Rockwell Automation 2711C-xxxx User Manual

Installation Instructions
PanelView Component HMI Terminals
Catalog Numbers 2711C-F2M, 2711C-K2M, 2711C-T3M, 2711C-K3M, 2711C-T6M, 2711C-T4T, 2711C-T6C, 2711C-T6T, 2711C-T10C
Topic Page
Environment and Enclosure 3
Catalog Number Explanation 6
About the Terminals 6
Install the Terminal 9
USB Ports 20
Choose a Power Supply 21
Remove the Power Terminal Block 22
Connect Power 23
Ground the Terminal 25
Connect Devices 25
Troubleshooting 26
Battery Replacement 27
Specifications 30
Additional Resources 33

About This Publication

This document provides instructions on how to install, wire, ground, and troubleshoot PanelView Component HMI terminals. It does not provide information on how to configure or run applications on the following devices:
2 PanelView Component HMI Terminals

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
available from your local Rockwell Automation sales office or online
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Publication 2711C-IN001H-EN-P - July 2014

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1
for additional installation requirements.
• NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
PanelView Component HMI Terminals 3
Publication 2711C-IN001H-EN-P - July 2014
4 PanelView Component HMI Terminals
IMPORTANT

North American Hazardous Location Approval - For 2711C-T4T only

The following information applies when operating this equipment in hazardous
Informations sur l’utilisation de cet équipement en environnements dangereux:
locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of comp onents may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION
• Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S’assurer que l’environnement est classé non dangereux avant de changer les piles.
Only the 2711C-T4T catalog is UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada.
Publication 2711C-IN001H-EN-P - July 2014

Prevent Electrostatic Discharge

ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION: Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements.
ATTENTION: This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the power supply's mounting tabs or DIN rail (if used) are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication
1770-4.1
, for additional information.
PanelView Component HMI Terminals 5
ATTENTION: If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment maybe impaired.
ATTENTION: Do not place the module in direct sunlight. Prolonged exposure to direct sunlight could degrade the LCD.
ATTENTION: The USB port is intended for temporary local programming purposes only and not intended for permanent connection. The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
Publication 2711C-IN001H-EN-P - July 2014
6 PanelView Component HMI Terminals
PanelView C300
PanelView C200
F1
F11F22F33F44F5
5
F66F77F88F99F10
0
F2 F3 F4
PanelView C300
6
1
2 34 5
B
T T- R R- S
44868

Catalog Number Explanation

Cat. No. Model Operator Input Size Display Type
2711C-F2M C200 Function keys 2 in. Monochrome
2711C-K2M Numeric and function keys
2711C-T3M C300 Touch screen 3 in.
2711C-K3M Numeric and function keys
2711C-T4T C400 Touch screen and function keys 4 in. Color TFT
2711C-T6M C600 Touch screen 6 in. Monochrome
2711C-T6C Color STN
2711C-T6T Color TFT
2711C-T10C C1000 Touch screen 10 in. Color TFT

About the Terminals

PanelView Component terminals are operator interface devices for monitoring and controlling devices attached to a controller. HMI applications are created using a Web application while your computer is connected directly to the terminal. You see the direct result on the terminal display without having to download first.
PanelView Component C200 and C300 Terminals
Publication 2711C-IN001H-EN-P - July 2014
PanelView Component HMI Terminals 7
1
3
4
5
6
5
9
10
2
11
7
8
45820
Item Description Item Description
1 Function keys, keypad, or touch display 4 USB device port
2 24V DC power input 5 RS-232 serial port
3 RS-422 and RS-485 port 6 USB host
PanelView Component C400 Terminal
Item Description Item Description
1 Touch display, function keys 7 24V DC power input
2 Power status LED
3 RS-422 and RS-485 port 9 USB host port
4 RS-232 serial port 10 Replaceable real-time clock battery
5 Mounting slots 11 Diagnostic status indicator
6 10/100 MBit Ethernet port
(1)
The Power Status LED is red when in screen saver o r dimmer mode and green when in normal (operational) mode.
(1)
8 USB device port
Publication 2711C-IN001H-EN-P - July 2014
8 PanelView Component HMI Terminals
234 6 7
8
1
11
10
9
PanelView C600
FAULT
B
61
T T- R R- S
5
44869
(C600 Series C terminal shown)
PanelView Component C600 and C1000 Terminals
Item Description Item Description
1 Touch display 7 USB device port
2 24V DC power input 8 Diagnostic status indicator
3 10/100 MBit Ethernet port 9 Replaceable real-time clock battery
4 RS-422 or RS-485 port 10 USB host port
5 Mounting slots
(for 2711C-T6M, -T6C Series C or later, 2711C-T6T Series A or later only)
6 RS-232 serial port
11 Secure digital (SD) card slot
Parts List
PanelView Component terminals ship with these items:
•Power terminal block
• RS-422/RS-485 5-pin terminal block
• Panel cutout template
• A pair of mounting levers (for C600 Series C and C1000 terminals. For C600 — 2711C-T6M, 2711-T6C Series C or later, 2711C-T6T Series A or later.)
Publication 2711C-IN001H-EN-P - July 2014
PanelView Component HMI Terminals 9
TIP

