POINT I/O and ArmorPOINT I/O DeviceLogix Modules User Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may
lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or
economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may
be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach
dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc
Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements
for safe work practices and for Personal Protective Equipment (PPE).
2Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Rockwell Automation Publication 1734-UM015B-EN-E - May 20205
Table of Contents
Notes:
6Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the additions made to this revision.
TopicPage
Updated version and revision information13, 84
Changed Function Block category to Compute/Math67
Added Down Counter type in Timer/Counter category instruction
types
Updated Timer/Counter Category information 70
Removed Square Root (SQR) and Power (XPY) in the Compute
Category
Updated Logic Execution Time table74
New Appendix section for Write Enable Flag Feature113
69
71
Rockwell Automation Publication 1734-UM015B-EN-E - May 20207
Summary of Changes
Notes:
8Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Preface
Purpose of This Manual
This manual describes how to install, configure, and troubleshoot your
POINT I/O™ DeviceLogix™ and ArmorPOINT® I/O DeviceLogix
modules.
POINT I/O and ArmorPOINT I/O modules can be used in EtherNet/IP™,
DeviceNet®, and ControlNet® systems. As such, you may need to refer to
other publications in addition to this one.
When using POINT I/O DeviceLogix modules with a communication
adapter, use this manual in conjunction with the user manual for the adapter
you are using as shown in the table.
POINT I/O DeviceLogix modules are not compatible with the PROFIBUS
adapter.
When using ArmorPOINT I/O DeviceLogix modules with a communication
adapter, use this manual in conjunction with the user manual for the adapter
you are using as shown in the table.
ArmorPOINT I/O DeviceLogix modules are not compatible with the
PROFIBUS adapter.
The modules in this manual are DeviceNet-ready. Each module can exist on
the DeviceNet network as one of the following:
• An individual node
• With an adapter (catalog number 1734-ADN or 1734-ADNX) as a
single node
For applications using these modules in a network with a 1734-PDN
DeviceNet Communication Interface, or a 1734D-xx POINTBlock I/O
module, this user manual is the primary documentation.
Rockwell Automation Publication 1734-UM015B-EN-E - May 20209
Preface
Who Should Use This
Manual
This manual is intended for qualified personnel. You should know how to do
the following:
• Use RSNetWorx™ software or similar configuration software to se
and calib
•
Download and use electronic data sheet (EDS) files.
rate these module
s.
In addition, you should be familiar with RSLogix 5000® and CIP™ Network
terminology. If you do not, refer to your
software documentation or online
help before attempting to use these modules.
Related Publications
Refer to this table for a list of related POINT I/O products and
documentation. The publications are available atrok.auto/literature. For
specification and safety certification information, refer to the installation
instructions.
Resource Description
POINT I/O DeviceLogix Module
POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix
Installation Instructions, publication 1734-IN039
Communication Devices
ControlNet Adapter Installation Instructions, publication 1734-IN582Provides installation information about 1734-ACNR adapters.
ControlNet Adapter User Manual, publication 1734-UM008
DeviceNet Communication Interface Module Installation Instructions,
publication 1734-IN057
DeviceNet Adapter Installation Instructions, publication 1734-IN026Provides installation information about 1734-ADN and 1734-ADNX
DeviceNet Adapter User Manual, publication 1734-UM002
RSNetWorx for DeviceNet Getting Results Guide, publication DRNET-
GR001
EtherNet/IP Adapter Installation Instructions, publication 1734-IN590Provides installation information about 1734-AENT adapters.
EtherNet/IP Adapter User Manual, publication 1734-UM011
Power Supplies, Wiring Base Assemblies, Miscellaneous
Field Potential Distributor Installation Instructions, publication 1734-IN059Provides installation information about 1734-FPD distributors.
POINT I/O 24V DC Expansion Power Supply Installation Instructions,
publication 1734-IN058
POINT I/O 120/240V AC Expansion Power Supply Installation Instructions,
publication 1734-IN017
POINT I/O Common Terminal Module Installation Instructions, publication
1734-IN024
POINT I/O Voltage Terminal Module Installation Instructions, publication
1734-IN024
Provides installation information and wiring diagrams for 1734-8CFGDLX
modules.
Describes how to use 1734-ACNR adapters.
Provides installation information about 1734-PDN modules.
adapters.
Describes how to use 1734-ADN and 1734-ADNX adapters.
Describes how to install and navigate the RSNetWorx for DeviceNet
software.
Describes how to use 1734-AENT adapters.
Provides installation information about 1734-EP24DC power supplies.
Provides installation information about 1734-EPAC power supplies.
Provides installation information about 1734-CTM modules.
Provides installation information about 1734-VTM modules.
t up
10Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Resource Description
POINT I/O Wiring Base Assembly Installation Instructions, publication
1734-IN511
POINT I/O Wiring Base Assembly Installation Instructions, publication
1734-IN013
POINT I/O One-piece Wiring Base Assembly Installation Instructions,
publication 1734-IN028
Provides installation information about 1734-TB and 1734-TBS assemblies.
Provides installation information about 1734-TB3 and 1734-TB3S
assemblies.
Provides installation information about 1734-TOP, 1734-TOPS, 1734-TOP3,
and 1734-TOP3S assemblies.
Refer to this table for a list of related ArmorPOINT I/O products and
documentation. The publications are available atrok.auto/literature. For
specification and safety certification information, refer to the installation
instructions.
ArmorPOINT I/O DeviceNet Adapter User Manual, publication 1738-UM001 Describes how to use 1738-ADN and 1738-ADNX adapters.
ArmorPOINT EtherNet/IP Adapter, Series A Installation Instructions,
publication 1738-IN017
ArmorPOINT I/O 2-Port EtherNet/IP Adapter, Series A Installation
Instructions, publication 1738-IN028
Power Supplies, Wiring Base Assemblies, Miscellaneous
ArmorPOINT I/O Field Potential Distributor, Series A Installation
Instructions, publication 1738-IN019
ArmorPOINT I/O 24V DC Expansion Power Supply, Series A Installation
Instructions, publication 1738-IN020
Provides wiring diagrams for 1738-8CFGDLXM8, 1738-8CFGDLXM12, and
1738-8CFGDLXM23.
Provides installation information about 1738-8CFGDLXM8, 17388CFGDLXM12, and 1738-8CFGDLXM23.
Provides installation information about 1738-ACNR adapters.
Provides installation information about 1738-ADN and 1738-ADNX
adapters.
Provides installation information about 1738-AENT adapters.
Provides installation information about 1738-AENTR adapters.
Provides installation information about 1738-FPD distributors.
Provides installation information about 1738-EP24DC power supplies.
Preface
Rockwell Automation Publication 1734-UM015B-EN-E - May 202011
Preface
Notes:
12Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Introduction
Chapter
1
About This Chapter
About the Modules
This chapter introduces POINT I/O and ArmorPOINT I/O configurable
modules with DeviceLogix capability.
•About the Modules
• Quick Start - Prepare the Modules to work on DeviceNet
• Quick Start - Prepare the Modules to work on EtherNet/IP and
ControlNet
The POINT I/O and ArmorPOINT I/O modules work with EtherNet/IP,
DeviceNet, and ControlNet network adapters. Each module has eight 24V DC
I/O points that self-configure to be inputs or outputs. Inputs are IEC Type 3
and outputs are self-protecting 0.5 A outputs.
The firmware in these modules uses Version 3 (1738-8CFGDLXM8,
1738-8CFGDLXM12, 1738-8CFGDLXM23) and Version 7
(1734-8CFGDLX) of the DeviceLogix master library. The modules can
execute 144 DeviceLogix function blocks in 3 ms. Smaller programs that
contain fewer than 40 function blocks can be executed in 1 ms.
Each module produces 20 bytes of data including I/O state (8 bits), eight
user-defined bits, and eight user-defined words of analog data to be consumed
by processors or other DeviceLogix modules. Each module consumes 20 bytes
of data to set the I/O state (8 bits), eight user-defined control bits, and eight
user-defined words of analog data. It is also possible to consume the data from
up to eight other peers.
This table lists 1734 and 1738 configurable I/O modules with DeviceLogix.
Module DescriptionCat. No.
POINT I/O module with 8 configurable 24V DC I/O points
and DeviceLogix capabilities
ArmorPOINT I/O module with 8 configurable 24V DC M8
connectors and DeviceLogix
ArmorPOINT I/O module with 8 configurable 24V DC M12
connectors and DeviceLogix
ArmorPOINT I/O module with 1 configurable 24V DC M23
connector and DeviceLogix
Rockwell Automation Publication 1734-UM015B-EN-E - May 202013
1734-8CFGDLX
1738-8CFGDLXM8
1738-8CFGDLXM12
1738-8CFGDLXM23
Introduction
1734-8CFGDLX
This module is an 8-point 24V DC I/O module with eight self-configuring
points and DeviceLogix capabilities. Each of the I/O points can be either a
DC input or output. The module supports removal and insertion under power,
auto-address, and auto-baud in compliance with the POINTBus™ backplane.
1738-8CFGDLXM8, 1738-8CFGDLXM12, and 1738-8CFGDLXM23
The ArmorPOINT I/O family consists of modular I/O modules. The sealed
IP67 housing of these modules requires no enclosure. Environmental
requirements other than IP67 may require an additional appropriate housing.
I/O connectors are sealed M8 (Pico™), M12 (micro) or M23 styles. The
mounting base ships with the module.
Modes of Usage
The module can be used in one of the following modes:
• as a standard POINT I/O module,
• in a standalone DeviceLogix program where it controls its own I/O, and
• in network applications with or without the peer exchange of data.
Standard POINT I/O Module
The module can simply be used as an 8-point configurable POINT I/O
module. It uses ODVA pre-defined Produce and Consume assemblies. Default
settings help to facilitate quick setup right out-of-the-box. It is CIP network
independent and it can run on DeviceNet, EtherNet/IP or ControlNet when
used in conjunction with an adapter.
14Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Introduction
Stand Alone DeviceLogix
If DeviceLogix is enabled (programmed), then the module becomes the owner
of its outputs. The DeviceLogix program reads inputs and controls the
onboard outputs.
• The produced assembly may be shared with a controller if a connection
exists.
• As the owner of its local outputs, the module may run without an
external controller.
An external controller, which is the owner of the connection to the module,
can influence the module’s logic via a consume assembly – both digital and
analog data. Configuration of the module is performed via RSNetWorx for
DeviceNet. When used on ControlNet or EtherNet/IP, the tool bridges
through the adapter to directly communicate with the DeviceLogix module on
the POINT I/O backplane.
Peer Enabled POINT I/O
The POINT I/O DeviceLogix module can “listen in” on data connections to
other POINT I/O modules on the backplane. This data can be used in the
DeviceLogix program to control the outputs. It can consume data from eight
different peers. The data from each peer can be up to 24 bytes long. The data
can be digital, analog (16-bit), or a mixture. The module supports the “Auto
Produce” parameter to produce I/O data automatically without the need for a
master. It will also produce and consume network data. Configuration of peer
data is performed via RSNetWorx.
See Chapter 6, Configuring POINT I/O and ArmorPOINT I/O DeviceLogix
modules using RSNetWorx for DeviceNet.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202015
Introduction
Mount the Module
For POINT I/O, see Chapter 2
.
For ArmorPOINT I/O, see Chapter 3
.
