Rockwell Automation 1785-LTx, D178510.3 User Manual

AllenBradley
Classic PLC5 Programmable Controller
(Cat.
No. 1785LT, L
L
T3, and L
T4)
Quick Start
Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation, and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or in part, without written permission of Allen-Bradley Company, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or
!
Attention statements help you to:
death, property damage or economic loss.
identify a hazard
avoid the hazard
recognize the consequences
Important: Identifies information that is critical for successful
application and understanding of the product.
ControlNet is a trademark; PLC is a registered trademark of Allen-Bradley Company, Inc.

Table of Contents

Important User Information -1. . . . . . . . . . . . . . . . . . . . . . . .
Preface P-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Who Should Use This Manual P-1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Purpose of This Manual P-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Related
Common Techniques Used in This Manual P-3. . . . . . . . . . . . . . . . . .
AllenBradley Support P-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Product Support P-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Product Assistance P-3. . . . . . . . . . . . . . . . . . . . . . . . .
Your Questions or Comments about This Manual P-3. . . . . . . . . . .
Overview 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
What You Need to Do 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Components You Need 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Documentation
P-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set up the Hardware 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configure
Install the Hardware 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ground
Install the Power Supply 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Install the PLC5 Processor 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . .
Powerup the System 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Install Connect the Programming Terminal and the PLC5
Processor to the Communication Card 2-6. . . . . . . . . . . . . . . . . .
the I/O Chassis
the I/O Chassis
the I/O Modules
Set up the Software 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Install the Software and Set Up the Programming System 3-1. . . . . . .
Start the Programming Software 3-1. . . . . . . . . . . . . . . . . . . . . . . . .
Powerup the System 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshoot the Processor System 4-1. . . . . . . . . . . . . . . . .
Use the PLC5 Processor Status Indicators 4-1. . . . . . . . . . . . . . . . .
Specifications A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Processor Battery
Specific
Specifications
A-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Preface

Preface
Read this preface to familiarize yourself with the rest of the manual. This preface covers the following topics:
who should use this manual
the purpose of this manual
how to use this manual
conventions used in this manual
Allen-Bradley support

Who Should Use This Manual

Purpose of This Manual

To use this manual, you should understand programmable controllers and be able to interpret the ladder logic instructions required to control your application. For more information, see the documents listed on the following page or contact your local Allen-Bradley representative.
This manual is for users of the classic PLC-5R processor. It:
presents you with the basic information you need to get your
system up and running
provides “memory jogger” information, such as specific bit and
switch settings for modules
includes high-level procedures with cross-references to other
manuals for more detail
Publication 178510.3 - October 1996
PrefaceP–2
Related Documentation
The following documents contain additional information concerning the products discussed in this manual.
For more information about: See this document: Publication
number:
Classic PLC5 programmable controllers Classic PLC5 Programmable Controllers User Manual 17856.2.1
To obtain a free copy of this manual, complete and send in the User Manual Request Card that came packaged with this quick start.
.
Classic PLC5 programmable controllers Classic PLC5 Programmable Controllers Hardware Installation Manual 17856.6.1
Universal 1771 I/O chassis Universal I/O Chassis Installation Instructions 17712.10
power supply Redundant Power Supplies (1771P4R, P6R) Installation Data 17712.166
DH+R network
communication cards
cables
batteries AllenBradley Guidelines for Lithium Battery Handling and Disposal AG5.4
grounding and wiring AllenBradley programmable controllers
current AllenBradley documentation, including ordering instructions
terms and definitions AllenBradley Industrial Automation Glossary AG7.1
Enhanced and Ethernet PLC5 Programmable Controllers User Manual 17856.5.12
Data Highway/Data Highway Plus/Data Highway II/Data Highway485 Cable Installation Instructions
1784KTx Communication Interface Card User Manual 17846.5.22
AllenBradley Publication Index (for your specific communication card) SD499
Classic PLC5 Programmable Controllers User Manual 17856.2.1
AllenBradley Programmable Controller Wiring and Grounding Guidelines
AllenBradley Publication Index SD499
17706.2.2
17704.1
Publication
178510.3 - October 1996
Preface P–3

