Rockwell Automation PowerFlex 40 Installation Instructions Manual

Page 1
PowerFlex 40 Configured AC Drives
INSTALLATION INSTRUCTIONS
Page 2

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at www.rockwellautomation.com/literature) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
http://
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
!
environment, which may lead to personal injury or death, property damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
!
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
Burn Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be at dangerous temperatures.
PowerFlex, DriveExplorer, DriveExecutive, DPI, and SCANport are either trademarks or registered trademarks of Rockwell Autom ation, Inc.
Page 3

Table of Contents

Preface Overview
Who Should Use this Manual? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-1
What Is Not in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-1
Reference Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-2
Manual Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-2
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-3
Compliance Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-3
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p-4
Chapter 1 PowerFlex 40 Standard Configured Drive Standard Features and Options
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Enclosure Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Power Disconnect Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Operator Device Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Quick Disconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
I/O Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
Chapter 2 Control Wiring Overview
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Control Wiring Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Schematic Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Chapter 3 Mechanical Installation
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Mounting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Layout Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Appendix A Specifications
Appendix B Replacement Parts
Publication 23B-IN001G
Page 4
2 Table of Contents
Notes:
Publication 23B-IN001G
Page 5

Overview

Preface

Who Should Use this Manual?

The purpose of this manual is to provide basic information needed to install PowerFlex
®
40 Adjustable Frequency AC Standard Configured Drives.
User documentation for the PowerFlex 40 Standard Configured Drives includes these Installation Instructions and the PowerFlex 40 User Manual, Publication 22B-UM001…. Both manuals are required to properly install and operate PowerFlex 40 Adjustable Frequency AC Standard Configured Drives.
For information on … See page …
Who Should Use this Manual? What Is Not in this Manual P-1 Reference Materials P-2 Manual Conventions P-2 General Precautions P-3 Compliance Certification P-3 Catalog Number Explanation P-4
P-1
This manual is intended for qualified personnel. You must be able to program and operate Adjustable Frequency AC Drive devices. In addition, you must have an understanding of the parameter settings and functions.

What Is Not in this Manual

The PowerFlex 40 Adjustable Frequency AC Standard Configured Drives Installation Instructions is designed to provide only basic installation and operation information. For this reason, the following topics have not been included:
Troubleshooting
Start-Up
Programming and Parameters
Please refer to the PowerFlex 40 User Manual for detailed drive information.
Publication 23B-IN001G
Page 6
P-2 Overview

Reference Materials

The following manuals are recommended for general drive information:
Title Publication Available Online at …
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives
Preventive Maintenance of Industrial Control and Drive System Equipment
Safety Guidelines for the Application, Installation and Maintenance of Solid State Control
A Global Reference Guide for Reading Schematic Diagrams
Guarding Against Electrostatic Damage 8000-4.5.2
DRIVES-IN001…
DRIVES-TD001…
SGI-1.1
0100-2.10
www.rockwellautomation.com/ literature
For detailed PowerFlex 40 information including drive parameters, programming, start-up, troubleshooting, specifications:
Title Publication Available Online at …
PowerFlex 40 User Manual 22B-UM001… PowerFlex Reference Manual PFLEX-RM001…
www.rockwellautomation.com/literature
The latest version of this Installation Instructions can be obtained online at …
www.rockwellautomation.com/literature
For Allen-Bradley Drives Technical Support:
Title Online at … Allen-Bradley Drives Technical Support www.ab.com/support/abdrives

Manual Conventions

To help differentiate parameter names and LCD display text from other text, the following conventions will be used:
– Parameter Names will appear in [brackets].
For example: [DC Bus Voltage].
– Display Text will appear in “quotes.” For example: “Enabled.”
The following words are used throughout the manual to describe an action:
Word Me aning
Can Possible, able to do something Cannot Not possible, not able to do something May Permitted, allowed Must Unavoidable, you must do this Shall Required and necessary Should Recommended Should Not Not recommended
Publication 23B-IN001G
Page 7

General Precautions

Overview P-3
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control
!
precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, “Guarding Against Electrostatic Damage” or any other applicable ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring
!
or application errors, such as, undersizing the motor, incorrect or inadequate AC supply, or excessive ambient temperatures may result in malfunction of the system.
ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or
!
implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage.

Compliance Certification

ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing
!
any work on the drive. Measure the voltage at the drive (Refer to the PowerFlex 40 User Manual for test point locations). The voltage must be zero.
Certifications are applicable to approved program defined options.
U.S./Canada UL: UL508C
CUL: CAN/CSA-C22.2 No. 14
Please refer to the PowerFlex 40 User Manual, publication 22B-UM001, for additional information.
Publication 23B-IN001G
Page 8
P-4 Overview

Catalog Number Explanation

1-3 4 56-8 9 10111213141516+
23B
D 4P0 D 1 0 4 N N P6
The PowerFlex 40 Adjustable Frequency AC Standard Configured Drives catalog numbering scheme is shown below.
Position
abcdefghi j
a
Drive
Code Type
23B PowerFlex 40
b
Voltage Rating
Code Voltage Ph.
D 480V ac 3
c
Amp Rating
480V 60Hz Input
Code Amps kW (Hp)
1P4 1.4 0.4 (0.5)
2P3 2.3 0.75 (1.0)
4P0 4.0 1.5 (2.0)
6P0 6.0 2.2 (3.0)
010 10.5 4.0 (5.0)
012 12 5.5 (7.5)
017 17 7.5 (10)
024 24 11 (15)
d
Enclosure
Code Enclosure
C NEMA/UL Type 4X ‡
D NEMA/UL Type 4 ‡
‡ The design of the PowerFlex 40 Standard
Configured Drive supports indoor and outdoor applications that are not in direct sunlight.
Code Interface Module
1 Fixed Keypad on Drive
Display with Digital Speed Control
F
This option changes the enclosure rating to
indoor only.
Code Rating
0 Not Filtered
Code Version
4 RS485 (Standard)
C ControlNet
D DeviceNet
E EtherNet/IP
P PROFIBUS DP
Code Rating
N Reserved
Code Rating
N Reserved
e
HIM
Fixed Keypad on Drive and LCD
HIM on Enclosure Door
(22-HIM-C2S)
f
Emission Class
g
Version
h
i
j
Options
Code Description
-E22
-E23
-P3 Motor Circuit Protector
-P3T
-P6 Disconnect Switch - Fused
-P6T
-R3
-R4 DeviceNet Point I/O w/IB4 (4 Inputs)
-R5
-S1
-S4 Auto/Manual S.S. (Speed Ref.)
-S7 Start and Stop P.B.
-S8 Forward/Reverse S.S.
-S18
-S20
-S21
-S22
-S23 Clear Fault P.B.
DeviceNet Quick Disconnect
(Bottom)
DeviceNet Quick Disconnect (Left
Side)
Motor Circuit Protector (Customer
wiring into top of device)
Disconnect Switch - Fused
(Customer wiring into top of device)
DeviceNet I/O (4 In/2 Out) w/Spring Return HOA and Power Disconnect
Aux. Contact
-R3 plus 4 I/O Quick Disconnects and (1) 24V DC Receptacle
Hand/Off/Auto S.S.
(Start/Stop/Speed Ref.)
Door Mounted Local Speed Pot (1-
Tur n )
Local/Remote and Local Control
Off/Run Forward Selector Switches
Local/Off/Remote with 1 N.O.
Interposing Relay
Spring Return Hand/Off Auto S.S.
(Start/Stop/Speed Ref.)
Publication 23B-IN001G
Page 9

