Rockwell Automation AutoMax ControlNet Communication Interface Module User Manual

Rockwell Automation
AutoMax ControlNet Communication Interface
Module
(Cat. No. O-58820-2)
Major Rev. 2
User Manual
Page 2 AutoMax ControlNet Module
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. “Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls” (Publication SGI-
1.1) describes some important differences between solid state equipment and hard–wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation cannot assume responsibility or liability for actual use based on the examples and diagrams.
Rockwell Automation assumes no patent liability with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Attentions help you:
identify a hazard
avoid the hazard
recognize the consequences
Important: Identifies information that is especially important for successful application and understanding of the product.
Microsoft is a registered trademark of Microsoft Corporation.
Windows, Windows 95 and Windows NT are trademarks of Microsoft Corporation.
ControlLogix and Data Highway Plus are trademarks of the Allen-Bradley Company, Inc.
Publication number DSMBCN-UM001B-EN-P February 2003
INTRODUCTION 9
Who Should Use This Manual? 9
Purpose of this Manual 9
Conventions Used in this Manual 9
Getting Support 10
Reference Documents 10
Requirements 10
MBCN AUTOMAX CONTROLNET MODULE 11
Overview 11
Module Overview 11
Hardware Features 13
7-Segment Display 13 OK LED 14 MAC ID Thumbwheels 14 Serial Configuration Port 14 NAP Port 15 ControlNet Connectors 15 Network Status LEDs 15 7-Segment LED Codes 16 Communication Error 18
INSTALLATION 19
Prevent Electrostatic Discharge 19
Installation and Wiring 20
Connecting to the Network 21
Troubleshooting Wiring Problems 21
QUICK START 22
PROGRAMMING THE MBCN 23
Overview 23
AutoMax ControlNet Module Page 5
Memory Overview 23
Configuring Scheduled Connections 24
Creating a Configuration 24 Configuring 1771 I/O 25 Configuring Flex I/O 26 Configuring Scheduled Data with Another MBCN 27 Configuring Scheduled Data with a PLC-5 28 Configuring Scheduled Data with a ControlLogix Processor 29
Setting the Network Properties 32
Downloading the Configuration 32
Putting the MBCN in Run Mode 32
Accessing I/O Data 32
Application Example 33
Multicast Connections 34
MONITORING MODULE OPERATION 35
Status of Each Connection 35 Operating Status 38 Summary of Registers for Monitoring Operation 39
UNSCHEDULED MESSAGING 41
Register Organization 41 AutoMax Application Programming 42 GATEWAY_CMD_OK@ Status Codes 51 Extended Status (EXT_STS) Codes for Command 0F 53 Commands from Remote Nodes 54 Differences from the M/N 57C442 Module Interface 56
VIEWING NETWORK PARAMETERS 57
Current Network Parameters 57 Pending Network Parameters 58
STATE REGISTERS 60
Module State 60 NAM State 60 Keeper State 61 Flash State 62 Serial CONFIG Port State 62 Channel State 63
DIAGNOSTIC COUNTERS 64
Publication number DSMBCN-UM001B-EN-P February 2003
Page 6 AutoMax ControlNet Module
Standard ControlNet Counters 64 Module Specific Counters 65 The Error Log 66
ACTIVE NODE LIST 67
ID AREA 68
Vendor ID 68 Device Type 68 Product Code 68 Major Revision 68 Minor Revision 68 Status 68 Serial Number 69 Product Name Length 69 Product Name 69 Current Address 70 MAC ID Switches 70 Summary of ID Area Locations 70
FIRMWARE VERSION INFORMATION 71
USING THE HOST WATCHDOG 72
UPDATING THE FIRMWARE 73
CONVERTING FROM MAJOR REVISION 1 TO 2 76
If you have access to the Reliance MBCN hardware 76
If you have an offline configuration file (*.xc) 76
SPECIFICATIONS 78
SUPPORT 79
Publication number DSMBCN-UM001B-EN-P February 2003
AutoMax ControlNet Module Page 7
Table of Figures
Figure 1 Serial Cable Wiring.......................................................................................................................14
Figure 2 LED Status Table..........................................................................................................................16
Figure 3 7-Segment LED Codes .................................................................................................................17
Figure 4 Memory Overview........................................................................................................................24
Figure 5 Connection Status Values .............................................................................................................38
Figure 6 Scanner State Table.......................................................................................................................39
Figure 7 – Adapter (Scheduled Produced Data) State Table.......................................................................39
Figure 8 Summary of Monitor Registers.....................................................................................................40
Figure 9 Summary of Unscheduled Message Registers..............................................................................41
Figure 10 Control and Status Registers.......................................................................................................42
Figure 11 Command Table..........................................................................................................................46
Figure 12 GATEWAY_CMD_OK Status Table.........................................................................................51
Figure 13 Local and Remote Status Table ..................................................................................................52
Figure 14 Extended Status Error Codes Table ............................................................................................54
Figure 15 Unsolicited PLC-5 Commands ...................................................................................................54
Figure 16 Unsolicited Basic Command Set Commands .............................................................................55
Figure 17 Current Network Parameters.......................................................................................................58
Figure 18 Pending Network Parameters......................................................................................................59
Figure 19 Module State Table.....................................................................................................................60
Figure 20 NAM State Table........................................................................................................................61
Figure 21 Keeper State Table......................................................................................................................62
Figure 22 Flash Memory State Table..........................................................................................................62
Figure 23 Serial Config State ......................................................................................................................62
Figure 24 Channel State Table....................................................................................................................63
Figure 25 Standard ControlNet Diagnostic Counters..................................................................................65
Figure 26 Module-Specific Diagnostic Counters........................................................................................66
Figure 27 Active Node Table......................................................................................................................67
Figure 28 Device Status Table ....................................................................................................................68
Figure 29 Device Status, Bits 4-7................................................................................................................69
Figure 30 ID Locations Table .....................................................................................................................70
Figure 31 Firmware Versions Table............................................................................................................71
Publication number DSMBCN-UM001B-EN-P February 2003
This introduction covers the following topics:
who should use this manual
the purpose of the manual
contents of the manual
conventions used in the manual
getting support

