Roberts Gorden Combat HVE 400, Combat HVE 450, Combat HVE 650 Installation, Operation And Service Instructions

Page 1
Roberts-Gordon Europe Limited
Unit A, Kings Hill Business Park Darlaston Road, Wednesbury West Midlands, WS10 7SH UK Telephone: +44 (0)121 506 7700 Fax: +44 (0)121 506 7701 Service Telephone: +44 (0)121 506 7706 Service Fax: +44 (0)121 506 7702 E-mail: uksales@rg-inc.com E-mail: export@rg-inc.com
www.robertsgordon.co.uk www.blackheatheaters.co.uk
WARNING
Installation must be done by an electrician qualified in the installation and service of control systems for heating equipment.
Improper installation, adjustment, alteration, service or maintenance can result in death, injury or property damage. Read the Installation, Operation and Service Manual thoroughly before installing or servicing this equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place in order to provide
your service technician with necessary information.
© 2014 Roberts-Gordon Europe Limited
P/N 160101UK Orig 07/14
Combat® HVE
Energy Saving Fans
with Control Options
Installation, Operation &
Service Manual
Page 2
Page 3
© 2014
Roberts-Gordon Europe Limited
All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Roberts-Gordon Europe Limited.
TABLE OF CONTENTS
SECTION 1: Introduction........................................................ 2
1.1 Electrical Requirements ............................................... 2
1.2 Check Installation Materials ......................................... 2
1.3 Safety Labels and Their Placement ............................. 3
SECTION 2: Specifications .................................................... 4
2.1 Electrical Specifications............................................... 4
2.2 Fan Specifications........................................................ 4
2.3 Dimension Data ...........................................................4
SECTION 3: Critical Considerations .....................................5
3.1 Location and Suspension ............................................5
3.2 Minimum Required Installation Clearances. ................5
SECTION 4: Installation.......................................................... 6
4.1 Preparation ..................................................................6
4.2 Electrical Supply ..........................................................7
SECTION 5: Typical External Wiring Diagrams .................... 8
5.1 External Wiring Connection Details ............................. 8
SECTION 6: Troubleshooting............................................... 10
6.1 Sequence of Operation.............................................. 10
SECTION 7: Replacement Parts .......................................... 11
Printed in U.K.
Page 4
Page 5
TABLE OF FIGURES
Figure 1: Label Placement........................................................ 3
Figure 2: Dimension Data .........................................................4
Figure 3: Mounting Hole Layout................................................6
Figure 4: Suspension Methods .................................................7
Figure 5: BJ8 Fan Control Wiring Diagram................................8
Figure 6: DP5 Fan Control Wiring Diagram............................... 8
Figure 7: WAC6 Fan Control Wiring Diagram............................9
Figure 8: HVE Fan Without Speed Control Wiring Diagram ...... 9
Figure 9: Internal Components Diagram ................................. 12
Page 6
Page 7
1 of 12
Product Approval
ROBERTS GORDON® appliances have been tested and CE certified as complying with the essential requirements of the Gas Appliance Directive, the Low Voltage Directive, the Electromagnetic Compatibility Directive and the Machinery Directive for use on natural gas and LPG when installed, commissioned and maintained in accordance with these instructions.
These instructions refer to appliances designed to operate in the European Union. Appliances designed for other countries (Non-European Union) are available on request. This appliance must be installed in accordance with the local and national codes in force and used
only in a sufficiently ventilated space, as specified in these instructions. Before installation, check that the local gas distribution systems, nature of gas and pressure, and
adjustment of the appliance are compatible.
Page 8
SYSTEM CONTROL INSTALLATION, OPERATION AND SERVICE MANUAL
2 of 12
SECTION 1: INTRODUCTION
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special atten­tion when reading and following the warnings in these
sections. Installation, service and annual inspection of controller must be done by an electrician qualified in the installation and service of control systems for heating equipment. Installation, service and annual inspection of heater must be done by a contractor qualified in the installation and service of gas or oil fired heating equipment. Read this manual carefully before installation, operation, or service of this equipment. The equipment must be applied and operated under the general concepts of resonable use and installed using best building practices. This equipment is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the equipment.
For optimum heater performance and safe heating conditions, inspect and maintain heater(s) before every heating season and as necessary. Also, know and maintain heater clearances to combustibles, see heater Installation, Operation and Service Manual for further details. If you require additional manuals, con­tact Roberts-Gordon at +44 (0)121 506 7700 or at www.robertsgordon.co.uk.
1.1 Electrical Requirements
Failure to comply with the installation instructions will invalidate the limited warranty.
