New System Parameters ........................................................................................................ 16
English
WatchOUT 315DT Installation Manual 3
Relay Mode Installation
Introduction
RISCO Group's Dual Technology Outdoor Detector, WatchOUT 315DT, is a unique detector with
signal processing based on two Passive Infrared (PIR) channels and two Microwave (MW)
channels. The detector can operate as a regular relay detector connected to any control panel, or
as a BUS accessory when connected to RISCO Group's ProSYS control panel via the RS485
BUS, thus having unique remote control and diagnostic capabilities.
The instructions describe herein, describe the WatchOUT 315DT in Relay & BUS mode.
1. For low installations, below 1.7m (5'6") in which
pet immunity is required, use the supplied
RL300F lens (low wall or fence installations).
2. The detector's pet immunity (height of an animal,
no weight limitation), is up to 70 cm (2'4"), when
installing the detector at 2.2m (7'2"). If the
installation is bellow the height mentioned
above, the Pet Immunity decreases accordingly;
every 10 cm (4") decrease in installation height
leads to 10 cm (4") decrease in pet imunity.
If possible, avoid pointing the detector to
moving objects (swaying trees, bushes etc.)
Keep d istance o f
minimum 5m (16')
from moving objects
5m (16')
Ensure any objects do not obstruct the field of
view for both technologies. Pay attention to
growing trees or bushes, plants with big
moving leaves etc
For installations with extensive vehicle traffic or targets beyond
the required detection range, it is recommended to adjust the
MW sensitivity and/or to tilt the detector down.
Note:
Tilting the detector down may reduce the pet immunity
For optimum detection, select a
location that is likely to
intercept an intruder moving
across the coverage pattern at
a 45° trajectory.
Out of
Detection Range
NOTE: Disable Proximity AM during heavy rain (if WatchOUT 315DT is not sheltered) to
prevent Proximity AM alerts.
4 WatchOUT 315DT Installation Manual
Wall Mount Installation
t
Note:
The installation knockouts numbering are marked on
the back plate.
1. Open WatchOUT front cover
(unlock C1, Figure 1).
2. Release internal base (unlock I1, Figure 2).
3. Select mounting installation as follows:
Flat Mounting:
Open knockouts on external base (Figure 3).
• B1 - B4: Wall mounting knockouts
• T1: Back tamper knockout
• W2 / W3: wires entry knockouts
45° angle Mounting (Left side
mounting)
a. Open knockouts on external base
(Figure 3)
• L1, L2: Left mounting knockouts
• T3: Left tamper knockout
• W5 / W6: Wire entry knockouts
b. Remove tamper spring.
c. Replace tamper bracket (Item 1) with
supplied flat tamper bracket (Item 2).
Item 1
d. Insert Tamper lever B onto T5 and T3
and secure screw A (Figure 3).
4. Insert external wires through external base
W2, W3 (Flat Mounting) or W5, W6 (Left
side mounting) (Figure 3).
5. Secure external base to the wall.
6. Insert external wires and tamper wires
through internal base (Figure4).
7. Secure internal base to external base (lock
I1, Figure2).
8. Close the front cover (Lock C1, Figure1)
after wiring and setting DIP switches.
9. Walk test the detector.
Item 2
Figure 1
Figure 3
Tamper
Lever
B
A
Figure 4
Figure 2
C1
T1
T3
L1
B1
W5
W6
W3
L2
B4
l1
English
T5
T6
T4
T2
R1
(not visible)
B2
W9
W2
R2
(not visible)
B3
Note:
For 45° right side installation use the equivalent units on the external base as follows:
The back tamper is by default secured on the right
side of the internal base (rear view). If you wish to
move it to the left side (rear view), do the following
Figure 5
Left Side
Tamper
6
(Figure 5):
1. Remove tamper screw 1 in order to release the
tamper from position 7.
2. Ensure tamper spring 2 rests over tamper wire
3
1
base 4.
3. Ensure plastic tamper bracket 3 rests over both
2 and 4.
