Recover, Recycle, and Recharge Unit
for R-12 or R-134a Refrigerant
Voltage: 220–230; 50–60 Hz
SAFETY DEFINITIONS: Follow all WARNING, CAUTION, IMPORTANT, and NOTE messages in this manual.
These messages are dened as follows: WARNING means you may risk serious personal injury or death; CAU-
TION means you may risk personal injury, property damage, or serious unit damage; IMPORTANT means you may
risk unit damage; and NOTEs provide clarity and helpful tips. These safety messages cover situations ROBINAIR
is aware of. ROBINAIR cannot know, evaluate, and advise you regarding all possible hazards. You must make sure
all conditions and procedures do not jeopardize your personal safety.
COPYRIGHT: No part of this manual may be reproduced, stored in a retrieval system, or transmitted in any form
or by any means (electronic, mechanical, photocopy, recorded, or otherwise) without the prior written permission of
ROBINAIR.
DISCLAIMER: All information, illustrations, and specications contained in this manual are based on the latest in-
formation available at the time of publication. The right is reserved to make changes at any time without obligation
to notify any person or organization of such revisions or changes. ROBINAIR shall not be liable for errors contained
herein or for incidental or consequential damages (including lost prots) in connection with the furnishing, performance, or use of this material. If necessary, obtain additional health and safety information from the appropriate
government agencies, and the vehicle, refrigerant, and lubricant manufacturers.
WARNINGS
ALLOW ONLY QUALIFIED PERSONNEL TO OPERATE THE UNIT. Before operating the unit,
read and follow the instructions and warnings in this manual. The operator must be familiar with air
conditioning and refrigeration systems, refrigerants, and the dangers of pressurized components. If
the operator cannot read these instructions, operating instructions and safety precautions must be
read and discussed in the operator’s native language.
PRESSURIZED TANK CONTAINS LIQUID REFRIGERANT. Do not recover or charge refrigerants
into non-rellable containers; use only authorized rellable containers.
ALL HOSES MAY CONTAIN LIQUID REFRIGERANT UNDER PRESSURE. Contact with refrigerant may cause personal injury. Wear protective equipment, including safety goggles. Disconnect
hoses using extreme caution.
DO NOT BREATHE REFRIGERANT AND LUBRICANT VAPOR OR MIST. Exposure may cause
personal injury, especially to the eyes, nose, throat, and lungs. Use the unit in locations with mechanical ventilation that provides at least four air changes per hour. If accidental system discharge
occurs, ventilate the work area before resuming service.
AVOID USING AN EXTENSION CORD. An extension cord may overheat and cause re. If you
must use an extension cord, use the shortest possible cord with a minimum size of 14 AWG.
TO REDUCE THE RISK OF FIRE, do not use the unit in the vicinity of spilled or open containers
of gasoline or other ammable substances.
DO NOT USE COMPRESSED AIR TO PRESSURE TEST OR LEAK TEST THE UNIT OR VEHICLE AIR CONDITIONING SYSTEM. Some mixtures of air and refrigerant are combustible at
elevated pressures. These mixtures are potentially dangerous and may result in re or explosion
causing personal injury or property damage.
USE THE UNIT WITH EITHER R-134a OR R-12 REFRIGERANT. The unit is designed for recover-
ing, recycling, and recharging either R-134a or R-12 refrigerant. The user must dedicate the unit
to only one type of refrigerant. Do not attempt to adapt the unit for another refrigerant. Do not mix
refrigerant types through a system or in the same container; mixing of refrigerants will cause severe
damage to the unit and the vehicle air conditioning system.
HIGH VOLTAGE ELECTRICITY INSIDE THE UNIT HAS A RISK OF ELECTRICAL SHOCK. Exposure may cause personal injury. Disconnect the power before opening the back door or servicing
the unit.
Table of Contents
Safety Precautions....................................................... inside front cover
Limited Warranty.......................................................... inside back cover
Recover/Recycle/Recharge Unit
1
Introduction
General Description
CAUTION
Once the
machine has
been dedicated
to a specific
refrigerant, do
NOT adapt the
unit to another
refrigerant. Do
not mix
refrigerants
through a
system or in the
same container;
mixing
refrigerants
will cause severe
damage to the
unit and the
vehicle air
conditioning
system.
::
:
::
The AC375C recovers, recycles, and recharges vehicle refrigerant in one
hookup. It is compatible with existing service equipment and standard service
procedures.
The AC375C may be configured to recover, recycle, and recharge either
R-134a or R-12 refrigerant. Once configured to R-12 or R-134a, the unit
should be used only with the refrigerant for which it was initially
configured.
The AC375C is equipped with a power receptacle; the user provides the
power cord, depending on the electrical power connection in the region where
the unit is being used.
Throughout this manual metric measurements are used with U.S. equivalents
in parentheses.
Glossary of Terms
A/C System — The vehicle air conditioning system being serviced.
Hose Storage Fittings — When not in use, the R-134a fittings can be connected to
these fittings for storage purposes.
Internal Storage Vessel (ISV) — The refillable refrigerant storage vessel inside
the unit.
Panel Valves — The high-side and low-side valves on the control panel, when
described together.
Service Couplers — The couplers on the service hoses used to connect the hoses
to the A/C system or to a source tank.
Service Hoses — The red and blue hoses used to connect the unit to the A/C system.
