Important User Information2
Environment and Enclosure3
Hazardous Locations4
Wiring and Safety Guidelines8
About the PanelView Plus 700 to 1500 Terminals8
Parts List10
Required Tools10
Install the Terminal10
DC Power Connections16
AC Power Connections20
Battery Precautions22
Troubleshooting24
Specifications28
Additional Resources30
About This Publication
This document provides instructions on how to install these devices in a panel.
• Factory-assembled PanelView Plus or PanelView Plus CE 700 to 1500 terminals
• PanelView Plus or PanelView Plus CE 700 to 1500 display modules
• Factory-assembled PanelView Plus Compact 1000 terminal
For complete information on installing, wiring, and troubleshooting the terminals, refer to the
publications listed under Additional Resources.
2 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1
available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
) describes some important differences between solid state
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information about practices or circumstances that can cause an explosion in
a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal injury
or death, property damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment (for example, a drive or motor) to alert
people that dangerous voltage may be present.
Labels may be on or inside the equipment (for example, a drive or motor) to alert
people that surfaces may reach dangerous temperatures.
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 3
Environment and Enclosure
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in
overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes
up to 2000 m (6561 ft) without derating.
The terminals are intended for use with programmable logic controllers. Terminals that
are AC powered must also be connected to the secondary of an isolating transformer.
This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR Publication 11. Without appropriate precautions, there may be potential
difficulties ensuring electromagnetic compatibility in other environments due to
conducted as well as radiated disturbance.
Korean Radio Wave Suitability Registration - This equipment is registered for
Electromagnetic Conformity Registration as business equipment (A), not home
equipment. Sellers or users are required to take caution in this regard.
This equipment is supplied as open-type equipment. It must be mounted within an
enclosure that is suitably designed for those specific environmental conditions that will
be present and appropriately designed to prevent personal injury resulting from
accessibility to live parts. The interior of the enclosure must be accessible only by the use
of a tool. The terminals meet specified NEMA Type and IEC ratings only when mounted in
a panel or enclosure with the equivalent rating. Subsequent sections of this publication
may contain additional information regarding specific enclosure type ratings that are
required to comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, for additional installation
requirements, publication 1770-4.1
• NEMA Standards publication 250 and IEC publication 60529, as applicable, for
explanations of the degrees of protection provided by different types of enclosure.
.
ControlNet Communication Port
ATTENTION
PanelView Plus terminals with ControlNet communications ports include a Network
Applications Port (NAP). This port is for temporarily connecting programming terminals
to devices on a ControlNet network, and are not intended for continuous operation.
Publication 2711P-IN001I-EN-P - November 2009
4 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Hazardous Locations
This equipment is suitable for these locations:
• Class I, Division 2 Groups A, B, C, D
• Class II, Division 2 Groups F, G
• Class III
• Ordinary, nonhazardous locations only
The following statement applies to use in hazardous locations.
WARNING
Explosion Hazard
• Substitution of components may impair suitability for hazardous locations.
• Do not disconnect equipment unless power has been switched off and area is
known to be nonhazardous.
• Do not connect or disconnect components unless power has been switched off.
• All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section
18-1J2 as appropriate.
• Peripheral equipment must be suitable for the location in which it is used.
The terminals have a temperature code of T4 when operating in a 55 °C (131 °F) maximum
ambient temperature. Do not install the terminals in environments where atmospheric gases
have ignition temperatures less than 135 °C (275 °F).
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 5
Environnements dangereux
Cet équipement ne peut être utilisé que dans les environnements suivants :
• Classe I, Division 2, Groupes A, B, C, D
• Classe II, Division 2, Groupes F, G
• Classe III
• ou environnements non-dangereux
La mise en garde suivante s’applique à une utilisation en environnement dangereux.
AVERTISSEMENT
DANGER D’EXPLOSION
• La substitution de composants peut rendre cet équipement impropre à une
utilisation en environnement dangereux.
• Ne pas déconnecter l’équipement sans s’être assuré que l’alimentation est
coupée ou que l’environnement est classé non dangereux.
• Ne pas connecter ou déconnecter des composants sans s’être assuré que
l’alimentation est coupée.
• L’ensemble du câblage doit être conforme, selon le cas, aux articles 501-4(b),
502-4(b) et 503-3(b) du Code national de l’électricité des Etats-Unis.
• L’équipement périphérique doit être adapté à l’environnement dans lequel il
est utilisé.
Le code de température de fonctionnement des terminaux PanelView Plus et PanelView
Plus CE est T4 pour une température ambiante maximale de 55 °C. N’installez pas les
terminaux dans des environnements contenant des gaz atmosphériques inflammables à
moins de 135 °C.
Publication 2711P-IN001I-EN-P - November 2009
6 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
USB Ports
All PanelView Plus and PanelView Plus Compact terminals contain universal serial bus (USB)
ports that comply with hazardous location environments. This section details the field-wiring
compliance requirements and is provided in accordance with the National Electrical Code,
article 500.
