For R-12 and R-134a Refrigerants .................................1
Manuel de Fonctionnement, Modèle 348002K/348012K
Unité de Récupération/Recyclage/Recharge
Pour Réfrigérant R-12 e R-134a .................................. 30
Manuale Operativo, Modelli 348002K/348012K
Unità di Recupero/Rigenerazione/Ricarica
Per refrigeranti R-12 e R-134a..................................... 60
Manual Operativo, Modelo 348002K/348012K
Unidad de Recuperación/Reciclado/Recarga
De los Refrigerantes R-12 y R-134a............................ 90
Bedienungs-Anleitungen, Modell 348002K/348012K
Rückgewinnen/Recyclen/Abfüllen Station
Für R-12 und R-134a Kältemittel ............................... 120
Series: 348002K/348012K
Refrigerants: R-12 and R-134a
Refrigerant Recovery,
Recycling and Recharging Station
WARNING
PRESSURIZED TANK CONTAINS LIQUID REFRIGERANT. OVERFILLING OF THE TANK MAY CAUSE VIOLENT
EXPLOSION AND POSSIBLE INJURY OR DEATH. Refer to the instruction manual for tank specifications and ordering
information. Do not recover refrigerants into a non-refillable storage container! Federal regulations require refrigerant to
be transported only in containers meeting DOT spec. 4BW or DOT spec. 4BA.
ALL HOSES MAY CONTAIN LIQUID REFRIGERANT UNDER PRESSURE. Contact with refrigerant may cause injury.
Wear proper protective equipment, including safety goggles. Disconnect hoses with extreme caution.
HIGH VOLTAGE ELECTRICITY INSIDE PANELS. RISK OF ELECTRICAL SHOCK. Disconnect power before servicing
unit. Refer to the instruction manual.
TO REDUCE THE RISK OF FIRE, avoid the use of an extension cord because the
extension cord may overheat. However, if you must use an extension cord, use No. 14 AWG at the minimum and as
short as possible. Do not use this equipment in the vicinity of spilled or open containers of gasoline or other flammable
substances.
Use this equipment in locations with mechanical ventilation that provides at least four air changes per hour or locate the
equipment at least 18 inches above the floor.
Make certain all safety devices are functioning properly before operating the unit. Before operating, read and follow the
instructions and warnings in this manual.
CAUTION: SHOULD BE OPERATED BY QUALIFIED PERSONNEL. Operator must be familiar with air conditioning
and refrigeration systems, refrigerants and the dangers of pressurized components.
Use only with R-12 or R-134a. This equipment is not designed for any other purpose than recovering, recycling
or recharging refrigerants! Do not mix refrigerant types!
ATTENTION!
Ce réservoir sous pression contient du frigorigène liquide. S’il est surchargé, ce réservoir peut exploser et causer des
blessures ou la mort.
ATTENTION. Débrancher avant la maintenance.
ATTENTION. Pour réduire les risques d’incendie, ne pas utiliser de cordon prolongateur de section inférieure à 14 AWG
de facon à éviter la surchauffe du cordon.
ATTENTION. Utiliser seulement du frigorigène R-134a.
OPERATING NOTES
At temperatures exceeding 120
Use the Series 348002K/348012K only with R-12 or R-134a! Cross-contamination with other refrigerant types will cause
severe damage to the A/C system and to service tools and equipment. Do not mix refrigerant types through a system or
in the same container!
Avoid breathing A/C refrigerant and lubricant vapor or mist. Exposure may irritate eyes, nose and throat. To remove
R-12 or R-134a from the A/C system, use service equipment certified to meet the requirements of SAE-J2210 (R-12 or
R-134a recycling equipment). If accidental system discharge occurs, ventilate work area before resuming service.
R-12 or HFC-134a service equipment or vehicle A/C systems should not be pressure tested or leak tested with compressed air. Some mixtures of air/HFC-R-12 /R-134a have been shown to be combustible at elevated pressures. These
mixtures are potentially dangerous and may result in fire or explosion causing injury or property damage.
Additional health and safety information may be obtained from refrigerant and lubricant manufacturers.