Wire the Module
For POINT I/O, see Chapter 2
.
For ArmorPOINT I/O, see Chapter 3
.
Configure DeviceNet Network and
Scanner
See Chapter 4
.
Configure the Module using
RSNetWorx for DeviceNet
See Chapter 6
.
Write the DeviceLogix Program
See Chapter 7
.
Quick Start - Prepare the
Modules to work on
DeviceNet
16Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Quick Start - Prepare the
Mount the Module
For POINT I/O, see Chapter 2
.
For ArmorPOINT I/O, see Chapter 3
.
Wire the Module
For POINT I/O, see Chapter 2
.
For ArmorPOINT I/O, see Chapter 3
.
Add Module to RSLogix 5000
See Chapter 5
.
Write the DeviceLogix Program in
RSNetWorx for DeviceNet
See Chapter 7
.
Modules to work on
EtherNet/IP and ControlNet
Introduction
Rockwell Automation Publication 1734-UM015B-EN-E - May 202017
Introduction
Notes:
18Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Chapter
ATTENTION
2
Install POINT I/O DeviceLogix Modules
If you are using ArmorPOINT I/O modules
(1738-8CFGDLXM8/M12/M23), go to Chapter 3, Install ArmorPOINT I/O
DeviceLogix Modules.
About This Chapter
Read this chapter for installation and wiring information including how to
complete the following:
• Install the Mounting Base Assembly
• Install an I/O Module
• Install the Removable Terminal Block
• Remove a 1734-TB or 1734-TBS Base
• Wire the Modules
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications
(as defined in IEC publication 60664-1), at altitudes up to 2000 m
(6561 ft) without derating.
This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be potential difficulties ensuring
electromagnetic compatibility in other environments due to
conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be
mounted within an enclosure that is suitably designed for those
specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from
accessibility to live parts. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain
product safety certifications.
See NEMA Standards 250 and IEC 60529, as applicable, for
explanations of the degrees of protection provided by different
types of enclosure. Also, see the appropriate sections in this
publication, as well as the Allen-Bradley publication 1770-4.1
(Industrial Automation Wiring and Grounding Guidelines), for
additional installation requirements pertaining to this equipment.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202019
Install POINT I/O DeviceLogix Modules
ATTENTION
WARNING
ATTENTION
POINT I/O is grounded through the DIN rail to chassis ground.
Use zinc-plated, yellow-chromated steel DIN rail to assure proper
grounding. The use of DIN rail materials (for example, aluminum
or plastic) that can corrode, oxidize, or are poor conductors, can
result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.).
EXPLOSION HAZARD
• Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment
unless power has been removed or the area is known to
be nonhazardous. Secure any external connections that
mate to this equipment by using screws, sliding latches,
threaded connectors, or other means provided with this
product.
• Substitution of components may impair suitability for
Class I, Division 2.
• If this product contains batteries, they must only be
changed in an area known to be nonhazardous.
Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these
guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging
when not in use.
20Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Install POINT I/O DeviceLogix Modules
Module
Status
Network
Status
NODE:
0
1
2
3
4
5
6
7
Mechanical
Keying (orange)
Module Wiring
Diagram
Module Locking
Mechanism
Insertable I/O
Module
Mounting Base
Removable Terminal
Block (RTB)
DIN Rail Locking
Screw (orange)
Slide-in Writable
Label
Interlocking Side
Pieces
44713
RTB Removal
Handle
44714
1734-TOP or
1734-TOPS
One-piece
Terminal Base
with Screw or
Spring Clamp
Insertable
I/O Module
Slide-in
Writable Label
Handle
Module Locking
Mechanism
Interlocking
Side Pieces
DIN Rail Locking
Screw (orange)
Module Wiring
Diagram
Mechanical
Keying (orange)
Install the Mounting Base
Assembly
The 1734-8CFGDLX is compatible with 1734-TB, 1734-TBS, 1734-TOP, and
1734-TOPS wiring bases.
The 1734-TB or 1734-TBS wiring base assembly consists of a 1734-MB
mounting base and a 1734-RTB or 1734-RTBS removable terminal
block (RTB).
1734-TB or 1734-TBS wiring base
The 1734-TOP and 1734-TOPS are one-piece terminal bases.
1734-TOP or 1734-TOPS wiring base
Rockwell Automation Publication 1734-UM015B-EN-E - May 202021
Install POINT I/O DeviceLogix Modules
44858
Removable Terminal
Block (RTB)
Mounting Base
31586
To install the mounting base assembly on the DIN rail, proceed as follows.
1. If you are using the 1734-TB or 1734-TBS mounting base, attach the
RTB to the mounting base.
Otherwise, skip to step 2.
2. Position the mounting base (wiring base assembly) vertically above the
installed units, for example, adapter, power supply, or existing module.
3. Slide the mounting base down, allowing the interlocking side pieces to
engage the adjacent module, power supply, or adapter.
4. Press firmly to seat the mounting base on the DIN rail until the base
snaps into place.
22Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
5. Use a small-bladed screwdriver to rotate the DIN-rail locking screw to
the horizontal position.
This locks the assembly to the DIN rail.
Install POINT I/O DeviceLogix Modules
WARNING
Notch
Position 1 is shown.
44710
44966
Install an I/O Module
Install the module before or after base installation. Make sure that the
mounting base is correctly keyed before installing the module into the
mounting base. In addition, make sure the mounting base locking screw is
positioned horizontally referenced to the base.
When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed
or the area is nonhazardous before proceeding.
1. Use a bladed screwdriver to rotate the keyswitch on the mounting base
clockwise until the number required for the type of module aligns with
the notch in the base.
ModuleKeyswitch Position
1734-8CFGDLX1
2. Make certain the DIN-rail locking screw is in the horizontal position,
noting that you cannot insert the module if the locking mechanism is
unlocked.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202023
Install POINT I/O DeviceLogix Modules
2
4V
D
C
Source
Ou
tput
Module
S
t
atus
N
etw
ork
St
a
t
us
17
3
4
O
B
4
E
0
1
2
3
N
ODE:
44967
44859
Handle
Module
3. Insert the module straight down into the mounting base and press to
secure.
4. Secure the module with the RTB removal handle (for 1734-TB or
1734-TBS bases) or handle (for 1734-TOP or 1734-TOPS bases).
24Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Install POINT I/O DeviceLogix Modules
WARNING
44968
Install the Removable
Terminal Block
A removable terminal block (RTB) is supplied with your mounting base
assembly.
To remove, pull up on the RTB handle. This lets you remove and replace the
base when necessary without removing any of the wiring.
To reinsert the RTB, proceed as follows.
When you connect or disconnect the RTB with field-side power
applied, an electrical arc can occur. This could cause an
explosion in hazardous location installations. Be sure to remove
power or that the area is nonhazardous before proceeding.
1. Insert the RTB end opposite the handle into the base unit.
This end has a curved section that engages with the mounting base.
2. Rotate the terminal block into the mounting base until it locks itself in
place.
3. If an I/O module is installed, snap the RTB handle into place on the
module.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202025
Install POINT I/O DeviceLogix Modules
WARNING
44969
Remove a 1734-TB or
1734-TBS Base
To remove a 1734-TB or 1734-TBS mounting base, do the following.
When you insert or remove the module while backplane power
is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations. Be sure to remove power or
that the area is nonhazardous before proceeding.
1. Unlatch the RTB handle on the I/O module.
2. Pull on the RTB handle to remove the RTB.
3. Press the module lock on the top of the I/O module and pull the I/O
module out of the base.
4. Remove the I/O module to the right of the base you are removing,
noting that the interlocking portion of the base sits under the adjacent
module.
5. Use a small-bladed screwdriver to rotate the orange DIN-rail locking
screw on the mounting base to a vertical position.
6. This unlocks the mounting base from the DIN rail.
7. Lift the mounting base straight up to remove.
26Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Install POINT I/O DeviceLogix Modules
WARNING
Remove a 1734-TOP or
1734-TOPS Base
To remove a wiring base from the DIN rail, you must remove the module
installed to the right of the base.
If you connect or disconnect wiring while the field-side power
is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations.
Be sure that power is removed or the area is nonhazardous
before proceeding.
1. Squeeze the module locking mechanism of the module to the right of
the base, pulling up to remove the module.
2. Use a small-bladed screwdriver to rotate the orange DIN-rail locking
screw on the mounting base to a vertical position.
This unlocks the mounting base from the DIN rail.
3. Slide the base up to release it from its mating units.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202027
Install POINT I/O DeviceLogix Modules
7
1
3
0
2
Module
Status
Network
Status
Device
Logix
Status
1734
8CFGDLX
1
3
0
2
5
7
4
6
NODE:
44758
Module Status
Network Status
I/O 0I/O 1
I/O 2I/O 3
I/O 4I/O 5
I/O 6I/O 7
Status of I/O 0
Status of I/O 1
Status of I/O 2
Status of I/O 3
Note that voltage and current to the module is applied through the adapter,
the 1734-FPD module, or the 1734-EP24DC module. V = 10…28.8 V DC.
Status of I/O 4
Status of I/O 5
Status of I/O 6
Status of I/O 7
DeviceLogix Status
Prox
I/O 0
Load
Prox
Prox
Prox
Load
Load
Load
I/O 2
I/O 4
I/O 6
I/O 1
I/O 3
I/O 5
I/O 7
V CC
If a connection to Common or the Supply Voltage is required for two- or
three-wire devices, then a 1734-CTM or 1734-VTM can be used.
Each I/O point is either Input or Output.
44687
Wire the Modules
This section provides wiring instructions for the modules.
1734-8CFGDLX I/O Module
28Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
1734-8CFGDLX Wiring Diagram
Prox
Prox
Prox
Prox
I/O 0
I/O 2
I/O 4
I/O 6
I/O 1
I/O 3
I/O 5
I/O 7
Load
Load
Load
Load
Install POINT I/O DeviceLogix Modules
ChannelTerminal Number
I/OCommonVoltage
00
External
(1)
11
22
33
44
55
66
77
10/28.8 V DC is supplied through the internal power bus.
(1)
Common connections require an external connection, such as a 1734-CTM module.
(2)
Supply Voltage Connections require an external connection such as a 1734-VTM module.
External
(2)
System and Power Considerations
There are no power terminals on the POINT I/O DeviceLogix module. The
module gets its power from the Field Power Bus of the back plane. Depending
on your system and network topology, power can be applied through one of
the following:
• 1734-PDN (DeviceNet adapter)
• 1734-ADN or 1734-ADNX (DeviceNet adapter)
• 1734-ACNR (ControlNet adapter)
• 1734-AENT or 1734-AENTR (EtherNet/IP adapter)
• 1734-EP24DC (Expansion power supply)
• 1734-FPD (Field power distribution)
Rockwell Automation Publication 1734-UM015B-EN-E - May 202029
Install POINT I/O DeviceLogix Modules
1734adn4
Adapter
Status
DeviceNet
Status
POINTBus
Status
I
E
2
C
O
E
2
C
I
B
2
O
B
2
E
ADN
I
B
2
O
B
2
E
O
B
4
E
EP24DC
0 1 0 1
0 1
0 1
0 1
24V DC supply
1734-EP24DC
1734-ADN
12V DC
Status
Power
Power
DeviceNet
System
DeviceNet
Power
Power
0 1 0 1 0 1
1734
VTM
1734-VTM
1734-CTM
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Common
Common
Common
Common
Common
Common
Common
Common
43929
Voltage Out = 0…7
Common = 0…7
Example of Logical Partitioning
Similarly, field power and common (return) can be terminated in the POINT
I/O system by using the following modules:
• 1734-VTM (Voltage termination module)
• 1734-CTM (Common termination module)
1734
CTM
30Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Chapter
ATTENTION
IMPORTANT
ATTENTION
ATTENTION
3
Install ArmorPOINT I/O DeviceLogix Modules
If you are using POINT I/O modules (1734-8CFGDLX), go to Chapter 2,
Install POINT I/O DeviceLogix Modules.
