Addr 1]
[Peer Inp Addr 2]
255 . 255 . 255 . 255
[Peer Inp Addr 3]
[Peer Inp Addr 4]
Stopped
0.00 Hz
Edit Fr Peer Addr 1
0 << 255
ESC
7. If a Logic Command is being sent, use Parameter 78 - [Logic Src Cfg] to set the Datalink number containing the Logic Command.
Otherwise, set Parameter 78 to a value of “0.” For bit definitions, refer to Appendix
D or the drive documentation.
8. If a Reference is being sent, use Parameter 79 - [Ref Src Cfg] to set the Datalink number containing the Reference. Otherwise, set Parameter 79 to a value of “0.”
9. In each PowerFlex 750-Series slave drive, set drive parameter 308 ­[Direction Mode] to “1” (Bipolar) to ensure that it properly follows the master drive’s speed reference and commanded direction.
10. Reset the adapter by power cycling the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder so that changes to Parameter 76 - [DLs Fr Peer Cfg] take effect.
11. Set Parameter 85 - [Fr Peer Enable] to a value of “2” (Custom).
Figure 3.15 Edit Fr Peer Enable HIM Screen
Stopped
0.00 Hz
Edit Fr Peer Enable
Off 0
0<<2
▲▼
ESC
AUTO
ENTER
F
Value Setting
0 Off (Default) 1Cmd/Ref 2Custom
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 36
3-14 Configuring the Adapter

Setting a Fault Action

By default, when I/O communications are disrupted (for example, the network cable is disconnected), the controller is idle (in program mode or faulted), and/or Peer I/O or explicit messaging for drive control is disrupted, the drive responds by faulting. You can configure a different response to:
Disrupted I/O communication by using Parameter 54 - [Comm Flt
Action].
An idle controller by using Parameter 55 - [Idle Flt Action].
Disrupted Peer I/O by using Parameter 56 - [Peer Flt Action].
Disrupted explicit messaging for drive control via PCCC and the CIP
Register Object by using Parameter 57 - [Msg Flt Action].
ATTENTION: Risk of injury or equipment damage exists. Embedded adapter Parameters 54 - [Comm Flt Action], 55
!
- [Idle Flt Action], 56 - [Peer Flt Action], and 57 - [Msg Flt Action] respectively let you determine the action of the
adapter and drive if I/O communication is disrupted, the controller is idle, Peer I/O is disrupted, or explicit messaging for drive control is disrupted. By default, these parameters fault the drive. You can set these parameters so that the drive continues to run. Precautions should be taken to ensure that the settings of these parameters do not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected network cable, controller in idle state or explicit message control disruption).
Changing the Fault Action
Set the values of Parameters 54 - [Comm Flt Action], 55 - [Idle Flt Action], 56 - [Peer Flt Action], and 57 - [Msg Flt Action] to the
desired responses:
Value Action Description
0 Fault The drive is faulted and stopped. (Default) 1 Stop The drive is stopped, but not faulted. 2 Zero Data The drive is sent 0 for output data. This does not command a stop. 3 Hold Last The drive continues in its present state. 4 Send Flt Cfg The drive is sent the data that you set in the fault configuration
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
parameters (Parameters 58 - [Flt Cfg Logic], 59 - [Flt Cfg Ref], and 60
- [Flt Cfg DL 01] through 75 - [Flt Cfg DL 16]).
Page 37
Figure 3.16 Edit Fault Action HIM Screens
Configuring the Adapter 3-15
Stopped
0.00 Hz
Edit Comm Flt Action
Fault 0
0<<4
▲▼
ESC
AUTO
ENTER
F
Stopped
0.00 Hz
Edit Idle Flt Action
Fault 0
0<<4
▲▼
ESC
AUTO
ENTER
F
Stopped
0.00 Hz
Edit Peer Flt Action
Fault 0
0<<4
▲▼
ESC
AUTO
ENTER
F
Stopped
0.00 Hz
Edit Msg Flt Action
Fault 0
0<<4
▲▼
ESC
Changes to these parameters take effect immediately. A reset is not required.
Setting the Fault Configuration Parameters
If you set Parameter 54 - [Comm Flt Action], 55 - [Idle Flt Action], 56 - [Peer Flt Action] or Parameter 57 - [Msg Flt Action] to “Send
Flt Cfg,” the values in the following parameters are sent to the drive after an I/O communications fault, idle fault, Peer I/O fault, and/or explicit messaging for drive control fault occurs. You must set these parameters to values required by your application.
Parameter Description Parameter 58 - [Flt Cfg Logic] A 32-bit value sent to the drive for Logic Command. Parameter 59 - [Flt Cfg Ref] A 32-bit REAL (floating point) value sent to the drive for
Reference.
Parameter 60 - [Flt Cfg DL 01]
through
Parameter 75 - [Flt Cfg DL 16]
A 32-bit integer value sent to the drive for a Datalink. If the destination of the Datalink is a REAL (floating point) parameter, you must convert the desired value to the binary representation of the REAL value. (An internet search of “hex to float” provides a link to a tool to do this conversion.)
AUTO
ENTER
F
Changes to these parameters take effect immediately. A reset is not required.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 38
3-16 Configuring the Adapter

Setting Web Access Control

By using a web browser to access the IP address set for the adapter, you can view the adapter’s web pages for information about the adapter, the drive, and other DPI devices connected to the drive, such as HIMs or converters. Additionally, the adapter can be configured to automatically send e-mail messages to desired addresses when selected drive faults occur and/or are cleared, and/or when the adapter takes a communication or idle fault action. For more details on the adapter’s web pages, refer to Chapter
By default, the adapter web pages are disabled. To enable the adapter web pages, set Parameter 52 - [Web Enable] to “1” (Enabled) and then reset the adapter for the change to take effect.
Figure 3.17 Edit Web Enable HIM Screen
Stopped
0.00 Hz
Edit Web Enable
Disabled 0
0<<1
▲▼
ESC
Bit 0 of Parameter 53 - [Web Features] is used to protect the configured settings for e-mail messaging. By default, settings are not protected and the user can make changes. To protect the configured settings, set the value of E-mail Cfg Bit 0 to “0” (Disabled). You can unprotect the configuration by changing Bit 0 back to “1” (Enabled). E-mail messaging will always remain active regardless of whether or not its settings are protected—unless e-mail messaging was never configured. For more information about configuring adapter e-mail messaging or to stop e-mail messages, refer to Configure E-mail
Notification Web Page on page 8-6.
ENTER
8, Viewing the Adapter Web Pages.
AUTO
F
Value Description
0 Disabled (Default) 1 Enabled
Figure 3.18 Edit Web Features HIM Screen
Bit 0 is the right-most bit. In Figure 3.18 it equals “1” (Enabled).
Changes to this parameter take effect immediately. A reset is not required.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Stopped
0.00 Hz
Edit Web Features
xxxx xxxx xxxx xxx1
E-mail Cfg
WX
ES C ENTER
AUTO
Bit Description
F
0 E-mail Cfg (Default = 1 = Enabled) 1 - 15 Not Used
Page 39
Configuring the Adapter 3-17

Resetting the Adapter

Restoring Adapter Parameters to Factory Defaults

Changes to switch settings and some adapter parameters require that you reset the adapter before the new settings take effect. You can reset the adapter by cycling power to the drive or by using the HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting control I/O to the drive, the drive
!
may fault when you reset the adapter. Determine how your drive will respond before resetting the adapter.
Adapter parameters can be restored in two ways:
ALL—restores ALL adapter parameters to their factory default
values.
MOST—restores MOST adapter parameters—except the following
which are used for network setup:
– Parameter 36 - [BOOTP] – Parameters 38 through 41 - [IP Addr Cfg 1-4] – Parameters 42 through 45 - [Subnet Cfg 1-4] – Parameters 46 through 49 - [Gateway Cfg 1-4] – Parameter 50 - [Net Rate Cfg]
To restore adapter parameters to their factory default values:
1. Access the Status screen, which is displayed on HIM power up.
Figure 3.19 Status Screen
PAR#
AUTO
F
Stopped
0.00 Hz
Host Drive
240V 4.2A
Rev 3.002 Ser. A
00
ESC REF TEXT
2. Use the or key to scroll to Port 13, which is the port always dedicated to the embedded EtherNet/IP adapter.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select Set Defaults.
6. Press the (Enter) key to display the Set Defaults pop-up box.
7. Press the (Enter) key again to display the warning pop-up box
to reset parameters to their factory default values.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 40
3-18 Configuring the Adapter
8. Press the MOST soft key to restore MOST parameters to factory defaults or press the ALL soft key to restore ALL parameters. Or press the
Important:When performing a Set Defaults, the drive may detect a
9. Reset the adapter by cycling power to the drive or by using the
HIM’s Reset Device function located in the drive’s DIAGNOSTIC folder.
ESC soft key to cancel.
conflict and then not allow this function to occur. If this happens, first resolve the conflict and then repeat this Set Defaults procedure. Common reasons for a conflict include the drive running or a controller in Run mode.

Viewing the Adapter Status Using Parameters

Flash Updating the Adapter

The following parameters provide information about the status of the adapter. You can view these parameters at any time.
Parameter Description 34 - [DLs From Net Act] The number of controller-to-drive Datalinks that are included in
the network I/O connection (controller outputs).
35 - [DLs To Net Act] The number of drive-to-controller Datalinks that are included in
the network I/O connection (controller inputs).
37 - [Net Addr Src] Source from which the adapter node address is taken. This will be
50 - [Net Rate Act] The data rate used by the adapter. 86 - [Fr Peer Status] The status of the consumed peer input connection.
77 - [DLs Fr Peer Act] The number of peer-to-drive Datalinks that the drive is expecting. 88 - [DLs To Peer Act] The number of drive-to-peer Datalinks that the drive is expecting.
The adapter can be flash updated over the network or serially through a direct connection from a computer to the drive using a 1203-USB or 1203-SSS serial converter.
When flashing over the network, you can use the Allen-Bradley software tool ControlFLASH, the built-in flash capability of DriveExplorer Lite or Full, or the built-in flash capability of DriveExecutive.
either “0” (Switches), “1” (Parameters) which uses the address from Parameters 38-41 [IP Addr Cfg x], or “2” (BOOTP). The source is determined by the settings of the IP address switches (Figure 2.1
) on the adapter.
Values: 0 = Off; 1 = Waiting; 2 = Running; 3 = Faulted
When flashing through a direct serial connection from a computer to a drive, you can use the same Allen-Bradley software tools described above, or you can use HyperTerminal set to the X-modem protocol.
To obtain a flash update for this adapter, go to http://www.ab.com/
support/abdrives/webupdate. This site contains all firmware update files
and associated Release Notes that describe firmware update enhancements/anomalies, how to determine the existing firmware version, and how to flash update using DriveExplorer, DriveExecutive or ControlFLASH.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 41

Chapter 4

Configuring the I/O

This chapter provides instructions on how to configure a Rockwell Automation controller (ControlLogix, PLC-5, SLC 500 or MicroLogix
1100) to communicate with the adapter and PowerFlex drive.
Topic Page
Using RSLinx Classic ControlLogix Example 4-2 Limitations When Using PLC-5, SLC 500, and MicroLogix 1100 4-20 PLC-5 Example 4-21 SLC 500 Example 4-29 MicroLogix 1100 Example 4-37
4-1

Using RSLinx Classic

RSLinx Classic, in all its variations (Lite, Gateway, OEM, etc.), is used to provide a communication link between the computer, network, and controller. RSLinx Classic requires its network-specific driver to be configured before communications are established with network devices. To configure the RSLinx driver:
1. Start RSLinx and select Communications > Configure Drivers to display the Configure Drivers screen.
2. In the Available Driver Types box, select “EtherNet/IP Driver” and then click Add New to display the EtherNet/IP Driver Selection screen.
3. When the Add New RSLinx Driver screen appears, type a name (if desired) and click OK to display the “Configure driver:” screen.
4. Depending on your application, select either the browse local or remote subnet option, and click OK. The Configure Drivers screen reappears with the new driver in the Configured Drivers list (Figure 4.1
Figure 4.1 Configure Drivers Screen with a Configured Driver
).
5. Click Close to close the Configure Drivers screen. Leave RSLinx running.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 42
4-2 Configuring the I/O
6. Verify that your computer recognizes the drive. Select Communications > RSWho and, in the menu tree, click the “+”
symbol next to the Ethernet driver.
Note that two other RSLinx drivers (Ethernet devices or Remote Devices via Linx Gateway) may be used. Use one of these drivers if the “EtherNet/IP Driver” cannot see your drive.