Source Tank — A tank ofnew refrigerant used to refill the internal storage vessel.
Unit — The recover, recycle, and recharge unit.
This manual contains important procedures concerning the setup, operation, and
maintenance of the unit. Read and follow all the warnings outlined at the beginning
of this manual. Do not operate the unit until you have read and entirely understand
the contents of this manual. If you do not understand any of the contents of this manual,
notify your supervisor.
If the operator cannot read these instructions, all instructions and safety precautions must
be read and discussed in the operator’s native language.
Unpacking the Accessory Kit
Unpack the accessory kit from the bag and remove the plastic packaging. The
accessory kit consists of the following:
The unit ships with a language chart on the control panel. An optional decal is
also provided, which lists other languages. If desired, remove the backing from
the translation decal, align it over the existing chart on the control panel, and
press it in place.
Recover/Recycle/Recharge Unit
7
Initial Setup
Adding Vacuum Pump Oil
Use the following steps to add oil to the vacuum pump.
IMPORTANT: For maximum unit performance, change the vacuum
pump oil after every 10 hours of operation.
CAUTION: The
vacuum pump is
shipped without
oil in the
reservoir. To
avoid pump
damage, add oil
before starting
the pump.
Oil Fill Port
Oil Sight Glass
INST0983 FH.eps
Vacuum Pump
CAUTION:
Avoid using an
extension cord.
An extension
cord may
overheat and
cause fire. If you
must use an
extension cord,
use the shortest
possible cord
with a minimum
size of 14 AWG.
1. Plug a user supplied power cord into the unit and then into a correct
voltage outlet.
2. Turn ON the power switch on the unit’s control panel.
3. Remove the plastic plug from the oil fill port.
4. Pour about 177 mL (6 ounces) of oil into the oil fill port.
5. On the control panel, verify both panel valves are open and the service
couplers are disconnected. The screen will display:
CLEAR 02.00
6. Press the Start/Stop key (
NOTE: At this time, the unit automatically evacuates all air from the unit.
7. With the vacuum pump running, slowly add oil until the level rises to
the center of the oil sight glass.
NOTE: The pump holds approximately 237 mL (8 ounces) of oil.
8. When the vacuum pump countdown reaches zero, the vacuum pump
stops, and the unit display changes to the recover function.
9. Replace the plastic plug in the oil fill port.
After adding oil to the vacuum pump, add refrigerant to the internal
storage vessel. Refer to the instructions on the next page.
Note: The unit’s
weight default is in
kilograms. To change
the default to pounds:
1. Press the Up and
Down arrow keys
at the same time.
UNITS KG
will be displayed.
2. Press the Up or
Down arrow key to
toggle to LBS.
3. Press the Menu
() key until the
display reads EXIT.
4. Press Start/Stop
( ) key to exit.
Recover/Recycle/Recharge Unit
9
Initial Setup
Adding Refrigerant to the Internal Storage Vessel
Add refrigerant to the internal storage vessel (ISV) after adding oil to the
vacuum pump. After the initial refrigerant fill, refill the ISV as necessary.
(Refer to Adding Additional Refrigerant to the ISV.) The AC375C is shipped
as an R-12 refrigerant unit. Use the following steps to dedicate the unit to
R-134a refrigerant and add refrigerant to the internal storage vessel.
WARNING
Wear safety goggles when working with refrigerant. All hoses
may contain liquid refrigerant under pressure. Disconnect
hoses using extreme caution. Read and follow all warnings at
the beginning of this manual before operating the unit.
CAUTION: Use
only one type of
refrigerant
(either
R-134a or R-12)
in the unit. Do
not mix
refrigerant types
through a
system or in the
same container;
mixing of
refrigerants will
cause severe
damage both to
the unit and the
vehicle air
conditioning
system. Do not
attempt to adapt
the unit for another refrigerant.
Adding Refrigerant to the Internal Storage Vessel contd.
R-12 refrigerant users start with Step 3.
1. Connect the blue R-134a coupler to the blue hose and the red R-134a
coupler to the red hose as shown.
R-134a Coupler
2. Connect the low-side tank adapter (from the accessory kit) to the liquid
valve on the refrigerant source tank. NOTE: If using a refillable source
tank, connect the tank adapter to the vapor valve.
R-134a Tank Adapter
3. Connect the service coupler of the low-side hose (blue) to the refrigerant
source tank.
4. Open the valve on the source tank, and place the tank upside down in the
source tank compartment. Secure the source tank in place by wrapping
the strap around the tank and then fastening the strap.
5. The screen should display RECOVER XX.XXKG.
If it does not, scroll through the functions, pressing the Menu key (
RECOVER XX.XXKG is displayed.
) until
6. Press the Arrow keys to adjust the recover weight to 7 kg (15 lbs.).
Recover/Recycle/Recharge Unit
11
Initial Setup
Adding Refrigerant to the Internal Storage Vessel contd.
High-Side
Gauge
Low-Side
Gauge
Display Screen
Low-Side
Panel Valve
High-Side
Panel Valve /
Oil Inject
Oil Drain Valve
ISV Pressure
Gauge
5. On the control panel, open the low-side valve; verify the high-side valve is
closed.
6. Press the Start/Stop key (
and the screen displays the amount of refrigerant being transferred to the
internal storage vessel.
