Rockwell Automation 1794-TB3GK, 1794-TB3GS, 1794-TB3T, 1794-TB3TS, 1794-TBN User Manual

...
FLEX I/O Terminal Base Units
WARNING
IMPORTANT
ATTENTION
ATTENTION
WARNING
WARNING
ATTENTION
ATTENTION
ATTENTION
ATTENTION
ATTENTION
1794-TB2, -TB3, -TB3K, -TB3S, -TB32, -TB32S, -TB3G,
-TB3GK, -TB3GS, -TB3T, -TB3TS, -TBN, -TBNK, -TBNF,
-TBNFK, -TBKD, -TB3SK, -TB3GSK, -TB3TK, -TB3TSK
(Modules with a K in the last position of the catalog number are conformally coated to meet noxious gas requirements of ISA/ANSI-71.040 1985 Class G3 Environment.)
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
http://www.literature.rockwellautomation.com) describes some important differences between
solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
SGI-1.1 available from your local Rockwell Automation sales office or online at
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Installation Instructions
When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
FLEX I/O systems are grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in
use.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, or recognize the consequence
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1 requirements.
NEMA Standards 250 and IEC 60529, as applicable, for
explanations of the degrees of protection provided by different types of enclosure.
, for additional installation
Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.
Do not wire more than 1 conductor on any single terminal.
Personnel responsible for the application of safety-related Programmable Electronic Systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.
Publication 1794-IN092E-EN-P - November 2009
2 FLEX I/O Terminal Base Units
WARNING
AVERTISSEMENT
WARNING
Cat. No. 1794-TB2, -TB3, -TB3K, -TB32, -TB3G, -TB3GK, -TB3T, -TB3TK
1794-TB2
1794-TB3, -TB3K, -TB32,
1
2
3
4
5
6
7
8
9
10
11
-TB3G, -TB3GK, -TB3T, -TB3TK
Cat. No. 1794-TBN, -TBNK
1
2
3
4
5
6
8
15
10
11
9
Cat. No. 1794-TBKD
1
2
3
4
5
6, 7
6, 7
9
10
11
16
Cat. No 1794-TBKD
North American Hazardous Location Approval
The following terminal bases are Hazardous Location approved: 1794-TBN,
-TBNK, -TB2, -TB3, -TB3K, -TB3S, - TB3SK, -TB3G, TB3GK, -TB3GS,
-TB3GSK, -TB3T, -TB3TK, -TB3TS, -TB3TSK, -TB32S, -TB32.
The following information applies when operating this equipment in hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux :
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.
RISQUE D’EXPLOSION
• Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S’assurer que l’environnement est classé non dangereux avant de changer les piles.
European Hazardous Location Approval
The following adapters are European Zone 2 approved: 1794-TBN, -TBNK, -TB2,
-TB3, -TB3K, -TB3S, - TB3SK, -TB3G, TB3GK, -TB3GS, -TB3GSK, -TB3T,
-TB3TK, -TB3TS, -TB3TSK.
European Zone 2 Certification (The following applies when the product bears the Ex or EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
FLEX I/O Spring-clamp Terminal Base Units
Cat. No. 1794-TB3S, -TB3SK, -TB32S, -TB3GS, -TB3GSK, -TB3TS, -TB3TSK
1
5
6
7
8
9
10
4 3
11
2
12 13 12
FLEX I/O Terminal Base Units
FLEX I/O Fused Terminal Base Units
Cat. No. 1794-TBNF, -TBNFK
10
4
1
5
6
14
15
9
14
3
11
2
6
Observe the following additional Zone 2 certification requirements.
This equipment is not resistant to sunlight or other sources of UV
radiation.
This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by
Allen-Bradley.
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.
Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or the
area is known to be nonhazardous.
FLEX I/O Cage-clamp Terminal Base Units
Publication 1794-IN092E-EN-P - November 2009
FLEX I/O Knifeswitch Terminal Base Unit
Description
1 Female flexbus connector 2 Terminal base unit 3 Male flexbus connector 4 Keyswitch - set to the position required for the installed module 5 Mounting holes for panel mounting 6, 7, 8Input/output terminal strips for connecting inputs/output wiring, commons, power
connections, customer power supplies, chassis grounds 9 Locking tab 10 Module locking latch 11 Cover plug for male flexbus connector 12 Cold-junction compensation terminals (1794-TB3T, -TB3TS, -TB3TK, -TB3TSK only) 13 Chassis ground terminations (1794-TB3T, -TB3TS, -TB3TK, -TB3TSK, -TB3G, -TB3GS,
-TB3GSK only) 14 Fuses - eight 5x20 mm (1794-TBNF, -TBNFK only) 15 Terminal strip cover (1794-TBN, -TBNK -TBNF, -TBNFK only) 16 Knife switches (1794-TBKD only)
FLEX I/O Terminal Base Units 3
ATTENTION
ATTENTION
A
B
A
C
DIN Rail
Position the terminal base at a slight angle and hook it over the top of the DIN rail.
