This document provides instructions on how to install, wire, ground, and troubleshoot PanelView
Component HMI terminals. It does not provide information on how to configure or run applications on the
following devices:
Solid-state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State
Controls (Publication SGI-1.1
at http://www.rockwellautomation.com/literature/) describes some important differences
between solid-state equipment and hard-wired electromechanical devices. Because of this
difference, and also because of the wide variety of uses for solid-state equipment, all persons
responsible for applying this equipment must satisfy themselves that each intended application of
this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential
damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because
of the many variables and requirements associated with any particular installation, Rockwell
Automation, Inc. cannot assume responsibility or liability for actual use based on the examples
and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information,
circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of
Rockwell Automation, Inc., is prohibited.
available from your local Rockwell Automation sales office or online
Throughout this manual, when necessary, we use notes to make you aware of safety
considerations.
WARNING: Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death,
property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you identify
a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment (for example,
drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive
or motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT
Identifies information that is critical for successful application and understanding of the
product.
Publication 2711C-IN001H-EN-P - July 2014
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1), at
altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR 11. Without appropriate precautions, there may be difficulties with
electromagnetic compatibility in residential and other environments due to conducted
and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an
enclosure that is suitably designed for those specific environmental conditions that will
be present and appropriately designed to prevent personal injury resulting from
accessibility to live parts. The enclosure must have suitable flame-retardant properties to
prevent or minimize the spread of flame, complying with a flame spread rating of 5VA,
V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible
only by the use of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to comply with
certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1
for additional installation requirements.
• NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees
of protection provided by different types of enclosure.
PanelView Component HMI Terminals 3
Publication 2711C-IN001H-EN-P - July 2014
4 PanelView Component HMI Terminals
IMPORTANT
North American Hazardous Location Approval - For 2711C-T4T only
The following information applies when
operating this equipment in hazardous
Informations sur l’utilisation de cet équipement
en environnements dangereux:
locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for
use in Class I Division 2 Groups A, B, C, D, Hazardous
Locations and nonhazardous locations only. Each product is
supplied with markings on the rating nameplate indicating
the hazardous location temperature code. When combining
products within a system, the most adverse temperature
code (lowest "T" number) may be used to help determine the
overall temperature code of the system. Combinations of
equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD
• Do not disconnect equipment
unless power has been removed
or the area is known to be
nonhazardous.
• Do not disconnect connections
to this equipment unless power
has been removed or the area is
known to be nonhazardous.
Secure any external
connections that mate to this
equipment by using screws,
sliding latches, threaded
connectors, or other means
provided with this product.
• Substitution of comp onents may
impair suitability for Class I,
Division 2.
• If this product contains
batteries, they must only be
changed in an area known to be
nonhazardous.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de Classe
I Division 2 Groupes A, B, C, D dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque
d'identification qui indiquent le code de température pour les
environnements dangereux. Lorsque plusieurs produits sont
combinés dans un système, le code de température le plus
défavorable (code de température le plus faible) peut être
utilisé pour déterminer le code de température global du
système. Les combinaisons d'équipements dans le système
sont sujettes à inspection par les autorités locales qualifiées
au moment de l'installation.
RISQUE D’EXPLOSION
• Couper le courant ou s’assurer
que l’environnement est classé
non dangereux avant de
débrancher l'équipement.
• Couper le courant ou s'assurer
que l’environnement est classé
non dangereux avant de
débrancher les connecteurs.
Fixer tous les connecteurs
externes reliés à cet équipement
à l'aide de vis, loquets
coulissants, connecteurs filetés
ou autres moyens fournis avec ce
produit.
• La substitution de composants
peut rendre cet équipement
inadapté à une utilisation en
environnement de Classe I,
Division 2.
• S’assurer que l’environnement
est classé non dangereux avant
de changer les piles.
Only the 2711C-T4T catalog is UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada.
Publication 2711C-IN001H-EN-P - July 2014
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION: Make sure all connectors and caps are securely tightened to properly seal the
connections against leaks and maintain IP enclosure type requirements.
ATTENTION: This product is intended to be mounted to a well-grounded mounting surface such
as a metal panel. Additional grounding connections from the power supply's mounting tabs or
DIN rail (if used) are not required unless the mounting surface cannot be grounded. Refer to
Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication
1770-4.1
, for additional information.
PanelView Component HMI Terminals 5
ATTENTION: If this equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment maybe impaired.
ATTENTION: Do not place the module in direct sunlight. Prolonged exposure to direct sunlight
could degrade the LCD.
ATTENTION: The USB port is intended for temporary local programming purposes only and not
intended for permanent connection. The USB cable is not to exceed 3.0 m (9.84 ft) and must not
contain hubs.
Publication 2711C-IN001H-EN-P - July 2014
6 PanelView Component HMI Terminals
PanelView C300
PanelView C200
F1
F11F22F33F44F5
5
F66F77F88F99F10
0
F2F3F4
PanelView C300
6
1
234 5
B
T T- R R- S
44868
Catalog Number Explanation
Cat. No.ModelOperator InputSizeDisplay Type
2711C-F2MC200Function keys2 in.Monochrome
2711C-K2MNumeric and function keys
2711C-T3MC300Touch screen3 in.