About This Chapter
Install the Mounting Base
Read this chapter for information about how to install ArmorPOINT I/O
modules to include the following:
• Install the Mounting Base
• Install the Module
• Wire the Modules
• Remove the Modules
This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR Publication 11. Without
appropriate precautions, there may be potential difficulties
ensuring electromagnetic compatibility in other environments
due to conducted as well as radiated disturbance.
Mount the I/O base on a wall or panel, using the screw holes provided in the
base.
The ArmorPOINT I/O module must be mounted on a grounded
metal mounting plate or other conductive surface.
Make sure all connectors and caps are securely tightened to
properly seal the connections against leaks and maintain IP
enclosure type requirements.
To comply with the CE Low Voltage Directive (LVD), all
connected I/O must be powered from a source compliant with
the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage
(PELV).
Rockwell Automation Publication 1734-UM015B-EN-E - May 202031
Install ArmorPOINT I/O DeviceLogix Modules
Adapter
102 mm
4.02 in
46 mm
1.81 in
47.2 mm
1.9 in
50 mm
2.0 in
22 mm
0.87 in
22 mm
0.87 in
50 mm
2.0 in
50 mm
2.0 in
Adapter
46 mm
1.81 in
47.2 mm
1.9 in
50 mm
2.0 in
22 mm
0.87 in
22 mm
0.87 in
50 mm
2.0 in
50 mm
2.0 in
43769
Ground lug connection
Latching mechanism
43675
Mounting illustration for the ArmorPOINT adapter with I/O bases
Install the mounting as follows:
1. Lay out the required points as shown above in the drilling dimension
drawing.
2. Drill the necessary holes for M4 (#8) machine or self-tapping screws.
3. Mount the base using M4 (#8) screws.
4. Ground the system using the ground lug connection.
The ground lug connection is also a mounting hole.
32Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Install ArmorPOINT I/O DeviceLogix Modules
Keyswitch
43675
Set to position 1, for the
1738 24V DC modules
Module bridges two bases
43771
1738-8CFGDLXM12
shown
Install the Module
Follow the instructions to install the module.
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base
clockwise until the number 1 aligns with the notch in the base.
2. Position the module vertically above the mounting base.
The module bridges two bases.
A
H
DLX
B
C
D
1738-8CFGDLXM12
24V DC Out
MOD
NET
G
F
E
0
1
2
3
4
5
6
7
3. Push the module down until it engages the latching mechanism.
You will hear a clicking sound when the module is properly engaged.
The locking mechanism locks the module to the base.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202033
Install ArmorPOINT I/O DeviceLogix Modules
ATTENTION
M
OD
NET
1738-8CFG
DLXM8
24V DC
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
DLX
Connector M8-A
LED indicators
Connector M8-B
Connector M8-G
Connector M8-H
43683
Connector M8-C
Connector M8-E
Connector M8-F
Connector M8-D
Remove the Module from the Mounting Base
Follow the instructions to remove the module from the mounting base.
1. Put a flat blade screwdriver into the slot of the orange latching
mechanism.
2. Push the screwdriver toward the I/O module to disengage the latch.
The module lifts up off the base.
3. Pull the module off the base.
Wire the Modules
This section provides wiring instructions for the modules.
Make sure all connectors and caps are securely tightened to
properly seal the connections against leaks and maintain IP
enclosure type requirements.
1738-8CFGDLXM8 I/O Module
34Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
1738-8CFGDLXM8 Wiring Diagram
43583
(view into connector)
Pin 1 - 24V DC
Pin 3 - Common
Pin 4 - I/O 0 (M8-A)
The ArmorPOINT I/O DeviceLogix module gets its power from the Field
Power Bus of the backplane. Depending on your system and network
topology, power can be applied through one of the following:
• 1738-ADN12 or 1738-ADN18, 1738-ADN18P, 1738-ADNX
(DeviceNet adapter)
• 1738-ACNR (ControlNet adapter)
• 1738-AENT or 1738-AENTR (EtherNet/IP adapter)
• 1738-EP24DC (Expansion power supply)
• 1738-FPD (Field power distribution)
36Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Chapter
4
DeviceLogix for POINT I/O and ArmorPOINT
I/O on DeviceNet
About This Chapter
Offline Configuration using
RSNetWorx for DeviceNet
This chapter provides information on the following:
• Offline Configuration using RSNetWorx for DeviceNet
• Online Configuration using RSNetWorx for DeviceNet
• I/O Data Assembly Maps
This section is not a substitute for RSNetWorx or DeviceNet scanner and
adapter publications. It is suggested that you have those publications available
while performing the procedures in this section See Related Publications
list of related publications.
This section describes the setup of a DeviceNet network using RSNetWorx for
DeviceNet when the module is not connected to the network.
When configuring the module in the Offline mode, you must place all nodes
on the network in The view window manually. Use the Hardware tree to find
each module and place it into the view window. This can be done by
double-clicking the module or dragging it to the view window.
If using a POINT I/O or ArmorPOINT I/O DeviceNet adapter, make sure
you select Adapter for the main DeviceNet network, and Scanner for the
POINTBus backplane.
for a
Rockwell Automation Publication 1734-UM015B-EN-E - May 202037
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Example: Build the Backplane
This example shows you how to build the backplane. The following screen
shows the 1734-ADN POINT I/O Scanner added.
Next, locate the I/O modules. In this example, the following modules will be
added:
• 1734-8CFGDLX POINT I/O DeviceLogix module
• 1734-IB8 POINT I/O DC Input module
• 1734-IE4C POINT I/O 4...20 mA Analog Input module
38Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
The digital modules can be found under the category, “General Purpose
Discrete I/O”, and the analog modules can be found under the “Rockwell
Automation miscellaneous” category.
The configuration of each module can now be edited from the Properties
dialog box of each module. For instructions on editing the configuration of the
DeviceLogix module, see Chapter 6
.
Include all the I/O modules in the backplane to the Scanner’s scan list.
After configuration is complete, save your work in the DNT file. “DNT” is the
three-letter file name extension. One file contains all the configuration data for
all the modules on the network or backplane.
Remember that you need to go to the Online mode with RSNetWorx for
DeviceNet to download all the configuration data to the I/O modules and
scanners.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202039
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Online Configuration using
RSNetWorx for DeviceNet
To set up a DeviceNet network using RSNetWorx for DeviceNet when
connected to the network, do the following:
1. If you have a DNT file that has been configured, open the file in
RSNetWorx for DeviceNet. To do this, go to the Online mode by
pressing <F10>. You can also click Network > Online, or click the
Online button .
RSLinx® application will start. If the Online path is not set in Network
> Properties, the Browse for network dialog box will appear.
2. Navigate to the DeviceNet network or DeviceNet subnet if configuring
the backplane.
The OK button will become available when you select a valid network.
RSNetWorx will automatically browse the network to discover all the
participants.
3. If there are any module identity issues, correct them before continuing.
4. Ensure that the configuration in the DNT file matches the configuration
in each node.
In this section, it is assumed that all the work was done in the Offline
mode and that the DNT file contains all the correct information.
40Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
To update all the modules in the most efficient way, click Network >
Download to Network on the menu bar.
5. Review the Message window for any errors.
The stored configuration (DNT file) and the configuration of all the
modules now match.
6. If any changes are made, be sure to download them to the module and
save them in the DNT file.
7. When in the Online mode, you can change the configuration of a
module by double-clicking its icon. You can also right-click the icon and
select Properties.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202041
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Familiarize yourself with all the tabs in the Properties window before
proceeding to Chapter 6
DeviceLogix module.
where you will learn how to configure the
42Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
I/O Data Assembly Maps
Read this section for information about how to communicate with your
module.
I/O messages are sent to (consumed) and received from (produced) the I/O
modules. These messages are mapped into the processor’s or scanner’s
memory. Each module produces 1 byte, 8 or 20 bytes of input data based on
which produced assembly is selected. The default setup is 20 bytes.
It consumes 1 byte, 8 or 20 bytes of I/O data (scanner Tx).
Default Data Map - Produced Assembly Instance 101
Message Size: 20 Bytes
Bit76543210
Data [0]Pt 07Pt 06Pt 05Pt 04Pt 03Pt 02Pt 01Pt 00
Data [1]PNB 07 PNB 06PNB 05 PNB 04 PNB 03PNB 02 PNB 01 PNB 00
Data [2]ReservedOwnedLogicEn
Data [3]PM7PM6PM5PM4PM3PM2PM1PM0
Data [4]Produced Network Analog Word 0
Data [5]
Data [6]Produced Network Analog Word 1
Data [7]
Data [8]Produced Network Analog Word 2
Data [9]
Data [10] Produced Network Analog Word 3
Data [11]
Data [12] Produced Network Analog Word 4
Data [13]
Data [14] Produced Network Analog Word 5
Data [15]
Data [16] Produced Network Analog Word 6
Data [17]
Data [18] Produced Network Analog Word 7
Data [19]
Where:
Pt = value of the I/O point,
PNB = Produced Network Bit,
PM = Peer Missing (a 1 indicates the absence of a configured peer)
Owned = Owned by a master.
When set to 0, the module is producing data without a master.
When set to 1, the module is producing while being owned by a master.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202043
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
You can select other produced assemblies:
• Produced assembly instance 4 is the first byte of produced assembly
• Produced assembly instance 111 is the first eight bytes of produced
Default Data Map - Consumed Assembly Instance 102
Message Size: 20 Bytes
Bit76543210
Data [0]Pt 07Pt 06Pt 05Pt 04Pt 03Pt 02Pt 01Pt 00
Data [1]CNB 07 CNB 06 CNB 05 CNB 04 CNB 03 CNB 02 CNB 01 CNB 00
Data [2]Reserved
Data [3]
Data [4]Consumed Network Analog Word 0
Data [5]
Data [6]Consumed Network Analog Word 1
instance 101 (Data [0]).
assembly instance 101 (Data [0]…[7]).
Data [7]
Data [8]Consumed Network Analog Word 2
Data [9]
Data [10] Consumed Network Analog Word 3
Data [11]
Data [12] Consumed Network Analog Word 4
Data [13]
Data [14] Consumed Network Analog Word 5
Data [15]
Data [16] Consumed Network Analog Word 6
Data [17]
Data [18] Consumed Network Analog Word 7
Data [19]
Where: Pt = value to be applied to the output point, CNB = Consumed Network Bit
You can select other consumed assemblies:
• Consumed assembly instance 34 is the first byte of consumed assembly
instance 102 (Data [0]).
• Consumed assembly instance 112 is the first eight bytes of consumed
assembly instance 102 (Data [0]…[7]).
44Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Data Map - Configuration Assembly Instance 123
Message Size: 48 Bytes
Bit76543210
Data [0]Group Off2On Input filter
Data [1]
Data [2]Group On2Off Input filter
Data [3]
Data [4]FltM 7FltM 6FltM 5FltM 4FltM 3FltM 2FltM 1FltM 0
Data [5]FltV 7FltV 6FltV 5FltV 4FltV 3FltV 2FltV 1FltV 0
Data [6]IdlM 7IdlM 6IdlM 5IdlM 4IdlM 3IdlM 2IdlM 1IdlM 0
Data [7]IdlV 7IdlV 6IdlV 5IdlV 4IdlV 3IdlV 2IdlV 1IdlV 0
Data [8]ReservedRACKCFODMMP
Data [9]Reserved
Data [10] Masterless Produce Assembly Instance (0, 4, 101, 111)
Data [11]
Data [12] Masterless Produce EPR (ms)
Data [13]
Data [14] Masterless Produce PIT (ms)
Data [15]
Data [16] Peer 0 - Slot/MacID
Data [17] Peer 0 - Consume Message Length (bytes)
Data [18] Peer 0 - EPR (ms)
Data [19]
Data [20] Peer 1 - Slot/MacID
Data [21] Peer 1 - Consume Message Length (bytes)
Data [22] Peer 1 - EPR (ms)
Data [23]
Data [24] Peer 2 - Slot/MacID
Data [25] Peer 2 - Consume Message Length (bytes)
Data [26] Peer 2 - EPR (ms)
Data [27]
Data [28] Peer 3 = Slot/MacID
Data [29] Peer 3 - Consume Message Length (bytes)
Data [30] Peer 3 - EPR (ms)
Data [31]
Data [32] Peer 4 - Slot/MacID
Data [33] Peer 4 - Consume Message Length (bytes)
Rockwell Automation Publication 1734-UM015B-EN-E - May 202045
DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
Data Map - Configuration Assembly Instance 123 (Continued)
Message Size: 48 Bytes
Data [34] Peer 4 - EPS (ms)
Data [35]
Data [36] Peer 5 - Slot/MacID
Data [37] Peer 5 - Consume Message Length (bytes)
Data [38] Peer 5 - EPR (ms)
Data [39]
Data [40] Peer 6 - Slot/MacID
Data [41] Peer 6 - Consume Message Length (bytes)
Data [42] Peer 6 - EPR (ms)
Data [43]
Data [44] Peer 7 - Slot/MacID
Data [45] Peer 7 - Consume Message Length (bytes)
Data [46] Peer 7 - EPR (ms)
Data [47]
Where:
Filter = 0 to 65535 s (1000 = default)
FltM = Fault Mode (0 = Use Fault Value (default), 1 = Hold Last State)
FltV = Fault Value (0 = OFF (default), 1 = ON)
IdlM = Idle Mode (0 = Use Idle Value (default), 1 = Hold Last State)
IdlV = Idle Value (0 = OFF (default), 1 = ON)
RACK = Produce with Rack Assembly 4 and Consume Rack Assembly 34
(0 = Disabled (default), 1 = Enabled)
CFO = DeviceLogix Communication Fault Override of Outputs
1 = Enabled. When enabled, the DeviceLogix program will continue to control the
outputs even in the event of a communication fault.
0 = Disabled (default). When disabled, the outputs will follow the Fault and Idle
settings in the event of a communication fault.
DM = Dependent Mode
1 = Enabled. When enabled, the DeviceLogix program execution will follow the
Run/Idle state of the owning processor.
MP = Masterless Produce
0 = Disabled (default), 1 = Enabled. When enabled, the module will begin producing
data at power-up and after a connection with a controller is terminated.
EPR = Expected Packet Rate
PIT = Production Inhibit Time
Slot/MacID = Address of peer
Configuration of the modules must be done through RSNetWorx for
DeviceNet. See Chapter 6
46Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
for details.
Chapter
5
DeviceLogix for POINT I/O and ArmorPOINT
I/O on Ethernet/ControlNet
About This Chapter
Add a POINT I/O
DeviceLogix Module to
RSLogix 5000
In this chapter, you will learn how to perform the following tasks:
• Create a POINT I/O DeviceLogix module in RSLogix 5000 when using
EtherNet/IP or ControlNet adapters
• Identify the tags created in your program for your use
• Use RSNetWorx for DeviceNet to configure the POINT I/O
DeviceLogix module
To add a POINT I/O DeviceLogix module to RSLogix 5000, do the
following.
1. In the I/O Configuration tree, find the adapter.
In this example, we will be using the 1734-AENT with the
1734-8CFGDLX. The same procedure applies if you are using an
ArmorPOINT I/O DeviceLogix module, or if the network is
ControlNet.
2. Right-click the POINT I/O Chassis and select New Module.
47Rockwell Automation Publication 1734-UM015B-EN-E - May 202047
DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet
IMPORTANT
3. Under Digital, double-click the POINT I/O DeviceLogix module.
If you cannot find the module in the Select Module dialog box,
you will need to install the Add-On Profile (AOP) for the module.
You can download the AOP at rok.auto/pcdc
The following dialog box appears.
.
48Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet
4. Enter the slot number in the Slot box.
It is not possible to make a Rack connection to the POINT I/O
DeviceLogix module. The connection must be a direct one.
On the Connection tab, you can change the Requested Packet Interval
(RPI), the default is 20 ms.
The Module Info tab will display the status and identity information of
the module when the module is online.
There is no tab for configuration. Configuration of the POINT I/O
DeviceLogix modules is done only using RSNetWorx for DeviceNet.
See Chapter 6
for more details.
RSLogix 5000 will create the following input tags:
Rockwell Automation Publication 1734-UM015B-EN-E - May 202049
DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet
I/O Tags
The following table lists the input tags and their descriptions.
Input tags and their descriptions
TagDescription
DataThis will contain the state of eight I/O points. See Chapter 6
LogicDefinedDataThese 8 bits are assigned using the Network Output Bit tags in
LogicEnabledWhen set, the DeviceLogix program is running.
OwnedWhen set, the module is owned by a master.
PeerMissingEach bit represents one of the eight possible peers. If a bit is
LogicDefinedData[]These eight values are assigned using the Network Output
for
details.
the DeviceLogix program.
set, the data from that peer is missing or invalid.
Word tags in the DeviceLogix program.
The following table lists the output tags and their descriptions.
Output tags and their descriptions
TagDescription
DataThis value is sent by the master to set the output state of the
eight output points. This can be overwritten if the DeviceLogix
program is controlling the outputs (Logic Enable On).
See Chapter 6
LogicDefinedDataThese 8 bits can be used in the DeviceLogix program with the
Network Input Bit tags.
LogicDefinedIntData[]These eight values can be used in the DeviceLogix program
with the Network Input Word tags.
for details.
50Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet
Launch RSNetWorx for
DeviceNet to Configure the
Module
The POINT I/O DeviceLogix module can only be configured using
RSNetWorx for DeviceNet.
The following example assumes that the module is configured while it is
online. If the module is configured offline, then apply the same procedure
when you download the contents of the DNT file to the I/O module.
To configure the module:
1. Start RSNetWorx for DeviceNet.
2. Go online by doing one of the following:
• Click the Online button.
• On the Network menu, click Online.
• Press <F10>.
The RSLinx Browse window appears.
3. Navigate the tree down to the EtherNet/IP or ControlNet POINT I/O
or ArmorPOINT I/O adapter.
4. Expand the tree branch for the adapter.
You should see two additional ports. The first is the backplane, and the
second is a DeviceNet port. Physically they are the same port, which is
the backplane.
RSNetWorx needs a DeviceNet port.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202051
DeviceLogix for POINT I/O and ArmorPOINT I/O on Ethernet/ControlNet
IMPORTANT
5. Select POINTBus Port, DeviceNet, and click OK.
RSNetWorx automatically browses the network to discover all the
participating modules.
Note the online path in the Messages window at the bottom
half of the screen. This path will be saved in the DNT file. To
open the file, select Properties on the Network menu.
6. If you are configuring the module offline, you must download the
configuration to the module after you go online. To do this, right-click
the module’s icon and select Download to Device.
7. To change the configuration of a module, double-click that module’s
icon. Alternatively, you can right-click the icon and select Properties.
Details on configuring the module can be found in Chapter 6
.
52Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Chapter
6
Configuring POINT I/O and ArmorPOINT I/O
DeviceLogix modules using RSNetWorx for
DeviceNet
About This Chapter
Configure the Module using
the Configuration tab
In this chapter, you will learn how to do the following:
The following diagram shows the Configuration tab of a POINT I/O
DeviceLogix module in RSNetWorx for DeviceNet. The Configuration tab of
an ArmorPOINT I/O DeviceLogix module looks similar.
• Configure the module using the Configuration tab
• Use the data on the Parameters tab
• Configure peer communication
• Produce data without using a master
• Start the DeviceLogix Function Block Editor on the DeviceLogix tab
Rockwell Automation Publication 1734-UM015B-EN-E - May 202053
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
Parameters on the Configuration tab
ParameterDescription
Off-to-On DelayThis is the OFF to ON filter constant for all inputs on the module. A
high signal must be present for this amount of time before the module
will report an ON.
The value must be entered in microseconds (s). The default value is
1000 s. The minimum value is 0 and the maximum is 65535 s.
The actual resolution of this value is milliseconds. The user selected
value will be truncated at milliseconds. For example, 65535 s
represents a 65 ms filter value.
On-to-Off DelayThis is the ON to OFF filter constant for all inputs on the module. A
low signal must be present for this amount of time before the module
will report an OFF.
The value must be entered in microseconds (s). the default value is
1000 s. The minimum value is 0 and the maximum is 65535 s.
The actual resolution of this value is millisecond. User selected value
will be truncated at milliseconds. For example, 65535 s represents a
65 ms filter value.
Output Fault
State
This parameter controls the action of each output during a
communication fault.
0 = Go to Output Fault Value (default)
1 = Hold Last State
This parameter is ignored if DLX Fault Override is enabled.
Output Fault
Value
The state of each output if a communication fault occurs. This
parameter is ignored if the Output Fault State is set to Hold Last State
or if DLX Fault Override is enabled.
0 = OFF (default)
1 = ON
Output Idle State This parameter controls the action of each output when in Idle state
or Program mode.
0 = Go to Output Idle Value (default)
1 = Hold Last State
This parameter is ignored if DLX Fault Override is enabled.
Output Idle Value The state of each output when in Idle state or Program mode. This
parameter is ignored if the Output Idle State is set to Hold Last State
or if DLX Fault Override is enabled.
0 = OFF (default)
1 = ON
Auto ProduceEnabling this parameter will allow the module to produce data
without a master. This parameter is disabled by default.
If enabled, the module will begin to produce data on the backplane or
network after power up and network address verification (Dup MAC
check). The Owned bit in the produced assembly will be cleared (0).
A master may still make a connection to the module and then the
Owned bit will be set (1). If a master connection fails, the module will
continue to produce data, but the Owned bit will be cleared (0).
The produced assembly, EPR, and PIT are described later in this table.
Auto Production may be important to support data to listening peers.
54Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
Parameters on the Configuration tab (Continued)
ParameterDescription
DLX Dependent
Mode
This parameter allows the logic in the module to be enabled or
disabled according to the I/O connection status or the state of the
owning processor. The default is disabled.
If Dependent Mode is enabled, the DeviceLogix program will be
disabled when the owning processor is in program mode. When the
processor transitions to RUN, the logic will automatically be enabled.