C
Make sure the hook (C) on the terminal base slides under the edge of the adapter and the flexbus connector is fully retracted. Slide the terminal base over, tight against the adapter.
Press down on the terminal base to lock it on the DIN rail. If the terminal base does not lock into place, use a screwdriver or similar device to open the locking tab, press down on the base, and release the locking lever to lock the base in place.
ATTENTION
Gently push the flexbus connector into the side of the side of the adapter to complete the backplane connection.
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
Wiring Connections for the 1794-TB32, 1794-TB32S
NC
+V2 = Terminals 43, 45, 47, 49
Inputs/Outputs
Inputs/Outputs
+V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC
+V1 = Terminals 35, 37, 39, 41
COM1 = Terminals 36, 38, 40, 42
NC = No connections (terminals 16, 33, 34, 51)
COM2 = Terminals 44, 46, 48, 50
NC NC
(1794-TB32 shown)
A
B
C
Wiring Connections for the 1794-TB32, -TB32S
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
Inputs
Commons
(1794-TB3 shown)
-V (Common) = Terminals B-16 and B-33 +V (Voltage In) = Terminals C-34 and C-51
-V
Voltage In +V
Voltage Out +V
Voltage
Terminals 35 to 50 not available on 1794-TB2
A
B
C
Common
-V
Common
Wiring Connections for the 1794-TB2, 1794-TB3, 1794-TB3K, 1794-TB3S
For daisy-chaining: Supply in - C-34 (+) and B-16 (-)
Supply out - C-51 (+) and B-33 (-)
Wiring Connections for the 1794-TB2, -TB3, -TB3K, -TB3S, TB3SK
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
Wiring Connections for the 1794-TB3G, 1794-TB3GK, 1794-TB3GS
Inputs/Outputs
Inputs/Outputs
Chassis Ground
(1794-TB3G shown)
Chassis Ground
+V COM
24V dc Supply In
+V COM
24V dc Supply Out
Chassis Grounds for Shields
Chassis Ground
Chassis Ground
I/O
I/O
+24V dc = Terminals C-34, C-50 COM = C-35, C-51 Chassis Ground = Terminals B-16, B-33, C-38, C-40 through 45, C-47
A
B
C
For daisy-chaining: Supply in - C-34 (+), C-35 (-)
Supply out - C-50 (+), C-51 (-)
NC = No connection
NC
NC
Wiring Connections for the 1794-TB3G, -TB3GK, -TB3GS, -TB3GSK
Mount the Terminal Base Unit on a DIN Rail
During mounting of all devices, be sure that all debris (such as metal chips or wire strands) is kept from falling into the module. Debris that falls into the module could cause damage upon application of power.
1. Remove the cover plug (if used) in the male connector of the unit to which
you are connecting this terminal base unit.
2. Check to make sure the 16 pins in the male connector on the adjacent
device are straight and in line so that the mating female connector on this terminal base unit will mate correctly.
3. Make certain the female connector (B) is fully retracted.
4. Position the terminal base unit on the 35 x 7.5 DIN rail (A) (A-B pt no.
199-DR1).
Do not force the terminal base into the adjacent base/adapter. Forcing the units together can bend or break the hook and allow the units to separate and break communication over the backplane.
6. Refer to the installation instructions for specific wiring information for the
module you are installing in this terminal base.
7. Repeat the above steps to install the next terminal base.
When using FLEX I/O modules in a high-vibration installation, especially when mounting the DIN rail vertically, use DIN-rail locks (A-B part number 1492-EA35) to prevent accidental separation of the terminal block units.
Wire Connections for the Terminal Base Units
5. Rotate the terminal base onto the DIN rail with the top of the rail hooked under the lip on the rear of the terminal base. Use caution to make
sure that the female flexbus connector does not strike any of the pins in the mating connector.