All wiring must comply with current wiring regulations and any local regulations which may apply. Always switch off electrical supply to equipment and discon­nect by removing plug before working on equipment.
Equipment must be electrically grounded in accor­dance with local specifications and codes.
1.2 Check Installation Materials
Before proceeding with installation of ROBERTS GORDON
®
COMBAT
®
HVE Fan, check the following
points:
1.2.1 Control Options
Each HVE Fan has a built in thermostat that allows it to turn on when ambient temperature at fan exceeds thermostat’s setpoint. In addition, HVE Fans can be used with a number of different speed control options.
Control Options Specifications
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Equipment must be properly grounded.
Failure to follow these instructions can result in death or electrical shock.
Model WAC6 DP5 BJ8
Control Unit Capacity (No. of Fans) HVE400 1 4 8
HVE450 N/A 1 2
HVE650 N/A 1 2
Manual On/Off Yes Yes Yes
Manual Fan Speed Adjustment Yes Yes No
Automatic Fan Speed Adjustment No No Yes
Fans ‘ON’ Neon Indicator Yes No No
Temperature Sensor Range [°C] N/A N/A 0-40
Temperature Sensor Cable Length [m] N/A N/A 10
Maximum Starting Current [A] 3 10 20
Maximum Running Current [A] 1.5 5 10
Page 9
SECTION 1: INTRODUCTION
3 of 12
1.2.2 Electrical Installation Materials
A 230 V, 50 Hz, 1 ph, 20 A power supply to equipment must be installed and comply with current wiring regulations and any local regulations which may apply.
1.3 Safety Labels and Their Placement
Product safety signs or labels should be replaced by product user when they are no longer legible. Please contact Roberts-Gordon Europe Limited or your ROBERTS GORDON
®
independent distributor to
obtain replacement signs or labels.
FIGURE 1: Label Placement
Description Part Number
Logo Label 91040030 Shock Hazard Label 91008001 Address Label 91040006 Wiring Diagram Label 91040400 Terminal Connection Label (not shown) 91040401 Rating Plate Label 91010450
Page 10
SYSTEM CONTROL INSTALLATION, OPERATION AND SERVICE MANUAL
4 of 12
SECTION 2: SPECIFICATIONS
2.1 Electrical Specifications
Supply: 230 V, 50 Hz, 1 Ø, 20 A
2.2 Fan Specifications
2.3 Dimension Data
FIGURE 2: Dimension Data
Model HVE 400 HVE 450 HVE 650
Air Capacity
[m
3
/h]
[ft
3
/min]
3,600 2,120
6,300 3,710
10,80 0
6,360
Fan Diameter [mm] 400 500 650
Motor Speed [RPM] 1400 1430 890
Electrical Load [W] 179 499 598
Capacitor [μF] 3 8 12
Electrical Supply 230 V / 50 Hz / 1 Ø
Starting Current [A] 1.5 6.4 6.0
Running Current [A] 1.0 1.6 2.6
Noise Level @ 3m NR dB [A] 55 68 70
Maximum Ambient Temperature [°C] 60 65 40
Thermostat
Recommended Minimum Setting [°C] 15 15 15
Maximum Setting [°C] 30 30 30
Recommended Minimum Setting above room temperature
[°C] 3 3 3
Model HVE 400 HVE 450 HVE 650
‘A’ Depth [mm] 300 305 284
‘B’ Casing Width [mm] 527 610 790
‘C’ Overall Width [mm] 582 665 845
Weight [kg] 15 25 33
Minimum Recommended Mounting Height [m] 6 11 14
Maximum Recommended Mounting Height [m] 11 18 25
Minimum Wall Clearance [m] 1.75 1.75 1.75
Minimum Roof Clearance [m] 1 1 1
Page 11
SECTION 3: CRITICAL C ONSIDERATIONS
5 of 12
SECTION 3: CRITICAL CONSIDERATIONS
3.1 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position.
• Fan must be suspended from above (See Page 7, Figure 4). Drop rods must be a minimum of 10 mm diameter mild steel. Four suspension points (M10 nuts) are located on top of fan. Mounting hardware must be sufficient to support fan weight as listed in the dimension data on Page 4, Sec- tion 2.3.
• Must be installed in a manner which allows
access to all serviceable components.
3.2 Minimum Required Installation Clearances.
Clearances around fan must be as indicated on Page 4, Section 2.3 to ensure access for servicing and cor-
rect operation.
