Roberts Gorden CRV-B-8, CRV-B-6, CRV-B-4, CRV-B-2 User Manual

®
CoRayVac
Custom Engineered,
Gas-Fired, Low-Intensity
Infrared Heating System
CRV-B-2 CRV-B-4 CRV-B-6 CRV-B-8
CRV-B-10 CRV-B-12
CRV-B-12A
Design Manual
All designs must be installed in strict accordance with the CORAYVAC®
Installation, Operation and Service Manual (P/N 127102NA).
Roberts-Gordon LLC
1250 William Street P.O . B o x 44 Buffalo, New York 14240-0044 Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
CRV-B-9
© 2009 Roberts-Gordon LLC
www.rg-inc.com www.radiantheaters.com www.corayvac.com
P/N 127500NA Rev D 05/09
© 2009
Roberts-Gordon LLC
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon LLC.
TABLE OF CONTENTS
SECTION 1: Concept ..............................................................1
SECTION 2: The CRV-Series System.....................................2
2.1 Safety...........................................................................2
2.2 Zero Regulator ............................................................. 2
2.3 Fuel Savings and Comfort ...........................................4
SECTION 3: Clearances to Combustibles.............................5
3.1 Required Clearances to Combustibles.........................5
SECTION 4: Sizing and Design Considerations...................9
4.1 Radiant Adjustment to Heat Loss ................................9
4.2 Radiant Height Adjustment Factor...............................9
4.3 Selecting the Burners ................................................ 10
4.4 Radiant Distribution ................................................... 10
SECTION 5: Flow Loading.................................................... 12
5.1 Radiant Branch Flow .................................................12
5.2 Pump Capacity ..........................................................14
5.3 Tailpipe Flow.............................................................. 14
SECTION 6: Radiant Tube and Tailpipe............................... 15
6.1 Radiant Tube Length.................................................. 15
6.2 Tailpipe.......................................................................15
6.3 Design Parameters .................................................... 16
6.4 CRV-Series Design Methods ..................................... 16
6.5 Tailpipe Design Method ............................................. 18
SECTION 7: Example CRV-Series System Layouts............21
7.1 Example System Layout (Option 1) ............................ 21
7.2 Example System Layout (Option 2) ............................ 22
7.3 Example System Layout (Option 3) ............................ 22
7.4 Example System Layout (Option 4) ............................ 23
7.5 Example System Layout (Option 5) ............................ 23
7.6 Example System Layout (Option 6) ............................ 24
7.7 Example System Layout (Option 7, 8 and 9)............... 25
SECTION 8: Control Methods .............................................. 26
8.1 ROBERTS GORDON
(P/N 02770002) .........................................................26
8.2 ROBERTS GORDON® ULTRAVAC™..........................26
8.3 SPST Transformer Relay (P/N 90417600K)...............27
8.4 DPST Transformer Relay (P/N 90436300).................27
8.5 Pressure Switch .........................................................27
SECTION 9: Air Supply System ...........................................28
9.1 Pressurized................................................................28
9.2 Non-Pressurized ........................................................ 28
9.3 Outside Air System Design Requirements.................28
SECTION 10: ROBERTS GORDON
Requirements.................................................31
SECTION 11: CRV-Series Equipment Specifications......... 32
11.1 Burner and Burner Controls......................................32
11.2 Equipment ................................................................32
®
System Control
®
ULTRAVAC™ Design
Printed in U.S.A.
TABLE OF FIGURES
Figure 1: Assembly Overview (Two Branch System Shown).....3
Figure 2: Standard Reflector .....................................................6
Figure 3: One Side Reflector.....................................................6
Figure 4: Two Side Reflectors ...................................................6
Figure 5: Universal Shield, Position 1 .......................................7
Figure 6: Universal Shield, Position 2 .......................................7
Figure 7: Universal Shield, Position 3 .......................................7
Figure 8: 2-Foot Deco Grille......................................................8
Figure 9: Barrier Shield .............................................................8
Figure 10: Protective Grille........................................................8
Figure 11: Radiant Distribution (Average Coverage)............... 11
Figure 12: Radiant Distribution (Increased Coverage) ............ 11
Figure 13: Radiant Distribution (Heavy Coverage).................. 11
Figure 14: Burner Flow Units .................................................. 13
Figure 15: Vacuum Loss Curve for 4" Shared Tailpipe...........14
Figure 16: Tube Length vs. Efficiency...................................... 16
Figure 17: Possible Damper Coupling Locations ....................20
Figure 18: Example System Layout (Option 1)....................... 21
Figure 19: Example System Layout (Option 2)....................... 22
Figure 20: Example System Layout (Option 3)....................... 22
Figure 21: Example System Layout (Option 4)....................... 23
Figure 22: Example System Layou
Figure 23: Example System Layout (Option 6)....................... 24
Figure 24: Example System Layout (Option 7)....................... 24
Figure 25: Example System Layout (Option 8)....................... 24
Figure 26: Example System Layout (Option 9)....................... 25
Figure 27: Air Supply System Capacity by Duct Length and
Diameter ................................................................28
Figure 28: Outside Air Blower .................................................29
Figure 29: Sample Layout for Pressurized Outside Air
Systems..................................................................30
t (Option 5).......................23
LIST OF TABLES
Table 1: CORAYVAC® Design Parameters ............................12
Table 2: Pump Capacity..........................................................14
Table 3: Pump Exhaust Requirements ...................................14
Table 4: Allowable Tailpipe Lengths .......................................17
Table 5: Operating Characteristics; Condensing or
Non-Condensing ......................................................18
SECTION 1: CONCEPT
The concept of CRV-Series is easy to understand. However, it means discarding old ideas because CRV­Series is a different kind of heating system.
CRV-Series is a gas-fired, vacuum-operated, low- intensity infrared heating system incorporating a pat­ented incremental burner system.
Gas-Fired means it uses clean-burning Natural or Propane gas.
Vacuum-Operated means that the pump draws all the products of combustion through the system and expels them outdoors.
Low-Intensity means the radiant surfaces of the tubes do not glow red; instead they operate at a lower temperature (less than 900° F or 482.2° C) and radiate heat at lower intensity per square foot of radiating sur- face. Area coverage is provided by long runs of 4" (10 cm) O.D. tubing which hang from the ceiling or roof supports. Reflectors direct the radiant heat downward to occupied areas.
SECTION 1: CONCEPT
Radiant refers to the heat radiated by the CRV-Series
system. Because this heat is in the form of infrared rays, it does not directly heat the air. Instead, the rays heat objects such as floors, people, walls, cars, machines, tools, etc. The warm objects, in turn, heat the air throu
gh convection.
Incremental Burner System means that several burners can operate in-series and fire into the same run of steel tube that carries the combustion gases from upstream burners. Each of these burners in a radiant branch may have different firing rates; also, the space between burners may vary. This allows the designer to match heat gain to heat loss for each area of the building. Firing burners in-series provides higher thermal and radiant efficiency.
In a properly designed low-intensity radiant system, the occupants should be barely aware of the radiant heat when the system is firing. They will feel little or no change when the thermostat is satisfied and the sys­tem is not firing. This combines with warm floors, warm walls and draft-free operation to improve the mean radiant temperature of the space. This is the key to the exceptional comfort and fuel efficiency provided by the CRV-Series system.
1
CRV-SERIES DESIGN MANUAL
SECTION 2: THE CRV-SERIES SYSTEM
A CRV-Series system consists of one pump, a control system, and a number of burners, see Page 3, Figure
1. It also includes an extended tube surface (4" (10 cm) steel tubing) covered by highly efficient reflectors to direct the radiant heat downward to the floor. The tubing nearest the burners radiates with the most intensity and is called radiant tube. This should be located over areas with the greatest heat loss. The rest of the tubing surface (located between the radiant tube and the pump) radiates with less intensity and is called tailpipe. This can be located in areas with lower heat loss.
While it is important to locate radiant tubes over areas with high heat loss, such as the perimeter of the build- ing, it is not essential to cover all areas directly with radiant heat. Center areas (away from external walls) and other areas of low heat loss can be adequately heated without direct coverage as long as the input of the system is adequate for the total building heat loss. However, to achieve the highest degree of comfort and fuel savings, it is recommended that the CRV-Series system be located to provide as complete and even a distribution as is practical. In addition, several different reflector and shield configurations are available to direct the radiant heat to or away from desired areas.
