Roberts Gorden CTCU, CTCU 11, CTCU 15, CTCU 27, CTCU 22 User Manual

...
Page 1
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Leave the building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
7. If you cannot reach your gas supplier, call the Fire Department.
WARNING
®
C mbat
Compact Tubular Unit Heaters
Installation, Commissioning,
Operation & Service Manual
Models CTCU 7
CTCU 11 CTCU 15
Fire Hazard
Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
WARNING
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the installation, operation and service manual thoroughly before installing or servicing this equipment.
Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
CTCU 27 CTCU 32
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your serviceman with necessary information.
Quality in Any Language™
© Copyright 2006 Roberts-Gordon, LLC
Roberts-Gordon Europe Limited
Oxford Street Bilston, West Midlands WV14 7EG UK Telephone: +44(0) 1902 494425 Fax: +44(0) 1902 403200 Service Telephone: +44(0) 1902 498733 Service Fax: +44(0) 1902 401464 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
www.rg-inc.com
P/N 11110 0 UK Re v B 10 / 0 6
Page 2
Page 3
TABLE OF CONTENTS
SECTION 1: Heater Safety...................................................... 2
SECTION 2: Installer Responsibility .....................................2
2.1 Clearances to Combustibles ........................................ 2
2.2 Corrosive Chemicals....................................................2
2.3 National Standards and Applicable Codes .................. 2
SECTION 3: Critical Considerations .....................................3
3.1 Basic Information......................................................... 3
3.2 Location and Suspension ............................................3
3.3 Minimum Required Installation Clearances .................3
3.4 Clearances to Combustibles ........................................ 3
3.5 Ventilation .................................................................... 3
3.6 Gas Supply ..................................................................3
3.7 Electrical Supply .......................................................... 3
3.8 Flue..............................................................................3
SECTION 4: Specifications ....................................................5
4.1 CTCUA (All Models) ....................................................5
4.2 General Technical Data Table (All Models) ..................6
4.3 Technical Data Table (All Models)................................6
SECTION 5: Heater Installation.............................................. 7
5.1 General........................................................................ 7
5.2 Shelf Mounting and Suspension.................................. 7
5.3 Wall Mounting.............................................................. 7
SECTION 6: Flue Installation .................................................9
6.1 Changing Flue and Air Intake Orientation.................... 9
6.2 Flue Installation............................................................9
6.3 Type C
6.4 Type B
SECTION 7: Air Supply......................................................... 11
7.1 Room Sealed Installation ........................................... 11
7.2 Open Flued Installation .............................................. 11
7.3 Building Ventilation ..................................................... 11
SECTION 8: Gas Piping........................................................12
8.1 Connections............................................................... 12
SECTION 9: Wiring and Electrical Information................... 13
9.1 Electrical Supply ........................................................ 13
9.2 Remote Controls ........................................................ 13
9.3 CTCUA Wiring Diagram Models 7 - 32...................... 14
SECTION 10: Commissioning..............................................15
10.1 Pre-Commission Checks.......................................... 15
10.2 Begin Commissioning ..............................................15
10.3 Complete the Commissioning ..................................17
SECTION 11: User Instructions............................................ 18
11.1 User Instructions.......................................................18
11.2 Heater Operation ...................................................... 18
11.3 Common User Controls ............................................ 18
11.4 Lighting Instructions..................................................18
11.5 Simple Fault Finding................................................. 19
SECTION 12: Servicing.........................................................20
12.1 Servicing Instructions .............................................. 20
12.2 Burner Maintenance ................................................20
12.3 Fan/Motor Assembly Maintenance........................... 20
12.4 Heat Exchanger Maintenance..................................20
12.5 Gas Control Valve Maintenance...............................20
12.6 Flue Fan................................................................... 20
, C32 & C62 Appliance ...................................... 9
12
Appliance....................................................... 9
22
SECTION 13: Conversion Between Gases ..........................21
13.1 General ....................................................................21
13.2 Burner Conversion ...................................................21
13.3 Gas Valves ...............................................................21
SECTION 14: Troubleshooting .............................................22
14.1 General ....................................................................22
14.2 Troubleshooting For Automatic Ignition
Burner Systems .......................................................23
14.3 Troubleshooting for Flame Supervision System .......24
14.4 Troubleshooting for Solenoid Valves ........................25
14.5 Troubleshooting for Main Fan...................................25
SECTION 15: Removal and Replacement Parts..................26
15.1 Gas Valve .................................................................26
15.2 Burner Compartment ...............................................27
15.3 Ignition Electrode and Flame Probe.........................28
15.4 Flue Fan Vertical Installation ....................................29
15.5 Pressure Switch........................................................30
15.6 Ignition Control .........................................................31
15.7 CTCUA Axial Fan/Guard/Motor Assembly ...............31
15.8 Fan and Limit Thermostats ......................................31
© 2006
Roberts-Gordon, LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon, LLC.
Printed in U.S.A.
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Installation Clearances and Clearances to
Combustibles.............................................................. 4
Figure 2: Suspension Methods ................................................. 7
Figure 3: Shelf Mounting and Hanging Suspension.................. 8
Figure 4: Vertical Louvres (Optional) ........................................8
Figure 5: Flue and Roof Detail ..................................................9
Figure 6: Vertical and Horizontal Flue Termination -
Type B Figure 7: Vertical and Horizontal Flue Termination -
Type C Figure 8: Gas Connection with Stainless Steel
Flex Connector......................................................... 12
Figure 9: Automatic Burner Control Box Sequence ................16
Figure 10: Gas Valve for Heater Models 7 - 32 ....................... 16
Figure 11: Heater Operating Sequence...................................18
Appliance ................................................... 10
22
& C62 Appliances.................................. 10
12 C32
Page 6
Page 7
®
COMBAT
Compact Tubular Unit Heaters are high efficiency heaters and are listed on the Enhanced Capital Allowance Scheme ’Energy Technology Product List’. The ETL symbol is a UK registered certification mark of The Carbon Trust.
Product Approval
ROBERTS GORDON® appliances have been tested and CE certified as complying with the essential requirements of the Gas Appliance Directive, the Low Voltage Directive, the Electromagnetic Compatibility Directive and the Machinery Directive for use on natural gas and LPG when installed, commissioned and maintained in accordance with these instructions.
These instructions refer to appliances designed to operate in the European Union. Appliances designed for other countries (non European Union) are available on request. This appliance must be installed in accordance with the local and national codes in force and used
only in a sufficiently ventilated space, as specified in these instructions. Before installation, check that the local gas distribution systems, nature of gas and pressure, and
adjustment of the appliance are compatible.
1
Page 8
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 1: HEATER SAFETY
Your Safety is Important to Us! This symbol is used throughout the
clearances to combustibles. Affix the tag on a wall
near the heater. manual to notify you of possible fire, electrical or burn hazards. Please pay
2.2 Corrosive Chemicals
special attention when reading and following the warnings in these sections.
Installation, service and annual inspection of heater must be done by a registered installer/contractor
Do not use heater in an area containing corrosive chemicals.
qualified in the installation and service of gas-fired heating equipment.
Read this manual carefully before installation, operation, or service of this equipment.
Corrosive chemicals will damage the burner and heat exchanger parts.
Failure to follow these instructions can result in property damage.
