RKI Instruments Beacon 800 User Manual

Beacon 800 Gas Monitor
Operator’s Manual
Part Number: 71-0037RK Revision: C Released: 1/2/14
www.rkiinstruments.com
RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge. This warranty does not apply to those items, which by their nature, are subject to deterioration or consumption in normal service, and which must be cleaned, repaired, or replaced on a routine basis. Examples of such items are as follows:
a) Absorbent cartridges d) Batteries b) Pump diaphragms and valves e) Filter elements c) Fuses
Warranty is voided by abuse including mechanical damage, alteration, rough handling, or repair procedures not in accordance with the operator’s manual. This warranty indicates the full extent of our liability , and we are not responsible for removal or replacement costs, local repair costs, transportation costs, or contingent expenses incurred without our prior approval.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED, AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF RKI INSTRUMENTS, INC., INCLUDING BUT NOT LIMITED TO, THE WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS, INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR CONSEQUENTIAL LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF ITS PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR OPERATE PROPERLY.
This warranty covers instruments and parts sold to users by authorized distributors, dealers, and representatives as appointed by RKI Instruments, Inc.
We do not assume indemnification for any accident or damage caused by the operation of this gas monitor, and our warranty is limited to the replacement of parts or our complete goods.
Beacon 800 Gas Monitor Operator’s Manual
Table of Contents
Chapter 1: Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About the Beacon 800 Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
About This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Chapter 2: Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
External Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Internal Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Chapter 3: Installation & Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Mounting the Beacon 800 Gas Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Wiring the Beacon 800 Gas Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Starting Up the Beacon 800 Gas Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Chapter 4: Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Alarm Indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Viewing & Resetting Min/Max Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Chapter 5: Configuration Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Enabling or Disabling Channels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Calibration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Configure Channel Settings Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Chapter 6: Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Replacing the Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Chapter 7: Optional Recorder Output Board & Heavy Duty Relay Board . . . . . . . . . . 32
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Recorder Output Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Heavy Duty Relay Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Beacon 800 Gas Monitor Operator’s Manual
Chapter 1: Introduction
Overview
This chapter briefly describes the Beacon 800 Gas Monitor. This chapter also describes the Beacon 800 Gas Monitor Operator’s Manual (this document). Table 1 at the end of this chapter lists the specifications for the Beacon 800.
About the Beacon 800 Gas Monitor
The Beacon 800 is a fixed-mounted, continuous-monitoring instrument. This multiple channel gas monitor is capable of detecting gas at up to eight locations. The display screens simultaneously display the gas readings of all active channels.
The Beacon 800 includes audible and visual alarms that warn you of hazardous gas conditions. The alarm circuit includes two levels of gas alarms. The fail circuit alerts you to failures in the gas tra nsmitter(s) or Beacon 800.
The Configuration menu allows you to change channel and calibration settings.
About this Manual
The Beacon 800 Gas Monitor Operator’s Manual is organized as follows:
Chapter 1 is an introduction to the Beacon 800.
Chapter 2 describes the components of the Beacon 800.
Chapter 3 describes the installation and start-up procedures of the Beacon 800.
Chapter 4 describes the operatio n of the Beaco n 800.
Chapter 5 describes the configuration procedures of the Beacon 800.
Chapter 6 describes the maintenanc e of the Beacon 800.
Chapter 7 describes the optional Recorder Output and Heavy Duty Relay boards. The Beacon 800 Gas Monitor Operator’s Manual uses the following conventions for notes,
cautions, and warnings:
NOTE: Describes additional or critical information.
CAUTION: Describes potential damage to equipment.
WARNING: Describes potential danger that can result in injury or death.
1 • Overview Beacon 800 Gas Monitor Operator’s Manual
Specifications
Table 1 lists specifications for the Beacon 800.
Description Specification
Input Power 100 to 240 VAC or 24 VDC Detector Head Input Type 2 or 3 wire 4-20mA transmitters Construc tion (housing) Fibergla ss/polyester with lexan window (NEMA 4X) Dimensions 12.5 in. H x 11.0 in. W x 6.4 in. D
Weight 10.4 lbs. (without AC line cord) Operating Temperature -4°F to 122°F (-20°C to 50°C) Storage Temperature -4°F to 158°F (-20°C to 70°C) Regulatory CSA, NRTL/C
T a ble 1: Beacon 800 Specifications
(31.8 cm H x 27.9 cm W x 16.3 cm D)
Environmental Conditions For indoor or outdoor locations (Type 4X)
2000 meter max altitude
Maximum humidity: 80% relative
Pollution Degree 2
Installation Category II
User Controls Reset switch
Program buttons: ESCAPE, UP (YES), DOWN (NO), and ENTER) Relays CSA Rated for 3 amps at 115 VAC resistive, Form C Standard Accessory Operator’s manual (this document)
Beacon 800 Gas Monitor Operator’s Manual Specifi cations • 2
Chapter 2: Description
Overview
This chapter describes external and internal components of the Beacon 800 Gas Monitor.