Common Techniques Used in This Manual

More
AllenBradley Support
We use the following conventions throughout this manual:
Bulleted lists provide information, not procedural steps.
Numbered lists provide sequential steps or hierarchical
information.
We use this symbol to indicate additional references you can use when you need more information about a particular topic.
Allen-Bradley offers support services worldwide, with over 75 sales/support offices, 512 authorized distributors, and 260 authorized systems integrators located throughout the United States alone, plus Allen-Bradley representatives in every major country in the world.
Local Product Support
Contact your local Allen-Bradley representative for:
sales and order support
product technical training
warranty support
support service agreements
Technical Product Assistance
If you need to contact Allen-Bradley for technical assistance, call your local Allen-Bradley representative.
Your Questions or Comments about This Manual
If you discover a problem with this manual, please notify us of it by completing and sending the enclosed Publication Problem Report (at the back of this manual).
If you have any suggestions about how we can make this manual more useful to you, please contact us at the address below:
Allen-Bradley Company, Inc. Automation Group Technical Communication 1 Allen-Bradley Drive Mayfield Heights, OH 44124-6118
Telephone: (216) 646-5000 FAX: (216) 646-3083
Publication
178510.3 - October 1996

What You Need to Do

Set
up the hardware
(Chapter 2)
Chapter 1
Overview
This quick start is designed to provide you with the information you need to get your system up and running quickly. Use this document if you are knowledgeable about Classic PLC-5 products, but may not have used one or more of them recently. The information we provide is geared to “jog your memory.”
PC with programming software installed
Set up the software (Chapter 3)
Troubleshoot
the Processor System (Chapter 4)

Components You Need

terminal cable
Product name: Catalog number:
Hardware
Classic PLC5 processor with 2 keys
Lithium Battery (in a clear bag)
I/O chassis
Memory modules
Power supply 1771P1, P2 P3, P4, P4S, P4S1, P4R, P5, P6S,
Programming System
PC
PLC5 programming software
communication module DH+ interface and interconnect cable
PLC5/25
1785LT4, LT3, LT2, LT
1770XY
1771A1B, A2B, A3B1, A4B (panel mount) 1771A3B (rack or panel mount)
1785MJ 1785MK (PLC5/25 only)
P6S1, P6R, P7, PS7
Check your programming software documentation for system requirements, such as memory, etc.
Choose a programming software package that is compatible with Classic PLC5 processors.
Important: In this manual, we assume you are using a brand-new
Classic PLC-5 processor out of the box.
Publication
178510.3 - October 1996
Install the hardware
1
(page 2-2)
Connect the programming terminal
2
and the PLC5 processor to the communication card (page 26)
Set up the Hardware
PC with programming software installed
terminal cable
PLC5/25
Chapter 2
More
For more information, see the Classic PLC-5 Programmable Controllers Hardware Installation Manual, publication number 1785-6.6.1.
Publication
178510.3 - October 1996
2–2 Set up the Hardware