7. The unit automatically stops when 7 kg (15 lbs.) has been transferred to
the internal storage vessel. The display will flash between:
Menu Key
Up Arrow
Down Arrow
Start/Stop Key
Power Switch
Control Panel
). The internal storage vessel begins filling,
12
RECOVERXX.XXKG
NOTE: Do not drain oil until the following steps are complete. Drain oil
instructions begin on next page.
8. Unstrap the source tank, remove it from its compartment, and close the
source tank valve.
9. Disconnect the hose from the tank.
10. Cap the source tank with its original tank cap. For storage, place the source
tank upright in the source tank compartment. Secure the source tank in
place by wrapping the strap around the tank and then fastening the strap.
Adding Refrigerant to the Internal Storage Vessel contd.
12. Do the following to clear the service hoses:
a. Press the Menu key (
) to:
RECOVERXX.XXKG
b. Press the Start/Stop key (
c. Watch the low-side gauge. When gauge pressure reaches 34 kPa
(10 in. Hg) vacuum, press the Start/Stop key (
process.
13. Close the low-side panel valve.
Drain Oil
1. On the control panel, open the oil drain valve.
2. Watch the oil drain into the oil drain bottle. When oil stops draining, close
the oil drain valve.
3. Press the Start/Stop key (
The initial setup is now complete.
) to start hose clearing.
) to stop the clearing
) to exit the recover function.
Recover/Recycle/Recharge Unit
13
Operation
WARNING
This manual contains important procedures concerning the setup, operation, and
maintenance of the unit. Read and follow all warnings at the beginning of this
manual. Do not operate the unit until you have read and entirely understand the
contents of this manual. If you do not understand any of the contents of this manual,
notify your supervisor.
If the operator cannot read these instructions, all instructions and safety precautions
must be read and discussed in the operator’s native language.
Operating Guidelines
For best results when operating the unit, use the following guidelines along
with the operation instructions contained in this manual.
l
CAUTION:
Using the
recovery
compressor in
vacuum for an
extended period
of time could
damage the
compressor.
The compressor pulls the A/C system to a partial vacuum only. Use the
vacuum function for a minimum of 15 minutes to remove moisture from the
A/C system. Refer to Evacuating the A/C System in the “Operation”
section of this manual.
lThe unit includes a 71 l/m (3 cfm) high vacuum pump for fast, thorough
evacuation. Change the vacuum pump oil after every 10 hours of vacuum
pump use. The unit displays a CHANGE OIL message as a reminder.
Refer to Changing the Vacuum Pump Oil in the “Maintenance” section
of this manual.
lThe unit is equipped with a circuit breaker button, located on the back of
the unit. If the circuit breaker trips, the unit will not function correctly and
will lose all power. If necessary, press the circuit breaker button to reset
the unit.
lThis unit should be operated between the ambient temperatures of
11–49° C (50–120° F). At temperatures exceeding 40° C (104° F ), wait 10
minutes between recovery jobs.
lFollow the SAE-J2211 recommended service procedure for the containment
of R-134a refrigerant, or SAE-J1989 for R-12 refrigerant.
lDuring normal use, periodically inspect the unit for leaks. At a minimum,
inspect the unit every three months. Refer to Checking for Leaks in the
“Maintenance” section of this manual.
lDuring operation, any of the following messages may appear on the
display screen. If a message appears, immediately take the appropriate
action.
CHANGE FILTER — This message appears after every 68.0 kg (150 lbs.)
of refrigerant has been recovered, indicating that the filter-drier needs to
be replaced. Refer to Replacing the Filter-Drier in the “Maintenance”
section of this manual. NOTE: To avoid service delays, keep extra filter-
driers on hand.
CHANGE OIL — This message appears after every 10 hours of vacuum
pump use. Refer to Changing the Vacuum Pump Oil in the “Mainte-
nance” section of this manual.
DRAIN OIL — This message appears after recovering refrigerant from
an A/C system. For more information, refer to Draining the A/C System
Oil in this “Operation”section of this manual.
Operation
HIGH PRESSURE — This message appears if the internal storage vessel’s pressure rises to 25 bar (365 psig) or higher. Let the unit cool down
for 30 minutes. Then press the Menu key (
clear the message from the display screen. If the message does not
clear, contact a manufacturer-authorized service technician.
OVERLOAD — This message appears if the weight of the internal
storage vessel reaches 21.3 kg (47 lbs.), or if the unit’s weight scale is
damaged, disconnected, or out of calibration. Immediately remove
refrigerant from the internal storage vessel. Then press the Menu key (
and the Up arrow key to clear the message from the display screen. If the
message does not clear, contact a manufacturer authorized service
technician.
PRESSURE EXISTS — This message appears if there is pressure in the
hoses when the vacuum cycle is started, and is designed to protect the
vacuum pump from damage due to over pressurization. If this happens,
you must recover before the vacuum operation is started.
SLOW CHARGE — This message appears if the unit cannot charge
.05 lbs. in 30 seconds. It may be necessary to use the vehicle to pull the
refrigerant in. Refer to the Slow Charge procedure in this “Operation”
section of this manual.
) and the Up arrow key to
)
Recover/Recycle/Recharge Unit
15
Operation
Recovering the A/C System Refrigerant
WARNING
Wear safety goggles when working with refrigerant. All hoses may contain liquid
refrigerant under pressure. Disconnect hoses using extreme caution. Read and
follow all warnings at the beginning of this manual before operating the unit.