DLX Fault
Override
When an output is being locally controlled, its state is either
controlled by the DeviceLogix program or by the Fault/Idle states.
Enabling this parameter allows the local logic to override the
Fault/Idle states in the event of a communication fault or transition to
Idle (Program) state. When this parameter is disabled (default) and a
communication fault occurs or when in Idle (Program) state, all
outputs, including those that are locally controlled, will go to the
Fault/Idle states. Enabling this parameter and using the "Network
Fault" status bit (Bus-off or Dup Mac Error) or COS/Cyclic Cnxn
Idle/Fault bits in the DeviceLogix program, a controlled stop or
maintenance of a machine state can be achieved when
communication is lost with a master.
Auto Produce
Assembly
When the Auto produce parameter is enabled, this parameter selects
which assembly to produce:
000: 20-byte assembly (default)
004: 1-byte assembly
101: 20-byte assembly
111: 8-byte assembly
For details on the contents of the assembly, see I/O Data Assembly
Maps in Chapter 4.
For the list of I/O tags, see I/O Tags
in Chapter 5.
The 20-byte assembly contains all the data. The 8-byte assembly can
be produced in one packet (non-fragmented).
Auto Produce EPR When the Auto Produce parameter is enabled, this parameter sets the
Expected Packet Rate. The units are milliseconds (ms). The default is
1000 ms. The maximum is 65535 ms and the minimum is 0 ms.
When Auto Produce is enabled, the module produces data at every
change of state (COS) or when the EPR timer expires.
Auto Produce PIT When the Auto Produce parameter is enabled, this parameter sets the
Product Inhibit Time. The units are milliseconds (ms). The default is
1 ms. The maximum is 65535 ms, and the minimum is 0 ms.
If a Change of State occurs and the PIT has not expired, the message
will wait until the PIT has expired. This can be used to prevent one
module from using all the available network bandwidth.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202055
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
Parameters on the Configuration tab (Continued)
ParameterDescription
Peer #xx MacIDThere are eight (0…7) peer Mac ID parameters. Each one defines the
MacID or Slot Number of the peer from which this module will
consume data. The default is "No Connection."
You can enter the MacID or Slot number, 0…63, or a relative offset
from the address of the module (-4 to +4).
Once a valid MacID is set, Peer Exists = 1 in DeviceLogix program.
See more details on peer configuration later in this chapter and in
Appendix A
.
Peer #xx SizeThere are eight (0…7) Peer Size parameters. Each one defines the
size in bytes of the message received from the peer. The default and
maximum value is 24 bytes. The minimum is 1 byte. See Appendix A
for peer message sizes of POINT I/O and ArmorPOINT I/O modules.
If the received message size does not match the Peer Size value, the
data will be considered invalid and the appropriate error bits will be
set (Produced assembly: Peer Missing = 1. In DeviceLogix program:
Peer Data valid = 0.)
This parameter is ignored if the Peer MacID is set to "No Connection."
Peer #xx EPRThere are eight (0…7) Peer EPR parameters. Each one defines the
Expected Packet Rate in milliseconds (ms) of the peer connection. If
this module does not receive valid data from a peer for 4 times the
EPR, the appropriate error bits will be set (Produced assembly: Peer
Missing = 1. In DeviceLogix program: Peer Data Valid = 0.)
The default value is 1000 ms. The maximum is 65535 ms and the
minimum is 0 ms.
This parameter is ignored if the Peer MacID is set to "No Connection."
56Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
Parameters on the Parameters tab
Parameters on the Parameters tab
ParameterDescription
Data Input/Output
Data - Consumed
Bits
Consumed
Analog Word #xx
Network Status
Override
Comm Status
Override
Peer StatusThe 8 bits in this parameter are used to determine the connection
ZIP Security KeyThis is a legacy parameter for DeviceLogix and ZIP (Zone Interlock
This parameter is the same as the first byte of the Produced I/O
assembly. It is the state of the eight I/O points.
This parameter is the same as the second byte of the Consumed I/O
assembly. It is the state of the Consumed Network Bits or
User-Defined Bit Data.
These eight parameters are from the Consumed I/O assembly. They
contain the state of the Consumed Network Words or User-Defined
Word Data.
This is a legacy Parameter for DeviceLogix and ZIP. It shows the state
of Network Status Override.
This is a legacy Parameter for DeviceLogix and ZIP. It shows the state
of Communication Status Override.
status of a peer.
Parameters). The ZIP Security Key is a 16-bit value used to uniquely
identify a module and its configuration. This value can be used in the
DeviceLogix program to verify that the configuration of a peer has not
changed. More details on using the ZIP Security Key will be provided
in the later part of this chapter.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202057
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
Parameters on the Parameters tab (Continued)
ParameterDescription
Zone ControlThis is a legacy parameter for DeviceLogix and ZIP. It shows the state
of Zone Control, whether it is enabled or disabled.
Sequential Auto
Address
This parameter should only be used in a DeviceNet system. It is used
to set another POINT I/O or ArmorPOINT I/O module to the right of
this module to a node address one greater than this module.
This message will propagate to all modules to the right. Each address
will change to one greater than its neighbor.
Configure Peer
Communication
Broadcast Baud
Rate
Broadcast
AutoBaud
This parameter should only be used in a DeviceNet system. It is used
to set another POINT I/O or ArmorPOINT I/O module to the right of
this module to the desired baud rate.
1: 125 kHz
2: 250 kHz
3: 500 kHz
The only way a module can achieve a 1 MHz baud rate is by using the
AutoBaud feature.
This parameter should only be used in a DeviceNet system. It is used
to set another POINT I/O or ArmorPOINT I/O module to the right of
this module to Autobaud (enable) or used to save the baud rate
(disable).
This section will describe how to configure the POINT I/O and
ArmorPOINT I/O DeviceLogix module to consume data from peers. The
POINT I/O DeviceLogix module can use data from other modules to affect
the DeviceLogix program.
The module can perform the following functions:
• Get Change-Of-State (COS) data from up to eight I/O modules or
peers.
• Each peer can have up to 24 bytes of data.
• Each peer has its own expected packet rate.
• Each peer has its own status bit that can be used in logic.
• The data from each peer can be digital (bit), analog (16-bit words), or a
mixture of both.
The following functions are not supported:
• Make a connection.
• Configure a peer.
• Control outputs on a peer.
• Listen to a peer that is on another network.
The module can only listen to peers on the backplane or local
DeviceNet network.
58Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
• Consume data from a safety connection
The module can consume data from a safety module with a standard
connection.
• Consume data sent to a peer from a master.
Set Up Peer Communication Parameters
For each peer, you need to configure a set of parameters.
Here are the three parameters in their default settings (no peer data).
Parameter
number
31Peer#0 MacIDSlot numberNo connection
39Peer#0 SizeInput data size24 bytes
65Peer#0 EPRTime out value1000 ms
Parameter
name
Parameter descriptionDefault value
Example
To listen to the data from a 1734-IB4 module in the first slot (node 1), you can
configure the parameters in the following way:
Parameter
number
31Peer#0 MacIDSlot number1
39Peer#0 SizeInput data size1 byte
65Peer#0 EPRExpected packet rate100 ms
The 1734-IB4 is "Peer#0". Enter its produced data size, "1" as its input data
size. If the module does not consume data from this peer in four times the
expected packet rate (EPR), which is 400 ms in this case, the Peer #0
connection fault bit will be set.
Parameter
name
Parameter descriptionValue
The contents of the data are mapped to the Peer#0 data table.
To use the data from the 1734-IB4 in the DeviceLogix editor, click to
place a Boolean bit input on the function block sheet, and select the desired bit
to use in logic under the "Network Boolean Input" category.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202059
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
Select bit0 of byte0. With up to 24 bytes of data available for mapping, the last
entry is "Peer#0 (Byte 23, Bit7)." 192 bits per peer can be used for a total of
1536 data bits.
You are highly encouraged to use the connection status bits to verify that the
device is receiving valid data from the peer. They are located under the Status
Input category of the "bit input" I/O tags.
In our example, "Peer#0 Data Valid" will be set to 1 when the POINT I/O
DeviceLogix module is consuming data from the peer that is timely (which is,
within the EPR timeout) and of the correct length. No other checking is done
on the data by the module.
"Peer#0 Exists" is set to 1 when a peer connection has been configured.
Analog data can also be used in a peer connection. If a 1734-IE4C module is
located in the third slot, you can configure the POINT I/O DeviceLogix
module like this:
Parameter
number
32Peer#0 MacIDSlot number3
40Peer#0 SizeInput data size12 bytes
66Peer#0 EPRExpected packet rate500 ms
Parameter
name
Parameter descriptionDefault value
60Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
The 1734-IE4C has an input message that looks like this:
Default Data Map for the 1734-IE4C Analog Input Module
Message size: 12 bytes
Input Channel 0 High ByteInput Channel 0 Low Byte
Input Channel 1 High ByteInput Channel 1 Low Byte
Input Channel 2 High ByteInput Channel 2 Low Byte
Input Channel 3 High ByteInput Channel 3 Low Byte
Status Byte for Channel 1Status Byte for Channel 0
ORURH
Status Byte for Channel 3Status Byte for Channel 2
ORURH
LLAHALACMCF ORURH
H
A
LLAHALACMCF ORURH
H
A
LLAHALACMCF
H
A
LLAHALACMCF
H
A
To use the analog data from channel 2, click to place an analog bit input
on the function block sheet in the DeviceLogix editor.
Channel 2 is mapped to Word 2. Select this as shown below. For help on
mappings, see Appendix A
.
To use the overrange bit of channel 1, you can use "bit input" I/O tag and
select Peer#1, byte 9, bit 7.
Again, it is best to use the Peer Connection Status bits (Peer#1 Data Valid and
Peer#1 Exists) to validate the data before using it.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202061
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
If the POINT I/O DeviceLogix module is consuming data from a peer that
has double precision analog data (32-bit), like the 1734-VHSC24, the data can
be used in logic by addressing the high-word and low-word separately. By using
math functions (multiply and add), the two words can be combined into one
value.
Produce Data Without
Using a Master
See Very High-Speed Counter Input Modules
in Appendix A.
With the POINT I/O DeviceLogix module (and other DeviceLogix modules
that support "ZIP"), you can send data to another listener without a network
master to set up the connection.
The following parameters are used to configure this feature:
Parameter
number
74Auto ProduceSee page 54
75Auto Produce EPRSee page 55
76Auto Produce PITSee page 55
99Auto Produce
Parameter nameParameter
description
See page 55
Assembly
Default value
.Disabled
.1000 ms
.1 ms
.20-byte produced
(default)
Soon after power-up and getting online, when Auto Produce is enabled, the
POINT I/O DeviceLogix module begins producing change-of-state (COS)
type I/O data on the connected network or backplane. It produces the
selected "Auto Produce Assembly" at the selected "Auto Produce EPR"
(Expected Packet Rate).
The Auto Produce Assembly data can be:
• 20 bytes of produced data (it sends all possible data)
• 8 bytes of produced data (this does not require the fragmentation
protocol, so it will reduce network bandwidth)
• 1 byte of produced data (only the state of the 8 I/O)
A description of these assemblies can be found in Chapter 4.