ControlLogix Example

Example Network
After the adapter is configured, the drive and adapter will be a single node on the network. This section provides the steps needed to configure a simple EtherNet/IP network (see Figure 4.2 example, we will configure a 1756-ENBT (Series A) bridge to communicate with a drive using Logic Command/Status, Reference/ Feedback, and 32 Datalinks (16 to read/16 to write) over the network.
Figure 4.2 Example ControlLogix EtherNet/IP Network
IP Address 10.91.100.80
ControlLogix Controller with 1756-ENBT Bridge
IP Address 10.91.100.79
PowerFlex 755 Drive with Embedded EtherNet/IP Adapter
Computer with Ethernet Connection
). In our
Adding the Bridge to the I/O Configuration
To establish communications between the controller and adapter over the network, you must first add the ControlLogix controller and its bridge to the I/O configuration.
1. Start RSLogix 5000. The RSLogix 5000 window appears. Select
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
File > New to display the New Controller screen (Figure 4.3
).
Page 43
Configuring the I/O 4-3
Figure 4.3 New Controller Screen (RSLogix 5000 v16 shown)
Select the appropriate choices for the fields in the screen to match your application. Then click OK. The RSLogix 5000 window reappears with the treeview in the left pane.
2. In the treeview, right-click the I/O Configuration folder and select New Module… The Select Module screen appears. Expand the
Communications group to display all of the available communication modules (Figure 4.4
Figure 4.4 Bridge Select Module Screen
).
3. In the list, select the EtherNet/IP bridge used by your controller. In this example, we use a 1756-ENBT EtherNet/IP Bridge (Series A), so the 1756-ENBT/A option is selected. Then click OK. In the Select Major Revision pop-up dialog box, select the major revision of its firmware.
4. Click OK. The bridge’s New Module screen (Figure 4.5
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
) appears.
Page 44
4-4 Configuring the I/O
Figure 4.5 Bridge New Module Screen
5. Edit the following:
Box Setting
Name A name to identify the bridge. Description Optional – description of the bridge. IP Address The IP address of the EtherNet/IP bridge. Host Name Not used. Slot The slot of the EtherNet/IP bridge in the rack. Revision The minor revision of the firmware in the bridge. (You already set the major
revision by selecting the bridge series in Step 3.)
Electronic Keying
Open Module Properties
Compatible Module. The “Compatible Module” setting for Electronic Keying ensures the physical module is consistent with the software configuration before the controller and bridge make a connection. Therefore, ensure that you have set the correct revision in this screen. Refer to the online Help for additional information on this and other Electronic Keying settings.
When this box is checked, additional module properties screens will appear to further configure the bridge after clicking OK. When unchecked, the bridge’s New Module screen will close after clicking OK. For this example, uncheck this box.
6. Click OK. The bridge is now configured for the EtherNet/IP
There are two ways to add the adapter into the I/O configuration:
Add-On Drive Profiles (RSLogix 5000 version 16 or higher)
Generic Profile (RSLogix 5000 all versions)
These are described in the following separate sections. If your version of RSLogix 5000 supports Add-On Drive Profiles, we highly recommend using this method.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
network. It appears in the I/O Configuration folder. In our example, a 1756-ENBT bridge appears under the I/O Configuration folder (Figure 4.6
Figure 4.6 RSLogix 5000: I/O Configuration Folder
) with its assigned name.
Page 45
Configuring the I/O 4-5
Using RSLogix 5000 Add-On Drive Profiles (v16 or Higher)
When compared to using the Generic Profile (all versions), the RSLogix 5000 Add-On Drive Profiles provide these advantages:
Profiles for specific drives that provide descriptive controller tags for
basic control I/O words (Logic Command/Status and Reference/ Feedback) and the name of the drive parameter to which they are assigned. These profiles virtually eliminate I/O mismatch errors and substantially reduce drive configuration time.
New Drive tab eliminates the need for a separate drive software
configuration tool.
Drive configuration settings are saved as part of the RSLogix 5000
v16 project file (.ACD) and also downloaded to the controller.
Adding the Drive/Adapter to the I/O Configuration
To transmit data between the bridge and the drive, you must add the drive as a child device to the parent bridge.
Datalinks. Additionally, Datalinks automatically take
1. In the treeview, right-click on the bridge and select New Module… to display the Select Module screen. In our example, we right-click on the 1756-ENBT/A bridge. Expand the Drives group to display all of the available drives with their communication adapters.
Figure 4.7 Drive Select Module Screen
2. From the list (Figure 4.7), select the drive and its connected adapter. For this example, we selected “PowerFlex 755-EENET.” Then click OK. The drive’s New Module screen (Figure 4.8
) appears.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 46
4-6 Configuring the I/O
Figure 4.8 Drive New Module Screen
3. On the General tab, edit the following data about the drive/adapter:
Box Setting
Name A name to identify the drive. Description Optional – description of the drive/adapter. IP Address The IP address of the adapter.
4. In the Module Definition section, click Change… to launch the Module Definition screen (Figure 4.9 configuration process.
Figure 4.9 Module Definition Screen
5. In the Module Definition screen, edit the following information:
Box Setting
Revision The major and minor revision of the firmware in the drive. If the drive’s
major and minor revision is not available, the drive database is not installed on your computer. To get the correct database, click either the Create Database…, Web Update…, or Match Drive button on the bottom left of this screen. See the information following this table for descriptions of each button.
) and begin the drive/adapter
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 47
Configuring the I/O 4-7
Box Setting
Electronic Keying
Drive Rating The voltage and current rating of the drive. If the drive rating is not listed,
Rating Options Selects the drive power output required for the application. Special Types Reserved for future use. Connection Parameters via Datalinks. When selecting “Parameters via Datalinks”
Data Format Parameters. When the Connection field is set to “Parameters via
Input Data Assigns selected drive or connected peripheral parameters to be READ
Output Data Assigns selected drive or connected peripheral parameters to be
Use Network Reference Box
Compatible Module. The “Compatible Module” setting for Electronic Keying ensures the physical module is consistent with the software configuration before the controller and bridge make a connection. Therefore, ensure that you have set the correct revision in this screen. Refer to the online Help for additional information on this and other Electronic Keying settings. If keying is not required, select “Disable Keying.”
the drive database is not installed on your computer. To get the correct database, click either the Create Database…, Web Update…, or Match Drive button on the bottom left of this screen. See the information following this table for descriptions of each button.
(default), the controller tags for the Datalinks use the drive parameter names to which they are assigned. When selecting “Datalinks,” the controller tags for the Datalinks have non-descriptive UserDefinedData[n] names like those used in RSLogix 5000 v15.
Datalinks,” “Parameters” is automatically selected. When the Connection field is set to “Datalinks,” you must select the number of Datalinks required for your application in the “Data Format” field.
by the controller using DL To Net Datalinks. See Steps 5A through 5E below for details.
WRITTEN to the controller using DL From Net Datalinks. See Steps 5A through 5E below for details.
Conveniently selects the speed reference for the drive to come from the network. This box is checked by default.
Three buttons at the bottom left of the Module Definition screen are provided for your convenience to perform specific functions:
Create Database: Clicking this button enables you to create a
database from an online network device. Thereafter, the database appears in the list for selection on the Module Definition screen.
Web Update: Clicking this button opens the Allen-Bradley Web
Updates web site for downloading product-specific firmware update files.
Match Drive: This button is useful when the drive being added
to the network matches the drive profile (revision, rating, Datalinks, configuration settings, etc.) of an existing online network drive. Clicking this button conveniently creates a duplicate drive profile from the online drive, and automatically loads this identical information into the Module Definition screen. This eliminates the need to manually enter the information each time a new drive with a matching profile is added to the network.
On the Module Definition screen, notice that the Drive Status, Feedback, Logic Command, and Reference are always used.
However, when using Datalinks you must still assign adapter Parameters 01-16 - [DL From Net 01-16] and Parameters 17-32
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 48
4-8 Configuring the I/O
- [DL To Net 01-16] to point to the appropriate drive or connected peripheral parameters. The procedure to configure the Datalinks on the Module Definition screen for the Input Data and Output Data is the same:
A. Click the button in the topmost blank row to display the
Parameter Properties screen for the corresponding Datalink.
Important:Always use the Datalink parameters in consecutive
numerical order, starting with the first parameter. (For example, use Parameters 01, 02, and 03 to configure 3 Datalinks to write data and/or Parameters 17, 18, 19, 20, and 21 to configure 5 Datalinks to read data.) Otherwise, the network I/O connection will be larger than necessary, which needlessly increases controller response time and memory usage.
Figure 4.10 Example Datalink Parameter Properties Screen
B. In the Port field, click the pull down list and select the port of
the device to which this Datalink will be assigned (for this example, Port 0, the PowerFlex 755 drive).
C. In the Parameter field, click the pull down list for the selected
device and select the parameter to which this Datalink will point (for this example, drive parameter 370 - [Stop Mode A]).
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
D. Click OK to complete configuration of the Datalink. The name
of the parameter that this Datalink points to is now shown in the row on the Module Definition screen.
E. Repeat Steps 5A through 5D for each Datalink being
configured.
Page 49
Configuring the I/O 4-9
6. Click OK on the Module Definition screen to save the drive and adapter configuration and close the screen. The drive’s New Module screen reappears.
7. On the New Module screen, click the Connection tab (Figure 4.11
Figure 4.11 Connection Screen
8. In the “Requested Packet Interval (RPI)” box, set the value to 2.0 milliseconds or greater. This value determines the maximum interval that a controller should use to move data to and from the adapter. To conserve bandwidth, use higher values for communicating with low priority devices.
).
The “Inhibit Module” box, when checked, inhibits the module from communicating with the RSLogix 5000 project. When the “Major Fault on …” box is checked, a major controller fault will occur when the module’s connection fails while the controller is in the Run Mode. For this example, leave the “Inhibit Module” and “Major Fault On …” boxes unchecked.
9. On the New Module screen, click the Port Configuration tab (Figure 4.12
Figure 4.12 Port Configuration Screen
).
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 50
4-10 Configuring the I/O
10. In the Port Configuration screen, edit the following information:
Box Setting
IP Address The IP address of the adapter that was already set in the General tab. This
field is not configurable (grayed out).
Subnet Mask The Subnet Mask configuration setting of the network. This setting must
Gateway Address
Enable BootP When this box is checked, BOOTP is enabled in the adapter and will
11. Click Set to save the Port Configuration information which sets the corresponding offline Subnet Cfg x and Gateway Cfg x parameters in the adapter.
12. Click OK on the New Module screen. The new node (“My_PowerFlex_755_Drive” in this example) now appears under the bridge (“My_EtherNet_IP_Bridge” in this example) in the I/O Configuration folder. If you double-click on the Controller Tags, you will see that module-defined data types and tags have been automatically created (Figure 4.13 tag names are defined and Datalinks include the assigned drive parameter name. After you save and download the configuration, these tags allow you to access the Input and Output data of the drive via the controller’s ladder logic.
match the setting of other devices on the network (for example,
255.255.255.0). The Gateway Address configuration setting of the network. This setting
must match the setting of other devices on the network (for example,
10.91.100.1).
ignore the IP address set in the General tab. When unchecked, the controller uses the set IP address. This is another method to enable/ disable BOOTP in the adapter. For this example, leave this box unchecked.
and Figure 4.14). Note that all
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 51
Figure 4.13 Controller Input Tags
Configuring the I/O 4-11
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 52
4-12 Configuring the I/O
Figure 4.14 Controller Output Tags
Saving the I/O Configuration to the Controller
After adding the bridge and drive/adapter to the I/O configuration, you must download the configuration to the controller. You should also save the configuration to a file on your computer.
1. In the RSLogix 5000 window, select Communications > Download. The Download dialog box (Figure 4.15
Figure 4.15 Download Dialog Box
) appears.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 53
Configuring the I/O 4-13
TIP: If a message box reports that RSLogix 5000 is unable to go online, select Communications > Who Active to try to find your controller in the Who Active screen. After finding and selecting the controller, click Set Project Path to establish the path. If your controller does not appear, you need to add or configure the EtherNet/IP driver in RSLinx. Refer to the RSLinx online help.
2. Click Download to download the configuration to the controller. When the download is successfully completed, RSLogix 5000 goes into the Online mode and the I/O Not Responding box in the upper-left of the window should be flashing green. Also, a yellow warning symbol should be displayed on the I/O Configuration folder in the treeview and on the drive profile.
If the controller was in Run Mode before clicking Download, RSLogix 5000 prompts you to change the controller mode back to Remote Run. In this case, choose the appropriate mode for your application. If the controller was in Program Mode before clicking
Download, this prompt will not appear.
3. Select File > Save. If this is the first time you saved the project, the
Save As dialog box appears. Navigate to a folder, type a file name, and click Save to save the configuration to a file on your computer.
To ensure that the present project configuration values are saved, RSLogix 5000 prompts you to upload them. Click Yes to upload and save them.
Correlating the Drive with the Controller
You must now correlate the drive settings to the RSLogix 5000 project I/O settings so that they match. This requires loading the project I/O settings into the drive.
1. In the treeview under I/O Configuration, right-click on the drive profile (for this example My_PowerFlex_755_Drive) and select
Properties.
2. Click the Drive tab and then click Connect to Drive (Figure 4.16
to begin the correlation process.
)
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 54
4-14 Configuring the I/O
Figure 4.16 Drive Correlation Screen
After the drive configuration data has been verified, a pop-up dialog box will appear to synchronize ports from the online drive to the project to ensure that the correct Datalinks are assigned. Click OK.
If the Differences Found screen (Figure 4.17 typical, click Download. This will download the project settings from the controller to the drive and its connected adapter. If Upload is clicked, the drive and adapter settings are uploaded to the controller.
Figure 4.17 Differences Found Screen
3. The I/O Configuration Differences screen (Figure 4.18) appears.
Figure 4.18 I/O Configuration Differences Screen
) appears — which is
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 55
Configuring the I/O 4-15
To match the Datalinks in the drive to the project I/O configuration, click Use Project. After the datalinks have been matched, the Input Data and Output Data columns are grayed out. Click Continue.
A series of download dialog boxes appear, which may take a minute to complete. Thereafter, the I/O OK box in the upper-left of the RSLogix 5000 window should now be solid green and the yellow warning symbols in the treeview under the I/O Configuration folder and drive profile should be gone.
4. Click OK to close the Module Properties screen for the drive.
Using the RSLogix 5000 Generic Profile (all versions)
The basic RSLogix 5000 Generic Profile is only recommended when:
A specific drive profile in other versions of RSLogix 5000 is
unavailable.
Users are already familiar with a Generic Profile and do not want to
convert an existing project to an Add-On Drive Profile (v16 or higher).
A project must maintain specific revision level control.
Version 16 Only — The controller cannot be taken offline. Version
16 enables the Generic Profile to be added while the controller is online and in the Run mode.
Adding the Drive/Adapter to the I/O Configuration
To transmit data between the bridge and the drive, you must add the drive as a child device to the parent bridge.
1. In the treeview, right-click on the bridge and select New Module… to display the Select Module screen (Figure 4.19 we right-click on the 1756-ENBT/A bridge. Expand the Communications group to display all of the available communication modules.
Figure 4.19 Select Module Screen
). In our example,
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 56
4-16 Configuring the I/O
2. Select “ETHERNET-MODULE” from the list (Figure 4.19) to configure the drive and its embedded EtherNet/IP adapter, and then click OK. The drive’s New Module screen (Figure 4.20
Figure 4.20 Drive New Module Screen
3. Edit the following information about the drive/adapter:
Box Setting
Name A name to identify the drive and adapter. Description Optional – description of the drive/adapter. Comm Format Data - DINT (This setting formats the data in 32-bit words.) IP Address The IP address of the adapter. Open Module
Properties
When this box is checked, the drive’s New Module screen will close when clicking OK. When unchecked, additional module properties screens will appear to further configure the drive/adapter when OK is clicked. For this example, check this box.
) appears.
4. Under Connection Parameters, edit the following:
Box
Input 1 (This value
Output 2 (This value
Configuration 6 (This value
Enter the number of 32-bit words that are required for your I/O in the Input Size and Output Size boxes. Since the adapter always uses the 32-bit Logic Status, 32-bit Feedback, and a 32-bit word dedicated for memory allocation of the Generic Ethernet module profile, at least three 32-bit words must be set for the Input Size. The adapter also uses the 32-bit Logic Command and 32-bit Reference, requiring at least two 32-bit words for the Output Size. If any or all of the drive’s sixteen 32-bit Datalinks are used (see
Setting a Master-Slave Hierarchy Configuration on page 3-11), the Input and Output Size settings
must be increased accordingly.
– Input Size: Start with 3 words and add 1 word for each Datalink
used to write data. For example, if 3 Datalinks—[DL From Net xx] parameters—will be used to write to drive or peripheral
Assembly Instance
is required.)
is required.)
is required.)
Size
The value will vary based on the number of [DL From Net xx] parameters used for your application (see details below).
The value will vary based on the number of [DL To Net xx] parameters used for your application (see details below).
0 (This value is required.)
on page 3-8 or Custom Peer I/O
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 57
Configuring the I/O 4-17
parameters, add 3 words to the required 3 words for a total of 6 words.
– Output Size: Start with 2 words and add 1 word for each
Datalink used to read data. For example, if 7 Datalinks—[DL To Net xx] parameters—will be used to read drive or peripheral parameters, add 7 words to the required 2 words for a total of 9 words.
For the example in this manual, all 16 [DL From Net xx] and all 16 [DL To Net xx] are used, resulting in an Input Size of “19” and an Output Size of “18.”
5. After setting the information in the drive’s New Module screen, click OK. The Module Properties screen appears.
6. Click the Connection tab (Figure 4.21
Figure 4.21 Connection Screen
7. In the “Requested Packet Interval (RPI)” box, set the value to 2.0 milliseconds or greater. This value determines the maximum interval that a controller should use to move data to and from the adapter. To conserve bandwidth, use higher values for communicating with low priority devices. For this example, leave the “Inhibit Module” and Major Fault …” boxes unchecked.
8. Click OK. The new node (“My_PowerFlex_755_Drive” in this example) now appears under the bridge (“My_EtherNet_IP_Bridge” in this example) in the I/O Configuration folder. If you double-click on the Input and Output Controller Tags (Figure 4.22
4.23), you will see that module-defined data types and tags have
been automatically created. After you save and download the configuration, these tags allow you to access the Input and Output data of the drive via the controller’s ladder logic.
).
and Figure
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 58
4-18 Configuring the I/O
Figure 4.22 Input Image Controller Tags
Figure 4.23 Output Image Controller Tags
Saving the I/O Configuration to the Controller
After adding the bridge and drive/adapter to the I/O configuration, you must download the configuration to the controller. You should also save the configuration to a file on your computer.
TIP: When using RSLogix 5000 (v16 or higher), you can add the I/O configuration of a Generic Profile while the controller is online and in the Run mode.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 59
Configuring the I/O 4-19
1. In the RSLogix 5000 window, select Communications > Download. The Download dialog box (Figure 4.24
Figure 4.24 Download Dialog Box
) appears.
TIP: If a message box reports that RSLogix 5000 is unable to go online, select Communications > Who Active to try to find your controller in the Who Active screen. After finding and selecting the controller, click Set Project Path to establish the path. If your controller does not appear, you need to add or configure the EtherNet/IP driver in RSLinx. See Using RSLinx Classic
page 4-1 for details.
2. Click Download to download the configuration to the controller. When the download is successfully completed, RSLogix 5000 goes into the Online mode and the I/O OK box in the upper-left of the screen should be solid green.
3. Select File > Save. If this is the first time you saved the project, the Save As dialog box appears. Navigate to a folder, type a file name, and click Save to save the configuration to a file on your computer.
4. Any Datalinks that were enabled in the controller and adapter during I/O configuration must also be configured in the drive. Each Datalink being used must be assigned to a specific parameter in the drive or connected peripheral (see Setting a Master-Slave
Hierarchy on page 3-8 or Custom Peer I/O Configuration on page 3-11). If this is not done, the controller will receive or send
placeholder data instead of actual drive or peripheral parameter values.
on
5. Place the controller in Remote Run or Run Mode.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 60
4-20 Configuring the I/O