This heater is designed for heating non-residential indoor spaces. Do not install in residential spaces. These instructions, the layout drawing, local codes and ordinances and applicable standards that apply to gas piping, electrical wiring, venting, etc. must be thoroughly understood before proceeding with the installation.
Roberts-Gordon cannot be responsible for ensuring
that all appropriate safety measures are undertaken
prior to installation; this is entirely the responsibility
of the installer. It is essential that the contractor, the
sub-contractor, or the owner identifies the presence
of combustible materials, corrosive chemicals or
halogenated hydrocarbons* anywhere in the
SECTION 2: INSTALLER RESPONSIBILITY
• To install the heater, as well as the gas and elec­trical supplies, in accordance with applicable specifications and codes. Roberts-Gordon recommends the installer contact a local building inspector, Fire Officer or insurance company for guidance.
• To use the information given in the manual together with the local and national codes to perform the installation.
• To install the heater in accordance with the clearances to combustibles of this heater.
• To furnish all needed materials not furnished as standard equipment.
• To plan location of supports, flues and air
premises.
* Halogenated Hydrocarbons are a family of chemical compounds characterized by the presence of halogen elements (fluorine, chlorine, bromine, etc.). These compounds are frequently used in refrigerants, cleaning agents, solvents, etc. If these compounds enter the air supply of the burner, the lifespan of the heater components will be greatly reduced. Warranty will be invalid if the heater is exposed to halogenated hydrocarbons.
2.3 National Standards and Applicable Codes
All appliances must be installed in accordance with the latest revision of applicable standards and local and national codes. This refers also to the electric, gas and venting installation. Note: Additional standards for installations in public garages, aircraft hangars, etc. may be applicable.
intakes.
• To provide access to burners for servicing.
• To provide the owner with a copy of this Installation, Commissioning, Operation and Service Manual.
• To never use heater as support for ladder or other access equipment and never hang or suspend anything from heater.
• To ensure that there is sufficient ventilation in the area to comply with the requirements of all relevant local and national codes.
2.1 Clearances to Combustibles
In all situations, clearances to combustibles must be maintained. Caution must be used when running the heater near combustible materials such as wood, paper, rubber, etc. A wall tag is on the back cover of this manual as a permanent reminder of the safety instructions and the importance of the required
CAUTION
2
Page 9
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Basic Information
CTCU heaters have automatic ignition burners for ON/OFF operation only.
3.2 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position with horizon­tal or vertical discharge.
• May be mounted on a shelf of non-combustible material. (See Page 5, Section 4 and Page 7, Figure 2 for support points.)
• May be suspended from above (See Page 7, Fig- ure 2) or from wall brackets of sufficient strength to support the heater as listed in the Dimension Data Table on Page 5, Section 4.1. Drop rods must be a minimum of 10 mm diameter mild steel. Four suspension points (M10 nuts) are located on top and back side of the heater.
• Must be installed in a manner which allows access to all serviceable components.
SECTION 3: CRITICAL CONSIDERATIONS
3.8 Flue
Choose heater siting to allow for the proper location of the flue. Each heater must be fitted with an individual and correctly sized sealed flue system (See Page 9, Section 6).
No other appliance may be connected to the flue. For room sealed installation, the air intake must be
the same size sealed system and the flue/air intake must terminate at an approved concentric wall or roof terminal.
3.3 Minimum Required Installation Clearances
Clearances around the heater and flue must be as indicated on Page 4, Figure 1; Page 9, Figure 5 through Page 10, Figure 7 to ensure access for servicing, and correct operation.
3.4 Clearances to Combustibles
Clearances must be as indicated on Page 4, Figure
1. If clearances to combustibles are not indicated,
then installation clearances apply.
3.5 Ventilation
It is important to ensure that there is adequate air circulation around the heater to supply air for combustion, ventilation and distribution in accordance with local and national codes.
3.6 Gas Supply
It is important that the gas supply pipe is sized correctly to provide the inlet pressure as stated on the heater data plate. The gas supply pipe and electrical connections must not support any of the heater's weight.
3.7 Electrical Supply
A permanent 230 V 50 Hz 1 Ø electrical supply is required at the main electrical terminals. The heater also requires suitable energy controls in accordance with Section 9.
3
Page 10
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapours the required distance away from the heater.
Failure to follow these instructions can result in death, injury or property damage.
Figure 1: Installation Clearances and Clearances to Combustibles
Installation Clearances
Roof Terminal
Air
Intake
Wall
Terminal
Flue
25 cm
15 cm
3 m
2.5 - 3.5 m*
Roof Terminal
3 m
* Heaters may be mounted at a higher level if destratification
fans are installed.
The heater must always be installed at least 1.8 m above the floor. The flue pipe must have clearance from combustibles by 5 cm.
Clearances to Combustibles
15 cm
50 cm** 10 cm
30 cm
**80 cm is necessary to service
heater.
If installed at low levels where individuals can come in contact with hot heat exchanger components, adequate guarding must be provided.
All distances are minimum clearance requirements for service access, air flow and safety.
4
Page 11
SECTION 4: SPECIFICATIONS
4.1 CTCUA (All Models)
Top View
448 26514
422
Mounting
Holes
463
C
120
SECTION 4: SPECIFICATIONS
4 x M10 Captive Nuts Provided
Air Intake (Optional Position)
Flue (Optional Position)
171
Rear View
4 x M10 Captive Nuts Provided
448
B
Mounting
Holes
728
* 140 for 27 - 32
Dimension Data - CTCUA (All Models)
Model CTCU-7 CTCU-11 CTCU-15 CTCU-22 CTCU-27 / 32
Height
A
Mounting Hole Spacing
B
Centre of Flue (Top Option)
C
Centre of Flue
D
Weight kg 28 30.5 38.5 41 52.3
mm (in)
mm (in)
mm (in)
mm (in)
120
*
Air Intake
Electrical Connection
Lockout Reset Gas Supply
304
(12.0)
239
(9.4)
151
(5.9)
68
(2.7)
Flue
171
Air Intake on Model 22
D
45
85
304
(12.0)
239
(9.4)
151
(5.9)
68
(2.7)
A
End View
450
(17.7)
385
(15.2)
151 (5.9)
68
(2.7)
514
450
(17.7)
385
(15.2)
172
(6.8)
46
(1.8)
660
578
(22.8)
513
(20.2)
149
(5.9)
59
(2.3)
5
Page 12
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
4.2 General Technical Data Table (All Models)
Model CTCU-7 CTCU-11 CTCU-15 CTCU-22 CTCU-27 / 32
CTCUA, Axial Fans
Total Electrical Load W 260 274 336 384 345
R u n C u r ren t A 1.1 1. 2 1. 5 1. 7 1. 5
Start Current A 1.7 1.8 2.5 2.9 2.6
3
Air Flow m
Sound Pressure Level at 3 m
/h 1120 1220 2710 2750 4474
[NR]
dB(A)
[31]
37
[35]
41
[39]
45
[42]
48
[42]
48
Flue and AIr Intake
Flue and Air Intake Size mm Ø 80 80 80 80 100
*Maximum Straight Flue/Air Intake m 2.5 4 5 5 5
Electrical load at 230 V 50 Hz measured by calculating from total run current of appliance.
* Do not exceed the maximum length of flue stated or heater may not operate properly.
Reduce the maximum length stated by 1 m for each 90° bend installed.
