For R-12 and R-134a Refrigerants .................................1
Manuel de Fonctionnement, Modèle 348002K/348012K
Unité de Récupération/Recyclage/Recharge
Pour Réfrigérant R-12 e R-134a .................................. 30
Manuale Operativo, Modelli 348002K/348012K
Unità di Recupero/Rigenerazione/Ricarica
Per refrigeranti R-12 e R-134a..................................... 60
Manual Operativo, Modelo 348002K/348012K
Unidad de Recuperación/Reciclado/Recarga
De los Refrigerantes R-12 y R-134a............................ 90
Bedienungs-Anleitungen, Modell 348002K/348012K
Rückgewinnen/Recyclen/Abfüllen Station
Für R-12 und R-134a Kältemittel ............................... 120
Series: 348002K/348012K
Refrigerants: R-12 and R-134a
Refrigerant Recovery,
Recycling and Recharging Station
WARNING
PRESSURIZED TANK CONTAINS LIQUID REFRIGERANT. OVERFILLING OF THE TANK MAY CAUSE VIOLENT
EXPLOSION AND POSSIBLE INJURY OR DEATH. Refer to the instruction manual for tank specifications and ordering
information. Do not recover refrigerants into a non-refillable storage container! Federal regulations require refrigerant to
be transported only in containers meeting DOT spec. 4BW or DOT spec. 4BA.
ALL HOSES MAY CONTAIN LIQUID REFRIGERANT UNDER PRESSURE. Contact with refrigerant may cause injury.
Wear proper protective equipment, including safety goggles. Disconnect hoses with extreme caution.
HIGH VOLTAGE ELECTRICITY INSIDE PANELS. RISK OF ELECTRICAL SHOCK. Disconnect power before servicing
unit. Refer to the instruction manual.
TO REDUCE THE RISK OF FIRE, avoid the use of an extension cord because the
extension cord may overheat. However, if you must use an extension cord, use No. 14 AWG at the minimum and as
short as possible. Do not use this equipment in the vicinity of spilled or open containers of gasoline or other flammable
substances.
Use this equipment in locations with mechanical ventilation that provides at least four air changes per hour or locate the
equipment at least 18 inches above the floor.
Make certain all safety devices are functioning properly before operating the unit. Before operating, read and follow the
instructions and warnings in this manual.
CAUTION: SHOULD BE OPERATED BY QUALIFIED PERSONNEL. Operator must be familiar with air conditioning
and refrigeration systems, refrigerants and the dangers of pressurized components.
Use only with R-12 or R-134a. This equipment is not designed for any other purpose than recovering, recycling
or recharging refrigerants! Do not mix refrigerant types!
ATTENTION!
Ce réservoir sous pression contient du frigorigène liquide. S’il est surchargé, ce réservoir peut exploser et causer des
blessures ou la mort.
ATTENTION. Débrancher avant la maintenance.
ATTENTION. Pour réduire les risques d’incendie, ne pas utiliser de cordon prolongateur de section inférieure à 14 AWG
de facon à éviter la surchauffe du cordon.
ATTENTION. Utiliser seulement du frigorigène R-134a.
OPERATING NOTES
At temperatures exceeding 120
Use the Series 348002K/348012K only with R-12 or R-134a! Cross-contamination with other refrigerant types will cause
severe damage to the A/C system and to service tools and equipment. Do not mix refrigerant types through a system or
in the same container!
Avoid breathing A/C refrigerant and lubricant vapor or mist. Exposure may irritate eyes, nose and throat. To remove
R-12 or R-134a from the A/C system, use service equipment certified to meet the requirements of SAE-J2210 (R-12 or
R-134a recycling equipment). If accidental system discharge occurs, ventilate work area before resuming service.
R-12 or HFC-134a service equipment or vehicle A/C systems should not be pressure tested or leak tested with compressed air. Some mixtures of air/HFC-R-12 /R-134a have been shown to be combustible at elevated pressures. These
mixtures are potentially dangerous and may result in fire or explosion causing injury or property damage.