Who Should Use This Manual?

Use this manual if you are responsible for designing, installing, programming or troubleshooting systems that are based on AutoMax Control using the MBCN ControlNet module (O-58820-2) with major revision 2 firmware.
You should have a basic understanding of AutoMax products. You should understand Allen Bradley PLC-5s and ControlLogix PLCs and be familiar with using ControlNet I/O modules on the ControlNet network.

Introduction

Purpose of this Manual

This manual shows you how to install and use the MBCN ControlNet module. It describes the procedures to install, configure, and operate the MBCN ControlNet module.

Conventions Used in this Manual

The following conventions are used throughout this manual:
bulleted lists, such as this one, provide information, not procedural steps
numbered lists provide sequential steps
bold type is used for emphasis
courier font is used for text you should type
hexadecimal numbers are shown with a trailing ‘h’, for example,
1234h
titles for menu items, dialog boxes, etc. in software are shown in italics
addresses that refer to a single byte within an AutoMax register are shown with a trailing ‘L’ or ‘H’ to indicate the low or high byte of the register.
T=>O means ControlNet target-to-originator; O=>T means originator-to-target. The originator is the node that opens the connection to the target.
RSNetWorx means RSNetWorx for ControlNet
Page 10 AutoMax ControlNet Module

Getting Support

Refer to page 79 for information on how to obtain support for the MBCN module.
For support on the AutoMax processor or programming software, contact Rockwell Automation or your local distributor.

Reference Documents

For information on using RSNetWorx, refer to:
RSNetworx ControlNet Getting Results, Publication Number 9399­CNETGR, Catalog number 9357-CNETL3
For information on ControlNet, refer to one of the following:
ControlNet Specification, available from ControlNet International,
www.controlnet.org
IEEE 518 Guide for the Installation of Electrical Equipment to Minimize Electrical Noise Input to Controllers
ControlNet user manual, publication 1786-2.12
, approximate cost US$350