Install the Hardware

Set
the backplane switches.
1
Pressed in at top ON (closed)
Pressed in at bottom OFF (open)
Always Off
Configure the I/O Chassis
Switch
1
ON
OFF
Outputs of this I/O chassis remain in their last state when a hardware failure occurs.
Outputs of this I/O chassis are turned off when a hardware failure occurs.
Switches
4
5
OFF OFF
OFF ON
ON OFF
ON ON
Switches
67
OFF OFF
ON ON
ON OFF
Addressing
2-slot
1-slot
1/2 - slot
Not allowed
EEPROM memory transfer to processor memory at powerup.
EEPROM memory transfers to processor memory if processor memory not valid.
EEPROM memory does not transfer to processor memory
Last State
1
1
EEPROM transfer
2
3
.
Switch
8
OFF
ON
RAM memory protection
RAM memory protection disabled.
RAM memory protection enabled.
4
1. Regardless of this switch setting, outputs are reset when any of the following occurs:
processor detects a runtime error
an I/O chassis backplane fault occurs
you select program or test mode
you set a status file bit to reset a local rack
2. If an EEPROM module is not installed and processor memory is valid, the processor's PROC LED indicator blinks, and the processor sets S:11/9, bit 9 in the major fault status word.
3. A processor fault occurs if processor memory (solid red PROC LED) is not valid.
4. You cannot clear processor memory when this switch is on.
19309
Publication
178510.3 - October 1996
Set
the power supply configuration
2
jumper.
NY
Install the keying bands.
3
Set
NY
Y when you install a power supply module in the chassis; set N (the default) when you use an external power supply
2–3Set up the Hardware
Are
you using a power supply module in the chassis?
.
YN
PLC5/20 Processor
Keying Bands
I/O Module
I/O Module
See the user manual for your particular I/O module for information on where to set these
between
keying bands.
40 & 42
54 & 56
20609-M
(for remote I/O systems)
Enclosure
Ground bus
More
electrode conductor
Grounding
T
o grounding electrode system
I/O chassis wall
Ground lug
Star washer
Ground lug
For more information, see the Universal I/O Chassis Installation Instructions, publication number 1771-2.10.
Ground the I/O Chassis
(for extendedlocal systems)
Nut
15561
Enclosure
Ground bus
Extendedlocal I/O cables
To grounding electrode system (single point only)
Enclosure
Ground bus
I/O chassis wall
Star washer
Ground lug
Ground lug
Nut
18585
More
For more information, see the Allen-Bradley Programmable Controller Wiring and Grounding Guidelines, publication number 1770-4.1.
Publication
178510.3 - October 1996
2–4 Set up the Hardware
Install the Power Supply
Locking
Bar
1
Set
the jumpers on the back side of the power supply like this:
2
Connect the power cord to the 120V ac connector of the power supply module.
This
side plugs into connector on the module.
More
insert wire here
insert wire here
or
place tool here
3
Install the power supply in the chassis
20619-M
and snap the modulelocking bar over the modules.
For more information, see the Redundant Power Supplies (1771-P4R, -P6R) Installation Data, publication number 1771-2.166.
place tool here
Publication
178510.3 - October 1996
Install the PLC5 Processor
1
Define
the DH+ Station Address of Channel 1A
by setting switch assembly SW
1 on the back of
the processor.
To p
view of processor
side view
2–5Set up the Hardware
Card Guides
PLC-5/25 Processor
Memory
module slot
More
Locking
Bar
Battery
Battery
Lift Eector T
Connector
Battery Cover
More
ab
T
2
connector into the processor until you hear them snap together the battery cover
If
3
Install the processor
4
ATTENTION: Do not insert or remove the EEPROM under power
Insertion or removal under power can result in loss of program memory and a processor fault.
For detailed information about handling and disposing of the battery as well as other important guidelines, see publication AG5.4.
OFF
Set Switch assembly SW1 address here
o install the battery, slide the batteryside
side connector
, and attach
.
you plan to install an EEPROM, install it now
.
For more information, see the Classic PLC-5 Programmable Controllers Hardware Installation Manual, publication number 1785-6.6.1.
.
.
Powerup the System
Powerup the system. Check the LED display on the processor. If your system is operating properly, the PROC LED should be steady red. If the PROC LED is not red, see chapter 4 for troubleshooting information before you install the I/O modules.
Publication
178510.3 - October 1996
2–6 Set up the Hardware
Card Guides
Install the I/O Modules
Locking Bar
20618-M
Install
each I/O module and connect
the wiring arm.
More
Connect the Programming Terminal and the PLC5 Processor to the Communication Card
More
For more information, see the installation instructions or user manual for the particular module you are installing.
1
Connect CP cable to the communication card.
Connect the CP cable to the connector on
2
the PLC5 processor
the industrial terminal end of the
.
For more information, see:
Classic PLC-5 Programmable Controllers Hardware Installation
Manual, publication number 1785-6.6.1
1784-KTx Communication Interface Card User Manual,
publication number 1784-6.5.22
Data Highway/Data Highway Plus/Data Highway II/Data
Highway 485 Cable Installation Manual, publication 1770-6.2.2
Publication
178510.3 - October 1996
Set up the Software
Install the software
1