Additional health and safety information may be obtained from refrigerant and lubricant manufacturers.
Mfd. by Robinair, SPX Corporation, Montpelier, OH 43543
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
1
Introduction
This manual contains important safety procedures concerning the
operation, use, and maintenance of this product. Failure to follow the
instructions contained in this manual may result in serious injury. If you are
unable to understand any of the contents of this manual, please bring it to
the attention of your supervisor. Do not operate this equipment unless you
have read and understood the contents of this manual.
The 348002K and 348012K models are designed to be used on R-12 and R-134a
vehicles. They are compatible with existing service equipment and standard service
procedures.
The 348002K model is UL-listed. The 348012K is CE approved. Both are single
pass systems that meet the SAE specifications for recycled refrigerant.
To validate your warranty, complete the warranty card attached to your unit and
return it within ten days from date of purchase.
GLOSSARY OF TERMS
A/C SystemThe air conditioning system being serviced.
UnitThe refrigerant recovery/recycling/recharging unit.
External Storage VesselThe refillable refrigerant storage vessel designed
specifically for this unit.
Source TankA disposable tank of new refrigerant used to refill
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
3
Set-Up Instructions
INITIAL SET-UP
CAUTION!CAUTION!
CAUTION! R-134a systems have special fittings (per SAE
CAUTION!CAUTION!
specifications) to avoid cross-contamination with R-12 systems. Do
not attempt to adapt your unit for another refrigerant — system
failure will result! Read and follow all warnings at the beginning of
this manual before operating the unit.
CACA
UTION! UTION!
CA
UTION! Avoid the use of an extension cord because the
CACA
UTION! UTION!
extension cord may overheat. However, if you must use an
extension cord, use a No. 14 AWG minimum and keep the cord as
short as possible.
IMPORTANT!
You must press
the MENU key to
access all the
functions.
1. Lock both front casters of the unit by stepping on the cam brake levers, plug
the power cord into the power cord receptacle (Item 9 in the INST 0707
drawing on page 3). Turn on the MAIN POWER switch.
2. Press MENU.
3. Use the UP and DOWN arrows to select LANGUAGE SELECTION. Press
ENTER.
4. Use the UP and DOWN arrows to scroll through the language options and
press ENTER to select a language and exit LANGUAGE SELECTION.
5. Press MENU. Use the ARROW keys to go to SELECT AUTO RESTART.
Press ENTER.
6. Use the UP and DOWN arrows to toggle between AUTO RESTART ON and
AUTO RESTART OFF. Press ENTER to select.
NOTE: See the Operating Guidelines section of this manual for a description of
these functions.
7. Press MENU. Use ARROW keys to go to SELECT PROMPT. Press ENTER.
4
8. Use the UP and DOWN arrows to toggle between BASIC PROMPTS and
ADVANCED PROMPTS. Press ENTER to select.
NOTE: See the Operating Guidelines section of this manual for a description of
these functions.
1. Press VACUUM to get to the VACUUM mode. Press START to go into
VACUUM.
Set Up Instructions
NOTE: The vacuum pump is shipped without oil in the reservoir. Before
starting the pump, oil must be added to the pump or damage may occur.
2. Close all manifold valves on the control panel.
3. Remove bolts holding the door closed and open the door.
4. Remove the black plastic plug from the fill port on the top of the vacuum
pump.
5. Attach the oil fill tube to the 16 oz. bottle of vacuum pump oil provided in the
accessory kit.
6. While the vacuum pump is running, add oil until it reaches the center of the
sight glass. Press STOP. The vacuum pump is now filled to the proper level
with oil.
7. Pour oil (approximately 12 oz.) into the fill port of the vacuum pump until the
oil appears at the bottom of the sight glass. Press ENTER.
IMPORTANT!
For maximum
performance, be
sure to change
the vacuum
pump oil
frequently.
IMPORTANT!
Be sure the
pump is
running when
adding oil.