External Description
This section describes the housing and all external components of the Beacon 800. For the purposes of this description, the housing door is considered the front of the monitor.
Housing
The Beacon 800’s fiberglass housing is weather- and corrosion-resistant. It is suitable for installation where general purpose equipment is in use. The housing door is hinged on the left side and is secured by two latches on the right side. The display screens and status lights are visible through windows in the housing door. Four mounting feet are attached to the back of the housing (one at each corner). The mounting feet allow you to install the housing to a vertical surface. Four conduit hubs on the bottom of the housing are for external wiring connections.
CAUTION: To avoid electrical interference, do not route transmitter and power wiring
through the same conduit hub.
Reset Switch
The reset switch is on the bottom of the housing, in front of the buzzer. The reset switch serves three functions:
Resets the alarm circuits for “latched” alarms after an alarm 1 or alarm 2 condition passes.
Y ou can set each channel for latched or self-resetting alarms in the channel setup pro­gram. See Chapter 5, Configuration, for more information.
Silences the buzzer during an alarm 1 or alarm 2 condition. You cannot silence failure alarms.
Displays and resets the minimum and maximum gas concentration values.
Buzzer
The buzzer is on the bottom of the housing, behind the reset switch. The buzzer sounds audible warnings to warn you of gas alarms and instrument failures.
3 • Overview Beacon 800 Gas Monitor Operator’s Manual
Internal Description
y y
(
(
r)
This section describes the internal components of the Beacon 800.
Main board
Power supply
Display board
(see Figure 2)
Housing
(shown without doo
Alarm 2 common rela Alarm 1 common rela
Fail common relay Power switch Channel relays
(see Figure 3)
Alarm terminal strip
channels 1-4; alarm 2)
Transmitter terminal strip
(channels 5-8)
Transmitter terminal strip
(channels 1-4)
Alarm terminal strip
channels 1-4; alarm 1)
Conduit hub
(total of 4)
Display Screens
NOTE: The display screens, status lights, and program buttons are mounted to a
AC terminal strip
Controller
terminal strip
Alarm terminal strip
(channels 5-8; alarm 2)
Alarm terminal strip
(channels 5-8; alarm 1)
Ground Stud
Reset switch
Buzzer
(behind switch)
Figure 1: Beacon 800 Gas Monitor Component Location
secondary circuit board. This circuit board is mounted to the main circuit board by standoffs.
The display screens simultaneously display the target gas, measuring unit, and current gas reading of all active channels. The top screen displays channels 1 through 4; the bottom screen displays channels 5 through 8.
The display screens also display messages, settings, and other data when you are operating the configuration menu.
Beacon 800 Gas Monitor Operator’s Manual Internal Description • 4
Display screen 1
(channels 1-4)
ALARM 2 light
ALARM 1 light
Display screen 2
(channels 5-8)
Status Lights
The Beacon 800 includes four status lights that indicate the current status of the monitor: the ALARM 1 light, the ALARM 2 light, the FAIL light, and the PILOT light (see Figure 2).
PILOT Light
The PILOT light is on when the Beacon 800 is receiving incoming power, either AC or DC power.
FAIL light
Thumbscrew
(total of 2)
Figure 2: Display Board Component Location
ESCAPE button
UP (YES) button
DOWN (NO) button
ENTER button
PILOT light
FAIL Light
The FAIL light turns on when the Beacon 800 is experiencing a fail condition. A fail condition can be caused by a failure within the Beacon 800 or transmitter(s) wired to the Beacon 800 (see “Chapter 6: Maintenance” on page 29).
ALARM 1 Light
The ALARM 1 light is on when the Beacon 800 is experiencing a low-level (alarm 1) or high-level (alarm 2) gas condition.
ALARM 2 Light
The ALARM 2 light is on when the Beacon 800 is experiencing a high-level (alarm 2) gas condition.
