Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this
control equipment must satisfy themselves that all necessary steps
have been taken to assure that each application and use meets all
performance and safety requirements, including any applicable laws,
regulations, codes and standards.
The illustrations, charts, sample programs and layout examples
shown in this guide are intended solely for example. Since there are
many variables and requirements associated with any particular
installation, Allen-Bradley does not assume responsibility or liability
(to include intellectual property liability) for actual use based upon
the examples shown in this publication.
Allen-Bradley publication SGI–1.1, “Safety Guidelines For The
Application, Installation and Maintenance of Solid State Control”
(available from your local Allen-Bradley office) describes some
important differences between solid-state equipment and
electromechanical devices which should be taken into consideration
when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in
whole or in part, without written permission of Allen–Bradley
Company, Inc. is prohibited.
Throughout this manual we make notes to alert you to possible
injury to people or damage to equipment under specific
circumstances.
ATTENTION: Identifies information about practices
or circumstances that can lead to personal injury or
!
death, property damage, or economic loss.
Attention helps you:
• identify a hazard
• avoid the hazard
• recognize the consequences
Important: Identifies information that is especially important for
successful application and understanding of the product.
Important: We recommend you frequently backup your application
programs on appropriate storage medium to avoid
possible data loss.
DeviceNet, DeviceNetManager, and RediSTATION are trademarks of Allen-Bradley Company, Inc.
PLC, PLC–2, PLC–3, and PLC–5 are registered trademarks of Allen-Bradley Company, Inc.
Windows is a trademark of Microsoft.
Microsoft is a registered trademark of Microsoft
IBM is a registered trademark of International Business Machines, Incorporated.
All other brand and product names are trademarks or registered trademarks of their respective companies.
The information below summarizes the changes to the
company-wide templates since the last release.
New Information
Updated Information
The following new information has been added to this manual:
• the “L” type thermocouple selection has been added for use in
some European markets.
Calibration procedures have been revised to eliminate 1 method in
order to better control calibration results.
Change Bars
The areas in this manual which are different from previous editions
are marked with change bars (as shown to the right of this paragraph)
to indicate the addition of new or revised information.
Publication
1794-6.5.7 – April 1997
soc–iiSummary of Changes
Publication
1794-6.5.7 – April 1997
Table of Contents
Overview of Flex I/O and
your Thermocouple/mV
Module
How to Install Your
Thermocouple/mV Input
Module
Chapter 1
Chapter Objectives
The FLEX I/O System
How
FLEX I/O Analog Modules Communicate with Programmable
Controllers
Typical
Communication Between an Adapter and a Module
Features
Chapter Summary
Read this preface to familiarize yourself with this manual and to
learn how to use it properly and efficiently.
We assume that you have previously used an Allen-Bradley
programmable controller, that you are familiar with its features, and
that you are familiar with the terminology we use. If not, read the
user manual for your processor before reading this manual.
In addition, if you are using this module in a DeviceNet system, you
must be familiar with:
• DeviceNetManager
• Microsoft Windows
TM
Software, cat. no. 1787-MGR
TM
In this manual, we refer to:
• the individual thermocouple/mV module as the “module.”
• the programmable controller as the “controller” or the
“processor.”
The contents of this manual are as follows:
ChapterTitleWhat’s Covered
1
2
3Module Programming
4
5
6Calibrating Your Module
Appendix
ASpecifications
BThermocouple RestrictionsExtracted from NBS Monograph 125 (IPTS–68)
Overview of Flex I/O and Your
Thermocouple/mV Module
How to Install Your
Thermocouple/mV Input Module
Writing Configuration to and Reading
Status from Your Module with a
Remote I/O Adapter
How Communication Takes Place
and I/O Image Table Mapping with
the DeviceNet Adapter
Describes features, capabilities, and hardware
components.
Installation and connecting wiring
Block transfer programming and programming
examples
Describes block transfer write and block transfer read
configurations, including complete bit/word descriptions.
Describes communication over the I/O backplane
between the module and the adapter, and how data is
mapped into the image table.
Lists the tools needed, and the methods used to
calibrate the thermocouple input module
Module specifications, derating curve, resolution curves
for thermocouples, worst case accuracy and error due
to open circuit current.
Publication
1794-6.5.7 – April 1997
Using This ManualP–2
Catalog
Conventions
For Additional Information
Number
1787-MGRDeviceNetManager Software User Manual1787-6.5.3
17941794 FLEX I/O Product Data1794-2.1
1794-ADNDeviceNet Adapter1794-5.141794-6.5.5
1794-ASB/CRemote I/O Adapter1794-5.461794-6.5.9
We use these conventions in this manual:
In
this manual, we show:Like this:
that there is more information about a topic
in another chapter in this manual
that there is more information about the
topic in another manual
More
For additional information on FLEX I/O systems and modules, refer
to the following documents:
Publications
Description
Industrial Automation Wiring and Grounding Guidelines1770-4.1
Installation
Instructions
User
Manual
Summary
This preface gave you information on how to use this manual
efficiently. The next chapter introduces you to the remote I/O
adapter module.
Publication
1794-6.5.7 – April 1997
Chapter
1
Overview of FLEX I/O and your
Thermocouple/mV Module
Chapter Objectives
The FLEX I/O System
Adapter/Power SupplyTerminal BaseI/O Module
In this chapter, we tell you:
• what the FLEX I/O system is and what it contains
• how FLEX I/O modules communicate with programmable
controllers
• the features of your thermocouple module
FLEX I/O is a small, modular I/O system for distributed
applications that performs all of the functions of rack-based I/O. The
FLEX I/O system contains the following components shown below:
How FLEX I/O Analog
Modules Communicate
with Programmable
Controllers
20125
• adapter/power supply – powers the internal logic for as many as
eight I/O modules
• terminal base – contains a terminal strip to terminate wiring for
thermocouple or millivolt inputs.
• I/O module – contains the bus interface and circuitry needed to
perform specific functions related to your application
FLEX I/O thermocouple/mV modules are block transfer modules
that interface analog signals with any Allen-Bradley programmable
controllers that have block transfer capability. Block transfer
programming moves input or output data words between the
module’s memory and a designated area in the processor data table.
Block transfer programming also moves configuration words from
the processor data table to module memory.
Publication
1794-6.5.7
Overview of FLEX I/O and your Thermocouple/mV Module 1–2
The adapter/power supply transfers data to the module (block
transfer write) and from the module (block transfer read) using BTW
and BTR instructions in your ladder diagram program. These
instructions let the adapter obtain input or output values and status
from the module, and let you establish the module’s mode of
operation. The illustration describes the communication process.
Typical Communication Between an Adapter and a Module
ADAPTER
ACTIVE FAULT
Allen-Bradley
LOCAL
FAULT
1
The adapter transfers your configuration data
to the module using a BTW.
Flexbus
POWER SUPPLY
RIO ADAPTER
1794-ASB
24VDC
4
Your ladder program instructs the
adapter to perform a BTR of the values
and stores them in a data table.
5
The adapter and module determine
that the transfer was made without error and
input values are within specified range.
6
Your ladder program can use and/or move the data (if valid)
before it is written over by the transfer of new data in a
subsequent transfer.
INPUT
0
+– +–
External devices transmit
analog signals to the module.
Allen-Bradley
THERMOCOUPLE
INPUT 8 CHANNEL
INPUT 2INPUT 4INPUT 6INPUT 1INPUT 3INPUT 5INPUT 7
+–+–+– +–+–+–
The module converts analog signals
into binary format and stores these
values until the adapter requests
their transfer.
2
1794–IT8
3
OK
3
Publication
7
Your ladder program performs BTWs to the module only when
you power it up, or any time you wish to reconfigure the module.
1794-6.5.7
Overview of FLEX I/O and your Thermocouple/mV Module 1–3
Features of your Modules
The module label identifies the keyswitch position, wiring and
module type. A removable label provides space for writing
individual designations per your application.
1794-IT8
Module Type
Allen-Bradley
INPUT
0
+– +–
THERMOCOUPLE
INPUT 2INPUT 4INPUT 6INPUT 1INPUT 3INPUT 5INPUT 7
+– +– +– +–+–+–
INPUT 8 CHANNEL
Input Designators
1794–IT8
Removable Label
3
Keyswitch
OK
Position
Indicator (#3)
Power On Indicator
The thermocouple/mV module comes with 2 cold junction
compensators. These are designed to mount in designated positions
on the temperature terminal base unit (cat. no. 1794-TB3T). Refer to
chapter 2 for installation instructions for the cold junction
compensator assemblies.
Chapter Summary
In this chapter, you learned about the FLEX I/O system and the
thermocouple module, and how they communicate with
programmable controllers.
Publication
1794-6.5.7
Overview of FLEX I/O and your Thermocouple/mV Module 1–4
Publication
1794-6.5.7
Chapter
How to Install Your
Thermocouple/mV Input
Module
In this chapter, we tell you:
• how to install your module
• how to set the module keyswitch
• how to wire the terminal base
• about the indicators
2
Before You Install Your
Input Module
European Union Directive
Compliance
Before installing your thermocouple/mV module in the I/O chassis:
You need to:As described under:
Calculate the power requirements of all
modules in each chassis.
Position the keyswitch on the terminal baseInstalling the Module, page 2–4
ATTENTION: The Thermocouple module does not
receive power from the backplane. +24V dc power
!
If this product has the CE mark it is approved for installation within
the European Union and EEA regions. It has been designed and
tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC) and the following standards,
in whole or in part, documented in a technical construction file:
• EN 50081-2EMC – Generic Emission Standard, Part 2 –
Industrial Environment
• EN 50082-2EMC – Generic Immunity Standard, Part 2 –
Industrial Environment
must be applied to your module before installation. If
power is not applied, the module position will appear
to the adapter as an empty slot in your chassis.
Power Requirements, page 2-2
This product is intended for use in an industrial environment.
Publication
1794-6.5.7
2–2
How to Install Your Thermocouple/mV Input Module
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC
Low Voltage, by applying the safety requirements of EN 61131–2
Programmable Controllers, Part 2 – Equipment Requirements and
Tests.
For specific information required by EN 61131-2, see the appropriate
sections in this publication, as well as the following Allen-Bradley
publications:
• Industrial Automation Wiring and Grounding Guidelines For
Noise Immunity, publication 1770-4.1
• Guidelines for Handling Lithium Batteries, publication AG-5.4
• Automation Systems Catalog, publication B111
Power Requirements
The wiring of the terminal base unit is determined by the current
draw through the terminal base. Make certain that the current draw
does not exceed 10A.
ATTENTION: Total current draw through the
terminal base unit is limited to 10A. Separate power
!
!
connections may be necessary.