8. Replace the plug in the fill port.
9. Press STOP to exit.
1. Oil Fill Port
2. Sight Glass
3. Oil Drain
10. Close the door and replace the bolts holding the door shut.
INSTALLATION ROUTINE
1. Press MENU. Use the ARROW keys to go to the INSTALLATION
ROUTINE.
2. Press ENTER. The display toggles between CONNECT LS RXX HOSE TO
SOURCE TANK and TURN ALL VALVES TO VACUUM/RECOVER
AND PRESS START TO BEGIN. Follow the on-screen prompts.
3. Remove the service hoses from the accessory kit and remove
the plugs from the hoses using a pair of pliers.
4. Attach the service hoses to the high and low side bulkheads on the rear of the
unit. Attach the R-134a hoses to the left rear. Attach the R-12 hoses to the
right rear. Attach the RED hoses to the bulkheads labeled HIGH and the
BLUE hoses to the bulkheads labeled LOW.
1
2
3
INST0760
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
5
Operating Guidelines
5. Press START. The unit automatically evacuates the system for 5:00 minutes
to remove any air from the external storage vessel (Ensure that all tank valves
are open).
IF THE SELECTOR SWITCH IS SET TO R-134A:
6. Connect the lowside service coupler to the source tank valve, using the
adapter supplied with the unit, when the 5:00 minute evacuation is complete.
Open the service coupler and turn manifold valves to RECOVER/VACUUM.
IF THE SELECTOR SWITCH IS SET TO R-12:
7. When the 5:00 minutes evacuation is complete, connect the low side hoses the
hose adapter supplied with the unit. Attach the adapter to the source tank.
USING THE SELECTION MENU
1. Press MENU. The top line of the display reads LANGUAGE SELECTION.
2. Use the UP and DOWN arrows to scroll through the menu choices. The menu
choices are (in order of appearance):
3. Press ENTER to make a choice from the menu. Press STOP to terminate any
process.
1. LANGUAGE SELECT
2. CHANGE FILTER
3. FILTER WEIGHT
4. SELECT AUTO RESTART
5. MEASUREMENT UNITS
6. CHANGE VACUUM PUMP OIL
7. TANK FILL
8. VACUUM OIL TIME
9. INSTALLATION ROUTINE
10. SELECT PROMPTS
11. CHANGE DEFAULT (Password
Protected)
CHANGE FILTER
The filter-drier removes acid, particulates and water from the refrigerant. Change
the filter-drier after 150 pounds of refrigerant has been filtered. See the DRIER
RECOVERED LBS. section on the following page as well as the Maintenance
Section on page 20 for instructions.
NOTE: If using a refillable tank, place the tank upside down and connect the
lowside service hose to the vapor valve.
Set SELECTOR switch to R-12:
1. Connect the 6" yellow adapter to the end of the low side service hose.
2. Connect the low side service hose to the source tank and open valve.
3. Select TANK FILL from the Selection Menu.
4. Press ENTER. Then press START and the tank automatically refills. The
unit stops when a sufficient amount of refrigerant has been transferred to the
ESV- or - the source tank is empty.
NOTE: Press STOP if you wish to stop fill before it completes.
5. Close the valve on the source tank.
6. Disconnect the 96" blue service hose from the adapter, then disconnect the
6" yellow adapter from the source tank.
7. Press STOP to exit.
R-12
Low Side
Service Hose
Source
Tank
ESV
INST0710
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
7
Operating Guidelines
USING THE SELECTION MENU (continued)
4-b. TANK FILL (R-134a Users)
NOTE: If using a refillable tank, place the tank upside down and connect the
lowside service hose to the vapor valve.
Set the SELECTOR switch to R-134a:
1. Connect the tank to quick-coupler adapter (supplied with the unit) to the
low side service hose.
2. Connect the low side service hose to the source tank and open valve.
3. Select TANK FILL from the Selection Menu.
4. Press ENTER. Then press START and the tank automatically refills. The
unit stops when a sufficient amount of refrigerant has been transferred to
the ESV- or - the source tank is empty.