Do not overfill the internal storage vessel. Overfilling may cause explosion and
serious personal injury or death. If the message OVERLOAD appears in the display
screen, the internal storage vessel is too full — remove refrigerant. If the message
HIGH PRESSURE appears in the display screen, let the unit cool down. If the
message does not clear, call an authorized service technician.
Do not recover or charge refrigerants into nonrefillable containers; use only
authorized refillable refrigerant containers. Do not overfill refrigerant containers.
Overfilling may cause explosion and serious personal injury or death.
The unit is designed to recover, recycle, and recharge either R-134a or R-12
refrigerant! The user must dedicate the unit to only one type of refrigerant. Do not
attempt to adapt the unit for another refrigerant. Do not mix refrigerant types through
a system or in the same container; mixing of refrigerants will cause severe damage
to the unit and the vehicle air conditioning system.
Use the following steps to recover refrigerant from the vehicle’s A/C system.
1. Plug the user supplied power cord into a correct voltage outlet, and turn
the unit ON. Note: It is normal to hear air purge from the tank every time
the unit is powered.
2. Connect the service hoses to the A/C system. IMPORTANT: Connect
the red service hose to the A/C system’s high side; connect the blue
service hose to the low side.
4. Press the Menu key (
the amount of refrigerant capacity remaining in the internal storage vessel
[ISV].) Press the Start/Stop key (
Once recovery begins, RECOVER X.XXKG changes from the amount in
the ISV to the amount being recovered.
Note:
Verify there is enough room in the ISV by comparing the amount of
•
refrigerant in the A/C system to the amount on the display screen. The
amount in the A/C system should not be greater than the amount initially
displayed. If the amount is greater, charge some of the refrigerant from the
ISV into another refillable refrigerant tank making enough room available.
The compressor pulls the A/C system to a partial vacuum only. You must
•
use the unit’s vacuum (evacuate) cycle to remove moisture from the A/C
system.
5. Watch the low-side gauge. When the pressure gauge reaches 34 kPa
(10 in. Hg) vacuum, press the Start/Stop key (
indicate how much refrigerant has been recovered. The display screen
toggles between:
RECOVERXX.XXKG
) until RECOVER X.XX KG is displayed. (X.XX is
) to begin the recovery operation.
). The display screen will
and
DRAIN OIL
CAUTION:
Using the
recovery
compressor in
vacuum for an
extended period
of time could
damage the
compressor.
NOTE: Drain oil after the recovery is complete; refer to next page for
draining the oil.
6. Close both panel valves.
7. Wait two minutes and then check the low-side gauge for a rise in pressure
to above zero. If there is a rise in pressure, repeat Steps 4 through 8 as
needed until the pressure holds below zero for two minutes.
NOTE: If the pressure does not drop to 34 kPa (10 in. Hg) vacuum, or
does not hold at 34 kPa (10 in. Hg) vacuum for at least two minutes, there
was freezing in the A/C system during recovery, or the A/C system
requires repair. Repeat recovery or repair the A/C system as necessary.
8. Press the Start/Stop key (
After recovering all refrigerant from the A/C system, drain the A/C system oil.
Refer to the instructions on the next page.
) to exit the recover function.
Recover/Recycle/Recharge Unit
17
Operation
Draining the A/C System Oil
After recovering the refrigerant from the A/C system, use the following steps
to drain the A/C system oil into the unit’s oil drain bottle.
Oil Drain Valve
Oil Drain Bottle
Oil Drain Bottle Location
1. Verify the oil drain bottle is empty. Remove, empty, and replace the oil
drain bottle if necessary.
NOTE: Dispose of oil according to current local regulations.
2. On the control panel, open the Oil Drain valve. Watch the oil drain into
the oil drain bottle.
3. When the oil stops draining, close the Oil Drain valve.
4. Check the oil drain bottle, and record the amount of oil removed. This is
the amount of oil that must be added to the A/C system after evacuating
the A/C system. Refer to Replenishing the A/C System Oil in the
“Operation” section of this manual.
5. Remove, empty, and replace the oil drain bottle.
After draining the oil, evacuate the A/C system. Refer to the instructions on
the next page.
After recovering all refrigerant from the A/C system, draining the oil from the
system, and making repairs to the A/C system, use the following steps to evacuate (VACUUM) the A/C system.
WARNING
Wear safety goggles when working with refrigerant. All hoses may contain liquid
refrigerant under pressure. Disconnect hoses using extreme caution. Read and follow all warnings at the beginning of this manual before operating the unit.
1. Verify the power cord is plugged into a correct voltage outlet, and the
service hoses are connected to the A/C system. IMPORTANT: Connect
the red service hose to the A/C system’s high side; connect the blue
service hose to the low side.
2. On the control panel, turn the unit ON, and open both panel valves.
Operation
3. Press the Menu key () until the VACUUM screen displays. Press the
Arrow keys to set the amount of time desired for the vacuum. Fifteen
minutes is recommended, but the time may vary depending on environmental conditions.
VACUUM 15:00
NOTE: The display screen shows the time as mm:ss; where mm represents minutes and ss represents seconds. Setting vacuum time to 0
(zero) will result in continuous vacuum pump operation. To exit the vacu-
um function, press the Start/Stop key (
4. Press the Start/Stop key ( ) to begin the vacuum operation. Watch the
vacuum time on the display — the display counts down the amount of
time it will take to evacuate the A/C system.