Limitations When Using PLC-5, SLC 500, and MicroLogix 1100

Controlling I/O with explicit messages is relatively complex compared to normal implicit I/O control.
ControlLogix and CompactLogix controllers with EtherNet/IP provide the easiest and most integrated form of implicit I/O control for a PowerFlex drive. RSLogix 5000 v16 (and higher) programming software for ControlLogix and CompactLogix controllers contains integrated profiles for PowerFlex drives that, with a few clicks of the mouse, automatically create all controller tags and an implicit connection at the specified Requested Packet Interval to control the drive. This connection is monitored at both ends to ensure that the controller and drive are communicating. A watchdog will cause a drive fault if the drive does not respond within approximately 100 milliseconds. Therefore, using a ControlLogix or CompactLogix controller is by far the much preferred method of controlling drives on EtherNet/IP.
If you are not using either of these type of controllers, then PowerFlex drives on EtherNet/IP can be controlled with explicit messages using PLC-5, SLC 500 or MicroLogix 1100 controllers with the following limitations:
An explicit message is a much slower form of control and is
non-deterministic. This means that you cannot guarantee how long the drive will take to start up or stop when the command is given. Therefore, all equipment used in this manner should be subject to a risk assessment, taking into account the mechanical and electrical implementation.
A timeout value (in seconds) in the drive will issue a drive fault if a
message is not received from the controller within the specified time. However, the controller has no way of detecting a loss of communications to the drive until the next cycle of explicit messages. This is another factor in the risk assessment.
Any additional drives to be controlled will require additional explicit
messages for their control, and they need to be carefully sequenced. Most controllers have small communication queues (refer to its User Manual), which need to be carefully managed if messages are not to be lost.
Each controller has a limited number of communication connections
(refer to its User Manual for maximum connections), which will limit the number of drives that can be connected.
In summary, unlike a ControlLogix or CompactLogix controller, programming a PLC-5, SLC 500 or MicroLogix 1100 controller using RSLogix 5 or RSLogix 500 software with explicit messages is a lot more difficult, and produces a far more complex program.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 61
Configuring the I/O 4-21