The Auto Produce EPR sets the cyclic rate at which data is produced if there is
no change of I/O state. If there is a change of state, new data is produced
immediately. If data changes often, to reduce change-of-state traffic on the
network, you can increase the Auto Produce Production Inhibit Time (PIT).
For example, if the PIT is set to 10 ms, the quickest the module can produce
data is once every 10 ms even if there is a change of state.
Auto Produce is only recommended on a DeviceNet network in situations
where a master is not required.
62Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
Due to the fact that there is no master to verify the connection and the
configuration of each module, it is recommended that the ZIP Security Key be
produced in the data. This unique number is calculated using the identity of
the module and the present configuration. The ZIP Security Key value is in the
DeviceLogix Logic Editor, under the Analog Input I/O tags.
The output of the Analog Input I/O tag can be wired to the input of an
Analog Output I/O tag to map it into the Produced Assembly Image:
Rockwell Automation Publication 1734-UM015B-EN-E - May 202063
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
In this example, the ZIP Security Key is mapped to Network Output Word 3.
Any module receiving this data should verify the constant value.
For example:
The ZIP Security Key constant is added using the ellipses button of the NEQ
function block. This output can be used to condition the execution of other
function blocks using the Enable input.
Note that there could be an "unsigned value to signed value conversion" when
the ZIP Security Key is displayed in the Logic Editor, which leads to a
mismatch of displayed value. However, the value is consistent in HEX format.
64Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
Start the Function Block
Editor
To start the Function Block editor, do the following.
1. Go to the property dialog box of the module.
2. Click the DeviceLogix tab, followed by Start Logic Editor.
On this tab, you can enter the Author’s name, revision, and description of the
logic program. These are generic text fields. They are saved in the DNT file
created by the RSNetWorx for DeviceNet application.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202065
Configuring POINT I/O and ArmorPOINT I/O DeviceLogix modules using RSNetWorx for DeviceNet
If a program is saved in the DNT file, it will be displayed.
To learn how to use this editor, refer to Chapter 2 of the DeviceLogix System
User Manual, publication RA-UM003
. For specific uses of the POINT I/O
and ArmorPOINT I/O DeviceLogix modules, proceed to Chapter 7
66Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
.
DeviceLogix Capabilities
Chapter
7
About This Chapter
Function Block Instructions
This chapter lists the DeviceLogix capabilities supported by the POINT I/O
DeviceLogix and ArmorPOINT I/O DeviceLogix modules.
The module can support up to 144 function blocks. These function blocks are
categorized in the following manner:
• Process
• Filter
•Select/Limit
• Statistical
• Timer/Counter
•Comparison
• Compute/Math
•Move/Logical
Process Category
The process category includes the following instruction types:
•Alarm
• Timing Diagnosis
Alarm
The Alarm function block initiates an alert based on the comparison between
the input value and the threshold. The output of the DeviceLogix Alarm
function block contains these alerts.
•High-High alarm
• High alarm
• Low alarm
•Low-Low alarm
Rockwell Automation Publication 1734-UM015B-EN-E - May 202067
DeviceLogix Capabilities
Timing Diagnosis
The DeviceLogix Timing Diagnosis function block object determines whether
the occurrence of the expected event is within the preset timing interval.
For more information on the Alarm and Timing Diagnosis function blocks,
refer to the DeviceLogix System User Manual, publication RA-UM003
.
Filter Category
The Filter category includes a single instruction type: Low Pass Filter.
Low Pass Filter
The DeviceLogix Low Pass Filter (LPF) function block provides a filter to
attenuate input frequency above the cutoff frequency.
The module supports only two instances of the LPF function block.
For more information on the Low Pass Filter function block, refer to the
DeviceLogix System User Manual, publication RA-UM003
.
Select Limit Category
The Select Limit category includes the following instruction types:
• Select
• High Low Limit
Select
The DeviceLogix Select function block identifies one input within the selected
two function block inputs as the output according to the value of the selector.
The Select function block is outlined in detail as follows.
IF Selector = 1
Output = value of Input 2
IF Selector = 0
Output = value of Input 1
END
68Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix Capabilities
IMPORTANT
High/Low Limit
The DeviceLogix High/Low Limit function block limits the input value within
the specified data range. The High/Low Limit function block is outlined in
detail as follows.
IF value of Input > HighLimit
Output = HighLimit
ELSE IF value of Input < LowLimit
Output = LowLimit
ELSE
Output = Input
END
For more information on the Select and High/Low Limit function block, refer
to the DeviceLogix System User Manual, publication RA-UM003
.
Statistical Category
The statistical category includes a single instruction type: Moving Average.
Moving Average
The module supports only two instances of the Moving Average
(MAV) function block.
The DeviceLogix Moving Average function block calculates a time average
value for the input signal.
For more information on the Moving Average function block, refer to the
DeviceLogix System User Manual, publication RA-UM003
.
Timer/Counter Category
The Timer/Counter category includes the following instruction types:
• On-Delay Timer
•Off-Delay Timer
• Pulse Timer
•Up Counter
•Down Counter
•Up/Down Counter
Rockwell Automation Publication 1734-UM015B-EN-E - May 202069
DeviceLogix Capabilities
IMPORTANT
Beginning with DeviceLogix firmware revision 5, the
accumulator (ACC) is available as output for Timer and Counter.
For more information on the Timer/Counter category, refer to the
DeviceLogix System User Manual, publication RA-UM003
.
Comparison Category
The Comparison category includes basic comparison functions, including
these instruction types:
• Greater Than (GRT)
• Greater Than or Equal To (GEQ)
• Equal (EQU)
• Not Equal (NEQ)
• Less Than (LES)
• Less Than or Equal (LEQ)
• Mask (MEQ)
Operation rules [all except Mask (MEQ)]
The conditions and outputs of each function block are described below.
Function Block
Type
Greater Than (GRT)Source A > Source B1
Greater Than or
Equal (GEQ)
Equal (EQU)Source A == Source B1
Not Equal (NEQ)Source A!= Source B1
Less Than (LES)Source A < Source B1
Less Than or Equal
(LEQ)
ConditionOutput
Source A <= Source B0
Source A >= Source B1
Source A < Source B0
Source A!= Source B0
Source A == Source B0
Source A >= Source B0
Source A <= Source B1
Source A > Source B0
70Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix Capabilities
Operation rules [Mask (MEQ) only]
The Mask process is outlined below:
IF (Source AND Mask) == (Compare AND Mask)
Output is Set
ELSE
Output is Clear
END
For more information on the Comparison category, refer to the DeviceLogix
System User Manual, publication RA-UM003
.
Compute Category
The Compute category includes fundamental arithmetic operations, including
the instruction types:
• Add (ADD)
• Multiple (MUL)
• Subtract (SUB)
• Divide (DIV)
•Modulus (DINT)
•Modulus (REAL)
• Absolute (ABS)
• Negative (NEG)
Operation rules [all except Mask (MEQ)]
The conditions and outputs of each function block are described below.
Function Block
Type
Add (ADD)= Source A + Source B
Multiply (MUL)= Source A x Source B
Subtract (SUB)= Source A - Source B
Divide (DIV)= Source A / Source B
Modulus (DINT)= Source A - (Source A / Source B) x Source B
Modulus (REAL)= Source A - (DINT)(Source A / Source B) x Source B
Output
Absolute (ABS)= Absolute value of (Source A)
Negative (NEG)= -Source A
Rockwell Automation Publication 1734-UM015B-EN-E - May 202071
DeviceLogix Capabilities
Square Root (SQR)= Square root of (Source A)*
Power (XPY)= Source A * * Source B
* If Source A is negative, the operation takes the absolute value of Source A before
calculating the square root and no fault is reported.
For more information on the Compute category, refer to the DeviceLogix
System User Manual, publication RA-UM003
.
Move/Logical Category
The Move/Logical category includes fundamental bit type logic operations,
including the instruction types:
•Boolean
AND (BAND)
Not AND (BNAND)
OR (BOR)
Not OR (BNOR)
Exclusive OR (BXOR)
Exclusive Not OR (BXNOR)
NOT (BNOT)
•Latch
Set Latch (SETD)
Reset Latch (RESD)
Boolean Functions
The Boolean functions are as follows. The number of inputs can be changed
on some functions but are limited to a maximum of four. The latch instruction
type has two fixed inputs, "Set" as input 1 and "Reset" as input 2.
Function Block TypeInput 1Input 2Output Value
AND (BAND)000
010
100
111
Not AND (BNAND)001
011
101
110
72Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix Capabilities
Function Block TypeInput 1Input 2Output Value
OR (BOR) 000
011
101
111
Not OR (BNOR)001
010
100
110
Exclusive OR (BXOR)000
011
101
110
Exclusive Not OR (BXNOR)001
010
100
111
NOT (BNOT)
(1)
0N/A1
1N/A0
(1)
The Input number can be set in a property page; the default number is 2. BNOT has only one input.
Latch Functions
There are two kinds of Latch functions: Set Dominant Latch (SR) and Reset
Dominant Latch (RS). Unlike the Latch in RSLogix 5000, DeviceLogix Latch
requires the Reset binding. So the Set/Reset appears in pair and the RS type
and SR type have different element order. See its truth table below.
Function Block TypeResetSetValue at time +
t
0
SETD (Set Dominant)0000
0101
1000
1101
0011
0111
1010
Value at time +
t
0+1
1111
Rockwell Automation Publication 1734-UM015B-EN-E - May 202073
DeviceLogix Capabilities
Function Block TypeResetSetValue at time +
t
0
RS (Reset Dominant)0000
0101
1000
1100
0011
0111
1010
1110
Value at time +
t
0+1
For more information on the Move/Logical category, refer to the DeviceLogix
System User Manual, publication RA-UM003
.
Logic Execution Time
The execution time is dependent on the total number of function blocks used
in the entire DeviceLogix program.
Number of Function BlocksApproximate Expected
Execution Time (ms)
0…401
41…1002
101…1443
The module will execute the entire logic program before applying the outputs.
The module follows these steps:
1. Sample all inputs (hardware, network, peer).
2. Execute logic.
3. Apply all outputs (hardware, network).
74Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix Capabilities
Digital Inputs to Function Blocks
When the Bit Input I/O tag connector is added to the DeviceLogix editor, the
following input options are available:
Hardware
Discrete Input 0 through Discrete Input 7 are the states of the eight I/O
points on the module.
Status
The following is a list of status bits that can be selected. Most will only be used
in a DeviceNet network:
• Explicit Msg Cnxn Exists
• Polled Cnxn Exists
• COS/Cyclic Cnxn Exists
• Polled Cnxn Fault
• COS/Cyclic Cnxn Fault
• Polled Cnxn Idle
•Network Fault
• Minor Module Fault
• Bit-Strobe Cnxn Exists
• Bit-Strobe Cnxn Fault
• Bit-Strobe Cnxn Idle
Rockwell Automation Publication 1734-UM015B-EN-E - May 202075
DeviceLogix Capabilities
If you are using the EtherNet/IP or ControlNet adapter, it is suggested that
you use the COS/Cyclic connection status bits to determine the health of the
connection with a master.
The following are the status bits for the eight Peer connections:
• Peer#X Data valid
• Peer#X Exists
Use the Exists bits to determine if a connection is configured, and the Data
Valid bit to check if the data from the peer has been received in the expected
time (EPR) and with the expected data size.