Requirements

RSNetWork for ControlNet version 3.21 and above includes support for configuring the MBCN.
MBCN firmware version 1.10 and above requires RSNetWorx for ControlNet for configuration.
The MBCN must be running firmware version 1.10 or above to be used with ControlFlash.
To use the connection status information, you need RSNetWork for ControlNet version 4.11 or above and firmware version 2.1 or above on the MBCN.
Refer to page 73 for information on updating the firmware in the MBCN.
Refer to page 76 for information on converting a revision 1 MBCN to a revision 2 MBCN in RSNetWorx for ControlNet.
Publication number DSMBCN-UM001B-EN-P February 2003

Overview

Module Overview

AutoMax ControlNet Module Page 11

MBCN AutoMax ControlNet Module

This chapter contains the following information:
module overview
a summary of hardware features
a description of how the hardware works
The MBCN module makes it possible for an application running in an AutoMax Controller to communicate with and control ControlNet I/O devices. The MBCN can also exchange data with other processors over the ControlNet network using scheduled produced and consumed data.
The MBCN uses the standard AutoMax memory-mapped interface to the host processor.
All I/O data is mapped into AutoMax registers 16384-32767. You can select the register assignment for the data for each connection or have the register assignment created automatically when you create the I/O configuration.
The module:
supports up to 127 scheduled connections, up to 480 words per connection
supports a maximum of 16 Kbytes total input data
maps input data into AutoMax Processor registers 16384-24575
supports a maximum of 16 Kbytes total output data
maps output data into AutoMax Processor registers 24576-32767
provides global status on all originator to target (O=>T) connections
and global status on all target to originator (T=>O) connections
provides status on each connection, in AutoMax registers 15362­15614, two 16-bit words per connection. You map the location of the status information for a connection using RSNetWorx. This requires major revision 2 of the MBCN firmware and RSNetWorx for ControlNet 4.11 or later. Major revision 1 of the MBCN firmware does not support status on individual connections
You use RSNetWorx for ControlNet to configure the I/O devices being scanned and all scheduled produced and consumed connections.
The MBCN maintains standard ControlNet diagnostic counters, as well as additional diagnostic counters, to monitor MBCN operation and to diagnose problems.
The MBCN maintains an active node list.
Publication number DSMBCN-UM001B-EN-P February 2003
Page 12 AutoMax ControlNet Module
The MBCN can send unscheduled messages to other nodes on the network, and receive and respond to unscheduled messages from other nodes, using PLC-5 PCCC commands. The MBCN emulates the AutoMax interface on the M/N 57C442 Data Highway Plus module.
Publication number DSMBCN-UM001B-EN-P February 2003

Hardware Features

AutoMax ControlNet Module Page 13
The main hardware features of the MBCN are:
7-segment display
MBCN
O-58820
Fault Code
MAC ID
OK
OK LED
switches to set the MBCN’s ControlNet address
serial config port for updating the MBCN firmware
ControlNet NAP port
ControlNet BNC connectors
network status LEDs
10
These are described in detail in the following sections
1
Config NAP
A
COM
B
COM

7-Segment Display

The MBCN has a 7-segment LED to indicate status. Refer to page 16 for a summary of 7-segment display codes.
Publication number DSMBCN-UM001B-EN-P February 2003
Page 14 AutoMax ControlNet Module
6
7
8
9

OK LED

The MBCN contains a hardware watchdog that monitors operation of the MBCN hardware and software. The hardware watchdog times out only when there is a catastrophic hardware or firmware failure on the MBCN. The green OK LED is on when the hardware watchdog is OK and is off if the watchdog times out.
NOTE: The hardware watchdog is NOT the same as the host watchdog. See page 72 for information on using the host watchdog.

MAC ID Thumbwheels

Use the two thumbwheels labelled MAC ID to set the MBCN’s address on ControlNet. The upper thumbwheel sets the most significant digit; the lower thumbwheel sets the least significant digit.
To maximize network efficiency and reduce network overhead, you usually assign ControlNet addresses consecutively, starting at 1.
NOTE: 0 is not a valid address.
The MBCN reads the thumbwheels only at power-up. You must power down and power back up for changes in the thumbwheel settings to be recognized.