**If minimum air flow requirements are not met, then temperature limit devices will shut down the heater.
4.3 Technical Data Table (All Models)
Appliance Category II
Heat Input
Gross CV
Heat Input
Net CV
Approximate
Heat Output
Natural Gas (G20) Data - Inlet Pressure 20 mbar (7.8 in WG) Min. 17 mbar (6.8 in WG) Max. 25 mbar (10 in WG)
Burner Pressure mbar 9.5 9.5 9.5 9.5 9.0 9.0
Gas Rate
Natural Gas (G25) Data - Inlet Pressure 25 mbar (10 in WG) Min. 20 mbar (7.8 in WG) Max. 30 mbar (12 in WG)
Burner Pressure mbar 9.0 9.0 9.5 9.2 9.2 9.3
Gas Rate
LPG / Propane (G31) Data - Inlet Pressure 37 mbar (14.6 WG) Min. 25 mbar (10 in WG) Max. 45 mbar (18 in WG)
Alternative where permitted 50 mbar (20 in WG) Min. 42.5 bar (17 in WG) Max. 57.5 mbar (23 in WG)
Burner Pressure mbar 25.6 29.4 29.4 28.6 29.9 29.9
Gas Rate
2H/L 3B/P
Model CTCU-7 CTCU-11 CTCU-15 CTCU-22 CTCU-27 CTCU-32
kW
(Btu/h) x (1000)
kW
(Btu/h) x (1000)
kW
(Btu/h) x (1000)
3
m
/h
3
ft
/h
3
m
/h
3
ft
/h
3
/h
m
3
kg
/h
8.5 29
7. 7 26
7. 1 24
0.8 29
0.9 33
0.3
0.16
13.4 46
12.1 41
11.1 38
1. 3 45
1. 5 52
0.5
0.25
6227.5 9433
18.3
16.5
24.8
56
15.1 52
1. 7 62
2.0 72
0.7
0.34
0.51
85
23 78
2.6 93
3
108
1
113
29.7 101
27.2
93
3.1
110
3.6
127
1. 2 .61
38.5 131
34.7 118
31.7 108
3.6
127
4.2
148
1. 4 .71
LPG / Butane (G30) Data - Inlet Pressure 29 mbar (11,4 in WG) Min. 20 mbar (7.8 in WG) Max. 35 mbar (13.8 WG)
Burner Pressure mbar 19.2 21.9 22.9 21.4 21.4 22.4
3
/h
Gas Rate
m
kg
3
/h
0.2
0.09
0.4
0.14
0.5
0.19
0.8
0.29
Gas rates corrected to standard conditions 1013.25 mbar 15° C.
6
.9
.34
1. 1 .42
Page 13
SECTION 5: HEATER INSTALLATION
Cone Point
Set Pin
Window
Clamp
Unistrut
10 mm Steel Drop Rod
Nut
Washer
Riv
Nut
10 mm Steel Drop Rod
Washer
Nut
Unistrut
Channel Nut
5.1 General
Heaters are designed for installation above 1.8 m. These heaters must be installed within the heated space. Duct delivery systems are not permitted with axial fans. When handling or supporting the heater from below, ensure that the weight is taken at the support points.
5.2 Shelf Mounting and Suspension
WARNING
Crush Hazard
Use 10 mm steel drop rod minimum.
Failure of the supports can result in death, injury or property damage.
For typical suspension, See Page 7, Figure 2.
Figure 2: Suspension Methods
SECTION 5: HEATER INSTALLATION
5.3 Wall Mounting
For typical suspension, See Page 8, Figure 3. Heaters blowing parallel to the wall can only be installed with the service door away from the wall.
The wall mounting brackets must be attached to a suitable wall through all mounting holes. Screw sizes less than M10 may not be used. In order for the wall mounting brackets to adequately carry the weight of the heater, it must be installed with best building practice.
Ensure all suspension hardware is torqued to a minimum of 27 Nm (20 ft lbs).
NOTE: For vertical installations, use the mounting points on the rear of the unit.
Shelf Mounting
Brackets
Support Points
Existing cabinet screws must be re-used.
Description Part Number Qty. Shelf Mounting Bracket Kit
She l f M o un t in g Bra ck et ( 2) 1111115 10 2 Screw #10 x 1/2" Type AB Phil HWH Z (2)
111115 10 K
94311008 2
7
Page 14
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Figure 3: Shelf Mounting and Hanging Suspension
Shelf Mounting
Hanging
Shelf Mounting Brackets (Fasten to Wall Mounting Bracket)
Wall Mounting Bracket Arm (Right & Left)
M8 Bolt Washer Lock Washer M8 Locknut
Wall Mounting
Torque to 4.5 Nm (40 in lb)
Bracket Diagonal
Wall Mounting Bracket Vertical
Description Part Number Qty. Wall Suspension Mounting Bracket Kit 11111511K 1
Description Part Number Qty. Wall Shelf Mounting Bracket Kit 11111512K 1
Wall Suspension Mounting Bracket Kit 1111510K 1 She lf M o un t in g Br a ck et K it 111115 11K 1
Wall Mounting Bracket Arm Left 111WALL1L 1 Wall Mounting Bracket Arm Right 111WALL1R 1 Wall Mounting Bracket Vertical 111WAL2 2 Wall Mounting Bracket Diagonal 111WAL3 2 M8 x 85 mm Hex Head Bolt 97311405 6 M8 Lock Nut with Nylon Insert 92204504 6 M8 Flat Washer 95204502 6 M8 Lockwasher 96404502 6
Hardware provided to construct mounting bracket assembly only.
M10 Fasteners
Figure 4: Vertical Louvres (Optional)
Remove Horizontal Louvres
Push in
Louvre and compress
spring to remove
(opposite end first)
Description Part Number Vertical Louvre Kit CTCU 7 and 11
Vertical Louvre Bracket 11111903 #10 Screw S103 CTCU 7-11 Vertical Louvres 11111901 Louver Spring 90901200 Instruction Sheet 91040021
111119 01 K
Description Part Number Vertical Louvre Kit CTCU 15 and 22
Vertical Louvre Bracket 11111903 #10 Screw S103
Instruction Sheet 91040021
111119 0 0K
Install Vertical Louvre Brackets (top and bottom) with supplied screws.
Install Vertical Louvres and Springs into Brackets with Springs at Top
Description Part Number Vertical Louvre Kit CTCU 27 and 32
Vertical Louvre Bracket 11111903
#10 Screw S103 27-32 Vertical Louvre 11111902 Instruction Sheet 91040021
11111902K
For models 15 and 22, horizontal louvres are re-used.
8
Page 15
SECTION 6: FLUE INSTALLATION
6.1 Changing Flue and Air Intake Orientation
The heater is sold with horizontal flue and fresh air connections as standard. If vertical flue and fresh air connections are required, follow the instructions on Page 29, Section 15.4.
6.2 Flue Installation
SECTION 6: FLUE INSTALLATION
Figure 5: Flue and Roof Detail
Flue
Terminal
WARNING
Fire Hazard
Some objects will catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapours the required distance away from the heater.
Failure to follow these instructions can result in death, injury or property damage.
