Rockwell Automation 937CU-AIHLP-DC1 User Manual

937CU-AIHLP-DC1 Installation Instructions
HART Loop Converter
Symbols Used
Warn ing
Warn ing
Attention
Caution!
This symbol indicates a possible fault.
Non-observance could interrupt devices and any connected facilities or systems, or result in their complete failure.
Bul. 937C HART Loop Converter Installation Instructions
Danger!
This symbol indicates an imminent danger.
Non-observance will result in personal injury or death.
This symbol warns of possible danger. Failure to heed this warning may result in personal injury or death, or property damage, including destruction.
Warning!
This symbol indicates a possible fault or danger.
Non-observance
may cause personal injury or serious property damage.
Note
This symbol draws attention to important information.
1
Safety Notes
Warn ing
Attention
Attention
Attention
Warn in g
Attention
Warn in g
Note
Note
Bul. 937C HART Loop Converter Installation Instructions
The HART Loop Converter must only be operated by trained personnel in accordance with this handbook.
The protection of operating personnel and of the system is only ensured if the devices are used in accordance with their intended purpose. Any other type of operation than that described in this manual places the safety and functionality of the devices and systems connected to them in question.
The devices may only be installed, connected, and adjusted by electrical professionals outside the hazardous area.
If faults cannot be elimina ted, the devices must b e taken out of operation and protected from being placed in service again inadvertently. Tampering with or making changes to the devices is dangerous and therefore not permitted. They render the warranty void.
The responsibility for the adherence to local safety standards lies with the operator.
2
Bul. 937C HART Loop Converter Installation Instructions
Reference to further documentation
Laws, standards, or directives applicable to the intended use must be observed. In relation to hazardous areas, Directive 1999/92/EC must be observed.
The corresponding data sheets, declarations of conformity, EC-type-examination certificates, certificates and Control Drawings if applicable (see data sheet) are an integral part of this document. You can find this information under www.ab.com. Due to constant revisions, documentation is subject to permanent change. Please refer only to the most up-to-date version, which can be found under www.ab.com.
Marking
HART Loop Converter
Certification under Pepperl+Fuchs GmbH
Lilienthalstrasse 200, 68307 Mannheim, Germany
KFD2-HLC-Ex1.D.2W (937CU-AIHLP-DC1)
BASEEFA 07 ATEX 0174 , for additional certifications, see www.ab.com
E II (1)GD [Ex ia] IIC, [Ex iaD]
Pepperl+Fuchs Statement of Conformity
E II 3G Ex nA II T4 X
Intended Use
The devices are only approved for appropriate and intended use. Ignoring these instructions will void any warranty and absolve the manufacturer from any liability.
The device must only be operated in the ambient temperature range and at the relative humidity (non-condensing) specified.
The de
vices are used in Control &Instrumentation (C&I) technology for the galvanic isolation of C&I signals such as 20 mA and 10 V standard signals or alternatively for adapting or standardizing signals. Devices that incorporate intrinsically safe circuit are used for operating intrinsically safe field devices in hazardous areas.
3
Improper Use
Protection of the operati is not being used according to its intended purpose.
equipment is not suitable for isolating signals in high current
The is noted
Mounting/Installation
Prior to mounting, installation, and commissioning o familia The device must not be installed at locations where corrosive vapors may be present. The devices fulfill a degree of protection IP 20 according to IEC/EN 60529. The devices are designed for use in pollution degree 2 and overvoltage category II as per IEC/EN 60664-1. If used in areas with higher pollution degree, the devices need to be protected accordingly. Only use power supplies that provide protection against direct contact (e. g. SELV or PELV) for the connection to power feed modules. Observe the tightening torque of the terminal screws. The installation instructions in accordance with IEC/EN 60079-14 must be observed. Intrinsically safe circuits of associated apparatus (installed in safe areas) can be led into hazardous areas, whereby special attention must be paid to maintain separation distances to all non-intrinsically safe circuits according to the requirements in IEC/EN 60079-14. All separation distances between two adjacent intrinsically safe circuits need to be observed in accordance with IEC/EN 60079-14. If "Ex i" protected circuits (intrinsically safe) were operated with non-intrinsically safe circuits, they must no longer be used as "Ex i" protected circuits.
4
ng personnel and t
separately
r with the
corresponding dat
in the
device and carefully read the instruction manual.
h
7C HART Loop
Bul. 93
e overall system is not ensured if the product
asheet.
f the device you shou
ter
Conver
applications
Installation Instructions
unless
this
ld make
yourself
Bul. 93
7C HART Loop
Converter Installation
Instructions
T
he respective to e devices with intrinsically safe circuits of associated apparatus (verification of intrinsic safety). Make sure to observe IEC/EN 60079-14 and IEC/EN 60079-25.
If more channels of one connection is made directly at the terminals of the device. When verifying the intrinsic safety, the maximum values for the parallel connection must be considered.
peak values of the field device and the assoc
x
plosion protection should be considered when connecting intrinsically safe field
nected i
device are con
n parallel, make sure the parallel
iated apparatus with regard
Operation, Maintenance, Repair
he devices must not be repaired, changed or
T product must always be replaced with an original device.
nipulated. If there
ma
Delivery, Transport, Disposal
C
heck the packaging and contents for damage.
Check if
Keep the original packaging. Always store and transport the
Alway temperature (see data sheet) must be considered.