Chapter 1

PowerFlex 40 Standard Configured Drive Standard Features and Options

Chapter Objectives

Standard Features

This chapter describes the standard features and operation for PowerFlex 40 Standard Configured Drives and associated options.
For information on … See page …
Standard Features Enclosure Options 1-2 Communication Options 1-3 Power Disconnect Options 1-4 Operator Device Options 1-9 Quick Disconnects 1-15 I/O Options 1-16
This package integrates the Standard PowerFlex 40 drive. The PowerFlex 40 drive can be used for Volts per hertz or Sensorless Vector applications and offers an Autotune feature allowing the drive to adapt to individual motor characteristics.
The PowerFlex 40 is assembled in an enclosure which includes the following features…
NEMA/UL Type 4/4X - indoor and outdoor applications other than direct sunlight.
Flange mount drive/external heatsink reducing overall enclosure size.
(1)
1-1
Mounting feet - orientation is adjustable per customer requirements.
If required, the drive can be removed from the front of the enclosure for ease of assembly or repair.
Low cost, highly configurable I/O inputs and/or 0-10V/4-20 mA outputs that are not used by program standard features and options are available for customer use.
(1)
The enclosure does not normally protect electrical equipment from condensation, corrosion or contamination, which may occur within the enclosure or enter via the conduit or unsealed openings. Users must make adequate provisions to safeguard against such conditions, and satisfy themselves that the equipment is properly protected. For further information on criteria associated with NEMA enclosure ratings, refer to NEMA standards Publication No. 250-1991. When optional Door Mounted HIM is supplied, enclosure is rated indoor only. See enclosure options for specific enclosure style quoted.
Publication 23B-IN001G
Page 10
1-2 PowerFlex 40 Standard Configured Drive Standard Features and Options

Enclosure Options

NEMA/UL Type 4 (Position 9, Code D)
The enclosure provided is a NEMA/UL Type 4, painted mild steel, which supports both NEMA/UL Type 4 and NEMA/UL Type 12 applications. Type 4 enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against windblown dust and rain, splashing water, and hose directed water, and to be undamaged by the formation of ice on the enclosure. They are designed to meet hose-down, dust, and external icing and rust resistance design tests. Doors and openings will be gasket sealed. There are no ventilation openings within the enclosure to allow for free exchange of inside and outside air.
Note: If optional Door Mounted HIM is not supplied, the design of the PowerFlex 40 Standard Configured Drive supports indoor and outdoor applications that are not in direct sunlight.
NEMA/UL Type 4X (Position 9, Code C)
The enclosure provided is a NEMA/UL Type 4X. The material is type 304 stainless steel. Type 4X enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water, and to be undamaged by the formation of ice on the enclosure. They are designed to meet hose-down, dust, and external icing and rust resistance design tests. Doors and openings will be gasket sealed. There are no ventilation openings within the enclosure to allow for free exchange of inside and outside air.
Note: If optional Door Mounted HIM is not supplied, the design of the PowerFlex 40 Standard Configured Drive supports indoor and outdoor applications that are not in direct sunlight.
Publication 23B-IN001G
Page 11
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-3

Communication Options

DeviceNet (Position 12, Code D)
The DeviceNet option is drive mounted and consists of the DeviceNet communication adaptor (22-COMM-D) and adaptor cover (22B-CCB for frame B drives or 22B-CCC for frame C drives). When DeviceNet is present, no other communication option is available other than the HIM. When used as a slave, the HIM will have limited functionality. For details related to the DeviceNet option, refer to the PowerFlex DeviceNet Adapter User Manual, publication 22COMM-UM003….
To review this schematic see
Figure 2.1 on page 2-2 and Figure 2.3 on page 2-4.
EtherNet/IP (Position 12, Code E)
The EtherNet/IP option is drive mounted and consists of the EtherNet/IP communication adaptor (22-COMM-E) and adaptor cover (22B-CCB for frame B drives or 22B-CCC for frame C drives). When EtherNet/IP is present, no other communications option is available other than the HIM. When used as a slave, the HIM will have limited functionality. For details related to the EtherNet/IP option, refer to the PowerFlex EtherNet/IP Adapter User Manual, publication 22COMM-UM004….
To review this schematic see
Figure 2.1 on page 2-2 and Figure 2.3 on page 2-4.
PROFIBUS (Position 12, Code P)
The PROFIBUS option is drive mounted and consists of the PROFIBUS communication adaptor (22-COMM-P) and adaptor cover (22B-CCB for frame B drives or 22B-CCC for frame C drives). When PROFIBUS is present, no other communication option is available other than the HIM. When used as a slave, the HIM will have limited functionality. For details related to PROFIBUS option, refer to the PowerFlex PROFIBUS Adapter User Manual, publication 22COMM-UM005….
To review this schematic see
Figure 2.1 on page 2-2 and Figure 2.3 on page 2-4.
ControlNet (Position 12, Code C)
The ControlNet option is drive mounted and consists of the ControlNet communication adaptor (22-COMM-C) and adaptor cover (22B-CCB for frame B drives or 22B-CCC for frame C drives). When ControlNet is present, no other communication option is available other than the HIM. When used as a slave, the HIM will have limited functionality. For details related to ControlNet option, refer to the PowerFlex ControlNet Adapter User Manual, publication 22COMM-UM006….
To review this schematic see
Figure 2.1 on page 2-2 and Figure 2.3 on page 2-4.
Publication 23B-IN001G
Page 12
1-4 PowerFlex 40 Standard Configured Drive Standard Features and Options