With CRV-Series, all equipment and controls are C.S.A. design certified, both as individual parts and also as a complete heating system. Also, individual electrical component parts are listed as applicable.
2.2 Zero Regulator
CRV-Series uses a 100% pre-mix burner with the input dependent on system vacuum. With no vacuum, the zero regulator prevents gas flow. When vacuum is present, the burner fires and input increases as vac- uum increases. As the input increases, the amount of air also increases. Over the normal range of operating vacuum, the gas/air ratio is essentially linear.
This unique and patented feature provides optimum combustion conditions at all times. Combustion condi- tions are unaffected by fluctuations in fuel pressure, vacuum, dirty air filters, changes in atmospheric pres­sure, wind velocity or other climate conditions.
Page 3, Figure 1 illustrates the components of a typi- cal CRV-Series system. The system shown is a four burner system composed of two branches. A branch consists of a single run of tubing, including an end burner, followed by any burners downstream. A branch ends at a tee or a cross (where other branches connect). For a single branch system, the branch ends at the pump.
2.1 Safety
Safety is a prime consideration of CRV-Series. First, there is a pre-purge of the complete tube network prior to flame ignition. Then, to ensure that there will be no gas flow unless the pump is operating, a pressure switch located at the pump must activate prior to igni- tion. After the pressure switch has closed, there are two valves in-series in each burner that must be ener- gized, as well as a zero regulator. Additionally, slow opening gas valves provide smooth ignition and enhance reliability. Once the thermostat has been sat­isfied, the burners turn off and the pump continues to run for two minutes to purge the entire system of flue gases.
2
FIGURE 1: Assembly Overview (Two Branch System Shown)
Pump
End
Vent
Combustion
Chamber
End Burner
Radiant
Tube
Coupling
Reflector
End Cap
Reflector
Support
Burner
Tube &
Reflector
Hanger
Reflector
Reflector
with Hole
End Vent
Exhaust to
Outside
Shared Tailpipe
End Burner
Tailpipe
Tailpipe
1. Radiant tubing between burners, and 20-50' (6-15 m)
downstream of the last burner is normally hot rolled steel or
heat-treated aluminized steel. All tailpipe tubing must be por-
celain coated steel or heat-treated aluminized steel.
2. Damper couplings are required when layout has unequal
branches. Unequal branches are achieved by unequal
geometry, burner quantity or burner firing rates.
3. Plain couplings are used to connect combustion chambers
to radiant tubing and radiant tubing to tailpipe tubing. All
tailpipe couplings must be lined.
SECTION 2: THE CRV-SERIES SYS TEM
3
CRV-SERIES DESIGN MANUAL
2.3 Fuel Savings and Comfort
Space heating can be accomplished with less input capacity when a radiant heating system is utilized, rather than with a conventional convective heating system. Why is this so?
A conventional, convective heating system, such as a
unit heater or central furnace works by heating the air, which then indirectly heats the area and
occupants. CRV-Series utilizes infrared energy to heat objects, people and surfaces directly, not the air. The warm objects and floor create a heat reservoir, which then re-radiates to the surroundings and also heats the air by convection.
The radiant energy received by the occupants, directly from the heater or indirectly from the surroundings via re-radiation, serves to increase the mean radiant temperature (MRT) of the space. In a manner similar to direct sunlight, the increased MRT allows the occupant to perceive a comfort condition at a reduced air temperature. The resulting reduced air temperature within the space provides the following fuel-saving advantages:
• Reduced stratification of air in the space.
• Reduced transmission heat loss due to lower tem­perature inside than assumed design condition.
• Redu
ced air change heat loss, to the extent that exfiltration through cracks or openings near the roof will be decreased because of decreased stack effect.
• Decreases the actual degree days experienced.
4
SECTION 3: CLEARANCES TO COMBUSTIBLES
WARNING
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
3.1 Required Clearances to Combustibles
Clearances are the required distances that combusti- ble objects must be away from the heater to prevent serious fire hazards. Combustibles are materials, which may catch on fire and include common items such as wood, paper, rubber, fabric, etc. Maintain
clearances to combustibles at all times for safety.
Clearances for all heater models are located on the burner assembly and on Page 6, Figure 3 through Page 8, Figure 10 in this manual. Check the clear- ances on each burner for the model heater being installed to make sure the product is suitable for your application and the clearances are maintained. Read and follow the safety guidelines below:
• Keep gasoline or other combustible materials including flammable objects, liquids, dust or vapors away from this heater or any other appli- ance.
SECTION 3: CLEARANCES TO C OMBUSTIBLES
• Hang heater in accordance to the minimum sus- pension requirements.
• If the radiant tubes must pass through the building structure, be sure that adequate sleeving and fire stop is installed to prevent scorching and/or fire hazard.
The stated clearances to combustibles represents a surface temperature of 90° F (32° C) above room temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, can­vas, tri-ply, etc) may be subject to degradation at lower temperatures. It is the installer’s responsibil­ity to assure that adjacent materials are protected from degradation.
• Maintain clearances from heat sensitive equipment and workstations.
• Maintain clearances from vehicles parked below the heater.
• Maintain clearances from swinging and overhead doors, overhead cranes, vehicle lifts, partitions, storage racks, hoists, building construction, etc.
• In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain required clearances from the heater to the com­bustibles. Signs must be posted adjacent to the heater thermostat. In the absence of a thermo­stat, signs must be posted in a conspicuous loca­tion.
• Consult local Fire Marshal, Fire Insurance Carrier or other authorities for approval of proposed installation when there is a possibility of exposure to combustible airborne materials or vapors.
5
CRV-SERIES DESIGN MANUAL
B
C
D
A
A
B
C
D
A
B
C
D
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the combustion chamber and the tube connect.
FIGURE 2: STANDARD REFLECTOR
Model A B C D A B C D
CRV-B-2 4 20 48 20 11 51 122 51
CRV-B-4 4 20 48 20 11 51 122 51
CRV-B-6 4 20 48 20 11 51 122 51
CRV-B-8 4 20 48 20 11 51 122 51
CRV-B-9 4 36 60 36 11 92 153 92
CRV-B-10 4 366036119215392
CRV-B-12 4 36 60 36 11 92 153 92
CRV-B-12A 4 36 60 36 11 92 153 92
.
(inches) (centimeters)
FIGURE 3: ONE SIDE REFLECTOR
(inches) (centimeters)
Model A B CDABCD
CRV-B-2 4 12 56 20 11 31 143 51
CRV-B-4 4 12 56 20 11 31 143 51
CRV-B-6 4 12 56 20 11 31 143 51
CRV-B-8 4 12 56 20 11 31 143 51
CRV-B-9 4 12 60 42 11 31 153 107
CRV-B-10 4 12 60 42 11 31 153 107
CRV-B-12 4 12 60 42 11 31 153 107
CRV-B-12A 4 12 60 42 11 31 153 107
FIGURE 4: TWO SIDE REFLECTORS
(inches) (centimeters)
Model A B CDABCD
CRV-B-2 4 12 56 12 11 31 143 31
CRV-B-4 4 12 56 12 11 31 143 31
CRV-B-6 4 12 56 12 11 31 143 31
CRV-B-8 4 12 56 12 11 31 143 31
CRV-B-9 4 12 60 12 11 31 153 31
CRV-B-10 4 12 60 12 11 31 153 31
CRV-B-12 4 12 60 12 11 31 153 31
CRV-B-12A 4 12 60 12 11 31 153 31
6
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
C
A
B
D
C
A
B
D
C
A
B
D
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the combustion chamber and the tube connect.