Publication 1794-IN092E-EN-P - November 2009
4 FLEX I/O Terminal Base Units
16
0
1
2
3
4
5
6789101112
13
14
15
51
33
34
+V
COM
+V
COM
B
C
Even Numbered I/O Terminals 0 to 14
Odd Numbered I/O Terminals 1 to 15
(1794-TBN shown)
+V = Terminals C-34, C-51 COM (-V) = Terminals B-16, B-33
Wiring Connections for the 1794-TBN, 1794-TBNK, 1794-TBNF, 1794-TBNFK
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
Wiring Connections for the 1794-TB3T, -TB3TS
Inputs/Outputs
(1794-TB3T shown)
+V = Supply Out - Terminals C-50, C-51
Supply In
Supply Out
A
B
C
CN3
CJC
+V
CCCCCCCCCN2N1N0 N7N6N5N4
+VCJC
Chassis Ground
+V) = 24V dc Supply In - Terminals C-34, C-35
Channel Channel Channel Channel Channel Channel Channel Channel
01234567
+
--
+
--
+
--
+
-- +--+--+--+
--
C = -V dc common
-V = 24V dc Common Terminal B-16
-V = Terminal B-33
Wiring Connections for the 1794-TB3T, - TB3TK, -TB3TS, -TB3TSK
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
Inputs/Outputs
Common
-V (Common) = Terminals B-16, B-33, C-35 through C-50
+V (Voltage In) = Terminals C-34, C-51
-V
Voltage In +V
Voltage Out +V
B
C
Common
-V
Common
Wiring Connections for the 1794-TBKD
For daisy-chaining: Supply in - C-34 (+), B-16 (-)
Supply out - C-51 (+), B-33 (-)
CH0 CH2 CH3 CH4 CH5 CH6 CH7CH1
CH0 RET
CH2 RET
CH3 RET
CH4 RET
CH5 RET
CH6 RET
CH7 RET
CH1 RET
Wiring Connections for the 1794-TBKD
Wiring when total current draw through base is less than 10 A.
Wiring when total current draw through base is greater than 10 A.
Modules in this configuration must be all analog or all digital.
Total current draw through any base must not be greater than 10 A.
Wiring when there is a mix of analog and digital modules.
24V dc 24V dc
24V dc
Digital Module
Digital Module
Digital Module
Thermocouple
or Analog Module
Use separate power supplies for analog and digital modules.
Press down to open.
For Spring-clamp Terminal Base Units: 1794-TB3S, -TB3TS, -TB3GS, -TB32S,
-TB3SK, -TB3TSK, -TB3GSK
Insert a 2.54…3.05 mm (0.10…0.12 in.) wide-bladed screwdriver into the slot and lift up.
Insert wire, and remove screwdriver.For Cage-clamp Terminal Base Units: 1794-TB2,
-TB3, -TB3K, -TB3T,-TB3TK, -TB3G, -TB3GK, -TB32
Tighten screws to 0.8 Nm (7 lb-in).
For Knifeswitch Cage-clamp Terminal Base Unit: 1794-TBKD
Tighten screws to 0.53 Nm (6 lb-in).
For NEMA Screw-clamp Terminal Base Units: 1794-TBN, -TBNK, -TBNF,
-TBNFK
Tighten screws to 1.02 Nm (9 lb-in).
Install or Change a Fuse in the 1794-TBNF or 1794-TBNFK Terminal Base Unit
This terminal base unit has fuse holders for 5x20 mm fuses on each of the eight even-numbered I/O terminals (0 through 14 - row B). To install or change a fuse:
1. Press the fuse holder down toward the terminal strip.
2. Remove the fuse from the fuse holder.
3. Insert a known good 5x20 mm fuse into the fuse holder.
4. Rotate the fuse holder back to vertical until it snaps into the locked
position.
The 1794-TBNF and 1794-TBNFK terminal base units are shipped with eight 5x20 mm, 1.6 A, 250V AC slow-blow fuses, one for each even-numbered terminal (0 through 14 on row B). These fuses are suitable for use with the 1794-OA8 AC output module. Refer to the specific installation instructions for fusing recommendations for your particular module.
Typical Wiring Guidelines
Terminal base units are rated at 10 A.
Publication 1794-IN092E-EN-P - November 2009
Use the Knifeswitch Terminal Base
The knifeswitch terminal base has 16 individual mechanical-knifeswitch circuit breakers (two for each channel). Each switch opens or closes one side (input/output and return) for a channel.