VACUUM 00.00
5. When the evacuation is complete, the unit automatically shuts off, and INJECT OIL displays on the screen.
Caution: If the
display shows
PRESSURE EXISTS, there is
pressure in the
hoses which
may damage the
vacuum pump.
You must perform a recovery
operation before
starting the vacuum operation.
8. Check the low-side gauge for a rise in pressure. If pressure remains stable, evacuation is complete. If there is a rise in pressure, the A/C system
may need further repairs, or the evacuation may need to be repeated.
Recover/Recycle/Recharge Unit
19
Operation
Replenishing the A/C System Oil
Before recharging the A/C system, replenish the A/C system oil. Add only the
amount of oil that was removed during recovery. If no oil was removed, do
not add any oil.
NOTE:
• Consult the A/C system manufacturer for correct oil replacement procedures and oil specifications.
• Replacing A/C system components may require adding more oil. Consult
the component manufacturer for recommendations.
1. Refer to amount of oil that was removed during recovery. (See Step 4 on
page 18.)
2. Fill oil injector bottle with new oil:
• Add 30–60 mL (1–2 ounces) more oil than was recovered in Step 4 on
page 18.
• Add any additional oil required by A/C component change.
3. Note the level of new oil in the bottle.
4. Turn the high-side valve to the Oil Inject position (
replenished with the desired amount of oil. NOTE: To avoid getting air
into the A/C system, do not remove all the oil from the oil inject bottle.
5. Close the high-side valve.
6. Press the Start/Stop key (
To ensure replenishment of oil into the A/C system, immediately recharge the
A/C system. Refer to instructions on the next page.
Wear safety goggles when working with refrigerant. All hoses may contain liquid
refrigerant under pressure. Disconnect hoses using extreme caution. Read and
follow all warnings at the beginning of this manual before operating the unit.
After evacuating the A/C system and replenishing the A/C system oil as
necessary, use the following steps to recharge the A/C system’s refrigerant.
NOTE: For maximum unit performance during recharging, verify the refrigerant level in the source tank is at least 1.4 kg (3 lbs.) more than the amount
required for recharging the vehicle being serviced.
1. Refer to the A/C system manufacturer’s service manual to determine the
required amount of refrigerant to recharge.
2. Verify the unit’s power cord is plugged into a correct voltage outlet and
that the service hoses are connected to the A/C system. IMPORTANT:
Connect the red service hose to the A/C system’s high side; connect
the blue service hose to the low side.
3. On the control panel, turn the unit ON. Press the Menu key (
CHARGE XX.XX displays (XX.XX refers to the charge weight). Use the
Arrow keys to program how much to charge. Refer to the vehicle
manufacturer’s specifications for the amount to charge.
) until
Operation
CAUTION:
R-134a systems
have special fittings to avoid
cross
contamination
with R-12
systems. Do not
attempt to adapt
the unit for
another
refrigerant —
system failure
will result!
4. Open the appropriate panel valve(s) according to the A/C system
manufacturer’s specifications.
5. Press the Start/Stop key (
amount of refrigerant being charged.
6. Watch the display screen. When the required amount appears, the screen
will toggle between CHARGE COMPLETE and the amount that has been
charged.
CHARGE COMPLETE
In some cases, the unit may not be able to charge the full amount, and
will display SLOW CHARGE. Skip to the Slow Charge Procedure on the
next page.
) to begin charging. The screen displays the
and
CHARGE XX.XX
Recover/Recycle/Recharge Unit
21
Operation
Recharging the A/C System Refrigerant contd.
Clear Hoses
After the charge is complete, or after using the unit to diagnose an A/C
system, clear remaining refrigerant from the hoses to ensure a more accurate
charge. Follow this procedure to ensure all the liquid refrigerant trapped in the
CAUTION:
Before starting
the vehicle’s
engine, verify
the vehicle is in
PARK, or
NEUTRAL, with
the emergency
brake ON. Never
run a vehicle
without
adequate
ventilation in the
work area.
service hoses is transferred to the vehicle A/C system.
1. Disconnect the high-side service coupler from the vehicle.
2. Open both panel valves
3. Place the vehicle gear selector in park or neutral with the emergency
brake ON.
4. Start the vehicle. Set the A/C system to its maximum setting.
5. The unit will charge out of the low-side inlet only, allowing the vehicle’s
compressor to pull the refrigerant into the A/C system.
6. Open and disconnect the low-side coupler from the vehicle after the highand low-side pressure gauges are at their lowest pressure reading.
7. Turn off the vehicle engine.
8. Close the panel valves.
9. Press the Start/Stop key (
Slow Charge Procedure
In some cases, the unit may not be able to charge the full amount. If the unit
cannot charge .05 lbs. in 30 seconds, the display shows SLOW CHARGE. If
this occurs, follow this procedure to pull the refrigerant in using the vehicle.
1. Disconnect the high-side service coupler from the vehicle.
2. Open both panel valves.
3. Place the vehicle gear selector in park, or neutral, with the emergency
brake ON.
4. Start the vehicle. Set the A/C system to its maximum setting.
5. The unit will charge out of the low-side inlet only, allowing the vehicle’s
compressor to pull the refrigerant into the A/C system.