FIGURE 5: UNIVERSAL SHIELD, POSITION 1
Model A B CDABCD
CRV-B-2 4 12 12 12 11 31 31 31
CRV-B-4 4 12 12 12 11 31 31 31
CRV-B-6 4 12 12 12 11 31 31 31
CRV-B-8 4 12 12 12 11 31 31 31
CRV-B-9 8 18 24 18 21 46 61 46
CRV-B-10 8 18241821466146
CRV-B-12 8 18 24 18 21 46 61 46
CRV-B-12A 8 18 24 18 21 46 61 46
SECTION 3: CLEARANCES TO C OMBUSTIBLES
(inches) (centimeters)
FIGURE 6: UNIVERSAL SHIELD, POSITION 2
(inches) (centimeters)
Model A B CDABCD
CRV-B-2 4 24 48 24 11 61 122 61
CRV-B-4 4 24 48 24 11 61 122 61
CRV-B-6 4 24 48 24 11 61 122 61
CRV-B-8 4 24 48 24 11 61 122 61
CRV-B-9 4 36 48 36 11 92 122 92
CRV-B-10 4 36 48 36 11 92 122 92
CRV-B-12 4 36 48 36 11 92 122 92
CRV-B-12A 4 36 48 36 11 92 122 92
FIGURE 7: UNIVERSAL SHIELD, POSITION 3
(inches) (centimeters)
Model A B CDABCD
CRV-B-2 4 12 56 30 11 31 143 77
CRV-B-4 4 12 56 30 11 31 143 77
CRV-B-6 4 12 56 30 11 31 143 77
CRV-B-8 4 12 56 30 11 31 143 77
CRV-B-9 8 12 60 42 21 31 153 107
CRV-B-10 8 12 60 42 21 31 153 107
CRV-B-12 8 12 60 42 21 31 153 107
CRV-B-12A 8 12 60 42 21 31 153 107
7
CRV-SERIES DESIGN MANUAL
A
B
C
D
C
A
B
D
A
B
C
D
NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the combustion chamber and the tube connect.
FIGURE 8: 2-FOOT DECO GRILLE
(inches) (centimeters)
Model A B CDABCD
CRV-B-2 4 12 48 12 11 31 122 31
CRV-B-4 4 12 48 12 11 31 122 31
CRV-B-6 4 12 48 12 11 31 122 31
CRV-B-8 4 12 48 12 11 31 122 31
CRV-B-9 4 18 56 18 11 46 143 46
CRV-B-10 4 18 56 18 11 46 143 46
CRV-B-12 4 18 56 18 11 46 143 46
CRV-B-12A 4 18 56 18 11 46 143 46
FIGURE 9: BARRIER SHIELD
(inches) (centimeters)
Model A B CDABCD
CRV-B-2 4 12 12 12 11 31 31 31
CRV-B-4 4 12 12 12 11 31 31 31
CRV-B-6 4 12 12 12 11 31 31 31
CRV-B-8 4 12 12 12 11 31 31 31
CRV-B-9 - UNAPPROVED - - UNAPPROVED -
CRV-B-10 - UNAPPROVED - - UNAPPROVED -
CRV-B-12 - UNAPPROVED - - UNAPPROVED -
CRV-B-12A - UNAPPROVED - - UNAPPROVED -
FIGURE 10: PROTECTIVE GRILLE
(inches) (centimeters)
Model A B CDABCD
CRV-B-2 4 20 48 20 11 51 122 51
CRV-B-4 4 20 48 20 11 51 122 51
CRV-B-6 4 20 48 20 11 51 122 51
CRV-B-8 4 20 48 20 11 51 122 51
CRV-B-9 4 36 60 36 11 92 153 92
CRV-B-10 4 36 60 36 11 92 153 92
CRV-B-12 4 36 60 36 11 92 153 92
CRV-B-12A 4 36 60 36 11 92 153 92
8
SECTION 4: SIZING AND DESIGN CONSIDERATIONS
Given a building with a calculated heat loss of 350,000 (Btu/h), what is the installed capacity required of a CORAYVAC
®
system mounted at
30' (9 m)?
CORAYVAC
®
Installed Capacity = Heat Loss x
Radiant Adjustment x Height Adjustment
For CORAYVAC
®
systems, a .80 radiant adjust-
ment factor is used.
The height adjustment is 1% per foot over 20' (3% per meter over 6 meters), or 1.10.
CORAYVAC
®
Installed Capacity = 350,000
(Btu/h) x .80 x 1.10 = 308,000 (Btu/h)
A 12% reduction in installed capacity vs. a conventional heating system.
The building heat loss must be calculated in accor- dance to accepted energy load calculation methods. ASHRAE (American Society of Heating, Refrigeration and Air-Conditioning Engineers) offers in-depth infor­mation that is useful in calculating energy loads. The CRV-Series system input is determined in concert with the required radiant adjustment to heat loss and height adjustment factors.
4.1 Radiant Adjustment to Heat Loss
The practice of applying an adjustment factor to heat loss calculations for radiant heating systems is well known within the radiant heating industry, having been used by manufacturers for over 25 years. A number of studies have been conducted to identify the values of the adjustment factor in the range of 0.8 to 0.85 depending on efficiency (higher efficiency uses lower factor). This adjustment can be more thoroughly understood when considering the following radiant effect issues:
• Infrared energy heats objects, not the air.
• Lower ambient temperatures reduce the amount of air infiltration.
• Less air stratification with radiant heat.
heating system. The ability of a radiant system to pro­vide the advantages of these radiant effects rests largely with the ability of this system to establish a reserve heat capacity in the floor. Without this reserve capacity, radiant comfort cannot be achieved. (The exception is station heating/spot heating applications where sufficiently high levels of direct radiation are received from the heater.) The height adjustment fac­tor is a means to insure adequate floor level radiant intensity to “charge” the floor heat reservoir.
Proportionately larger wall surfaces also remove energy from the floor to a larger degree, decreasing the heat reservoir.
The increased input capacity recommended by a height adjustment factor is not extraneous as com­pared to the heat loss calculation. Rather, it is a real­ization that in order to maintain radiant comfort conditions (and the economic benefits), a minimum radiant level must be maintained at the floor.
It is recommended that an adjustment to the heat loss of 1% per foot (3% per meter) for mounting heights above 20' (6 m), be added up to 60' (18 m). Above this height, additional correction overstates the BTU requirement as determined by the heat loss.
• Lower ambient air temperatures reduce the trans-
EXAMPLE 1:
mission heat loss through walls and roof.
SECTION 4: SIZING AND DESIGN C ONSIDERATIONS
• Elevated floor temperature provides a thermal reserve capacity.
• Increased mean radiant temperature allows occu- pants to perceive thermal comfort at the reduced air temperature.
Each of these issues impacts favorably on the reduc- tion of the installed capacity of the radiant heating sys­tem. This fact, together with the realization that the standard ASHRAE heat loss calculation methods (particularly the transmission heat loss coefficients) have been developed specifically for conventional hot air systems, demonstrates the need for the heat loss adjustment factor.
• In general, a .80 adjustment factor should be used for CRV-Series systems.
4.2 Radiant Height Adjustment Factor
As discussed above, the installed input capacity of radiant heating systems is typically reduced as com­pared to the calculated heat loss due to the radiant effects associated with a properly designed radiant
9
CRV-SERIES DESIGN MANUAL
Given a building with a calculated heat loss of 500,000 Btu/h, what is the installed capac­ity required of a CRV-Series system mounted at 50' (15 m)?
CORAYVAC
®
Installed Capacity = Heat Loss x
Radiant Adjustment x Height Adjustment.
For CORAYVAC
®
systems, a .80 radiant adjust-
ment factor is used.
The height adjustment is 1% per foot over 20' (3% per meter over 6 meters), or 1.30.
CORAYVAC
®
Installed Capacity = 500,000
(Btu/h) x .80 x 1.30 = 520,000 (Btu/h).
EXAMPLE 2:
Note in Example 2, if equipment had been convention­ally sized based on thermal output only, a nearly iden­tical input requirement would result. For mounting heights above 60' (18 m), no further correction is gen­erally necessary if the floor level radiant intensity is sufficient to establish a reserve capacity (hence, radi­ant comfort), and the heat loss requirement is satisfied based on thermal output.
Due to the complexity of installations with mounting heights over 60' (18 m), it is advisable to contact Rob­erts-Gordon for further information regarding the spe­cific application.
4.3 Selecting the Burners
The number of burners and input for each must be specified in the design layout. The following factors should be considered when selecting burner input:
• Heat gain and distribution required.
• Mounting height.
• Flow loading restrictions.
• Length of radiant branches.
• Distance required between burners.
• Desired radiation intensity.
In general, lower burner inpu
ts can be used for lower mounting heights and where lower heat gains are required. Higher burner inputs are used primarily with higher mounting heights and where high heat gain is required.
The number of burners required can be calculated by dividing the input rating of the selected sizes into the
10
calculated CRV-Series system required installed capacity.
4.4 Radiant Distribution
Radiant heat distribution at occupant level must be considered in the burner and design selection process.
Distribution of heat between radiant branches at floor level is more critical at the perimeter of buildings. This is where the heat loss is highest. Therefore, it may be possible to combine different applications of distribu- tion within the same building. The following figures show three different applications of rules to determine distribution.