PLC-5 Example

Important:The PLC-5 must be Series E (Rev. D.1 or higher) to support
the MultiHop feature that routes messaging to the drive.
Example Network
After the adapter is configured, the connected drive and adapter will be a single node on the network. This section provides the steps needed to configure a simple EtherNet/IP network (see Figure 4.25 example, we will configure a PLC-5/40E controller to communicate with a drive using Logic Command/Status, Reference/Feedback, and 32 Datalinks (16 to read/16 to write) over the network.
Figure 4.25 PLC-5 Example EtherNet/IP Network
IP Address 10.91.100.80
PLC-5/40E Controller with Embedded Ethernet
IP Address 10.91.100.79
PowerFlex 755 Drive with Embedded EtherNet/IP Adapter
). In our
Computer with Ethernet Connection
Configuring Parameters for Network I/O
Since the I/O for the drive is message-based, there is no need to configure any I/O inside the RSLogix 5 (v7 or higher) project until using the I/O as described in Chapter 5
However, to get the adapter to operate with the I/O created in Chapter 5, we need to configure the adapter to accept the I/O and the drive to point to the appropriate Datalinks.
Since the adapter always uses the 32-bit Logic Status and 32-bit Feedback, at least two 32-bit words must be accounted for in the controller input image. The adapter also uses the 32-bit Logic Command and 32-bit Reference, requiring at least two 32-bit words that must be accounted for in the controller output image. If any or all of the drive’s sixteen 32-bit Datalinks are used (see Setting a Master-Slave
Hierarchy on page 3-8 or Custom Peer I/O Configuration on page 3-11):
.
An additional 32-bit word for each [DL From Net xx] Datalink used
to write to drive or peripheral parameters must be accounted for in the controller input image.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 62
4-22 Configuring the I/O
An additional 32-bit word for each [DL To Net xx] Datalink used to
read data must be accounted for in the controller output image.
Adapter Parameter Settings for PLC-5 Example
These adapter settings were used for the example ladder logic program in this section.
Adapter Parameter Value Description 01 - [DL From Net 01] 370 Points to drive Par. 370 - [Stop Mode A] 02 - [DL From Net 02] 371 Points to drive Par. 371 - [Stop Mode B] 03 - [DL From Net 03] 535 Points to drive Par. 535 - [Accel Time 1] 04 - [DL From Net 04] 536 Points to drive Par. 536 - [Accel Time 2] 05 - [DL From Net 05] 537 Points to drive Par. 537 - [Decel Time 1] 06 - [DL From Net 06] 538 Points to drive Par. 538 - [Decel Time 2] 07 - [DL From Net 07] 539 Points to drive Par. 539 - [Jog Acc Dec Time] 08 - [DL From Net 08] 556 Points to drive Par. 556 - [Jog Speed 1] 09 - [DL From Net 09] 557 Points to drive Par. 557 - [Jog Speed 2] 10 - [DL From Net 10] 571 Points to drive Par. 571 - [Preset Speed 1] 11 - [DL From Net 11] 572 Points to drive Par. 572 - [Preset Speed 2] 12 - [DL From Net 12] 573 Points to drive Par. 573 - [Preset Speed 3] 13 - [DL From Net 13] 574 Points to drive Par. 574 - [Preset Speed 4] 14 - [DL From Net 14] 575 Points to drive Par. 575 - [Preset Speed 5] 15 - [DL From Net 15] 576 Points to drive Par. 576 - [Preset Speed 6] 16 - [DL From Net 16] 577 Points to drive Par. 577 - [Preset Speed 7] 17 - [DL To Net 01] 370 Points to drive Par. 370 - [Stop Mode A] 18 - [DL To Net 02] 371 Points to drive Par. 371 - [Stop Mode B] 19 - [DL To Net 03] 535 Points to drive Par. 535 - [Accel Time 1] 20 - [DL To Net 04] 536 Points to drive Par. 536 - [Accel Time 2] 21 - [DL To Net 05] 537 Points to drive Par. 537 - [Decel Time 1] 22 - [DL To Net 06] 538 Points to drive Par. 538 - [Decel Time 2] 23 - [DL To Net 07] 539 Points to drive Par. 539 - [Jog Acc Dec Time] 24 - [DL To Net 08] 556 Points to drive Par. 556 - [Jog Speed 1] 25 - [DL To Net 09] 557 Points to drive Par. 557 - [Jog Speed 2] 26 - [DL To Net 10] 571 Points to drive Par. 571 - [Preset Speed 1] 27 - [DL To Net 11] 572 Points to drive Par. 572 - [Preset Speed 2] 28 - [DL To Net 12] 573 Points to drive Par. 573 - [Preset Speed 3] 29 - [DL To Net 13] 574 Points to drive Par. 574 - [Preset Speed 4] 30 - [DL To Net 14] 575 Points to drive Par. 575 - [Preset Speed 5] 31 - [DL To Net 15] 576 Points to drive Par. 576 - [Preset Speed 6] 32 - [DL To Net 16] 577 Points to drive Par. 577 - [Preset Speed 7]
TIP: The [DL From Net xx] parameters are inputs into the drive that come from controller outputs (for example, data to write to a drive parameter). The [DL To Net xx] parameters are outputs from the drive that go to controller inputs (for example, data to read a drive parameter).
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 63
Configuring the I/O 4-23
Creating RSLogix 5 (v7 or higher) Project
To transmit (read and write) data between the controller and drive, you must create message instructions that allocate data table addresses in the controller for Logic Command/Status, Reference/Feedback, and Datalinks. Note that three messages need to be configured. The timeout message has to be executed first before the Logic Command, Reference, and DL to Net Datalink messages will work. For more information on N42:3 and N45 target device data table addresses, refer to N-Files
page C-8.
Selecting the Controller
1. Start RSLogix 5. The RSLogix 5 window appears. Select File > New to display the Select Processor Type screen (Figure 4.26
Figure 4.26 PLC-5 Select Processor Type Screen
on
).
2. Assign a name for the processor. From the pull-down fields, select the appropriate choices to match your PLC-5 controller and application, and click OK. The RSLogix 5 project window appears.
Creating PLC-5 Ladder Logic for the Control Timeout
1. In the RSLogix 5 project window treeview under Program Files double-click on LAD 2.
2. Insert a ladder rung, double-click on the rung to display the rung editor, and enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG10:n), and
n is an unused element of the data file chosen for xx (for example, MG10:0
Then press Enter.
3. Insert another separate rung, double-click on the rung to display the rung editor, and enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ ER BND OTU MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element (for example,
:0) for the message created in Step 2.
MG10
)
Important:The information must be entered with appropriate
numbers for “xx” and “n” for your application, and with spaces and forward slashes exactly as shown.
Then press Enter.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 64
4-24 Configuring the I/O
4. In the MSG instruction (Figure 4.27), double-click on Setup Screen to launch the message configuration screen (Figure 4.28
Figure 4.27 PLC-5 Ladder Logic for the Control Timeout
Step 2
Step 3
Step 4
5. Configure the General tab by entering or verifying the information shown in the screen.
Figure 4.28 PLC-5 Message Configuration Screens for the Control Timeout
).
General Tab Box Setting
This PLC-5 Communication Command PLC-5 Typed Write. The controller type and command type for the controller to write the control
Data Table Address Size in Elements Port Number 2. Controller port to which the EtherNet/IP network is connected. Target Device (data for adapter/drive) Data Table Address MultiHop Yes . Enables communication to allow Ethernet messaging to be routed to the adapter/drive.
MultiHop Tab Box Setting
To Address 10.91.100.79. The IP address of the adapter connected to the drive.
(1)
(2)
(3)
timeout value to the drive.
N20:0. An unused controller data table address containing the control timeout value to be written.
1. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N42:3. Specific starting address of the destination file in the drive.
When “Yes” is selected, a MultiHop tab appears on the message configuration screen.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 65
Configuring the I/O 4-25
(1)
For details on data table addresses for this example project, refer to Table 5.D on page 5-15.
(2)
For details to determine element size for a specific drive, refer to Understanding Controller Data Table Addresses on page 5-14.
(3)
For details on setting the control timeout value and its function, see N-Files on page C-8.
Creating PLC-5 Ladder Logic for the Logic Status, Feedback, and DL From Net Datalinks
1. Insert another separate rung, double-click on the rung to display the rung editor, and enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG11:n), and n is an unused element of the data file chosen for xx (for example, MG11:0
Then press Enter.
2. Insert another separate rung, double-click on the rung to display the rung editor, and enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ ER BND OTU MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element (for example, MG11
:0) for the message created in Step 1.
)
Important:The information must be entered with appropriate
numbers for “xx” and “n” for your application, and with spaces and forward slashes exactly as shown.
Then press Enter.
3. In the MSG instruction (Figure 4.29 to launch the message configuration screen (Figure 4.30
Figure 4.29 PLC-5 Ladder Logic for the Logic Status, Feedback, and DL
From Net Datalinks
Step 1
Step 2
), double-click on Setup Screen
Step 3
).
4. Configure the General tab by entering or verifying the information shown in the screen.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 66
4-26 Configuring the I/O
Figure 4.30 PLC-5 Message Configuration Screens for the Logic Status
Feedback, and DL From Net Datalinks
General Tab Box Setting
This PLC-5 Communication Command PLC-5 Typed Read. The controller type and command type for the controller to read data
Data Table Address Size in Elements Port Number 2. Controller port to which the EtherNet/IP network is connected. Target Device (data for adapter/drive) Data Table Address MultiHop Ye s. Enables communication to allow Ethernet messaging to be routed to the adapter/drive.
MultiHop Tab Box Setting
To Address 10.91.100.79. The IP address of the adapter connected to the drive.
(1)
For details on data table addresses for this example project, refer to Table 5.D on page 5-15.
(2)
For details to determine element size for a specific drive, refer to Understanding Controller Data Table Addresses on page 5-14.
(3)
For N-File details, see N-Files on page C-8.
(1)
(2)
(3)
from the drive.
N20:1. An unused controller data table address containing the data to be read from the drive.
36. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N45:0. Specific starting address of the source file in the drive.
When “Yes” is selected, a MultiHop tab appears on the message configuration screen.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 67
Configuring the I/O 4-27
Creating PLC-5 Ladder Logic for the Logic Command, Reference, and DL To Net Datalinks
1. Insert another separate rung, double-click on the rung to display the rung editor, and enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG12:n), and n is an unused element of the data file chosen for xx (for example, MG12:0
Then press Enter.
2. Insert another separate rung, double-click on the rung to display the rung editor, and enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ ER BND OTU MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element (for example,
:0) for the message created in Step 1.
MG12
Important:The information must be entered with appropriate
numbers for “xx” and “n” for your application, and with spaces and forward slashes exactly as shown.
Then press Enter.
)
3. In the MSG instruction (Figure 4.31 to launch the message configuration screen (Figure 4.32
Figure 4.31 PLC-5 Ladder Logic for the Logic Command, Reference, and DL
To Net Datalinks
Step 1
Step 2
4. Configure the General tab by entering or verifying the information shown in the screen.
), double-click on Setup Screen
).
Step 3
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 68
4-28 Configuring the I/O
Figure 4.32 PLC-5 Message Configuration Screens for the Logic Command,
Reference, and DL To Net Datalinks
General Tab Box Setting
This PLC-5 Communication Command PLC-5 Typed Write. The controller type and command type for the controller to write data to
Data Table Address Size in Elements Port Number 2. Controller port to which the EtherNet/IP network is connected. Target Device (data for adapter/drive) Data Table Address MultiHop Ye s. Enables communication to allow Ethernet messaging to be routed to the adapter/drive.
MultiHop Tab Box Setting
To Address 10.91.100.79. The IP address of the adapter connected to the drive.
(1)
For details on data table addresses for this example project, refer to Table 5.D on page 5-15.
(2)
For details to determine element size for a specific drive, refer to Understanding Controller Data Table Addresses on page 5-14.
(3)
For N-File details, see N-Files on page C-8.
(1)
(2)
(3)
the drive.
N20:37. An unused controller data table address containing the data to be written to the drive.
36. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N45:0. Specific starting address of the destination file in the drive.
When “Yes” is selected, a MultiHop tab appears on the message configuration screen.
TIP: If the controller is controlling more than one drive, it is recommended to intersperse the control I/O messaging for each drive to conserve network bandwidth and decrease response time. That is, sequence the message instructions for each drive so that its group of messages will occur at a different time than those for another drive.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 69
Configuring the I/O 4-29