Install the Terminal

Before installing the terminal in a panel, review minimum clearances, panel guidelines, panel cutout dimensions, and product dimensions.

Minimum Spacing

Plan for adequate space around the terminal, inside the enclosure, for ventilation and cabling. Consider heat produced by other devices in the enclosure. The ambient temperature around the terminal must be 0…50 °C
(32…122 °F).
PanelView Component Top Bottom Sides Back
C200 Function Key C300 Touch
C200 and C300 Keypad C600 Touch C400 Touchscreen and function keys
C1000 Touch 25 mm (1 in.)
51 mm (2 in.) 102 mm (4 in.) 25 mm (1 in.) 13 mm (0.5 in.)
51 mm (2 in.)
WARNING: When you insert or remove the SD Card while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
The minimum spacing requirements are sufficient for connecting cables and inserting or removing a memory card. Plan for additional clearance if using the USB host port on the back of the unit.

Mounting Angle

You ca n mount th e termin al verti cally a gains t the pan el, or t ilted f orward or backw ards, up to a 45° angle. For mounting angles greater than 45°, the operating temperature is restricted to 40 °C (104 °F).

Panel Guidelines

Supporting panels must be at least 16 gauge to provide proper sealing against water and dust and to provide proper support. The panel surface must be flat and free of imperfections to maintain an adequate seal and NEMA Type ratings.
Publication 2711C-IN001H-EN-P - July 2014
10 PanelView Component HMI Terminals

Panel Cutout Dimensions

Use the template shipped with your terminal to mark the cutout dimensions.
PanelView Component Terminal Height, Approx., mm (in.) Width, Approx., mm (in.)
C200 Function Key and C300 Touch 64.0 ± 1.0 (2.52 ± 0.04) 99.0 ± 1.0 (3.90 ±0.04)
C200 and C300 Keypad C400 Touchscreen and function keys
C600 Touch 135.0 ± 1.0 (5.31 ± 0.04) 189.0 ± 1.0 (7.44 ±0.04)
C1000 Touch 231.0 ± 1.0 (9.09 ± 0.04) 289.0 ± 1.0 (11.38 ±0.04)
99.0 ± 1.0 (3.90 ± 0.04) 119.0 ± 1.0 (4.69 ±0.04)

Mount the C200, C300, or C600 Terminal in a Panel

PanelView Component C200, C300, and C600 terminals install easily in a panel without any tools or hardware. The terminals have panel clamps that automatically latch when the terminal is pushed into the panel opening.
ATTENTION: Disconnect all electrical power from the panel before making the panel cutout.
• Make sure the area around the panel cutout is clear.
• Take precautions so metal cuttings do not enter any components already installed in the panel.
• Failure to follow these instructions may result in personal injury or damage to panel components.
WARNING: If you connect or disconnect the serial cable with power applied to this module or the serial device on the other end of the cable, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
Follow these steps to mount the terminal in a panel.
1. Cut an opening in the panel using the template shipped with the terminal.
2. Make sure the sealing gasket is properly positioned on the terminal.
This gasket forms a compression type seal. Do not use sealing compounds.
3. Place the terminal in the panel cutout.
Publication 2711C-IN001H-EN-P - July 2014
PanelView Component HMI Terminals 11
IMPORTANT
IMPORTANT
44870
The terminal temperature must be greater than 0 °C (32 °F) during panel installation.
1. Push the terminal firmly into the cutout on all sides and corners until the plastic bezel contacts the enclosure and the gasket is fully compressed.
PanelView C600
PanelView C600
PanelView C600
You will hear a series of clicks as the clamps self-adjust to the panel thickness.
Do not push on the display when pushing the terminal into the panel or you may damage the display.
Publication 2711C-IN001H-EN-P - July 2014