Power Disconnect Options

Drive Motor Circuit Protector (Position 16+, Code -P3)
The Drive Motor Circuit Protector option is factory installed and provides a manual means of disconnecting input power to the drive. The Allen-Bradley Bulletin 140M switch is designed to meet short circuit requirements for branch circuit protection. The rotary style handle is padlockable in On or Off position. This option has a 65 kA short circuit withstand rating. Over load protection is supplied by the drive not the motor circuit protector. Incoming customer supplied power cables terminate at terminals R, S, T (L1, L2, L3) located on the bottom of the device.
Component Specifications
Switch A-B Bulletin 140M, 480V, 65 kA short circuit withstand rating
3-pole, Rod operated UL listed, CE Approved, CSA Certified
Handle Rotary style handle through the door, Door interlocked
Padlockable in On or Off position, Defeatable in the On position IP66 (Type 3R, 3, 12, 4, 4X)
Drive Motor Circuit Protector (Position 16+, Code -P3T)
The Drive Motor Circuit Protector option is factory installed and provides a manual means of disconnecting input power to the drive. The Allen-Bradley Bulletin 140M switch is designed to meet short circuit requirements for branch circuit protection. The rotary style handle is padlockable in On or Off position. This option has a 65 kA short circuit withstand rating. Over load protection is supplied by the drive not the motor circuit protector. Incoming customer supplied power cables terminate at terminals R, S, T (L1, L2, L3) located on the top of the device.
Component Specifications
Switch A-B Bulletin 140M, 480V, 65 kA short circuit withstand rating
3-pole, Rod operated UL listed, CE Approved, CSA Certified
Handle Rotary style handle through the door, Door interlocked
Padlockable in On or Off position, Defeatable in the On position IP66 (Type 3R, 3, 12, 4, 4X)
Publication 23B-IN001G
Page 13
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-5
Drive Input Fused Disconnect Switch (Position 16+, Code -P6)
The Drive Input Fused Disconnect Switch option is factory installed and provides a manual means of disconnecting input power to the drive. The Allen-Bradley Bulletin 194R switch is designed to meet disconnect switch requirements for branch circuit protection. The rotary style handle is padlockable in On or Off position. This option has a 100 kA short circuit withstand rating. Class J fuses are supplied with the disconnect switch. Incoming customer supplied power cables terminate at terminals R, S, T (L1, L2, L3) located on the bottom of the device.
Component Specifications
Switch A-B Bulletin 194R, 600V, 100 kA short circuit withstand rating
Integral class J fuses, Captive terminal clamps 3-pole, Rod operated UL listed, CE Approved, CSA, ASTA, and LOVAG Certified
Handle Rotary style handle through the door, Door interlocked
Padlockable in On or Off position, Defeatable in the On position True switch status indication IP66 (Type 3R, 3, 12, 4, 4X)
Drive Input Fused Disconnect Switch (Position 16+, Code -P6T)
The Drive Input Fused Disconnect Switch option is factory installed and provides a manual means of disconnecting input power to the drive. The Allen-Bradley Bulletin 194R switch is designed to meet disconnect switch requirements for branch circuit protection. The rotary style handle is padlockable in On or Off position. This option has a 100 kA short circuit withstand rating. Class J fuses are supplied with the disconnect switch. Incoming customer supplied power cables terminate at terminals R, S, T (L1, L2, L3) located on the top of the device.
Component Specifications
Switch A-B Bulletin 194R, 600V, 100 kA short circuit withstand rating
Integral class J fuses, Captive terminal clamps 3-pole, Rod operated UL listed, CE Approved, CSA, ASTA, and LOVAG Certified
Handle Rotary style handle through the door, Door interlocked
Padlockable in On or Off position, Defeatable in the On position True switch status indication IP66 (Type 3R, 3, 12, 4, 4X)
Publication 23B-IN001G
Page 14
1-6 PowerFlex 40 Standard Configured Drive Standard Features and Options
Main Fuses (F1-F3)
ATTENTION: Most codes require that upstream branch circuit protection be provided to protect input power wiring. Install the
!
fuses recommended in Table 1.A Failure to observe this precaution could result in damage to, or destruction of, the equipment.
Input line branch circuit protection fuses must be used to protect the input power lines. If input fuses are not provided with your drive, recommended fuse values are shown in Table 1.A
1.A are applicable for one drive per branch circuit. No other load may be
applied to that fused circuit. The recommended fuse type for all PowerFlex 40 Standard Configured
Drives is UL Class J.
Table 1.A Branch Fusing
Voltage Rating Drive Rating HP Fuse Rating Amps
480V AC 0.5 3
1.0 6
2.0 10
3.0 15
5.0 20
7.5 25
10 30
15 50
. Do not exceed the fuse ratings.
. The input fuse ratings listed in Tabl e
Publication 23B-IN001G
Page 15
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-7
Input Power Wiring
Refer to the PowerFlex 40 User Manual for additional detailed information about input power wiring recommendations and selection.
ATTENTION: Protect the contents of the options cabinet from metal chips and other debris while drilling the conduit openings.
!
Failure to observe this precaution could result in damage to, or destruction of, the equipment.
ATTENTION: Do not route signal and control wiring with power wiring in the same conduit. This can cause interference
!
with drive operation. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
To connect AC input power to the drive package:
1. Select the proper wire size according to NEC and all applicable local
codes and standards. Note that you must punch openings in the Option Cabinet of the desired conduit size, following NEC and all applicable local codes and standards. Power terminal block specifications are listed in Table 1.B
.
2. Connect the three-phase AC input power leads (three-wire VAC) to the
appropriate terminals. Connect the AC input power leads to terminals L1, L2, L3 on the fused disconnect switch or motor circuit protector.
Note: Drive Input Fused Disconnect Switch (-P6) and Drive Motor Circuit Protector (-P3) options are bottom fed. Drive Input Fused Disconnect Switch (-P6T) and Drive Motor Circuit Protector (-P3T) options are top fed.
3. Tighten the AC input terminal power terminals to the proper torque
according to drive type as shown in Table 1.B
Table 1.B Component Current Ratings and Wire Sizing
PowerFlex 40 SPD Drive Rating - 480V
HP Continuous
Current Rating
Amps
0.5-3 30 2.5 mm
5-7.5 30 3.5 mm
10-15 60 4.0 mm
(1)
Wire is Black Hypalon.
(2)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Factory Power Wire Size
(14 AWG)
(12 AWG)
(10 AWG)
(1)(2)
2
2
2
.
Customer Terminal Wire Size
2.5-8.4 mm (14-8 AWG)
2.5-8.4 mm (14-8 AWG)
2.5-16.0 mm (14-4 AWG)
2
2
2
Operating Torque
4.0 N-m (35 lb.-in.)
4.0 N-m (35 lb.-in.)
4.0 N-m (35 lb.-in.)
Publication 23B-IN001G
Page 16
1-8 PowerFlex 40 Standard Configured Drive Standard Features and Options
Output Power Wiring
Refer to the PowerFlex 40 User Manual for additional detailed information about output power wiring recommendations and selection.
ATTENTION: Unused wires in conduit must be grounded at both ends to avoid a possible shock hazard caused by induced
!
voltages. Also, if a drive sharing a conduit is being serviced or installed, all drives using this conduit should be disabled to eliminate the possible shock hazard from cross-coupled motor leads. Failure to observe these precautions could result in bodily injury.
ATTENTION: Do not route signal and control wiring with power wiring in the same conduit. This can cause interference
!
with drive operation. Failure to observe this precaution could result in damage to, or destruction of, the equipment.
To connect AC output power wiring from the drive to the motor:
1. Wire the three-phase AC output power motor leads by routing them
according to the drive option type. Note that you must punch openings in the option cabinet of the desired conduit size, following NEC and all applicable local codes and standards. Power terminal block specifications are listed in Table 1.C
.
Do not route more than three sets of motor leads through a single conduit. This will minimize cross-talk that could reduce the effectiveness of noise reduction methods. If more than three drive/motor connections per conduit are required, shielded cable must be used. If possible, each conduit should contain only one set of motor leads.
2. Connect the three-phase AC output power motor leads to terminals
U, V, W (T1, T2, T3) on the power terminal block located on the drive.
3. Tighten the three-phase AC output power terminals to the proper torque
according to drive type as shown in Table 1.C
Table 1.C AC Output Power Terminal Block Specifications
Frame Maximum Wire Size
2
B 5.3 mm
C 8.4 mm
(1)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(10 AWG) 1.3 mm2 (16 AWG) 1.7-2.2 N-m (16-19 lb.-in.)
2
(8 AWG) 1.3 mm2 (16 AWG) 2.9-3.7 N-m (26-33 lb.-in.)
(1)
Minimum Wire Size Recommended Torque
.
Publication 23B-IN001G
Page 17
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-9

