Rockwell Automation 1798-IB4D User Manual

Installation Instructions
FlexArmor 24V dc Diagnostic Sinking Input Module
Catalog Number 1798-IB4D
0
D
1
D
2
D
3
D
The FlexArmor I/O module (Cat. No. 1798-IB4D) mounts in a FlexArmor Baseplate. Use compatible sealed cordsets to connect all field side wiring.
43001

Package Contents

Your package contains:
1 FlexArmor 1798-IB4D module
installation instructions
(Note: Baseplates and other components are ordered and shipped separately.)
Publication 1798-IN010A-EN-P - April 2002
2 FlexArmor 24V dc Diagnostic Sinking Input Module
ATTENTION
!

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Allen-Bradley be responsible or liable for indirect or consequential damage resulting from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a
potential hazard:
Publication 1798-IN010A-EN-P - April 2002
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
FlexArmor 24V dc Diagnostic Sinking Input Module 3
IMPORTANT
ATTENTION
!
Identifies information that is critical for successful application and understanding of the product.
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as "enclosed" equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.
Publication 1798-IN010A-EN-P - April 2002
4 FlexArmor 24V dc Diagnostic Sinking Input Module
ATTENTION
!
IMPORTANT

Related Publications

For DeviceNet software configuration information, refer to the
1798-ADN User Manual, publication 1798-UM001.
For PROFIBUS configuration information, refer to the
1798-APB User Manual, publication 1798-UM002.

Install the Module into the Baseplate

For instructions on how to mount the FlexArmor Baseplate, refer to publication no. 1798-IN003.
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge
potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on
component boards.
Do not touch circuit components inside the
equipment.
If available, use a static-safe workstation.
When not in use, store the equipment in
appropriate static-safe packaging.
To install the module into the FlexArmor Baseplate:
Publication 1798-IN010A-EN-P - April 2002
1. Hold the module at an angle and engage the top of the module in the indention on the rear of the Baseplate.
2. Press the module down flush with the panel until the locking lever locks.
3. Repeat these steps for each I/O module and each remaining Baseplate I/O slot.
I/O modules can be installed in any slot location to the right of the adapter module. The adapter is capable of addressing up to eight I/O modules.
FlexArmor 24V dc Diagnostic Sinking Input Module 5
4. Screw down the module retaining screws to ensure IP67 compliance.
IMPORTANT
Torque the screws to 0.5-0.7 Nm. (4.43 - 6.2
inch pounds).
Dust caps must have 4 inch pounds of torque
to maintain IP67 compliance.

Connect the Cordset to the FlexArmor Module

The module use 5 pin micro (12mm) style PCB mounted connectors.
Four micro caps cover the I/O connectors on this module. Remove the caps and connect your cables to the appropriate ports. Keep the caps in place on any unused connector to maintain the IP67 rating.
Refer to publication no. C114-CA001A-EN-P for compatible Rockwell Automation cables and cordsets.
A pinout diagram for the connectors is shown below.
Female Input Micro-Connector
(View into Socket) Pin 1 Sensor Power Pin 2 Not Used Pin 3 Sensor Common Pin 4 Input A Pin 5 Not Used
42652
ATTENTION
!
Make sure all connectors and caps are
securely tightened to properly seal the connections against leaks and maintain IP67 requirements.
For maximum noise immunity, input and
output cable return wires must be properly terminated. When inputs and outputs are connected in loopback, return wires should be connected together.
I/O cable length should be less than 30
meters.
Publication 1798-IN010A-EN-P - April 2002
6 FlexArmor 24V dc Diagnostic Sinking Input Module

Troubleshooting with the Indicators

The following table describes status indicators on the diagnostic input modules.
I/O Status Indicators Function Indicator Status
Inputs
Diagnostic LED
Yellow Off
Solid Red Blinking Red Off
Input ON Input OFF
Sensor Power Short Off Wire Normal

Specifications

Specifications - 1798-IB4D
Module Type Digital Input, Sinking Number of Channels 1 group of 4 Sensor Source Current 50 mA per connector On-state Voltage 10-28.8V dc; 24V dc nominal On-state Current 2-12 mA; 8 mA @ 24V dc Off-state Voltage 5V dc maximum Off-State Current 1.5 mA minimum Channel Impedance 4.6KΩ maximum Isolation Voltage 850V dc channel-to-system for 1s Delay Times: Off to On
FlexBus Current 80 mA maximum Power Dissipation 2.0W @ 28.8V dc Thermal Dissipation 6.8 BTU/hr. @ 28.8V dc Indicators 4 channel status - yellow
External DC Power
Voltage (24V dc nom.) Current
Dimensions (H x D x W)
Operational Temperature
On to Off
256 us, 512 us, 1 ms, 2ms 4 ms, 8 ms, 16 ms, 32 ms (Selectable; 256 us default)
4 diagnostic indicators- red
10-28.8V dc; 5% AC ripple 300 mA maximum
118 mm x 57 mm x 40 mm
4.63 in. x 2.25 in. x 1.58 in. IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)
Publication 1798-IN010A-EN-P - April 2002
FlexArmor 24V dc Diagnostic Sinking Input Module 7
Specifications - 1798-IB4D (continued)
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
Shock IEC60068-2-27 (Test Ea, Unpackaged shock):
Emissions CISPR 11:
ESD Immunity IEC 61000-4-2:
Radiated RF Immunity IEC 61000-4-3:
EFT/B Immunity IEC 61000-4-4:
Surge Transient Immunity
Conducted RF Immunity IEC 61000-4-6:
Vibration IEC60068-2-6 (Test Fc, Operating):
Conductors See publication DN-6.7.2 Enclosure Meets IP67 Agency Certification
(When product is marked)
1. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)
Operating 30g Non-operating 50g
Group 1, Class A
6kV contact discharges 8kV air discharges
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 10V/m with 200Hz 50% Pulse 100%AM at 900MHz
±2kV at 5kHz on power ports ±2kV at 5kHz on signal ports
IEC 61000-4-5: ±1kV line-line(DM) and ±2kV line-earth(CM) on power ports ±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
5g @ 10-500Hz
c-UL-us UL Listed Industrial Control Equipment, certified for
US and Canada
UL UL Listed Industrial Control Equipment CE
C-Tick
1
European Union 89/336/EEC EMC Directive, compliant with: EN 50081-2; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity
1
Australian Radiocommunications Act, compliant with: AS/NZS 2064; Industrial Emissions
Publication 1798-IN010A-EN-P - April 2002
Allen-Bradley is a registered trademark of Rockwell Automation. DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA). RSNetWorx for DeviceNet is a trademark of Rockwell Software, Inc.
Publication 1798-IN010A-EN-P - April 2002 PN 957564-70
Copyright © 2002 Rockwell Automat ion. All rights reserved. Prin ted in the U.S.A.