Rockwell Automation 937CU-AITXF-DC1 User Manual

937CU-AITXF-DC1 Installation Instructions
Transmitter Supply Converter
Symbols Used
Warning
Attention
Note
Bul. 937C Transmitter Supply Converter Installation Instructions
This symbol warns of possi Failure to heed this warning may result in personal injury or death, or property damage, including destruction.
This symbol warns the user of a possible fault.
to heed this warning can lead to total failure of the device and any other
Failure connected equipment.
This symbol draws attention to important information.
ble danger.
1
Safety Notes
Attention
Attention
Bul. 937C Transmitter Supply Converter Installation Instructions
The Transmitter Supply Converter must only be operated by trained personnel in accordance with this handbook.
The protection of operating personnel and of the system is only accordance with their intended purpose. Any other type of operation than that described in this manual places the safety and functionality of the devices and systems connected to them in question.
The devices may only be installed, connected, and a hazardous area.
ensured if the devices are used in
djusted by electrical professionals outside the
2
Attention
Warning
Note
If faults cannot be eliminated, the devices must be taken out of operation and protected from being placed in service again dangerous and therefore not permitted. They render the warranty void.
The responsibility for the adherence to local
Note
inadvertently. Tampering with or making changes to the devices is
safety standards lies with the operator.
Bul. 937C Transmitter Supply Converter Installation Instructions
ation and Connection
Install
Application Information
Bulletin 937 Intrinsically Safe Barriers transmit si gnals between field devices and a process control system/control system.
They are suitable for the connection of field devices used in potentially explosive atmospheres. Safe field circuits for these devices are intrinsically safe and are galvanically isolated from non-intrinsically safe circuits. establish an electroma gnetic separation be tween the potentially explosive atmospheres and the safe areas in a system.
The transmitter supply coverters are measuring units that
provide an output signal consisting of a unit current signal (4 mA ... 20 mA). A transmitter power supply provides a transmitter with power and processes the current signal.
The transmitter supply conerter translates a fully parameterizable partition of input signal into a proportional output current (4ma...20mA)
This output signal will be transferred to indicators or to analog inputs on the process control system/control system, for example. Both relay outputs of the transmitter supply converter can monitor two fully parameterizable trip values of the input signal.
3
Bul. 937C Transmitter Supply Converter Installation Instructions
Installa
tion
The Transmitter Supply Converter can be mounted on a 35 mm standard rail corresponding to DIN EN
60175. The devices must be snapped onto the rail vertically, and never slanted or tipped to the side.
CORRECT: Device snapped on vertically.
INCORRECT: Device snapped on from the side. Can damage
the contacts and cause the device to fail.
4
Bul. 937C Transmitter Supply Converter Installation Instructions
Connection
The removable terminals of the Bulletin 937 Converters simplif y the connection and the switch cabinet assembly. They make it possible to replace devices quickly and without error if a customer service becomes necessary.
Terminals are equipped with screws, are self- opening , have a large connection area for a wire cross-section up to 2.5 mm/14 AWG and coded plugs, making it impossible to mix them up.
Connection terminals (Input) IS Side
The intrinsically safe field circuit is connected to the blue terminals 1 and 3. These may be g uided into the potentially explosive areas with connector cables in accordance with DIN EN 60079-14. Terminal 2 is always left unconnected.
The non-intrinsically safe field circuit is connected to the black terminals 1
Yo u c an co nn e ct :
a 3-wire transmitter
a 2-wire transmitter with HART
an active current source
through 3.
1
2
3.
HART
mA
1+
2-
3
mA
Zone 0, 1, 2
Div. 1, 2
Power Rail
ERR 24 V DC
5
Bul. 937C Transmitter Supply Converter Installation Instructions
Connection (Output) Safe Side
The functions of the other black terminals are as
follows:
The control circuit and the power supply are connected to the b te
rminals 7 to 24
The terminals have the following functions:
• Terminals 7/8: current output (terminal 9 not used)
• Terminals 16 ... 18: relay 2
24 V DC power supply
Terminals 4 ... 6, 13 ... 15 and 19 ... 21 do not exist
6
.
Terminals 10 ... 12: relay 1
Terminals 23/24: (terminal 22 not used)
lack
1+
2-
3
Power Rail
ERR 24 V DC
10 11
I
12
16 17
II
18
7-
mA
III
8+
23+
24 V DC
24-
Zone 2
Div. 2
Bul. 937C Transmitter Supply Converter Installation Instructions
Front
The following indicating and operating elements are located on the front of the
Transmitter Supply Converter:
ED CHK (red) to indicate a device fault
• L
• LED PWR (green) to indicate the presen
• LED OUT 1 (yellow) to indi
• LED OUT 2 (yellow) to indi
RS 232 serial interface for a connection to a PC for setting parameters
cate that relay 1 is active cate that relay 2 is active
and diagnosis of the transmitter supply converter using FDT.
• Display for indicati
parameteri
on of the measured values, fault messages and
zation modi
• Four keys for setting the parameters of the transmitter supply converter:
(Up)
(Down) ESC (Escape) OK
ce of
the supply voltage
1 234 5
PWR
ERR
1 2
OUT
RS232
7 8 9
13
14 15
192021
10 11 12 16 222324
6
ESC
OK
17 18
7
Bul. 937C Transmitter Supply Converter Installation Instructions
Display modes and error messages
In normal operation, the current measured value is indicated in the selected unit.
If the Alarm freeze is triggered but the device continues operating normally, a corresponding message appears in the second line of the display.
If a fault occurs, one of the following messages is displayed until the fault is rectified (when parameterized):
Err Mem for device fault,
Err LB for lead breakage,
Err SC for short circuit,
The relays de-energizes when a fault occurs.
The display of the device is updated at regular intervals. This can causes a short flickering of the display. This flickering isn't a defect of the display.
Note
Editing Device Data
WARNING: A change in device data will change the operation of the device! WARNING: Before entering new data into the device, you should therefore as
certain that no danger to the installation will result.
FDT Interface
This manual describes Parameterization mode of the universal frequency converter using the control panel. parameterization mode for the universal frequency converter is more convenient with a PC using Field Device Tool (FDT) software.
Some specialized functions can only be selected using the FDT , for instance, pulse suppression
as an alternative to the start-up override. The FDT interface is the specification describing the standardized data exchange between devices and control system or engineering or asset management tools. Examples include: PACTwareTM , FieldCare,
FactoryTalk AssetCentre, and Process Device Configuration. FDT frame software can be downloaded from the web: www.pactware.com www.fdtgroup.org. PACTwareTM is trademark of PACTware Consortium
8
Parameterization mode control panel
Programming
Bul. 937C Transmitter Supply Converter Installation Instructions
Main menu parameterization mode
Display mode
You can return to display mode from any point in the menu in parameterization mode by pressing the ESC key (possibly multiple times). If you do not press any key for 10 m parameterization mode, the device automatically switches back into display mode.
OK + ESC (simultaneously, 1 sec)
ESC
Unit ()
Input ()
Output
Service
inutes in
9
Loading...
+ 25 hidden pages