Rockwell Automation 937CS-AITMP-DC1 User Manual

937CS-AITMP-DC1 Installation Instructions
Universal Temperature Converter
Symbols Used
Warn ing
Warn ing
Attention
Note
Bul. 937C Universal Temperature Converter Installation Instructions
This symbol warns of possible danger. Failure to heed this warning may result in personal injury or death, or property damage, including destruction.
This symbol draws attention to important information.
1
Safety Notes
Warn ing
Attention
Attention
Attention
Warn in g
Attention
Warn in g
Note
Note
2
Bul. 937C Universal Temperature Converter Installation Instructions
The Universal Temperature Converter must only be operated by trained personnel in accordance with this handbook.
The protection of operating personnel and of the system is only ensured if the devices are used in accordance with their intended purpose. Any other type of operation than that described in this manual places the safety and functionality of the devices and systems connected to them in question.
The devices may only be installed, connected, and adjusted by electrical professionals outside the hazardous area.
If faults cannot be elimina ted, the devices must b e taken out of operation and protected from being placed in service again inadvertently. Tampering with or making changes to the devices is dangerous and therefore not permitted. They render the warranty void.
The responsibility for the adherence to local safety standards lies with the operator.
Bul. 937C Universal Temperature Converter Installation Instructions
Overview
The devices of the Bul. 937C IS Barriers, Isolators and Converters are used to transmit signals between field devices and the process control system or control.
The Bulletin 937 devices are suitable for connection to field devices in the hazardous area. The field current circui not intrinsically safe circuits. The devices thus represent an electrical isolation between the hazardous area and the secure area.
Further information (e. g. certificates, the data sheets for the Universal Temperature Converter and the operating instructions can be found on www.ab.com.
ts of these devices are intrinsically safe and are galvanically isolated from the
The temperature converter is used for temperature measurement.
Resistance temperature detectors, thermocouples, potentiometers or voltage sources can be connected to the inputs of the converter.
The Universal Temperature Converter converts the input signals into proportional current signals. The output signals can, for example, be for-warded to displays or analog inputs of the process control system.
3
Mounting
Attention
Bul. 937C Universal Temperature Converter Installation Instructions
The Universal Temperature Converter is constructed in protection class IP20 and must therefore be protected fr small foreign objects).
om undesirable environmental conditions (water, dust,
The Universal Temperature Converter can be mounted on a 35 mm top-hat rail corresponding to DIN EN
50022. The devices must be snapped onto the rail
Further mounting alternatives, e. g. using the Power Rail, can be found in the operating instructions for the Bul 937 at www.ab.com.
CORRECT: Device
snapped on vertically.
vertically, and never slanted or tipped to the side.
INCORRECT: Device snapped on from the side. Can damage the contacts and
cause the device to fail.
4
Bul. 937C Universal Temperature Converter Installation Instructions
20
115
Connection
The slip-off terminals significantly simplify connection and construction of switching cabinets. They allow free exchange of the unit when service is needed.
The terminals can be screwed on, are self-opening, and have generous connection room for a wire diameter of up to 2.5 mm² and coded plugs, so that leads cannot be confused.
Intrinsically safe field circuits are connected to the blue terminals 1 to 6 of the Universal Temperature Converter. These may be conducted using DIN hazardous area.
Non-intrinsically safe field circuits are connected to the black terminals 7 to 15
Only one sensor can be connected to the Universal Temperature Converter.
EN 60079-14-compliant leads into the
of the Universal Temperature Converter.
quick and error-
111
118
5
Mounting and Connection
Bul. 937C Universal Temperature Converter Installation Instructions
following
The
• Resistance temperature sensors
Pt10, Pt50, Pt100, Pt500, Pt1000
according to EN 60751: 1995 or GOST 6651-94
Ni 100 according to DIN 43760
Cu10, Cu50, Cu100 according to
GOST P50353-92
in 2-wire, 3-wire or 4-wire technique
• Thermocouples
Type B, E, J, K, N, R, S, T according to
IEC 584-1: 1995
Type L according to DIN 43710
Type TXA, TXK, TXKH according to
GOST P8.585-2001
or a cold junction compen
F r
equire accessory instead of terminal block 1 to 3 or 4 to 6.