Start the programming software

2
Chapter 3
More

Install the Software and Set Up the Programming System

Powerup
3
The following instructions are general. For specific information, see the documentation set for your particular software package.
Before you install your programming software, make certain you meet the system requirements for that software – sufficient disk space, memory, etcetera. Then, follow the procedures outlined in the software documentation to install the software and configure communication.
the system
Start the Programming Software
Start the programming software by following the procedures described in your programming software documentation.
If you have difficulty, verify that the power supply is turned on. To monitor your system as you configure and run it, check the LED
display for the following indicators:
This LED: lights when:
COMM
BATT no battery is installed or the battery voltage is low
REM I/O you establish Remote I/O communication
ADAPT the processor is in adapter mode
FORCE forces are present in your ladder program
you establish DH+ communication
Publication
178510.3 - October 1996
3–2 Set up the Software

Powerup the System

If your keyswitch is in this position:
PROGRAM
REMOTE
RUN No access or privilege violation.
Powerup the system if you have not done so already. Check the LED display on the processor. If your system is operating properly, the PROC LED should be steady red. See the following table to proceed. If the PROC LED is not red, turn to chapter 4 for troubleshooting information.
you see this message: and then this occurs:
Processor RAM is faulted. Press <Enter> to clear memory."
Processor RAM is faulted. Press <Enter> to clear memory."
After you clear memory, the PROC LED turns of The software is in Program mode.
After you clear memory, the PROC LED turns of The software is in Remote Program mode.
You see this message because you cannot clear memory in Run mode. Change the keyswitch position to Program or Remote and powerup the system again.
f.
f.
Publication
178510.3 - October 1996
Chapter 4
Troubleshoot the Processor System
Use the PLC5 Processor Status Indicators
Indicator Color Description Probable Cause Recommended Action
PROC green
(steady)
green (blinking)
COMM
REM I/O
ADPT
R U N
FAULT
ACTIVE
RUN
REM
BATT
PROC
FORCE
P R O G
red (blinking)
red (steady)
off processor in program load or
BATT
PROC
FORCE
COMM
processor in RUN mode and fully operational
Processor memory being transferred to EEPROM
major fault runtime error Check major fault bit in status file (S:11)
major fault
TEST mode or is not receiving power
normal operation no action required
normal operation no action required
user RAM has
checksum error
memory module
error
Use
1
the PLC5 Processor Status Indicators (page 4-1)
for error definition. Clear fault bit, correct problem, and return to RUN mode.
Clear memory and reload program.
Check backplane switch settings
Check power supply and connections.
and/or insert correct memory module.
PROC REM I/O
FORCE amber
BATT red
ADPT (continues)
all red (steady)
(steady)
amber (blinking)
off no forces present normal operation no action required
(steady)
off battery is good normal operation no action required
green (steady)
internal diagnostics have failed
forces enabled normal operation no action required
forces present, but not enabled
battery low Replace battery within 12 days (typical).
processor is in adapter mode normal operation no action required
normal operation no action required
Power down, reseat processor and power up. Then, clear memory and reload your program. Replace EEPROM with new program. Then, if necessary, replace the processor.
Publication
178510.3 - October 1996
4–2 Troubleshoot the Processor System
Indicator Recommended ActionProbable CauseDescriptionColor
ADPT off processor is in scanner mode normal operation no action required
REM I/O (in adapter mode)
REM I/O (in scanner mode)
green
active remote I/O link normal operation no action required
(steady)
green (blinking)
remote I/O active and host processor is in program load or TEST mode
red (steady)
green (sporadic)
no communication with host processor
bad communication with host processor
off no communication with host
processor
green
active remote I/O link normal operation no action required
(steady)
red
remote I/O link fault wiring, adapter
(steady)
green/red
partial remote I/O link fault one or more
(blinking)
normal operation no action required
duplicate station
Correct station address.