The flue must terminate outside of the building. Flues and air intakes must be a fully sealed system and correctly sized for the model. Flues should be assembled as detailed on Page 9, Figure 5 through Page 10, Figure 7. The joints between the flue terminal and the roof or wall must be properly sealed. If the flue passes through a wall or ceiling of combustible material it must be enclosed by a sleeve of non-combustible material and be separated from the sleeve by at least a 25 mm air gap.
Flues and air intakes must be adequately supported so that the heater does not bear the weight of the pipes.
For flue termination See Page 9, Figure 5 through Page 10, Figure 7.
6.3 Type C
Room Sealed. The heaters are designed to be installed as room
sealed appliances. The flue and air intake are run as separate pipes to the special concentric wall or roof terminal. See Page 10, Figure 7. The wire mesh inside the fresh air adapter on the heater must be removed prior to installation.
, C32 & C62 Appliance
12
Roof
25 mm Air Gap to
Combustible Material
Masterflash
Soaker Flashing
or Rain Collar.
Metal Sleeve
Flue
6.4 Type B
Appliance
22
The flue must be fitted with a low resistance terminal. See Page 9, Figure 5 through Page 10, Figure 6.
9
Page 16
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Figure 6: Vertical and Horizontal Flue Termination - Type B
Roof Terminal
Masterflash
Flue
Vertical Option
Flue
Horizontal Option
Appliance
22
Masterflash
Wall Terminal
Figure 7: Vertical and Horizontal Flue Termination - Type C
Roof Terminal
Plastic Cup
Masterflash
Manifold
Air Intake
Vertical Option
Remove Internal
Wire Mesh
Flue
Horizontal Option
& C62 Appliances
12 C32
Wall Plate
10
Flue
Air Intake
Remove Internal
Wire Mesh
Manifold
Wall Terminal
Page 17
SECTION 7: AIR SUPPLY
7.1 Room Sealed Installation
When installed as a room sealed heater, the air for combustion is drawn in from outside the building. It is important to ensure that there is adequate ventilation to provide air for the distribution fan.
7.2 Open Flued Installation
It is important to ensure that there is adequate air supply at all times for both combustion and heating requirements in accordance with local and national codes.
7.2.1 Heaters Installed Within the Heated Space
Where the volume of the heated space is greater than 4.7 m
3
per kilowatt of total rated heat input and the air change rate is at least 0.5/h, additional high and low level ventilation will not be required.
For a building having an air change rate less than
0.5/h, ventilation will be necessary in accordance with local and national codes. Ventilation direct to outside must be provided as follows:
• Heaters up to 70 kW heat input 5.0 cm
2
per kW
of rated heat input
SECTION 7: AIR SUPPLY
7.3 Building Ventilation
Where ventilation is required, air must be taken from an outside point where it is not likely to be contaminated or obstructed.
Where natural ventilation is used, suitable ventilation with outside air at low level must be provided in accordance with Section 7.2.1 and local and national codes.
Where mechanical ventilation is used, extract rate must be 5% - 10% less than the inlet rate. The mechanical ventilation must be interlocked with the burner on the CTCU heater.
11
Page 18
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 8: GAS PIPING
8.1 Connections
Connect the heater to the gas supply ensuring that
WARNING
the final connections are as follows:
• Gas supply pipe work is run in medium or heavy gauge tubing in compliance with local and national codes.
• The gas supply pipe is adequately sized to carry the total volume of gas for the complete
Fire Hazard
Connect gas supply according to Figure 8.
Gas can leak if not installed properly.
Failure to follow these instructions can result in death, injury or property damage.
installation.
• An isolating valve and union connection should be used and fitted into the supply adjacent to the heater.
• For suspended heaters, use an approved metal flexible connection between the isolating valve and the heater. To reduce pressure loss, use
It is important that the gas supply pipe and the electrical connections do not support any of the
one pipe size larger than the heater gas connection.
heater’s weight. A gas meter is connected to the service pipe by the
gas supply company. An existing meter should be checked, preferably by the company, to ensure that
IMPORTANT - The complete installation must be purged and tested for gas soundness in accordance with local and national codes.
the meter is adequate for the rate of gas supply required.
Installation pipes must be fitted in accordance with local and national codes. Pipe work from the meter to the heater(s) must be of adequate size. Pipes of smaller size than the heater inlet gas connection should not be used.
Figure 8: Gas Connection with Stainless Steel Flex Connector
• Hold gas nipple securely with pipe wrench when attaching the flex gas connector.
• Do not twist flexible gas connector.
• Ensure all joints are gas tight.
Do not bend flexible gas connector sharply.
Gas Isolating Valve
Option A:
Stainless Steel Flex Gas Connector
Option B:
Medium or Heavy Gauge Tubing Gas Connector
12
Union
Connection
Drip Leg
Cap
Page 19
SECTION 9: WIRING AND ELECTRICAL INFORMATION
9.1 Electrical Supply
All heater models need a constant 230 V 50 Hz 1 Ø supply connected to terminals L
, N & Earth.
1
Polarity "L & N" must be correct. The voltage between neutral and earth should be 0 and never
9.2.3 Remote Frost Thermostat
When required, connect to L room thermostat. Locate within the heated space adjacent to the most vulnerable equipment that
requires protection. See Page 14, Section 9.3. exceed 15 volts. All heaters and controls must be correctly earthed. All external wiring must comply with the relevant
local codes. Wire specification H05VV-F. External controls must have the same constant
230 V 50 Hz supply.
9.2.4 Remote Fan Controls
The fan will operate automatically providing there is
a constant 230 V supply.
A switch or control wired between L
allow external control of the fan(s).
The fan may be controlled to operate continuously An isolator with a contact separation of at least
3 mm on all poles must be installed adjacent to, but not attached to, the heater to disconnect all supplies
from an external control, with the burner cycling on
and off, providing that the fan run-on at close down
is not impaired. to the heater and any remote control. This switch
should be fused to 5 A.
The final connection to the heater should be made by flexible cable or conduit to the 7 pole plug using 1
2
mm
cable on all models.
SECTION 9: WIRING AND ELECTRICAL INFORMATION
and T2 parallel to the
1
and T1 will
1
WARNING
Electrical Shock Hazard
Disconnect electrical power before servicing.
Failure to follow these instructions can result in death or electrical shock.
9.2 Remote Controls
The heater is designed to be operated by controls installed remote from the heater. See Page 14, Section 9.3.
9.2.1 Burner Controls (Thermostat)
Controls to operate the burner must be connected between L
9.2.2 Positioning Room Thermostats or ROBERTS GORDON
A room thermostat or ROBERTS GORDON control should be mounted on a wall or column at a height of approximately 1.5 metres from the floor to measure the ambient temperature. It should be clear of both cold draughts and the direct path of warm air from the heater.
and T2.
1
®
Control
®
13
Page 20
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
9.3 CTCUA Wiring Diagram Models 7 - 32
GAS
SITE WIRING
VALV E
GREEN/YELLOW
BLUE
BROWN
YELLOW
1112 7910 8 564
IGNITION CONTROL
REMOTE LOCKOUT INDICATION
THERMOSTAT
REMOTE LOCKOUT RESET
NEUTRAL
REMOTE FAN ON
GROUND
LINE
L1NT1T2S3B4
L1NT1T2S3B4
7 POLE PLUG
WHITE YELLOW BLACK
GROUND AT LIMIT
THERMOSTAT
PRESSURE SWITCH
LOCKOUT
RESET WITH
INDICATOR
LIGHT
4 5
1 2
WHITE
BLACK
BROWN
PINK
PURPLE
GREY
23 1
SENSE
IGNITION CONTROL
BLACK
230 V 50 Hz
SUPPLY
7 POLE SOCKET
BROWN
RED
BLACK
FAN DELAY THERMOSTAT
BLUE
BROWN
BLUE
THERMOSTAT
LIMIT
E
N
L
LEN
BROWN
AXIAL FANCOMBUSTION FAN
EMC FILTER
NOTE:
If any of the original wire supplied with the heater must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C and 600 volts.