• Potentiometers (800 - 20 k) in 3-wire
technique
• Sources for voltage signals between
-100 mV and +100 mV
sensors
the
937A-TCJC ter
can be connected
n (CJC), you
satio minal blo
th
e normal
:
ck as an
2- 3+
2-1- 3+
equal lead resistances
2-1- 3+ 4+
2-1+
937A-TCJC
2-13+
equal lead resistances
2-1+
6
Bul. 937C Universal Temperature Converter Installation Instructions
The remaining black terminals have the following functions (10,11,12 NA):
1 2 3
4 5 6
RS 232
14 15
14,15 Power supply 24 VDC
7
8
9
10
11
12
7
8
10
11
7,8 Current output, source
7,9 Current output, sink
7
Bul. 937C Universal Temperature Converter Installation Instructions
If a current output is operated as a sink, the voltage across the terminals must be between 5 V and 30 V. An additional resistance is only required if the voltage is above 16.5 V. The resistance must be between (U - 16.5 V)/0.0215 A and (U - 5 V)/0.0215 A (see diagram).
Example: U = 24 V (24 V - 16.5 V)/0.0215 A = 350 (24V - 5V)/0.0215A = 880
R []
1200
1000
800
600
400
200
0
16 20 25 30
U [V]
Resistance area
8
7C
Bul. 93
Universal Temperature Converter Installation Instructions
If a current output is operated as a source, the load resistance must be between 0 and 550 (535 if the output format is 4 mA to 20 mA unlimited).
Controls and indicators of the Universal Temperature Converter
Front panel of the universal temperature converter:
• LED ERR 1 (red) to indicate
a lead fault at input 1 (terminals 1 to 3; flashes red)
the simulation mode (flashes red)
a device fault (steady red)
• LED PWR (green) to indicate the supply voltage
USB interface to connect to a PC for parameterization and
• diagnosis of the universal temperature converter using FDT
9
Bul. 937C Universal Temperature Converter Installation Instructions
Configuration tools
The Bul 937CS-AITMP-DC1 Universal Temperature Converter is parameterised using an FDT configuration tool such as PACTwareTM.
Installation and connection with the device
Install the FDT software (ie PACTwareTM) on a PC. Connect the PC and the Bul 937CS-AITMP-DC1 using the 937A-USBA USB cable. This cable can be ordered as an accessory.
Pressing the plug in by force may damage the end devices.
Connect the cable with the jack plug to the USB interface on the front panel of the Bul 937CS-AITMP-DC1. At the PC, connect the USB connector to a free USB interface port.
FDT Interface
This manual describes Parameterization mode of the universal temperature converter using the control panel. parameterization mode for the universal frequency converter is more convenient with a PC using Field Device Tool (FDT) software.
Some specialized functions can only be selected using the FDT .
The FDT interface is the specification describing the standardized data exchange between devices and control system or engineering or asset management tools. Examples include: PACTwareTM , FieldCare,
FactoryTalk AssetCentre, and Process Device Configuration. FDT frame software can be downloaded from the web: www.pactware.com www.fdtgroup.org.
PACTwareTM is trademark of PACTware Consortium
10
7C
Bul. 93
Universal Temperature Converter Installation Instructions
Communication driver
In a PACTwareTM project, communication with a 937CS-AITMP-DC1 is only possible via the communication driver P2P USB FDT. If your project does not yet contain such a driver, please add it to the project from the device catalogue (see "PACTwa reTM process automation
configuration tool" manual).
The parameters of the communication DTM is the used PC interface and the number of retries. The parameter is set as follows:
• Double-click the P2P RS232 FDT driver with the mouse
• Select the Communication Port
Communication Retries: number of retries the COM DTM attempts to establish communication to the connected device.
To add a 937CS-AITMP-DC1 to a project, select a P2P RS232 FDT driver of the project.
Then add the 937CS-AITMP-DC1 from the device catalog.
Further information on the individual steps can be found in the "PACTwareTM process automation configuration tool" manual.
The description in the following chapter assumes that a 937CS-AITMP-DC1 has been selected
in the project.
11
Bul. 937C Universal Temperature Converter Installation Instructions
Measured value
If you have started the communication between PACTwareTM and device (e. g. via Device data Establish connection), you can open the Measured value window via Device data → Measured value.
It shows the following information on the outputs of the 937CS-AITMP-DC1 Universal Temperature Converter:
• Measured values at the inputs as numerical values and bar graph, displayed in the selected units.
• Values of the analogue outputs as numerical value and bar graph, displayed in the selected unit.
12
Bul. 937C Universal Temperature Converter Installation Instructions
Simulation
If you have started the communication between PACTwareTM and Bul. 937CS-AITMP-DC1 (e. g. via Device data Establi sh connection), you can open the Simulation window via Device dataSimulation.