4. Secure tamper screw 1 into 3 over position 6.
4
2
Notes:
1. Verify that you hear a "Click" when attaching the tamper spring to the wall.
2. For pole installation, the tamper can be moved to the bottom right-hand side of the internal base.
Terminal Wiring
12VDC
Right Side
Tamper
7
5
+-
+,ALARM
FREE YEL
TAMPER
FREE
ALARM
N.C
FREE
YEL
TAMPER
N.C
FREE
GREEN
LEDs
AM
ENABL
WatchOUT DT - PCB
12 VDC
N.C relay, 24VDC , 0.1A
This terminal is a free pin that can be used to connect wires and EOL resistors
N.C switch, 24VDC , 0.1A
This terminal is a free pin that can be used to connect wires and EOL resistors
DUST TEST
SET/
UNSET
GREEN
AM
Normally closed AM relay output (
24VDC, 0.1A) indicates Anti Masking alarm or any
trouble in the detector (not including dust/dirty lens).
The Proximity AM enables receiving sabotage alerts before the detector is
damaged or masked, using both microwave channels.
Note:
When DIP8 is defined as Enabled this relay also opens momentarily when a Proximity AM
LED
ENABLE
attempt occurs.
Used to remotely control the LEDs when DIP1 is set to ON.
Enable: input is +12V OR no terminal connection
Disable: Connect the input to 0V
DUST N.O. collector max 70 mA. Indicates that the lens is dirty and requires cleaning.
TEST
Used to perform remote alarm testing to the detector by applying 0 volts to this
terminal.
Success: Alarm relay is momentary opened.
Failure: AM relay is opened
SET/
UNSET
This input enables to control Anti-masking and LEDs operation in accordance to
the system status, Set (Arm) / Unset (Disarm).
While the system is armed this feature prevents an intruder from gaining
knowledge of the detector’s status and disables Anti-masking detection.
System StatusInput StatusAM RelayLEDs
Set (Arm)0VOf
Unset (Disarm)12V or no connectionOn*On**
* DIP7 is ON (Anti masking enabled)
** DIP1 is ON (LEDs enabled) and LEDs ENABLE input terminal is enabled
(+12V OR no terminal connection).
6 WatchOUT 315DT Installation Manual
DIP Switch Settings
O
N
O
3
2
1
7
6
5
4
8
Factory Defaults
DIP 1: LEDs operation
On: LEDs Enabled
Off: LEDs Disabled
DIP 2-3: Detection Sensitivity
Sensitivity DIP2DIP3
Low Off Off
Mid Off On
Normal (Default)
On Off
Maximum* On On
* In maximum sensitivity sway recognition is
disabled to achieve maximum sensitivity
DIP 4: Anti masking Sensitivity
On: High
Off: Low
DIP 5: Detector's optics
On: Barrier / Long range
Off: Wide angle
DIP 6: Red LED /3 LED
On: Red LED only
Off: 3 LEDs
DIP 7: Anti masking operation
On: Enabled
Off: Disabled
DIP 8: Proximity AM
On: Enabled
Off: Disabled
Microwave Adjustment
Adjust Microwave coverage area by using the trimmer on the PCB.
Walk test
Two minutes after applying power, walk test the protected area to verify
proper operation.
For installations on uneven surfaces slide the PCB inside the internal base to
the appropriate setting according to the desired height (1.0m, 1.5m, 2.2m,
2.7m) as printed on the bottom left corner of the PCB or use the standard
swivel accessory.
For reducing the detection range, slide the PCB up
.
down
or tilt the swivel
MIN
MAX
PCB
1.00M
1.50M
2.20M
2.70M
English
LEDs Display
LED State Description
YELLOW
GREEN
RED
All LEDs
Notes:
1. DIP-Switch 1 should be in ON position to enable LED indications.
2. Only one LED is active at any one time. For example, in the case of both PIR and MW detection, either the
steady YELLOW LED or the steady GREEN LED is displayed (the first to detect), followed by the Alarm RED
3. In order to prevent the analysis of detection technologies such as PIR, Microwave, Active IR AM and
Proximity AM, set DIP Switch 6 (SW1) to ON. Only the red LED will be activated.
WatchOUT 315DT Installation Manual 7
Steady Indicates PIR detection
Flashing Indicates Active IR AM (Anti mask) detection
Steady Indicates MW detection
Flashing Indicates Proximity AM detection
Steady Indicates ALARM
Flashing Indicates malfunctioned communication with ProSYS (BUS
mode only)
Flashing (One
Unit initialization on power up
after another)
Relay Mode / BUS Mode Jumper
J-BUS jumper (located on the PCB between the red and green
LEDs) is used to define the detector’s mode of operation as
follows:
Relay
Mode
O
N
BUS Mode
N
O
Standard Swivel Installation
The Outdoor detector packaging contains a standard swivel for flexible installation. Please follow
the instructions below for mounting the detector with the Standard Swivel:
1. Open WatchOUT front cover (Unlock C1, Figure1).
2. Release internal base (Unlock I1, Figure 2).
3. Open knockouts on external base (Figure 6, Detail B)
• W1: Wires knockout
• S1,S2: Knockouts for securing external base to Standard Swivel
• S3: External base locking screw knockout
4. On the swivel accessory remove the required swivel cable wiring knockout S2, S7 or S9
(Figure 6, Detail A).