6. Open and disconnect the low-side coupler from the A/C system when the
high and low pressure gauges are at their lowest reading.
7. When the required amount has been charged, the display shows
CHARGE COMPLETE. Close both panel valves and disconnect the unit
from the vehicle.
Adding Additional Refrigerant to the Internal Vessel
Periodically, the internal storage vessel (ISV) will require additional refrigerant.
Use the following steps to add refrigerant to the ISV.
1. Connect the service coupler of the low-side hose (blue) to the refrigerant
source tank.
NOTE: If using a refillable source tank, connect to the vapor valve.
R-134a tanks require the tank adapter (illustrated on page 11) to be used
on the source tank.
2. Open the valve on the source tank, place the tank upside down in the
source tank compartment, and secure the strap around the tank.
3. Press the Menu key (
(XX.XX is the amount of refrigerant capacity remaining in the ISV.)
4. Press the Arrow keys to adjust to the desired recover weight.
Note: Although the display shows the refrigerant capacity remaining in the
ISV, the ISV should not be filled to this level. At least 4 kg (9 lbs.) of refrigerant capacity should be available in the ISV after filling to allow space for
the next A/C recovery. Therefore, adjust the unit to fill the ISV to a level at
least 4 kg (9 lbs.) less than what the display shows for remaining refrigerant capacity.
5. On the control panel, open the low-side valve; verify the high-side valve is
closed.
6. Press the Start/Stop key (
displays the amount of refrigerant being transferred to the ISV.
7. The unit automatically stops when the desired amount has been
transferred to the ISV. The display will flash between:
RECOVERXX.XXKG
NOTE: Drain oil after the internal storage vessel is filled.
) until RECOVER XX.XXKG (LBS) is displayed.
). The ISV begins filling, and the screen
and
DRAIN OIL
8. Unstrap the source tank, remove it from its compartment, and close the
source tank valve.
9. Disconnect the hose from the tank.
10. Cap the source tank with its original tank cap. For storage, place the source
tank upright in the source tank compartment, and secure the source tank
strap around the tank.
11. Press the Start/Stop key (
Recover/Recycle/Recharge Unit
) to exit the recover function.
23
Maintenance
Adding Additional Refrigerant to the Internal Vessel contd.
12. Do the following to clear the service hoses:
a. Press Menu key (
) to:
RECOVERXX.XXKG
b. Press Start/Stop key (
c. Watch the low-side gauge. When gauge pressure reaches 34 kPa
(10 in. Hg) vacuum, press the Start/Stop key (
process.
13. Close the low-side panel valve.
Drain Oil
1. On the control panel, open the oil drain valve.
2. Watch the oil drain into the oil drain bottle. When oil stops draining, close
the oil drain valve.
For maximum unit performance, change the vacuum pump oil after every 10
hours of operation. The unit keeps track of vacuum pump running time and
notifies the user on the display screen when it is time to change oil. For
optimum performance, use only Robinair Premium High Vacuum Oil. Use the
following steps to change the vacuum pump oil.
Oil Fill Port
Oil Drain Port
INST0983 FH.eps
Vacuum Pump
1. Remove the cap from the oil drain port, and drain the oil into a suitable
container for disposal. The container must be 474 mL (16 oz.) or larger.
NOTE: Dispose of oil according to current local area regulations.
2. Replace the cap on the oil drain port.
3. Remove oil fill cap.
4. Add 177 mL (6 ounces) of oil.
5. Verify panel gauges read less than 0.
6. Press Menu key (
Stop key (
7. With the vacuum pump running, slowly add oil until the level rises to the
center of the oil sight glass.
NOTE: The pump holds approximately 237 mL (8 ounces) of oil.
8. Press Start/Stop key (
9. Replace cap.
10. Press Start/Stop key (
After changing the vacuum pump oil, reset oil time.
).
) until screen displays VACUUM XX.XX. Press Start/
).
) to exit vacuum.
Recover/Recycle/Recharge Unit
25
Maintenance
Resetting Oil Time
Every time the vacuum pump oil is changed, the vacuum pump oil timer
should be reset. Use the following steps to reset the oil timer.
1. Press and hold the Up and Down arrows until the display shows UNITS
KG (LBS).
2. Press Menu key (
3. Press and hold the Up and Down arrows until the screen displays OIL
600 (minutes).
The filter-drier inside the unit removes acid, particulates, and moisture from
refrigerant during the recovery function. To provide adequate contaminant
and moisture removal, the filter-drier must be replaced after every 68 kg
(150 lbs.) of refrigerant recovered. The following will appear in the display:
CHANGE FILTER
Use the following steps to replace the filter-drier.
NOTE: For maximum unit performance, use only SPX/ROBINAIR filter-driers.
To avoid service delays, keep extra filter-driers on hand. Refer to the Re-
placement Partssection of this manual.
1. Plug the power cord into a correct voltage outlet.
2. Verify the service hoses are NOT connected to a vehicle.
High-Side
Gauge
Low-Side
Gauge
Display Screen
Low-Side
Panel Valve
High-Side
Panel Valve /
Oil Inject
Oil Drain Valve
ISV Pressure
Gauge
3. On the control panel, open both panel valves.
4. Press the Menu key (
5. Press the Start/Stop key (
6. Watch the low-side gauge. When the gauge pressure reaches 34 kPa
(10 in. Hg) vacuum, close both panel valves.