Warning
The simulation interrupts the normal function of the device! Before starting the simulation, make sure that no dangerous condi tion in the plant will result.
The simulation mode is started with the check box Simulation Active.
You can now specify output currents or output voltages for testing purposes. Press Enter to take over the set numerical value.
Use the check box Simulation Active to end the simulation.
If the power supply is interrupted, the device ends the simulation.
You can close the simulation window with the Close button or by clicking on the Windows-standard button at the top right. The device will remain in simulation
Note
mode, however, until you select Simulation Off again.
13
Diagnosis
Bul. 937C Universal Temperature Converter Installation Instructions
If you have started the commun ication between PACTwareTM and Bul. 937CS-AITMP-DC1 (e. g. via Device data Establish connection), you can open the Diagnosis window via Device data Diagnosis. It shows the following information:
Explanations:
Memory error: error in the memory of the Bul. 937CS-AITMP-DC1; if this error was caused by
an incorrect data transfer, you can eliminate it via Device data Additional functions Service (see section Service); otherwise, please contact Rockwell Automation
Internal device error: please contact Rockwell Automation
Redundancy error: only if Redundancy active has been selected (see Menu Input Extras) in the case of a lead fault at both inputs (see below)
Simulation mode: see Simulation section
14
Bul. 937C Universal Temperature Converter Installation Instructions
Undervoltage lockout: the supply voltage is too low for the outputs to work properly, the outputs return 0 mA or 0 V, no matter which fault current/which fault voltage has been selected
Redundancy too large: only if Redundancy active has been selected (see Menu Input Extra section), if the set maximum deviation is exceeded
Sensor breakage: see Menu Input section
Sensor short circuit: only RTD type of sensor; see Menu Input section
Overrange, Underrange: measured variable outside the maximum measuring range of the selected sensor (see Menu Output section and Behavior of the current output or voltage output section)
CJC Error: if the cold junction compensation has been selected (see Menu Input section) and a breakage or short circuit occurs within the Bul 937A-TCJC terminal
Input 1: terminals 1 to 3 (also uses terminal 4 for 4-wire resistance measurement);
Service
In menu Service the factory settings of the Bul. 937CS-AITMP-DC1 can be reloaded.
Reload the factory settings via pressing the button Factory Reset.
S
15
Bul. 937C Universal Temperature Converter Installation Instructions
Editing device data
Any change to device data will change the operation of the device! Before transferring new data into the device, make sure that no danger to the installation will result.
Warning
If you call the parameters for a Bul. 937CS-AITMP-DC1 in PACTwareTM (e. g. Device data Parameters, a window with menus for parameterization appears, these manues will be described as follows.
Menu Information and Description
The information in the upper part of the menu Information is read from the 937CS-AITMP-DC1. This information cannot be changed.
16
Bul. 937C Universal Temperature Converter Installation Instructions
Please specify the frequency of your supply network (50 Hz or 60 Hz) under Net frequency. This way you achieve the best possible suppression of influences of this net frequency on the
Bul. 937CS-AITMP-DC1
Via Output Type the type of the analog output (current, voltage) can be preselected. This depends on the device which shall be parameterised.
The information in menu Description can be edited as desired.
17
Bul. 937C Universal Temperature Converter Installation Instructions
Menu Input
The Input tab has the three subordinate tabs I/input, II/input and Extras.
Menu Input 1
On the menu Input 1, you set the parameters for the input at the terminals 1 to 3.
18
Bul. 937C Universal Temperature Converter Installation Instructions
The following parameters can be set:
Sensor (see Connection section):
Resistance temperature detector: Pt10GOST etc.
Thermocouple: TXK etc.
Potentiometer
Voltage
Connection mode (for resistance temperature detectors only, see Connection section):
2-wire
3-wire
4-wire
Unit:
− for resistance temperature detectors and thermocouples: °F, K or °C
for potentiometers: fixed ratio
for voltage (sources): fixed mV
The unit selected here will be used for all respective settings and displays in PACTwareTM.
Cold junction compensation (for thermocouples only):
external (Reference temperature)
internal (Bul 937A-TCJC)
If you have selected Ext. ref. temp., you can enter the external reference temperature (range of values: -100 °C to 320 °C)
For an internal Cold junction compensation, you require the Bul 937A-TCJC terminal block as an accessory instead of the normal terminal 1 to 3 (see Connection section).