4.4.1 Radiant Distribution (Average Coverage)
The aim of this distribution is to provide average or lighter than average radiant intensity and works well for general b
uilding heating. See Page 11, Figure 11. The distance between radiant branches can vary between 2.5 to 4 (or more) times the mounting height.
This distribution is commonly used in applications such as warehouses and lower heat loss areas of a building.
Lighter coverage can be used in areas where occu- pant traffic is low.
4.4.2 Radiant Distribution (Increased Coverage)
The aim of this distribution is to provide continuous radiant intensity. See Page 11, Figure 12. The distance between radiant branches is about 2 times the mounting height.
This distribution is commonly used in areas bordering high heat loss areas or areas requiring increased radi- ant intensity to achieve occupant comfort.
4.4.3 Radiant Distribution (Heavy Coverage)
The aim of this distribution is to provide increased radi­ant intensity in areas that range from sedentary work to spot heating for loading docks. See Page 11, Figure
13. The y dimensions in the diagram is the height above floor level where overlap of the radiant output will occur.
In practice, y = 6' (1.83 m) is commonly used in areas where occupant comfort doing sedentary work is an important factor. In loading bays, spot heating and areas of high heat loss, the horizontal distance (x) between branches can be as little as 0.5 times the mounting height.
FIGURE 11: Radiant Distribution (Average Coverage)
H
90°
3 H
H= mounting height
2 H
H
90°
H= mounting height
H
90°
y
x=2H-2y
x
y= height above the
floor level where overlap of radiant output will occur
H= mounting height
FIGURE 12: Radiant Distribution (Increased Coverage)
SECTION 4: SIZING AND DESIGN C ONSIDERATIONS
FIGURE 13: Radiant Distribution (Heavy Coverage)
11
CRV-SERIES DESIGN MANUAL
SECTION 5: FLOW LOADING
The patented CRV-Series burner system allows a number of burners to be installed in-series, in the same radiant tube, resulting in a long, continuous radi­ant emitting surface to give even heat distribution within the building.
To enable the burners to be correctly located within the system, to maintain system operating vacuum and obtain design flue gas temperatures at the pump, the design layout is based on a simplified flow principle using a “flow unit.”
The flow unit is defined as the amount of fuel/air mix­ture for a heat input of 10,000 (Btu/h). This corre­sponds to a flow rate of 1.83 cfm at 65-70°F.
For the purpose of design, flow units enter the CRV­Series system in one of two ways:
• Through the burner.
• Through the end vent plate.
Flow units exit the system as spent produ
cts of com-
bustion via the pump.
The purpose of the end vent air is to dilute the hot combustion gases at the burner, thereby promoting uniform heating of the tube while avoiding excessive heating of the combustion chamber.
For the end burner, the burner inlet flow consists of the end vent air and combustion air. For all other
burners, the burner inlet flow consists the of the total of the end vent air plus the combustion gases from all upstream burners.
The requirement for minimum burner inlet flow is met if the total flow units entering the combustion chamber meets or exceeds the minimum as shown on Page 12, Table 1.
5.1 Radiant Branch Flow
The flow in a radiant branch consists of the end vent flow units plus the flow units of combustion air from all burners. Page 13, Figure 14 shows a representation of flow
units for various types of branches.
The limiting factor for maximum flow in the radiant sec­tion has been determined experimentally in terms of the maximum burner inlet flow units that can be toler­ated without degradation of combustion characteris- tics at the last downstream burner. If more than the maximum number of burners are installed per radiant branch, the vacuum loss across the additional burners will increase appreciably.
This maximum flow in the radiant branch can be expressed for each burner firing rate by either a maxi­mum number of burners per branch or the maximum number of flow units. See Page 12, Table 1.
Table 1: CORAYVAC® Design Parameters
Burner Model B-2 B-4 B-6 B-8 B-9* B-10 B-12A B-12
Input (Btu/h) x (1000) 20 40 60 80 90 100 110 120
Flow Units per Burner 2 4 6 8 9 10 12 12
Flow Units per End Vent (minimum flow units entering combustion chamber)
Maximum Number of Burners per Branch 6 4 4 4 2 4 3 3
Maximum Number of Flow Units per Branch 18 26 39 52 33 60 56 56
Radiant Tube Length (average distance between burners)
Minimum (ft) 10 12.5 20 20 20 30 35 35
Recommended (ft) 15 20 25 30 30 40 50 50
Maximum (ft) 20 25 35 45 50 60 70 70
Minimum Distance from Burner to Downstream Elbow (ft) 5 5 10 10 10 15 15 15
Suggested Minimum mounting Height (ft) 8 8 8 10 10 15 15 15
6 10152015202020
* CRV B-9 requires first downstream tube from burner to be aluminized heat-treated.
12
FIGURE 14: Burner Flow Units
B-10 Burner #1
End Burner
End Vent Air
+ 20 Flow Units
Combustion Gas
+ 10 Flow Units
Coupling
B-10 Burner #2
Downstream Burner
Combustion Gas
+ 10 Flow Units
B-10 Burner #3
Downstream Burner
Combustion Gas
+ 10 Flow Units
Burner 1
Burner 2
Burner 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2
1 2 3
1 2 3
1 2 3
End Vent
Flow Units
Burner Firing Rate
Btu/h
Burner #
Burner #1
Flow Units
Burner #2
Flow Units
Burner #3
Flow Units
Total Flow
Units
6
20,000 20,000 20,000
40,000 40,000 40,000
60,000 60,000 60,000
80,000 80,000 80,000
90,000 90,000
100,000 100,000 100,000
120,000 (or 110,000) 120,000 (or 110,000) 120,000 (or 110,000)
120,000 100,000
80,000
10
15
20
15
20
20
20
2
2
2
12
4
4
4
22
6
6
6
33
8
8
8
44
9
9
33
10
10
10
50
12
12
12
56
12
10
8
50
Total Flow
Units
20 + 10 + 10 + 10
= 50 Flow Units
SECTION 5: FLOW LO ADING
13
CRV-SERIES DESIGN MANUAL
NOT OK
OK
SIDE
10
20
30
40
50
60
70
80
90
100
120
130
Length of Tailpipe Section (feet)*
Maximum Flow Units per Single Tailpipe Section
30
40
50 60 70
80
90 100
110
120
5.2 Pump Capacity
The flow unit capacity of the pump is indicated on Page 14, Table 2, as a function of installed altitude.
When the CRV-Series system is designed in accor­dance with this set of instructions and is in proper operating condition, a vacuum from 2-3" w.c. will be obtainable at each end vent (i.e. at all burners).
Table 2: Pump Capacity
Installed Altitude Maximum Flow Units
Feet Above
Sea Level
' - 2000'
0
2001' - 3000' 3001' - 4000'
4001
' - 5000'
5001' - 6000' 6001' - 7000'
7001
' - 8000'
8001' - 9000'
Meters Above
Sea Level
0 m - 609 m 66 112 224
610 m - 914 m 63 105 215
915 m - 1219 m 60 100 206
1220 m - 1524 m 57 95 197
1525 m - 1828 m 54 90 188
1829 m - 2134 m 51 84 180
2135 m - 2438 m 48 80 170
2439 m - 2743 m 45 75 161
EP-100
EP-200
Series
EP-300
Series
number of flow units carried in the tube.
See Figure 15. Readings for length and flow when plotted on the graph must fall on OK side to avoid excessive vacuum losses.
FIGURE 15: Vacuum Loss Curve for 4" Shared Tailpipe
There are a number of design requirements which, if not met, will reduce the vacuum obtainable and thereby the effective flow capacity of the pump. These include:
Minimum Length of Tailpipe - If less than the minimum length of tailpipe is provided per radiant branch, there will be insufficient cooling of the com- bustion gases and improper operation of the pump.
Line Loss Check for Tailpipe is applicable to sections of tailpipe which are common to two or more radiant branches (i.e. shared lengths). See Page 14, Figure 15.
Excessive back pressure on discharge line of pump can be caused by partial blockage or too much flow for length. See Section 5.3.1
More than maximum number of burners or flow units per radiant branch. See Page 14, Table 2.
Excessive number of elbow or tee fittings which increases vacuum loss.
5.3 Tailpipe Flow
Excessive flow loading in a single section of tailpipe can cause low vacuum and lower effective pump capacity. For the pump to develop the proper vacuum, the length of tailpipe m
14
ust not be excessive for the
NOTE: For 6" (15 m) tailpipe, length is limited to a maximum of 100’ (30 m). See Page 16, Section 6.3 for more details.