2711C-K3MNumeric and function keys
2711C-T4TC400Touch screen and function keys4 in.Color TFT
2711C-T6MC600Touch screen6 in.Monochrome
2711C-T6CColor STN
2711C-T6TColor TFT
2711C-T10CC1000Touch screen10 in.Color TFT
About the Terminals
PanelView Component terminals are operator interface devices for monitoring and controlling devices
attached to a controller. HMI applications are created using a Web application while your computer is
connected directly to the terminal. You see the direct result on the terminal display without having to
download first.
PanelView Component C200 and C300 Terminals
Publication 2711C-IN001H-EN-P - July 2014
PanelView Component HMI Terminals 7
1
3
4
5
6
5
9
10
2
11
7
8
45820
ItemDescriptionItemDescription
1Function keys, keypad, or touch display4USB device port
224V DC power input5RS-232 serial port
3RS-422 and RS-485 port6USB host
PanelView Component C400 Terminal
ItemDescriptionItemDescription
1Touch display, function keys724V DC power input
2Power status LED
3RS-422 and RS-485 port9USB host port
4RS-232 serial port10Replaceable real-time clock battery
5Mounting slots11Diagnostic status indicator
610/100 MBit Ethernet port
(1)
The Power Status LED is red when in screen saver o r dimmer mode and green when in normal (operational) mode.
(for 2711C-T6M, -T6C Series C or later,
2711C-T6T Series A or later only)
6RS-232 serial port
11Secure digital (SD) card slot
Parts List
PanelView Component terminals ship with these items:
•Power terminal block
• RS-422/RS-485 5-pin terminal block
• Panel cutout template
• A pair of mounting levers (for C600 Series C and C1000 terminals. For C600 — 2711C-T6M,
2711-T6C Series C or later, 2711C-T6T Series A or later.)
Publication 2711C-IN001H-EN-P - July 2014
PanelView Component HMI Terminals 9
TIP
Install the Terminal
Before installing the terminal in a panel, review minimum clearances, panel guidelines, panel cutout
dimensions, and product dimensions.
Minimum Spacing
Plan for adequate space around the terminal, inside the enclosure, for ventilation and cabling. Consider heat
produced by other devices in the enclosure. The ambient temperature around the terminal must be 0…50 °C
(32…122 °F).
PanelView Component TopBottomSidesBack
C200 Function Key
C300 Touch
C200 and C300 Keypad
C600 Touch
C400 Touchscreen and function
keys
C1000 Touch25 mm (1 in.)
51 mm (2 in.)102 mm (4 in.)25 mm (1 in.)13 mm (0.5 in.)
51 mm (2 in.)
WARNING: When you insert or remove the SD Card while power is on, an electrical arc
can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
The minimum spacing requirements are sufficient for connecting cables and inserting or
removing a memory card. Plan for additional clearance if using the USB host port on the
back of the unit.
Mounting Angle
You ca n mount th e termin al verti cally a gains t the pan el, or t ilted f orward or backw ards, up to a 45° angle. For
mounting angles greater than 45°, the operating temperature is restricted to 40 °C (104 °F).
Panel Guidelines
Supporting panels must be at least 16 gauge to provide proper sealing against water and dust and to provide
proper support. The panel surface must be flat and free of imperfections to maintain an adequate seal and
NEMA Type ratings.
Publication 2711C-IN001H-EN-P - July 2014
10 PanelView Component HMI Terminals
Panel Cutout Dimensions
Use the template shipped with your terminal to mark the cutout dimensions.
PanelView Component TerminalHeight, Approx., mm (in.)Width, Approx., mm (in.)
C200 Function Key and C300 Touch64.0 ± 1.0 (2.52 ± 0.04)99.0 ± 1.0 (3.90 ±0.04)
C200 and C300 Keypad
C400 Touchscreen and function keys
PanelView Component C200, C300, and C600 terminals install easily in a panel without any tools or
hardware. The terminals have panel clamps that automatically latch when the terminal is pushed into the
panel opening.
ATTENTION: Disconnect all electrical power from the panel before making the panel cutout.
• Make sure the area around the panel cutout is clear.
• Take precautions so metal cuttings do not enter any components already installed in the
panel.
• Failure to follow these instructions may result in personal injury or damage to panel
components.
WARNING: If you connect or disconnect the serial cable with power applied to this module or
the serial device on the other end of the cable, an electrical arc can occur. This could cause an
explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be
mounted in a suitable enclosure with proper wiring method that complies with the governing
electrical codes.
Follow these steps to mount the terminal in a panel.
1. Cut an opening in the panel using the template shipped with the terminal.
2. Make sure the sealing gasket is properly positioned on the terminal.
This gasket forms a compression type seal. Do not use sealing compounds.
3. Place the terminal in the panel cutout.
Publication 2711C-IN001H-EN-P - July 2014
PanelView Component HMI Terminals 11
IMPORTANT
IMPORTANT
44870
The terminal temperature must be greater than 0 °C (32 °F) during panel installation.
1. Push the terminal firmly into the cutout on all sides and corners until the plastic bezel contacts the
enclosure and the gasket is fully compressed.
PanelView C600
PanelView C600
PanelView C600
You will hear a series of clicks as the clamps self-adjust to the panel thickness.
Do not push on the display when pushing the terminal into the panel or you may damage
the display.
Publication 2711C-IN001H-EN-P - July 2014