NOTE: Press STOP if you wish to stop fill before it completes.
5. Close the valve on the source tank.
6. Disconnect the 96" blue service hose from the adapter, then disconnect the
adapter from the source tank.
7. Press STOP to exit.
VACUUM OIL TIME
This feature displays the number of hours the vacuum pump has been used since
the last oil change and needs reset after an oil change. Change the vacuum pump
oil after every 10 hours of operation. See the Maintenance section on page 20 of
this manual for instructions.
USING THE SELECTION MENU (continued)
FILTER WEIGHT
This function is used to show the operator how many pounds of refrigerant have
been recovered since the last filter change.
1. Select FILTER WEIGHT from the menu. Press ENTER.
2. The display shows amount of refrigerant recovered since last filter change.
3. If display reads greater than 300 lbs., go to MENU/CHANGE FILTER
4. Press STOP to exit.
SELECT PROMPT
Use the BASIC PROMPT option to receive step-by-step, on-screen prompting
through any procedure. Use ADVANCED PROMPT once you know the procedure
and no longer need the step-by-step routine.
1. Choose SELECT PROMPTS from the menu. Press ENTER.
2. Toggle between BASIC/ADVANCED using the ARROW keys.
3. Press ENTER to select the current choice.
SELECT AUTO RESTART
The AUTO RESTART ON option is used to automatically restart the unit if a
pressure rise is detected by the unit during the five minute waiting period after
recovering refrigerant. If AUTO RESTART OFF is selected, the operator must
watch the gauges for a pressure rise and manually restart the recovery process if a
pressure rise is detected.
1. Select AUTO RESTART. Press ENTER.
2. Use ARROW keys to toggle between the two options.
3. Press ENTER to select the current choice.
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
9
Operating Guidelines
USING THE SELECTION MENU (continued)
MEASUREMENT UNITS
1. Select MEASUREMENT UNITS from the menu. Press ENTER.
2. Toggle between UNITS ENGLISH and UNITS METRIC using the ARROW
keys.
3. Press ENTER to select the current choice.
LANGUAGE SELECTION
The operator can choose between English, Spanish, French, or German.
1. Scroll through the selection menu to LANGUAGE SELECTION and press
ENTER.
2. Use the UP and DOWN arrows to scroll through the languages and then press
ENTER to save the current choice.
INSTALLATION ROUTINE and FIRST FILL
The INSTALLATION ROUTINE is an automatic function that is used only for
initial set-up. See the Initial Set-Up section of this manual for details.
Follow the recommended service procedure for the containment of R-12 and R-134a.
The recovery compressor is not a vacuum pump. The compressor pulls the A/C
system to a partial vacuum only. You must use the unit’s vacuum cycle to remove
moisture from the A/C system. We recommend a minimum 15-minute vacuum with
more time as required by the system manufacturer.
This unit is designed to be used with the manifold gauge set built into the control
panel.
It includes a 6 cfm (142 l/m) vacuum pump for fast, thorough evacuation. Be sure to
change the vacuum pump oil after 10 hours of vacuum pump use.
R-12 and R-134a systems require special oils. Refer to the A/C system manufacturer’s
service manuals for oil specifications.
NOTE: The following operating instructions are written to be used with the BASIC
PROMPTS mode of operation. It is recommended that the BASIC PROMPTS mode
is used until the operator becomes very familiar with the operation of the unit. See
the OPERATING GUIDELINES section of this manual for instructions on how to
select between BASIC PROMPTS and ADVANCED PROMPTS.
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
13
Operating Instructions
RECOVERING REFRIGERANT
Always wear safety goggles when working with refrigerant. Read and
follow all warnings at the beginning of this manual before operating
the unit.
1. Connect the power cord to the back of the unit and plug into the proper
voltage outlet.
2. Turn on the MAIN POWER and empty the oil drain bottle located on the right
hand side of the unit.
3. Press RECOVER.
4. If 300 or more pounds of refrigerant has been recovered since the last filterdrier change, the display reads REPLACE FILTER.