Lengths shown include allowance for 1 elbow every 50' (15 m); deduct 15% of length for each additional elbow used per 50' (15 m) length.
5.3.1 Pump Exhaust Length Requirements
The tube length on the exhaust side of the pump is considered excessive if not within the following condi- tions:
Table 3: Pump Exhaust Requirements
Pump Series Exhaust Tube Length Exhaust Tube Diameter
EP-100 Up to 25' (7.6 m) 4" 3 Elbows
EP-100 Up to 50' (15 m) 5" 3 Elbows
EP-200 Up to 10' (3 m) 4" 0 Elbows
EP-200 Up to 25' (7.6 m) 5" 3 Elbows
EP-200 Up to 50' (15 m) 6" 3 Elbows
EP-300 Up to 10' (3 m) 6" 1 Elbows
EP-300 Up to 25' (7.6 m) 7" 3 Elbows
EP-300 Up to 50' (15 m) 8" 3 Elbows
SECTION 6: RADIANT TUBE AND TAILPIPE
The main purpose of the tailpipe and the radiant tube is to provide sufficient tube surface to transfer the heat from the flue gases to the tube wall where it radiates from the tube. Radiant tube is defined as the tubing between burners firing in a radiant branch, plus the radiant tubing immediately following the last down- stream burner. Tailpipe is defined as all tubing between the radiant tube and the pump.
Most of the radiant heat supplied by each burner is released from the radiant tube; the balance is released by the tailpipe. The placement of radiant tube to corre­spond to areas of major heat loss is the key to provid­ing uniform comfort levels. The use of adequate tailpipe is the key to high combustion efficiency and proper operation of the pump.
6.1 Radiant Tube Length
The considerations in the selection of the length of radiant tube include the following:
SECTION 6: RADIANT TUBE AND TAILPIPE
Page 16, Figure 16 relates the effect on system ther­mal efficiency of variations in radiant and tailpipe lengths. The chart was created based on test data obtained in accordance with methodology developed by the National Bureau
of Standards (NBSIR 80-2110) and recommendations on flue loss calculation con­tained in ANSI Z83.20/CSA 2.34 (latest edition). Actual installation variables (gas BTU content, air tem­perature and operation cycle, etc.) may effect efficien­cies (positively or negatively). Page 16, Figure 16 is presented as a guide to the designer for information only.
NOTE: When accounting for the required tailpipe lengths during the design process, it is important to verify that the tailpipe for each branch is at least equal to the specified minimum.
6.1.1 Minimum Radiant Tube Length
Provides for the highest level of intensity per length of radiant tube and good radiant heat uniformity between b
urners. More tailpipe length is required to maintain
operating efficiency and pump capacity.
6.1.2 Maximum Radiant Tube Length
Provides the lowest level of intensity per length of radi- ant tube, and consequently the largest span between burners. The radiant intensity will be reduced slightly for the last 5'-10' (2-3 m) of radiant tube before the next burner.
The length of radiant tube required varies according to the burner input. Consideration has been given to the use of a standard 10' (3 m) length of tube or lengths that can be cut from same without waste. See Page 12, Table 1.
When positioning radiant tube to give the required radiant distribution, it is important to consider:
• Clearances to combustible materials.
• Lighting equipment and other suspended objects.
6.2 Tailpipe
Tailpipe provides a low level of radiant intensity per length. The length of tailpipe for systems can be varied according to the flow units in the system and the designed radiant length. Longer lengths of tailpipe will attain higher operating efficiencies and therefore con­densation will occur.
15
CRV-SERIES DESIGN MANUAL
Length of Tailpipe per Flow Unit (feet)
3.0
2.5
2.0
1.5
1.0
83% 84% 85% 86% 87% 88% 89% 90%
Steady State Thermal Efficiency (%)
M
a
x
i
m
u
m
R
a
d
i
a
n
t
P
i
p
e
M
i
n
i
m
u
m
R
a
d
i
a
n
t
P
i
p
e
N
o
m
i
n
a
l
R
a
d
i
a
n
t
P
i
p
e
NOTE: Thermal efficiency values shown do not include the contribution due to condensing conditions when operating in cyclic fashion. To estimate cyclic efficiencies, add 2-3% to the values obtained from the graph.
Flow Units Per Branch
Branch 1 + Branch 2 + Branch 3 + Branch 4 + Branch 5 + Branch 6 +
To t a l S ys te m Flow Units =
FIGURE 16: Tube Length vs. Efficiency
6.3 Design Parameters
When designing branches of 4 B-8 or larger burners in-series, the following limitation to the pump capacity applies:
Pump Model Series
Maximum Loading
EP-100:Not Allowed EP-200:1 Branch of 4 burners EP-300:2 Branches of 4 burners
For systems that are designed above 90% pump capacity, the following limitations of shared tailpipe apply:
• 4" (10 cm) tailpipe: limited to maximum of 2 com­bined branches and length limited to maximum of 20' (6 m). See Page 14, Figure 15 for all other tailpipe considerations.
• 6" (15 cm) tailpipe limited to maximum of 4 com­bined branches and length limited to maximum of 100' (30 m).
• When calculating required tailpipe length 1' (.3 m) of 6" manifold tube is equivalent to 1.3' (.4 m) of 4" tailpipe.
in insufficient vacuum to burners.
6.4 CRV-Series Design Methods
1. L ay o ut the system to suit the BTU input required.
2. Calculate the system design for each branch individually.
3. Calculate the number of flow units per branch of burners. Add the flow units for each branch together to get the total system flow units. See Page 12, Table 1 for the r model. See Page 13, Figure 14 for example flow
unit calculations.
ules for each burner
Failure to comply with the above parameters will result
16
4. Select pump model series for total system flow
Burner
Radiant Tube Length
After Each Burner
1+ 2+ 3+ 4+ 5+ 6+
Total Radiant Tube Length in Branch =
Average Radiant Length Per Burner =
units: EP-100: up to 66 flow units EP-200: up to 110 flow units EP-300: up to 224 flow units
5. See Page 14, Table 2 for altitudes greater than 2000'.
6. For each branch, add the length of radiant tube after each heater:
SECTION 6: RADIANT TUBE AND TAILPIPE
Repeat this calculation for each branch in the system.
7. Divide the total radiant tube length in the branch by the number of burners in the branch to get the average radiant length per burner.
Repeat this calculation for each branch in the system.
8. Using the average radiant length per burner (Calculated in Step 7) See Page 17, Table 4 to select the allowable tailpipe lengths per flow unit.
Table 4: Allowable Tailpipe Lengths
Radiant Tube Length (average distance between burners)
Minimum (ft) 10 12.5 20 20 20 30 35
Recommended (ft) 15 20 25 30 30 40 50
Maximum (ft) 20 25 35 45 50 60 70
Tailpipe length per flow unit
Minimum (ft)* 1.2 1.2 1.2 1.2 1.2 1.2 1.2
Recommended (ft) 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Maximum (ft) 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Maximum (ft) for EP-100 only 1.7 1.7 1.7 1.7 1.7 1.7 1.7
*Minimum tailpipe lengths can only be used if radiant tube length is recommended or greater.
B-2 B-4 B-6 B-8 B-9 B-10 B-12/B-12A
Burner Model
17
CRV-SERIES DESIGN MANUAL
For a B-10 burner system of 200 flow units and an average of 40' radiant tube length per burner, See Page 17, Table 4 for the tailpipe lengths per flow unit that can be used and the corresponding operating characteristic.
From Table 4, we can use between 1.2' per flow unit and 2.5' per flow unit when the average radiant length per B-10 burner is 40'. By multiplying the number of flow units in the system (200 flow units) by the mini- mum tailpipe length from the chart (1.2' per flow unit), we see that we will need a minimum of 240' of tailpipe for this system. Likewise, by multiplying the number of flow units in the system (200 flow units) by the maxi- mum tailpipe length from the chart (2.5' per flow unit), we see that maximum system, tailpipe length is 500'.
Tailpipe length range for a B-10 burner system with 200 flow units and an average radiant tube length of 40’ is 240'-500'. The length of the tailpipe will determine whether the system is condensing or non-condensing. Given a certain radiant tube length and tailpipe length, the operating characteristic can be determined
u
sing Table 5.
Total tailpipe ' (includes 1 elbow / 50').