ATTENTION: Do not daisy chain power or ground
from the thermocouple terminal base unit to any ac or
dc discrete module terminal base unit.
Publication
1794-6.5.7
How to Install Your Thermocouple/mV Input Module
Methods of wiring the terminal base units are shown in the
illustration below.
Wiring the Terminal Base Units (1794-TB2 and -TB3 shown)
ATTENTION: Do not daisy chain power or
!
ground from the thermocouple terminal base unit to
any ac or dc discrete module terminal base unit.
2–3
Daisy-chaining
Individual
24V dc or
120V ac
24V dc
Thermocouple
or Analog Module
24V dc
24V dc
Thermocouple module wiring separate from discrete wiring.
Note: All modules must be analog modules for this configuration.
Wiring
when total current draw is less than 10A
Discrete
Module
Thermocouple
or Analog Module
Thermocouple
or Analog Module
Thermocouple
or Analog Module
Discrete
Module
Note: Use this configuration if using any
“noisy” dc discrete I/O modules in your system.
Thermocouple
or Analog Module
Discrete
Module
Combination
24V dc
24V dc
W
iring when total current draw is greater than 10A
Discrete
Module
Note: All modules powered by the same power supply
must be analog modules for this configuration.
T
otal current draw through any base unit must not be greater than 10A
Thermocouple
or Analog Module
Thermocouple
or Analog Module
Thermocouple
or Analog Module
Publication
1794-6.5.7
2–4
How to Install Your Thermocouple/mV Input Module
Installing the Module
The thermocouple/mV module mounts on a 1794-TB2, -TB3 or
-TB3T terminal base unit.
Important:You must use a 1794-TB3T terminal base unit if you
are using the thermocouple/mV module for
thermocouple inputs. You can use the 1794-TB2 or
-TB3 terminal base for millivolt inputs only.
7
3
4
1. Rotate the keyswitch (1) on the terminal base unit (2) clockwise
to position 3 as required for the thermocouple/mV module.
2. Make certain the flexbus connector (3) is pushed all the way to
the left to connect with the neighboring terminal base/adapter.
You cannot install the module unless the connector is fully
extended.
1
2
6
5
ATTENTION: Remove field-side power before
removing or inserting the module. This module is
!
designed so you can remove and insert it under
backplane power. When you remove or insert a
module with field-side power applied, an electrical arc
may occur. An electrical arc can cause personal injury
or property damage by:
• sending an erroneous signal to your system’s field
devices causing unintended machine motion
• causing an explosion in a hazardous environment
Repeated electrical arcing causes excessive wear to
contacts on both the module and its mating connector.
Worn contacts may create electrical resistance.
3. Before installing the module, check to make sure that the pins on
the bottom of the module are straight so they will align properly
with the female connector in the base unit.
4. Position the module (4) with its alignment bar (5) aligned with
the groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base
unit. The module is seated when the latching mechanism (7) is
locked into the module.
Publication
6. Repeat the above steps to install the next module in its terminal
base unit.
1794-6.5.7
How to Install Your Thermocouple/mV Input Module
2–5
Connecting Wiring for the
Thermocouple/mV Module
1794-TB2
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
COMCOM
VV
V = 24V dc
COM
= 24V dc common
These
and 1794-TB3
terminals on 1794-TB3 only
Thermocouple/mV module wiring is made through the terminal base
unit on which the module mounts. The module comes with 2 cold
junction compensators for use when using the thermocouple module
in the thermocouple mode.
Compatible terminal base unit are:
Module1794-TB21794-TB31794-TB3T
1794-IT8Yes
1
The
1794-TB3T terminal base unit contains connections for cold junction
compensation for use with thermocouple modules.
2
For millivolt inputs only
2
.
Yes
2
1794-TB3T
A
0
–15
B
16–33
C
34–51
.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
CN0 C N1 C N2 CCN3 C N4 C N5 C N6 C N7
C
B
VCJCCJCV
C
Where:
V = 24V dc
C = 24V dc common
CJC = cold junction compensation
1
Yes
N = additional input
Connecting Wiring using a 1794-TB2, -TB3 and -TB3T Terminal
Base Units
= chassis ground
1. Connect the individual signal wiring to numbered terminals on
the 0–15 row (A) on the terminal base unit. Connect the high side
(+) to the even numbered terminals, and the low side (–) to the
odd numbered terminals. See Table 2.A.
2. Connect shield return to the associated terminal on row B, as
shown in Table 2.A.
• On 1794-TB2 and -TB3 bases only: terminate shields to the
associated shield return terminals on row (B).
• On 1794-TB3T bases only: terminate shields to terminals 39
to 46 on row C.
3. Connect +24V dc to terminal 34 on the 34-51 row (C), and 24Vcommon to terminal 16 on the B row.
Important:To reduce susceptibility to noise, power analog modules
and discrete modules from separate power supplies.
ATTENTION: Do not daisy chain power or ground
from the thermocouple terminal base unit to any ac or
!
dc discrete module terminal base unit.
Publication
1794-6.5.7
2–6
Thermocouple
2
2
inals 36, 37, 38 and 47, 48, 49 are cold junction
How to Install Your Thermocouple/mV Input Module
Cold Junction Compensator
Pt.No. 969424-01
ATTENTION: The Thermocouple/mV module does
not receive power from the backplane. +24V dc power
!
must be applied to your module before installation. If
power is not applied, the module position will appear
to the adapter as an empty slot in your chassis.
4. On 1794-TB3T terminal base units: Connect the cold junction
compensation (CJC) wiring to terminals 36, 37 and 38 for inputs
0 through 3, and terminals 47, 48 and 49 for inputs 4 through 7.
Connect the tail of the cold junction compensator to any of the
associated thermocouple input terminals: 0 through 7 for CJC
connected to 36, 37 and 38; or 8 through 15 for CJC connected to
47, 48 and 49. The tail of the cold junction compensator shares
a terminal with an input.
5. If daisy chaining the +24V dc power to the next base unit,
connect a jumper from terminal 51 on this base unit to terminal
34 on the next base unit.
24V dc Common16 thru 3316, 17, 19, 21, 23, 25, 27, 29, 31 and 33
+24V dc power1794-TB2 – 34 and 51; 1794-TB3 – 34 thru 5134, 35, 50 and 51
1
Terminals
39 to 46 are chassis ground.
T
erm
compensator terminals.
1
Publication
1794-6.5.7
How to Install Your Thermocouple/mV Input Module
ATTENTION: The thermocouple/mV modules do
not receive power from the backplane. +24V dc power
!
must be applied to your module before operation. If
power is not applied, the module position will appear
to the adapter as an empty slot in your chassis. If the
adapter does not recognize your module after
installation is completed, cycle power to the adapter.
ATTENTION: Total current draw through the
terminal base unit is limited to 10A. Separate power
!
connections to the terminal base unit may be necessary.
Example of Millivolt Input Wiring to a 1794-TB3
Terminal Base Unit
12 34567891011121314150
0123456789101112131415
1718192021222324252627282930313233
16
3536373839404142434445464748495051
34
2–7
0
–15
16–33
34–51
1794-TB3
+
Millivolt
Source
–
Millivolt input Channel 1
Channel 0 (Terminals 0, 1 and 17)
Example of 3-wire Thermocouple Wiring to a 1794-TB3T
Temperature Terminal Base Unit
12 34567891011121314150
0123456789101112131415
1718192021222324252627282930313233
16
3536373839404142434445464748495051
34
CJCCJC
+
–
1794-TB3T
0
16–33
34–51
Cold
Junction Compensator
Allen-Bradley PN 969424–01
(2 supplied with module)
–15
Channel 0 (Terminals 0, 1 and 39)
Publication
1794-6.5.7
2–8
How to Install Your Thermocouple/mV Input Module
Module Indicators
The thermocouple/mV module has one status indicator that is on
when power is applied to the module. This indicator has 3 different
states:
Allen-Bradley
THERMOCOUPLE INPUT 8 CHANNEL
INPUT
0
+– +–
A = Status Indicator – indicates diagnostic results and configuration status
B = Insertable label for writing individual input designations
ColorStateMeaning
RedOnIndicates a critical fault (diagnostic failure, etc.)
BlinkingIndicates a noncritical fault (such as open sensor, input out of range, etc.)
GreenOnModule is configured and fully operational
BlinkingModule is functional but not configured
OffModule not powered
INPUT 2INPUT 4INPUT 6INPUT 1INPUT 3INPUT 5INPUT 7
+– +–+– +–+–+–
1794–IT8
3
OK
AB
Chapter Summary
In this chapter, you learned how to install your thermocouple/mV
module in an existing programmable controller system and how to
wire to the terminal base units.
Publication
1794-6.5.7
Chapter
3
Chapter Objectives
Block Transfer
Programming
In this chapter, we tell you about:
• block transfer programming
• sample programs for the PLC-3 and PLC-5 processors
Your thermocouple/mV module communicates with the processor
through bidirectional block transfers. This is the sequential operation
of both read and write block transfer instructions.
A configuration block transfer write (BTW) is initiated when the
thermocouple module is first powered up, and subsequently only
when the programmer wants to enable or disable features of the
module. The configuration BTW sets the bits which enable the
programmable features of the module, such as scaling, alarms,
ranges, etc. Block transfer reads are performed to retrieve
information from the module.
Block transfer read (BTR) programming moves status and data from
the module to the processor’s data table. The processor user program
initiates the request to transfer data from the module to the processor.
The transferred words contain module status, channel status and
input data from the module.
ATTENTION: If the thermocouple/mV module is
not powered up before the remote I/O adapter, the
!
The following sample programs are minimum programs; all rungs
and conditioning must be included in your application program. You
can disable BTRs, or add interlocks to prevent writes if desired. Do
not eliminate any storage bits or interlocks included in the sample
programs. If interlocks are removed, the program may not work
properly.
Your program should monitor status bits and block transfer read
activity.
adapter will not recognize the module. Make certain
that the thermocouple/mV module is installed and
powered before or simultaneously with the remote I/O
adapter. If the adapter does not establish
communication with the module, cycle power to the
adapter.
Publication
1794-6.5.7
3–2
Module Programming
Sample programs for
FLEX I/O Analog Modules
The following sample programs show you how to use your analog
module efficiently when operating with a programmable controller.
These programs show you how to:
• configure the module
• read data from the module
These example programs illustrate the minimum programming
required for communication to take place.
PLC-3 Programming
Block transfer instructions with the PLC-3 processor use one binary
file in a data table section for module location and other related data.
This is the block transfer control file. The block transfer data file
stores data that you want transferred to your module (when
programming a block transfer write) or from your module (when
programming a block transfer read). The address of the block
transfer data files are stored in the block transfer control file.
The same block transfer control file is used for both the read and
write instructions for your module. A different block transfer
control file is required for every module.