Terminals Control Drawing
Associated Nonincendive Field Wiring Apparatus
PanelView Plus Host Product
Nonincendive Field
Wiring Apparatus
Nonincendive Field Wiring
USB Port
USB
Peripheral
Device
Table 1 - PanelView Plus USB Port Circuit Parameters
C
V
oc
I
sc
Groups A and BGroups C and DGroups A and BGroups C and D
a
5.25V DC1.68 A10 µF10 µF15 µH15 µH
Selected nonincendive field wiring apparatus must have nonincendive circuit parameters
conforming with Table 2.
L
a
Table 2 - Required Circuit Parameters for the USB Peripheral Device
V
max
I
max
Ci + C
+ L
L
i
cable
cable
≥ V
≥ I
≤ Ca
≤ L
oc
sc
a
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 7
Application Information
Per the National Electrical Code the circuit parameters of nonincendive field wiring apparatus
for use in hazardous locations shall be coordinated with the associated nonincendive field
wiring apparatus such that their combination remains nonincendive. The PanelView Plus
terminals and the USB peripheral device shall be treated in this manner.
The circuit parameters of the PanelView Plus USB port are given in Table 1. The USB
peripheral device and its associated cabling shall have circuit parameters with the limits given
in Table 2 for them to remain nonincendive when used with the PanelView Plus USB port. If
cable capacitance and inductance are not known the following values from ANSI/ISA-RP
12.06.01-2003 may be used:
= 197 µF/m (60 µF/ft)
C
cable
= 0.7 µF/m (0.20 µH/ft)
L
cable
Nonincendive field wiring must be wired and separated in accordance with 501.10(B)(3) of
the National Electrical Code (NEC) ANSI/NFPA 70 or other local codes as applicable.
This associated nonincendive field wiring apparatus has not been evaluated for use in
combination with another associated nonincendive field wiring apparatus.
Symbol Definitions
V
oc
I
sc
V
max
I
max
C
i
C
a
L
i
L
a
Open circuit voltage of the host USB port.
Maximum output current of the host USB port.
Maximum applied voltage rating of the USB peripheral device.
V
shall be greater than or equal to Voc in Table 1 (V
max
max
≥ V
oc ).
Maximum current to which the USB peripheral device can be subjected.
I
shall be greater than or equal to Isc in Table 1 (I
max
max
≥Isc).
Maximum internal capacitance of the USB peripheral device.
Maximum allowed capacitance of the USB peripheral device and its associated cable. The
sum of C
of the USB peripheral device and C
i
≤ Ca).
a
than or equal to C
+ C
(C
i
cable
of the associated cable shall be less
cable
Maximum internal inductance of the USB peripheral device.
Maximum allowed inductance of the USB peripheral device and its associated cable. The
sum of L
of the USB peripheral device and L
i
cable
a
≤ La).
or equal to L
(L
+ L
i
of the associated cable shall be less than
cable
Publication 2711P-IN001I-EN-P - November 2009
8 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Wiring and Safety Guidelines
Use publication NFPA 70E, Electrical Safety Requirements for Employee Workplaces, IEC
60364 Electrical Installations in Buildings, or other applicable wiring safety requirements for
the country of installation when wiring the devices. In addition to the NFPA guidelines:
• connect the device and other similar electronic equipment to its own branch circuit.
• protect the input power by a fuse or circuit breaker rated at no more than 15 A.
• route incoming power to the device by a separate path from the communication lines.
• cross power and communication lines at right angles if they must cross.
Communication lines can be installed in the same conduit as low-level
DC I/O lines (less than 10V).
• shield and ground cables appropriately to avoid electromagnetic interference (EMI).
Grounding minimizes noise from EMI and is a safety measure in electrical
installations.
For more information on grounding recommendations, refer to the National Electrical Code
published by the National Fire Protection Association.
For more information, refer to Wiring and Grounding Guidelines for PanelView
Plus/PanelView Plus CE Devices Technical Data, publication 2711P-TD001
this publication in the Literature Library website, http://literature.rockwellautomation.com
. You can find
.
About the PanelView Plus 700 to 1500 Terminals
The PanelView Plus terminals have these modular components:
• Display module (700, 1000, 1250, and 1500)
• Logic module with AC or DC power, CompactFlash card slot, Ethernet port, serial
port, and USB ports
• Internal CompactFlash card with firmware or operating system, RAM memory
(SO-DIMM)
• Communication module for specific communication protocols
These items can be ordered as separate components for field installation or factory assembled
per your configuration. The base-configured unit includes the display module and the logic
module with internal CompactFlash and RAM.
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 9
Modular Components
Communication Module
Power Input, AC or DC
Ethernet Port
Serial Port
Display Module
Logic Module
CompactFlash Card Slot
USB Ports
If the modules are ordered separately, attach the logic and communication module to the
display module before panel installation. See the instructions shipped with each module.