Mfd. by Robinair, SPX Corporation, Montpelier, OH 43543
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
1
Introduction
This manual contains important safety procedures concerning the
operation, use, and maintenance of this product. Failure to follow the
instructions contained in this manual may result in serious injury. If you are
unable to understand any of the contents of this manual, please bring it to
the attention of your supervisor. Do not operate this equipment unless you
have read and understood the contents of this manual.
The 348002K and 348012K models are designed to be used on R-12 and R-134a
vehicles. They are compatible with existing service equipment and standard service
procedures.
The 348002K model is UL-listed. The 348012K is CE approved. Both are single
pass systems that meet the SAE specifications for recycled refrigerant.
To validate your warranty, complete the warranty card attached to your unit and
return it within ten days from date of purchase.
GLOSSARY OF TERMS
A/C SystemThe air conditioning system being serviced.
UnitThe refrigerant recovery/recycling/recharging unit.
External Storage VesselThe refillable refrigerant storage vessel designed
specifically for this unit.
Source TankA disposable tank of new refrigerant used to refill
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
3
Set-Up Instructions
INITIAL SET-UP
CAUTION!CAUTION!
CAUTION! R-134a systems have special fittings (per SAE
CAUTION!CAUTION!
specifications) to avoid cross-contamination with R-12 systems. Do
not attempt to adapt your unit for another refrigerant — system
failure will result! Read and follow all warnings at the beginning of
this manual before operating the unit.
CACA
UTION! UTION!
CA
UTION! Avoid the use of an extension cord because the
CACA
UTION! UTION!
extension cord may overheat. However, if you must use an
extension cord, use a No. 14 AWG minimum and keep the cord as
short as possible.
IMPORTANT!
You must press
the MENU key to
access all the
functions.
1. Lock both front casters of the unit by stepping on the cam brake levers, plug
the power cord into the power cord receptacle (Item 9 in the INST 0707
drawing on page 3). Turn on the MAIN POWER switch.
2. Press MENU.
3. Use the UP and DOWN arrows to select LANGUAGE SELECTION. Press
ENTER.
4. Use the UP and DOWN arrows to scroll through the language options and
press ENTER to select a language and exit LANGUAGE SELECTION.
5. Press MENU. Use the ARROW keys to go to SELECT AUTO RESTART.
Press ENTER.
6. Use the UP and DOWN arrows to toggle between AUTO RESTART ON and
AUTO RESTART OFF. Press ENTER to select.
NOTE: See the Operating Guidelines section of this manual for a description of
these functions.
7. Press MENU. Use ARROW keys to go to SELECT PROMPT. Press ENTER.
4
8. Use the UP and DOWN arrows to toggle between BASIC PROMPTS and
ADVANCED PROMPTS. Press ENTER to select.
NOTE: See the Operating Guidelines section of this manual for a description of
these functions.
1. Press VACUUM to get to the VACUUM mode. Press START to go into
VACUUM.
Set Up Instructions
NOTE: The vacuum pump is shipped without oil in the reservoir. Before
starting the pump, oil must be added to the pump or damage may occur.
2. Close all manifold valves on the control panel.
3. Remove bolts holding the door closed and open the door.
4. Remove the black plastic plug from the fill port on the top of the vacuum
pump.
5. Attach the oil fill tube to the 16 oz. bottle of vacuum pump oil provided in the
accessory kit.
6. While the vacuum pump is running, add oil until it reaches the center of the
sight glass. Press STOP. The vacuum pump is now filled to the proper level
with oil.
7. Pour oil (approximately 12 oz.) into the fill port of the vacuum pump until the
oil appears at the bottom of the sight glass. Press ENTER.
IMPORTANT!
For maximum
performance, be
sure to change
the vacuum
pump oil
frequently.
IMPORTANT!
Be sure the
pump is
running when
adding oil.
8. Replace the plug in the fill port.
9. Press STOP to exit.
1. Oil Fill Port
2. Sight Glass
3. Oil Drain
10. Close the door and replace the bolts holding the door shut.
INSTALLATION ROUTINE
1. Press MENU. Use the ARROW keys to go to the INSTALLATION
ROUTINE.