1. Place a small-bladed screwdriver into the slot of the knifeswitch of the I/O
point circuit that you wish to break.
2. Rotate downward to open the circuit.
This opens the path of an individual circuit.
3. To reestablish the circuit, rotate the knifeswitch back into the terminal base
unit until it snaps into place.
General
Attribute Value
Terminal screw torque
Supply voltage range (max)
Isolation voltage Capable of 250V (continuous) maximum, Basic Insulation Type, Field Wiring
0.56...0.79 Nm (5...7 lb-in) (1794-TB3TK, -TB3G, -TB3GK, -TB2, -TB32, -TB3,
-TB3K, -TB3T)
0.3...0.6 Nm (2.6...5.3 lb-in) (1794-TBKD)
1.4 Nm (12 lb-in) (1794-TBN, -TBNF, -TBNFK, -TBNK)
FLEXBUS: 5V DC, 640 mA I/O Terminals: 2A max V/COM Terminals: 125V DC/AC, 50/60Hz, 10A (1794-TB3SK, -TB3TK,-TB2, -TB3,
-TB3K, -TB3S, -TB3TK, -TB3TS) V/COM Terminals: 31.2V DC/AC, 50/60Hz, 10A (1794-TB3GSK, -TB3G, -TB3GS,
-TB3GK, -TB32, -TB32S V/COM Terminals: 250V DC/AC, 50/60Hz, 10A (1794-TBN, -TBNF, -TBNFK,
-TBNK)
1794-TBKD only FLEXBUS: 5V DC, 640 mA Terminal Block: 120V AC, 50/60Hz, 10A Disconnecting Switch: 3A, 20mΩ
ATTENTION A disconnecting switch does not shut off the current. Make or break a circuit only under no-load conditions.
Terminals to FLEXBUS, or the lesser of the installed module. (1794-TBN, -TBNF,
-TBNFK, -TBNK) Capable of 125V (continuous) maximum, Basic Insulation Type, Field Wiring Terminals to FLEXBUS, or the lesser of the installed module (1794-TB3SK,
-TB3TK, -TB3TK, -TB3TSK, -TB2, -TB3, -TB3K, -TB3S, -TB3TS) Capable of 50V (continuous) maximum, Basic Insulation Type, Field Wiring Terminals to FLEXBUS, or the lesser of the installed module. (1794-TB3G,
-TB3GS, -TB3GK, -TB3GSK, -TB32, -TB32S)
2500V DC/sec, Field Wiring Terminals to FLEXBUS. 220V DC/sec, Field Wiring Terminals to Functional Ground. (1794-TBKD)
Voltage rating See Working Voltage and Isolation Voltage Ratings for nominal values
Enclosure type rating
None (open-style)
FLEX I/O Terminal Base Units 5
General
North American temp code
IEC temp code T4 (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, -TB3S,
Dimensions, approx.
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
Environmental
Attribute Valu e
Operating temperature
Non-operating temperature
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Vibration IEC 60068-2-6 (Test Fc, Operating):
Operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Non-operating shock
T4A (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK,
-TB3S,-TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK, -TB32, -TB32S)
T6 (1794-TB2)
-TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK)
T6 (1794-TB2) 94 x 94 x 69 mm (HxWxD) (3.7 x 3.7 x 2.7 in.)
(with module installed in terminal base)
1770-4.1.