Lead Resistance: When connecting an RTD with 2 wire connection the lead resistance of the cabling can be entered numerically if known.
2-Wire Calibration: When connecting an RTD with 2-wire connection the lead resistance of the cabling can be calibrated if the resistance is unknown. For calibration the sensor must be jumpered.
Sensor-breakage monitoring (for all types of sensors)
Sensor-short-circuit monitoring (for resistance temperature detectors only)
You activate or deactivate monitoring by clicking the respective checkbox ( = selected, = deselected).
19
Bul. 937C Universal Temperature Converter Installation Instructions
Behavior of the current output of the Bul. 937CS-AITMP-DC1
The linear behaviour outside the measurement range described in the following only results if temperature values ranging between the minimum value and the maximum value of the selected sensor correspond to the current values. If this is not the case, the output current jumps to the minimum or maximum specified value. The Diagnosis window (see Diagnosis section) shows the message Above limit or Below limit.
If you select Characteristic inverted, the conversion of start value and end value will be inverted.
Setting 4 mA ... 20 mA unlimited
mA
22
20.0
4.0
0
At this setting, the start value of the measurement range is converted to 4 mA and the end value to 20 mA. Intermediate values are converted proportionately.
If the value falls below the start value, the output current decreases linearly to a minimum of 0 mA (­25 % of the measurement range). Further decreases cannot be evaluated (output 0 mA). If the value exceeds the end value, the output current increases linearly to a maximum of 22 mA (approx. 112.5 % of the measurement range). Further increases cannot be evaluated (output approx. 22 mA).
Setting 4 mA ... 20 mA (NE 43)
mA
20.5
20.0
4.0
3.8 0
0100≈ 112.5-25
0100≈ 103
-1.25 Start value End value range
% meas. rangeStart value End value
% meas.
20
Bul. 937C Universal Temperature Converter Installation Instructions
At this setting, the start value of the measurement range is converted to 4 mA and the end value to 20 mA. Intermediate values are converted proportionately.
If the value falls below the start value, the output current decreases linearly to a minimum of 3.8 mA (-1.25 % of the measurement range) . Further decreases cannot be evaluated (output 3.8 mA). If the value exceeds the end value, the output current increases linearly to a maximum of 20.5 mA (approx. 103 % of the measurement range). Further increases cannot be evaluated (output 20.5 mA).
Setting 4 mA ... 20 mA limited
mA
20.0
4.0
0
At this setting, the start value of the measurement range is converted to 4 mA and the end value to 20 mA. Intermediate values are converted proportionately.
Values below the start value cannot be evaluated (output 4 mA). Values above the end value cannot be evaluated either (output 20 mA).
Setting 0 mA ... 20 mA
20.5
20.0
0100
Start value End value range
% meas.
0
0
Start value
100 102.5mA% meas.
End value range
21
Bul. 937C Universal Temperature Converter Installation Instructions
At this setting, the start value of the measurement range is converted to 0 mA and the end value to 20 mA. Intermediate values are converted proportionately.
Values less than the start value cannot be evaluated (output 0 mA). If the value exceeds the end value, the output current increases linearly to a maximum of 20.5 mA (102.5 % of the measuring range). Further increases cannot be evaluated (output 20.5 mA).
Fault current
The following table shows the values of the current output during a fault, depending on the settings. For information on the behavior of the current output if Redundancy active has been selected, refer to Menu Input Extras section.
Setting
Upscale
Downscale
Characteristic 4 mA ... 20 mA
unlimited
approx. 22 mA
(cannot be distinguished from
value exceeding end value)
(cannot be distinguished from
0 mA
value below start value)
Hold last measured value before the fault
approx. 22 mA
in the case of lead short circuit
Upscale/
downscale
only makes
sense for RTD
22
(cannot be distinguished from
value exceeding end value)
in the case of lead breakage
(cannot be distinguished from
0 mA
value below start value)
Characteristics 4 mA ... 20 mA (NE 43) 4 mA ... 20 mA limited
Characteristic 0mA...20mA
approx. 21.5 mA approx. 21.5 mA
2.0 mA
approx. 21.5 mA
in the case of
lead short circuit
2.0 mA
in the case of
lead breakage
(cannot be distinguished
from measurement of
the start value)
approx. 21.5 mA
in the case of lead short
in the case of lead
(cannot be distinguished
from measurement of
the start value)
0 mA
circuit
0 mA
breakage
Publication 937-IN005A-EN-P - April 2014 (DIR 10001238756)
Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A .
Loading...