Operator Device Options

Hand/Off/Auto Selector Switch (Position 16+, Code S1)
This 800F door mounted operator device is factory installed and provides a Hand/Off/Auto selector switch.
The Hand/Off/Auto selector switch will start the drive in Hand mode and stop the drive in Off mode. In Auto mode the drive will be stopped and started from remote contact closures. In all cases, the Stop input to the drive must be present before the drive will start.
The Hand/Off/Auto selector switch also determines the source of the actual drive speed reference. In Hand mode, speed source is parameter A072 [Preset Freq 2]. In Auto mode, speed source is parameter A071 [Preset Freq 1].
If the door mounted speed potentiometer (Option S18) is supplied and it is intended to be the speed reference in Hand mode, set parameter A052 [Digital In2 Sel] to option 13 “10V In Ctrl”. Refer to the table below and the PowerFlex 40 User Manual, publication 22B-UM001, for other options.
Hand/Off/Auto Selector Switch (Code S1)
Speed Reference Parameter Settings
Hand Mode Auto Mode P038 [Speed Reference] A051 [Digital In1 Sel] A052 [Digital In2 Sel]
Preset Speed Preset Speed 4 “Preset Freq” 4 “Preset Freq” 4 “Preset Freq”
Analog Input (0-10V) 4 “Preset Freq” 13 “10V In Ctrl” 4 “Preset Freq”
Analog Input (4-20mA) 4 “Preset Freq” 14 “20mA In Ctrl” 4 “Preset Freq”
Communication Port
Speed Pot (Door) Preset Speed 4 “Preset Freq” 4 “Preset Freq” 13 “10V In Ctrl”
Analog Input (4-20mA) 4 “Preset Freq” 14 “20mA In Ctrl” 13 “10V In Ctrl”
Communication Port
HIM (Door) Preset Speed 4 “Preset Freq” 4 “Preset Freq” 6 “Comm Port”
Analog Input (0-10V) 4 “Preset Freq” 13 “10V In Ctrl” 6 “Comm Port”
Analog Input (4-20mA) 4 “Preset Freq” 14 “20mA In Ctrl” 6 “Comm Port”
(1)
Communication port will have both logic and reference control.
(1)
4 “Preset Freq” 6 “Comm Port” 4 “Preset Freq”
(1)
4 “Preset Freq” 6 “Comm Port” 13 “10V In Ctrl”
Component Specifications
Bulletin 800F Devices
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts
2
(22–12 AWG) maximum
Hand/Off/Auto Selector Switch
Screw terminals, 0.3–3.5 mm 3 position, Maintained
4 N.O. contacts
Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm
2
(18 AWG), Blue
Schematics Figure 2.4 on page 2-5
Figure 2.5 on page 2-6
This option is not compatible with Codes R3, R5, S4, S7, S20, S21 or S22.
Publication 23B-IN001G
Page 18
1-10 PowerFlex 40 Standard Configured Drive Standard Features and Options
Auto/Manual Selector Switch (Position 16+, Code S4)
This 800F door mounted operator device is factory installed and provides an Auto/Manual selector switch.
The Auto/Manual selector switch determines the source of the actual drive speed reference. Using 2-wire control in Auto mode, speed source is parameter A071 [Preset Freq 1]. In Manual mode, the speed source is parameter A072 [Preset Freq 2].
If the door mounted speed potentiometer (Option S18) is supplied and it is intended to be the speed reference in Manual mode, set parameter P052 [Digital In2 Sel] to option 13 “10V In Ctrl”. Refer to the table below and the PowerFlex 40 User Manual, publication 22B-UM001, for other options.
Auto/Manual Selector Switch (Code S4)
Speed Reference Parameter Settings
Manual Mode Auto Mode P038 [Speed Reference] A051 [Digital In1 Sel] A052 [Digital In2 Sel]
Preset Speed Preset Speed 4 “Preset Freq” 4 “Preset Freq” 4 “Preset Freq”
Analog Input (0-10V) 4 “Preset Freq” 13 “10V In Ctrl” 4 “Preset Freq”
Analog Input (4-20mA) 4 “Preset Freq” 14 “20mA In Ctrl” 4 “Preset Freq”
Communication Port
Speed Pot (Door) Preset Speed 4 “Preset Freq” 4 “Preset Freq” 13 “10V In Ctrl”
Analog Input (4-20mA) 4 “Preset Freq” 14 “20mA In Ctrl” 13 “10V In Ctrl”
Communication Port
HIM (Door) Preset Speed 4 “Preset Freq” 4 “Preset Freq” 6 “Comm Port”
Analog Input (0-10V) 4 “Preset Freq” 13 “10V In Ctrl” 6 “Comm Port”
Analog Input (4-20mA) 4 “Preset Freq” 14 “20mA In Ctrl” 6 “Comm Port”
(1)
Communication port will have both logic and reference control.
(1)
4 “Preset Freq” 6 “Comm Port” 4 “Preset Freq”
(1)
4 “Preset Freq” 6 “Comm Port” 13 “10V In Ctrl”
Component Specifications
Bulletin 800F Devices
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts
2
(22–12 AWG) maximum
Auto/Manual Selector Switch
Screw terminals, 0.3–3.5 mm 2 position, Maintained
1 N.C. contact
Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm
2
(18 AWG), Blue
Schematics Figure 2.6 on page 2-7
Figure 2.7 on page 2-8 Figure 2.8 on page 2-9
This option is not compatible with Codes R3, R5, S1, S20, S21 or S22.
Publication 23B-IN001G
Page 19
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-11
Start and Stop Push Buttons (Position 16+, Code S7)
This option provides factory installed 800F Start and Stop push buttons. In all cases, the Stop input to the drive must be present before the drive will
start. Using 3-wire control, speed source is parameter A070 [Preset Freq 0]. The Stop push button may also be used as a fault reset.
Component Specifications
Bulletin 800F Devices
Start Push Button Flush head, Green, 1 N.O. contact Stop Push Button Extended head, Red, 1 N.C. contact Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm Schematics Figure 2.7 on page 2-8
This option is not compatible with Codes R3, R5, S1, S20, S21, S22 or S23.
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts Screw terminals, 0.3–3.5 mm
2
(18 AWG), Blue
Figure 2.9 on page 2-10 Figure 2.10 on page 2-11
2
(22–12 AWG) maximum
Forward/Reverse Selector Switch (Position 16+, Code S8)
This 800F door mounted operator device is factory installed and provides a Forward/Reverse selector switch.
When configured for 2-wire control, the drive will start when the selector switch is set to Forward. When the selector switch is set to Reverse, the drive will run in reverse. If the selector switch is operated while the drive is running, a change of direction command will occur. If the drive is stopped and the selector switch is operated, a change of direction command will occur. The speed source is parameter P070 [Preset Freq 0].
When configured for 3-wire control (Code S7 with S8), the selector switch only changes direction. The drive is started and stopped via the Start and Stop push buttons (Code S7).
Component Specifications
Bulletin 800F Devices
Forward/Reverse Selector Switch
Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm Schematics 2-Wire Control: Figure 2.5 on page 2-6
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts Screw terminals, 0.3–3.5 mm
2-Wire: 2 position, Maintained, 1 N.O. & 1 N.C. contacts 3-Wire: 2 position, Maintained, 1 N.C. contact
2
(18 AWG), Blue
Figure 2.11 on page 2-12
3-Wire Control: Figure 2.10 on page 2-11
2
(22–12 AWG) maximum
, Figure 2.8 on page 2-9,
This option is not compatible with Codes R3, R5, S20 or S21.
Publication 23B-IN001G
Page 20
1-12 PowerFlex 40 Standard Configured Drive Standard Features and Options
Local Speed Potentiometer (Code S18)
This option provides a factory installed 800F door mounted one turn potentiometer for speed control. The device provides the speed source when no digital inputs are active.
When this option is provided, it becomes the speed source for the Hand mode of the Hand/Off/Auto selector switch (Option S1) and the Manual mode of the Auto/Manual selector switch (Option S4).
Component Specifications
Bulletin 800F Devices
Speed Potentiometer 1-turn, 10k, 2.25W, 500V Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm Schematic Figure 2.13 on page 2-14
This option is not compatible with Codes R3-R5.
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified Screw terminals, 0.3–3.5 mm
2
(18 AWG), Blue
2
(22–12 AWG) maximum
Local Control Off/Run Forward and Local/Remote Selector Switches
(Code S20)
This option provides two factory installed 800F door mounted selector switches. The Local/Remote selector switch determines the source of the start, stop, speed and direction commands. In Local mode, the factory default setting for parameter P038 [Speed Reference] = 4 “Preset Freq.”
In Remote mode, the factory default setting for parameter A051 [Digital In1 Sel] = 6 “Comm Port.” The Off/Run Forward selector switch allows the drive to be started and stopped when in Local Control.
Component Specifications
Bulletin 800F Devices IEC style, Internationally rated
Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts Screw terminals, 0.3–3.5 mm
Local Control Off/Run Forward Selector Switch
Local/Remote Selector Switch
Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm Schematic Figure 2.12 on page 2-13
2 position, Maintained, 1 N.O. contact
2 position, Maintained, 1 N.O. contact
2
(18 AWG), Blue
2
(22–12 AWG) maximum
Publication 23B-IN001G
This option is not compatible with Codes R3, R5, S1, S4, S7, S8, S21 or S22.
Page 21
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-13
Local/Off/Remote Selector Switch With One Normally Open Interposing Relay (Code S21)
This 800F door mounted operator device and interposing relay option is factory installed and provides a Local/Off/Remote selector switch.
The Local/Off/Remote selector switch will start the drive in Local mode and stop it in Off mode. In Remote mode, the drive will be stopped and started from the factory installed CR1 contact which is energized by a customer supplied and protected 120V AC source. In all cases, the Stop input to the drive must be present before the drive will start.
In both Local and Remote modes, the speed source is parameter A070 [Preset Freq 0].
Component Specifications
Bulletin 800F Devices
Local/Off/Remote Selector Switch
Interposing Control Relay
Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm Schematic Figure 2.14 on page 2-15
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts Screw terminals, 0.3–3.5 mm
3 position, Maintained, 2 N.O. contacts
1 relay, 10 amp, 120V AC coil, Octal base
2
(18 AWG), Blue
2
(22–12 AWG) maximum
This option is not compatible with Codes R3, R5, S1, S4, S7, S8, S20 or S22.
Publication 23B-IN001G
Page 22
1-14 PowerFlex 40 Standard Configured Drive Standard Features and Options
Spring Return Hand-Off-Auto Selector Switch (Code S22)
This 800F door mounted operator device is factory installed and provides a Hand/Off/Auto selector switch. The Hand position is equipped with a spring return.
The Hand/Off/Auto selector switch will start the drive while held in Hand mode and stop the drive in Off mode. The selector switch has a spring return disallowing the operator to remain in Hand. In Auto mode the drive will be stopped and started from remote contact closures. In all cases, the Stop input to the drive must be present before the drive will start.
The Hand/Off/Auto selector switch also determines the source of the actual drive speed reference. In Hand mode, speed source is parameter A072 [Preset Freq 2]. In Auto mode, speed source is parameter A071 [Preset Freq 1].
If the door mounted speed potentiometer (Option S18) is supplied and it is intended to be the speed reference in Hand mode, set parameter A052 [Digital In2 Sel] to option 13 “10V In Ctrl.”
Spring Return HOA Selector Switch (Code S22)
Speed Reference Parameter Settings
Hand Mode Auto Mode P038 [Speed Reference] A051 [Digital In1 Sel] A052 [Digital In2 Sel]
Preset Speed Preset Speed 4 “Preset Freq” 4 “Preset Freq” 4 “Preset Freq”
Analog Input (0-10V) 4 “Preset Freq” 13 “10V In Ctrl” 4 “Preset Freq”
Analog Input (4-20mA) 4 “Preset Freq” 14 “20mA In Ctrl” 4 “Preset Freq”
Communication Port
Speed Pot (Door) Preset Speed 4 “Preset Freq” 4 “Preset Freq” 13 “10V In Ctrl”
Analog Input (4-20mA) 4 “Preset Freq” 14 “20mA In Ctrl” 13 “10V In Ctrl”
Communication Port
HIM (Door) Preset Speed 4 “Preset Freq” 4 “Preset Freq” 6 “Comm Port”
Analog Input (0-10V) 4 “Preset Freq” 13 “10V In Ctrl” 6 “Comm Port”
Analog Input (4-20mA) 4 “Preset Freq” 14 “20mA In Ctrl” 6 “Comm Port”
(1)
Communication port will have both logic and reference control.
(1)
4 “Preset Freq” 6 “Comm Port” 4 “Preset Freq”
(1)
4 “Preset Freq” 6 “Comm Port” 13 “10V In Ctrl”
Publication 23B-IN001G
Component Specifications
Bulletin 800F Devices
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts
2
(22–12 AWG) maximum
Hand/Off/Auto Selector Switch:
Screw terminals, 0.3–3.5 mm 3 position, Hand (spring return), Off, Auto (maintained), 4 N.O. contacts
Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm
2
(18 AWG), Blue
Schematic Figure 2.16 on page 2-17
This option is not compatible with Codes R3, R5, S1, S4, S7, S20 or S21.
Page 23
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-15
Clear Fault Push Button (Code S23)
This option provides a factory installed 800F Clear Fault push button.
Component Specifications
Bulletin 800F Devices
Clear Fault Push Button:
Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm Schematic Figure 2.17 on page 2-18
This option is not compatible with Code S7.
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts Screw terminals, 0.3–3.5 mm Flush head, Black, 1 N.O. contact
2
(18 AWG), Blue
2
(22–12 AWG) maximum