The logic module for the terminals is available with or without RAM and CompactFlash
preinstalled. If memory is ordered separately, you must install the memory before attaching
the logic module to the display module. See the instructions shipped with the logic module.
About the PanelView Plus Compact 1000 Terminal
The PanelView Plus Compact 1000 terminal has a fixed configuration. It does not support
communication modules, or the replacement of the logic module. The 1000 terminal contains
a non-isolated DC power supply.
Compact Flash
USB Ports
RS-232 Serial Port
The PanelView Plus Compact 1000 terminal has these features:
• 1000 touch screen display module
• USB ports (2)
• RS-232 serial port
• 10/100Base T Ethernet port
• Power input, 24V DC non-isolated
• CompactFlash Type 1 card slot
Publication 2711P-IN001I-EN-P - November 2009
Power Input, 24V DC
Ethernet Port
10 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Parts List
These items are shipped with the terminals:
• Power terminal block
• Mounting clips
• FactoryTalk View software preloaded
• Installation instructions and panel cutout template
Required Tools
These tools are required for panel installation:
• Panel cutout tools
• Small, slotted screwdriver
• Torque wrench (lb•in)
Install the Terminal
Before installing the terminal in a panel, review the following topics:
• Mounting clearances
• Panel cutout dimensions
• Product dimensions
Mounting Clearances
Allow adequate clearance around the terminal, inside the enclosure, for adequate ventilation.
Consider heat produced by other devices in the enclosure. The ambient temperature around
the terminals must be between 0…55 °C (32…131 °F).
These minimum clearances are required for ventilation.
• Top clearance: 51 mm (2 in.)
• Bottom clearance: 102 mm (4 in.)
• Side clearances: 25 mm (1 in.)
• Back clearance: 25 mm (1 in.)
Minimum side clearance for insertion of memory card is 102 mm (4 in.).
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 11
Panel Cutout Dimensions
Use the full size template shipped with your terminal to mark the cutout dimensions.
Terminal TypeHeight, mm (in.)Width, mm (in.)
700 Keypad or Keypad and Touch167 (6.57)264 (10.39)
700 Touch 154 (6.08)220 (8.67)
1000 Keypad or Keypad and Touch224 (8.8)375 (14.75)
1000 Touch 224 (8.8)305 (12.00)
1250 Keypad or Keypad and Touch257 (10.11)390 (15.35)
1250 Touch257 (10.11)338 (13.29)
1500 Keypad or Keypad and Touch305 (12.00)419 (16.50)
1500 Touch 305 (12.00)391 (15.40)
Mount the Terminal in a Panel
Mounting clips secure the terminal to the panel. The number of clips you use
(4, 6, or 8) varies by terminal type.
ATTENTION
Disconnect all electrical power from the panel before making the panel cutout.
Make sure the area around the panel cutout is clear.
Take precautions so metal cuttings do not enter any components already installed in
the panel.
Failure to follow these instructions may result in personal injury or damage to panel
components.
Follow these steps to mount the terminal in a panel.
1. Cut an opening in the panel by using the panel cutout shipped with the terminal.
2. Make sure the terminal sealing gasket is properly positioned on the terminal.
Publication 2711P-IN001I-EN-P - November 2009
12 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
This gasket forms a compression type seal. Do not use sealing compounds.
Sealing Gasket
3. Install the legend strips before installing the terminal if you are using keypad legend
strips on keypad terminals.
Be careful not to pinch the legend strip during installation.
4. Place the terminal in the panel cutout.
5. Slide the ends of the mounting clips into the slots on the terminal.
Mounting Clip Slot
Mounting Clip
6. Tighten the mounting clip screws by hand until the gasket seal contacts the mounting
surface uniformly.
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 13
7. Tighten the mounting clip screws to a torque of 0.90…1.1 N•m
(8…10 lb•in) by using the specified torque sequence, making sure not to overtighten.
14
4 Clips
32
ATTENTION
Tighten the mounting clips to the specified torque to provide a proper seal and prevent
damage to the product. Rockwell Automation assumes no responsibility for water or
chemical damage to the product or other equipment within the enclosure because of
improper installation.
13
46
5
6 Clips
2
1
3
8 Clips
7
52
6
8
4
Product Dimensions
The table provides product dimensions for the terminals including depth dimensions for the:
• base configured unit (display module and logic module).
• base configured unit with communication module.
Height,
Terminal Type
700 Keypad or Keypad and Touch193 (7.58)290 (11.40)55 (2.18)
700 Touch Screen179 (7.04)246 (9.68)
1000 Keypad or Keypad and Touch248 (9.77)399 (15.72)
1000 Touch Screen248 (9.77)329 (12.97)
1250 Keypad or Keypad and Touch282 (11.12)416 (16.36)
1250 Touch Screen282 (11.12)363 (14.30)
1500 Keypad or Keypad and Touch330 (12.97)469 (18.46)65 (2.55)
1500 Touch Screen330 (12.97)416 (16.36)
Approx.,
mm (in.)