Program
Action
At power-up in RUN mode, or when the
processor is switched from PROG to RUN,
the user program enables a block transfer
read. Then it initiates a block transfer write
to configure the module.
Thereafter, the program continuously
performs read block transfers.
Note: You must create the data file
for the block transfers before you
enter the block transfer instructions.
The pushbutton allows the user to
manually request a block transfer write.
A sample program segment with block transfer instructions is shown
in Figure 3.1, and described below.
Figure 3.1
PLC-3 Family Sample Program Structure
BTR
BLOCK XFER READ
RACK:
GROUP:
MODULE:
CONTROL:
DATA FILE:
LENGTH:
BTW
BLOCK XFER WRITE
RACK:
GROUP:
MODULE:
CONTROL:
DATA FILE:
LENGTH:
7
0
0
#B3:0
#B4:0
11
7
0
0
#B3:0
#B5:0
3
1
2
Pushbutton
Power-up Bit
B4:10
03
Block Transfer
Read Done Bit
B3:0
15
Block Transfer
rite Done Bit
W
B3:0
05
EN
Done
DN
ER
13
Enable
EN
Done
DN
Error
ER
Enable
12
15
Error
02
05
03
Publication
1794-6.5.7
Module Programming
PLC-5 Programming
The PLC-5 program is very similar to the PLC-3 program with the
following exceptions:
1.Block transfer enable bits are used instead of done bits as the
conditions on each rung.
2.Separate block transfer control files are used for the block
transfer instructions.
Figure 3.2
PLC-5 Family Sample Program Structure
3–3
Program
Action
At power-up in RUN mode, or when the
processor is switched from PROG to RUN,
the user program enables a block transfer
read. Then it initiates a block transfer write
to configure the module.
Thereafter, the program continuously performs read block transfers.
The pushbutton allows the user to
manually request a block transfer write.
BTR Enable Bit
1
2
Power-up Bit
N12:0
15
Pushbutton
N13:10
03
BTW Enable Bit
N12:5
15
BTR
BLOCK
TRANSFER READ
RACK:
GROUP:
MODULE:
CONTROL:
DATA FILE:
LENGTH:
CONTINUOUS:N
BTW
BLOCK
TRANSFER WRITE
RACK:
GROUP:
MODULE:
CONTROL:
DATA FILE:
LENGTH:
CONTINUOUS:N
N12:0
N13:0
N12:5
N13:20
EN
2
1
DN
0
ER
11
EN
2
1
DN
0
ER
3
Publication
1794-6.5.7
3–4
Module Programming
PLC-2 Programming
The 1794 analog I/O modules are not recommended for use with
PLC-2 family programmable controllers due to the number of digits
needed for high resolution.
Chapter Summary
In this chapter, you learned how to program your programmable
controller. You were given sample programs for your PLC-3 and
PLC-5 family processors.
Publication
1794-6.5.7
Chapter
Writing Configuration to and
Reading Status from your
Module with a Remote I/O
Adapter
4
Chapter Objectives
Configuring Your
Thermocouple/mV Module
In this chapter, we tell you about:
• configuring your module’s features
• entering your data
• reading data from your module
• the read block format
Because of the wide variety of possible configurations, you must
configure your module to conform to the specific application that
you have chosen. The module is configured using a group of data
table words that are transferred to the module using a block transfer
write instruction.
The software configurable features available for the thermocouple
module are:
• input/output range selection, including full range and bipolar
• selectable first notch filter
• data reported in
Note: PLC-5 family programmable controllers that use 6200
software (version 5.2 or later) programming tools can take advantage
of the IOCONFIG utility to configure these modules. IOCONFIG
uses menu-based screens for configuration without having to set
individual bits in particular locations. Refer to your 6200 software
literature for details.
o
F, oC, unipolar or bipolar count
Publication
1794-6.5.7 – April 1997
4–2
rocoupl
Writing Configuration to and Reading Status from your Module with a Remote I/O Adapter
Range Selection
Input Scaling
Individual input channels are configurable to operate with the
following sensor types:
Sensor TypeRange
VoltageMillivolt–76.50 to +76.50mV
Thermocouple
Type B300 to 1800oC
Type E–230 to 1000oC
Type J–195 to 1200oC
Type K–230 to 1372oC
Type R–50 to 1768oC
Type S–50 to 1768oC
Type T–195 to 400oC
Type N–270 to 1300oC
Type C0 to 2315oC
Type L–175 to 800oC
You select individual channel ranges using write words 1 and 2 of
the block transfer write instruction.
Scaling lets you report each channel in actual engineering units.
Scaled values are in integer format.
Input TypeRangeScalingMaximum Resolution
Millivolt–76.50 to +76.50mV–7650 to +7650
Type B300 to 1800oC3000 to 180000.1oC
Type E–230 to 1000oC–2300 to 100000.1oC
Type J–195 to 1200oC–1950 to 120000.1oC
Type K–230 to 1372oC–2300 to 137200.1oC
Type R–50 to 1768oC–500 to 176800.1oC
Type S–50 to 1768oC–500 to 176800.1oC
Type T–195 to 400oC–1950 to 40000.1oC
Type N–270 to 1300oC–2700 to 130000.1oC
Type C0 to 2315oC0 to 231500.1oC
Type L–175 to 800oC–1750 to 80000.1oC
Type B572 to 3272oF5720 to 327200.1oF
Type E–382 to 1832oF–3820 to 183200.1oF
Type J–319 to 2192oF–3190 to 219200.1oF
Type K–382 to 2502oF–3820 to 250200.1oF
Type R–58 to 3214oF–580 to 321400.1oF
Type S–58 to 3214oF–580 to 321400.1oF
Type T–319 to 752oF–3190 to 75200.1oF
Type N–450 to 2372oF–4500 to 237200.1oF
Type C32 to 4199oF320 to 419900.1oF
Type L–283 to 1472oF–2830 to 147200.1oF
Note:
In thermocouple mode, scaled number has an implied decimal point 1 digit from the right. For example, if reading is
18000, temperature is 1800.0. In millivolt mode, the implied decimal point is to the left of the last 2 digits. For example, if
reading is 2250, actual reading is 22.50mV
10µV
Publication
1794-6.5.7 – April 1997
Writing Configuration to and Reading Status from your Module with a Remote I/O Adapter
You select input scaling using the designated words of the write
block transfer instruction. Refer to the Bit/Word description for write
word 0, bits 00 and 01.
A hardware filter in the analog to digital converter lets you select a
frequency for the first notch of the filter. Selection of the filter
influences the analog to digital output data rate and changes the
module throughput. Module throughput is a function of the number
of inputs used and the first notch filter. Both of these influence the
time from a thermocouple input to arrival at the backplane.
Throughput in Normal Mode
25Hz
(16-bits)
1
1.16s680600440296248224
50Hz
(16-bits)
60Hz
(16-bits)
System Throughput (in ms and s)
100Hz
(16-bits)
250Hz
(13-bits)
500Hz
(11-bits)
1000Hz
(9-bits)
Publication
1794-6.5.7 – April 1997
4–4
Writing Configuration to and Reading Status from your Module with a Remote I/O Adapter
Reading Data From Your
Module
Mapping Data for the
Analog Modules
Read programming moves status and data from the thermocouple
input module to the processor’s data table. The processor’s user
program initiates the request to transfer data from the
thermocouple/mV input module to the processor.
The following read and write words and bit/word descriptions
describe the information written to and read from the
thermocouple/mV input module. The module uses up to 11 words of
input image and up to 3 words of output image. Each word is
Input Data Channel 3
Input Data Channel 4
Input Data Channel 5
Input Data Channel 6
Input Data Channel 7
Underrange
Calibration Status
Configuration
Thermocouple Type
Thermocouple Type
Thermocouple/mV Input Module (1794-IT8) Read
Decimal
Bit
15141312111009080706050403020100
Octal Bit17161514131211100706050403020100
Read Word 0Reserved
1Channel 0 Input Data
2Channel 1 Input Data
3Channel 2 Input Data
4Channel 3 Input Data
5Channel 4 Input Data
6Channel 5 Input Data
7Channel 6 Input Data
8Channel 7 Input Data
Publication
1794-6.5.7 – April 1997
Writing Configuration to and Reading Status from your Module with a Remote I/O Adapter
4–5
Bit
9Overrange BitsUnderrange Bits
Bad
Cal
1000000
Cal
Done
Cal
Range
0Diagnostic Status
PwrUpBad
Thermocouple/mV Input Module (1794-IT8) Write
Dec.
Bit
15141312111009080706050403020100
Octal Bit 17161514131211100706050403020100
Cal
Write Word 08-Bit Calibration Mask
1Thermocouple 3 TypeThermocouple 2 TypeThermocouple 1 TypeThermocouple 0 Type
2Thermocouple 7 TypeThermocouple 6 TypeThermocouple 5 TypeThermocouple 4 Type
Where:FDF
= fixed digital filter bit
Clk
Cal hi
Cal lo
Filter CutoffFDFData Type
Word/Bit Descriptions for the 1794-IT8 Thermocouple/mV
Input Module
Decimal
Word
Bit
(Octal Bit)
Description
Structure
CJC
over
00010203040506070809101112131415Decimal
00010203040506071011121314151617Octal Bit
CJC
Under
Read Word 000–15 (00–17) Reserved
Read Word 100–15 (00–17) Channel 0 Input data
Read Word 200–15 (00–17) Channel 1 Input data
Read Word 300–15 (00–17) Channel 2 Input data
Read Word 400–15 (00–17) Channel 3 Input data
Read Word 500–15 (00–17) Channel 4 Input data
Read Word 600–15 (00–17) Channel 5 Input data
Read Word 700–15 (00–17) Channel 6 Input data
Read Word 800–15 (00–17) Channel 7 Input data
Read Word 9
Read Word 10
00–07 (00–07) Underrange bits – these bits are set if the input signal is below the input channel’s minimum range.
08–15 (10–17) Overrange bits – these bits are set if 1), the input signal is above the input channel’s maximum range,
or 2), an open detector is detected.
00 (00)Cold Junction sensor underrange bit. – this bit is set if the cold junction temperature is below 0oC.
01 (01)Cold Junction sensor overrange bit. – this bit is set if the cold junction temperature is above 70oC.
02 (02)Bad Structure – this bit is set if an invalid thermocouple type is selected.
03 (03)Powerup bit – this bit is set (1) until configuration data is received by the module.
04–06 (04–06) Critical Error bits – If these bits are anything other than all zeroes, return the module to the factory for
repair
07 (07)Unused – set to 0
08 (10)Calibration Range bit – set to 1 if a reference signal is out of range during calibration
09 (11)Calibration Done bit – set to 1 after an initiated calibration cycle is complete.