Network
Network Input 0 through Network Input 7 are sent to the DeviceLogix
program through the Output Data assembly byte 1. In RSLogix 5000, the tag
name for these bits is UserDefinedBitData.
Reserved Bit 8 through Reserved Bit 31 are legacy bits and should not be used.
There are many Peer#X (Byte X Bit X) bits. This is a mapping of 24-byte bit
data for the eight peer connections. You need to know the Input Memory map
of each of the peers in order to use this data. See Appendix A
.
76Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix Capabilities
Analog Inputs to Function Blocks
When the Analog Input I/O tag connector is added to the DeviceLogix editor,
the following options are available.
Network Analog Input
Network Input Word 0 through Network Input Word 7 are sent to the
DeviceLogix program through the Output Assembly. In RSLogix 5000, the tag
name for these words is UserDefinedWordData[0..7].
The ZIP Security Key defines a unique number that can be sent to a peer to
verify the identity and configuration of the module. The ZIP key can be
directly tied to a Network Output Word in the DeviceLogix program.
Peer#x (Word x)
There are eight groups of peer data (0…7) and 12 words within each group.
These are the eight peers and up to 24 bytes of data mapped from each peer.
You need to know the input data map from each peer to know what data to
use. See Appendix A
.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202077
DeviceLogix Capabilities
Discrete Output 0
Consume Data Assembly
Byte 076 54 32 1 0
44953
Digital Outputs from Function Blocks
Hardware
Discrete Output 0 through Discrete Output 7 are the eight hardware outputs
available on the module. If these tags are unused (that is, not mapped in the
DeviceLogix program), then there is a virtual mapping from the Data Byte
Output Assembly to the output point. This means that the output is under
control of the owning processor. If the Discrete Output is mapped in logic, it
is controlled by the module.
Virtual Connection if Output Not Used in Logic
78Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix Capabilities
DOP: Digital Output Point
EM: Explicit Message
This flowchart shows the process and priority the module follows when
updating each Digital Output Point (DOP). The process considers module
states such as Network Fault and Run/Idle, configurable parameters such as
Network Fault Override, and Logic states such as Logic Enabled and Force.
Output Ownership (Value Source Selector Behavior for Bound Outputs)
Update
Output
Explicit Message Request
to change DOP value
I/O Message to
change DOP value
Return Object State
Conflict Error
Network
Fault
EM
I/O
Comm
Override
Fault
Idle
Run
Available State
Available
Yes
Yes
Yes
Fault Exists
Receive Idle
DOP in RUN mode
DOP in
Perform Logic
Network
Fault
Override
Logic
Enabled
Program
Disabled
Use Idle Action
and Idle Value
Use Fault Action
and Fault Value
Clear DOP Value
Ignore Message
Apply Force Value
Apply Value to DOP
End
Rockwell Automation Publication 1734-UM015B-EN-E - May 202079
DeviceLogix Capabilities
Network
Network Output Bit 0 through Network Output Bit 7 are mapped to the Input
I/O Assembly byte 1. These bits can be sent to the owning processor or to
other peers. In RSLogix 5000, the tag name is UserDefinedBitData.
Analog Outputs from Function Blocks
Network
Network Output Word 0 through Network Output Word 7 are mapped to the
Input I/O Assembly. These words can be sent to the owning processor or to
other peers. In RSLogix 5000, the tag name is UserDefinedWordData[0..7].
80Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix Capabilities
Enable Line feature
The Enable Line feature can be supported by each instruction type in the
Function Block Editor. When an instruction supports the Enable Line feature,
that particular instruction can only be executed when Enable Line is on;
otherwise, that instruction maintains the data from the last data scan. In this
manner, functions can be executed conditionally based on the state of the
Enable input. Under normal conditions, the Enable output will have the same
value as the input, passing the enable information to the next instruction.
Certain error conditions that occur within the processing of a function block
may cause the Enable output to go false.
If the Enable Line feature is used, EnableIn can be connected to an input I/O
tag or the output of another function block. The EnableIn input will retain the
value of the source that it is bound to.
If the Enable Line feature is not needed, the EnableIn input can use a constant
value which can be set on each instruction’s property page. By default, this
constant will allow execution of the function.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202081
DeviceLogix Capabilities
DNT File
RSNetWorx for DeviceNet
Online
Module
Offline and Online Editing
Editing of the configuration and DeviceLogix program can be done off-line
and saved in the DNT file created by RSNetWorx for DeviceNet. The
changes, however, must be manually downloaded to the module while online.
When using RSLogix 5000 with an EtherNet/IP or ControlNet adapter, the
forward open to the DeviceLogix module does not contain any configuration
information. The configuration must be sent via RSNetWorx for DeviceNet
while online.
The I/O module will save the configuration and DeviceLogix program locally
(inside the module). You will only need to download the configuration once. If
you replace the device, you need to download the configuration to the new
module.
Before the DeviceLogix program executes, it must be enabled. You can do this
using the Editor while online. For details, see Enable/Disable Logic
.
Alternatively, you can use the owning processor to enable the program. For
details, see Messaging
.
82Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix Capabilities
Enable/Disable Logic
For logic to execute, it must be enabled. While editing online with RSNetWorx
for DeviceNet, you can enable logic.
Logic Enable On
Use the Logic Enable On function to notify the device to start processing the
stored logic diagram. To set Logic Enable On, select Communications > Logic
Enable On.
Logic Enable Off
Use the Logic Enable Off option to notify the device to stop executing the
logic program. When you select this option, the device enters an idle state,
turning off the Logic Enable Bit in the produced data. The Logic Enable bit in
the Produced I/O assembly of the device reflects a 0 or 1 for Logic Enable
Off or Logic Enable On. To set Logic Enable Off, select Communications >
Logic Enable Off.
Dependent Mode
Logic will also be enabled or disabled if the Dependent Mode parameter is
Enabled. In this case, logic will execute following the state of the owning
connection. When the connection is in RUN, the logic is enabled. When the
connection is in Idle, Fault, or non-existent, logic is disabled.
You can also enable or disable logic through explicit messages from the
owning controller. See Messaging
.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202083
DeviceLogix Capabilities
IMPORTANT
Function block instances
Messaging
There are certain parameters that you may want to SET or READ from the
module that are not part of the I/O Assemblies. Those parameters are still
available through messaging.
This section contains advanced user information. You should understand the
CIP object model and be familiar with the terms Service, Class, Instance, and
Attribute.
This section discusses how to SET and READ information from the Timer
and Counter function blocks and how to enable and disable logic with the
Logic Supervisor Object.
The first thing that is important to know is that each function block has a
handle or an instance number. This instance number is assigned by the editor,
it can be found in the upper left corner of the function block.
The instance number can change if you edit the program. It may also be
different from module to module. Verify the instance number before using
messaging.
For devices running firmware revision 4 or higher, each
instruction instance ID number is assigned once and will never
change.
84Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
DeviceLogix Capabilities
To access the information, you need the “address” of that information. The
address is made up of the Class Code, the instance (as discussed above), and
the attribute.
The following table shows this data for the Logic Supervisor, Timer, and
Counter function blocks.
Function BlockClass
Code
Logic Supervisor0x30E1Logic Enable (0x01)1 byte
Timer Function
Block
Counter Function
Block
0x30ADisplayed in
0x309Preset Value (0x05)2 bytes
InstanceAttributeData Length
Preset Time (0x04)2 bytes
editor
Elapsed Time (0x07)2 bytes
Time Base (0x08)1 byte
0 = 1 ms (default)
1 = 10 ms
Count Value (0x07)2 bytes
Maximum Input
Frequency (0x08)
2 bytes
Note that there is only one Logic Supervisor and its instance is always "1".
If you are using RSLogix 5000, you can send a message by using the MSG
instruction.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202085
DeviceLogix Capabilities
DeviceNet scanner name, port, node address
To configure the message, do the following:
1. Click the ellipsis (…) button.
The Message Configuration dialog box appears.
2. Set the message type to “CIP Generic.”
3. Set the Service Type to “Set Attribute Single” to set data or “Get
Attribute Single” to read data.
4. Enter the Class value in hexadecimal from the table (“30A” is the Timer
function block).
5. Copy the Instance number from the upper left corner of the Timer
function block to which you are sending the message.
6. Enter the Attribute number in hexadecimal (“4” is the Preset Time).
7. Verify that the Source Element and Source Length (in bytes) is correct.
8. Click the Communication tab.
9. If you are using EtherNet/IP or ControlNet, click Browse to navigate to
the DeviceLogix module.
If you are using DeviceNet, browse to the DeviceNet Scanner
(1756-DNB) and enter Port "2" (for the DeviceNet port) and the node
number of the DeviceLogix module (node "4" in the following example)
separated by commas.
86Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Troubleshooting
Node-level diagnostics:
Module status indicator
indicates the health of the
module.
Network Status indicator
indicates the status of the
communication link.
DeviceLogix indicator
indicates the state of the
DeviceLogix program.
I/O point indicator
indicates I/O (ON/OFF or
fault/diagnostic) status.
I/O Channel State
Module Status
Network Status
44759
DeviceLogix Status
Chapter
8
About This Chapter
About Module Diagnostics
This chapter provides information about module diagnostics, and about
troubleshooting with the following indicators:
• Module status
•Network status
• DeviceLogix status
• Power indication
• I/O POINT status (ON/OFF/fault or diagnostic)
In addition, the following troubleshooting scenarios are provided:
• Peer connection is not working
• Configuration or DeviceLogix program cannot be downloaded to the
module
• Module’s DeviceLogix program exits the Run mode unexpectedly
All status and diagnostic information (strobed, polled, cyclic, or
change-of-state) is reported back over the network communication adapter.
A single point of failure is detected and reported at the module and to the
control system.
Module
Status
Network
Status
NODE:
Device
Logix
Status
0
0
4
1
1
5
2
2
Rockwell Automation Publication 1734-UM015B-EN-E - May 202087
3
3
1734
8CFGDLX
6
7
Troubleshooting
1
3
0
2
Module
Status
Network
Status
Device
Logix
Status
1734
8CFGDLX
1
3
0
2
5
7
4
6
NODE:
44759
Status of I/O 0
Status of I/O 1
Status of I/O 2
Status of I/O 3
Status of I/O 4
Status of I/O 5
Status of I/O 6
Status of I/O 7
Module Status
Network Status
DeviceLogix Status
Status Indicators of POINT
I/O Module
See the figure and tables that show how to interpret the status indicators.
1734-8CFGDLX Module
Module Status
IndicationProbable CauseRecommended Action
OffNo power applied to device.Apply power to device.
GreenDevice operating normally.None.
Flashing
green
Device needs commissioning due to
missing, incomplete or incorrect
Configure device properly.
configuration.
Flashing redRecoverable fault.1. Cycle power to device.
2. If condition persists, replace
device.
RedUnrecoverable fault may require
Replace device.
device replacement.
Flashing
Device is in self-test.None.
red/green
88Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Network Status
IndicationProbable CauseRecommended Action
OffDevice is not online.
- Device has not completed
dup_MAC_id test.
- Device not powered - check module
status indicator.
GreenDevice is online and has connections
in the established state.
Apply power to device, wait for
dup_MAC_id to complete, and
correct, as needed.
None.
Troubleshooting
Flashing
green
Flashing redOne or more I/O connections are in
RedCritical link failure - failed
Flashing
red/green
Device is online but has no
connections in the established state.
the timed-out state.