5. Remove back tamper from the internal base (see “Changing Back Tamper Position"
paragraph) and connect it to S5 (Figure 6, Detail A) on the Standard Swivel.
Note:
Ensure that you see the engraved UP mark on the upper front face of the swivel.
6. Select the mounting installation type as follows:
Wall Mounting
a. Insert external cable wiring through knockouts S2, S7 or S9 and extract them (including the
tamper wires) through the Swivel Wires Passage (Figure 6, Detail B).
b. Secure swivel to the wall through holes S1, S3, S6 and S8.
Swivel Conduit Mounting (using Conduit Metal Swivel Adaptor – CSMA, Figure 6, Detail A)
Tamper
Spring
Holes
M1
M2
M3
M4
CSMA
Detail ADetail B
Ø 16 mm
Ø 21 mm
Standard Swivel
S1
S9
S8
Swivel Wires
Passage
S2
S7 S6
S3
S4
Tamper
(see Detail C)
Snaps
W1
S1
S5
S2
S3
Detail C
Figure 6
Note:
The CSMA is required when wall external wiring is used and protection pipe is required. The CSMA should
be ordered separately - P/N RA300SC0000A.
a. Choose the direction upon which to mount the CSMA according to the required diameter:
16mm (0.63 inches) or 21mm (0.83 inches).
b. Insert conduit to the CSMA.
8 WatchOUT 315DT Installation Manual
c. Secure CSMA to the wall through points (M1, M4).
d. Insert external cables and tamper wires from the conduit through the swivel wires
passage of the swivel (Figure 6, Detail A).
e. Secure swivel to the wall through holes S1, S3, S6 and S8.
Note:
The Tamper spring S5 (Figure 7) should make contact with the wall through the tamper spring holes M2 or
M3 on the CSMA. Make sure to hear the tamper "Click" when connecting to the wall.
7. Insert tamper wires and external cable wiring from Standard Swivel through knockout W1 on
the external base (Figure 6, Detail B).
8. Connect the external base to the swivel using the dedicated snaps (Figure 7).
Swivel to External Base
Connecting Screws
Internal Base
S1
Angle Locking
Screw
(See Note 2)
External Base
See Detail A
Snaps
W1
S2
S3
Detail A
English
PCB
Swivel Assy
Connectin g Screw
(See Note)
Figure 7
Note:
Do not open or close the Swivel Assy Screw since it is used for connecting the swivel parts only.
9. Secure external base to swivel with two screws fastened to knockouts S1 and S2 (Figure 7).
10. Insert the supplied angle locking screw from the external base through the angle locking screw
knockout S3 on the external base to the standard swivel (Figure 7).
11. Tilt and Rotate the Standard Swivel to the desired position. Once the Standard Swivel is in the
desired position, secure the angle locking screw.
12. Line up the internal base onto the external base. Insert all wiring cables through the internal
base.
13. Secure internal base to external base (Lock I1, Figure 2).
14. To readjust the Standard Swivel when the PCB is installed (Figure 7):
a. Bend down the black foam located below the RED LED on the PCB (enough to reach the
Swivel locking screw).
b. Use a Philips screwdriver to release the locking screw (see Figure 8).
c. Tilt and/or Rotate the Standard Swivel to the desired position.
d. Secure the angle locking screw.
Note:
When marks on the two movable parts are aligned (Figure 8), the Standard Swivel is in 0°
vertical /horizontal position. Each click from this position represents shifting of 5° in vertical / horizontal
position.
15. Close the front cover (Lock C1, Figure 1) and walk test the detector.
WatchOUT 315DT Installation Manual 9
Note:
The screw has to pass through External Base and locked to the swivel.
Figure 8
Replacing Lenses
1. Unlock the six screws that hold the lens holding sleeve from the back of the front cover.
2. To release the protective sleeve, gently push the lens from the external side of the front cover.
3. Disconnect the lens from the sleeve by gently pushing the lens clips that secure it to the
sleeve.