10 (12)Calibration Bad bit – set to 1 if the channel has not had a valid calibration.
11–15 (13–17) Unused – set to 0
Publication
1794-6.5.7 – April 1997
4–6
Word
Writing Configuration to and Reading Status from your Module with a Remote I/O Adapter
Decimal
Bit
(Octal Bit)
Description
Write Word 0
00–01 (00–01) Module Data Type
Bit0100Definition
00oC (default)
01oF
10Bipolar counts scaled between –32768 and +32767
11Unipolar counts scaled between 0 and 65535
Bit 02 (02)Fixed Digital Filter – When this bit is set (1), a software digital filter is enabled. This filter settles to
100% of a Full Scale step input in 60 times the selected first notch filter time shown on page 4–3.
1111000hZ
06 (06)Calibration High/Low bit – This bit is set during gain calibration; reset during offset calibration.
07 (07)Calibration clock – this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate
calibration.
08–15 (10–17) Calibration mask – The channel, or channels, to be calibrated will have the correct mask bit set. Bit 8
corresponds to channel 0, bit 9 to channel 1, and so on.
Publication
1794-6.5.7 – April 1997
Word
Writing Configuration to and Reading Status from your Module with a Remote I/O Adapter
Decimal
Bit
(Octal Bit)
Description
4–7
Write Word 1
Write Word 2
00–03 (00–03) Channel 0 Thermocouple Type
Bit03020100Thermocouple Type – Range
0000Millivolts (default)
0001B 300 to 1800oC (572 to 3272oF)
0010E –230 to 1000oC (–382 to 1832oF)
0011J–195 to 1200oC (–319 to 2192oF)
0100K –230 to 1372oC (–382 to 2502oF)
0101R –50 to 1768oC (–58 to 3214oF)
0110S –50 to 1768oC (–58 to 3214oF)
0111T –195 to 400oC (–319 to 752oF)
1000C 0 to 2315oC(32 to 4199oF)
1001N –270 to 1300oC (–450 to 2372oF)
1010L -175 to 800oC(-283 to 1472oF)
1011Reserved
1100Module reports cold junction temperature for channels 00–03
1101Module reports cold junction temperature for channels 04–07
1110Reserved
1111No sensor connected (do not scan)
04–07 (04–07) Channel 1 Thermocouple Type (see bits 00–03)
08–11 (10–13) Channel 2 Thermocouple Type (see bits 00–03)
12–15 (14–17) Channel 3 Thermocouple Type (see bits 00–03)
00–03 (00–03) Channel 4 Thermocouple Type (see write word 1, bits 00–03)
04–07 (04–07) Channel 5 Thermocouple Type (see write word 1, bits 00–03)
08–11 (10–13) Channel 6 Thermocouple Type (see write word 1, bits 00–03)
12–15 (14–17) Channel 7 Thermocouple Type (see write word 1, bits 00–03)
Chapter Summary
In this chapter, you learned how to configure your module’s features
and enter your data.
Publication
1794-6.5.7 – April 1997
4–8
Writing Configuration to and Reading Status from your Module with a Remote I/O Adapter
Publication
1794-6.5.7 – April 1997
Chapter
Chapter
ectives
Polled I
Structure
How Communication Takes
Place and I/O Image Table
Mapping with the DeviceNet
Adapter
5
Obj
About DeviceNet Manager
More
/O
In this chapter, we tell you about:
• DeviceNetManager software
• I/O structure
• image table mapping
• factory defaults
DeviceNetManager software is a software tool used to configure
your Flex I/O DeviceNet adapter and its related modules. This
software tool can be connected to the adapter via the DeviceNet
network.
You must know and understand how DeviceNet Manager works in
order to add a device to the network. Refer to the DeviceNetManager
Software User Manual, publication 1787-6.5.3, and the DeviceNet
Adapter Module User Manual, publication 1794-6.5.5.
Output data is received by the adapter in the order of the installed
I/O modules. The Output data for Slot 0 is received first, followed
by the Output data for Slot 1, and so on up to slot 7.
The first word of input data sent by the adapter is the Adapter Status
Word. This is followed by the input data from each slot, in the order
of the installed I/O modules. The Input data from Slot 0 is first after
the status word, followed by Input data from Slot 2, and so on up to
slot 7.
Network
Network WRITE
READ
DeviceNet Adapter
Read Data
Adapter
Status
Slot 0 Input Data
Slot 1 Input Data
...
Slot 7 Input Data
Write Data
Slot 0 Output Data
Slot 1 Output Data
...
Slot 7 Output Data
...
...
Read
Write
I/O Module
Slot 0
I/O Module
Slot 1
Publication
I/O Module
...
1794-6.5.7 – April 1997
Slot 7
5–2
ault
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Adapter Input Status Word
The input status word consists of:
• I/O module fault bits – 1 status bit for each slot
• node address changed – 1 bit
• I/O status – 1 bit
I/O Module Fault Bits
15Bit:01234567810 through 15
9
Not Used
I/O State Bit
Node Address Changed Bit
Slot 7
Slot 6
Slot 5
Slot 4
The adapter input status word bit descriptions are shown in the
following table.
Bit DescriptionBitExplanation
0This bit is set (1) when an error is detected in slot position 0.
1This bit is set (1) when an error is detected in slot position 1.
2This bit is set (1) when an error is detected in slot position 2.
I/O Module F
Node Address Changed8
I/O State9
3This bit is set (1) when an error is detected in slot position 3.
4This bit is set (1) when an error is detected in slot position 4.
5This bit is set (1) when an error is detected in slot position 5.
6This bit is set (1) when an error is detected in slot position 6.
7This bit is set (1) when an error is detected in slot position 7.
This bit is set (1) when the node address switch setting has been
changed since power up.
Bit = 0 – idle
Bit = 1 – run
10 thru 15Not used – sent as zeroes.
Slot 3
Slot 2
Slot 1
Slot 0
Publication
Possible causes for an I/O Module Fault are:
• transmission errors on the Flex I/O backplane
• a failed module
• a module removed from its terminal base
• incorrect module inserted in a slot position
• the slot is empty
The node address changed bit is set when the node address switch
setting has been changed since power up. The new node address does
not take affect until the adapter has been powered down and then
powered back up.
1794-6.5.7 – April 1997
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
5–3
System Throughput
SEE
PAGE 4–3
Mapping Data into the
Image Table
System throughput, from analog input to backplane, is a function of:
• the configured A/D filter first notch frequency
• the number of channels actually configured for connection to a
specific sensor
The A/D converter which converts channel 0 through 7 analog data
to a digital word provides a programmable first notch filter. You can
set the position of the first notch of this filter during module
configuration. The selection influences the A/D output data rate, thus
affecting system throughput.
The number of channels included in each input scan also affects
system throughput.
FLEX I/O thermocouple module data table mapping is shown below.
Input Data Channel 3
Input Data Channel 4
Input Data Channel 5
Input Data Channel 6
Input Data Channel 7
Underrange
Calibration Status
Configuration
Thermocouple Type
Thermocouple Type
Thermocouple/mV Input Module (1794-IT8) Read
Dec.
Bit
1514131211100908070605 0403020100
Octal Bit 1716151413121110070605 0403020100
Read Word 1Reserved
Read Word 2Channel 0 Input Data
Read Word 3Channel 1 Input Data
Read Word 4Channel 2 Input Data
Read Word 5Channel 3 Input Data
Read Word 6Channel 4 Input Data
Publication
1794-6.5.7 – April 1997
5–4
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Bit
Read Word 7Channel 5 Input Data
Read Word 8Channel 6 Input Data
Read Word 9Channel 7 Input Data
Read Word 10Overrange BitsUnderrange Bits
Bad
Read Word 1100000
Cal
Cal
Done
Cal
Range
0Diagnostics
Pwr
Up
Bad
Structure
Thermocouple/mV Input Module (1794-IT8) Write
Dec.
Bit
15141312111009080706050403020100
Octal Bit 17161514131211100706050403020100
Cal
Write Word 18-Bit Calibration Mask
Write Word 2Thermocouple 3 TypeThermocouple 2 TypeThermocouple 1 TypeThermocouple 0 Type
Write Word 3Thermocouple 7 TypeThermocouple 6 TypeThermocouple 5 TypeThermocouple 4 Type
Where:FDF
= fixed digital filter bit
Clk
Cal hi
Cal lo
Filter CutoffFDFData Type
Word/Bit Descriptions for the 1794-IT8 Thermocouple/mV
Input Module
CJC
over
00010203040506070809101112131415Dec.
00010203040506071011121314151617Octal Bit
CJC
Under
Decimal
Word
Read Word 100–15 (00–17) Reserved
Read Word 200–15 (00–17) Channel 0 Input data
Read Word 300–15 (00–17) Channel 1 Input data
Read Word 400–15 (00–17) Channel 2 Input data
Read Word 500–15 (00–17) Channel 3 Input data
Read Word 600–15 (00–17) Channel 4 Input data
Read Word 700–15 (00–17) Channel 5 Input data
Read Word 800–15 (00–17) Channel 6 Input data
Read Word 900–15 (00–17) Channel 7 Input data
Read Word 10
Read Word 11
00–07 (00–07) Underrange bits – these bits are set if the input signal is below the input channel’s minimum range.
08–15 (10–17) Overrange bits – these bits are set if 1), the input signal is above the input channel’s maximum range,
Bit
(Octal Bit)
or 2), an open detector is detected.
00 (00)Cold Junction sensor underrange bit. – this bit is set if the cold junction temperature is below 0oC.
01 (01)Cold Junction sensor overrange bit. – this bit is set if the cold junction temperature is above 70oC.
02 (02)Bad Structure – this bit is set if there is an invalid thermocouple type selected.
Description
Publication
1794-6.5.7 – April 1997
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
continu
Decimal
Word
Bit
(Octal Bit)
Description
5–5
Read Word 11
ed
Write Word 1
03 (03)Powerup bit – this bit is set (1) until configuration data is received by the module.
04–06 (04–06)
Critical Fault bits – If these bits are anything other than zero, return the module to the factory for repair.
07 (07)Unused – set to 0
08 (10)Calibration Range bit – set to 1 if a reference signal is out of range during calibration
09 (11)Calibration Done bit – set to 1 after an initiated calibration cycle is complete.
10 (12)Calibration Bad bit – set to 1 if the channel has not had a valid calibration.
11–15 (13–17) Unused – set to 0
00–01 (00–01) Module Data Type
Bit0100Definition
00oC (default)
01oF
10Bipolar counts scaled between –32768 and +32767
11Unipolar counts scaled between 0 and 65535
Bit 02 (02)Fixed Digital Filter – When this bit is set (1), a software digital filter is enabled. This filter settles to
100% of a Full Scale step input in 60 times the selected first notch filter time shown on page 4–3.