address selected
Check connections.
no action required
Check all connections, check adapter
module(s)
module(s).
If you have programming software,
put the processor in PROG mode and do an autoconfigure for remote racks.
Check status bits in status file
remote I/O chassis faulted
(element #7) to identify faulted chassis number; check wiring, adapter module(s), power supplies.
If you have programming software, put
the processor in PROG mode and do an auto configure for remote racks.
Publication
COMM green
178510.3 - October 1996
off no remote I/O selected no action required
(blinking rapidly
processor is transmitting or receiving on DH+ link
normal operation no action required
or slowly)
red (steady)
watchdog timeout hardware error Turn power off, then on. Check that the
software configurations match the hardware setup. Replace the processor.
red (sporadic)
off
bad communication on DH+ link
If directly connected to
duplicate station address selected
Correct station address.
no action required
processor, no communication on DH+ link
If last processor on DH+
Check DH+ wiring connections.
link, no communication on DH+ link
General
Appendix
Specifications
This table lists general specifications.
Weight PLC5/10 (1785LT4) 1336 g (47.12 oz.)
PLC5/12 (1785LT3) 1337 g (42.15 oz.)
PLC5/15 (1785LT) 1339 g (47.23 oz.)
PLC5/25 (1785LT2) 1337 g (42.15 oz.)
Backplane Current 2.5A
Environmental Conditions:
operating temperature
storage temperature
relative humidity 5 to 95% (without condensation)
Vibration (operating and nonoperating)
Shock
operating
nonoperating
° to 60
°
0
40° to 85° C (40° to 185° F)
1 g @ 10 to 500 Hz
0.012 inches peaktopeak displacement
30 g peak acceleration for 11
50 g peak acceleration for 11±1 ms duration
C (32° to 140° F)
±1 ms duration
TimeofDay Clock and Calender
maximum variations at 60
° C
typical variations at 20° C ± 20 s per month
timing accuracy one program scan
Typical Discrete I/O Scan
I/O Modules Bulletin 1771 I/O including 8, 16, 32pt., and intelligent modules
Hardware Addressing:
2slot
1slot
1/2slot any mix of 8,16, or 32pt modules
Communication
Location 1771I/O chassis, leftmost slot
Keying
Agency Certification
(when product is marked)
User Manual publication 17856.2.1
± 3 min per month
1ms/local I/O rack
10 ms/remote I/O adapter communication at 57.6 kbps
any mix of 8pt modules
16pt modules must be I/O pairs
no 32pt modules
any mix of 8 or 16pt modules
32pt modules must be I/O pairs
DH+ 3,048 cablem (or 10,000 cableft) max
DH using 1785KA
between 40 and 42
between 54 and 56
CSA certified
CSA Class I, Division 2, Groups A, B, C, D
UL listed
Publication
178510.3 - October 1996
A–2
Specifications
CSA Hazardous Location Approval Approbation d'utilisation dans des emplacements dangereux par la
CSA certifies products for general use as well as for use in hazardous locations. Actual CSA certification is indicated by the product label as shown below, and not by statements in any user documentation.
Example of the CSA certification product label Exemple d'étiquette de certification d'un produit par la CSA
To comply with CSA certification for use in hazardous locations, the following information becomes a part of the product literature for CSAcertified AllenBradley industrial control products.
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, D, or nonhazardous locations only.
The products having the appropriate CSA markings (that is, Class
I Division 2, Groups A, B, C, D), are certified for use in other equipment where the suitability of combination (that is, application or use) is determined by the CSA or the local inspection office having jurisdiction.
Important: Due to the modular nature of a PLC control system, the product with the highest temperature rating determines the overall temperature code rating of a PLC control system in a Class I, Division 2 location. The temperature code rating is marked on the product labelas shown.
CSA
La CSA certifie les produits d'utilisation générale aussi bien que ceux qui s'utilisent dans des emplacements dangereux. La certification CSA en vigueur est indiquée par l'étiquette du produit et non par des affirmations dans la documentation à l'usage des utilisateurs.
Pour satisfaire à la certification de la CSA dans des endroits dangereux, les informations suivantes font partie intégrante de la documentation des produits industriels de contrôle AllenBradley certifiés par la CSA.
Cet équipement convient à l'utilisation dans des emplacements de