Total tailpipe - 10' = Optimum unshared
tailpipe per branchNumber of branches
Total system tailpipe
= Tailpipe ft/flow unit
To t a l f l ow units
EXAMPLE 3: B-10 Radiant Tube vs. Tailpipe Length
Table 5: Operating Characteristics; Condensing or Non-Condensing
Radiant Tube Length (average distance between burners)
Minimum N/A NC Borderline C
Recommended NC Borderline C C
Maximum Borderline C C C
N/A=Not Allowed NC=Non Condensing C=Condensing
Minimum Recommended 1.7 ft/flow unit Maximum
Tailpipe Length per Flow Unit
6.5 Tailpipe Design Method
Given the overall length of tailpipe for the system, the following section provides the method for ensuring the design will function correctly.
the section of tailpipe.
If flow units entering a shared tailpipe system exceed 90% of pump capacity, the length of 4" diameter tailpipe must not exceed 20'.
System with EP-300 Series Pump
6.5.1 Rule of Thumb Unshared Calculations
For shared tailpipe up to 115 flow units, 4" diameter tailpipe can be used. See Page 14, Figure 15 for max- imum permissible length of tailpipe for the number of
flow units entering the section of tailpipe. Select a pump discharge location and plan the route of the tailpipe. For example system layouts See Page 21, Figure 18 through Page 25, Figure 26 for different pump and system efficiency requirements. If these lay­outs are not suitable, it is necessary to customize the layout for the CRV-Series system to the individual building requirements.
For multiple branch systems, always plan to connect the unshared tailpipe together as close to the pump as possible for better system efficiency.
6.5.2 Shared Tailpipe Calculation
System with EP-100 or EP-200 Series Pump
Shared tailpipe greater than 115 flow units use 6"
diameter tube. Note that all tailpipe lengths for the pur-
poses of calculation are expressed in terms of 4"
diameter tube.
Effective length: 10' (3 m) of 6" (15 cm) diameter
tube = 13' (4 m) of 4" diameter tube.
6.5.3 To Calculate the Total System Tailpipe
To ta l unshared tailpipe + shared 4" branch tailpipe +
effective length of shared 6".
6.5.4 To Check Performance Criteria
See Page 14, Figure 15 for maximum permissible length of tailpipe for the number of flow units entering
Compare the results to Page 17, Table 4 and Page 18,
18
Table 5 for the burner model to ensure that the result- ing tailpipe lengths maintain intended operating char­acteristic.
6.5.5 Damper Couplings
Damper couplings are needed:
• In any tailpipe branch that carries less flow units than other tailpipe branches connected to the same pump
• In unsymmetrical layouts with branches having the same number of flow units, the damper cou- pling is placed in every branch except for the longest branch.
The purpose of the damper coupling is to adjust the end vent vacuum down to the desired level. These are to be placed in the tailpipe section and not the radiant branch. The recommended location is before the first tee fitting or 10'-40' from the end of the radiant pipe.
See Page 20, Figure 17; Page 23, Figure 21, Page 24, Figure 25, and Page 25, Figure 26 for placement
examples.
SECTION 6: RADIANT TUBE AND TAILPIPE
19
CRV-SERIES DESIGN MANUAL
Damper Coupling
Damper
NOTE: Damper setting
will vary
Zone 1
Zone 2
Zone 3
Zone 1
End Vent
Zone 3
End Vent
Zone 2
End Vent
Zone 1
Damper
Coupling
Zone 2
Damper
Coupling
Zone 3
Damper
Coupling
Pump
Damper
FIGURE 17: Possible Damper Coupling Locations
20
SECTION 7: EXAMPLE CRV-SERIES SYSTEM LAYOUTS
CORAYVAC
®
Burner
LEGEND
Pump
Damper
Radiant Tube
Tailpipe
6" Tailpipe
30'
(9 m)
30'
(9 m)
30'
(9 m)
20'
(6 m)
20'
(6 m)
20'
(6 m)
10' (3 m)
Systems that are symmetrical are preferred because
FIGURE 18: Example System Layout (Option 1)
the vacuum available in the system branches are bal­anced as a function of design (damper couplings are not needed).
Where radiant tube lengths are variable in a single branch, the average length shall be used to determine the total radiant tube length. Tailpipe will begin after the last radiant tube following the last burner in the branch.
CRV-Series is most effective when there are at least 3 burners in the radiant branch.
To assist with the selection of burners and system designs, the following figures show system layouts that have been used extensively with CRV-Series since
1962. Designing systems using these layouts will mean altering the dimensions to suit the individual building.
SECTION 7: EXAMPLE CRV-SERIES SYSTEM L AYOUTS
Generally, shared tailpipe reduces the available sys­tem vacuum. See Page 14, Section 5.3 for shared tailpipe design rules.
7.1 Example System Layout (Option 1)
Six B10 burners at minimum radiant tube length and
2.5 ft/flow unit tailpipe, the recommended pump for this system is an EP-200 Series p
ump.
This system provides maximum radiant intensity on the left and right and adds supplemental radiant effects through the center creating very even radiant effects over the coverage area.
Layout to provide high system efficiency, condensed radiant output and good uniformity of distribution. Adjust the lengths as necessary for different input sys­tems and to change the efficiency levels.
21
CRV-SERIES DESIGN MANUAL
40'
(12 m)
40'
(12 m)
40'
(12 m)
40'
(12 m)
40'
(12 m)
20' (6 m)
10' (3 m)
30'
(9 m)
30'
(9 m)
40'
(12 m)
40'
(12 m)
30'
(9 m)
50'
(15 m)
6" Tailpipe
FIGURE 19: Example System Layout (Option 2)
7.2 Example System Layout (Option 2)
FIGURE 20: Example System Layout (Option 3)
Six B10 burners at recommended radiant tube length and 1.2'/flow unit tailpipe, the recommended pump for this system is an EP-200 Series pump.
Layout will minimize up front equipment cost of tubing by implementing minimum tailpipe length.
Layout will exhibit minimum system efficiency. Adjust the lengths as necessary for different input systems and to increase the efficiency levels.
7.3 Example System Layout (Option 3)
Twelve B10 burners at minimum radiant tube length and 1.56'/flow unit tailpipe, the pump for this system is an EP-300 Series Pump.
All shared tailpipe is 6" diameter.
Layout will provide maximum radiant intensity between burners.
Layout will exhibit minimum system efficiency. Adjust the lengths as necessary for different input systems and to increase the efficiency levels.
22
SECTION 7: EXAMPLE CRV-SERIES SYSTEM L AYOUTS
30'
(9 m)
40'
(12 m)
30'
(9 m)
40'
(12 m)
40'
(12 m)
40'
(12 m)
30'
(9 m)
6" Tailpipe
70'
(21 m)
10'
(3 m)
30'
(9 m)
30'
(9 m)
30'
(9 m)
FIGURE 21: Example System Layout (Option 4)
FIGURE 22: Example System Layout (Option 5)
7.4 Example System Layout (Option 4)
Nine B10 burners at recommended radiant tube length and 1.58'/flow unit tailpipe, the pump for this system is an EP-300 Series Pump.
All shared tailpipe is 6" diameter.
Layout will exhibit nominal system efficiency. Adjust the lengths as necessary for different input systems and to increase the efficiency levels.
7.5 Example System Layout (Option 5)
Six B10 burners at minimum radiant tube length and
1. 5 ' / f l o w unit tailpipe, the pump for this system is an EP-200 Series pump.
23
CRV-SERIES DESIGN MANUAL
100'
(30 m)
10' (3 m)
30'
(9 m)
30'
(9 m)
30'
(9 m)
10' (3 m)
30'
(9 m)
30'
(9 m)
30'
(9 m)
30'
(9 m)
30'
(9 m)
30'
(9 m)
negligible
180'
(55 m)
10' (3 m)
30'
(9 m)
30'
(9 m)
30'
(9 m)
10' (3 m)
Layout to provide minimum system efficiency. Adjust the lengths as necessary for different input systems and to increase the efficiency levels.
This system is generally accompanied by an addi­tional system, as shown, so that the radiant output of the additional system supplements the lack of radiant intensity from the tailpipe of the first system. This lay­out method is used in high heatloss and perimeter heating applications.
FIGURE 23: Example System Layout (Option 6)
This layout method is often used effectively in heatloss and perimeter heating applications.