Width,
Approx.,
mm (in.)
Depth, Approx., mm (in.)
display to logic module
83 (3.27)
display to comm module
display to logic module
93 (3.65)
display to comm module
Publication 2711P-IN001I-EN-P - November 2009
14 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
The illustration shows product dimensions for the PanelView Plus and PanelView Plus
Compact 1000 touch only terminals. The other size terminals look similar. Measurements are
in mm (in.).
1000 Terminal Dimensions
Keypad or Keypad & Touch
399 (15.72)
a 55 (2.18) Display to Logic Module
b 83 (3.27) Display to Comm Module
a
b
Touch Screen
329 (12.97)
248 (9.77)
248 (9.77)
a 55 (2.18) Display to Logic Module
b 83 (3.27) Display to Comm Module
a
b
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 15
Ethernet Wiring
Use Belden 7921A shielded Ethernet Category 5e cable according to TIA 568-B.1 and RJ45
connector according to IEC 60603-7 for compliance with Marine emissions limits and
European Union 89/336/EEC EMC Directive.
The maximum cable length between the terminal’s Ethernet port and a 10/100 Base-T port
on an Ethernet hub (without repeaters or fiber) is 100 m (328 ft).
Remove and Install the Power Terminal Block
The terminals are shipped with a power terminal block installed. You can remove the terminal
block for ease of installation, wiring, and maintenance.
WARNING
ATTENTION
Explosion Hazard
Substitution of components may impair suitability for hazardous locations.
Do not disconnect equipment unless power has been switched off and area is known to
be nonhazardous.
Do not connect or disconnect components unless power has been switched off.
All wiring must comply with N.E.C. articles 501, 502, 503, and/or C.E.C. section 18-1J2 as
appropriate.
Peripheral equipment must be suitable for the location in which it is used.
Disconnect all power before installing or replacing components. Failure to disconnect
power may result in electrical shock or damage to the terminal.
• Series A to D, DC logic modules use a 3-position terminal block.
• Series E or later, DC logic modules use a 2-position terminal block.
• All logic modules with an AC power input use a 3-position terminal block.
Publication 2711P-IN001I-EN-P - November 2009
16 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Follow these steps to remove the terminal block.
1. Loosen the two screws that secure the terminal block.
2. Gently pull the terminal block away from the connector.
2-position DC Terminal Block
(series E or later)
3-position AC or DC
Terminal Block
Follow these steps to install the terminal block.
1. Reattach the terminal block to the connector until seated.
2. Tighten the two screws that secure the terminal block to the connector.
DC Power Connections
DC-powered PanelView Plus devices have an integrated 24V DC power supply. Both isolated
and non-isolated power supplies have these ratings:
• 24V DC nominal (18…32V DC)
• 70 W maximum (2.9 A at 24V DC)
The power supply is internally protected against reverse polarity of the DC+ and DCconnections. Connecting DC+ or DC- to the earth/ground terminal may damage the device.
The input power terminal block supports these wire sizes.
Wire Specifications for DC Input Power Terminal Block
Logic ModuleWire Type
Series A to D
Series E and later0.56 N•m (5 lb•in)
(1)
Two-wire max per terminal.
Stranded
or solid
Cu 90 °C
(194 °F)
Dual-wire
Gauge
22…16 AWG22…14 AWG
(1)
Single-wire
Gauge
Ter minal Scre w
Tor qu e
0.23…0.34 N•m
(2…3 lb•in)
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 17
External Power Supply For Non-isolated DC Terminals
TIP
To identify non-isolated DC logic modules refer to the PanelView Plus Terminals user
manual, publication 2711P-UM001
.
Use a single, 24V DC power supply to power each PanelView Plus device, such as catalog
number 2711P-RSACDIN. Using a separate, isolated and ungrounded source to power each
terminal prevents ground loop currents from damaging the terminals.
The output on the power supply must be isolated from the input and not connected to
earth/ground.
ATTENTION
Use a Class 2 or SELV supply as required by local wiring codes for your installation. The
Class 2 and SELV power sources provide protection so that under normal and single-fault
conditions, the voltage between the conductors, and between the conductors and
functional earth or protective earth does not exceed a safe value.
Multiple AC Power Supplies to Power Multiple DC Terminals
L1L2
AC/DC Power Supply
(2711P-RSACDIN)
dc+
dc-dc+dc-
CircuitryCircuitry
AC/DC Power Supply
L1L2
(2711P-RSACDIN)
PanelView Plus
PanelView Plus
Publication 2711P-IN001I-EN-P - November 2009
18 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
External Power for Isolated DC Terminals
TIP
Isolated DC logic modules are identified by catalog number 2711P-RPxDx.