IGNITION
BLACK
14
Page 21
SECTION 10: COMMISSIONING
Installation, service, commissioning and annual inspection of the heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment. Read this manual carefully before installation, commissioning, operation, or service of this equipment. All components are accessed via the door secured by 4 sheet metal screws. Opening the door exposes live electrical connections and hot components.
WARNING
Electrical Shock Hazard
Use extreme caution while commissioning.
Failure to follow these instructions can result in death or electrical shock.
SECTION 10: COMMISSIONING
1. Check that all site wiring is connected in accordance with the appropriate wiring diagram on Page 14, Section 9.3.
2. Check the correct fuse size is fitted; See Page 13, Section 9.1.
10.1.3 Gas Supply
All aspects of the gas installation including the gas meter must be inspected, tested for soundness and purged in accordance with local and national codes.
Ensure that the air is fully purged from the heater inlet pipe up to the main gas valve inlet test nipple.
10.1.4 Mechanical Checks
1. Check that the fan is free to run and delivery louvres are turned to give required air deflection.
2. Check that the flue (and air intake for room sealed) is installed in accordance with these instructions and local regulations.
NOTE: The limit thermostat is sealed at the factory and is not adjustable.
10.1 Pre-Commission Checks All pre-commission checks must be carried out
before lighting the heater.
Ensure that the heater and all controls are suitable for the gas, pressure and electrical supply to which they are to be connected.
10.1.1 Louvres
Where fitted, the air delivery louvres need to be set during commissioning to give the required air distribution (optional vertical louvres).
WARNING
Cut Hazard
10.2 Begin Commissioning
10.2.1 Before Operating the Heater
To ensure that all the controls are in safe working order, operate the heater for the first time with the isolating gas valve turned off.
1. Turn off the isolating gas valve.
2. Using the installed external control, turn on the burner. The automatic sequence will now begin as described on Page 16, Figure 9.
There will be no ignition of the burner and lockout will occur, which proves the controls are operating correctly.
Tur n off gas and electrical supply before maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can result in severe injury or
10.1.2 Electrical Checks
All pre-commission checks must be carried out before commissioning the heater.
product damage.
15
Page 22
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Figure 9: Automatic Burner Control Box Sequence
Burner sequence for Honeywell S4565C
START
Supply 230 V
Flue Fan
Pressure Switch
Ignition Spark
Start Gas Valve
Flame Signal
NO
P
C
NC
*Purge time begins at pressure switch change over.
30 Sec. Purge*
ts = 10 seconds
Required Incoming Signals
Signals Output By Control
If at any stage the flame fails, the control will go into "lockout". The red light inside the RESET switch will illuminate and the control will need to be manually reset before any further start attempt can be made.
Figure 10: Gas Valve for Heater Models 7 - 32
CLOSE DOWNRUN
End View
Ignition
Output
Flame
Probe
Connection
Regulator
(Under Cover)
Outlet Pressure
Inlet Pressure
Screw
Ignition Control (Plugs into Gas Valve)
12 Cable Connector
Gas Inlet
16
Page 23
SECTION 10: COMMISSIONING
10.2.2 Commissioning the Gas Valve (All Gases)
10.2.2.1 Check Burner Gas Pressure
1. Loosen the screw cover of the outlet (burner) pressure test point and connect a manometer.
2. With the burner firing, measure the pressure on the manometer. To adjust the burner pressure, remove the regulator cover from the valve and turn the regulator adjustment screw to set the required burner pressure as stated in the Tech­nical Data Tables for the correct gas and model on Page 6, Section 4.3.
NOTE: If the correct burner pressure cannot be reached, then check the inlet pressure to the valve, with the burner firing. See Technical Data Tables on Page 6, Section 4.3 for inlet pressure requirement.
Do not continue to adjust the regulator if the pressure is not changing.
If the inlet pressure is too low to allow correct burner pressure setting, then the gas inlet pressure must be corrected before completing the commission.
Check Gas Rate
1. After burner pressure adjustment, allow the heater to operate for at least 15 minutes and then re-check settings.
2. Remove the manometer and refit all covers to the valve and tighten the screw of the outlet pressure tap.
3. Check gas flow rate at gas meter.
10.2.5 Turning Off the Heater
Set the external controls to the "OFF" position and the main burner will stop.
The fan will run until it is stopped automatically by the fan thermostat.
Do not use Electrical Isolator for control of heater. Electrical Isolator will switch off the fan. Heat exchanger could be damaged. Warranty will not cover damage to the heat exchanger if operated improperly.
10.2.6 External Controls
External Controls may include time switch, room thermostat and frost thermostat. Operate each control to ensure that they function correctly. Set the time switch (if fitted) and room thermostat to the users’ requirements.
10.3 Complete the Commissioning
Ensure that all covers are fitted correctly and all test points are properly sealed.
10.3.1 Instruction to the User
Explain the controls of the heater to the user including how to turn it on and off, using the controls fitted on site.
Give this manual to the user. Ensure that the user is shown and understands the
importance of maintaining clearances to combustibles and the user instructions on Page 18, Section 11 through Page 19, Section 11.5 and all warnings defined in this manual.
10.2.3 Combustion Testing
The only adjustment to alter combustion performance is burner pressure. Combustion quality must be tested to prove correct heater operation. Incorrect results will indicate faults with the installation or appliance.
Combustion testing must be carried out with all covers in place. The flue gas is sampled in the flue, within 1 meter of the heater. The values of CO
2
should be between 5.7% to 8.0% for natural gas and
6.8% to 9.2% for LPG dependant upon model. The CO will be up to 80 ppm (0.008%) dry, air free
dependant upon model. Temperature rise of the flue gases above ambient should be approximately 130° C to 160° C. Seal test hole in flue after testing.
10.2.4 Pressure Switch
The pressure switch is factory pre-set for each model and is not adjustable.
17
Page 24
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 11: USER INSTRUCTIONS
11.1 User Instructions
The CTCU heaters are fully automatic and operate from the external controls fitted on site.
The only user controls at the heater are the: Burner Lockout
Reset Button ................ See Page 18, Section 11.3.3
Limit Thermostat Reset See Page 18, Section 11.3.2
These are hand reset devices to give further protection against fan failure.
WARNING
Electrical Shock Hazard
Disconnect electrical power before servicing.
NOTE: To reset, the heat exchanger must be cool.
Description Part Number
Limit Thermostat 90412100
Press to reset
WARNING
Failure to follow these instructions can result in death or electrical shock.
11.2 Heater Operation
When the heater has been switched on by the remote controls installed on site, the main burner will automatically turn on.
The burner control box will control the safe ignition of the flame.
All heaters require a constant gas and electricity supply which must not be interrupted during the normal operation of this heater.