Classe 1, Division 2, Groupes A, B, C, D, ou ne convient qu'à l'utilisation dans des endroits non dangereux.
Les produits portant le marquage approprié de la CSA (c'est à dire,
Classe 1, Division 2, Groupes A, B, C, D) sont certifiés à l'utilisation pour d'autres équipements où la convenance de combinaison (application ou utilisation) est déterminée par la CSA ou le bureau local d'inspection qualifié.
Important: Par suite de la nature modulaire du système de contrôle PLC), le produit ayant le taux le plus élevé de température détermine le taux d'ensemble du code de température du système de contrôle d'un PLC dans un emplacement de Classe 1, Division 2. Le taux du code de température est indiqué sur l'étiquette du produit.
Temperature code rating
Look for temperature code rating here
The following warnings apply to products having CSA certification for use in hazardous locations.
ATTENTION: Explosion hazard 
Substitution of components may impair suitability
!
for Class I, Division 2.
Do not replace components unless power has
been switched off or the area is known to be nonhazardous.
Do not disconnect equipment unless power has
been switched off or the area is known to be nonhazardous.
Do not disconnect connectors unless power has
been switched off or the area is known to be nonhazardous. Secure any usersupplied connectors that mate to external circuits on an AllenBradley product using screws, sliding latches, threaded connectors, or other means such that any connection can withstand a 15 Newton (3.4 lb.) separating force applied for a minimum of one minute.
Taux du code de température
Le taux du code de température est indiqué ici
Les avertissements suivants s'appliquent aux produits ayant la certification CSA pour leur utilisation dans des emplacements dangereux.
AVERTISSEMENT: Risque d'explosion 
La substitution de composants peut rendre ce matériel
!
inacceptable pour lesemplacements de Classe I, Division 2.
Couper le courant ou s'assurer quel'emplacement est
désigné non dangereux avant de remplacer lescomposants.
Avant de débrancher l'équipement, couper le courant
ou s'assurer que l'emplacement est désigné non dangereux.
Avant de débrancher les connecteurs, couper le
courant ou s'assurer que l'emplacement est reconnu non dangereux. Attacher tous connecteurs fournis par l'utilisateur et reliés aux circuits externes d'un appareil AllenBradley à l 'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens permettant aux connexions de résister à une force de séparation de 15 newtons (3,4 lb.  1,5 kg) appliquée pendant au moins une minute.
Publication
178510.3 - October 1996
Specifications
A–3
Processor
Specific
Processor Maximum
Local Racks
Supported
PLC5/10 4
(1 resident
chassis)
PLC5/12 4
(1 resident
chassis)
PLC5/15 4
(1 resident
chassis)
Maximum
Remote Racks
Supported
none
none
3
(up to 12
physical
devices)
This table lists specifications of each Classic PLC-5 family processor.
I/O Capacity Memory
128 I/O with 8pt
modules
256 I/O with
16pt modules
512 I/O with
32pt modules
128 I/O with 8pt
modules
256 I/O with
16pt modules
512 I/O with
32pt modules
512 I/O
512 inputs and
1
1
1
1
1
1
1
(expands
512 outputs using 16 or 32pt modules
2
(Words)
to 14K)
Program Scan
Time
6 K 2 ms/K words
(bit logic)
8 ms/K words
(typical)
6K
Communication Memory
Modules
(optional)
standalone
DH+
standalone,
adapter
8K EEPROM
(1785MJ)
8K EEPROM
(1785MJ)
DH+
standalone
scanner (local and
remote I/O)
adapter
DH+
4K RAM
expansion, 1785MR
8 K RAM
expansion, 1785MS
8K
EEPROM (1785MJ)
Battery
1770XY
PLC5/25 4
(1 resident
chassis)
7
(up to 28
physical
devices)
1024 I/O
1024 inputs and
1024 outputs using 16 or 32pt modules
1
2
13 K
(expands
to 21K)
2 ms/K words
(bit logic)
8 ms/K words
(typical)
standalone
scanner (local and
remote I/O)
adapter
DH+
4K RAM
expansion (1785MR)
8 K RAM
expansion (1785MS)
8K
EEPROM (1785MJ)
16K
EEPROM backup, 1785MK
1
Any mix of I/O.
2
Maximum I/O possible using 16pt modules with 2slot addressing or 32pt modules with 1slot addressing. Modules must alternate IOIOIO in the
chassis slots.
Publication
178510.3 - October 1996
A–4
Specifications
Battery
Specifications
Battery Type
Classic PLC-5 processors use 1770-XY batteries, which contain less than 1/2 gram of lithium, or 3.6V, “AA” size Tadiran TL 5104 type AEL/S lithium batteries with pressure contact terminals.
Average Battery Lifetime Specifications
At this temperature: Power off 100%: Power off 50%:
60°C
329 days 1.4 yrs
Publication
178510.3 - October 1996