Serial Configuration Port

The thumbwheel switches must be positioned in the center of the detent. You can verify the switch settings by displaying register 32.
The serial CONFIG port on the front of the MBCN can be used to:
update the firmware on the MBCN
update the FPGA (field programmable gate array) configuration on
the MBCN
Note: you normally update both using ControlFlash over ControlNet.
The serial cable for a standard PC COM port must have lines 2 and 3 swapped. It does not require any handshaking. Pins 2 and 3 are wired the same as a PC 9-pin COM port. A cable is provided with the MBCN when shipped in the original packaging.
1 2 3 4 5
1
6
2
7
3
8
4
9
5
Figure 1 Serial Cable Wiring
Connect to the serial port using any communication software. For example, you can use the HyperTerminal program supplied with Windows. The MBCN serial port supports a baud rate of 57.6 Kbaud, with no parity, 8 data bits and 1 stop bit.
Refer to page 73 for information on updating MBCN firmware.
Publication number DSMBCN-UM001B-EN-P February 2003

NAP Port

AutoMax ControlNet Module Page 15
The MBCN has a standard ControlNet NAP port to allow a transient node to connect to the ControlNet network.
Use the NAP port on the MBCN if you want to attach a transient node to the network and you do not want to rewire the network. Do not connect any node to the network using both the NAP port and a coax path at the same time. The following figure shows how to correctly connect a transient node.

ControlNet Connectors

Network Status LEDs

NAP Connection 1
You can also use the NAP port on the MBCN to attach the MBCN to an existing network, by connecting to the NAP port on a node on the existing network.
The NAP cable has 8 conductors and a shield, with RJ-45 connectors at each end. The cables are reversed from one end of the cable to the other, so that 1->8, 2->7, etc. Maximum cable length is 10 m.
Connect the MBCN to the ControlNet network using the standard ControlNet BNC connectors.
There is one network status (COM) LED for each network connector.
The network status LEDs display the following states, using the priority scheme shown. If more than one condition exists, the LEDs display the state with the highest priority.
When using redundant cabling, both LEDs should be green. One will be brighter; this is the active channel.
Publication number DSMBCN-UM001B-EN-P February 2003
Page 16 AutoMax ControlNet Module
The LEDs do not reflect the state of the NAP port. If you connect the MBCN to the network via the NAP port, the two network status LEDs flash red together.
Priority State How to view Cause
1
(highest)
2 Both steady
3 Alternating
4 Alternating
5 Steady off Channel disabled or channel
6 Flashing
7 Flashing
8 Flashing
9
(lowest)
Both steady off
red
red/green
red/off
red/green
red/off
green/off
Steady green
Viewed together
Viewed Independently
Reset or no power
Failed link interface
Fatal error on MBCN
Self test
Bad node configuration, such as duplicate address
not supported
Invalid link configuration, such as address > UMAX
Link fault or no MAC frames received
Temporary channel error, or listen only
Normal operation
Figure 2 LED Status Table

7-Segment LED Codes

Value Meaning
1 NAM not attached. There are no other nodes
on the network.
2 Keeper faulted master. The MBCN schedule
needs to be updated using RSNetWorx.
3 Keeper faulted backup. The MBCN schedule
needs to be updated using RSNetWorx.
4 Keeper change
5 Keeper faulted change
6 Keeper temporary state
b Inactive. The MBCN is online but has no
scheduled connections and is not sending or receiving messages.
Publication number DSMBCN-UM001B-EN-P February 2003
AutoMax ControlNet Module Page 17
Value Meaning
C Communication error
d One or more connections requires a schedule.
Use RSNetWorx to schedule all connections.
E Bad thumbwheel value
P Scanning in program mode
U Firmware on the MBCN is being updated
H Hardware on the MBCN is being updated.
r Module requires reset, usually after an update.
Cycle power to the rack that contains the MBCN.
.0 Module checksum failure
.1 Local RAM data failure
.2 Local RAM address failure
.3 Local RAM FF fill failure
.4 Local RAM 00 fill failure
.5 Code copy failure
.6 Shared RAM failure
.7 Shared RAM address failure
.8 Shared RAM FF fill failure
.9 Shared RAM 00 fill failure
.A Module startup failure
.b Bootup shell activate prompt
.C Board reset failure
.d AutoMax watchdog failure
.E Power fail
.F Module hardware failure (jabber inhibit, host
watchdog). Cycle power to see if the problem disappears. If it does not, replace the MBCN.
Off Scanning OK in run mode
Figure 3 7-Segment LED Codes
LED codes that start with a dot are hardware failures and usually indicate that the MBCN has suffered a fatal hardware or firmware failure. Contact technical support.
Publication number DSMBCN-UM001B-EN-P February 2003
Page 18 AutoMax ControlNet Module