Quick Disconnects

DeviceNet Quick Disconnect - Bottom (Code E22)
A Brad Harrison, 5 pin, bulkhead, male receptacle is provided and wired to the drive mounted DeviceNet module. The connector is located through the bottom of the enclosure providing a quick disconnect. This option is designed to enhance the DeviceNet offering (Position 12, Code D) and is not compatible with options 4, C, E, P (Position 12), or E23.
To review schematic refer to To review layout refer to
Figure 2.4 on page 2-5.
Figure 3.4 on page 3-4.
For NEMA/UL Type 4 or less stringent environments, the outer connector construction is made of plastic designed to withstand washdown conditions.
DeviceNet Quick Disconnect - Left Side (Code E23)
A Brad Harrison, 5 pin, bulkhead, male receptacle is provided and wired to the drive mounted DeviceNet module. The connector is located through the left side of the enclosure providing a quick disconnect. This option is designed to enhance the DeviceNet offering (Position 12, Code D) and is not compatible with options 4, C, E, P (Position 12), or E22.
To review schematic refer to To review layout refer to
Figure 2.4 on page 2-5.
Figure 3.4 on page 3-4.
For NEMA/UL Type 4 or less stringent environments the outer connector construction is made of plastic designed to withstand washdown conditions.
Publication 23B-IN001G
Page 24
1-16 PowerFlex 40 Standard Configured Drive Standard Features and Options