Disposing in compliance with the applicable laws and guidelines of the respective country.
a
ve received every item and if the items received are the ones you ordered.
you h
n
s store the device in a clean a
of devices, packaging material, and possibly contained batteries must be
d dry environment. The permitted storage
device in the original packaging.
a defect, the
is
5
Product Specifications
Function
The
HART Loop Converter is an isolated barrier suitable for intrinsically safe applications
The device supplies f
The device analyzes u variables can be transformed into varying current signals from these four HART variables. These signals are used to display the values via the analog inputs of the process control system.
The device is easily configured by the use of key software.
In addition to the current outputs, the device has two changeover contacts. These changeover contacts can be programmed so that the changeover contacts function as trip values for the HART variables
Bul. 937C HART Loop Converter Installation Instructions
ield devices and can be connected in parallel to existing HART circuits.
p to four HART variables (PV, SV, TV, QV). Three HART
pad or with the FDT configuration
6
Product Specifications
Assembly
Operating and indicating elements
9
8
7
6
OUT
RS232
1 2
ERR PWR
1 2
3 4
7 8 9
13
14 15
192021
Bul. 937C HART Loop Converter Installation Instructions
1
3
6
4 5
2
ESC
10 11 12 16
17 18
222324
OK
3
4
5
7
Bul. 937C HART Loop Converter Installation Instructions
1 Removable terminals, blue
2
LC display Display for showing
3
Keypad
ESC
OK
4
Place for labeling
5
Removable terminals, green
6
Programming socket RS 232 serial interface for a connection to a PC for
7
yellow LEDs Outputs Out 1 ... 4, indicating relay status
8
red LEDs Indicating faults
9
green LEDs Indicating power supply
the measured values
the current output values
the fault messages
the parameterization mode
Four keys for selecting the displayed values,
output values and for setting the parameters of the
device Up
Down
Escape
Confirmation
setting parameters and diagnosis of the device using
FDT
the current
8
Product Specifications
Dimensions
Housi
Bul. 937C HART Loop Converter Installation Instructions
ng
40 mm (1.6")
115 mm (4.5'')
46 mm (1.82'')58 mm (2.28'')
104 mm (4.1'')
119 mm (4.7'')
Number of terminal blocks max. 10
Dimension drawing with screw terminals
When using screw terminals with test sockets the device is 124 mm (4.9 in) in height.
When using
spring terminals the device is 131 mm (5.16 in) in height.
9
Bul. 937C HART Loop Converter Installation Instructions
Ins
tallation
DIN Mounting Rail
The devices are mounted on a 35 mm DIN mounting rail according to EN 60715.
Example: DIN mounting rail(35 mm x 15 mm)
Power Rail
To reduce wiring and installation costs, Power Rail is the optimum solution. The Rail is a DIN mounting rail with plastic insert, that delivers power to the devices (24 V DC) and transfers bus signals and a collective error message.
The Power Rail is factory-equipped with cover and open segments of the Power Rail. Thus, the Power Rail is protected from contamination. Additionally the cover and end caps prevent that electrically conductive parts come in contact with the Power Rail.
and end caps. These parts cover empty
Power
10
Power Rail is available in two sizes:
Power Rail 937A-PR08 and 937A-PR20
Th
ree leads:
two conductors for power
one conduct
or for collective error messaging
Power Rail
Bul. 937C HART Loop Converter Installation Instructions
11
Mounting
Mounting the Isolated Barrier
Snap the device onto the DIN mounting rail in figure below.
Bul. 937C HART Loop Converter Installation Instructions
a vertical downward movement. See
CORRECT: Device snapped on vertically.
Mounting the Terminal Blocks
The insulation o replace the terminal blocks, observe the rated insulation voltage. If the rated voltage greater than 50 V AC, proceed as follows:
1. Switch off
2. Connect the terminal blocks or disconnect the terminal blocks.
12
INCORRECT: Device snapped on from the side.
Can damage the contacts and cause the device to fail.
f the removable terminal blocks protect against direct contact. If you
the voltage.
Bul. 937C HART Loop Converter Installation Instructions
Connection
The removable terminal blocks simplify connection and control cabinet construction significantly. These with core cross-sections of up to 2.5 mm² (14 AWG). The terminal blocks are coded with red coding pins so misconnection of terminal blocks are eliminated.
terminal blocks offer adequate space for the connection of leads
Input Connection (field circuit)
Connecting the Field Circuit
1. Connect the field circuit to the blue terminals.
2. Observe the tighteni
0.5Nm ...0.6Nm.
The intrinsically safe fie lines in accordance with DIN EN 60079-14. You can connect the following field devices:
1.
any separately supplied HART current circuit with transmitter or positioner connected in parallel
Connection to terminals 2 and 3
a HART-capable active curre
2.
transmitter Connection to terminals 2 and 3 with bridge between terminals 5 and 6
3.
a 2-wire HART measuring transmitter, e. g
output signal of 4 mA ... 20 mA The HART measuring transmitter is supplied by the isolated barrier Connection to terminals 1 and 3
ng torque of the terminal screws. The tightening torque is
ld circuit may be routed in the hazardous area with connection
nt source, e. g., a separately supplied HART measuring
., HART measuring transmitter with an analog
with bridge between terminals 4 and 5
13
HART
Bul. 937C HART Loop Converter Installation Instructions
+
+
-
+
mA
-
HART
1+
2+
HART
­3-
4
5
250 Ω
6
Zone 0, 1, 2 Div. 1, 2
Power Rail
ERR 24 V DC
14
Loading...
+ 36 hidden pages