Communication Error

The following are common causes for communication error ( C ) to be displayed on the 7-segment LED:
The MBCN couldn’t open one or more connections. Look at the status for each connection in RSNetWorx or on the MBCN
The MBCN has refused a connection or has returned an error to an unscheduled message. Look at the status for each connection using RSNetWorx or the status registers on the MBCN or look at the status of the connections on other nodes that have connections to the MBCN.
The MBCN is sending unscheduled messages that are failing.
Publication number DSMBCN-UM001B-EN-P February 2003

Prevent Electrostatic Discharge

The MBCN is sensitive to electrostatic discharge.
ATTENTION: Electrostatic discharge can damage integrated circuits or semiconductors if you touch backplane connector pins. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential
AutoMax ControlNet Module Page 19

Installation

Wear an approved wrist-strap grounding device
Do not touch the backplane connector or connector pins
Do not touch circuit components inside the module
If available, use a static-safe work station
When not in use, keep the module in its static-shield packaging
This chapter contains the information necessary to:
install the MBCN in the AutoMax rack
connect the MBCN to the ControlNet network
use the MBCN serial port
understand the MBCN LEDs
Publication number DSMBCN-UM001B-EN-P February 2003
Page 20 AutoMax ControlNet Module

Installation and Wiring

The user is responsible for conforming to all applicable local, national, and international codes. Wiring practices, grounding, disconnects, and over-current protection are of particular importance. Failure to observe this precaution could result in severe bodily injury or loss of life.
To reduce the possibility of electrical noise interfering with the operation of the control system, exercise care when installing the wiring from the control system to the external devices. For detailed recommendations, refer to IEEE 518.
Step 1. Stop any application tasks that may be running.
This equipment is at line voltage when AC power is connected. Disconnect and lock out all ungrounded conductors of the AC power line. Failure to observe this precaution could result in severe bodily injury or loss of life.
DANGER
DANGER
WARNING
Inserting or removing a module may result in unexpected machine motion. Power to the machine should be turned off before inserting or removing a module. Failure to observe these precautions could result in bodily injury.
Step 2. Turn off all power to the rack. All power to the rack as well as all power leading to the rack should be off.
CAUTION
This module contains static sensitive components. Careless handling can cause severe damage. Do not touch the connectors on the back of the module. When not in use, the module should be stored in an anti­static bag. The plastic cover should not be removed. Failure to observe this precaution could result in damage to or destruction of the equipment.
Step 3. Take the MBCN out of its shipping container. Take it out of the anti-static bag, being careful not to touch the connectors on the back of the MBCN.
Publication number DSMBCN-UM001B-EN-P February 2003
Step 4. Set the MBCN’s address on the network using the thumbwheels. Make sure the thumbwheels are centered on the detents.
Step 5. Insert the MBCN in the desired slot in the rack, making sure that it is well seated in the rack. Use a screwdriver to secure the MBCN in the rack.
Step 6. Connect the MBCN to the ControlNet network using the BNC connectors on the front of the MBCN.
Step 7. Turn on power to the rack.

Connecting to the Network

Connect the MBCN to the ControlNet network like any other ControlNet node, using a ControlNet tap to connect to the network trunkline. The drop cable from the tap to the MBCN should be 1 m long. The recommended trunk cable type is RG6. (It is recommended that you use standard ControlNet network taps available through Allen-Bradley.)
The physical ends of the network trunkline should be terminated with 75-ohm terminators. There should be two and only two terminators on the network.
AutoMax ControlNet Module Page 21
The MBCN supports redundant cabling.
Ensure that the address for the MBCN is less than or equal to the maximum unscheduled address (UMAX) configured on the network.
NOTE: 0 is not a valid address.
If the MBCN is being used as a scanner or for scheduled I/O, make sure the address is less than or equal to the maximum scheduled address (SMAX) configured on the network.
To maximize efficiency on the ControlNet network, assign consecutive node addresses to nodes on the network, with the nodes exchanging scheduled data at the lowest addresses.