Page 12
SYSTEM CONTROL INSTALLATION, OPERATION AND SERVICE MANUAL
6 of 12
SECTION 4: INSTALLATION
Installation of the COMBAT
®
HVE Fan and the asso­ciated external electrical wiring must be completed by an electrician qualified in the installation of control systems for heating equipment.
4.1 Preparation
Before installing the COMBAT
®
HVE Fan, observe the
following:
FIGURE 3: Mounting Hole Layout
Dimensions
4.1.1 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed in a level position.
• Fan must be suspended from above (See Page 7, Figure 4). Drop rods must be a minimum of 10
mm diameter mild steel. Four suspension points (M10 nuts) are located on top of fan. Mounting hardware must be sufficient to support fan weight as listed in the dimension data on Page 4, Sec- tion 2.3.
• Must be installed in a manner which allows access to all serviceable components.
4.1.2 Suspension Mounting
Model HVE 400 HVE 450 HVE 650
A mm 493 575 758
B mm 364 447 628
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Equipment must be properly grounded.
Failure to follow these instructions can result in death or electrical shock.
WARNING
Crush Hazard
Use 8 mm steel drop rod minimum.
Failure of the supports can result in death, injury or property damage.
Page 13
SECTION 4: INSTALLATION
7 of 12
FIGURE 4: Suspension Methods
4.2 Electrical Supply
All fans and controls need a constant 230 V 50 Hz single phase supply connected to terminals L, N, and Earth. Polarity "L & N" must be correct. The voltage between neutral and earth should be 0 and never exceed 15 volts.
All fans and controls must be correctly earthed. All external wiring must comply with relevant IEE and local regulations and be carried out by a qualified electrician.
Page 14
SYSTEM CONTROL INSTALLATION, OPERATION AND SERVICE MANUAL
8 of 12
SECTION 5: TYPICAL EXTERNAL WIRING DIAGRAMS
5.1 External Wiring Connection Details
If any of the original wire supplied with fan must be replaced, it must be replaced with wiring material having a temperature rating of at least 105 °C and 600 V.
FIGURE 5: BJ8 Fan Control Wiring Diagram
FIGURE 6: DP5 Fan Control Wiring Diagram
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be required to disconnect electric to the unit.
Failure to follow these instructions can result in death or electrical shock.
Page 15
SECTION 5: TYPICAL EXTERNAL WIRING D IAGRAMS
9 of 12
FIGURE 7: WAC6 Fan Control Wiring Diagram
FIGURE 8: HVE Fan Without Speed Control Wiring Diagram
Page 16
SYSTEM CONTROL INSTALLATION, OPERATION AND SERVICE MANUAL
10 of 12
SECTION 6: TROUBLESHOOTING
6.1 Sequence of Operation
The BJ8 Fan Control uses an external temperature sensor to automatically adjust HVE Fan speed. In AUTO mode, fan speed will increase as temperature rises beyond the point set at temperature dial. In MAX mode, fan will run at full speed regardless of temperature. The BJ8 has an ON/OFF switch for turning HVE Fan(s) on and off. The temperature sen­sor should be located as close as possible to one of the HVE Fans it is controlling.
The DP5 and WAC6 Fan Controls offer manual con­trol over HVE Fan speed. See Page 8, Section 5 wir- ing diagrams to utilize HVE Fan thermostat. In this case, each fan will turn on when temperature at fan exceeds thermostat setpoint. The fans speed will be determined by speed set on controller. To disable HVE Fan thermostat, wire line power to terminal “1” rather than terminal “L”.. In this configuration, fan con­trol ON/OFF switch will be used to turn HVE Fan(s) on and off.
If a fan control is not used, the built in thermostat on each HVE fan will turn equipment on when tempera­ture at fan exceeds setpoint of thermostat.
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be required to disconnect electric to the unit.
Failure to follow these instructions can result in death or electrical shock.
Page 17
SECTION 7: REPLACEMENT PARTS
11 o f 12
SECTION 7: REPLACEMENT PARTS
Carbon Monoxide Hazard
WARNING
Use only genuine ROBERTS GORDON® replacement parts per this installation, operation and service manual.
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Explosion Hazard
DANGER
Electrical Shock Hazard
Fire Hazard
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be required to disconnect electric to the unit.
Failure to follow these instructions can result in death or electrical shock.
Page 18
SYSTEM CONTROL INSTALLATION, OPERATION AND SERVICE MANUAL
12 of 12
FIGURE 9: Internal Components Diagram
Model Description Part Number
HVE 400 Axial Fan 400 mm A263A HVE 450 Axial Fan 450 mm A268A HVE 650 Axial Fan 650 mm A269
N/A Thermostat 230 V C2334B