4. Replace the lens. Place the 4 clips of the lens into the matching holes on the sleeve.
5. Insert the protective sleeve back into place on the front cover. Pay attention to place the
sleeve over the sealing rubber.
6. Secure the 6 holding screws back to their place.
Sleeve Locking
Screws
Lens Locking
Clips
Lens Prot ecting
Sleeve
Sockets for
Lens Clips
10 WatchOUT 315DT Installation Manual
Sealing Rubber
Front Cover
Locking Screw
Lens Types
Wide angle lens (RL300) /
Low installation - Pet lens (RL300F) :
40
11
9
30
7
20
5
3
10
1
0
0
1
10
3
5
20
7
30
9
11
40
Feet
0
Top view
2468100121415
20
10
304050
90°
Typical
Installation
Height:
2.2m (7'2")
Typical
Install ation
Height:
1.5m (5'3")
Note:
The detector's Pet Immunity (height of an animal, no weight limitation), is up to 70 cm (2'4"), when installing the
detector at 2.2m (7'2"). If the installation is bellow the height mentioned above, the Pet Immunity decreases
accordingly; every 10 cm (4") decrease in installation height leads to 10 cm (4") decrease in pet imunity.
Long range lens (RL300LR): Top view
Feet
1
3
0
0
3
1
Meters
Typical
Installation
Height:
2.2m (7'2")
246810012141618202223
Feet
0
Long range lens (RL300LR): Side view
Feet
10
0
Meters
Feet
20
10
3
1
0
0
304050
246810012141618 20 2223
20
10
304050
6070 75
6070 75
Wide angle lens (RL300):
Side View
Feet
10
3
1
0
0
Meters
2468100121415
Feet
0
20
10
304050
Low installation - Pet lens (RL300F) :
Side view
Feet
6
2
1
0
0
Meters
2468100121415
Feet
0
20
10
304050
Barrier lens (RL300B): Top view
Feet
3
5°
1
0
0
3
1
Meters
2468100121415
Feet
0
Barrier lens (RL300B): Side view
Feet
Typical
10
Installation
Height:
2.2m (7'2")
0
Meters
Feet
20
10
3
1
0
0
304050
2468100121415
20
10
304050
English
5°
WatchOUT 315DT Installation Manual 11
Technical Specification
Electrical
Current consumption 30mA at 12 VDC (Stand by)
42mA at 12 VDC (MAX with LED ON)
Voltage requirements 9 -16 VDC
Alarm contacts 24 VDC, 0.1A
AM contacts 24 VDC, 0.1A
Dust output Open collector 70mA max
Physical
Size: LxWxD 230 x 123 x 124mm (9 x 4.8 x 4.88 in.)
Weight 0.632 Kg (1.4lb)
Environmental
RF immunity According to EN50130-4
Operating/Storage temperature -30°C to 60°C (-22°F to 140°F)
* PIR technology is limited in rough environmental conditions.
Ordering Information
Standard Units
Model Description
WatchOUT 315DT WatchOUT DT + Swivel
Note:
Each of the detectors contains a standard swivel and 3 replacement lenses (P/N engraved on the Lens) 1.7m
low installation pet (RL300F), long-range (RL300R) and barrier lens (RL300B).
Accessories Kits
Model DescriptionWeight
RA300B WatchOUT Barrier Swivel Kit 0.1 Kg (0.23 lb)
RA300P WatchOUT Pole Adaptor Kit 0.25 Kg (0.55 lb)
RA300C WatchOUT Conduit Adaptor Kit 0.6 Kg (1.27 lb)
RA300HS WatchOUT Demo Housing - RA300SC WatchOUT Swivel Metal Conduit Adaptor 1Kg (2.2 lb)
Camera Option
Model Description
WatchOUT VC1 WatchOUT Camera Cover Adaptor
WatchOUT VC017 WatchOUT Narrow Camera
WatchOUT VC053 WatchOUT Wide Camera
WatchOUT VCPS WatchOUT Camera 220V Power Supply
WatchOUT VCPS WatchOUT Camera 120V Power Supply
UL Compliance Section
To comply with UL, note the following:
♦ The unit is intended for outdoor installation where unwanted alarms are tolerable. If not, it
is recommended to connect it to the trouble circuit of a listed compatible control unit.
♦ A dead zone of 5 ft should be considered during installation.
♦ The camera option is not UL listed.
♦ Disclaimer: PET feature has not been tested or verified by UL.
♦ 0.6 power factor inductive load can be used on the relays.
♦ Relay mode is intended to be connected to listed compatible control unit or power supply that provides 4
hours of standby power.