FIGURE 24: Example System Layout (Option 7)
7.6 Example System Layout (Option 6)
Six B10 burners at minimum radiant tube length and
2.3'/flow unit tailpipe, the pump for this system is an EP-200 Series pump.
FIGURE 25: Example System Layout (Option 8)
Layout to provide high system efficiency, condensed radiant output and good uniformity of distribution. Adjust the lengths as necessary for different input sys­tems and to change the efficiency levels.
24
SECTION 7: EXAMPLE CRV-SERIES SYSTEM L AYOUTS
30'
(9 m)
30'
(9 m)
10'
(3 m)
30'
(9 m)
10'
(3 m)
30'
(9 m)
30'
(9 m)
6"
Tailpipe
FIGURE 26: Example System Layout (Option 9)
Layout to provide condensed radiant output and good uniformity of distribution. Layout will exhibit minimum
system efficiency.
7.7 Example System Layout (Option 7, 8 and 9)
These systems are for B9 burners only, this burner is specially rated for 2 burners in-series applications in the systems shown.
Option 7 is a 180' (55 m) straight system connected to an EP-100 pump.
Option 8 is a system connected to an EP-200 Series pump.
Option 9 is a system connected to an EP-300 Series pump.
These layouts show minimum allowed lengths. Addi- tional tubing may be added. The distance between the burners can be varied from 30' (9 m) to 20’ (6 m), but the overall system lengths must remain the same.
Layout will minimize upfront equipment cost of tubing by implementing special shortened minimum tailpipe lengths.
25
CRV-SERIES DESIGN MANUAL
DANGER
Electrical Shock Hazard
Disconnect electric before service or maintenance.
More than one disconnect switch may be required to disconnect electric to the unit.
Control must be properly grounded to an electrical source.
Failure to follow these instructions can result in death or electrical shock.
WARNING
Explosion Hazard
Turn off gas supply to heater before service.
Failure to follow these instructions can result in death, injury or property damage.
SECTION 8: CONTROL METHODS
Electronic 24 Vac thermostats and mechanical ther­mostats with heat anticipator can be used. The sys­tem control offers a 24 Vac power supply to power electronic thermostats. Roberts-Gordon offers a selection of low voltage thermostats approved for use with the system control.
A System Control operated system has two minutes post purge pump operation to completely exhaust products of combustion from the system. A system control provides indication of power to the pump and zones and indicates the status of the pressure switch with lights.
The System Control is ETL listed in accordance with UL873 – Standard for Temperature Indicating and Regulating Equipment.
8.2 ROBERTS GORDON
®
ULTRAVAC
The ROBERTS GORDON® ULTRAVAC™ is a micro processor based control package designed for modu- lating control of CRV-Series heaters based on outdoor temperatures. The controls offer full modulation between 60% and 100% of system maximum rated input.
There are several methods of controlling CRV-Series systems. The options are as follows:
8.1 ROBERTS GORDON
®
System Control (P/N
02770002)
®
The ROBERTS GORDON
System Control is an electronic controller designed for the control of CORAYVAC systems.
®
and VANTAGE® NP (multiburner only)
The System Control is capable of giving four zones of burners' temperature control and power. The control will also give power output to as many as two pumps, provided that the load is not greater than 20 A and 1 Ø. For additional electrical specifications see the System Control Installation, Operation and Service manual (P/N 10091601NA).
This controller is capable of giving control outputs to one pump and three heating zones. The controller also features inputs which are used for indoor and out- door signal condition monitoring.
System status and settings are viewed and altered from a PC (not supplied) running ROBERTS GOR-
®
DON
ULTRAVAC™ Software.
®
ROBERTS GORDON a PC (not supplied) running Windows with a Pentium
®
class processor and at least 64k of
ULTRAVAC™ Software requires
®
95 or higher,
RAM.
Special design requirements apply for CRV-Series
®
systems using the ROBERTS GORDON
VAC
Controller, See Page 31, Section 10.
ULTRA-
26
SECTION 8: CONTROL METHODS
Buildings today demand all sorts of control options based on the user’s preference. ULTRAVAC™ controls offer a host of communication options for integration with controls’ networks to best serve individual needs:
BACnet
®
: Interface ULTRAVAC™ with other building management control platforms with our BACnet option. TCP/IP (LAN): Connect to ULTRAVAC™ via your local area network of computers. Load ULTRAVAC™ software onto any computer on the network and control and view your heating system from your computer. MODEM: Dial into ULTRAVAC™ from anywhere in the world via modem. Supplied as standard on all central controllers! RS-485: Hard wire ULTRAVAC™ directly to your computer.
There are references in this manual to various trademarks. All trademarks mentioned herein, whether registered or not, are the property of their respective owners. Roberts-Gordon is not sponsored by or affiliated with any of the trademark or registered trademark owners, and make no representations about them, their owners, their products or services. Roberts-Gordon LLC is not sponsored by or affiliated with BACnet®.
indication of operating conditions. The transformer relay wiring diagram is shown in the CORAYVAC
®
Installation, Operation and Service Manual (P/N 127102NA).
8.5 Pressure Switch
A pressure switch is required to confirm pump opera­tion on all systems.
A pressure switch is also required on the inlet duct of a non-pressurized air supply.
8.3 SPST Transformer Relay (P/N 90417600K)
The transformer relay can be used to control an EP­100 or EP-201 pump CORAYVAC
®
system. The single pole relay can only be used to control one zone of burners. The electrical circuit is a 120 V AC (20 A) supply. The transformer 24 V AC output for the ther­mostat is rated at 40 V A. Thermostats used with the transformer must not exceed this power requirement. A transformer relay operated system will not give any post purge pump operation to completely exhaust products of combustion from the system or provide indication of operating conditions. The transformer relay wiring diagram is shown in the CORAYVAC
®
Installation, Operation and Service Manual (P/N 127102NA).
8.4 DPST Transformer Relay (P/N 90436300)
The transformer relay can be used to control an EP­100 or EP-201 pump CORAYVAC
®
system. The double pole relay can only be used to control two zones of burners. The electrical circuit is a 120 V AC (20A) sup- ply. The transformer 24 V AC output for the thermostat is rated at 40 VA. Thermostats used with the trans- former must not exceed this power requirement. A transformer relay operated system will not give any post purge pump operation to completely exhaust products of combustion from the system or provide
27
CRV-SERIES DESIGN MANUAL
140
120
100
80
60
40
20
0
0 50 100 150 200 250
Flow Units
Straight Duct Length (feet)
4"
5"
6"
7"
NOTE: For capacity requirements larger than shown, use 8" duct.
Duct Diameter
SECTION 9: AIR SUPPLY SYSTEM
An air supply free of dust and corrosive contaminants is essential for proper operation and best life expect­ancy with any heating system. With CRV-Series, there are two alternatives available to the designer for pro­viding the air supply. These are:
• Room air, a filter is standard for each burner.
• Outside air system to duct air from an uncontami- nated source. The outside air system can be designed as a pressurized or non-pressurized system.
The first alternative above is usable when the dust load is not excessive and there is no usage of corro­sive contaminants such as solvents or vapors inside the building.
The outside air system must be used in all applica- tions where corrosive contaminants may be present in the air even in trace amounts (few parts per million).
It is important for designers and owners of heating systems to note that the presence of contaminants in the combustion air supply will greatly accelerate the rate of corrosion on tube surfaces and will shorten the useful life of the heating system. This is true regard- less of whether the heating system is CRV-Series, other infrared systems or conventional gas or oil-fired equipment such as u
nit heaters, central boiler plant,
etc.
With the unique vacuum powered burners, the fuel/air mix remains constant, even if combustion air filters are dirty. It can be expected that the use of an outside air system will reduce but not eliminate the potential for corrosion due to contamination.
®
ULTRAVAC™ or relay transformer, a separate
DON load relay package is required. Wire the control for the relay in parallel with the pump. The outside air blower must have a separate 20 A, 120 V power supply.
9.2 Non-Pressurized
For a non-pressurized outside air supply, a 4" O.D. sin­gle wall pipe duct may be attached to the burner and end vent. For length and duct sizing requirements See Section 9.3. To prevent condensation, insulate the outside air duct.
9.3 Outside Air System Design Requirements
9.3.1 Non Pressurized
• 6" diameter duct must not exceed 90' (27 m)
• 4" diameter duct must not exceed 90' (27 m)
• Elbows are equivalent to 10' (3 m) of duct length.