I/O Options

DeviceNet I/O (4 In/2 Out) w/Spring Return HOA and Power Disconnect Aux. Contact (Position 16+, Code R3)
This option provides a factory installed 800F door mounted operator device, a 100-DNY42R and a power disconnect auxiliary contact mounted internal to the cabinet.
The Hand/Off/Auto selector switch will start the drive while held in the Hand mode and stop it in the Off mode. The default speed reference comes from parameter P038, option 4 (Preset Freq). The selector switch has a spring return disallowing the operator to remain in Hand. When in Auto the default speed reference is derived parameter A051, option 4 (Preset Freq).
The 100-DNY42R is powered by DeviceNet and provides control based on customer control parameters.
This option is prewired with an auto contact from the Hand/Off/Auto selector switch between the I/O V+ and IN0 terminals. The main power disconnect auxiliary contact is wired between the I/O V+ and IN1 terminals indicating if the disconnect is on or off. Two inputs and two outputs are available for customer use.
Component Specifications
Bulletin 800F Devices
Hand/Off/Auto Selector Switch
Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm 100-DNY42R cULus Listed, CSA, CE
Schematic Figure 2.18 on page 2-19
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts Screw terminals, 0.3–3.5 mm
3 position, Hand (spring return), Off, Auto (maintained) 3 N.O. & 3 N.C. contacts
2
(18 AWG), Blue
DeviceLogix™, Rotary address switches 24V DC or 120V AC inputs High-Capacity transistor or Relay outputs ODVA Compliance v2.0 Tested Power Disconnect Auxiliary Contact 1 N.O. & 1 N.C. Side mounted contacts
2
(22–12 AWG) maximum
Publication 23B-IN001G
This option must be used with the drive mounted DeviceNet option D (Position 12) and is not compatible with options R4, R5, S1, S4, S7, S8, S20, S21 or S22. The drive mounted DeviceNet and the 100-DNY42R will appear as separate nodes on the communication system.
Page 25
PowerFlex 40 Standard Configured Drive Standard Features and Options 1-17
DeviceNet Point I/O w/IB4 (4 Inputs) (Position 16+, Code R4)
This option provides a factory installed 1734-ADNX Point I/O Scanner in combination with a 1734-IB4 (4 input) four point, 24V DC sink input.
The drive DeviceNet is prewired to the subnet connector of the 1734-ADNX. The customer is required to make the DeviceNet connection directly to the 1734-ADNX network connector. The 1734-IB4 is connected via a backplane offering four available inputs for customer use.
The Point I/O Scanner allows data to be gathered from the drive mounted DeviceNet and the 1734-IB4 (4 input) appear as one node on the communication system.
Refer to publication 1734-IN051 for more detail on the 1734-IB4.
Component Specifications
1734-ADNX Devices IEC style, Internationally rated
Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts Screw terminals, 0.3–3.5 mm
1734-IB4 Devices Refer to publication 1734-IN051 Schematic Figure 2.19 on page 2-20
2
(22–12 AWG) maximum
This option must be used with the drive mounted DeviceNet option D (Position 12) and is not compatible with options 4, C, E, P (Position 12), R3, or R5.
Note: Customer is required to supply external 24V DC/AC to power 1734-ADNX scanner.
Publication 23B-IN001G
Page 26
1-18 PowerFlex 40 Standard Configured Drive Standard Features and Options
DeviceNet I/O (4 In/ 2 Out) w/Spring Return HOA, Power Disconnect Aux. Contact, and 4 I/O Quick Disconnects (Position 16+, Code R5)
This option provides a factory installed 800F door mounted operator device, a 100-DNY42R mounted internal to the cabinet, a power disconnect auxiliary contact, four I/O quick disconnects, and a 24V DC male receptacle.
The Hand/Off/Auto selector switch will start the drive while held in the Hand mode and stop it in the Off mode. The default speed reference comes from parameter P038, option 4 (Preset Freq). The selector switch has a spring return disallowing the operator to remain in Hand. When in Auto the default speed reference is derived parameter A051, option 4 (Preset Freq).
The 100-DNY42R is powered by DeviceNet and provides control based on customer control parameters. The inputs and outputs are powered by customer supplied 24V DC.
This options is prewired with an auto contact from the Hand/Off/Auto selector switch between the I/O V+ and IN0 terminals. The main power disconnect auxiliary contact is wired between the I/O V+ and IN1 terminals indicating if the disconnect is on or off. The four I/O quick disconnects allow the customer to quickly connect to the remaining two inputs and outputs that are available for customer use.
Component Specifications
Bulletin 800F Devices
Hand/Off/Auto Selector Switch
Legend Plate 30 x 50 mm, Black with white lettering Wiring 0.8 mm 100-DNY42R cULus Listed, CSA, CE
Receptacle Shell Black anodized machined aluminum Connector Insert Nylon Contacts Machined brass with gold over nickel plating Schematic Figure 2.20 on page 2-21
IEC style, Internationally rated Meet IP65/IP66 and NEMA/UL Type 4/4X/13 UL Listed, CSA Certified 10 amp contacts Screw terminals, 0.3–3.5 mm
3 position, Hand (spring return), Off, Auto (maintained) 3 N.O. & 3 N.C. contacts
2
(18 AWG), Blue
DeviceLogix™, Rotary address switches 24V DC or 120V AC inputs High-Capacity transistor or Relay outputs ODVA Compliance v2.0 Tested Power Disconnect Auxiliary Contact 1 N.O. & 1 N.C. Side mounted contacts
2
(22–12 AWG) maximum
This option must be used with the drive mounted DeviceNet option D (Position 12) and is not compatible with options R3, R4, S1, S4, S7, S8, S20, S21 or S22. The drive mounted DeviceNet and the 100-DNYR42 will appear as separate nodes on the communication system.
Publication 23B-IN001G
Page 27

Control Wiring Overview

Chapter 2

Chapter Objectives

Control Wiring Overview

This chapter describes the control and signal wiring connection options.
For information on … See page …
Control Wiring Overview Schematic Drawings 2-2
2-1
Refer to the PowerFlex 40 User Manual for additional detailed information about control and signal wiring.
The Control I/O Terminal Block (TB1) and Relay Terminal Block (TB2) located on the drive Main Control Board provide terminals for interfacing customer supplied control inputs and outputs. All analog and discrete control wiring will be made at these terminals.
To connect control and signal wiring to the drive package:
1. Wire the control and signal leads by routing them according to the drive
option type. Note that you must punch openings in the option cabinet of the desired conduit size, following NEC and all applicable local codes and standards. I/O terminal block specifications are listed in Table 2.A
.
Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot).
2. Connect the control and signal wiring to the I/O terminals located on the
drive.
3. Tighten the I/O terminals to the proper torque according to drive type as
shown in Table 2.A
Table 2.A I/O Terminal Block Specifications
Voltage Rating Maximum Wire Size
208-460V AC 1.3 mm
(1)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
.
(1)
Minimum Wire Size Torque
2
(16 AWG) 0.13 mm2 (26 AWG) 0.5-0.8 N-m (4.4-7 lb.-in.)
Publication 23B-IN001G
Page 28
2-2 Control Wiring Overview

Schematic Drawings

Figure 2.1 Power Distribution Option
Publication 23B-IN001G
Page 29
Figure 2.2 Drive Ratings
Control Wiring Overview 2-3
Publication 23B-IN001G
Page 30
2-4 Control Wiring Overview
Figure 2.3 Control Logic Options 4, C, D, E & P
Publication 23B-IN001G
Page 31
Figure 2.4 Control Logic Option S1
Control Wiring Overview 2-5
Publication 23B-IN001G
Page 32
2-6 Control Wiring Overview
Figure 2.5 Control Logic Option S1 & S8
Publication 23B-IN001G
Page 33
Figure 2.6 Control Logic Option S4
Control Wiring Overview 2-7
Publication 23B-IN001G
Page 34
2-8 Control Wiring Overview
Figure 2.7 Control Logic Option S4 & S7
Publication 23B-IN001G
Page 35
Figure 2.8 Control Logic Option S4 with S8
Control Wiring Overview 2-9
Publication 23B-IN001G
Page 36
2-10 Control Wiring Overview
Figure 2.9 Control Logic Option S7
Publication 23B-IN001G
Page 37
Figure 2.10 Control Logic Option S7 and S8
Control Wiring Overview 2-11
Publication 23B-IN001G
Page 38
2-12 Control Wiring Overview
Figure 2.11 Control Logic Option S8
Publication 23B-IN001G
Page 39
Figure 2.12 Control Logic Option S20
Control Wiring Overview 2-13
Publication 23B-IN001G
Page 40
2-14 Control Wiring Overview
Figure 2.13 Control Logic Option S18
Publication 23B-IN001G
Page 41
Figure 2.14 Control Logic Option S21
Control Wiring Overview 2-15
Publication 23B-IN001G
Page 42
2-16 Control Wiring Overview
Figure 2.15 Control Logic Option S22
Publication 23B-IN001G
Page 43
Figure 2.16 Control Logic Option S22 & S8
Control Wiring Overview 2-17
Publication 23B-IN001G
Page 44
2-18 Control Wiring Overview
Figure 2.17 Control Logic Option S23
Publication 23B-IN001G
Page 45
Control Wiring Overview 2-19
Figure 2.18 Control Logic Option R3 with P3/P3T or P6/P6T
Publication 23B-IN001G
Page 46
2-20 Control Wiring Overview
Figure 2.19 Control Logic Option R4
Publication 23B-IN001G
Page 47
Control Wiring Overview 2-21
Figure 2.20 Control Logic Option R5 with P3/P3T or P6/P6T
Publication 23B-IN001G
Page 48
2-22 Control Wiring Overview
Figure 2.21 Interconnect Wire & Parts List
Publication 23B-IN001G
Page 49