Use an SELV or PELV 24V DC power supply, such as catalog number 2711P-RSACDIN, to
power the isolated DC PanelView Plus terminal.
The isolated DC terminals may be powered by the same power source as other equipment.
ATTENTION
Use an SELV or PELV supply as required by local wiring codes for your installation. The
SELV and PELV power sources provide protection so that under normal and single fault
conditions, the voltage between conductors and earth ground does not exceed a safe
value.
Earth/Ground Connection
PanelView Plus devices with a DC power input have a earth/ground terminal that you must
connect to a low-impedance earth/ground. The earth/ground connection is on the rear of
the display module.
IMPORTANT
The earth/ground terminal requires a minimum wire gauge.
Earth/Ground Wire Specifications for DC Power
The earth/ground connection to ground is mandatory. This connection is required for
noise immunity, reliability, and Electromagnetic Compliance (EMC) with the European
Union (EU) EMC directive for CE-mark conformance. This connection is required for safety
by Underwriters Laboratory.
SymbolWire TypeWire GaugeTerminal Screw Torque
GND
Stranded or solid Cu 90 °C (194 °F) 14…10 AWG1.13…1.36 N•m (10…12 lb•in)
On most PanelView Plus devices, the earth/ground terminal is internally connected to the
DC- terminal within the product.
ATTENTION
Damage or malfunction can occur when a voltage potential exists between two
separate ground points. Make sure the terminal does not serve as a conductive
path between ground points at different potentials.
The PanelView Plus devices have isolated and non-isolated communication ports.
For more information refer to the PanelView Plus Terminals User Manual, publication
2711P-UM001
.
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 19
Connect DC Power
WARNING
Explosion Hazard - Do not disconnect equipment unless power has been switched off and
area is known to be nonhazardous.
Disconnect all power before installing or replacing components. Failure to disconnect
power may result in electrical shock or damage to the terminal.
Follow these steps to connect the terminal DC power.
1. Verify that the terminal is not connected to a power source.
2. Secure the DC power wires to the terminal block.
Follow the markings on the terminal blocks and the terminal for proper connections.
3. Secure the earth/ground wire to the earth/ground terminal screw at the bottom of
the display.
DC Power Supply Connections
3-position Terminal Block
(series A to D logic modules)
–
+
DC+
DC-
2-position Terminal Block
(series E or later logic modules)
GND
–
+
Earth/Ground to Ground Bus
Publication 2711P-IN001I-EN-P - November 2009
GND
DC -
DC+
20 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
AC Power Connections
PanelView Plus devices with an integrated AC power supply have these power ratings:
• 85…264V AC (47…63 Hz)
• 160V A max
The input power terminal block supports these wire sizes.
Wire Specifications for AC Input Power Terminal Block
Wire Type
Stranded or solidCu 90 °C (194 °F) 22…16 AWG22…14 AWG0.56 N•m (5 lb•in)
(1)
Two-wire max. per terminal.
Dual-wire
(1)
Gauge
Single-wire
Gauge
Terminal Screw Torque
Protective Earth and Functional Earth Connection
PanelView Plus devices with an AC power input have both a protective earth and functional
earth terminal that you must connect to a low-impedance earth ground.
• Protective earth terminal is on the power input terminal block.
• Functional earth connection is on the back of the display.
ATTENTION
IMPORTANT
The protective earth and functional earth terminals require a minimum wire gauge.
The functional earth and protective earth connections to ground are mandatory. The
functional earth ground connection is required for electromagnetic compliance (EMC)
with the EU (European Union) EMC directive for CE-mark conformance. The protective
earth ground connection is required for safety and regulatory compliance.
On PanelView Plus devices with an AC power input, you must connect both protective
earth and functional earth to ground.
Functional Earth and Protective Earth Wire Specifications for AC Power
ConnectionWire TypeWire Gauge Terminal Screw
Protective earth Stranded or solid Cu 90 °C (194 °F) 14…12 AWG 0.56 N•m (5 lb•in)
Functional earth
Stranded or solid Cu 90 °C (194 °F) 14…10 AWG 1.13… 1.36 N•m
GND
Publication 2711P-IN001I-EN-P - November 2009
Tor qu e
(10…12 lb•in)
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 21
Connect AC Power
WARNING
ATTENTION
Explosion Hazard - Do not connect or disconnect equipment while circuit is live unless
area is known to be nonhazardous.
Disconnect all power before installing or replacing components. Failure to disconnect
power may result in electrical shock and/or damage to the terminal.
Improper wiring of power terminals may result in voltage at the communication
connector shells. Refer to the following figure when wiring.
Do not apply power to the terminal until all wiring connections have been made. Failure
to do so may result in electrical shock.
Follow these steps to connect the terminal to AC power.
1. Verify that the terminal is not connected to a power source.
2. Secure the AC power wires to the terminal block.
Follow the markings on terminal blocks and terminal for proper connections.