♦ It may be necessary to set detector at maximum sensitivity to achieve maximum distance.
♦ Do not connect the DUST output to a UL listed product.
♦ When the detectors are connected to the BUS of the ProSYS panel, the detectors are to be powered
from either the ProSYS (Version 7.55) panel or a listed compatible burglar alarm power supply that has
an output voltage range that does not exceed 9-16 vdc, has a minimum of 4 hrs. of standby power, and
is suitable for mercantile use.
12 WatchOUT 315DT Installation Manual
Only P/N:
RK315DT00USB
is UL approved
BUS Mode Installation
t
Introduction
The information in this section relates to WatchOUT 315DT installation in BUS Mode only. Up to
32 BUS detectors can be installed on the ProSYS RS485 BUS, saving cabling time and enabling
remote control and diagnostics.
Terminal Wiring
+,-
YELLOW
GREEN Used for data communication with the ProSYS. Connect to the terminal to the
TAMPER
LED
ENABLE
Note:
All terminals that are not mentioned in the table above are unused.
ProSYS
COM
AUX
BLK
RED
+-
Used for the connection of 12VDC power supply. Connect the (+) terminal to
the AUX RED and the (–) terminal to the COM BLK of the ProSYS terminals
Used for data communication with the ProSYS. Connect to the terminal to the
BUS YEL of the ProSYS
BUS GRN of the ProSYS
Used for the wiring for tamper detection, see below
Used for the wiring for tamper detection, see below
Cover and Back Tamper
BUS Mode:
Cover + Back tamper wiring
GREEN
FREE
BACK
TAMPER (N.C)
Short
BUS
YEL
GRN
TAMPER
FREE
ALARM
YEL
AUX
RED
LEDs
AM
DUST TEST
ENABLE
UNSET
+-
SET/
Cover Tamper Only
ProSYS
COM
BUS
BLK
YEL
GRN
FREE
ALARM
YEL
BUS Mode:
Cover Tamper Wiring
Short
FREE
TAMPER
GREEN
Cover Tamper to Zone Inpu
AUX
RED
ProSYS
BUS
COM
BLK
Zone
Input
BUS
YEL
Zone
COM
Z1Z2
GRN
BUS Mode:
Cover Tamper to Zone Input
Short
LEDs
AM
ENABLE
DUST TEST
UNSET
SET/
English
+-
ALARM
FREE
GREEN
YEL
FREE
TAMPER
LEDs
AM
ENABLE
DUST TEST
UNSET
SET/
DIP Switch Settings
DIP Switch
Number
1 - 5 Used to set the detector ID number. Set the ID number in the same way as for
6 - 8 Not used
WatchOUT 315DT Installation Manual 13
Description
any other ProSYS accessory (Refer to the ProSYS installation instruction
manual)
WatchOUT ID: DIP Switches 1 - 5
ID 1 2 3 4 5ID1 2 3 4 5
01 OFF OFF OFF OFF OFF 17 OFF OFF OFF OFF ON
02 ON OFF OFF OFF OFF 18 ON OFF OFF OFF ON
03 OFF ON OFF OFF OFF 19 OFF ON OFF OFF ON
04 ON ON OFF OFF OFF 20 ON ON OFF OFF ON
05 OFF OFF ON OFF OFF 21 OFF OFF ON OFF ON
06 ON OFF ON OFF OFF 22 ON OFF ON OFF ON
07 OFF ON ON OFF OFF 23 OFF ON ON OFF ON
08 ON ON ON OFF OFF 24 ON ON ON OFF ON
09 OFF OFF OFF ON OFF 25 OFF OFF OFF ON ON
10 ON OFF OFF ON OFF 26 ON OFF OFF ON ON
11 OFF ON OFF ON OFF 27 OFF ON OFF ON ON
12 ON ON OFF ON OFF 28 ON ON OFF ON ON
13 OFF OFF ON ON OFF 29 OFF OFF ON ON ON
14 ON OFF ON ON OFF 30 ON OFF ON ON ON
15 OFF ON ON ON OFF 31 OFF ON ON ON ON
16 ON ON ON ON OFF 32 ON ON ON ON ON
ProSYS Programming
The following section describes the additional software programming options, added to the
ProSYS software, that concern the settings of the WatcOUT DT as a BUS detector. Up to 32 BUS
detectors can be added to the system (16 in ProSYS 16) and each of them comes at the expense
of a zone in the system.