Troubleshooting Wiring Problems

If the MBCN does not go active on the network:
Check cabling for correct wiring to the MBCN.
Check network termination. Only the two nodes at the physical ends
of the network should have terminating resistors. There should be two and only two terminators on the network.
Check the network configuration. Make sure UMAX is high enough to include this node.
Check that you haven’t duplicated the address of another node on the network.
Check that the thumbwheels have been read correctly by displaying register 32.
Publication number DSMBCN-UM001B-EN-P February 2003
Page 22 AutoMax ControlNet Module
The following steps describe the procedure for using the MBCN as a scanner. The sections that follow describe the procedures and registers in more detail.
Step Description Refer to

Quick Start

page:
Step 1. Use RSNetWorx to create a configuration that
contains the I/O devices the MBCN is to scan and the scheduled produced and consumed connections for the MBCN.
Step 2. Download the configuration to the MBCN. 32
Step 3. Check the NAM state for online. 60
Step 4. Put the MBCN in run mode. 32
Step 5. Verify you can read input data and set output
data, check connection status, and so on.
24
32,35
Publication number DSMBCN-UM001B-EN-P February 2003

Overview

Memory Overview

AutoMax ControlNet Module Page 23

Programming the MBCN

This section is a guide for configuring and programming the MBCN.
Configure the scheduled connections using RSNetWorx. The configuration you create contains all the I/O devices to be scanned, and all the scheduled produced and consumed connections on the MBCN, the network parameters and the schedule for all updates.
This section starts with some general information, then describes the MBCN memory layout in detail, with information about the interface between your application and the MBCN, and the organization of the tables on the MBCN.
The MBCN contains 64 Kbytes (32768 16-bit registers) of shared memory that can be accessed through the AutoMax rack backplane by application tasks running on an AutoMax processor. The following table shows the general organization of the shared memory.
AutoMax Registers Description
0-63 Status and control
5 Module control register
64-7383 Unscheduled data
9216-9245 ID area
9247 Channel state
9248-9263 Active node list
9280-9292 Pending network parameters
9304-9316 Current network parameters
9336-9339 Error log
9344-9401 Diagnostic counters
9466 Serial port state
9468-9471 Revision information
9472 Module state
9473 NAM state
9474-9475 Host watchdog
9476 Keeper state
9477 Flash state
Publication number DSMBCN-UM001B-EN-P February 2003
Page 24 AutoMax ControlNet Module
AutoMax Registers Description
9478 Link timeout
15362-15614 Status for each connection
15744-15760 Overall status information
16384-24575 Scheduled receive data
24576-32767 Scheduled transmit data
Figure 4 Memory Overview

Configuring Scheduled Connections

The MBCN can act as a ControlNet scanner to scan I/O modules. As well, scheduled connections can be configured to exchange data with other scanner nodes on the network.
You use RSNetWorx to configure your network. The following sections briefly describe how to configure commonly occurring devices. For detailed information, refer to the RSNetWorx documentation and online help.

Creating a Configuration

You can use RSNetWorx as an offline or online configuration tool. In most cases you will use it online. The instructions that follow describe using RSNetWorx online. They assume that RSNetWorx and RSLinx have been installed, along with any hardware required to communicate with the ControlNet network.
1. Run RSNetWorx.
2. Create a new configuration using the File/New command.
3. Put RSNetWorx online using the Network/Online command.
4. Select a path to the network. RSNetWorx should go online and display the devices it finds on the network.
5. Click on the MBCN you are configuring to select it, right click on it and select Scanlist Configuration from the menu that appears. RSNetWorx asks whether you want to switch to Edit Mode. Click Yes.
6. The MBCN Scanlist Configuration Tool opens. There are two tabs – the Connection Configuration tab, which shows all the connections for the device you are configuring, and the Connection Status tab, which shows the status of those connections.
7. Select the Connection Configuration tab to create connections.
The device you are configuring, in this case the MBCN, is shown highlighted. The other devices are shown as a list.
Publication number DSMBCN-UM001B-EN-P February 2003
Loading...
+ 56 hidden pages