3. Secure the protective earth ground wire to the marked position of the power input
terminal block.
4. Secure the functional earth ground wire to the functional earth ground screw on the
back of the display to ground bus.
Functional Earth Ground to Ground Bus
5. Apply AC power to the terminal.
L1
L2/Neutral
GND
Protective Earth
to Ground Bus
Publication 2711P-IN001I-EN-P - November 2009
22 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Battery Precautions
WARNING
When you connect or disconnect the battery an electrical arc can occur. This could cause
an explosion in hazardous location installations. Be sure that power is removed and the
area is nonhazardous before proceeding.
For safety information on the handling of lithium batteries, including handling and
disposal of leaking batteries, see Guidelines for Handling Lithium Batteries, publication
AG 5-4
. Replace the battery only with the indicated catalog number.
Do not dispose of battery in a fire or incinerator. Dispose of used batteries in accordance
with local regulations.
Store batteries in a cool, dry environment. We recommend 25 °C (77 °F) with 40…60%
relative humidity. You may store batteries for up to 30 days between -45…85 °C
(-49…185 °F), such as during transportation. To avoid possible leakage, do not store
batteries above 60 °C (140 °F) for more than 30 days.
Replace the Battery
Follow these steps to replace the lithium battery in the logic module of PanelView Plus or
PanelView Plus Compact terminals.
1. Disconnect power from the terminal.
2. Place the terminal, display side down, on a flat stable surface.
3. Detach the communication module, if attached, from the logic module by removing
the four screws.
4. Loosen the six captive screws that attach the logic module to the display module.
Communication Module
Screw
Logic Module
Display Module
5. Carefully lift the logic module away from the terminal and turn over to expose the
circuit board.
Publication 2711P-IN001I-EN-P - November 2009
Captive
Screw
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 23
6. Locate the battery on the circuit board.
Lift up the edge of the
battery indicated by
the arrow.
7. Remove the battery by lifting up the side of the battery.
8. Insert the new battery.
IMPORTANT
Use only replacement battery catalog number 2711P-RY2032.
9. Reattach the logic module by aligning the two connectors on the bottom of the
module with the connectors on the terminal.
10. Push down on the logic module until it is firmly seated.
11. Tighten the six captive screws that secure the logic module to a torque of 0.58 N•m
(5…7 lb•in).
Publication 2711P-IN001I-EN-P - November 2009
24 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
12. Reattach the communication module, if necessary, and tighten the four screws to a
torque of 0.58 N•m (5…7 lb•in).
This product contains a hermetically sealed lithium battery which may need to be
replaced during the life of the product.
At the end of its life, the battery contained in this product should be collected separately
from any unsorted municipal waste.
The collectioin and recyling of batteries helps protect the environment and contributes to
the conservation of natural resources as valuable materials are recovered.
Troubleshooting
If the terminal is not operating correctly, check the power, display settings, status indicators,
and review the system startup and error messages.
Check for Adequate Power
A terminal that does not receive adequate power could cause unpredictable behavior. Verify
the power requirements in the Specifications table.
Check Status Indicators
The terminal has two status indicators to isolate operating problems.
• COMM indicator (green) for communication
• FAULT indicator (red) for hardware faults
COMM and FAULT Indicators
When the terminal starts, the fault indicator should be off, except for a few brief flashes, and
the comm indicator on. If the indicators remain off, the power supply or logic module has
failed. Check the power cable. If the power is not within range, replace the power supply. If
the power is within range, replace the logic module. After a successful startup, both indicators
are off and controlled by the application running on the terminal.
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 25
The table shows indicator states if the terminal powers on and stops during startup.
Indicator States If the Terminal Stops During Startup
Fault (Red)
Indicator
(1)
Blinking
(2)
On
(1)
Blinking red indicates a recoverable error.
(2)
Solid red indicates a nonrecoverable or fatal error.
Comm (Green)
Indicator
OffLast firmware download failed.
BlinkingEBC boot loader firmware failed or is missing.
OnWindows CE OS firmware failed or is missing.
OffFatal hardware error occurred.
BlinkingFatal hardware error in display.
Description
Reload firmware using Firmware Upgrade Wizard (FUW) utility.
Reload firmware using Firmware Upgrade Wizard (FUW) utility.
Reload firmware using Firmware Upgrade Wizard (FUW) utility.
Replace the logic module.
Replace the display module.
Check the Display
If the terminal display is dim or unreadable:
• check the brightness setting of the display. From Configuration mode on the terminal,
access Terminal Settings>Display Intensity.
• check the Screen Saver settings. The backlight may be turning off or dimming the
display unexpectedly. From Configuration mode on the terminal, access Terminal
Settings>Display>Screen Saver.
Publication 2711P-IN001I-EN-P - November 2009
26 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Startup Information Messages
Startup information messages display in a specific sequence on the terminal during startup
and typically display for a few seconds. These messages do not require that you perform any
action.