5. Connect the high and low side hoses to the A/C system service ports. For
R-134a, open the coupler valves.
WARNING
6. Place both High and Low Side manifold valves in the Recover/Vacuum
position on the control panel.
7. If the system pressure is below 25 psi, the display reads LOW SYSTEM
PRESSURE until the pressure increases or the START button is pressed.
8. If the unit has refrigerant in the low-side plumbing, it begins the clearing
process and displays CLEARING. If you wish to skip the clearing operation or
stop the clearing prematurely, press START.
NOTE: An inaccurate recovery weight may result if the clearing operation is
not completed.
9. When the system has recovered to a vacuum level of approximately 13 in. Hg.,
the compressor automatically shuts off.
10. The unit then goes into automatic oil drain and the display reads OIL
DRAINING. Oil draining can require up to 90 seconds to complete.
11. After the oil drain is complete, the display alternates between:
RECOVERY COMPLETE CHECK OIL BOTTLE.
RECOVERED XXX.XX lbs. RECOVERED XXX.X lbs.
12. Check the oil drain bottle and note the amount of oil that was removed from
the A/C system. This is the amount of oil that must be charged into the A/C
system after evacuation is complete.
13. To ensure complete recovery of refrigerant, wait 5 minutes and watch the
manifold gauges for a rise in pressure above 0 in. Hg. A pressure rise may
occur if there was freezing in the A/C system during recovery. If a rise occurs,
press START to repeat the recovery process. Repeat as needed until the
system pressure holds for two minutes, then press STOP. The AUTO
RESTART ON option can be used to automatically restart the recycling
process if the unit detects a pressure rise after five minutes. See the Selection
MENU section for details. This process meets SAE Spec J2211.
14. Press STOP to exit.
Recovery is now complete. You are now ready to make any repairs to the A/C
system, if necessary, or advance to the Evacuation Process.
Diagram of the Oil Injection System
Oil Injector Bottle
Oil Drain Bottle
INST 0713
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
15
Operating Instructions
EVACUATING THE A/C SYSTEM
Always wear safety goggles when working with refrigerant. Use only
authorized refillable refrigerant tanks. Read and follow all warnings at the
beginning of this manual before operating the unit. In addition to the
number keys, the keypad contains special keys that accomplish specific
operating functions.
WARNING
IMPORTANT!
You should
evacuate for at
least 15 minutes
to ensure
adequate moisture
and contaminant
removal.
IMPORTANT!
If the vacuum
pump has run for
10 or more hours
without an oil
change, the
message
VACUUM OIL
TIME = Xhr. Xmin
Xsec appears on
the display.
Change the
pump oil
following the
procedures in the
MAINTENANCE
INSTRUCTIONS.
1. Connect the service hoses to the vehicle. R-134a users: Open the coupler
valves.
2. Place both High and Low Side manifold valves in Recover/Vacuum.
3. Turn the unit on and press VACUUM.
4. If the vacuum pump has been run more than 10 hours since the last oil change,
the display reads: VACUUM OIL TIME= X hr. Xmin. Xsec. Press STOP to
change the vacuum pump oil or press START to continue. Instructions for
changing the vacuum pump oil are located in the maintenance section of this
manual.
NOTE: Vacuum Pump oil should be changed after 10 hours of use to maintain
maximum performance and endurance levels.
5. If the system being evacuated contains a pressure over 25 psi at any point
during the evacuation, the display reads HIGH SYSTEM PRESSURE . This
message indicates that the A/C system contains refrigerant. Press RECOVER
to continue. After recovery is complete, return to Step 1 to evacuate the A/C
system.
6. If the pressure is below 25 psi, the user is prompted to press START to
VACUUM or press CHARGE to use the VACUUM-CHARGE (VAC-CHG)
feature. If VACUUM is selected, the unit vacuums the system only and user
interaction is required to enter the CHARGE mode. If the VACUUMCHARGE feature is chosen, the unit automatically charges the system after
evacuation is complete.
