Bulletin 1494R Lug Adapter Kit Installation Instructions
(Cat 1494R-N16, 1494R-N17, 1494R-N18, 1494R-N19) 
(For use with Bulletin 1494C, 1494F, 1494G, 1494V Disconnect Switches)
WARNING
2
1
See Note 1
To prevent electrical shock, disconnect from power source before installing or servicing,  
Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
Wire Clamp
Adapter
Wire Lug
Disconnect Switch
Notes: 
  * 1. Assemble Washer beneath adapter for 30 amp. (See view)
Lug Adapter Kit Line and Load Lugs
Catalog 
Number
1494R-N16
1494R-N17 1494R-N1
1494R-N18 100A 90-110
1494R-N19 200A / 400A 175-200
Disconnect 
  Switch 
Rating (Size)
30A 25-28
60A 40-60
Adapter 
Torque 
(Lb.-In.)
  Wire 
  Clamp 
  Torque 
 (Lb.-In.)
25
Wire Clamp 
Wire Range
(1) 14-10 STR/SOL 
(1) 8 STR 
(2) 14 SOL/SOL 
(2) 14 STR/STR 
(2) 12 SOL/SOL 
(2) 12 STR/STR 
(2) 10 SOL/SOL 
(2) 10 STR/STR 
(2) 8 STR/STR
Catalog 
Number
Included with 
   Switch 
1494R-N2
1494R-N3
  Wire Lug 
   Torque 
  (Lb.-In.)
20
45
150
275
Wire Lug 
Wire Range
#14-#8 Cu, 
  Solid or 
 Stranded 
#14-#4 Cu, 
  Solid or 
 Stranded 
#8-#1/0 Cu, 
  Solid or 
 Stranded 
#6-#4/0 Cu, 
  Solid or 
 Stranded 