Message # MessageDescription
37 Video InitializedConfigures and initializes the graphics video system.
30Watchdog TestTests the watchdog circuitry to verify system integrity.
1RAM TestTests the RAM memory.
31Stuck KeyChecks the integrity of the function key hardware.
31.5 Stuck TouchChecks the integrity of the touch screen hardware.
32 Battery TestChecks the integrity of the battery hardware.
2.5 Registry SearchLocates and loads the most recent, valid registry. Multiple copies of
2Image SearchChecks for a new OS firmware upgrade on the external CompactFlash
50 External CFTransfers a new OS firmware upgrade from the external
23Internal CFPrograms the OS firmware just downloaded into the internal flash
24CRC CheckChecks the integrity of the OS firmware.
28Starting SystemLaunches the operating system (OS).
29System Check ###Internal file system integrity check (### is percent progress indicator).
29.1System CheckInternal file system integrity check disabled. Contact technical
the registry are maintained. If power is lost during a registry update, a
valid registry is available the next time power is applied to the
terminal.
card and the serial port.
CompactFlash card to the terminal. Message may display for several
minutes.
memory. Message may display for several minutes.
support.
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 27
Startup Error Messages
When an error occurs, the terminal displays an error number with a text message. The word
ERROR! appears under the message in different languages.
1RAM TestRAM test failure.Reset the terminal. If error persists, reseat the
SO-DIMM RAM module. If error still persists, replace
the logic module.
23 Internal CFError programming
the new OS firmware
to internal
CompactFlash card.
24CRC CheckChecksum of the OS
firmware failed.
30Watchdog TestWatchdog test
failure.
31Stuck KeyFunction key failure.Check that nothing is pressed against a key. Reset
31.5Stuck TouchTouch screen failure.Check that nothing is pressed against the touch
32 Battery TestBattery failure.Replace the battery. If error persists, replace the logic
33.5 NVRAM Access Nonvolatile memory
failure.
40EXE CheckSystem OS firmware
is missing or corrupt.
50 External CFError loading the OS
firmware from the
external
CompactFlash card.
Reload the firmware. If error persists, replace the
internal CompactFlash card. If error still persists,
replace the logic module.
Reload the firmware. If error persists, replace the
internal CompactFlash card. If error still persists,
replace the logic module.
Reload the firmware. If error persists, replace the
logic module.
the terminal without key presses. If error persists,
replace the display module.
screen. Reset the terminal without pressing the touch
screen. If error persists, replace the display module.
module.
Upgrade the system firmware to revision 3.10.03 or
later.
Reload the firmware. If error persists, replace the
internal CompactFlash card. If error still persists,
replace the logic module.
Reload the firmware. If error persists, replace the
external CompactFlash card and attempt the
firmware upgrade again.
Publication 2711P-IN001I-EN-P - November 2009
28 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Specifications
PanelView Plus Terminals - 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx, 2711PC-Txxxx
AttributeValue
Display
Display typeColor active matrix, thin film transistor (TFT), liquid crystal
display (LCD)
Display size
700
1000
1250
1500
Display area (WxH)
700
1000
1250
1500
Display resolution
700
1000
1250
1500
Luminance
Touch screenAnalog resistive
Electrical
Input voltage, DC24V DC nom (18… 32V DC)
Power consumption, DC70 W max (2.9 A @ 24V DC) 39 W typical (1.6 A @ 24V DC)
Input voltage, AC85… 264V AC (47…63 Hz)
Power consumption, AC160 VA max (65 VA typical)
(1)
PCI slot max. available power
Supply, DC
Supply, AC
Dimensions, Approx., (HxWxD) for based configured unit without communication module
700 keypad, or keypad and touch193 x 290 x 55 mm (7.58 x 11.40 x 2.18 in.)
700 touch179 x 246 x 55 mm (7.04 x 9.68 x 2.18 in.)
1000 keypad, or keypad and touch248 x 399 x 55 mm (9.77 x 15.72 x 2.18 in.)
1000 touch248 x 329 x 55 mm (9.77 x 12.97 x 2.18 in.)
1250 keypad, or keypad and touch282 x 416 x 55 mm (11.12 x 16.36 x 2.18 in.)
1250 touch282 x 363 x 55 mm (11.12 x 14.30 x 2.18 in.)
1500 keypad, or keypad and touch330 x 469 x 65 mm (12.97 x 18.46 x 2.55 in.)
1500 touch330 x 416 x 65 mm ((12.97 x 16.37 x 2.55 in.)
(1)
The PCI slot does not apply to the PanelView Plus Compact 1000 terminal.
6.5 in.
10.4 in.
12.1 in.
15 in.
132 x 99 mm (5.2 x 3.9 in.)
211 x 158 mm (8.3 x 6.2 in.)
246 x 184 mm (9.7 in x 7.2 in.)