NOTE: If any oil was drained from the system during recovery, DO NOT use the
VAC-CHG feature. The oil must be replenished into the A/C system, which is not
possible when the VAC-CHG function is used.
VACUUM
1. Press ENTER to accept the default evacuation time of 15:00 minutes or enter
the desired vacuum time by using the number keys (To enter 10 minutes, press
1 and 10:00 should appear on the display. To enter 1 minute, press 0 then press
1, and 1:00 should appear on the display).
2. Press ENTER. The unit evacuates the A/C system and stops when the
specified time has elapsed.
3. You are now ready to replenish the A/C system oil (if necessary) or to recharge
the system with refrigerant.
4. Press STOP to exit.
IMPORTANT!
You should
evacuate the A/C
system for at
least 15 minutes
to ensure
adequate
moisture and
contaminant
removal.
VAC-CHG
1. Press CHARGE to select the VAC-CHG feature.
2. Press START to charge the default amount of refrigerant (2.00lb) or use the
number keys to enter the desired charge weight. Then press ENTER.
3. If the weight entered leaves less than 5 lbs. of refrigerant in the external storage
vessel, the VAC-CHG process does not begin and the display reads LOW
REFRIGERANT. At this point, refrigerant must be added to the external
storage vessel. See the OPERATING GUIDELINES section of this manual for
external storage vessel refill instructions and then return to Step 1 of
EVACUATING THE A/C SYSTEM.
4. If the external storage vessel contains a sufficient amount of refrigerant, press
ENTER to accept the default evacuation time of 15:00 minutes or enter the
desired vacuum time by using the number keys. Then press ENTER.
5. The unit automatically charges the A/C system after the specified vacuum time
has elapsed.
6. Advance to Step 6 of RECHARGING THE A/C SYSTEM in this manual to
complete the charging process.
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
17
Operating Instructions
REPLENISHING A/C SYSTEM OIL
Before charging the A/C system, you must replenish any oil removed from the A/C
system during the recovery process.
1. Select the correct oil for the A/C system being serviced. Refer to the vehicle
manufacturer's service manual.
IMPORTANT!
You can charge
oil through either
the low side or
high side, or
both, depending
on the vehicle
manufacturer’s
recommendation.
Just open the
appropriate
manifold valve or
valves.
CAUTION! CAUTION!
CAUTION! To prevent air from entering the A/C system, never let the oil
CAUTION! CAUTION!
level drop below the pick-up tube while charging or replenishing.
2. Adjust the O-ring around the oil injector bottle to the required oil charge level.
For example, if the bottle's oil level is at 4 ounces and you need 1/2 ounce of
oil to replenish the A/C system, place the o-ring at the 3 1/2 ounce level.
3. Install the bottle on the oil injection assembly on the back of the unit.
CAUTION! CAUTION!
CAUTION! Never open the oil injection valve while there is positive
CAUTION! CAUTION!
pressure in the A/C system. This action could blow oil back through the bottle
vent.
4. Place the Low Side valve in the Closed position. Place the High Side valve in
the Oil Inject/Charge position.
5. Turn the oil injection valve at the top of the bottle and watch the level of oil
being drawn into the A/C system. This process takes only seconds—watch
carefully!
6. Turn OFF the valve when the required oil charge has been pulled into the
system.
Always wear safety goggles when working with refrigerant. Use only
authorized refillable refrigerant tanks. Disconnect hoses with extreme
caution!
All hoses may contain liquid refrigerant under pressure. Read and follow
all warnings at the beginning of this manual before operating the unit.
1. Press CHARGE.
2. Accept either the default weight by pressing START or type in a weight with
the number keys and press START (For example, to program 3 lbs, press 3
and 3.00 lbs will appear on the display. To program 3.25 lbs, press 3-2-5, in
that order, and 3.25 lbs will appear on the display).
3. If the weight entered will leave less than 5 lbs. of refrigerant in the refrigerant
tank, the charge function will not start and the display will read:
IMPORTANT!