Figure 11: Heater Operating Sequence
THERMOSTAT
CALL FOR
HEAT
BURNER
RUN
FAN
ON
ON
ON
2-3 MINUTES
CLOSE DOWN
RUN ON
11.3 Common User Controls
11.3.1 Fan Thermostat
The fan thermostat is located inside the access door at the top of the heater. See Page 28, Section 15.3.
This control ensures the heater does not blow cold air in the normal heating cycle.
11.3.2 Limit Thermostat
The limit thermostat is located inside the access door of the heater. See Page 28, Section 15.3. This control protects the heat exchanger against overheating.
Explosion Hazard
If control locks out, do not make more than 3
attempts to restart the heater.
Dangerous gas mixtures can build up.
The fault must be registered installer or service engineer.
Failure to follow these instructions can result in death, injury or property damage.
traced and repaired by a
11.3.3 Burner Lockout Reset Button
The red warning light on the back of the heater will illuminate when the control has gone to lockout. This may be caused by flame failure. Press the reset button on the back of the heater (See Page 5, Section 4.1) or the remote reset if installed on site.
11.4 Lighting Instructions
11.4.1 To Turn On Heater
1. Ensure that the electrical and gas supplies to the heater are on. Check that the on site con­trols are “ON”.
NOTE: The thermostat setting must be above the ambient temperature for the heater to operate.
2. The automatic firing sequence will begin as described on Page 16, Figure 9. The heater will now operate automatically under the control of the on site controls. Following long shut down periods, the control may go to lockout. See Page 18, Section 11.3.3.
18
Page 25
11.4.2 To Turn the Heater Off
Set the installed remote controls to the "OFF" position.
The burner will turn off immediately. The fan will continue to run for a few minutes. To restart, turn the control used above to "ON".
11.5 Simple Fault Finding
Some possible reasons for the heater not operating are:
1. Gas supply not turned "ON".
2. Electricity supply not turned "ON".
3. The time and/or temperature controls are not "ON".
4. The limit thermostat may have operated. This may be caused by an interruption of the electri­cal supply or failure of the distribution fan.
If the limit thermostat persistently operates, there is a fault which must be investigated by a contractor qualified in the installation and service of gas-fired heating equipment.
11.5.1 Simple Fault Finding (Burner Faults)
If the burner fails to ignite for any reason, it will go to lockout. This will be indicated by the red light on the back of the heater or at the remote indicator (if fitted).
1. Press in and release the lockout reset button. If a remote reset is not fitted, a reset button is on the back of the heater. See Page 5, Section 4.1.
SECTION 11: USER INSTRUCTIONS
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in your building.
5. Leave the building.
6. Immediately call your local gas supplier after leaving the building. Follow the gas suppliers instructions.
7. If you cannot reach your gas supplier, call the Fire Department.
WARNING
Fire Hazard
Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
Lockout should not occur during normal operation of the heater and indicates there is a fault condition which must be corrected.
19
Page 26
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 12: SERVICING
12.1 Servicing Instructions
After commissioning, the heater will require maintenance to be carried out annually. If the heater is used in a dirty or dusty area, more frequent maintenance may be necessary.
Installation Code and Annual Inspections: All installations and service of ROBERTS GORDON products must be performed by a contractor qualified in the installation and service of gas-fired heating equipment and conform to all requirements set forth in the ROBERTS GORDON governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON and perform service where necessary, using only ROBERTS GORDON
®
manuals and all applicable
®
replacement parts.
®
®
products
2. Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner. See Page 27, Section 15.2.
3. Remove the ignition electrode and flame probe. Check condition of ignition electrode and flame probe. Clean off any deposits which may have been formed, check condition of ceramic insulators. Replace as necessary.
12.3 Fan/Motor Assembly Maintenance
The main fan bearings are permanently sealed and do not need lubrication. Before cleaning, turn off gas and electrical supply. Remove the fan and use a small brush or duster to clean the fan blades from each side. Replace fan when done.
12.4 Heat Exchanger Maintenance
The heat exchanger will remain clean unless a problem has developed with combustion. Inspect the
WARNING
heat exchanger. Look for signs of overheating at the front tubes which may indicate burner over firing or persistently low air flows.
Cut Hazard
Tur n off gas and electrical supply before maintenance.
Fan can start automatically at any time.
Failure to follow these instructions can result in severe
injury or
product damage.
NOTE 1: After any maintenance or repair work, always test fire the heater in accordance with the commissioning instructions on Page 15, Section 10 through Page 17, Section 10.3.1 to ensure all safety systems are in working order before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts on Page 22, Section 14 through Page 25, Section 14.5.
NOTE 2: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks. Any cracks in the pipes or pipe joints must be repaired.
12.5 Gas Control Valve Maintenance
No regular maintenance is required on this device. To change gas control valves, See Page 26, Step
15.1 and Page 30, Section 15.5.
Do not repair or disassemble on site. Replace faulty gas valves with genuine
ROBERTS GORDON
®
replacement parts.
12.6 Flue Fan
The flue fan should not require maintenance. However, if the air pressure switch is causing burner lockout, then remove the flue fan from the vent box by unscrewing the three screws at the mounting plate. Remove the four screws attaching the mounting plate to the fan inlet (See Page 29, Section 15.4). Ensure that the fan is free to run and that the fan wheel is clean.
NOTE 3: Inspect all suspended components and hardware. Insure that they are in good condition, properly tightened, and corrosion free.
12.2 Burner Maintenance
1. Open the door and remove the burner compart­ment cover. See Page 27, Section 15.2.
20
Page 27
SECTION 13: CONVERSION BETWEEN GASES
13.1 General
Conversion between gases will require a change of burner injectors and the gas valve re-commissioning to the new conditions.
13.2 Burner Conversion
Conversion of the burner assembly from one gas to the other is the same for all types of heaters.
1. Remove the burner compartment cover as shown on Page 27, Section 15.2.
2. Remove the 4 screws holding the manifold and pull out the manifold.
3. Remove inshot burners by rotating them and sliding out the bracket.
4. Remove the main burner injectors.
5. Replace with the injectors for the new gas ensuring a gas tight seal.
6. Refit all components in reverse order.
SECTION 13: CONVERSION BETWEEN GASES
13.3 Gas Valves
All gas valves used on the CTCU have pressure regulators that may be set to operate on natural gas or LPG.
Conversion is carried out by re-setting the burner pressure to the value in the data table during commissioning. See Page 6, Section 4.3.
Ensure that the gas inlet pressure to the heater is correct for the new gas, and that the gas supply has been purged of the old gas.
21
Page 28
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 14: TROUBLESHOOTING
14.1 General
WARNING
Explosion Hazard
Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.
Failure to follow these instructions can result in death, injury or property damage.
Start
Are gas & electrical
supplies on?
Ye s
Is Red lockout
warning light on?
No
Does the fan run?
Ye s
Ye s
With external controls on,
does the burner continue
through the heating cycle?
No
Ye s
No
No
Turn on supplies.
Use 14.2 to test burner.
Use 14.5 to test fan.
Has burner Locked Out?
Use 14.2 to test burner.
Ye s
No
The limit thermostat has
tripped.
See Section 11.3.2.
Ye s
Replace axial fan.
Replace limit thermostat.
No
Ye s
Heater Operating
TROUBLESHOOT ENDS.