Mechanical Installation

Chapter 3

Chapter Objectives

Mounting Considerations

This chapter provides information on mounting a PowerFlex 40 Standard Configured Drive.
For information on … See page …
Mounting Considerations Dimensions 3-2 Layout Drawings 3-4
ATTENTION: The following information is merely a guide for proper installation. The Allen-Bradley Company cannot assume
!
responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
3-1
Environment
Before deciding on an installation site, verify that the PowerFlex Drive Packages are not installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. The drives are to be installed per the environmental rating they have been designed for.
Maximum Surrounding Air Temperature
PowerFlex 40 Standard Configured Drives are designed to operate at -10° to 40°C (14° to 104°F) surrounding air temperature. The design of the PowerFlex Standard Configured Drive supports indoor and outdoor applications that are not in direct sunlight.
Minimum Mounting Clearances
Be sure there is adequate clearance for air circulation around the drive. For best air movement, do not mount drives directly above each other. Note that no devices are to be mounted behind the drive. This area must be kept clear of all control and power wiring.
Publication 23B-IN001G
Page 50
3-2 Mechanical Installation
Figure 3.1 Minimum Mounting Clearances
Dimensions are in millimeters and (inches).
Drive or
other device
152.4 (6.00)

Dimensions

355.1
(13.98)
342.4
(13.48)
Figure 3.2 Frame B Dimensions
Dimensions are in millimeters and (inches).
405.9
(15.98)
393.2
(15.48)
(0.37)
304.8
(12.00)
9.4
285.8
(11.25)
152.4 (6.00)
355.6
(14.00)
O
F F
336.6
(13.25)
ON
152.4 (6.00)
152.4
177.8
(7.00)
(6.00)
69.3
(2.73)
ON
O
F F
287.5
(11.32)
Publication 23B-IN001G
6.35
(0.25)
Optional mounting bracket orientation.
Page 51
Figure 3.3 Frame C Dimensions
Dimensions are in millimeters and (inches).
Mechanical Installation 3-3
Frame C
460.8
(18.14)
427.2
(16.82)
(0.63)
406.4
(16.00)
9.7
(0.38)
16.0
457.2
(18.00)
425.2
(16.74)
P3 Option
383.3
(15.09)
P6 Option
364.2
(14.34)
177.8 (7.00)
ON
O
F F
146.1 (5.75)
Detail
19.1
(0.75)
19.1 (0.75)
12.7 (0.50)
Publication 23B-IN001G
Page 52
3-4 Mechanical Installation

Layout Drawings

Figure 3.4 PowerFlex 40 Frame B Layout Drawing
Publication 23B-IN001G
Page 53
Figure 3.5 PowerFlex 40 Frame C Layout Drawing
Mechanical Installation 3-5
Publication 23B-IN001G
Page 54
3-6 Mechanical Installation
Figure 3.6 PowerFlex 40 General Option Layout Drawing
Publication 23B-IN001G
Page 55

Appendix A

Specifications

Table A.A Standard Configured Drive Products
Input/Output Ratings Output Frequency: 0-400 Hz (Programmable)
Approvals
Fuses and Power Disconnecting Means
Protective Features Over Voltage: 480V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)
Environment Ambient Operating Temperature, NEMA 4/12, 4X (IP66): –10 to 40 degrees C (14 to 104 degrees F)
Control Carrier Frequency: 2-4 kHz. Drive rating and heat calculations are based on 4 kHz.
(1) The design of the PowerFlex 40 Standard Configured Drive NEMA 4/12 and 4X packages support indoor and outdoor applications that are not in direct sunlight.
When optional Door Mounted HIM is supplied, enclosure is rated for indoor use only.
Table A.B Standard PowerFlex 40 Drives
Digital Control Inputs
(Input Current = 6 mA)
Analog Control Inputs 4-20mA Analog: 250 ohm input impedance
Control Output Programmable Output (form C relay)
Fuses and Circuit Breakers Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
Protective Features Motor Protection: I
Dynamic Braking Internal brake IGBT included with all ratings Environment Altitude: 1000 m (3300 ft) max. without derating
Control Frequency Accuracy
Efficiency: 97.5% (Typical)
9
D
6
E
6
T
X
S
I
L
U
L
®
I
N
D
Q
E
C
T
O
N
UL508C
9
D
6
E
6
T
X
S
I
L
U
L
C
®
I
N
D
Q
E
C
T
O
N
CSA C 22.2 No. 14
140M Motor Circuit Protector: Provides branch circuit protection, 65 kA short circuit withstand 194R Fused Disconnect: Provides branch circuit protection, 100 kA short circuit withstand, Class J fuses
Under Voltage: 480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)
(1)
Cooling Method: Fan (All drive ratings)
SRC (Source) Mode: 18 – 24 Volts = ON; 0 – 6 Volts = OFF SNK (Sink) Mode: 0 – 6 Volts = ON; 18 – 24 Volts = OFF
0-10V DC Analog: 100k ohm input impedance External Pot: 1-10k ohms, 2 Watt minimum
Resistive Rating: 3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC Inductive Rating: 0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC
Opto Outputs
30V DC, 50 mA Non-inductive
Analog Output (10-bit)
0-10V, 1k ohm Min.
Recommended Circuit Breakers: HMCP circuit breaker or equivalent.
2
t overload protection – 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)
Overcurrent: 200% hardware limit, 300% instantaneous fault Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs Faultless Power Ride Through: 100 milliseconds
Storage Temperature: –40 to 85 degrees C (–40 to 185 degrees F) Atmosphere: Important: Drive must not be installed in an area where the ambient atmosphere contains
volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Relative Humidity: 0 to 95% non-condensing Shock (operating): 15G peak for 11ms duration (±1.0ms) Vibration (operating): 1G peak, 5 to 2000 Hz
Digital Input: Within ±0.05% of set output frequency. Analog Input: Within 0.5% of maximum output frequency. Analog Output: ±2% of full scale, 10-bit resolution
Speed Regulation - Open Loop with Slip Compensation: ±2% of base speed across a 40:1 speed range.
1% of base speed across a 60:1 speed range.
Stop Modes: Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve. Accel/Decel: Two independently programmable accel and decel times. Each time may be programmed from 0 -
600 seconds in 0.1 second increments.
Intermittent Overload: 150% Overload capability for up to 1 minute; 200% Overload capability for up to 3 seconds Electronic Motor Overload Protection: Class 10 protection with speed sensitive response.
Publication 23B-IN001G
Page 56
A-2 Specifications
Notes:
Publication 23B-IN001G
Page 57