You should
evacuate the A/C
system for at
least 15 minutes
for adequate
moisture and
contaminant
removal.
LOW REFRIGERANT
Refrigerant XX.XX lbs.
See the Operating Guidelines section of the manual for refill instructions.
4. Close the Low Side valve. Place the High Side valve in the Oil Inject/Charge
position (Note: Use the valves corresponding with the refrigerant you are
working with).
5. Upon entering a valid charge weight, the display shows:
CHARGE MODE
AMT. CHARGED XX.XX lbs.
Press START to continue.
6. The display will say "Charge complete. Amt. charged XX.XX".
7. Close the high and low side coupler valves and remove the service
hoses from the A/C system.
8. Turn off the MAIN POWER switch.
The A/C system is now ready for use.
Note: To add less than 1 pound of refrigerant, such as 0.25, press 0-2-5, in that order.
Closed
Oil Inject/Charge
CORRECTING AN INCOMPLETE CHARGE
INST 0770
On ocassions the AMT. CHARGED will not finish. The reason for this is that the pressures
in the ESV and the A/C system have equaled. To finish the charge, you should:
1.Turn high side valve on the control panel to the closed position.
2.Turn low side valve on the control panel to recover/vacuum position.
3.Start the vehicle and turn on the A/C.
4.The remainder of the charge will be pulled into the A/C system and display
will read CHARGE COMPLETE.
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
19
Maintenance Instructions
REPLACING THE FILTER-DRIER
Order part #34724 for a replacement filter-drier. The filterdrier on this unit is designed to trap acid and particulates and
is formulated to remove water from the refrigerant. You must
change the filter-drier to assure adequate moisture and
contaminant removal.
Typically, you can recycle up to 300 pounds (136 kilograms)
of refrigerant between filter changes.
CAUTION!For best results, use Robinair filter-driers
(part no. 34724). All performance tests and claims are
based on using this specially-blended filter-drier. Use of
another may affect performance results.
If the circuit breaker trips, all power to the unit is lost. Press the circuit breaker
button to reset. The circuit breaker is located near the fuse on the back of the unit.
GENERAL MAINTENANCE
1. On a regular basis, wipe off the unit with a clean cloth to remove grease, dust
or other dirt.
2. Periodically check the internal components for leaks—over time, fittings can
loosen as the unit is moved. Open the unit door panel and trace lines with a
leak detector. Also, check connections on the back of the unit. Tighten any
loose fittings or connections you may find.
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
23
Replacement Parts
The following is a list of replacement parts and accessories you may need to service
or maintain your unit.
We suggest you keep several filter-driers on hand so you will always be able to
change them and complete any recycling job that is in progress.
Premium High Vacuum Pump Oil is also available in handy quart containers or in
convenient gallon containers:
Quart (shipped 12 quarts per case) 13203
Gallon (shipped 4 gallons per case)13204
96" Red Hose68396A63096
96" Blue Hose68296A62096
FanRA17516RA19409
Filter-Drier3472434724
CompressorRA19735RA19735
Vacuum PumpRA15425RA15425
High Pressure SwitchRA19427RA19427
Main Power SwitchRA19344RA19343
Vacuum SwitchRA19428RA19428
Pump Protection SwitchRA19429RA19429
Automatic Expansion ValveRA19592RA19592
Scale AssemblyRA19603RA19603
Main Circuit BoardRA19594RA19740
High Side GaugeRA19742RA19613
Low Side Gauge RA19741RA19614
Low Side CouplerN/A18190A
High Side CouplerN/A18191A
Automatic Air PurgeRA19476RA19595
RelaysRA17459RA17459
TransformerRA19596RA19596
Solenoid Rebuild KitRA19258RA19258
UL CircuitRA19673RA19673
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
25
Replacement Parts List
348012K Replacement Parts
ComponentR-12R-134a
96" Red Hose68396A63096
96" Blue Hose68296A62096
FanRA17516RA19409
Filter-Drier3472434724
CompressorRA19736RA19736
Vacuum PumpRA15428RA15428
High Pressure SwitchRA19427RA19427
ReplacementReplacement
Part NumberPart Number
Main Power SwitchRA19344RA19343
Vacuum SwitchRA19428RA19428
Pump Protection SwitchRA19429RA19429
Automatic Expansion ValveRA19592RA19592
Scale AssemblyRA19603RA19603
Main Circuit BoardRA19740RA19740
High Side GaugeRA19742RA19613
Low Side Gauge RA19741RA19614
Low Side CouplerN/A18190A
High Side CouplerN/A18191A
Automatic Air PurgeRA19476RA19595
RelaysRA17324RA17324
TransformerRA19596RA19596
Solenoid Rebuild KitRA19258RA19258
UL CircuitRA19673RA19673
This product is warranted to be free from defects in workmanship, materials and
components for a period of one year from date of purchase. All parts and labor
required to repair defective products covered under the warranty will be at no charge.