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…70 °C (-4…158 °F) (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK,
-TB3, -TB3K, -TB3T, -TB3TK, -TB3S, -TB3SK, -TB3TS, -TB3TSK, TB32, -TB32S, -TBN, -TBNK)
0…55 °C (32…131 °F) (1794-TBKD)
-20…55 °C (-4…131 °F) (1794-TBNF, -TBNFK, -TB2) IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
-20…85 °C (-4…185 °F) (1794-TBKD)
5…95% noncondensing
5 g @ 10…500 Hz
30 g (Except for 1794-TBKD) IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g (Except for 1794-TBKD)
Working Voltage and Isolation Voltage Ratings
Terminal Base 1794- 24V 120V 230V Isolation Voltage
TBN, TBNK, TBNF, TBNFK AC/DC AC/DC AC/DC Dependent upon installed TB2, TB3, TB3K, TB3S, TB3SK AC/DC AC/DC TB3T, TB3TS, TB3TK, TB3TSK AC/DC AC/DC TB3G, TB3GK, TB3GS, TB3GSK AC/DC TB32, TB32S AC/DC TBKD DC AC
General
Attribute Valu e
Wire size 0.34... 3.3 mm² (22…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F
Wiring category
) or greater, 1.2 mm (3/64 in.) insulation max. Strip Length: 5-6 mm (0.20...0.24 in.) (1794-TB3SK, -TB3GSK, -TB3TSK, -TB3GK, -TB3GS, -TB32S, -TB3, -TB3K, -TB3S,
-TB3TS, -TBN, -TBNF, -TBNFK, -TBNK)
0.34…2.1 mm² (22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F ) or greater, 1.2 mm (3/64 in.) insulation max (1794-TBKD)
0.21... 1.3 mm² (24…16 AWG) stranded copper wire rated at 75 °C (167 °F ) or greater, 1.2 mm (3/64 in.) insulation max (1794-TB3TK, -TB3G, -TB2, -TB32)
Established by installed module
(1)
module - refer to individual installation instructions for your specific module.
Certifications (when product is marked)
Attribute Value
UL
c-UL-us
CSA
CE
(1794-TB2) UL Listed Industrial Control Equipment. See UL File E65584.
(1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, -TB3S, -TB3TS,
-TB3SK, -TB3TSK, -TBN, -TBNK, -TB32, -TB32S) UL Listed Industrial Control Equipment, cer tified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Gr oup A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
(1794 -TBKD, -TBNF, -TBNFK ) UL Listed Industrial Control Equipment, cer tified for US and Canada. See UL File E65584.
(1794-TB2, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, -TB3TK, -TB3SK, -TB3TSK, -TBN,
-TBNK, -TB3G, -TB3GK, -TB3GS, -TB3GSK) CSA Certified Process Control Equipment. See CSA File LR546 89C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
(1794-TBNF, -TBNFK) CSA Certified Process Control Equipment. See CSA File LR546 89C.
European Union 2004/108/EC EMC Direct ive, compliant with: EN 61326-1; Meas./Control/Lab., Industri al Requirements EN 61000-6-2; Industrial Immuni ty EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clau se 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clau se 11)
(1)
Publication 1794-IN092E-EN-P - November 2009
Certifications (when product is marked)
35 (1.4)
59 (2.3)
87 (3.4)
94 (3.7)
94 (3.7)
80 (3.2)
28 (1.2)
50 (2.0)
23 (0.9)
68 (2.7)
80 (3.2)
21 (0.83)
(3.4 x 2.7 x 2.7)
87 x 68 x 69
(3.7 x 3.7 x 2.7)
94 x 94 x 69
(3.7 x 3.7 x 2.7)
94 x 94 x 69
Secure DIN rail approximately every 200 mm (7.87 in.).
A = Mounting hole dimensions for optional mounting kit. B = DIN rail. C = Operating temperature 25.4 (1.0) below each module when mounted in any position
must not exceed 55 ˚C (131 ˚F).
Measure here for vertical mounting position with adapter up.
Measure here for horizontal position.
A
B
C
Terminal Base (1794-TB3S shown) Terminal Base (1794-TB3 shown)Adapter (1794-ASB shown)
94 (3.7)
94 (3.7)
35 (1.4)
Maintain at least 25.4 (1.0) air space around your FLEX I/O system installation.
Mounting Dimensions
mm (in.)
Australian Radiocommunications Act, compliant w ith:
C-Tick
AS/NZS CISPR 11; Industrial Emissions
(1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, TB3TK,
Ex
-TB3SK, -TB3TSK, -TBN, -TBNK) European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmo spheres, Protection "n" (II 3 G Ex nA IIC T4 X) EN 60079-0; General Requirements (Zone 2 )
(1794-TB2) European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmo spheres, Protection "n" (II 3 G Ex nA IIC T6 X) EN 60079-0; General Requirements (Zone 2 )
(1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, -TB3TK,
TÜV
-TB3SK, -TB3TSK, -TBNF, -TBNFK) TÜV Certified for Functional Safety: Capable of SIL 2
(1)
See the Product Certification link at http://www.ab.com for Declaration of Confor mity, Certificates, and other certification details.
(1)
Publication 1794-IN092E-EN-P - November 2009 6 PN-64237
Copyright © 2009 Rockwell Automation, Inc. All rights reserved.
Loading...