SLC 500 Example

Example Network
After the adapter is configured, the connected drive and adapter will be a single node on the network. This section provides the steps needed to configure a simple EtherNet/IP network (see Figure 4.33 example, we will configure a SLC 500 controller to communicate with a drive using Logic Command/Status, Reference/Feedback, and 32 Datalinks (16 to read/16 to write) over the network.
Figure 4.33 SLC 500 Example EtherNet/IP Network
IP Address 10.91.100.80
SLC 500 Controller with Embedded Ethernet
IP Address 10.91.100.79
PowerFlex 755 Drive with Embedded EtherNet/IP Adapter
Computer with Ethernet Connection
). In our
Configuring Parameters for Network I/O
Since the I/O for the drive is message-based, there is no need to configure any I/O inside the RSLogix 500 (v7 or higher) project until using the I/O as described in Chapter 5
However, to get the adapter to operate with the I/O created in Chapter 5, we need to configure the adapter to accept the I/O and drive to point to the appropriate Datalinks.
Since the adapter always uses the 32-bit Logic Status and 32-bit Feedback, at least two 32-bit words must be accounted for in the controller input image. The adapter also uses the 32-bit Logic Command and 32-bit Reference, requiring at least two 32-bit words that must be accounted for in the controller output image. If any or all of the drive’s sixteen 32-bit Datalinks are used (see Setting a Master-Slave
Hierarchy on page 3-8 or Custom Peer I/O Configuration on page 3-11):
An additional 32-bit word for each [DL From Net xx] Datalink used
to write to drive or peripheral parameters must be accounted for in the controller input image.
.
An additional 32-bit word for each [DL To Net xx] Datalink used to
read data must be accounted for in the controller output image.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 70
4-30 Configuring the I/O
Adapter Parameter Settings for SLC 500 Example
These adapter settings were used for the example ladder logic program in this section.
Adapter Parameter Value Description 01 - [DL From Net 01] 370 Points to drive Par. 370 - [Stop Mode A] 02 - [DL From Net 02] 371 Points to drive Par. 371 - [Stop Mode B] 03 - [DL From Net 03] 535 Points to drive Par. 535 - [Accel Time 1] 04 - [DL From Net 04] 536 Points to drive Par. 536 - [Accel Time 2] 05 - [DL From Net 05] 537 Points to drive Par. 537 - [Decel Time 1] 06 - [DL From Net 06] 538 Points to drive Par. 538 - [Decel Time 2] 07 - [DL From Net 07] 539 Points to drive Par. 539 - [Jog Acc Dec Time] 08 - [DL From Net 08] 556 Points to drive Par. 556 - [Jog Speed 1] 09 - [DL From Net 09] 557 Points to drive Par. 557 - [Jog Speed 2] 10 - [DL From Net 10] 571 Points to drive Par. 571 - [Preset Speed 1] 11 - [DL From Net 11] 572 Points to drive Par. 572 - [Preset Speed 2] 12 - [DL From Net 12] 573 Points to drive Par. 573 - [Preset Speed 3] 13 - [DL From Net 13] 574 Points to drive Par. 574 - [Preset Speed 4] 14 - [DL From Net 14] 575 Points to drive Par. 575 - [Preset Speed 5] 15 - [DL From Net 15] 576 Points to drive Par. 576 - [Preset Speed 6] 16 - [DL From Net 16] 577 Points to drive Par. 577 - [Preset Speed 7] 17 - [DL To Net 01] 370 Points to drive Par. 370 - [Stop Mode A] 18 - [DL To Net 02] 371 Points to drive Par. 371 - [Stop Mode B] 19 - [DL To Net 03] 535 Points to drive Par. 535 - [Accel Time 1] 20 - [DL To Net 04] 536 Points to drive Par. 536 - [Accel Time 2] 21 - [DL To Net 05] 537 Points to drive Par. 537 - [Decel Time 1] 22 - [DL To Net 06] 538 Points to drive Par. 538 - [Decel Time 2] 23 - [DL To Net 07] 539 Points to drive Par. 539 - [Jog Acc Dec Time] 24 - [DL To Net 08] 556 Points to drive Par. 556 - [Jog Speed 1] 25 - [DL To Net 09] 557 Points to drive Par. 557 - [Jog Speed 2] 26 - [DL To Net 10] 571 Points to drive Par. 571 - [Preset Speed 1] 27 - [DL To Net 11] 572 Points to drive Par. 572 - [Preset Speed 2] 28 - [DL To Net 12] 573 Points to drive Par. 573 - [Preset Speed 3] 29 - [DL To Net 13] 574 Points to drive Par. 574 - [Preset Speed 4] 30 - [DL To Net 14] 575 Points to drive Par. 575 - [Preset Speed 5] 31 - [DL To Net 15] 576 Points to drive Par. 576 - [Preset Speed 6] 32 - [DL To Net 16] 577 Points to drive Par. 577 - [Preset Speed 7]
TIP: The [DL From Net xx] parameters are inputs into the drive that come from controller outputs (for example, data to write to a drive parameter). The [DL To Net xx] parameters are outputs from the drive that go to controller inputs (for example, data to read a drive parameter).
Creating RSLogix 500 (v7 or higher) Project
To transmit (read and write) data between the controller and drive, you must create message instructions that allocate data table addresses in the controller for Logic Command/Status, Reference/Feedback, and Datalinks. Note that three messages need to be configured. The timeout
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 71
Configuring the I/O 4-31
message has to be executed first before the Logic Command, Reference, and DL to Net Datalink messages will work. For more information on N42:3 and N45 target device data table addresses, refer to N-Files
page C-8.
Selecting the Controller
1. Start RSLogix 500. The RSLogix 500 window appears. Select File > New to display the Select Processor Type screen (Figure 4.34
Figure 4.34 SLC 500 Select Processor Type Screen
on
).
2. Assign a name for the processor. In the list, select a 1747-L55x type controller. Then select the appropriate choices for the fields in the screen to match your application, and click OK. The RSLogix 500 project window appears.
Creating SLC 500 Ladder Logic for the Control Timeout
1. In the RSLogix 500 project window treeview under Program Files double-click on LAD 2.
2. Insert a ladder rung, double-click on the rung to display the rung editor, and enter MSG WRITE 500CPU LOCAL Nxx:n, where:
xx is an unused data file number (for example, N10:n), and n is an unused element of the data file chosen for xx (for example, N10:0
Then press Enter.
3. Insert another separate rung, double-click on the rung to display the rung editor, and enter BST XIC Nxx:n/13 NXB XIC Nxx:n/12 BND OTU Nxx:n/15, where:
xx and n must correspond to the assigned data file number and element (for example, N10
:0) for the message created in Step 2.
Important:The information must be entered with appropriate
numbers for “xx” and “n” for your application, and with spaces and forward slashes exactly as shown.
)
Then press Enter.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 72
4-32 Configuring the I/O
4. In the MSG instruction (Figure 4.35), double-click on Setup Screen to launch the message configuration screen (Figure 4.36
Figure 4.35 SLC 500 Ladder Logic for the Control Timeout
Step 2
Step 3
Step 4
).
5. Configure the General tab by entering or verifying the information shown in the screen.
Figure 4.36 SLC 500 Message Configuration Screens for the Control
Timeout
General Tab Box Setting
This Controller Communication Command This setting is unavailable (grayed out) and is established when the message is created in the ladder rung. Data Table Address Size in Elements Channel 1. Controller port to which the EtherNet/IP network is connected. Target Device (data for adapter/drive) Message Timeout This setting is unavailable (grayed out). Message timeout duration in seconds. Data Table Address MultiHop Ye s. Enables communication to allow Ethernet messaging to be routed to the adapter/drive. When “Yes”
MultiHop Tab Box Setting
To Add r e ss 10.91.100.79. The IP address of the adapter connected to the drive.
(1)
(2)
(3)
N20:0. An unused controller data table address containing the control timeout value to be written.
1. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N42:3. Specific starting address of the destination file in the drive.
is selected, a MultiHop tab appears on the message configuration screen.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 73
Configuring the I/O 4-33
(1)
For details on data table addresses for this example project, refer to Table 5.D on page 5-15.
(2)
For details to determine element size for a specific drive, refer to Understanding Controller Data Table Addresses on page 5-14.
(3)
For details on setting the control timeout value and its function, see N-Files on page C-8.
Creating SLC 500 Ladder Logic for the Logic Status, Feedback, and DL From Net Datalinks
1. Insert another separate rung, double-click on the rung to display the rung editor, and enter MSG READ 500CPU LOCAL Nxx:n, where:
xx is an unused data file number (for example, N11:n), and n is an unused element of the data file chosen for xx (for example, N11:0
Then press Enter.
2. Insert another separate rung, double-click on the rung to display the rung editor, and enter BST XIC Nxx:n/13 NXB XIC Nxx:n/12 BND OTU Nxx:n/15, where:
xx and n must correspond to the assigned data file number and element (for example, N11
:0) for the message created in Step 1.
)
Important:The information must be entered with appropriate
numbers for “xx” and “n” for your application, and with spaces and forward slashes exactly as shown.
Then press Enter.
3. In the MSG instruction (Figure 4.37 to launch the message configuration screen (Figure 4.38
Figure 4.37 SLC 500 Ladder Logic for the Logic Status, Feedback, and DL
From Net Datalinks
Step 1
Step 2
), double-click on Setup Screen
).
Step 3
4. Configure the General tab by entering or verifying the information shown in the screen.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 74
4-34 Configuring the I/O
Figure 4.38 SLC 500 Message Configuration Screens for the Logic Status,
Feedback, and DL From Net Datalinks
General Tab Box Setting
This Controller Communication Command This setting is unavailable (grayed out) and is established when the message is created in the
Data Table Address Size in Elements Channel 1. Controller port to which the EtherNet/IP network is connected. Target Device (data for adapter/drive) Message Timeout This setting is unavailable (grayed out). Message timeout duration in seconds. Data Table Address MultiHop Ye s. Enables communication to allow Ethernet messaging to be routed to the adapter/drive.
MultiHop Tab Box Setting
To Address 10.91.100.79. The IP address of the adapter connected to the drive.
(1)
For details on data table addresses for this example project, refer to Table 5.D on page 5-15.
(2)
For details to determine element size for a specific drive, refer to Understanding Controller Data Table Addresses on page 5-14.
(3)
For N-File details, see N-Files on page C-8.
(1)
(2)
(3)
ladder rung.
N20:1. An unused controller data table address containing the data to be read from the drive.
36. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N45:0. Specific starting address of the source file in the drive.
When “Yes” is selected, a MultiHop tab appears on the message configuration screen.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 75
Configuring the I/O 4-35
Creating SLC 500 Ladder Logic for the Logic Command, Reference, and DL To Net Datalinks
1. Insert another separate rung, double-click on the rung to display the rung editor, and enter MSG WRITE 500CPU LOCAL Nxx:n, where:
xx is an unused data file number (for example, N12:n), and n is an unused element of the data file chosen for xx (for example, N12:0
Then press Enter.
2. Insert another separate rung, double-click on the rung to display the rung editor, and enter BST XIC Nxx:n/13 NXB XIC Nxx:n/12 BND OTU Nxx:n/15, where:
xx and n must correspond to the assigned data file number and element (for example, N11
:0) for the message created in Step 1.
Important:The information must be entered with appropriate
numbers for “xx” and “n” for your application, and with spaces and forward slashes exactly as shown.
)
Then press Enter.
3. In the MSG instruction (Figure 4.39
to launch the message configuration screen (Figure 4.40
Figure 4.39 SLC 500 Ladder Logic for the Logic Command, Reference, and
DL To Net Datalinks
Step 1
Step 2
4. Configure the General tab by entering or verifying the information shown in the screen.
), double-click on Setup Screen
).
Step 3
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 76
4-36 Configuring the I/O
Figure 4.40 SLC 500 Message Configuration Screens for the Logic
Command, Reference, and DL To Net Datalinks
General Tab Box Setting
This Controller Communication Command This setting is unavailable (grayed out) and is established when the message is created in the
Data Table Address Size in Elements Channel 1. Controller port to which the EtherNet/IP network is connected. Target Device (data for adapter/drive) Message Timeout This setting is unavailable (grayed out). Message timeout duration in seconds. Data Table Address MultiHop Ye s. Enables communication to allow Ethernet messaging to be routed to the adapter/drive.
MultiHop Tab Box Setting
To Address 10.91.100.79. The IP address of the adapter connected to the drive.
(1)
For details on data table addresses for this example project, refer to Table 5.D on page 5-15.
(2)
For details to determine element size for a specific drive, refer to Understanding Controller Data Table Addresses on page 5-14.
(3)
For N-File details, see N-Files on page C-8.
(1)
(2)
(3)
ladder rung.
N20:37. An unused controller data table address containing the data to be written to the drive.
36. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N45:0. Specific starting address of the source file in the drive.
When “Yes” is selected, a MultiHop tab appears on the message configuration screen.
TIP: If the controller is controlling more than one drive, it is recommended to intersperse the control I/O messaging for each drive to conserve network bandwidth and decrease response time. That is, sequence the message instructions for each drive so that its group of messages will occur at a different time than those for another drive.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 77
Configuring the I/O 4-37