No
If problems persist, contact
Roberts-Gordon Ltd. at
Tel: +44 (0)1902 498733
www.rg-inc.com
For your safety and optimum heater performance, use only ROBERTS GORDON® replacement parts.
Conduct Commissioning procedure as shown on Page 15, Section 10.
22
Page 29
14.2 Troubleshooting For Automatic Ignition Burner Systems
Start
SECTION 14: TROUBLESHOOTING
WARNING
Are gas & electrical
supplies on?
Ye s
Are external controls on?
Ye s
Is red lockout light on?
No
Does flue fan run?
No
No
Ye s
No
Turn on supplies.
Turn on controls.
Press in lockout reset button
on rear of heater or remote
reset button if fitted.
Is 230 V supply at fan
connections?
Burner control faulty or plug in connections faulty. Repair
or replace as necessary
No
Ye s
Do not touch ignition components.
Voltage from ignition components is high.
Failure to follow these instructions can result in death or electri
Flue fan faulty; replace
Electrical Shock Hazard
cal shock.
Ye s
Does air pressure switch
change over?
Ye s
Wait 30 - 40 seconds.
Is ignition spark operating?
Ye s
Does the flame light?
Ye s
Is red lockout light on?
No
Heater Operating
TROUBLESHOOT ENDS.
Check for too much flue/air inlet
duct. Check for blockage in
No
No
No
Ye s
No
combustion air circuit.
Check for faulty air pressure
switch. See Section 15.5.
Is HT lead okay and
connected?
Is spark electrode okay?
Is the gas valve operating?
To test valve,
See Section 14.4.
Is the flame current at
least 1 µAmp DC when
the flame lights?
If problems persist, contact
Roberts-Gordon Ltd. at
Tel: +44 (0) 1902 498733
www.rg-inc.com
Ye s
Ye s
Ignition control faulty;
See Section 15.6.
No
Replace valve.
Trace fault in supervision
system. See Section 14.3.
replace.
For your safety and optimum heater performance,
®
use only ROBERTS GORDON
replacement parts.
Conduct Commissioning procedure as shown on Page 15, Section 10.
23
Page 30
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
14.3 Troubleshooting for Flame Supervision System
To measure flame current, connect a 0 - 50 μA DC meter in series with the flame probe. If the meter reads negative values, then reverse the test leads.
START
Connect a DC ammeter in
series with the flame probe.
Is the flame present and
at least 1 µA DC flame
current?
Ye s
Is there a current flowing in the
flame probe circuit with no
flame present?
No
Does lockout occur when
there is a flame present?
No
Heater Operating
TROUBLESHOOT ENDS.
No
Ye s
Ye s
No
Use Section 14.1 to
trace the fault.
Is the connecting lead
damaged? Is the flame probe
damaged or touching earthed
components?
Is inlet burner gas pressure
correct? Is live and neutral
polarity correct? Is
flame probe circuit correct?
No
Repair or replace as
necessary.
If problems persist, contact
Roberts-Gordon Ltd. at
www.rg-inc.com
Repair or replace as
Ye s
Ye s
necessary.
Control box faulty.
Replace with correct type.
NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.
24
Page 31
14.4 Troubleshooting for Solenoid Valves
START
SECTION 14: TROUBLESHOOTING
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
Ye s
Does gas pressure at outlet
of the valve rise when
valve turns on?
Ye s
Ye s
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
Ye s
Valve Operating
TROUBLESHOOT ENDS.
No
No
No
No
Fault elsewhere.
Valve or ignition control
faulty. Replace with one of correct type.
Valve faulty.
Replace with one of
correct type.
If problems persist, contact
Roberts-Gordon Ltd. at
Tel: +44 (0) 1902 498733
www.rg-inc.com
14.5 Troubleshooting for Main Fan
START
Does fan run
automatically?
Ye s
Does fan turn on and
off while burner is firing
continously?
No
Fan Operating
TROUBLESHOOT ENDS.
Ye s
No
Is power supply 230 V at
No
terminals T
Fan motor faulty.
Replace with correct type.
Replace fan
delay thermostat.
If problems persist, contact
Roberts-Gordon Ltd. at
Tel: +44 (0) 1902 498733
www.rg-inc.com
Ye s
1 to N?
No
Is there 230 V between
terminals L
1 and N?
Ye s
Replace fan
delay thermostat.
For your safety and optimum heater performance, use only genuine ROBERTS GORDON® replacement parts.
Conduct Commissioning procedure as shown on Page 15, Section 10.
25
Page 32
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 15: REMOVAL AND REPLACEMENT PARTS
See warnings and notes on Page 20, Section 12 before removing or replacing parts.
Burner Components
All serviceable burner parts are accessed by the door on the side of the heater. Remove the four sheetmetal screws.
15.1 Gas Valve
Remove the gas supply pipe at the heater inlet.
Disconnect wire harness
Unplug control from valve.
Remove
fixing
screw.
Replace in reverse order. Verify that the gas flow direction of the valve is correct. Use a minimum amount of gas seal on the thread joint. Check that all the joints are leak free. Reset gas valve. See Page 17, Section 10.2.2.
IT IS IMPORTANT THAT ONLY THE CORRECT GAS VALVE IS USED WHEN REPLACING THESE CONTROLS.
Ignition Control
Description Part Number
Gas Valve VK4105A 90033403 Ignition Control 90434010
26
Page 33
15.2 Burner Compartment
Unscrew Injectors
Manifold
SECTION 15: REMOVAL AND REPLACEMENT PARTS
15.2.1 Burner Injectors
Burner Compartment Cover
Viewing Port
Flame Probe Ignition Electrode
Remove flexible air duct from spigot.
Remove screws and pull off burner cover.
Manifold
Remove manifold
screws and pull
out manifold.
The burner compartment is a sealed compartment. Following any work, re-seal the compartment with the gas pipe rubber seal fully in place and all screws fitted and tight.
Ensure gas tight fitting of injectors. Ensure correct alignment with burners. Ensure all pipe joints are gas tight.
Burners
Injectors
Manifold
Mounting
Bracket
MODEL CTCU-7 CTCU-11 CTCU-15 CTCU-22 CTCU-27 CTCU-32
Injector Quantity 2 3 4 5 6 7
Natural Gas (G20)
Injector size mm Ø 1.78 1.85 1.85 2.06 2.057 2.057
in Ø 0.070 0.073 0.073 0.081 0.081 0.081
Marking 504949464646
RG P/N 91930050 91930049 91930049 91930046 91930046 91930046
Natural Gas (G25)
Injector size mm Ø 1.99 2.06 2.06 2.26 2.261 2.261
in Ø 0.0785 0.081 0.081 0.089 0.089 0.089
Marking 474646434343
RG P/N 91930047 91930046 91930046 91930043 91930043 91930043
LPG Propane (G31) and LPG Butane (G30)
Injector size mm Ø 1.18 1.18 1.18 1.25 1.25 1.25
in Ø 0.0465 0.0465 0.0465 0.049 0.049 0.049
Marking 5656561.251.251.25
RG P/N 91930056 91930056 91930056 91930125 91930125 91930125
Gromet
Marking
27
Page 34
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Burners
.120
(3 mm)
spark
gap
Ignition
Electrode
Flame Probe
Burners
15.3 Ignition Electrode and Flame Probe
Limit
Thermostat
Fan
Thermostat
Ignition
Electrode
Flame
Probe
Burner Compartment
To replace the ignition electrode or flame probe, remove the electrical lead and screw. Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the front view of the burner compartment.