Index

Symbols
**Empty**, -1, 3-1
B
Backplane current, A-1
Battery, A-3
lifetime specifications, A-4
C
Certification, A-1
Clock, processor, A-1
E
EEPROM, A-3
Environment specifications, A-1
I
I/O addressing, A-1
I/O scan, discrete, A-1
P
Processor, specifications, A-1
Processor memory, A-3
R
Rack addressing capability, A-3
S
Shock specifications, A-1
Specification, battery, A-4
Specifications, A-1
V
Vibration specifications, A-1
AllenBradley Publication Problem Report
If you find a problem with our documentation, please complete and return this form.
Pub.
Name Classic PLC5 Programmable Controller Quick Start for the Experienced User
Cat. No.
Check Problem(s) T
1785LT,
echnical Accuracy
Completeness
What information is missing?
Clarity
What is unclear?
LT2, LT3, L
ype:
T4
Pub. No. 178510.3
Describe Problem(s):
text illustrationT
procedure/step
example
explanation
Pub. Date October 1996
illustration
guideline
other
Part No. 95512654
definition
feature
Internal Use Only
info in manual
(accessibility)
info not in manual
Sequence
What is not in the right order?
Other
Comments
Use back for more comments.
Your
Name
Return to: Marketing Communications, AllenBradley Co., 1 AllenBradley Drive, Mayfield Hts., OH 4412461
Publication ICCG5.21August 1995 PN 95510782
Location/Phone
18
Phone: F
AX:
(216)6463176 (216)6464320
Other Comments
PLEASE F
ASTEN HERE (DO NOT ST
APLE)
PLEASE
FOLD HERE
BUSINESS REPLY MAIL
FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH
POSTAGE WILL BE P
AID BY THE ADDRESSEE
NO POSTAGE
NECESSAR
IF MAILED
IN THE
UNITED STATES
Y
PLEASE REMOVE
AllenBradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.
Worldwide representation.
Argentina
• Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark
• Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia •
Ecuador
• Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands
Jamaica Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden
Arab Emirates • United Kingdom • United States • Uruguay
United
V
enezuela
AllenBradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 3822000 Fax: (1) 414 3824444
New
Yugoslavia
Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto
Switzerland
T
aiwan
Ireland
•Israel • Italy
• Thailand • T
urkey
Publication
178510.3 -October 1996
Copyright
1996 AllenBradley Company
Publication 178510.3 -October 1996
, Inc. Printed in USA
PN 95512654
Loading...