MicroLogix 1100 Example

Example Network
After the adapter is configured, the connected drive and adapter will be a single node on the network. This section provides the steps needed to configure a simple EtherNet/IP network (see Figure 4.41 example, we will configure a MicroLogix 1100 controller to communicate with a drive using Logic Command/Status, Reference/ Feedback, and 32 Datalinks (16 to read/16 to write) over the network.
Figure 4.41 MicroLogix 1100 Example EtherNet/IP Network
IP Address 10.91.100.80
MicroLogix 1100 Controller
IP Address 10.91.100.79
PowerFlex 755 Drive with Embedded EtherNet/IP Adapter
Computer with Ethernet Connection
). In our
Configuring Parameters for Network I/O
Since the I/O for the drive is message-based, there is no need to configure any I/O inside the RSLogix 500 (v7 or higher) project until using the I/O as described in Chapter 5
However, to get the adapter to operate with the I/O created in Chapter 5 we need to configure the adapter to accept the I/O and drive to point to the appropriate Datalinks.
Since the adapter always uses the 32-bit Logic Status and 32-bit Feedback, at least two 32-bit words must be accounted for in the controller input image. The adapter also uses the 32-bit Logic Command and 32-bit Reference, requiring at least two 32-bit words that must be accounted for in the controller output image. If any or all of the drive’s sixteen 32-bit Datalinks are used (see Setting a Master-Slave
Hierarchy on page 3-8 or Custom Peer I/O Configuration on page 3-11):
An additional 32-bit word for each [DL From Net xx] Datalink used
to write to drive or peripheral parameters must be accounted for in the controller input image.
An additional 32-bit word for each [DL To Net xx] Datalink used to
read data must be accounted for in the controller output image.
.
,
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 78
4-38 Configuring the I/O
Adapter Parameter Settings for MicroLogix 1100 Example
These adapter settings were used for the example ladder logic program in this section.
Adapter Parameter Value Description 01 - [DL From Net 01] 370 Points to drive Par. 370 - [Stop Mode A] 02 - [DL From Net 02] 371 Points to drive Par. 371 - [Stop Mode B] 03 - [DL From Net 03] 535 Points to drive Par. 535 - [Accel Time 1] 04 - [DL From Net 04] 536 Points to drive Par. 536 - [Accel Time 2] 05 - [DL From Net 05] 537 Points to drive Par. 537 - [Decel Time 1] 06 - [DL From Net 06] 538 Points to drive Par. 538 - [Decel Time 2] 07 - [DL From Net 07] 539 Points to drive Par. 539 - [Jog Acc Dec Time] 08 - [DL From Net 08] 556 Points to drive Par. 556 - [Jog Speed 1] 09 - [DL From Net 09] 557 Points to drive Par. 557 - [Jog Speed 2] 10 - [DL From Net 10] 571 Points to drive Par. 571 - [Preset Speed 1] 11 - [DL From Net 11] 572 Points to drive Par. 572 - [Preset Speed 2] 12 - [DL From Net 12] 573 Points to drive Par. 573 - [Preset Speed 3] 13 - [DL From Net 13] 574 Points to drive Par. 574 - [Preset Speed 4] 14 - [DL From Net 14] 575 Points to drive Par. 575 - [Preset Speed 5] 15 - [DL From Net 15] 576 Points to drive Par. 576 - [Preset Speed 6] 16 - [DL From Net 16] 577 Points to drive Par. 577 - [Preset Speed 7] 17 - [DL To Net 01] 370 Points to drive Par. 370 - [Stop Mode A] 18 - [DL To Net 02] 371 Points to drive Par. 371 - [Stop Mode B] 19 - [DL To Net 03] 535 Points to drive Par. 535 - [Accel Time 1] 20 - [DL To Net 04] 536 Points to drive Par. 536 - [Accel Time 2] 21 - [DL To Net 05] 537 Points to drive Par. 537 - [Decel Time 1] 22 - [DL To Net 06] 538 Points to drive Par. 538 - [Decel Time 2] 23 - [DL To Net 07] 539 Points to drive Par. 539 - [Jog Acc Dec Time] 24 - [DL To Net 08] 556 Points to drive Par. 556 - [Jog Speed 1] 25 - [DL To Net 09] 557 Points to drive Par. 557 - [Jog Speed 2] 26 - [DL To Net 10] 571 Points to drive Par. 571 - [Preset Speed 1] 27 - [DL To Net 11] 572 Points to drive Par. 572 - [Preset Speed 2] 28 - [DL To Net 12] 573 Points to drive Par. 573 - [Preset Speed 3] 29 - [DL To Net 13] 574 Points to drive Par. 574 - [Preset Speed 4] 30 - [DL To Net 14] 575 Points to drive Par. 575 - [Preset Speed 5] 31 - [DL To Net 15] 576 Points to drive Par. 576 - [Preset Speed 6] 32 - [DL To Net 16] 577 Points to drive Par. 577 - [Preset Speed 7]
TIP: The [DL From Net xx] parameters are inputs into the drive that come from controller outputs (for example, data to write to a drive parameter). The [DL To Net xx] parameters are outputs from the drive that go to controller inputs (for example, data to read a drive parameter).
Creating RSLogix 500 (v7 or higher) Project
To transmit (read and write) data between the controller and drive, you must create message instructions that allocate data table addresses in the controller for Logic Command/Status, Reference/Feedback, and Datalinks. Note that three messages need to be configured. The timeout
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 79
Configuring the I/O 4-39
message has to be executed first before the Logic Command, Reference, and DL to Net Datalink messages will work. For more information on N42:3 and N45 target device data table addresses, refer to N-Files
page C-8.
Selecting the Controller
1. Start RSLogix 500. The RSLogix 500 window appears. Select File > New to display the Select Processor Type screen (Figure 4.42
Figure 4.42 MicroLogix 1100 Select Processor Type Screen
on
).
2. Assign a name for the processor. In the list, select the MicroLogix
1100. Then select the appropriate choices for the fields in the screen to match your application, and click OK. The RSLogix 500 project window appears.
Creating MicroLogix 1100 Ladder Logic for the Control Timeout
1. In the RSLogix 500 project window treeview under Program Files double-click on LAD 2.
2. Insert a ladder rung, double-click on the rung to display the rung editor, and enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG10:n), and n is an unused element of the data file chosen for xx (for example, MG10:0
Then press Enter.
3. Insert another separate rung, double-click on the rung to display the rung editor, and enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ ER BND OTU MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element (for example, MG10
:0) for the message created in Step 2.
)
Important:The information must be entered with appropriate
numbers for “xx” and “n” for your application, and with spaces and forward slashes exactly as shown.
Then press Enter.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 80
4-40 Configuring the I/O
4. In the MSG instruction (Figure 4.43), double-click on Setup Screen to launch the message configuration screen (Figure 4.44
Figure 4.43 MicroLogix 1100 Ladder Logic for the Control Timeout
Step 2
Step 3
Step 4
5. Configure the General tab by entering or verifying the information shown in the screen.
Figure 4.44 MicroLogix 1100 Message Configuration Screens for the
Control Timeout
).
General Tab Box Setting
This Controller (data for MicroLogix 1100) Channel 1 (integral). Controller port to which the EtherNet/IP network is connected. Communication Command 500CPU Write. The controller type and command type for the controller to read or write data. Since
Data Table Address Size in Elements Target Device (data for adapter/drive) Message Timeout 5. Message timeout duration in seconds. Data Table Address Routing Information File RI9:0. An unused routing information file for the controller.
MultiHop Tab Box Setting
To Address 10.91.100.79. The IP address of the adapter connected to the drive.
the MicroLogix 1100 is part of the SLC-500 controller family, the “500CPU” controller type was
(1)
(2)
(3)
selected. The “Write” command type was selected to write the control timeout value to the drive.
N20:0. An unused controller data table address containing the control timeout value to be written.
1. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N42:3. Specific starting address of the destination file in the drive.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 81
Configuring the I/O 4-41
(1)
For details on data table addresses for this example project, refer to Table 5.D on page 5-15.
(2)
For details to determine element size for a specific drive, refer to Understanding Controller Data Table Addresses on page 5-14.
(3)
For details on setting the control timeout value and its function, see N-Files on page C-8.
Creating MicroLogix 1100 Ladder Logic for the Logic Status, Feedback, and DL From Net Datalinks
1. Insert another separate rung, double-click on the rung to display the rung editor, and enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG11:n), and n is an unused element of the data file chosen for xx (for example, MG11:0
Then press Enter.
2. Insert another separate rung, double-click on the rung to display the rung editor, and enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ ER BND OTU MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element (for example, MG11
:0) for the message created in Step 1.
)
Important:The information must be entered with appropriate
numbers for “xx” and “n” for your application, and with spaces and forward slashes exactly as shown.
Then press Enter.
3. In the MSG instruction (Figure 4.45 to launch the message configuration screen (Figure 4.46
Figure 4.45 MicroLogix 1100 Ladder Logic for the Logic Status, Feedback,
and DL From Net Datalinks
Step 1
Step 2
), double-click on Setup Screen
).
Step 3
4. Configure the General tab by entering or verifying the information shown in the screen.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 82
4-42 Configuring the I/O
Figure 4.46 MicroLogix 1100 Message Configuration Screens for the Logic
Status, Feedback, and DL From Net Datalinks
General Tab Box Setting
This Controller (data for MicroLogix 1100) Channel 1 (integral). Controller port to which the EtherNet/IP network is connected. Communication Command 500CPU Read. The controller type and command type for the controller to read or write data.
Since the MicroLogix 1100 is part of the SLC-500 controller family, the “500CPU” controller
Data Table Address Size in Elements Target Device (data for adapter/drive) Message Timeout 5. Message timeout duration in seconds. Data Table Address Routing Information File RI9:1. An unused routing information file for the controller.
MultiHop Tab Box Setting
To Address 10.91.100.79. The IP address of the adapter connected to the drive.
(1)
For details on data table addresses for this example project, refer to Table 5.D on page 5-15.
(2)
For details to determine element size for a specific drive, refer to Understanding Controller Data Table Addresses on page 5-14.
(3)
For N-File details, see N-Files on page C-8.
(1)
(2)
(3)
type was selected. The “Read” command type was selected to read data from the drive.
N20:1. An unused controller data table address containing the data to be read from the drive.
36. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N45:0. Specific starting address of the source file in the drive.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 83
Configuring the I/O 4-43
Creating MicroLogix 1100 Ladder Logic for the Logic Command, Reference, and DL To Net Datalinks
1. Insert another separate rung, double-click on the rung to display the rung editor, and enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG12:n), and n is an unused element of the data file chosen for xx (for example, MG12:0
Then press Enter.
2. Insert another separate rung, double-click on the rung to display the rung editor, and enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ ER BND OTU MGxx:n/EN, where:
xx and n must correspond to the assigned data file number and element (for example,
:0) for the message created in Step 1.
MG12
Important:The information must be entered with appropriate
numbers for “xx” and “n” for your application, and with spaces and forward slashes exactly as shown.
Then press Enter.
)
3. In the MSG instruction (Figure 4.47 to launch the message configuration screen (Figure 4.48
Figure 4.47 MicroLogix 1100 Ladder Logic for the Logic Command,
Reference, and DL To Net Datalinks
Step 1
Step 2
4. Configure the General tab by entering or verifying the information shown in the screen.
), double-click on Setup Screen
).
Step 3
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 84
4-44 Configuring the I/O
Figure 4.48 MicroLogix 1100 Message Configuration Screens for the Logic
Command, Reference, and DL To Net Datalinks
General Tab Box Setting
This Controller (data for MicroLogix 1100) Channel 1 (integral). Controller port to which the EtherNet/IP network is connected. Communication Command 500CPU Write. The controller type and command type for the controller to read or write data.
Since the MicroLogix 1100 is part of the SLC-500 controller family, the “500CPU” controller
Data Table Address Size in Elements Target Device (data for adapter/drive) Message Timeout 5. Message timeout duration in seconds. Data Table Address Routing Information File RI9:2. An unused routing information file for the controller.
MultiHop Tab Box Setting
To Address 10.91.100.79. The IP address of the adapter connected to the drive.
(1)
For details on data table addresses for this example project, refer to Table 5.D on page 5-15.
(2)
For details to determine element size for a specific drive, refer to Understanding Controller Data Table Addresses on page 5-14.
(3)
For N-File details, see N-Files on page C-8.
(1)
(2)
(3)
type was selected. The “Write” command type was selected to write data to the drive.
N20:37. An unused controller data table address containing the data to be written to the drive.
36. Number of elements (words) to be transferred. Each element size is a 16-bit integer.
N45:0. Specific starting address of the destination file in the drive.
TIP: If the controller is controlling more than one drive, it is recommended to intersperse the control I/O messaging for each drive to conserve network bandwidth and decrease response time. That is, sequence the message instructions for each drive so that its group of messages will occur at a different time than those for another drive.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 85

Chapter 5

Using the I/O

This chapter provides information and examples that explain how to control, configure, and monitor a PowerFlex 755 drive using the configured I/O.
Topic Page
About I/O Messaging Understanding the I/O Image 5-2 Using Logic Command/Status 5-4 Using Reference/Feedback 5-4 Using Datalinks 5-5 Example Ladder Logic Program Information 5-6 ControlLogix Example 5-6 PLC-5, SLC 500, and MicroLogix 1100 Example 5-14
5-1

About I/O Messaging

ATTENTION: Risk of injury or equipment damage exists. The examples in this publication are intended solely for
!
purposes of example. There are many variables and requirements with any application. Rockwell Automation, Inc. does not assume responsibility or liability (to include intellectual property liability) for actual use of the examples shown in this publication.
On CIP-based networks, including EtherNet/IP, I/O connections are used to transfer the data which controls the PowerFlex drive and sets its Reference. I/O can also be used to transfer data to and from Datalinks in PowerFlex 755 drives.
The adapter includes the Logic Command, Logic Status, Reference, Feedback, and memory allocation for the Generic Ethernet module profile (all as 32-bit words) in the controller’s I/O image. This basic I/O must always be configured in the EtherNet bridge using RSLogix. Additional I/O, if needed, can be set using up to 16 Datalinks to write data and/or up to 16 Datalinks to read data. When using any combination of these Datalinks, add one 32-bit word for each Datalink to the basic I/O Input Size and/or Output Size.
Chapter 3 Configuring the I/O
on the network for the required I/O. The Glossary options. This chapter discusses how to use I/O after you have configured the adapter and controller.
, Configuring the Adapter, and Chapter 4,
, discuss how to configure the adapter and controller
defines the different
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 86
5-2 Using the I/O