It is recommend reading and fully understanding the ProSYS Installation and User Manuals,
before programming the WatchOUT.
Notes:
The WatchOUT is compatible with the ProSYS software Version 4.xx and above.
The WatchOUT can be programmed via the U/D Software from UD Version 1.8 and above.
For maximum operation stability, it is best NOT to exceed a total of 300 meters (1000 feet) of wiring when
connecting the WatchOUT to the BUS.
Adding / Deleting the WatchOUT DT
The WatchOUT is part of a new accessory category, BUS zones. Therefore, Adding/Deleting the
WatchOUT is identical to any other accessory with the following exception:
Each BUS Zone Detector should be assigned to a Regular Zone.
Any BUS detector can be assigned to a physical wired zone or to a virtual zone.
Physical zone: Any zone on the ProSYS PCB (zones 1-8) or on a wired zone expander (ZE08, ZE16).
Virtual zone: Any zone on a BUS zone expander defined as BZ08 or BZ16.
Notes:
Virtual BUS zones are cost effective. They enable to expand your system zones without adding physical zone
expanders.
The virtual BUS zone expander can be used only for BUS zone detectors.
To add a BUS zone expander select type BZ08 or BZ16 when adding a zone expander (Quick key [7][1][2]).
1. To Add / Delete the WatchOUT DT
1. From the installer menu enter the Add/Delete menu: Quick Key [7][1][9][5] for BUS Zones
detectors.
2. Use the
ID number for which you want to assign (or delete) a detector.
Note:
Make sure that the detector's physical ID number is identical to the ID number you select during programming.
/ or / keys to position the cursor over the BUS Zone
14 WatchOUT 315DT Installation Manual
3. Place the cursor on the TYPE field and use the / key to select ODT15 for the
t
WatchOUT DT detector.
4. Press
/ to confirm.
5. Repeat the process for the other BUS detectors.
2. Assigning the WatchOUT DT to a Zone
1. From the main installer menu enter Zones: One by One option (Quick key [2][1])
2. Select the zone number that you want to assign the BUS detector.
Note:
If you defined a BUS Zone Expander, select a zone number from the virtual zones (defined by the BUS zone
expander).
3. Define Partitions, Groups, Zone Type and Zone Sound.
4. In the Termination category select [5] BUS Zone followed by
/ .
The following display appears:
Z:001 LINK TO:
Z:001 LINK TO:
ID:01 TYPE=ODT15
ID:01 TYPE=ODT15
5. Select the BUS zone number to assign to the programmed zone. The type field will be
updated automatically when selecting the zone.
6. Press
/ . The loop response category is not applicable to a BUS zone and the
following display appears:
Z:001 RESPONSE:
Z:001 RESPONSE:
N/A-BUS ZONE
N/A-BUS ZONE
7. Press
/ , assign label and press / .
3. Configuring the WatchOUT DT Parameters
1. To access the WatchOUT settings option press [2][0][3] from the main installer menu. The
following display appears:
B-ZONE PRMS:
B-ZONE PRMS:
ZONE#=001 (M:ZZ)
ZONE#=001 (M:ZZ)
2. Select the zone that the BUS zone was assigned to and press
/ . You can
now program the WatchOUT parameters as follows:
Zones Miscellaneous: BUS Zone
Quick Keys ParameterDefaul
[2][0][3][zzz]
[1]
[2][0][3][zzz]
[1][1]
[2][0][3][zzz]
[1][2]
LEDS 3 LEDS
Defines the LEDS operation mode.
Off
Disables the LEDS operation.
Red Only
Only the Red led will operate. This option is highly recommended to avoid the
possibility that the intruder will “Learn” the detector behavior.
Defines the operation of the LEDs anti masking detections while the detector
is armed
No
Active IR AM and Proximity AM (Anti masking) is enabled
LEDs behave according to the LEDs parameter definition
Yes
Active IR AM and Proximity AM (Anti masking) is disabled
LEDs are disabled
Proximity AMDisable
Defines the operation of the Proximity Anti Masking detection
Proximity AM Options
1) Disable (Default) 2) Enable
NOTE: Disable Proximity AM during heavy rain (if WatchOUT 315DT is not
sheltered) to prevent Proximity AM alerts.
3) 40%
4) 60%
5) 80%
6) Maximum
7) Trimmer (MW is defined
by the trimmer setting on
the PCB)
System Parameters
System: System Control
Quick Keys Parameter Default:
[1][2][36] IR AM=Tamper No
Used to determine the operation of Active IR Anti Masking detection
Yes: Active IR Anti mask detection will activate tamper alarm.