This could also mean a peer is not
producing data at all, or it is not
configured correctly.
communication device. Device
detected error that prevents it
communicating on the network.
Device is in self-test.None.
None.
Check I/O connection with
master. Verify that peers are
present and configured properly.
Verify that adapter and terminal
bases are properly installed, and
reinstall, as needed.
DeviceLogix Status
IndicationProbable CauseRecommended Action
OffDeviceLogix program is not
controlling outputs.
GreenDeviceLogix program is controlling
outputs.
Flashing
green
At least one input in DeviceLogix
program is forced on/off.
None.
None.
None.
I/O Status
IndicationProbable CauseRecommended Action
OffInput or output is in the OFF state.None.
YellowInput or output is in the ON state.None.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202089
Troubleshooting
Module Status Indicator
44355
Network Status Indicator
I/O Status Indicators
1738-8CFGM12 shown
Status Indicators of
ArmorPOINT I/O Modules
See the figure and tables that show how to interpret the status indicators.
1738-8CFGDLXM8, 1738-8CFGDLXM12, and 1738-8CFGDLXM23
H
1738-8CFGDLXM12
24V DC Out
G
F
E
MOD
NET
0
1
2
3
4
5
6
7
Module Status
A
X
L
D
B
C
D
IndicationDescriptionRecommended action
OffNo power applied to device.Apply power to device.
GreenDevice operating normally.None.
Flashing
green
RedUnrecoverable fault – may require
Flashing redRecoverable fault.Cycle power to device.
Flashing
red/green
Device needs commissioning due to
Configure device properly.
missing, incomplete, or incorrect
configuration.
Replace device.
device replacement.
If condition persists, replace
device.
Device is in self-test.None.
90Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Network Status
IndicationDescriptionRecommended action
OffDevice is not online:
- Device has not completed
dup_MAC-id test.
- Device not powered – check module
status indicator.
Apply power to device, wait for
MAC_id to complete, and correct,
as needed.
Troubleshooting
GreenDevice is online and has one or more
I/O connections in established state.
Flashing
green
Flashing redOne or more I/O connections are in
RedCritical link failure – failed
Flashing
red/green
Device is online but has no
connections in established state.
the timed-out state.
communication device. Device
detected error that prevents it from
communicating on the network.
Device is in self-test.None.
None.
None.
Check for I/O module failure, and
correct, as needed.
Verify that adapter and terminal
bases are properly installed, and
reinstall, as needed.
DeviceLogix Status
IndicationDescriptionRecommended action
OffDeviceLogix program is not
controlling outputs.
GreenDeviceLogix program is controlling
outputs.
Flashing
green
At least one input in DeviceLogix
program is forced on/off.
None.
None.
None.
I/O Status
IndicationDescriptionRecommended action
OffI/O is inactive.None.
YellowI/O is active and under control.None.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202091
Troubleshooting
Troubleshooting Scenarios
The following are scenarios that you may encounter while using the modules.
Peer connection is not working
If the Network Status LED is flashing red, one or more connections to the
device are broken or not functioning properly. If the device has been
configured to consume data from peers, it is possible that the data size or data
rate have not been configured correctly.
• Use the Peer Missing bits in the I/O assembly to check which peer
connection is missing.
• Verify the configuration is correct. Upload from the module into
RSNetWorx for DeviceNet.
• Verify the Node number or Slot number is correct.
• Verify the connection size is correct.
• Increase the EPR (Expected Packet Rate).
• Verify that the owner of the connection to the peer (usually a scanner or
controller) is receiving data. The DeviceLogix module cannot make a
connection to a peer; it can only listen to COS (Change-of-State) I/O
data going from the peer to the master.
92Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Troubleshooting
Configuration or DeviceLogix program cannot be downloaded to
the module
A DeviceLogix program and most configurable parameters cannot be changed
while the DeviceLogix program is running or when an I/O connection is
active.
• Inhibit the connection in RSLogix 5000 (if using EtherNet/IP and
ControlNet).
• Disable logic in RSNetWorx for DeviceNet before downloading.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202093
Troubleshooting
• Clear the Node Active checkbox in RSNetWorx for DeviceNet (if using
a DeviceNet scanner or DeviceNet adapter).
Module’s DeviceLogix program exits the Run mode unexpectedly
The module’s DeviceLogix program exits the Run mode unexpectedly. A
possible reason may be that the ADR feature of the scanner is turned on and
the ADR data of the module stored in the scanner is not consistent with what
is on the module. When the scanner establishes connection to the module, it
will verify the configuration in itself with what is in the module. Any mismatch
would result in the scanner downloading its saved ADR data to the module.
• Check the ADR feature of the network scanner and verify if the
configuration stored in the scanner is the most recent and correct
version.
94Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Peer Data Maps
Appendix A
About This Appendix
Peer I/O Sizes
This appendix contains information to help you use peer data from
POINT I/O and ArmorPOINT I/O modules in your DeviceLogix program.
For descriptions or details on the individual modules, refer to the Installation
Instructions or User Manual for the specific modules.
The following tables list the produced I/O sizes of the digital and analog input
modules, including those of the POINT I/O and ArmorPOINT I/O
modules.
Only the input modules are listed below. The data sent to or consumed by
output modules cannot be used in Peer data connections. Although it is
possible to read the status information produced from some output modules,
they are not included here for the sake of brevity. If another module’s output
data is required in your DeviceLogix program, it is suggested that this data be
sent from the owning master to the DeviceLogix module through the output
(consumed) data assembly.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202095
Peer Data Maps
Digital Input Modules
Produced I/O Sizes of Digital Input Modules
Catalog NumberDescriptionProduced
Size
1734-IB22-point sinking DC input1
1738-IB2M12 (M8)2-point sinking DC input1
1734-IB44-point sinking DC input1
1738-IB4M12 (M8)4-point sinking DC input1
1734-IB4D4-point sinking DC input with diagnostics2 (default), 1
1738-IB4DM124-point sinking DC input with diagnostics2 (default), 1
1734-IB88-point sinking DC input1
1738-IB8M12 (M8, M23)8-point sinking DC input1
1734-IV22-point sourcing DC input1
1734-IV44-point sourcing DC input1
1738-IV4M12 (M8)4-point sourcing DC input1
1734-IV88-point sourcing DC input1
1738-IV8M12 (M8, M23)8-point sourcing DC input1
1734-IA22-channel 120V AC input1
1738-IA2M12AC32-channel 120V AC input1
1738-IA2M12AC42-channel 120V AC input1
1734-IA44-channel 120V AC input1
1734-IM22-channel 220V AC input1
1734-IM44-channel 220V AC input1
1734-IB16DM1216-point sinking DC input with diagnostics2 (default), 3
1734-8CFG8-point DC input/output1
1738-8CFGM12 (M8, M23) 8-point DC input/output1
1734-8CFGDLX8-point DC input/output with DeviceLogix20 (default),
8, 1
1738-8CFGDLXM12 (M8,
M23)
8-point DC input/output with DeviceLogix20 (default),
8, 1
96Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Peer Data Maps
Analog and Specialty Input Modules
Produced I/O Sizes of Analog and Specialty Input Modules
Catalog NumberDescriptionProduced
Size
1734-VHSC51-channel, 5V, 2-out Very High-Speed Counter6, 6,
10 (default)
1734-VHSC241-channel, 24V, 2-out Very High-Speed Counter 6, 6,
10 (default)
1734-VHSC24M231-channel, 24V, 2-out Very High-Speed Counter 6, 6,
10 (default)
1734-IJ1-channel, 5V counter6 (default),
6, 10
1734-IK1-channel, 24V counter6 (default),
6, 10
1738-IJM231-channel, 24V counter6 (default),
6, 10
1734-IE2C2-channel analog input6
1734-IE4C4-channel analog input12
1734-IE8C8-channel analog input24
1738-IE2CM122-channel analog input6
1738-IE4CM124-channel analog input12
1734-IE2V2-channel analog voltage input6
1738-IE2VM122-channel analog voltage input6
1734-IT2I2-channel, thermocouple input8
1738-IT2IM122-channel, thermocouple input8
1734-IR22-channel, 2-point RTD input6
1738-IR2M122-channel, 2-point RTD input6
1734-SSISynchronous Serial Interface10
1738-SSIM23Synchronous Serial Interface10
1734-232ASCRS232 ASCII Interface4…132,
Rockwell Automation Publication 1734-UM015B-EN-E - May 202097
Peer Data Maps
Internal Data Table in Module
Referenced in
DeviceLogix Function Block Editor (FBE)
Peer0 Data
Peer#0 (Byte 0,Bit 0)
Peer#0 (Word 11)
Bit-addressing
Word-addressing
7 6 5 4 3 2 1 0
b7b0
b15b8 b7b0
Peer1 Data
Peer2 Data
Peer3 Data
Peer4 Data
Peer5 Data
Peer6 Data
Peer7 Data
Up to 24 Bytes
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 22
Byte 23Byte 22
Byte 23
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
Up to 24 Bytes
44954
Peer Data Maps
The following are data maps for each of the catalogs listed in the preceding
tables. The peer data is mapped into one of eight 24-byte memory spaces.
Peer X is the specific memory space where X is 0…7.
The following is a diagram to help explain the addressing of bit data and word
data in the DeviceLogix function block editor.
98Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Peer Data Maps
In the following sections, the input tag name in the DeviceLogix editor is given
in the left column, and a description of the tag is given in the right column.
This section is intended to be used as a quick guide. For details, refer to the
installation instructions or user manual for the specific peer module.
Peer X (byte 0, bit 0)Input channel 0
Peer X (byte 0, bit 1)Input channel 1
Peer X (byte 0, bit 2)Input channel 2
Peer X (byte 0, bit 3)Input channel 3
Rockwell Automation Publication 1734-UM015B-EN-E - May 202099
Peer Data Maps
4-Point Digital Input with Diagnostics Modules
1734-IB4D, 1738-IB4DM12
Input Tags for 4-Point Digital Input with Diagnostic Modules
Input Tag in DeviceLogix EditorData
Peer X (byte 0, bit 0)Input channel 0
Peer X (byte 0, bit 1)Input channel 1
Peer X (byte 0, bit 2)Input channel 2
Peer X (byte 0, bit 3)Input channel 3
Peer X (byte 0, bit 4)Fault channel 0
Peer X (byte 0, bit 5)Fault channel 1
Peer X (byte 0, bit 6)Fault channel 2
Peer X (byte 0, bit 7)Fault channel 3
Peer X (byte 1, bit 0)Open wire channel 0
Peer X (byte 1, bit 1)Open wire channel 1
Peer X (byte 1, bit 2)Open wire channel 2
Peer X (byte 1, bit 3)Open wire channel 3
Peer X (byte 1, bit 4)Short circuit channel 0
Peer X (byte 1, bit 5)Short circuit channel 1
Peer X (byte 1, bit 6)Short circuit channel 2
Peer X (byte 1, bit 7)Short circuit channel 3
Peer X (byte 0, bit 0)Input channel 0
Peer X (byte 0, bit 1)Input channel 1
Peer X (byte 0, bit 2)Input channel 2
Peer X (byte 0, bit 3)Input channel 3
Peer X (byte 0, bit 4)Input channel 4
Peer X (byte 0, bit 5)Input channel 5
Peer X (byte 0, bit 6)Input channel 6
Peer X (byte 0, bit 7)Input channel 7
100Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.