The following restrictions apply:
1. The limited warranty applies to the original purchaser only.
2. The warranty applies to the product in normal usage situations only, as
described in the Operating Manual. The product must also be serviced and
maintained as specified.
3. If the product fails, it will be repaired or replaced at the option of the
manufacturer.
4. Transportation charges for warranty service will be reimbursed by the factory
upon verification of the warranty claim and submission of a freight bill for
normal ground service. Approval from Robinair must be obtained prior to
shipping to either an authorized service center or the factory.
5. Warranty service claims are subject to factory inspection for product defect(s).
6. Robinair shall not be responsible for any additional costs associated with a
product failure including, but not limited to, loss of work time, loss of refrigerant,
and unauthorized shipping and/or labor charges.
7. All warranty service claims must be made within the specified warranty period.
Proof-of-purchase date must be supplied to the manufacturer.
8. Use of Robinair recovery/recycling equipment with unauthorized refrigerants will
void our warranty. Authorized refrigerants are listed on the equipment or are
available through our Technical Service Department.
This Limited Warranty does not apply if:
•The product, or product part, is broken by accident.
•The product is misused, tampered with, or modified.
•The product is used for recovering or recycling any substance other than
the specified refrigerant type.
348002K/348012K Cool-Tech Recovery/Recycling/Recharging Unit
29
CONVERSION
TABLE
Visit our web site at
OZ.LBS.
0.50.03
1.00.06
1.50.09
2.00.13
2.50.16
3.00.19
3.50.22
4.00.25
4.50.28
5.00.31
5.50.34
6.00.38
6.50.41
7.00.44
7.50.47
8.00.50
8.50.53
9.00.56
9.50.59
10.00.63
10.50.69
11.00.69
11.50.72
12.00.75
12.50.78
13.00.81
13.50.84
14.00.88
14.50.91
15.00.94
15.50.97
16.01 lb.
www .robinair.com
or call our Toll-Free
Technical Support Line at
800-822-5561
in the continental U.S. or Canada.
In all other locations, contact your local distributor. To help us serve
you better, please be prepared to provide the model number, serial
number, and date of purchase.
To validate your warranty, you must complete the warranty card
attached to your unit and return it within ten days from date of purchase.
• NATIONWIDE NETWORK OF AUTHORIZED SERVICE CENTERS
If your unit needs repairs or replacement parts, you should contact
the service center in your area. For help in locating a service center,
call the toll free technical support line.
Due to ongoing product improvements, we reserve the right to change design,
specifications and materials without notice.
The 348002K and 348012K are designed to meet all applicable agency certifications including Underwriter's Laboratories, Inc., SAE Standards and CUL. Proper
maintenance of this equipment will provide accurate A/C service for many years.
Certain state and local jurisdictions dictate that using this equipment to sell refrigerant by weight may not be permitted. We recommend charging for any A/C service
by the job performed.
This weight scale provides a means of metering the amount of refrigerant needed
for optimum A/C system performance as recommended by OEM manufacturers.
SPX
123319 (Rev. 05/00) 348002K/348012K Operating ManualPrinted In USA