• See the CRV-Series Installation, Operation, and Service Manual (P/N 127102NA) for ducting installation details.
9.3.2 Pressurized Systems
• 6" diameter duct must not exceed 120' (36 m) total per system.
• 4" diameter duct must not exceed 120' (36 m) per radiant branch.
• See the CRV-Series Installation, Operation, and Service Manual (P/N 127102NA) for ducting installation details.
FIGURE 27: Air Supply System Capacity by Duct Length and Diameter
In a way similar to the CRV-Series pump system, the design of the air supply system also involves consider­ations of total flow units and acceptable combinations of duct lengths (and diameters) versus flow units car- ried. In certain circumstances, it may be desirable to introduce an outside air blower to pressurize the sys­tem. A small positive pressure is desirable and neces­sary to prevent the system from drawing in contaminated air.
9.1 Pressurized
For pressurized outside air supplies, the outside air blower motor has a pressure switch that must be used. Wire this switch in-series with the pu switch. When using an outside air blower with a ROB- ERTS GORDON
28
®
System Control, ROBERTS GOR-
mp pressure
9.3.3 Pipe sizing
To size each section of pipe proceed as follows:
• Calculate the required flow units at each outlet of the supply system.
• Measure the longest run of pipe from the blower to the most remote outlet. Use only this distance in Figure 27 (or the next longer distance if the exact distance is not shown). This is to provide assurance that the pressure drop to the most remote outlet will not exceed 0.25" w.c. when all outlets are supplied.
See Figure 27, find the intersection point on the graph for the appropriate duct length and number of flow units. The duct size above this intersection point indicates what size duct work should be used. Proceed in a similar manner for each outlet and each section of duct. For each section of duct, determine the total flow unit capacity sup- plied by that section.
SECTION 9: AIR SUPPL Y SYS TEM
Duct Design Rules
• System should be designed so that the blower is positioned closest to the highest flow require- ments (end vents).
• When a duct is carrying more than 40 flow units, it must be at least 6" diameter.
Blower (P/N 90707501) Performance 112 Flow Units:
One outside air blower is required per each EP-100 or EP-200 series pump and two outside air blowers may be required for each EP-300 series pump. Outside air blowers cannot be shared between two separate CRV-Series systems.
FIGURE 28: Outside Air Blower
29
CRV-SERIES DESIGN MANUAL
*NOTE: up to 10' (3 m) max. from blower inlet can be neglected for pressure drop calculations.
4
4
4
10
20 8
8
8
110'
(33 m)
(44)
15 6
66
(22)
(33)
P
100'
(30 m)
15'
(4.5 m)
B
50'
(15 m)
10'
(3 m)
max.*
4" duct
4" duct
Branch A
Branch B
Walls
Branch C
4" duct
6" Duct
4" Duct
6" duct
FIGURE 29: Sample Layout for Pressurized Outside Air Systems
30
®
SECTION 10: ROBERTS GORDON
ULTRAVAC™ DESIGN REQUIREMENTS
CRV-B-2 and CRV-B-4 are not available for use with ROBERTS GORDON
®
ULTRAVAC™ controls.
CRV-Series systems designed with minimum radiant tube lengthshall have 1.5' - 2.0' per flow unit of tailpipe length.
-OR-
CRV-Series systems with recommended radiant tube length shall have 1.2' - 1.5' per flow unit of tailpipe length.
SECTION 10: ROBERTS GORDON® ULTRAVAC™ DESIGN R EQUIREMENTS
31
CRV-SERIES DESIGN MANUAL
SECTION 11: CRV-SERIES EQUIPMENT SPECIFICATIONS
The total heating system supplied shall be design cer- tified by the CSA International per American National Standard ANSI Z83.20/CSA 2.34 (latest edition).
11.1 Burner and Burner Controls
11.1.1 Burners shall be designed to operate simulta-
neously in series without adverse effects from com-
11.2 Equipment
11.2.1 Burner
Each burner assembly shall consist of heavy-duty cast-iron burner heads, pre-wired gas controls with electronic, three-try direct spark ignition and combus- tion air filter.
bustion gases from upstream burners.
11.2.2 Pump
11.1.2 Burners shall be capable of firing on:
Natural Gas, or LP Gas.
11.1.3 Burners shall be supplied to fire at any one of the input firing rates as specified:
CRV-B-2-20,000 (Btu/h)
CRV-B-4-40,000 (Btu/h)
CRV-B-6-60,000 (Btu/h)
CRV-B-8-80,000 (Btu/h)
CRV-B-9-90,000 (Btu/h)
CRV-B-10-100,000 (Btu/h)
CRV-B-12A-110,000 (Btu/h)
CRV-B-12-120,000 (Btu/h)
When using ROBERTS GORDON
®
ULTRAVAC™ con­trols, burner rates will modulate between 60% and 100% rated input (CRV-B-2 and CRV-B-4 are not avail­able for use with ROBERTS GORDON
®
ULTRAVAC™
controls).
11.1.4 The design of burners supplied shall provide for maintaining a constant proportion of fuel gas to fil­tered combustion air. These conditions are met for burners in which the pressure of both the fuel gas and the combustion air are introduced at zero (atmo­spheric) pressure and the flow of each is established by a vacuum on the downstream side of the flow
The pump model supplied will vary with the capacity of the system. See the pump technical specification sheet or the installation, operation and service manual for product description and specification.
The pump shall be acoustically isolated from the sys­tem with a flexible connector with temperature rating of 350°F minimum. The motor in the vacuum pump shall be secured with rubber mounts for acoustical isolation.
11.2.3 Heat Exchanger
Radiant tubing (between burners and 10’ - 70’ down- stream of last burner) shall be of 4" O.D. steel or heat treated aluminized tubing.
As an option, the balance of the tubing shall be 4" O.D. steel tubing w of acid-resistant porcelain.
All heat exchanger (tubing) connections shall be made with stainless steel coupling assemblies. Standard couplings will be used in radiant sections. Lined cou- plings will be used in tailpipe sections.
11.2.4 Outside Air
When specified, in contaminated environments, the system shall be capable of supplying air from the out- side to each burner and end vent for the support of combustion.
metering orifices.
11.1.5 To as s ure a high degree of fail-safe operation, the design shall preclude flow of gas if any or all of the following abnormal conditions occur in the non- firing mode:
ith an internal and external coating
1. Main valve fails in open position.
2. Vacuum pump motor fails to operate.
3. Power fails.
11.1.6 To further assure a high degree of safety, the system will be under negative pressure at all times during operation to preclude the possibility of the escape of combustion gases inside the building.
11.1.7 The burner control assembly will include a zero regulator.
11.1.8 All bu
rners shall be pre-wired with a grounded
electrical cord and plug.
32
Infrared Heating
Maintain clearance
to the side and
clearance below
the heater from vehicles
and combustible materials.
www.rg-inc.com Printed in U.S.A. P/N 91037912 Rev. H
Attach this information to a wall near the ROBERTS GORDON
®
heater.
Read the Installation, Operation, and Service Manual thoroughly before installation, operation, or service.
Know your model number and installed configuration. Model number and installed configuration are found on the burner and in the Installation, Operation and Service Manual. Write the largest clearance dimensions with permanent ink according to your model number and configuration in the open spaces below.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting.
1. Set the thermostat to off or the lowest setting.
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the installation and service of gas-fired heating equipment.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
Fire Hazard
Keep all flammable objects, liquids and vapors the minimum required clearances to combustibles away from heater.
Some objects will catch fire or explode when placed close to heater.
Failure to follow these instructions can result in death, injury or property damage.
TO TURN OFF THE HEATER
Service Telephone: +44 (0)121 506 7709 Service Fax: +44 (0)121 506 7702 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
Roberts-Gordon LLC
1250 William Street P.O. Box 44 Buffalo, NY 14240-0044 USA Telephone: 716.852.4400 Fax: 716.852.0854 Toll Free: 800.828.7450
WARNING
Roberts-Gordon Europe Limited
Unit A, Kings Hill Business Park Darlaston Road, Wednesbury West Midlands WS10 7SH UK Telephone: +44 (0)121 506 7700 Fax: +44 (0)121 506 7701
®
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help
facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor conduct, at a minimum, annual inspections of your ROBERTS GORDON
®
equipment and
perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.
Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.
This product is not for residential use.
© 2009 Roberts-Gordon LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying, recording, taping, or information storage and retrieval s
ystems – without written permission of Roberts-Gordon LLC.
Loading...