Program Buttons
The Beacon 800 includes four program button that allow you to enter the Configuration Menu, navigate through the menu, update instrument and channel settings, and save changes to the settings. The program buttons, listed in Table 2, are near the right edge of the display board (see Figure 2).
5 • Internal Description Beacon 800 Gas Monitor Operator’s Manual
Table 2: Beacon 800 Program Button Functions
Button Function
ESCAPE Moves backward through the Configuration Menu
Cancels changes you make in the Configuration Menu
Enters the Configuration Menu (press with ENTER button)
UP (YES) Accepts the displayed setting and proceeds to the next setting
Changes the displayed setting
DOWN (NO) Allows you to update the displayed setting
Changes the displayed setting
ENTER Saves changes you make in the Configuration Menu
Enters the Configuration Menu (press with ESCAPE button)
Ground Stud
The ground stud is used for connecting earth ground to the Beacon 800. The ground stud is factory wired to the GND terminal on the AC terminal strip. The ground stud is located in the lower right corner of the main board.
Terminal Strips
The Beacon 800 includes four terminal strips for external wiring connections. See “Wiring the Beacon 800 Gas Monitor” on page 12 for detailed wiring procedures.
Transmitter Terminal Strips
Two transmitter terminal strips are mounted to the bottom left corner of the main circuit board (see Figure 1). These two 12-point terminal strips facilitate wiring connections to the detector heads. The bottom terminal strip is for channels 1 through 4; the top terminal strip is for channels 5 through 8.
Alarm Terminal Strips
Four alarm terminal strips are to the right of the transmitter terminal strips (see Figure 1). These four 12-point terminal strips facilitate wiring connections to external alarm devices (horn, strobe, etc.). The bottom row of alarm terminals is for alarm 1 connections; the top row of alarm terminals is for alarm 2 connection.
NOTE: The alarm terminal strips provide external alarm connections controlled by
individual channels. The Beacon 800 also provides common alarm terminals on
the controller terminal strip. The common alarm terminals are controlled by all active channels.
Controller Terminal Strip
The 19-point controller terminal strip is to the right of the alarm terminal strips (see Figure
1). The controller terminal strip facilitates various internal and external wiring connections. Table 3 lists the function of each terminal.
Beacon 800 Gas Monitor Operator’s Manual Internal Description • 6
Table 3: Terminal Assignments for the Controller Terminal Strip
Terminal No. Connects to:
24VDC (BAT-/BAT+)
ALM2
DC power source (you can use DC power as a primary or backup power source.)
Common alarm 2 (external alarm)
1
2
(C, NO, NC) ALM1
Common alarm 1 (external alarm)
3
(C, NO, NC) FAIL
Common fail (external alarm)
4
(C, NO, NC) +28V Communication TX Communication RX Communication GND Communication RESET (2) Reset switch (factory-wired) BUZ-/BUZ+ Internal buzzer (factory-wired)
1
If used as primary power source do not make wiring connections to the AC terminal strip.
2
Activates if any gas channel recognizes an alarm 2 condition.
3
Activates if any gas channel recognizes an alarm 1 condition.
4
Activates if any gas channel or the Beacon 800 recognizes a fail condition.
AC Terminal Strip
The 3-point AC terminal strip is above the controller terminal strip (see Figure 1). The AC terminal strip facilitates wiring connections to the AC power source. The GND terminal is factory wired to the ground stud.
Relays
The Beacon 800 includes 16 channel relays and three common relays. Both sets of relay contacts are single-pole, double-throw (SPDT) and are rated for 3 amps at 115 VAC (resistive).
NOTE: In the Configuration menu, you can select normally energized, or normally de-
energized relays for each channel relay. This section describes the default setting: normally de-energized.
The alarm 1 and alarm 2 common relays are factory-set as normally de­energized and the fail common relay is factory-set as normally energized. The normally energized/normally de-energized setting for the alarm 1, alarm 2, and fail common relays is not user-adjustable.
Channel Relays
The 16-channel relays are above the alarm terminal strips (see Figure 1). These relays are dedicated to specific channels and alarm levels.
7 • Internal Description Beacon 800 Gas Monitor Operator’s Manual
For example, the channel 1, alarm 1 relay energizes if channel 1 recognizes an alarm 1 condition. Figure 3 illustrates the allocation of the channel relays.