Understanding the I/O Image

The terms input and output are defined from the controller’s point of view. Therefore, output I/O is data that is produced by the controller and consumed by the adapter. Input I/O is status data that is produced by the adapter and consumed as input by the controller. The I/O image will vary based on:
How many of the drive’s 32-bit Datalinks (DL From Net 01-16 and
DL To Net 01-16) are used.
ControlLogix Controllers only — Specific drive profile used in
RSLogix 5000 (Add-On Drive Profile in v16 or higher or Generic Profile in all versions of RSLogix 5000).
ControlLogix Controller Image
Since the Add-On Drive Profile in RSLogix 5000 (v16 or higher) provides descriptive controller tags, the I/O image (tag size and location) is automatically configured based on the drive being used. When using the Generic Profile in RSLogix 5000, however, controller tags are not descriptive or defined.
Table 5.A
shows the I/O image when using all of the 32-bit Datalinks.
Table 5.A ControlLogix I/O Image for PowerFlex 750-Series Drives (32-bit Logic
Command/Status, Reference/Feedback, and Datalinks)
DINT Output I/O DINT Input I/O
0 Logic Command 0 Pad 1 Reference 1 Logic Status 2 DL From Net 01 2 Feedback 3 DL From Net 02 3 DL To Net 01 4 DL From Net 03 4 DL To Net 02 5 DL From Net 04 5 DL To Net 03 6 DL From Net 05 6 DL To Net 04 7 DL From Net 06 7 DL To Net 05 8 DL From Net 07 8 DL To Net 06 9 DL From Net 08 9 DL To Net 07 10 DL From Net 09 10 DL To Net 08 11 DL From Net 10 11 DL To Net 09 12 DL From Net 11 12 DL To Net 10 13 DL From Net 12 13 DL To Net 11 14 DL From Net 13 14 DL To Net 12 15 DL From Net 14 15 DL To Net 13 16 DL From Net 15 16 DL To Net 14 17 DL From Net 16 17 DL To Net 15
18 DL To Net 16
(1)
This is only required when the Generic Profile is used. The Add-On Profile automatically accounts for this and, therefore, hides the Pad in the I/O input image.
(1)
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 87
Using the I/O 5-3
PLC-5, SLC 500, and MicroLogix 1100 Controller Image
The I/O image for the PLC-5, SLC 500, and MicroLogix 1100 controller changes depending on how many of the drive’s sixteen 32-bit Datalinks are used.
TIP: Since PLC-5, SLC 500, and MicroLogix 1100 controllers are 16-bit devices, each 32-bit word for the Logic Command/Status, Reference/Feedback, and any used Datalinks will consume two contiguous words (Least and Most Significant) in the controller’s I/O image. Table 5.B
Table 5.B PLC-5, SLC 500, and MicroLogix 1100 I/O Image for PowerFlex
750-Series Drives (32-bit Logic Command/Status, Reference/ Feedback, and Datalinks)
Word Output I/O Word Input I/O
0 Logic Command (LSW) 0 Logic Status (LSW) 1 Logic Command (MSW) 1 Logic Status (MSW) 2 Reference (LSW) 2 Feedback (LSW) 3 Reference (MSW) 3 Feedback (MSW) 4 DL From Net 01 (LSW) 4 DL To Net 01 (LSW) 5 DL From Net 01 (MSW) 5 DL To Net 01 (MSW) 6 DL From Net 02 (LSW) 6 DL To Net 02 (LSW) 7 DL From Net 02 (MSW) 7 DL To Net 02 (MSW) 8 DL From Net 03 (LSW) 8 DL To Net 03 (LSW) 9 DL From Net 03 (MSW) 9 DL To Net 03 (MSW) 10 DL From Net 04 (LSW) 10 DL To Net 04 (LSW) 11 DL From Net 04 (MSW) 11 DL To Net 04 (MSW) 12 DL From Net 05 (LSW) 12 DL To Net 05 (LSW) 13 DL From Net 05 (MSW) 13 DL To Net 05 (MSW) 14 DL From Net 06 (LSW) 14 DL To Net 06 (LSW) 15 DL From Net 06 (MSW) 15 DL To Net 06 (MSW) 16 DL From Net 07 (LSW) 16 DL To Net 07 (LSW) 17 DL From Net 07 (MSW) 17 DL To Net 07 (MSW) 18 DL From Net 08 (LSW) 18 DL To Net 08 (LSW) 19 DL From Net 08 (MSW) 19 DL To Net 08 (MSW) 20 DL From Net 09 (LSW) 20 DL To Net 09 (LSW) 21 DL From Net 09 (MSW) 21 DL To Net 09 (MSW) 22 DL From Net 10 (LSW) 22 DL To Net 10 (LSW) 23 DL From Net 10 (MSW) 23 DL To Net 10 (MSW) 24 DL From Net 11 (LSW) 24 DL To Net 11 (LSW) 25 DL From Net 11 (MSW) 25 DL To Net 11 (MSW) 26 DL From Net 12 (LSW) 26 DL To Net 12 (LSW) 27 DL From Net 12 (MSW) 27 DL To Net 12 (MSW) 28 DL From Net 13 (LSW) 28 DL To Net 13 (LSW) 29 DL From Net 13 (MSW) 29 DL To Net 13 (MSW) 30 DL From Net 14 (LSW) 30 DL To Net 14 (LSW) 31 DL From Net 14 (MSW) 31 DL To Net 14 (MSW) 32 DL From Net 15 (LSW) 32 DL To Net 15 (LSW) 33 DL From Net 15 (MSW) 33 DL To Net 15 (MSW) 34 DL From Net 16 (LSW) 34 DL To Net 16 (LSW) 35 DL From Net 16 (MSW) 35 DL To Net 16 (MSW)
shows the I/O for a drive using all 32-bit Datalinks.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 88
5-4 Using the I/O

Using Logic Command/ Status

Using Reference/Feedback

The Logic Command is a 32-bit word of control data produced by the controller and consumed by the adapter. The Logic Status is a 32-bit word of status data produced by the adapter and consumed by the controller.
When using a ControlLogix controller, the Logic Command word is always DINT 0 in the output image and the Logic Status word is always DINT 0 in the input image when using the Add-On Profile or DINT 1 when using the Generic Profile. For a PLC-5, SLC 500 or MicroLogix 1100 controller, the Logic Command word is always words 0 (least significant word) and 1 (most significant word) in the output image and the Logic Status word is always words 0 (least significant word) and 1 (most significant word) in the input image.
This manual contains the bit definitions for compatible products available at the time of publication in Appendix
Status Words for PowerFlex 750-Series Drives.
The Reference is a 32-bit REAL (floating point) piece of control data produced by the controller and consumed by the adapter. The Feedback is a 32-bit REAL (floating point) piece of status data produced by the adapter and consumed by the controller.
D, Logic Command/
The Reference and Feedback 32-bit values represent engineering units. For example, a 32-bit REAL Reference value of “30.0” equals a Reference of 30.0 Hz. Note that the commanded maximum speed can never exceed the value of drive Parameter 510 - [Max Fwd Speed].
Table 5.C
755 drive that has its Parameter 37 - [Maximum Freq] set to 130 Hz and Parameter 520 - [Max Fwd Speed] set to 60 Hz.
When using a ControlLogix controller, the 32-bit REAL Reference is always DINT 1 in the output image and the 32-bit REAL Feedback is always DINT 1 in the input image when using the Add-On Profile or DINT 2 when using the Generic Profile. For a PLC-5, SLC 500 or MicroLogix 1100 controller, the 32-bit REAL Reference word is always words 2 (least significant word) and 3 (most significant word) in the output image and the 32-bit REAL Feedback is always words 2 (least significant word) and 3 (most significant word) in the input image. Because the I/O image is integer-based and the Reference and Feedback are floating point, a COP (Copy) instruction or UDDT is required to correctly write values to the Reference and read values from the Feedback. See the ladder logic program examples in Figure 5.8
Figure 5.9
TIP: When using the drive-specific add-on profile, the controller tags for Reference and Feedback are automatically and properly formatted. This eliminates the need for data conversion using COP (copy) instructions or a UDDT.
shows example References and their results for a PowerFlex
and
.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 89
Using the I/O 5-5
Table 5.C Example Speed Reference/Feedback Scaling for PowerFlex 750-Series
Drives

Using Datalinks

Network Reference Value
130.0 130 Hz 60 Hz
65.0 65 Hz 60 Hz
32.5 32.5 Hz 32.5 Hz 32.5
0.0 0 Hz 0 Hz 0.0
(1)
-32.5
(1)
The effects of values less than 0.0 depend on whether the PowerFlex 755 drive uses a bipolar or unipolar direction mode. Refer to the drive User Manual for details.
(2)
The drive runs at 60 Hz instead of 130 Hz or 65 Hz because drive Parameter 520 - [Max Fwd Speed] sets 60 Hz as the maximum speed.
A Datalink is a mechanism used by PowerFlex drives to transfer data to and from the controller. Datalinks allow a drive parameter value to be changed without using an Explicit Message. When enabled, each Datalink occupies one 32-bit word in a ControlLogix controller or two 16-bit words in a PLC-5, SLC 500 or MicroLogix 1100 controller.
The following rules apply when using PowerFlex 750-Series drive Datalinks:
The target of a Datalink can be any Host parameter, including those
of a peripheral. For example, drive parameter 535 - [Accel Time 1] can be assigned to the embedded adapter and any or all of the Option Cards installed in the drive.
Speed Command Value
32.5 Hz 32.5 Hz 32.5
Output Speed
(2)
(2)
60.0
Network Feedback Value
60.0
The data passed through the drive’s Datalink mechanism is
determined by the settings of adapter Parameters 01-16 - [DL From Net 01-16] and Parameters 17-32 - [DL To Net 01-16].
When a Datalink I/O connection is active, that Datalink is locked
and cannot be changed until that I/O connection becomes idle or inactive.
When you use a Datalink to change a value, the value is NOT written
to the Non-Volatile Storage (NVS). The value is stored in volatile memory and lost when the drive loses power. Thus, use Datalinks when you need to change a value of a parameter frequently.
Datalinks for PowerFlex 750-Series peripherals (embedded EtherNet/IP adapter and option modules such as an encoder or a communication module) are locked when the peripheral has an I/O connection with a controller. When a controller has an I/O connection to the drive, the drive does not allow a reset to defaults, configuration download or anything else that could change the makeup of the I/O connection in a running system. The I/O connection with the controller must first be disabled to allow changes to the respective Datalinks.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 90
5-6 Using the I/O
Depending on the controller being used, the I/O connection can be disabled by:
Inhibiting the module in RSLogix 5000
Putting the controller in Program mode
Placing the scanner in idle mode
Disconnecting the drive from the network
DeviceLogix Datalinks are also locked while the DeviceLogix program is running. The DeviceLogix program must first be disabled to allow changes to the Datalinks. Set DeviceLogix parameter 53 - [DLX Operation] to “DisableLogic” to disable the logic (the parameter value will then change to “LogicDisabld”).

Example Ladder Logic Program Information

ControlLogix Example

The example ladder logic programs in the sections of this chapter are intended for and operate PowerFlex 750-Series drives.
Functions of the Example Programs
The example programs enable you to:
Receive Logic Status information from the drive.
Send a Logic Command to control the drive (for example, start, stop).
Send a Reference to the drive and receive Feedback from the drive.
Send/receive Datalink data to/from the drive.
Logic Command/Status Words
These examples use the Logic Command word and Logic Status word for PowerFlex 750-Series drives. Refer to Appendix
Command/Status Words for PowerFlex 750-Series Drives to view
details.
Creating Ladder Logic Using the RSLogix 5000 Add-On Drive Profiles (v16 or higher)
D, Logic
Since the Add-On Drive Profile automatically created descriptive controller tags (Figure 4.13 can use these tags to directly control and monitor the drive without creating any ladder logic program. However, if you intend to use Human Machine Interface devices (PanelView, etc.) to operate the drive and view its status, you will need to create descriptive user-defined Program tags (Figure 5.1 Controller tag data to the Program tags.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
) for the entire I/O image in Chapter 4, you
) and a ladder logic program that will pass the
Page 91
Using the I/O 5-7
Figure 5.1 ControlLogix Program Tags for Integrated Drive Profile Ladder Logic
Program Example
An example ladder logic program that uses the automatically-created descriptive Controller tags and passes their data to the user-defined Program tags is shown in Figure 5.2 for the drive Controller tags is determined by the name assigned when configuring the I/O (Chapter 4
and Figure 5.3. Note that the prefix
).
Figure 5.2 ControlLogix Example Ladder Logic Program Using Add-On Drive
Profiles for Logic Status/Feedback
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 92
5-8 Using the I/O
Figure 5.3 ControlLogix Example Ladder Logic Program Using Add-On Drive
Profiles for Logic Command/Reference
Creating Ladder Logic Using the RSLogix 5000 Generic Profile (all versions)
Adapter Parameter Settings for ControlLogix Example
These adapter settings were used for the example ladder logic program in this section.
Adapter Parameter Value Description 01 - [DL From Net 01] 370 Points to drive Par. 370 - [Stop Mode A] 02 - [DL From Net 02] 371 Points to drive Par. 371 - [Stop Mode B] 03 - [DL From Net 03] 535 Points to drive Par. 535 - [Accel Time 1] 04 - [DL From Net 04] 536 Points to drive Par. 536 - [Accel Time 2] 05 - [DL From Net 05] 537 Points to drive Par. 537 - [Decel Time 1] 06 - [DL From Net 06] 538 Points to drive Par. 538 - [Decel Time 2] 07 - [DL From Net 07] 539 Points to drive Par. 539 - [Jog Acc Dec Time] 08 - [DL From Net 08] 556 Points to drive Par. 556 - [Jog Speed 1] 09 - [DL From Net 09] 557 Points to drive Par. 557 - [Jog Speed 2] 10 - [DL From Net 10] 571 Points to drive Par. 571 - [Preset Speed 1] 11 - [DL From Net 11] 572 Points to drive Par. 572 - [Preset Speed 2] 12 - [DL From Net 12] 573 Points to drive Par. 573 - [Preset Speed 3] 13 - [DL From Net 13] 574 Points to drive Par. 574 - [Preset Speed 4] 14 - [DL From Net 14] 575 Points to drive Par. 575 - [Preset Speed 5] 15 - [DL From Net 15] 576 Points to drive Par. 576 - [Preset Speed 6] 16 - [DL From Net 16] 577 Points to drive Par. 577 - [Preset Speed 7] 17 - [DL To Net 01] 370 Points to drive Par. 370 - [Stop Mode A] 18 - [DL To Net 02] 371 Points to drive Par. 371 - [Stop Mode B] 19 - [DL To Net 03] 535 Points to drive Par. 535 - [Accel Time 1] 20 - [DL To Net 04] 536 Points to drive Par. 536 - [Accel Time 2]
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 93
Using the I/O 5-9
Adapter Parameter Value Description 21 - [DL To Net 05] 537 Points to drive Par. 537 - [Decel Time 1] 22 - [DL To Net 06] 538 Points to drive Par. 538 - [Decel Time 2] 23 - [DL To Net 07] 539 Points to drive Par. 539 - [Jog Acc Dec Time] 24 - [DL To Net 08] 556 Points to drive Par. 556 - [Jog Speed 1] 25 - [DL To Net 09] 557 Points to drive Par. 557 - [Jog Speed 2] 26 - [DL To Net 10] 571 Points to drive Par. 571 - [Preset Speed 1] 27 - [DL To Net 11] 572 Points to drive Par. 572 - [Preset Speed 2] 28 - [DL To Net 12] 573 Points to drive Par. 573 - [Preset Speed 3] 29 - [DL To Net 13] 574 Points to drive Par. 574 - [Preset Speed 4] 30 - [DL To Net 14] 575 Points to drive Par. 575 - [Preset Speed 5] 31 - [DL To Net 15] 576 Points to drive Par. 576 - [Preset Speed 6] 32 - [DL To Net 16] 577 Points to drive Par. 577 - [Preset Speed 7]
TIP: The [DL From Net xx] parameters are inputs into the drive that come from controller outputs (for example, data to write to a drive parameter). The [DL To Net xx] parameters are outputs from the drive that go to controller inputs (for example, data to read a drive parameter).
Controller Tags
When you add the adapter and drive to the I/O configuration (Chapter 4 (non-descriptive) controller tags. In this example program, the following controller tags are used.
Figure 5.4 ControlLogix Controller Tags for Generic Drive Profile Example
You can expand the Output and Input tags to reveal the output and input configuration. The Input tag for this example requires nineteen 32-bit words of data (see Figure 5.5 requires eighteen 32-bit words of data (see Figure 5.6
), RSLogix 5000 automatically creates generic
Ladder Logic Program
). The Output tag for this example program
).
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 94
5-10 Using the I/O
Figure 5.5 ControlLogix Input Image for Generic Drive Profile Example Ladder
Logic Program
Figure 5.6 ControlLogix Output Image for Generic Drive Profile Example
Ladder Logic Program
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 95
Using the I/O 5-11
Program Tags
To use the Controller tags that are automatically created, you need to create the following Program tags for this example program.
Figure 5.7 ControlLogix Program Tags for Generic Drive Profile Example
Ladder Logic Program
Figure 5.8 ControlLogix Example Ladder Logic Program Using Generic Drive
Profiles for Logic Status/Feedback
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 96
5-12 Using the I/O
Figure 5.9 ControlLogix Example Ladder Logic Program Using Generic Drive
Profiles for Logic Command/Reference
Example Datalink Data
The Datalink data used in the example program is shown in Figure 5.10. Note that to describe the parameters to which the Datalinks are assigned, you may want to add descriptions to the automatically-created generic controller tags or create User Defined Data Types (UDDT).
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 97
Using the I/O 5-13
Figure 5.10 ControlLogix Example Datalinks for Ladder Logic Program Using
Generic Drive Profile
TIP: To determine the Data Type of a parameter, refer to the Data Type column in the chapter containing parameters in the PowerFl ex 750-Series AC Drives User Manual, publication 750-UM001.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 98
5-14 Using the I/O