Description Part Number
Spark Electrode 90427411 Automatic Ignition Flame Probe 90439300 Burners 92000002 Fan Thermostat 90412102 Limit Thermostat 90412100
Front Views
28
Page 35
15.4 Flue Fan Vertical Installation
Air Intake
Adapter
Air Intake Adapter Intake & Exhaust
Covers
Gasket
Mounting Plate
to Flue Fan
fixing screws
SECTION 15: REMOVAL AND REPLACEMENT PARTS
Intake & Exhaust Covers
Mounting Plate
to Vent Box
fixing screws
Gaskets
Vent Box
To remove the fan, remove 3 screws securing the fan and mounting plate to the vent box.
To remove the fan from the mounting plate, remove the 4 screws.
Refit in reverse order.
To change the flue and air intake orientation from back to top, remove the fan and mounting plate as above.
Remove intake and exhaust covers from top of the heater.
Rotate the fan, mounting plate and gasket clockwise until the flue adapter lines up with the top hole. Secure with 3 screws.
Remove the flexible duct from the air intake adapter on the back.
Flexible Duct
Remove the air intake adapter from the back of the heater and install in the appropriate hole on top. Reconnect the flexible duct.
Install intake and exhaust covers over the back holes.
Mounting Plate
to Vent Box
fixing screws
MODEL CTCU-7 CTCU-11 CTCU-15 CTCU-22 CTCU-27 CTCU-32
Flue Fan
RG P/N 90710470 90710470 90710470 90710460 90710460 90710460
Air Plate mm Ø 35 44 57 64 109.2 109.2
in Ø 1. 3 8 1. 7 5 2.25 2.50 4.3 4.3
RG P/ N 111112 10 111122 10 1111 321 0 11114 2 10 11115 210 11115210
Fasco
7021-11767
Fasco
7021-11768
Fasco
7021-11769
Ensure sealed joints. Ensure mounting plate orifice is clear and not obstructed.
To rin
S6818
Sit Controls
P1210838
Sit Controls
P1210838
IT IS IMPORTANT THAT ONLY THE CORRECT FLUE FAN SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.
Carry out a commission after working on or changing a flue fan. See Page 18, Section 11.
29
Page 36
COMBAT® CTCU UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
15.5 Pressure Switch
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of pressure switch for model. The pressure switches are colour coded for each pressure setting.
WARNING
Carbon Monoxide Hazard
Use correct pressure switch specified for each model.
Use of incorrect pressure switch could cause unsafe
condition.
Failure to follow these instructions can death or serious injury.
result in
Carry out a commission after working on or changing a pressure switch. See Page 15, Section
10.
Pressure Switch CTCU-7 CTCU-11 CTCU-15 CTCU-22 CTCU-27 CTCU-32
RG P/N 90439812 90439812 90439812 90439803 90439803 90439803
Colour Code orange orange orange grey grey grey
Set Point mbar 0.45 0.45 0.45 1.02 1.02 1.02
in wc 0.18 0.18 0.18 0.41 .041 .041
30
Page 37
SECTION 15: REMOVAL AND REPLACEMENT PARTS
15.6 Ignition Control
The control plugs onto the gas valve. Pull out 12 pin electrical connection. Pull out ignition cable and flame probe cable noting their positions
Release screw securing control to gas valve. Refit in reverse. Ensure correct location of ignition
and flame probe cables. Ensure that the earth connection is made directly to the earth point on the gas valve.
15.7 CTCUA Axial Fan/Guard/Motor Assembly
The axial fan unit for the CTCUA heater is supplied completely assembled and balanced.
15.7.1 Fan Removal and Replacement
Remove the screws
and washers.
15.8 Fan and Limit Thermostats
15.8.1 Removal and Replacement
1. Pull off the electrical connections to the thermostat
2. Unscrew the two screws securing the thermostat
3. Fit a new thermostat with two screws ensuring that the correct temperature setting and type are selected. See Page 6, Section 4.3.
4. Reconnect the electrical connections and test operation.
Description Part Number
Axial Fan CTCU-7 11111910 Axi al F an C TCU -11 111119 11 Axi al F an C TCU -15 111119 20 Axi al F an C TCU -22 111119 21 Axi al F an C TCU -27 /32 11111 92 2
15.7.2 To Replace the Fan Assembly
To replace the fan assembly, reverse the procedure shown above. Fit rubber washers to the guard mountings to reduce vibration.
• Check that the fan blades are free to rotate before turning on the power to the fan.
• Strictly comply with the colour code of the fan wires to ensure correct operation. See Page 14, Section 9.3 wiring diagram.
• Use only genuine ROBERTS GORDON
®
replacement parts.
31
Page 38
Page 39
Page 40
Attach this information to the wall near the ROBERTS GORDON® heater
®
Read the installation, Commissioning, Operation and Service Manual thoroughly before installation, operation or service.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting (above ambient temperature). The automatic starting sequence begins. NOTE: Following long shutdown periods, the burner control may go to to 'LOCKOUT' during the start sequence. Push the reset button to recommence firing. Contact service department if 'LOCKOUT' continues (see manual for details).
TO TURN OFF THE HEATER
1. Turn the thermostat/time switch to 'OFF'. The burner will turn 'OFF' immediately, but fans will continue to cool heat exchanger until the fan thermostat switches off.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the installation and service of gas-fired heating equipment.
Installation Clearances
Roof Terminal
Roof Terminal
WARNING
Fire Hazard
Some objects can catch fire or explode when placed close to heater.
Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.
Failure to follow these instructions can result in death, injury or property damage.
Clearances to Combustibles
Air
Intake
15 cm
15 cm
50 cm** 10 cm
Wall
Terminal
Flue
25 cm
3 m
30 cm
3 m
2.5 - 3.5 m*
**80 cm is necessary to service heater*Heaters may be mounted at a higher level if destratification fans are installed.
Roberts-Gordon, LLC
1250 William Street P.O. Box 44 Buffalo, NY 14240-0044 USA Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
Installation Code and Annual Inspections: All installations and service of ROBERTS GORDON® products must be performed by a contractor qualified in the installation and service of products sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON that a qualified contractor annually inspect your ROBERTS GORDON
Further Information: Applications, engineering and detailed guidance on systems design, installation and product performance is available through ROBERTS GORDON Please contact us for any further information you may require, including the Installation, Operation and Service Manual.
This product is not for residential use.
This document is intended to assist licensed professionals in the exercise of their professional judgement.
© 2006 Roberts-Gordon, LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means  graphic, electronic, or mechanical, including photocopying, recording, taping, or information storage and
www.rg-inc.com Printed in U.S.A.
retrieval systems  without written permission of Roberts-Gordon, LLC.
Roberts-Gordon Europe Limited
Oxford Street Bilston, West Midlands WV14 7EG UK Telephone: +44(0) 1902 494425 Fax: +44(0) 1902 403200
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends
®
products and perform service where necessary, using only ROBERTS GORDON® replacement parts.
Service Telephone: +44(0) 1902 498733 Service Fax: +44(0) 1902 401464 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
®
representatives.
Loading...