No: Active IR Anti mask detection will be regarded as trouble event.
[1][2][37] Prox AM=Tamper No
Used to determine the operation of the Proximity Anti Masking detection
Yes: Proximity Anti mask detection will activate tamper alarm.
No: Proximity Anti mask detection will be regarded as a trouble event.
16 WatchOUT 315DT Installation Manual
Diagnostics
The ProSYS enables you to test parameters that reflect the operation of the detector.
1. From the main user menu press
2. Enter the Installer code (or sub-installer) and press
[4] to access the Maintenance menu.
/ .
3. Press [9] [1] to for the BUS Zones diagnostic menu.
4. Enter the digit of the zone that you want to test and then press
/ . The system will
perform the diagnostics test and a list of test parameters will appear, as indicated in the table
below.
5. Use the keys
/ / to view the diagnostics test results.
User Menu: 4) Maintenance → 9) Diagnostic → 1) BUS Zone
Quick Keys Parameter
[4][9][1][zzz] Detector Input Voltage: Display the input voltage of the detector.
PIR 1 Level: PIR channel 1 DC level. Range 0.1v - 4v
PIR 1 Noise Level: PIR channel 1 AC level. Range 0VAC (No noise) - 4VA
PIR 2 Level: PIR channel 2 DC level. Range 0.1v - 4v
PIR 2 Noise Level: PIR channel 2 AC level. Range 0VAC (No noise) - 4VA
MW 1 Level: MW channel 1 DC level Range 0.1v - 4v
MW 1 Noise Level
: MW channel 1 AC level (0VAC (No noise) - 4VAC)
MW 2 Level: MW channel 2 DC level Range 0.1v - 4v
MW 2 Noise Level: MW channel 2 AC level (0VAC (No noise) - 4VAC
English
WatchOUT 315DT Installation Manual 17
18 WatchOUT 315DT Installation Manual
Indice Dei Contenuti
Installazione in modalità relé ............................................................................................... 20
Aggiunta e Cancellazione del WatchOUT DT ..................................................................... 31
Configurazione dei parametri del WatchOUT DT ................................................................ 32
Parametri di Sistema .............................................................................................................. 33
Italiano
Manuale di installazione WatchOUT 315DT 19
Installazione in modalità relé
Introduzione
Il rivelatore da esterno Doppia Tecnologia WatchOUT 315DT di RISCO Group è un dispositivo a
microprocessore che elabora i segnali rilevati tramite due canali all’infrarosso passivo (PIR) e due
canali a microonda (MW). Il rivelatore può funzionare come rivelatore tradizionale con uscite a
relé collegabili a qualsiasi centrale d’allarme, o come rivelatore indirizzato via BUS 485 collegato
ai sistemi ProSYS di RISCO. Quando viene collegato ai sistemi ProSYS, il rivelatore può essere
programmato e testato sia localmente che in remoto tramite tastiere LCD ProSYS e/o software di
Teleassistenza RISCO. Le istruzioni che seguono descrivono l’installazione e la configurazione
del WatchOUT 315DT sia in modalità Relé che via BUS. Per informazioni sul collegamento in
modalità BUS ProSYS, consultare il capitolo “Installazione in modalità BUS
”.
Installazione
Considerazioni per l’installazione
1m - 2.7m
(3'3" - 8'9")
Altezza di installazione: Grandangolo 15m
90° (RL300)
Se possibile, evitare di direzionare l’unità verso
oggetti in movimento (alberi ondeggianti,
cespugli, ecc.)
Note:
1. Per altezze di installazione basse, al di sotto di
1.7m ove è richiesta l’opzione di
discriminazione animali, vanno utilizzate le lenti
RL300F (muri bassi o installazione su
recinzioni).
2. La discriminazione animali (altezza
dell’animale senza limiti di peso) arriva fino a
70 cm con il rivelatore installato a 2.2m. Se
l’altezza di installazione è al di sotto di 2.2
metri la discriminazione animali si riduce
proporzionalmente. Ogni 10cm in meno
rispetto a 2.2 metri corrispondeono 10 cm in
meno di altezza dell’animale discriminato.