1111000hZ
06 (06)Calibration High/Low bit – This bit is set during gain calibration; reset during offset calibration.
07 (07)Calibration clock – this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate
calibration.
08–15 (10–17) Calibration mask – The channel, or channels, to be calibrated will have the correct mask bit set. Bit 8
corresponds to channel 0, bit 9 to channel 1, and so on.
Publication
1794-6.5.7 – April 1997
5–6
Word
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Decimal
Bit
(Octal Bit)
Description
Write Word 2
Write Word 3
00–03 (00–03) Channel 0 Thermocouple Type
Bit03020100Thermocouple Type – Range
0000Millivolts (default)
0001B 300 to 1800oC (572 to 3272oF)
0010E –230 to 1000oC (–382 to 1832oF)
0011J–195 to 1200oC (–319 to 2192oF)
0100K –230 to 1372oC (–382 to 2502oF)
0101R –50 to 1768oC (–58 to 3214oF)
0110S –50 to 1768oC (–58 to 3214oF)
0111T –195 to 400oC (–319 to 752oF)
1000C 0 to 2315oC(32 to 4199oF)
1001N –270 to 1300oC (–450 to 2372oF)
1010L -175 to 800oC(-283 to 1472oF)
1011Reserved
1100Module reports cold junction temperature for channels 00–03
1101Module reports cold junction temperature for channels 04–07
1110Reserved
1111No sensor connected (do not scan)
04–07 (04–07) Channel 1 Thermocouple Type (see bits 00–03)
08–11 (10–13) Channel 2 Thermocouple Type (see bits 00–03)
12–15 (14–17) Channel 3 Thermocouple Type (see bits 00–03)
00–03 (00–03) Channel 4 Thermocouple Type (see write word 2, bits 00–03)
04–07 (04–07) Channel 5 Thermocouple Type (see write word 2, bits 00–03)
08–11 (10–13) Channel 6 Thermocouple Type (see write word 2, bits 00–03)
12–15 (14–17) Channel 7 Thermocouple Type (see write word 2, bits 00–03)
Publication
1794-6.5.7 – April 1997
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
5–7
Defaults
Each I/O module has default values associated with it. At default,
each module will generate inputs/status and expect
outputs/configuration.
Module Defaults for:Factory DefaultsReal Time Size
Catalog
Number
1794-IT88 Thermocouple Input114100
Description
Input
Default
Output
Default
Input
Default
Output
Default
Factory defaults are the values assigned by the adapter when you:
• first power up the system, and
• no previous stored settings have been applied.
For analog modules, the defaults reflect the actual number of input
words/output words. For example, for the 8 thermocouple input
analog module, you have 11 input words, and 4 output words.
You can change the I/O data size for a module by reducing the
number of words mapped into the adapter module, as shown in “real
time sizes.”
Real time sizes are the settings that provide optimal real time data to
the adapter module.
More
Analog modules have 15 words assigned to them. This is divided
into input words/output words. You can reduce the I/O data size to
fewer words to increase data transfer over the backplane. For
example, an 8 thermocouple input module has 11 words input/4
words output with factory default. You can reduce the write words to
0, thus eliminating the configuration setting and unused words. And
you can reduce the read words to 10 by eliminating the calibration
status words.
For information on using DeviceNetManager software to configure
your adapter, refer to the DeviceNetManager Software User Manual,
publication 1787-6.5.3.
Publication
1794-6.5.7 – April 1997
5–8
How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter
Publication
1794-6.5.7 – April 1997
Chapter
Calibrating Your Module
6
Chapter Objective
General Information
In this chapter we tell you:
• what tools are needed to calibrate
• how to calibrate out lead wire resistance
• calibrate your module manually
• calibrate your module using DeviceNetManager software
Your module is shipped to you already calibrated. If a calibration
check is required,follow the procedure below.
Perform module calibration periodically, based on your application.
Module calibration may also be required to remove module error due
to aging of components
In addition, calibration may be required to eliminate long lead wire
resistance to open circuit detection current. See “Error Due to Open
Circuit Current Through Loop Resistance” in Appendix A.
Calibration can be accomplished using any of the following methods:
• manual calibration, as described below.
• 6200 I/O CONFIGURATION software (version 5.2 or later)–
refer to your 6200 software publications for procedures for
calibrating.
• DeviceNetManager Software – refer to your DeviceNetManager
software documentation for the DeviceNet Adapter Module, Cat.
No. 1794-ADN. Some portion of this calibration is included here
for use by personnel proficient with DeviceNet Adapter
configuration software.
Important:You can use a 1794-TB2 or -TB3 terminal base unit if
you are using the thermocouple/mV module in the
millivolt mode only. You must use a 1794-TB3T
terminal base unit for all thermocouple uses.
Publication
1794-6.5.7 – April 1997
6–2
or
Calibrating Your Module
Tools and Equipment
Tool or EquipmentDescription
Precision Voltage Source
Thermocouple Simulator
and Calibration source
Industrial Terminal and
Interconnect Cable
Removing Lead Wire or
Thermocouple Extension
Wire Resistance
In order to calibrate your thermocouple input module you will need
the following tools and equipment:
0–100mV, 1µV resolution
Programming terminal for A–B family processors
Analogic 3100, Data Precision 8200
or equivalent
Thermocouple Simulator/Calibrator
Model 1120
The thermocouple/mV module has open circuit detection. This is
accomplished by a 1µA current source in the module. This current
flowing through the lead wire or thermocouple extension wire
generates an error or offset voltage in the reading. Use the “Error
Due to Open Circuit Current Through Loop Resistance” in appendix
A to determine if the magnitude of the error is acceptable.
Calibrate this error out as follows:
Ectron Corporation
8159 Engineer Road
San Diego, CA 92111-1980
1
2
123456789 10 11 12 13 14 150
01234567891011 12131415
171819202122232425 262728 29303132 33
16
353637383940414243 444546 47484950 51
34
1794-TB3, -TB3T
Ω
123456789 10 11 12 13 14 150
01234567891011 12131415
171819202122232425 262728 29303132 33
16
353637383940414243 444546 47484950 51
34
Disconnect the lead wires at the terminal base unit.
a.
b.
Measure total loop resistance of both lead/extension wires and thermocouple.
c.
If using a sensor other than a thermocouple, disconnect the lead wires at the
sensor and tie together for this measurement. Reconnect after measurement.
d.
After measuring, remove ohmmeter
.
1794-TB3, -TB3T
a.
Decade Box
Voltage Source
Set decade box to value determined in step 1, and connect in series with a preci
sion voltage source.
b. Connect
c.
Perform an of
to the input terminals of the particular channel you are calibrating.
fset and gain calibration as outlined later in this chapter
0
–15
16–33
34–51
0
–15
16–33
34–51
A
B
C
Thermocouple
or
Sensor
A
B
C
-
Thermocouple
.
or
Sensor
Publication
Disconnected
1794-6.5.7 – April 1997
3
123456789 10 11 12 13 14 150
01234567891011 12131415
171819202122232425 262728 29303132 33
16
353637383940414243 444546 47484950 51
34
1794-TB3, -TB3T
a.
Remove the decade box and voltage source.
b.
Reconnect the lead wires to the input terminals for this channel.
c.
Repeat this procedure for the remaining channels.
Calibrating Your Module
0
–15
A
16–33
B
34–51
C
6–3
Thermocouple
or
Sensor
Manually Calibrating your
Thermocouple/mV Input
Module
You must calibrate the module in a FLEX I/O system. The module
must communicate with the processor and a programming terminal.
You can calibrate input channels in any order, or all at once.
Before calibrating your module, you must enter ladder logic into the
processor memory, so that you can initiate BTWs to the module, and
read inputs from the module.
Important:In order to allow the internal module temperature to
stabilize, energize the module for at least 40 minutes
before calibrating.
Module calibration consists of:
• Applying a reference to the desired input(s).
• Sending a message to the module indicating which inputs to read
and what calibration step is being performed (offset).
The module stores this input data.
• Applying a second reference signal to the module, and sending a
second message indicating which inputs to read and what
calibration step is being performed (gain).
The module computes new calibration values for the inputs.
Once the calibration is complete, the module reports back status
information about the procedure.
The following flow chart shows the procedure for calibration
Important:Perform the offset calibration procedure first, then the
gain calibration procedure.
Publication
1794-6.5.7 – April 1997
6–4
Calibrating Your Module
Apply
reference signal for of
calibration to each channel to
be calibrated.
Flow Chart for Calibration Procedure
fset
Apply reference signal for gain
calibration to each channel to
be calibrated.
Exit
Set corresponding bits in the
calibration mask and set cal
Hi/Lo = 0
BTW
Set cal–clk =1
BTW
BTR
NO
Cal–done = 1
?
YES
NO
Bad–cal = 0
Cal–range = 0
?
YES
Set cal–clk =0
Exit
Retain corresponding bits in
the calibration mask and set
cal Hi/Lo = 1
BTW
Set cal–clk =1
BTW
BTR
NO
Cal–done = 1
?
YES
NO
Bad–cal = 0
Cal–range = 0
?
YES
Set cal–clk =0
and
cal hi/lo = 0
Legend:
Publication
NO
= block transfer write
BTW
BTR
= block transfer read
1794-6.5.7 – April 1997
BTW
BTR
Cal–done = 0
?
YES
BTW
BTR
NO
Cal–done = 0
?
YES
Clear corresponding bits in
the calibration mask
BTW
Using
Thermocouple
a Precision V
Precision Voltage Source
Precision Voltage Source
oltage Source
Calibrating Your Module
Calibration Setups
123456789 10 11 12 13 14 150
0123456789101112131415
171819202122232425 262728 29303132 33
16
353637383940414243 4445464748495051
34
These terminals not on 1794-TB2
1794-TB2,
Note: Use 1794-TB2 and -TB3 terminal base units for millivolt inputs only.
123456789 10 11 12 13 14 150
0123456789101112131415
171819202122232425 2627282930313233
16
353637383940414243 4445464748495051
34
CJCCJC
1794-TB3T
-TB3
CJC
0 –15
16–33
34–51
0 –15
16–33
34–51
6–5
A
B
C
A
B
C
Note 2: CJC not required if using thermocouple for resistance only.
Wiring Connections for the Thermocouple Module
1794-TB2, -TB3 Terminal Base Units1794-TB3T Terminal Base Unit
24V dc Common16 thru 3316, 17, 19, 21, 23, 25, 27, 29, 31 and 33
+24V dc power1794-TB2 – 34 and 51; 1794-TB3 – 34 thru 5134, 35, 50 and 51
1
Terminals 39 to 46 are chassis ground.
2
Terminals 36, 37, 38 and 47, 48, 49 are cold
junction compensator connections.