Alarm 2
Alarm 1
Channel 1
Figure 3: Beacon 800 Channel Relay Allocation
Channel 8
Common Relays
The three common relays are above the AC terminal strip (see Figure 1). These relays are common for all channels.
For example, the alarm 1 common relay energizes if any channel recognizes an alarm 1 condition.
Power Switch
The power switch is to the left of the fuses (see Figure 1). The power switch turns the incoming power source on and off at the Beacon 800. When the switch is up, the power is on.
Power Supply
The power supply is near the top edge of the main circuit board. The power supply receives the AC input from the external power source and converts it to a DC voltage that is usable by the Beacon 800 circuitry.
Fuses
The Beacon 800 includes two AC fuses and one DC fuse. The fuses are housed in extractor-type fuse holders behind the display board and to the left of the common relays.
The AC fuses are the two 3A fuses. The AC fuses protect the AC line circuitry from short circuit or overload.
The DC fuse is the 6A fuse. The DC fuse protects the DC line circuitry from short circuit or overload.
NOTE: If your Beacon 800 includes the optional Recorder Output Board or the Heavy
Duty Relay Board, please see “Chapter 7: Optional Recorder Output Board & Heavy Duty Relay Board” on page 32 for a complete description of these options.
Beacon 800 Gas Monitor Operator’s Manual Internal Description • 8
Chapter 3: Installation and Start Up
Overview
This chapter describes procedures showing how to mount the Beacon 800 Gas Monitor, to make wiring connections to the monitor, and to start up the monitor.
WARNING: Perform all installation and start-up procedures in a “fresh air”
environment of normal oxygen content, and known to be free of combustible and toxic gas. The Beacon 800 is not in operation as a gas monitoring system until the start-up procedure is complete.
Mounting the Beacon 800 Gas Monitor
Perform the following procedure to install the Beacon 800 at the mounting site.
1. Select the mounting site. When you select the mounting site, consider the following factors:
Is an AC or DC power source available?
Is there enough room to open the housing door and make wiring connections
through the conduit hubs at the bottom of the housing?
Are the display screens and status lights visible?
2. Close and latch the housing door.
3. Position the monitor on a vertical surface at eye level (4 1/2 to 5 feet from the floor).
4. The Beacon 800 is shipped with the mounting feet positioned under the housing. Loosen the screws that secure the feet to the housing, rotate the feet to their mounting position (as shown in Figure 4), then tighten the screws.
5. Insert 1/4 in. screws through the slots in the mounting feet at each corner of the housing to secure the housing to the mounting surface (see Figure 4).
9 • Overview Beacon 800 Gas Monitor Operator’s Manual
(32.8 cm)
13.4 in.
(34.0 cm)
12.9 in.
12.5 in.
(31.8 cm)
8.0 in.
(20.3 cm)
10.5 in.
(26.7 cm)
Note:
The housing is
6.25 in. (15.9 cm) deep.
3/4 in. conduit hub
(total of 4 hubs)
Figure 4: Beacon 800 Gas Monitor Outline and Mounting Dimensions
Beacon 800 Gas Monitor Operator’s Manual Mounting the Beacon 800 Gas Monitor • 10
power if 24 VDC i s the
prim ary power s our ce.
100-240 V AC
Note: Do n otconnect AC
ContactRating of 10 Amps
Resistive at 2 50 VAC for Eac h
Alarm 1 T erminalStrip f or
Channels 1 - 4 ( typical wiring)
Stud
Ground
Line (Hot)
Neutral
Ground
Set of Al arm R elay C ontac ts.
AC Power Wiring
(factory wired)
+
Alarm
Power
Device
Battery
24 VD C
Buzzer
Reset Switch
(factory wired)
(for future u se)
Communication
Powe r
Alarm D ev ice
(typical wiring)
(factory wired)
2wire4-20mA
Transm itter Termi nals
(typical)
FB (4 - 2 0 m A)
+24VDC
Devices
3wire4-20mA
Transm iter Ter minals
(typical)
Common AlarmR elay Wirin g
(DC G round)
-
Alarm
Devices
+24VDC
FB (4 - 2 0 m A) Alarm
Transmitter Wiring Individual Alarm Relay Wiring
Figure 5: Beacon 800 Gas Monitor External Wiring Diagram
11 • Mounting the Beacon 800 Gas Monitor Beacon 800 Gas Monitor Operator’s Manual
Loading...
+ 30 hidden pages