2. Press ENTER. The display toggles between CONNECT LS RXX HOSE TO
SOURCE TANK and TURN ALL VALVES TO VACUUM/RECOVER
AND PRESS START TO BEGIN. Follow the on-screen prompts.
3. Remove the service hoses from the accessory kit and remove
the plugs from the hoses using a pair of pliers.
4. Attach the service hoses to the high and low side bulkheads on the rear of the
unit. Attach the R-134a hoses to the left rear. Attach the R-12 hoses to the
right rear. Attach the RED hoses to the bulkheads labeled HIGH and the
BLUE hoses to the bulkheads labeled LOW.
1
2
3
INST0760
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
5
Operating Guidelines
5. Press START. The unit automatically evacuates the system for 5:00 minutes
to remove any air from the external storage vessel (Ensure that all tank valves
are open).
IF THE SELECTOR SWITCH IS SET TO R-134A:
6. Connect the lowside service coupler to the source tank valve, using the
adapter supplied with the unit, when the 5:00 minute evacuation is complete.
Open the service coupler and turn manifold valves to RECOVER/VACUUM.
IF THE SELECTOR SWITCH IS SET TO R-12:
7. When the 5:00 minutes evacuation is complete, connect the low side hoses the
hose adapter supplied with the unit. Attach the adapter to the source tank.
USING THE SELECTION MENU
1. Press MENU. The top line of the display reads LANGUAGE SELECTION.
2. Use the UP and DOWN arrows to scroll through the menu choices. The menu
choices are (in order of appearance):
3. Press ENTER to make a choice from the menu. Press STOP to terminate any
process.
1. LANGUAGE SELECT
2. CHANGE FILTER
3. FILTER WEIGHT
4. SELECT AUTO RESTART
5. MEASUREMENT UNITS
6. CHANGE VACUUM PUMP OIL
7. TANK FILL
8. VACUUM OIL TIME
9. INSTALLATION ROUTINE
10. SELECT PROMPTS
11. CHANGE DEFAULT (Password
Protected)
CHANGE FILTER
The filter-drier removes acid, particulates and water from the refrigerant. Change
the filter-drier after 150 pounds of refrigerant has been filtered. See the DRIER
RECOVERED LBS. section on the following page as well as the Maintenance
Section on page 20 for instructions.
NOTE: If using a refillable tank, place the tank upside down and connect the
lowside service hose to the vapor valve.
Set SELECTOR switch to R-12:
1. Connect the 6" yellow adapter to the end of the low side service hose.
2. Connect the low side service hose to the source tank and open valve.
3. Select TANK FILL from the Selection Menu.
4. Press ENTER. Then press START and the tank automatically refills. The
unit stops when a sufficient amount of refrigerant has been transferred to the
ESV- or - the source tank is empty.
NOTE: Press STOP if you wish to stop fill before it completes.
5. Close the valve on the source tank.
6. Disconnect the 96" blue service hose from the adapter, then disconnect the
6" yellow adapter from the source tank.
7. Press STOP to exit.
R-12
Low Side
Service Hose
Source
Tank
ESV
INST0710
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
7
Operating Guidelines
USING THE SELECTION MENU (continued)
4-b. TANK FILL (R-134a Users)
NOTE: If using a refillable tank, place the tank upside down and connect the
lowside service hose to the vapor valve.
Set the SELECTOR switch to R-134a:
1. Connect the tank to quick-coupler adapter (supplied with the unit) to the
low side service hose.
2. Connect the low side service hose to the source tank and open valve.
3. Select TANK FILL from the Selection Menu.
4. Press ENTER. Then press START and the tank automatically refills. The
unit stops when a sufficient amount of refrigerant has been transferred to
the ESV- or - the source tank is empty.
NOTE: Press STOP if you wish to stop fill before it completes.
5. Close the valve on the source tank.
6. Disconnect the 96" blue service hose from the adapter, then disconnect the
adapter from the source tank.
7. Press STOP to exit.
VACUUM OIL TIME
This feature displays the number of hours the vacuum pump has been used since
the last oil change and needs reset after an oil change. Change the vacuum pump
oil after every 10 hours of operation. See the Maintenance section on page 20 of
this manual for instructions.