2
Shield
Return
1
Publication
1794-6.5.7 – April 1997
6–6
Calibrating Your Module
Read/Write Words for Calibration
Dec.
Bit
15141312111009080706050403020100
Octal Bit 17161514131211100706050403020100
Bad
Cal
Read Word 1000000
Write Word 08-Bit Calibration Mask
Cal
Done
Cal
Range
0Diagnostic Status
Cal
Clk
Cal hi
Cal lo
Filter CutoffFDFData Type
PwrUpBad
Struct
Offset Calibration
Inputs can be calibrated one at a time or all at once. To calibrate the
offsets for all inputs at once, proceed as follows:
1. Apply power to the module for 40 minutes before calibrating.
2. Connect 0.000V across each input channel. Connect all high
signal terminals together and attach to the positive lead from the
precision voltage source. Connect all low signal terminals
together and attach to the negative lead.
CJC
over
CJC
Under
3. After the connections stabilize, use a block transfer write to set
the bit(s) in the calibration mask that correspond to the channel(s)
you want to calibrate to 1. (Bits 08 through 15 in write word 0.)
4. Send another block transfer write to set the cal-clk bit (07 in write
word 0) to 1.
5. Monitor the cal-done bit (09 in read word 10). If the calibration is
successful, the cal-done bit will be set to 1. Verify that the bad-cal
bit (10 in read word 10) and the cal-range bit (08 in read word 10)
are not set (0).
6. Send another block transfer write to set the cal-clk bit (07 in write
word 0) to 0.
7. Monitor the cal-done bit (09 in read word 10). The cal-done bit
will be reset to 0.
8. If the calibration is successful, proceed to the gain calibration.
Publication
1794-6.5.7 – April 1997
Calibrating Your Module
6–7
Gain Calibration
After completing the offset calibration, proceed with the gain
calibration.
1. Apply power to the module for 40 minutes before calibrating.
2. Connect 75.000mV across each input channel. Connect all high
signal terminals together and attach to the positive lead from the
precision voltage source. Connect all low signal terminals
together and attach to the negative lead.
3. After the connections stabilize, send a block transfer write to the
module to set the bit in the calibration mask that corresponds to
the channel to be calibrated to 1, and the hi/lo bit (bit 06 in write
word 0) to 1. (Set bits 08 through 15 in write word 0 if calibrating
all inputs at one time.)
4. Send another block transfer write to set the cal-clk bit (07 in write
word 0) to 1.
5. Monitor the cal-done bit (09 in read word 10). If the calibration is
successful, the cal-done bit will be set to 1. Verify that the bad-cal
bit (10 in read word 10) and the cal-range bit (08 in read word 10)
are not set (0).
6. Send another BTW to set the cal-clk bit (07 in write word 0) to 0.
7. Send another BTW to set the hi/lo bit (bit 06 in write word 0)
to 0.
8. Monitor the cal-done bit (09 in read word 10). The cal-done bit
will be reset to 0.
9. If individually calibrating channels, repeat steps 1 through 7 for
offset calibration on any additonal channels you want to calibrate.
10.Send a block transfer write to the module to clear all calibration
mask bits to 0.
Publication
1794-6.5.7 – April 1997
6–8
Calibrating Your Module
Calibrating Your
Thermocouple/mV Module
using DeviceNetManager
Software
(Cat. No. 1787-MGR)
The following procedure assumes that you are using
DeviceNetManager software (cat. no. 1787-MGR) and have the
thermocouple/mV module installed in a working system.
Offset Calibration
Inputs can be calibrated one at a time or all at once. To calibrate the
offsets for all inputs at once, proceed as follows:
1. Connect 0.000V across each input channel. Connect all high
signal terminals together and attach to the positive lead from the
precision voltage source. Connect all low signal terminals
together and attach to the negative lead.
2. Apply power to the module for 45 minutes before calibrating.
3. Click on Configure for the slot containing the thermocouple
module.
Publication
The following screen appears:
1794-6.5.7 – April 1997
Calibrating Your Module
4. Click on to get to the calibration screen.
5. Click on the channels you want to calibrate.
6–9
6. Click on the radio button
for offset calibration. Then click on
.
7. When calibration is complete, a notification will appear on the
calibration status line.
Publication
1794-6.5.7 – April 1997
6–10
Calibrating Your Module
Gain Calibration
Make sure that you have calibrated the offset for this channel before
calibrating the gain.
1. Connect 75.000mV across each input channel. Connect all high
signal terminals together and attach to the positive lead from the
precision voltage source. Connect all low signal terminals
together and attach to the negative lead.
2. Click on the channels you want to calibrate.
3. Click on the radio button for gain calibration. Then click on
.
4. When calibration is complete, a notification will appear on the
calibration status line.
Publication
1794-6.5.7 – April 1997
6–1
The button populates the screen with the actual
values appearing at the inputs. Note that there is an implied decimal
point to the left of the last 2 digits.. For example, channel 0 data
value reads 7500. The actual reading is 75.00mV.
1Calibrating Your Module
After both offset and gain calibrations are successful, click on
.
You will be returned to the module configuration screen. Either save
to the device (adapter), or save to a file by clicking on the
appropriate button.
Publication
1794-6.5.7 – April 1997
6–12
Calibrating Your Module
If you attempt to close without saving your configuration
information by clicking on the
Number of Inputs8 Channels
Module LocationCat. No. 1794-TB2, -TB3 and -TB3T Terminal Base Units
Nominal Input Voltage Ranges+76.5mV
Supported Thermocouple TypesType B: 300 to 1800oC(572 to 3272oF)
Type C: 0 to 2315
Type E: –230 to 1000oC(–382 to 1832oF)
Type J: –195 to 1200
Type K: –230 to 1372oC(–382 to 2502oF)
Type N: –270 to 1300
Type R: –50 to 1768
Type S: –50 to 1768oC(–58 to 3214oF)
Type T: –195 to 400
Type L: –175 to 800oC(–283 to 1472oF)
Resolution16 bits (2.384 microvolts typical)
Accuracy with fixed digital filter
(at 24oC (+0.5oC))
Accuracy without fixed digital filter
o
C (+0.5oC))
(at 24
Data Format16-bit 2’s complement or offset binary (unipolar)
Normal Mode Noise Rejection–60db @ 60Hz
Common Mode Rejection–115db @ 60Hz; –100db @ 50Hz
Common Mode Input Range+10V
Channel to Channel Isolation
System Throughput325ms (1 channel scanned), programmable to 28ms
Settling Time to 100% of final valueAvailable at system throughput rate
Open Circuit DetectionOut of range reading (upscale)
Open Thermocouple Detection TimeAvailable at system throughput rate
Overvoltage Capability35V dc, 25V ac continuous @ 25oC
Channel Bandwidth0 to 2.62Hz (–3db) default
RFI ImmunityError of less than 1% of range at 10V/M
Input Offset Drift with Temperature+6 microvolts/oC maximum
Gain Drift with Temperature10ppm/oC maximum
Overall Drift with Temperature50ppm/oC of span (maximum)
Cold Junction Compensation Range0 to 70oC
Cold Junction CompensatorA-B Part Number 969424–01
Indicators1 red/green power status indicator
Flexbus Current20mA
Power Dissipation3W maximum @ 31.2V dc
Thermal DissipationMaximum 10.2 BTU/hr @ 31.2V dc
Keyswitch Position3
General Specifications
External dc Power
CablingThermocouples inputs
DimensionsInches
Environmental Conditions
Agency Certification
(when product or packaging is marked)
Installation InstructionsPublication 1794-5.21
1
Specifications based on A/D filter first notch frequency of 10Hz
2
3
Supply Voltage
Voltage Range
24V dc nominal
19.2 to 31.2V dc (includes 5% ac ripple)
19.2V dc for ambient temperatures less than 55
24V dc for ambient temperatures less than 55
31.2V dc for ambient temperatures less than 40
See derating curve.
Supply Current
150mA @ 24V dc
Appropriate shielded thermocouple extension wire
Millivolt inputs
Belden 8761
1.8H x 3.7W x 2.1D
(Millimeters)
Operational Temperature
Storage Temperature
Relative Humidity
(45.7 x 94.0 x 53.3)
0 to 55oC (32 to 131oF) See derating curve.
–40 to 85
5 to 95% noncondensing (operating)
5 to 80% noncondensing (nonoperating)
ShockOperating
Non-operating
Vibration
30 g peak acceleration, 11(+
50 g peak acceleration, 11(+
Tested 5 g @ 10–500Hz per IEC 68-2-6
• CSA certified
• CSA Class I, Division 2
Groups A, B, C, D certified
• UL listed
• CE marked for all applicable directives
.
Use 1794-TB2 or -TB3 terminal base unit for millivolt inputs only
thermocouple inputs.
Refer to the thermocouple manufacturer for the correct extension wire.
. Y
ou must use a 1794-TB3T terminal base unit when using
o
C (–40 to 185oF)
1)ms pulse width
1)ms pulse width
o
C
o
C
o
C
3
Publication
1794-6.5.7 – March 1997
Specifications
A–3
Derating Curve
The area within the curve represents the safe
operating range for the module under various
conditions of user supplied 24V dc supply
voltages and ambient temperatures.