PLC-5, SLC 500, and MicroLogix 1100 Example

Adapter Parameter Settings
For the adapter settings used for the example ladder logic program in this section:
Refer to the Table on… Controller Type
page 4-22 page 4-30 SLC 500 page 4-38
Understanding Controller Data Table Addresses
Since PLC-5, SLC 500, and MicroLogix 1100 controllers are 16-bit platforms being used with the 32-bit embedded EtherNet/IP adapter, the data will be transposed from the least significant word (LSW) to the most significant word (MSW) in the controller.
When the I/O was configured (Chapter 4 (N20) was used. Figure 5.11 for this example.
Figure 5.11 Data File Table for Example Ladder Logic Program
PLC-5
MicroLogix 1100
), an available data table file
shows the entire data file address structure
Important:The N20:0 data table address in this example is used to set
a control timeout value (in seconds) which determines how long it will take the adapter to detect a communication loss. Enter a valid value between 1 - 32767 for N20:0. A value of zero (0) is not valid, since it disables the timeout and all I/O messages (Logic Command/Status, Reference/Feedback, and Datalinks) intended for the drive will not execute.
Table 5.D
file (Figure 5.11
shows the I/O definitions as they relate to the N20 data table
) being used in this example.
For PowerFlex 750-Series drives, which contain both DINT (32-bit format) and REAL (floating point format) data types, you will always read from and write to the LSW data table address in the controller first. Then if the data value exceeds 16 bits, the remaining value will be in the MSW data table address.
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 99
Using the I/O 5-15
Table 5.D PLC-5, SLC 500, and MicroLogix 1100 Data Table Addresses for
PowerFlex 750-Series Drives
Data Table Address
N20:0 Control Timeout N20:1 Logic Status (LSW, see Appendix D N20:2 Logic Status (MSW, see Appendix D N20:3 Speed Feedback LSW N20:4 Speed Feedback MSW N20:5 Value of parameter assigned to adapter Parameter 17 [DL To Net 01] LSW N20:6 Value of parameter assigned to adapter Parameter 17 [DL To Net 01] MSW N20:7 Value of parameter assigned to adapter Parameter 18 [DL To Net 02] LSW N20:8 Value of parameter assigned to adapter Parameter 18 [DL To Net 02] MSW N20:9 Value of parameter assigned to adapter Parameter 19 [DL To Net 03] LSW N20:10 Value of parameter assigned to adapter Parameter 19 [DL To Net 03] MSW N20:11 Value of parameter assigned to adapter Parameter 20 [DL To Net 04] LSW N20:12 Value of parameter assigned to adapter Parameter 20 [DL To Net 04] MSW N20:13 Value of parameter assigned to adapter Parameter 21 [DL To Net 05] LSW N20:14 Value of parameter assigned to adapter Parameter 21 [DL To Net 05] MSW N20:15 Value of parameter assigned to adapter Parameter 22 [DL To Net 06] LSW N20:16 Value of parameter assigned to adapter Parameter 22 [DL To Net 06] MSW N20:17 Value of parameter assigned to adapter Parameter 23 [DL To Net 07] LSW N20:18 Value of parameter assigned to adapter Parameter 23 [DL To Net 07] MSW N20:19 Value of parameter assigned to adapter Parameter 24 [DL To Net 08] LSW N20:20 Value of parameter assigned to adapter Parameter 24 [DL To Net 08] MSW N20:21 Value of parameter assigned to adapter Parameter 25 [DL To Net 09] LSW N20:22 Value of parameter assigned to adapter Parameter 25 [DL To Net 09] MSW N20:23 Value of parameter assigned to adapter Parameter 26 [DL To Net 10] LSW N20:24 Value of parameter assigned to adapter Parameter 26 [DL To Net 10] MSW N20:25 Value of parameter assigned to adapter Parameter 27 [DL To Net 11] LSW N20:26 Value of parameter assigned to adapter Parameter 27 [DL To Net 11] MSW N20:27 Value of parameter assigned to adapter Parameter 28 [DL To Net 12] LSW N20:28 Value of parameter assigned to adapter Parameter 28 [DL To Net 12] MSW N20:29 Value of parameter assigned to adapter Parameter 29 [DL To Net 13] LSW N20:30 Value of parameter assigned to adapter Parameter 29 [DL To Net 13] MSW N20:31 Value of parameter assigned to adapter Parameter 30 [DL To Net 14] LSW N20:32 Value of parameter assigned to adapter Parameter 30 [DL To Net 14] MSW N20:33 Value of parameter assigned to adapter Parameter 31 [DL To Net 15] LSW N20:34 Value of parameter assigned to adapter Parameter 31 [DL To Net 15] MSW N20:35 Value of parameter assigned to adapter Parameter 32 [DL To Net 16] LSW N20:36 Value of parameter assigned to adapter Parameter 32 [DL To Net 16] MSW N20:37 Logic Command (LSW, see Appendix D N20:38 Logic Command (MSW, see Appendix D N20:39 Speed Reference LSW N20:40 Speed Reference MSW N20:41 Value of parameter assigned to adapter Parameter 01 [DL From Net 01] LSW N20:42 Value of parameter assigned to adapter Parameter 01 [DL From Net 01] MSW N20:43 Value of parameter assigned to adapter Parameter 02 [DL From Net 02] LSW N20:44 Value of parameter assigned to adapter Parameter 02 [DL From Net 02] MSW N20:45 Value of parameter assigned to adapter Parameter 03 [DL From Net 03] LSW N20:46 Value of parameter assigned to adapter Parameter 03 [DL From Net 03] MSW N20:47 Value of parameter assigned to adapter Parameter 04 [DL From Net 04] LSW N20:48 Value of parameter assigned to adapter Parameter 04 [DL From Net 04] MSW N20:49 Value of parameter assigned to adapter Parameter 05 [DL From Net 05] LSW N20:50 Value of parameter assigned to adapter Parameter 05 [DL From Net 05] MSW
Description
)
)
)
)
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Page 100
5-16 Using the I/O
Table 5.D PLC-5, SLC 500, and MicroLogix 1100 Data Table Addresses for
PowerFlex 750-Series Drives (Continued)
Data Table Address
N20:51 Value of parameter assigned to adapter Parameter 06 [DL From Net 06] LSW N20:52 Value of parameter assigned to adapter Parameter 06 [DL From Net 06] MSW N20:53 Value of parameter assigned to adapter Parameter 07 [DL From Net 07] LSW N20:54 Value of parameter assigned to adapter Parameter 07 [DL From Net 07] MSW N20:55 Value of parameter assigned to adapter Parameter 08 [DL From Net 08] LSW N20:56 Value of parameter assigned to adapter Parameter 08 [DL From Net 08] MSW N20:57 Value of parameter assigned to adapter Parameter 09 [DL From Net 09] LSW N20:58 Value of parameter assigned to adapter Parameter 09 [DL From Net 09] MSW N20:59 Value of parameter assigned to adapter Parameter 10 [DL From Net 10] LSW N20:60 Value of parameter assigned to adapter Parameter 10 [DL From Net 10] MSW N20:61 Value of parameter assigned to adapter Parameter 11 [DL From Net 11] LSW N20:62 Value of parameter assigned to adapter Parameter 11 [DL From Net 11] MSW N20:63 Value of parameter assigned to adapter Parameter 12 [DL From Net 12] LSW N20:64 Value of parameter assigned to adapter Parameter 12 [DL From Net 12] MSW N20:65 Value of parameter assigned to adapter Parameter 13 [DL From Net 13] LSW N20:66 Value of parameter assigned to adapter Parameter 13 [DL From Net 13] MSW N20:67 Value of parameter assigned to adapter Parameter 14 [DL From Net 14] LSW N20:68 Value of parameter assigned to adapter Parameter 14 [DL From Net 14] MSW N20:69 Value of parameter assigned to adapter Parameter 15 [DL From Net 15] LSW N20:70 Value of parameter assigned to adapter Parameter 15 [DL From Net 15] MSW N20:71 Value of parameter assigned to adapter Parameter 16 [DL From Net 16] LSW N20:72 Value of parameter assigned to adapter Parameter 16 [DL From Net 16] MSW
Description
TIP: Remember that most of the parameters in the drive being read/ written with the Datalinks are REAL (floating point) data types. Therefore, use a COP (Copy) instruction to convert the least significant word and most significant word values to a single floating point register (Fx:x).
You can use the controller data table addresses to directly control and monitor the drive without creating any ladder logic program. However, if you intend to use Human Machine Interface devices (PanelView, etc.) to operate the drive and view its status, you may want to create alternate controller data table addresses (Table 5.E logic program that will pass that data to the data table addresses used for messaging.
Table 5.E Controller and Program Data Table Address Descriptions for Example
Logic Status/Feedback Ladder Logic Program
Description
Drive Ready N20:1/0 Status Ready B3:1/0 Drive Active N20:1/1 Status Active B3:1/1 Actual Direction Forward (XIO) N20:1/3 Status Forward B3:1/3 Actual Direction Reverse (XIC) N20:1/3 Status Reverse B3:1/4 Drive Faulted N20:1/7 Status Faulted B3:1/7 Drive At Speed N20:1/8 Status At Speed B3:1/8 Speed Feedback N20:3 Speed Feedback B30:3
Controller Data Table Address
and Table 5.F) and a ladder
Description
Program Data Table Address
PowerFlex® 755 Drive Embedded EtherNet/IP Adapter User Manual
Publication 750COM-UM001A-EN-P
Loading...