Appendix B

Replacement Parts

Table B.A Components
Description Designation Voltage HP Part Number Manufacturer
Motor Circuit Protector Option P3 or P3T
MCP1 480V AC 0.5 140M-C2E-B40
1.0 140M-C2E-B63
2.0 140M-D8E-C10
3.0 140M-D8E-C16
5.0 140M-D8E-C25
7.5 140M-F8E-C25 10 140M-F8E-C32 15 140M-F8E-C45
1.0 363333 Allen-Bradley
Replacement Kit Option P3
(1)
MCP1 480V AC 0.5 363326 Allen-Bradley
2.0 363337 Allen-Bradley
3.0 363341 Allen-Bradley
5.0 363345 Allen-Bradley
7.5 363349 Allen-Bradley 10 363353 Allen-Bradley 15 363357 Allen-Bradley
Operator Handle Option P3 or P3T
Operator Handle
MCP1 480V AC 0.5-5
7.5-15
190-HS4 140M-C-DN66
MCP1 480V AC 0.5-15 140M-D-HA Allen-Bradley Adaptor Option P3 or P3T
Operator Shaft Option P3 or P3T
Operator Terminal Markings
MCP1 480V AC 0.5-5
7.5-15
194R-NX12 140M-C-DS
MCP1 480V AC 0.5-5.0 A46006-086-01
140M-C-TE
7.5-15 A46006-091-01 140M-F-TE
Disconnect Switch Option P6 or P6T
Operator Handle
DS1 480V AC 0.5-10 194R-NJ030P3 Allen-Bradley
15 194R-NJ060P3 Allen-Bradley
DS1 480V AC 0.5-15 194R-HS4 Allen-Bradley
Option P6 or P6T Operator Shaft
DS1 480V AC 0.5-15 194R-R1 Allen-Bradley
Option P6 or P6T Main Fuses
Option P6 or P6T
F1, F2, F3 480V AC 0.5 LPJ-3SP Bussman
AJT-3 Ferraz-Shawmut
1.0 LPJ-6SP Bussman
2.0 LPJ-10 Bussman LPJ-10SP Bussman AJT-10 Ferraz-Shawmut
3.0 LPJ-15 Bussman LPJ-15SP Bussman
5.0 LPJ-20 Bussman LPJ-20SP Bussman AJT-20 Ferraz-Shawmut
7.5 LPJ-25 Bussman LPJ-25SP Bussman AJT-25 Ferraz-Shawmut
10 LPJ-30 Bussman
LPJ-30SP Bussman AJT-30 Ferraz-Shawmut
15 LPJ-50 Bussman
LPJ-50SP Bussman
(1) Replacement Kit includes Motor Circuit Protector and top and bottom terminal labels/instructions. Does not
include handle, adaptor, or connection rod.
(2) Part of Motor Circuit Protector Replacement Kit.
(2)
Allen-Bradley
(2)
Allen-Bradley
(2)
Allen-Bradley
(2)
Allen-Bradley
(2)
Allen-Bradley
(2)
Allen-Bradley
(2)
Allen-Bradley
(2)
Allen-Bradley
Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley
(2)
(2)
Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley
(2)
(2)
Publication 23B-IN001G
Page 58
B-2 Replacement Parts
Table B.A Components (Continued)
Description Designation Voltage HP Part Number Manufacturer
Drive Module (with Heatsink)
Drive Module (Plate Drive)
EA1 480V AC 0.5 22B-D1P4F104 Allen-Bradley
1.0 22B-D2P3F104 Allen-Bradley
2.0 22B-D4P0F104 Allen-Bradley
3.0 22B-D6P0F104 Allen-Bradley
5.0 22B-D010F104 Allen-Bradley
7.5 22B-D012F104 Allen-Bradley 10 22B-D017F104 Allen-Bradley 15 22B-D024F104 Allen-Bradley
EA1 480V AC 0.5 22B-D1P4H204 Allen-Bradley
1.0 22B-D2P3H204 Allen-Bradley
2.0 22B-D4P0H204 Allen-Bradley
3.0 22B-D6P0H204 Allen-Bradley
5.0 22B-D010H204 Allen-Bradley
7.5 22B-D012H104 Allen-Bradley 10 22B-D017H104 Allen-Bradley 15 22B-D024H104 Allen-Bradley
Table B.B Communication Options
Description Designation Voltage HP Part Number Manufacturer
ControlNet EA1 All All 22-COMM-C Allen-Bradley DeviceNet EA1 All All 22-COMM-D Allen-Bradley EtherNet EA1 All All 22-COMM-E Allen-Bradley PROFIBUS EA1 All All 22-COMM-P Allen-Bradley Adaptor
Frame B Frame C
EA1 EA1
All All
0.5-5.0
7.5-15
22B-CCB 22B-CCC
Allen-Bradley Allen-Bradley
Table B.C Quick Disconnect Options
Description Designation Voltage HP Part Number Manufacturer
DeviceNet - Bottom E22 All All 41358N Brad Harrison DeviceNet - L Side E23 All All 41358N Brad Harrison
Table B.D HIM Options
Description Designation Voltage HP Part Number Manufacturer
Door Mounted IP 66 (NEMA/UL Ty pe
All All 22-HIM-C2S Allen-Bradley
Publication 23B-IN001G
Page 59
Replacement Parts B-3
Table B.E Operator Devices/Control Options
Option Description Designation Voltage HP Part Number Manufacturer
Option S1 Selector Switch
Mounting Latch Contact Block - 4 N.O. Legend Plate
Option S4 Selector Switch
Mounting Latch Contact Block - 1 N.O. Contact Block - 1 N.C. Legend Plate
Option S7 Push Button (Green)
Push Button (Red) Mounting Latch Contact Block - 1 N.O. Contact Block - 1 N.C. Legend Plate Legend Plate
Option S8 Selector Switch
Mounting Latch Contact Block - 1 N.O. Contact Block - 1 N.C. Legend Plate
Option S18 Potentiometer/Operator
Legend Plate
Option S20 Selector Switch
Mounting Latch Contact Block - 1 N.O. Legend Plate Legend Plate
Option S21 Selector Switch
Anti-Rotation Switch Mounting Latch Contact Block - 2 N.O. Legend Plate MOV Relay Relay Socket (Base) Relay Retainer Clip
Option S22 Selector Switch
Mounting Latch Contact Block - 1 N.O. Legend Plate
Option S23 Push Button (Black)
Mounting Latch Contact Block - 1 N.O. Legend Plate
Option R3/R5 Selector Switch
Aux Contact Adapter Aux Contact Aux Contact
(1) (2)
Contact Block - 5 N.O. Legend Plate I/O Module Quick Disconnect Quick Disconnect Terminal Block Fuse Block
(3)
Fuse
(3) (3)
(3)
(3)
Option R4 DeviceNet Adaptor
Point I/O Terminal Base Input I/O Module
(1) P6 and P6T option only. (2) P3 and P3T option only. (3) R5 option only. (4) Option S8 when S7 is not ordered. (5) Legend plates are not stocked for general sale. A custom quote is required to purchase.
(1)
SS2 SS2 SS2 SS2
SS1 SS1 SS1 SS1 SS1
PB2 PB3 PB2, PB3 PB2 PB3 PB2 PB3
SS3 SS3 SS3 SS3 SS3
RH1 RH1
SS1, SS2 SS1, SS2 SS1, SS2 SS1 SS2
SS2 SS2 SS2 SS2 SS2 CR1 CR1 CR1 CR1
SS2 SS2 SS2 SS2
PB1 PB1 PB1 PB1
SS2 DS1 DS1 MCP1 SS2 SS2 EA4 RCPT1-RCPT4 RCPT5 TB4 F6 F6
EA4 EA4 IB4
All All 800FP-SM32
800F-ALP 800F-X10 354614
All All 800FP-SM22
800F-ALP 800F-X10 800F-X01 354650
All All 800FP-F3
800FP-E4 800F-ALP 800F-X10 800F-X01 354666 354859
All All 800FP-SM22
800F-ALP 800F-X10 800F-X01
(4)
354662
All All 800F-POT6
362657
All All 800FP-SM22
800F-ALP 800F-X10 354702 354786
All All 800FP-SM32
800F-ALC1 800F-ALP 800F-X10 354769 V130LA10A 700-HA 32A1 700-HN125 700HN159
All All 800FP-SL32
800F-ALP 800F-X10 354614
All All 800FP-F2
800F-ALP 800F-X10 382966
All All 800FP-SL32CR
194R-AA 195-GA11 140M-C-ASA11 800F-X10 354614 100-DNY42R 888D-F4AC2-1 888D-M4AE1-1 1492-WTF3 1492-H6 MDA-3
All All 1734-ADNX
1734-TB3SQ10 1734-IB4
Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Harris Allen-Bradley Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley
Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Allen-Bradley Bussmann
Allen-Bradley Allen-Bradley Allen-Bradley
(5)
(5)
(5) (5)
(5)
(5)
(5) (5)
(5)
(5)
(5)
(5)
Publication 23B-IN001G
Page 60
B-4 Replacement Parts
Table B.F Miscellaneous
Description Designation Voltage HP Part Number Manufacturer
Fan FAN All 0.5-5.0 2410ML-05W-B30-B00 NMB Tech
Publication 23B-IN001G
Page 61
Page 62
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication 23B-IN001G-EN-P – May 2008 350679-P07
Supersedes 23B-IN001F-EN-P – January 2007 Copyright © 2007 Rockwell Automation, Inc. All rights reserved. Printed in USA.
Loading...