= Safe operating area
User Applied 24V dc Supply versus Ambient Temperature
31.2
24.0
User Applied 24V dc Supply
19.2
Resolution Curves for Thermocouples
o
C40
25
Ambient Temperature
o
C50oC55oC
102.4
184.3
89.60
161.3
76.80
138.2
64.00
115.2
51.20
92.16
38.40
69.12
25.60
46.08
12.80
23.04
Resolution
25.60
46.08
22.40
40.32
19.20
34.56
16.00
28.80
12.80
23.04
9.60
17.28
6.40
11.52
3.20
5.76
C
F
6.40
11.52
5.60
10.08
4.80
8.64
4.00
7.20
3.20
5.76
2.40
4.32
1.60
2.88
0.80
1.44
Type B Thermocouple
10–100Hz250Hz500Hz1000Hz
0.80
1.44
0.70
1.26
0.60
1.08
0.50
0.90
0.40
0.72
0.30
0.54
0.20
0.36
0.10
0.18
0
–300
–508
–150
–238
32
0
150
302
300
572
450
842
600
1112
Temperature
750
1382
C
F
900
1652
1050
1922
1200
2192
1350
2462
1500
2732
1650
3002
1800
3272
T
emplate revised June 23, 1995
Publication
1794-6.5.7 – March 1997
A–4
Specifications
Type E Thermocouple
64.00
115.2
51.20
92.16
38.40
69.12
25.60
46.08
12.80
23.04
Resolution
16.00
28.80
12.80
23.04
9.60
17.28
12.80
11.52
6.40
5.76
C
F
4.00
7.20
3.20
5.76
2.40
4.32
1.60
2.88
0.80
1.44
10–100Hz250Hz500Hz1000Hz
0.50
0.90
0.40
0.72
0.30
0.54
0.20
0.36
0.10
0.18
0
–300
–508
–150
–238
32
150
0
302
300
572
Temperature
450
842
600
1112
C
F
750
1382
900
1652
1050
1922
1200
2192
Type C Thermocouple
32.00
57.60
25.60
46.08
19.20
34.56
12.80
23.04
6.400
11.52
Resolution
8.00
14.4
6.40
11.52
4.80
8.64
3.20
5.76
1.60
2.88
C
F
2.00
3.60
1.60
2.88
1.20
2.16
0.80
1.44
0.40
0.72
10–100Hz250Hz500Hz1000Hz
0.25
0.45
0.20
0.36
0.15
0.27
0.10
0.18
0.05
0.09
0
–300
–508
0
32
300
572
600
1112
900
1652
Temperature
1200
2192
C
F
1500
2732
1800
3272
2100
3812
2400
4352
Publication
1794-6.5.7 – March 1997
Type J Thermocouple
Specifications
A–5
17.92
32.25
15.36
27.65
12.80
23.04
10.24
18.43
7.680
13.82
5.120
9.216
2.560
4.608
Resolution
4.480
8.064
3.840
6.912
3.200
5.760
2.560
4.608
1.920
3.456
1.280
2.304
0.640
1.152
C
F
1.120
2.016
0.960
1.728
0.800
1.440
0.640
1.152
0.480
0.864
0.320
0.576
0.160
0.288
10–100Hz250Hz500Hz1000Hz
0.140
0.252
0.120
0.216
0.100
0.180
0.080
0.144
0.060
0.108
0.040
0.072
0.020
0.036
0
–300
–508
–150
–238
32
150
0
302
Type K Thermocouple
300
572
Temperature
450
842
C
F
600
1112
750
1382
900
1652
1050
1922
1200
2192
Resolution
128.0
230.4
102.4
184.3
76.80
138.2
51.20
92.16
25.60
46.08
32.00
57.60
25.60
46.08
19.20
34.56
12.80
23.04
6.400
11.52
C
F
8.000
14.40
6.400
11.52
4.800
8.640
3.200
5.760
1.600
2.880
10–100Hz250Hz500Hz1000Hz
1.000
1.800
0.800
1.440
0.600
1.080
0.400
0.720
0.200
0.360
0
–300
–508
–150
–238
32
900
0
150
302
300
572
450
842
Temperature
600
1112
750
1382
C
F
1652
1050
1922
1200
2192
1350
2462
1500
2732
T
emplate revised June 23, 1995
Publication
1794-6.5.7 – March 1997
A–6
Specifications
Type R Thermocouple
102.4
184.3
76.80
138.2
51.20
92.16
25.60
46.08
Resolution
25.60
46.08
19.20
34.56
12.80
23.04
6.40
11.52
C
F
6.40
11.52
4.80
8.64
3.20
5.76
1.60
2.88
10–100Hz250Hz500Hz1000Hz
0.80
1.44
0.60
1.08
0.40
0.72
0.20
0.36
0
–300
–508
–150
–238
32
0
150
302
300
572
450
842
600
1112
Temperature
750
1382
C
F
900
1652
1050
1922
1200
2192
1350
2462
1500
2732
1650
3002
1800
3272
Type S Thermocouple
76.80
138.2
64.00
115.2
51.20
92.16
38.40
69.12
25.60
46.08
12.80
23.04
Resolution
19.20
34.56
16.00
28.80
12.80
23.04
9.60
17.28
6.40
11.52
3.20
5.76
C
F
4.80
8.64
4.00
7.20
3.20
5.76
2.40
4.32
1.60
2.88
0.80
1.44
10–100Hz250Hz500Hz1000Hz
0.60
1.08
0.50
0.90
0.40
0.72
0.30
0.54
0.20
0.36
0.10
0.18
0
–300
–508
–150
–238
32
0
150
302
300
572
450
842
600
1112
Temperature
750
1382
900
1652
C
F
1050
1922
1200
2192
1350
2462
1500
2732
1650
3002
1800
3272
Publication
1794-6.5.7 – March 1997
Type T Thermocouple
Specifications
A–7
102.4
184.3
89.60
161.3
76.80
138.2
64.00
115.2
51.20
92.16
38.40
69.12
25.60
46.08
12.80
23.04
Resolution
25.60
46.08
22.40
40.32
19.20
34.56
16.00
28.80
12.80
23.04
9.60
17.28
6.40
11.52
3.20
5.76
C
F
6.40
11.52
5.60
10.08
4.80
8.64
4.00
7.20
3.20
5.76
2.40
4.32
1.60
2.88
0.80
1.44
10–100Hz250Hz500Hz1000Hz
0.80
1.44
0.70
1.26
0.60
1.08
0.50
0.90
0.40
0.72
0.30
0.54
0.20
0.36
0.10
0.18
0
–300
–508
–150
–238
0
32
150
302
Temperature
C
F
300
572
450
842
600
1112
Type N Thermocouple
128.0
230.4
102.4
184.3
76.80
138.2
51.20
92.16
25.60
46.08
Resolution
32.00
57.60
25.60
46.08
19.20
34.56
12.80
23.04
6.40
11.52
C
F
8.00
14.40
6.40
11.52
4.80
8.64
3.20
5.76
1.60
2.88
10–100Hz250Hz500Hz1000Hz
1.00
1.80
0.80
1.44
0.60
1.08
0.40
0.72
0.20
0.36
0
–300
–508
–150
–238
32
150
0
302
300
572
Temperature
450
842
600
1112
C
F
750
1382
900
1652
1050
1922
1200
2192
1350
2462
T
emplate revised June 23, 1995
Publication
1794-6.5.7 – March 1997
A–8
Specifications
Type L Thermocouple
11.71
53.0
8.51
47.3
5.31
41.5
2.13
35.8
C
F
1.46
34.6
1.06
33.9
0.66
33.1
0.26
32.4
10–100Hz250Hz500Hz1000Hz
0.18
32.3
0.13
32.2
0.08
32.1
0.03
32.0
0
–200
–328
–150
–238
–100
–148
03250
122
100
200
212
392
Temperature
Resolution
93.69
200.6
68.09
154.5
42.49
108.4
17.04
62.6
Worst Case Accuracy for the Thermocouple/mV Module
The filter is enabled by setting bit 02 in write word 0.
+12µV+12µV+24µV/oC+24µV/oF
T
emplate revised June 23, 1995
Publication
1794-6.5.7 – March 1997
A–10
Specifications
Publication
1794-6.5.7 – March 1997
General
Appendix
B
Thermocouple Restrictions
(Extracted from NBS
Monograph 125 (IPTS-68))
Following are some restrictions extracted from NBS Monograph 125
(IPTS–68) issued March 1974 on thermocouples B, E, J, K, R, S
and T:
B (Platinum – 30% Rhodium vs Platinum – 6% Rhodium) Type
Thermocouples
“The ASTM manual STP 470 [1970] indicates the following
restrictions on the use of B type thermocouples at high temperatures:
They should not be used in reducing atmospheres, nor in those
containing metallic or nonmetallic vapors, unless suitably protected
wiht nonmetallic protecting tubes. They should never be inserted
directly into a metallic primary tube.”
“At temperatures below 450C the Seebeck coefficient of Type B
thermocouples becomes quite small and is almost negligible in the
normal room temperature range. Consequently, in most applications
the reference junction temperature of the thermocouple does not
need to be controlled or even known, as long as it is between 0 and
50C.”
Studies have shown that “a 0.1 percent change in the Rhodium
content of the Pt–30% Rh thermoelement produces a corresponding
change in the thermocouple voltage of about 15uV (i.e. 1.3C) at
1500C. In contrast a change of only .01% in the Rhodium content of
Pt–6% Rh thermoelement also produces a voltage change of about
15uV (1.3C) at this temperature.”
“The thermoelectric voltages of Type B thermocouples is sensitive to
their history of annealing, heat treatment and quenching. Calibration
of Type B wires above 1600C is undesirable in most circumstances.”
“ASTM Standard E230–72 in the Annual Book of ASTM Standards
[1972] specifies that the standard limits of error for Type B
commercial thermocouples be + 1/2 percent between 871 and 1705C.
Limits of error are not specified for Type B thermocouples below
871C. The recommended upper temperature limit for protected
thermocouples, 1705C, applies to AWG 24 (0.5mm) wire.”
Publication
1794-6.5.7
Thermocouple Restrictions B–2
E (Nickel–Chromium vs Copper–Nickel <Constantan*>) Type
Thermocouple
“Type E thermocouples are recommended by the ASTM Manual
[1970] for use in the temperature range from –250 to 871C in
oxidizing or inert atmospheres. The negative thermoelement is
subject to deterioration above about 871C, but the thermocouple may
be used up to 1000C for short periods.”
“The ASTM Manual [1970] indicates the following restrictions .. at
high temperatures. They should not be used in sulfurous, reducing or
alternately reducing and oxidizing atmospheres unless suitably
protected with protecting tubes. They should not be used in vacuum
(at high temperatures) for extended times, because the Chromium in
the positive thermoelement vaporizes out of solution and alters the
calibration. They should also not be used in atmospheres that
promote ”green–rot” corrosion (those with low, but not negligible,
oxygen content).”
“The negative thermoelement, a copper–nickel alloy, is subject to
composition changes under thermal neutron irradiation since the
copper is converted to nickel and zinc.”
“ASTM Standard E230–72 in the Annual Book of ASTM Standards
[1972] specifies that the standard limits of error for the Type E
commercial thermocouples be +/–1.7C between 0 and 316C and
+/–1/2 percent between 316 and 871C. Limits of error are not
specified for Type E thermocouples below 0C. Type E
thermocouples can also be supplied to meet special limits of error,
which are less than the standard limits of error given above:
+/–1.25C between 0 and 316C and +/–3/8 percent between 316 and
871C. The recommended upper temperature limit for protected
thermocouples, 871C, applies to AWG 8 (3.3mm) wire. For smaller
wires the recommended upper temperature decreases to 649C for
AWG 14 (1.6mm), 538C for AWG 20 (.8mm) and 427C for AWG 24
or 28 (0.5 or 0.3mm).
J (Iron vs Copper–Nickel <Constantan*>) Type Thermocouple
The J thermocouple “is the least suitable for accurate thermometry
because there are significant nonlinear deviations in the
thermoelectric output from different manufacturers. ... The total and
specific types of impurities that occur in commercial iron change
with time, location of primary ores, and methods of smelting.”