304 x 228 mm (12.0 x 9.0 in.)
640 x 480
640 x 480
800 x 600
1024 x 768
2
300 cd/m
Nits
11 W
5 W
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 29
PanelView Plus Terminals - 2711P-Kxxxx, 2711P-Txxxx, 2711P-Bxxxx, 2711P-RDxxxx, 2711PC-Txxxx
Weight, Approx. for base configured unit without communication module
700 keypad, or keypad and touch1.9 kg (4.2 lb)
700 touch1.7 kg (3.8 lb)
1000 keypad, or keypad and touch2.9 kg (6.3 lb)
1000 touch2.6 kg (5.7 lb)
1250 keypad, or keypad and touch3.4 kg (7.6 lb)
1250 touch3.2 kg (7.1 lb)
1500 keypad, or keypad and touch4.6 kg (10.0 lb)
1500 touch4.2 kg (9.3 lb)
General
Battery life4 years min. at 25 °C (77 °F)
ClockBattery-backed, + /- 2 minutes per month
Status indicatorsCOMM (green), Fault (red)
Application flash memory
700 to 1500 series D or earlier logic modules
2711P-RW1
2711P-RW2
2711P-RW3
700 to 1500 series E or later logic modules
2711P-RW6
2711P-RW7
2711P-RW8
External CompactFlash storage512 MB max
26 MB
72 MB
95 MB
80 MB
203 MB
446 MB
Environmental Specifications
SpecificationValue
Temperature, operating0…55 °C (32…131 °F)
Temperature, nonoperating-20…70 °C (-13…158 °F)
Vibration10… 57 Hz, 0.012 pk-pk displacement
57…500 Hz 2.0 g pk acceleration
Shock, operating15 g at 11 ms
Shock, nonoperating30 g at 11 ms
Relative humidity5…95% without condensation
Enclosure ratingsNEMA Type 12, 13, 4X (indoor use only), IP54, IP65
Airborne ContaminantsANSI/ISA S71.04-1985 Severity Level G3
EN60654-4:1998 Class 3
Publication 2711P-IN001I-EN-P - November 2009
30 PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules
Certifications
Certification
c-UL-usUL Listed Industrial Control Equipment, certified for use in US and
CE (EMC)European Union 89/336/EEC EMC Directive, compliant with:
CE (LVD)EN 61131-2; Programmable Controllers
C-TickAustralian Radiocommunications Act, compliant with:
MarineProducts identified with the suffix M in the catalog number, are certified
(1)
See the Product Certification link on http://www.ab.com for declarations of conformity, certificates, and other certification
details.
(1)
Canada. See File E10314.
UL Listed Industrial Control Equipment for use in:
• Class I, Div 2, Group A, B, C, D
• Class II, Div 2 Groups F, G
• Class III Hazardous Locations
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
AS/NZS CISPR 11; Industrial Emissions
to the requirements of one or more marine societies.
Additional Resources
For additional information on the terminals, refer to these publications.
ResourceDescription
PanelView Plus User Manual,
publication 2711P-UM001
Wiring and Grounding Applications for
PanelView Plus devices Technical Data,
publication 2711P-TD001
PanelView Plus Compact Terminals User
Manual, publication 2711PC-UM001
Provides an overview of the PanelView Plus and PanelView
Plus CE terminals and gives information on how to install,
operate, configure, and troubleshoot these devices.
Provides additional information on wiring and grounding the
PanelView Plus and PanelView Plus CE terminals.
Provides an overview of the PanelView Plus Compact
terminals and gives information on how to install, operate,
configure, and troubleshoot these devices.
You can view or download publications and translated versions of the installation instructions
at http://literature.rockwellautomation.com
.
To order paper copies of technical documentation, contact your local Rockwell Automation
distributor or sales representative.
Publication 2711P-IN001I-EN-P - November 2009
PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 31
Publication 2711P-IN001I-EN-P - November 2009
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its
products. At http://support.rockwellautomation.com
knowledge base of FAQs, technical and application notes, sample code and links to software
service packs, and a MySupport feature that you can customize to make the best use of these
tools.
For an additional level of technical phone support for installation, configuration and
troubleshooting, we offer TechConnect support programs. For more information, contact
your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the
information that's contained in this manual. You can also contact a special Customer Support
number for initial help in getting your product up and running.
, you can find technical manuals, a
United States1.440.646.3434
Monday – Friday, 8 a.m. – 5 p.m. EST
Outside United
States
Please contact your local Rockwell Automation representative for any
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when
shipped from the manufacturing facility. However, if your product is not functioning and
needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number
Outside United
States
Allen-Bradley, Rockwell Automation, FactoryTalk View, PanelView, PanelView Plus, and TechConnect are trademarks of Rockwell
Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
(see phone number above to obtain one) to your distributor to complete the
return process.
Please contact your local Rockwell Automation representative for the return
procedure.