Control Panel
) until RECOVER XX.XX displays on the screen.
).
Menu Key
Up Arrow
Down Arrow
Start/Stop Key
Power Switch
7. Press the Start/Stop key (
8. Remove the power cord from the outlet.
Recover/Recycle/Recharge Unit
).
27
Maintenance
Replacing the Filter-Drier contd.
WARNING
High voltage electricity inside the unit has a risk of electrical shock. Disconnect the
power before opening the back door or servicing the unit.
9. Open the back door of the unit’s protective covering by turning the two
screws 1/4 turn counterclockwise.
Filter-Drier
FLOW
#
Filter-Drier Location
10. Remove the strap, and disconnect the fittings from the filter-drier.
NOTE: Dispose of the filter-drier according to current local area
regulations.
11. Install the new filter-drier with the FLOW direction arrow pointing down,
tighten fittings, and secure with the strap.
12. Close and lock the back door of the unit’s plastic covering by turning the
two screws 1/4 turn clockwise.
After replacing the filter-drier, reset the filter-drier capacity. Refer to the
instructions on the next page.
The unit keeps track of the filter-drier’s remaining capacity. As the unit filters
refrigerant, the remaining capacity decreases from 68 kg (150 lbs.) to zero.
When the capacity reaches zero, the unit will display:
CHANGE FILTER
Use the following steps to reset the filter-drier’s capacity.
1. Plug the power cord into a correct voltage outlet.
2. Press the Arrow keys simultaneously until UNITS KG (LBS) appears on
the display.
3. Press the Menu key (
4. Press the Arrow keys simultaneously until FILTER 68KG (150 LBS)
appears on the display.
5. Press the Menu key (
6. Press the Start/Stop key (
The unit is now ready to begin counting down for the new filter-drier.
) until FILTER XXX appears on the display.
) until EXIT displays.
) to exit the diagnostics function.
Recover/Recycle/Recharge Unit
29
Maintenance
Checking for Leaks
Over time, fittings can loosen as the unit is used and moved. During normal
use, inspect the unit for leaks a minimum of every three months (or as
specified by current local laws). Use the following steps to check the unit for
leaks.
NOTE: The manufacturer does not reimburse for lost refrigerant.
1. Remove the power cord from the outlet.
High voltage electricity inside the unit has a risk of electrical shock. Disconnect the
power before opening the back door or servicing the unit.
2. Remove the four screws that secure the hood.
3. Remove the hood.
4. Open the back door of the unit’s protective covering by turning the two
screws 1/4 turn counterclockwise, and lift the door off the unit.
WARNING
5. Remove the five screws that secure the front section of the unit’s
protective covering, and remove the covering.
6. Use a leak detector to trace all lines and check all connections for
refrigerant leaks. Tighten any fittings or connections if a leak is indicated.
WARNING
DO NOT use compressed air to pressure test or leak test the unit. Some mixtures of
air and refrigerant are combustible at elevated pressures. These mixtures are
potentially dangerous and may result in fire or explosion.
7. Replace the unit’s protective covering as follows:
a. Replace the front section, and replace the five screws that secure the
covering.
b. Replace, close, and lock the back door by turning the two screws
1/4 turn clockwise.
c. Replace the hood, and replace the four screws that secure the hood.
This manual contains important procedures concerning the setup, operation, and
maintenance of the unit. Read and follow all warnings at the beginning of this
manual. Do not operate the unit until you have read and entirely understand the
contents of this manual. If you do not understand any of the contents of this manual,
notify your supervisor.
If the operator cannot read these instructions, all instructions and safety precautions
must be read and discussed in the operator’s native language.
Calibrating the Weight Scale
The unit’s weight scale is calibrated at the factory and requires no further
calibration.
NOTE: If the message OVERLOAD appears on the display screen on the
control panel, the weight of the internal storage vessel is too high, or the unit’s
weight scale is damaged, disconnected, or out of calibration. Call a qualified
service technician.
Cleaning the Unit
On a regular basis, wipe off the unit with a clean cloth to remove grease, dust,
or other dirt.
Recover/Recycle/Recharge Unit
31
Replacement Parts
The following is a list of replacement parts and accessories for the unit. For
ordering information, use the technical support telephone number listed on
the back cover of this manual.
This product is warranted to be free from defects in
workmanship, materials, and components for a period of
one year from date of purchase. All parts and labor required
to repair defective products covered under the warranty
will be at no charge. The following restrictions apply:
1. The limited warranty applies to the original purchaser
only.
2. The warranty applies to the product in normal usage
situations only, as described in the Operating Manual.
The product must be serviced and maintained as
specied.
3. If the product fails, it will be repaired or replaced at
the option of the manufacturer.
4. Transportation charges for warranty service will
be reimbursed by the factory upon verication of
the warranty claim and submission of a freight
bill for normal ground service. Approval from the
manufacturer must be obtained prior to shipping to an
authorized service center.
5. Warranty service claims are subject to authorized
inspection for product defect(s).
6. The manufacturer shall not be responsible for any
additional costs associated with a product failure
including, but not limited to, loss of work time, loss
of refrigerant, cross-contamination of refrigerant, and
unauthorized shipping and/or labor charges.