Publication
1794-6.5.7
Thermocouple Restrictions B–3
“Type J thermocouples are recommended by the ASTM [1970] for
use in the temperature range from 0 to 760C in vacuum, oxidizing,
reducing or inert atmospheres. If used for extended times above
500C, heavy gage wires are recommended because the oxidation rate
is rapid at elevated temperatures.”
“They should not be used in sulfurous atmospheres above 500C.
Because of potential rusting and embrittlement, they are not
recommended for subzero temperatures. They should not be cycled
above 760C even for a short time if accurate readings below 760C
are desired at a later time.”
“The negative thermoelement, a copper–nickel alloy, is subject to
substantial composition changes under thermal neutron irradiation,
since copper is converted to nickel and zinc.”
“Commercial iron undergoes a magnetic transformation near 769C
and <an alpha – gamma> crystal transformation near 910C. Both of
these transformations, especially the latter, seriously affect the
thermoelectric properties of iron, and therefore, the Type J
thermocouples. If Type J thermocouples are taken to high
temperatures, especially above 900C, they will lose accuracy of their
calibration when they are recycled to lower temperatures.”
“ASTM Standard E230–72 in the Annual Book of ASTM Standards
[1972] specifies that the standard limits of error for Type J
commercial thermocouples be +/–2.2C between 0 and 277C and
+/–3/4 percent between 277 and 760C. Limits of error are not
specified for Type J thermocouples below 0C or above 760C. Type J
thermocouples can also be supplied to meet special limits of error,
which are equal to one half the limits given above. The
recommended upper temperature limit for protected thermocouples,
760C, applies to AWG 8 (3.3mm) wire. For smaller wires the
recommended upper temperature decrease to 593C for AWG 14
(1.6mm), and 371C for AWG 24 or 28 (0.5 or 0.3mm).
*
It should be noted that the Constantan element of T
with the Constantan element of Types T or N due to the different ratio of copper and nickel
in each.
ype J thermoelements is NOT interchangeable
Publication
1794-6.5.7
Thermocouple Restrictions B–4
K (Nickel–Chromium vs Nickel–Aluminum) Type Thermocouple
“This type is more resistant to oxidation at elevated temperatures
than the Types E, J or T thermocouples and consequently it finds
wide application at temperatures above 500C.”
“Type K thermocouples may be used at” liquid hydrogen
“temperatures. However, their Seebeck coefficient (about 4uV/K at
20K) is only about one–half of that of Type E thermocouples.
Furthermore, the thermoelectric homogeneity of KN thermoelements
is generally not quite as good as that of EN thermoelements. Both
the KP and the KN thermoelements do have a relatively low thermal
conductivity and good resistance to corrosion in moist atmospheres
at low temperatures.”
“Type K thermocouples are recommended by the ASTM [1970] for
continuous use at temperatures within the range –250 to 1260C in
oxidizing or inert atmospheres. Both the KP and the KN
thermoelements are subject to oxidation when used in air above
about 850C, but even so, Type K thermocouples may be used at
temperatures up to about 1350C for short periods with only small
changes in calibration.”
“They should not be used in sulfurous, reducing, or alternately
reducing and oxidizing atmospheres unless suitably protected with
protecting tubes. They should not be used in vacuum (at high
temperatures) for extended times because the Chromium in the
positive thermoelement vaporizes out of solution and alters the
calibration. They should also not be used in atmospheres that
promote ”green–rot” corrosion (those with low, but not negligible,
oxygen content).”
“ASTM Standard E230–72 in the Annual Book of ASTM Standards
[1972] specifies that the standard limits of error for Type K
commercial thermocouples be +/–2.2C between 0 and 277C and
+/–3/4 percent between 277 and 1260C. Limits of error are not
specified for the Type K thermocouples below 0C. Type K
thermocouples can also be supplied to meet special limits of error,
which are equal to one half the standard limits of error given above.
The recommended upper temperature limit for protected Type K
thermocouples, 1260C, applies for AWG 8 (3.3mm) wire. For
smaller wires it decreases to 1093C for AWG 14 (1.6mm), 982C for
AWG 20 (0.8mm), and 871C for AWG 24 or 28 (0.5 or 0.3mm).”
Publication
1794-6.5.7
Thermocouple Restrictions B–5
R (Platinum–13% Rhodium vs Platinum) and
S (Platinum–10% Rhodium vs Platinum) Type Thermocouples
“The ASTM manual STP 470 [1970] indicates the following
restrictions on the use of S {and R} type thermocouples at high
temperatures: They should not be used in reducing atmospheres, nor
in those containing metallic vapor (such as lead or zinc), nonmetallic
vapors (such as arsenic, phosphorous or sulfur) or easily reduced
oxides, unless suitably protected with nonmetallic protecting tubes.
They should never be inserted directly into a metallic primary tube.”
“The positive thermoelement, platinum–10% rhodium {13%
rhodium for R}, is unstable in a thermal neutron flux because the
rhodium converts to palladium. The negative thermoelement, pure
platinum, is relatively stable to neutron transmutation. However, fast
neutron bombardment will cause physical damage, which will
change the thermoelectric voltage unless it is annealed out.”
“The thermoelectric voltages of platinum based thermocouples are
sensitive to their heat treatments. In particular, quenching from high
temperatures should be avoided.”
“ASTM Standard E230–72 in the Annual Book of ASTM Standards
[1972] specifies that the standard limits of error for Type S {and R}
commercial thermocouples be +/–1.4C between 0 and 538C and
+/–1/4% between 538 and 1482C. Limits of error are not specified
for Type S {or R} thermocouples below 0C. The recommended
upper temperature limit for continuous use of protected
thermocouples, 1482C, applies to AWG 24 (0.5mm) wire.
T (Copper vs Copper–Nickel <Constantan*>) Type Thermocouple
“The homogeneity of most Type TP and TN (or EN) thermoelements
is reasonably good. However, the Seebeck coefficient of Type T
thermocouples is moderately small at subzero temperatures (about
5.6uV/K at 20K), being roughly two–thirds that of Type E
thermocouples. This, together with the high thermal conductivity of
Type TP thermoelements, is the major reason why Type T
thermocouples are less suitable for use in the subzero range than
Type E thermocouples.”
Publication
1794-6.5.7
Thermocouple Restrictions B–6
“Type T thermocouples are recommended by the ASTM [1970] for
use in the temperature range from –184 to 371C in vacuum or in
oxidizing, reducing or inert atmospheres. The recommended upper
temperature limit for continuous service of protected Type T
thermocouples is set at 371C for AWG 14 (1.6mm) thermoelements,
since Type TP thermoelements oxidize rapidly above this
temperature. However, the thermoelectric properties of Type TP
thermoelements are apparently not grossly affected by oxidation
since Roeser and Dahl [1938] observed negligible changes in the
thermoelectric voltage of Nos. 12, 18, and 22 AWG Type TP
thermoelements after heating for 30 hours in air at 500C. At this
temperature the Type TN thermoelements have good resistance to
oxidation and exhibit only small changes in thermal emf with long
exposure in air, as shown by the studies of Dahl [1941].” ...
“Operation of Type T thermocouples in hydrogen atmospheres at
temperatures above about 370C is not recommended since severe
embrittlement of the Type TP thermoelements may occur.”
“Type T thermoelements are not well suited for use in nuclear
environments, since both thermoelements are subject to significant
changes in composition under thermal neutron irradiation. The
copper in the thermoelement is converted to nickel and zinc.”
“Because of the high thermal conductivity of Type TP
thermoelements, special care should be exercised in the use of the
thermocouples to insure that both the measuring and reference
junctions assume the desired temperatures.”
ASTM Standard E230–72 in the Annual Book of ASTM Standards
[1972] specifies that the standard limits of error for Type T
commercial thermocouples be +/–2 percent between –101 and –59C,
+/–.8C between –59 and 93C and +/–3/4 percent between 93 and
371C. Type T thermocouples can also be supplied to meet special
limits of error, which are equal to one half the standard limits of
error given above (plus a limit of error of +/–1 percent is specified
between –184 and –59C). The recommended upper temperature limit
for protected Type T thermocouples, 371C, applies to AWG 14
(1.6mm) wire. For smaller wires it decreases to 260C for AWG 20
(0.8mm) and 240C for AWG 24 or 28 (0.5 or 0.3mm).
Use this template for your appendices. If it were not for the different
running head, this would be your chapter 4 document.
Publication
1794-6.5.7
Index
Numbers
1794-TB3
example, thermocouple
connection, 2–7
A
accuracy
adapter input status word, 5–1
, worst case, A–7
B
bit/word description, thermocouple module,
1794-IT8, 4–5, 5–4
block transfer
read, 1–2
write, 1–2
block transfer programming, 3–1
block transfer read, 4–4
using DeviceNetManager
open circuit error
optimal defaults, 5–7
, A–8
, 6–9
P
PLC–2 programming, 3–4
polled I/O, structure, 5–1
power defaults, 5–7
preparing for calibration, 6–4
programming example
PLC–3, 3–2
PLC–5, 3–3
repeatability
resolution curves, A–3
type B thermocouple, A–3
type C thermocouple, A–4
type E thermocouple, A–3
type J thermocouple, A–4
type K thermocouple, A–5
type N thermocouple, A–7
type R thermocouple, A–5
type S thermocouple, A–6
type T thermocouple, A–6
, worst case, A–8
S
sample program, 3–4
scaling, 4–2
software, DeviceNetManager
specifications, thermocouple, A–1
status indicators, 2–8
system throughput, 5–3
At Allen-Bradley, customer service means experienced
representatives at Customer Support Centers in key cities throughout
the world for sales service and support. Our value-added services
include:
Technical Support
•
SupportPlus programs
• telephone support and 24-hour emergency hotline
• software and documentation updates
• technical subscription services
Engineering and Field Services
•
application engineering assistance
• integration and start-up assistance
• field service
• maintenance support
Technical Training
•
lecture and lab courses
• self-paced computer and video-based training
• job aids and workstations
• training needs analysis
Repair and Exchange Services
•
your only “authorized” source
• current revisions and enhancements
• worldwide exchange inventory
• local support
Worldwide representation.
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve
productivity and quality for more than 90 years. We design, manufacture and support a broad
range of automation products worldwide. They include logic processors, power and motion
control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the
world’s leading technology companies.
Argentina •
Denmark • Ecuador • Egypt • El Salvador
Ireland
Philippines •
Sweden
Australia • Austria • Bahrain • Belgium
• Israel • Italy • Jamaica •
Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore
• Switzerland • T
Japan • Jordan • Korea • Kuwait • Lebanon
aiwan
• Thailand • T
• Brazil •
• Finland •
urkey • United Arab Emirates • United Kingdom • United States • Uruguay • V