7. All warranty service claims must be made within the
specied warranty period. Proof-of-purchase date must
be supplied to the manufacturer.
8.
Use of recovery/recycling equipment with
unauthorized refrigerantsor sealants will void
warranty.
• Authorized refrigerants are listed on the equipment
or are available through the Technical Service
Department.
• The manufacturer prohibits the use of the recovery/
recycling equipment on air conditioning (A/C)
systems containing leak sealants, either of a sealswelling or aerobic nature.
Declaración de garantía
limitada Robinair
Revisión del 1 de noviembre de 2005
Se garantiza que este producto no posee defectos de mano
de obra, materiales y componentes por el período de un
año a partir de la fecha de compra. Todas las partes y mano
de obra requerida para reparar los productos con defecto
cubiertos bajo la garantía no tendrán costo. Aplican las
siguientes restricciones:
1. La garantía limitada aplica al comprador original únicamente.
2. La garantía aplica al producto en situaciones de uso
normal únicamente, como lo indica el Manual de funcionamiento. Al producto se le debe dar servicio y manten-
imiento como se especica.
3. Si falla el producto, se debe reparar o reemplazar a
discreción del fabricante.
4. Los cargos de transporte de servicio de garantía serán
reembolsados por la fábrica al vericar el reclamo de
garantía y presentar una boleta de ete por servicio
terrestre regular. Se debe obtener la aprobación del
fabricante antes de hacer el envío a un centro de servicio
autorizado.
5. Los reclamos de servicio de garantía están sujetos a
inspección de defectos del producto.
6. El fabricante no será responsable de los costos adicionales relacionados con fallas en el producto, que incluyen
pero no se limitan a, tiempo improductivo, pérdida de
refrigerante, contaminación de refrigerante y envío no
autorizado o cargos por mano de obra.
7. Todo reclamo de servicio de garantía se debe hacer dentro del período de garantía establecido. Se debe proporcionar la fecha de la prueba de compra al fabricante.
8. El uso de equipo de recuperación/reciclaje con refrigerantes o selladores no autorizados anula la garantía.
• Los refrigerantes autorizados se indican en el equipo
o están disponibles a través del Departamento de
servicio técnico.
• El fabricante prohíbe el uso de equipo de recuper-
ación/reciclaje en sistemas de aire acondicionado
(A/C) con fugas de sellador, ya sea porque un sello se
ina o es de naturaleza aeróbica.
This Limited Warranty does NOT apply if:
• The product, or product part, is broken by accident.
• The product is misused, tampered with, or modied.
•
The product is used for recovering or recycling any
substance other than the specied refrigerant type. This
includes, but is not limited to, materials and chemicals
used to seal leaks in A/C systems.
Esta garantía limitada NO aplica si:
• El producto, o parte de éste, se rompe accidentalmente.
• El producto se usa incorrectamente, se adultera o modica.
• El producto se usa para recuperar o reciclar cualquier
sustancia que sea diferente al tipo de refrigerante
establecido. Esto incluye, pero no se limita a materiales
y productos químicos utilizados para sellar fugas en
sistemas de A/C.
Call our
International Customer Service Line at
1-507-455-7223
%
or email our Technical Support at
Robinairtechsupport@servicesolutions.spx.com
To help us serve you better, be prepared to provide the model number, serial number, and
date of purchase of your unit.
To validate your warranty, complete the warranty card included with the unit, and return it
within ten days from the purchase date.
If your unit needs replacement parts, please contact your local distributor. If your unit needs
repairs, you may locate service centers at www.robinair.com or by calling International
Customer Service.
Llame a nuestra línea
internacional de servicio al cliente al
1-507-455-7223
o mándenos un correo electrónico a nuestro
Servicio Técnico a
Robinairtechsupport@servicesolutions.spx.com
Para ayudarnos a servirle mejor, esté preparado para proporcionarnos el número se
servicio, el número de serie y la fecha de compra de su unidad.
Para validar su garantía, complete la tarjeta de garantía incluida con la unidad y regrésela
dentro de los diez días posteriores a partir de la fecha de compra.
Si la unidad necesita partes de reemplazo, por favor contacte a su distribuidor local. Si la
unidad necesita reparaciones, usted puede localizar centros de servicio en www.robinair.
com o al llamar al Servicio internacional al cliente.
The unit’s weight scale provides a means for metering the amount of refrigerant needed for optimum
air conditioning system performance as recommended by OEM manufacturers. Do not use the unit to
sell refrigerant by weight, because this may not be permitted by certain local jurisdictions.
La escala de peso de la unidad proporciona un medio para medir la cantidad de refrigerante que se
necesita para el rendimiento óptimo del sistema de aire acondicionado, tal como lo recomiendan los
fabricantes OEM. No use la unidad para vender refrigerante por peso, porque esto puede no estar
permitido por ciertas jurisdicciones locales.
Due to ongoing product improvements,
we reserve the right to change design, specications,
Debido a las constantes mejoras del producto,
nos reservamos el derecho de cambiar diseño,
and materials without notice.
especicaciones y materiales sin aviso.
655 Eisenhower Drive
Owatonna, MN 55060-0995 USA
Technical Services: 1-800-822-5561
Fax: 1-866-259-1241
Customer Service: 1-800-533-6127
Fax: 1-800-322-2890
Web Site: www.robinair. com