Per quelle installazioni vicino a strade ad intenso traffico di
veicoli o oggetti oltre l’area di rilevazione desiderata, si
5m (16')
Mantenere una distanza
di almeno 5m (16') da
oggetti in movimento
Fuori campo di
rilevazione
Assicurarsi che nessun oggetto ostruisca il
campo di rilevazione dell’unità sia per la
sezione a microonda sia per quella ad
infrarossi. Prestare attenzione alla crescita di
alberi, rami e ad eventuali altre piante che con
il tempo possono coprire l’area di rilevazione.
consiglia di regolare la sensibilità della microonda (MW) e/o
inclinare il rivelatore verso il basso.
Nota:
Inclinando il rivelatore verso il basso è possibile che la funzione di
immunità agli animali si riduca.
Per una migliore rivelazione
selezionare una posizione di
installazione in modo che
l’eventuale intruso attraversi
l’area di copertura del rivelatore
con una traiettoria di circa 45°
rispetto allo stesso.
NOTA: Con la funzione ‘Antiavvicinamento’ abilitata e il sensore installato a cielo aperto, si
raccomanda di creare un riparo sopra di esso per evitare allarmi impropri in presenza di forti
pioggie o alternativamente disabilitare la funzione.
20 Manuale di installazione WatchOUT 315DT
Installazione a parete
Nota:
I numeri di riferimento dei fori a sfondare per
l’installazione sono marcati sulla base posteriore.
1. Aprire il coperchio frontale del WatchOUT.
(Svitare C1, figura 1).
2. Sganciare la base interna (svitare I1, fig. 2).
3. Selezionare l’altezza di installazione come
segue:
Installazione piana
Aprire i fori a sfondare della base esterna (fig. 3)
• B1 - B4: Fori a sfondare per installazione
a parete.
• T1: Foro a sfondare per il tamper
antirimozione
• W2 / W3: Fori a sfondare per il
passaggio cavi
Installazione angolare di 45°
(installazione a sinistra)
a. Aprire i fori a sfondare della base esterna
(fig. 3)
• L1, L2 : Fori a sfondare per lato sinistro
• T3: Foro a sfondare per tamper lato
sinistro
• W5 / W6: Fori a sfondare per passaggio
cavi
b. Rimuovere la molla del tamper
c. Sostituire la staffa (Item 1) con l’altra fornita
(Item 2).
Item 1
d. Inserire la leva B del tamper in T5 e T3 e
stringere la vite A (figura 3)
4. Inserire I cavi esterni attraverso la base
esterna W2, W3 (Installazione piana) o W5,
W6 (Installazione a sinistra) (figura 3).
5. Fissare la base esterna alla parete.
6. Inserire i cavi esterni e i cavi del tamper
attraverso la base interna. (figura 4).
7. Fissare la base interna a quella esterna
(bloccare I1, figura 2).
8. Chiudere il coperchio frontale (bloccare C1,
figura 1) dopo aver cablato l’unità e
predisposto i microinterruttori.
9. Effettuare le prove di copertura.
Item 2
Figura 1
Figura 3
Leva del
Tamper
B
A
Figura 4
Figura 2
C1
T1
T3
L1
B1
W5
W6
W3
L2
B4
l1
Italiano
T5
T6
T4
T2
R1
(non visibile )
B2
W9
W2
R2
)
(non visibile
B3
Manuale di installazione WatchOUT 315DT 21
Nota:
Per installazioni a 45° lato destro usare le equivalenti predisposizioni sulla base esterna come segue:
Descrizione fori a sfondare Sinistra Destra
Fori a sfondare per il fissaggio della base L1, L2 R1, R2
Foro a sfondare per la molla del tamper T1,T3 T2,T4
Punto di fissaggio vite tamper T5 T6
Fori a sfondare per passaggio cavi W5, W6 W7, W8
Modifica della posizione del tamper antirimozione
Di fabbrica il tamper antirimozione è fissato sul lato
destro della base interna (Vista Posteriore). Se si
desidera spostarlo nella parte sinistra, procedere come
segue (figura 5):
1. Svitare la vite tamper 1 per rimuoverlo dalla posiz. 7.
2. Assicurarsi che la molla 2 del tamper resti posizionata
sulla base 4 del tamper.
3. Assicurarsi che la staffa 3 del tamper resti tra 2 e 4.
4. Fissare la vite 1 del tamper in 3 sulla predisposizione 6.
Figura 5
1
2
Predisposizione
tamper a sinistra
6
3
4
Predisposizione
tamper a destra
7
5
Note:
1. Verificare che si senta un "Click" quando la molla del tamper viene spinta contro il muro.
2. Per l’installazione su palo il tamper può essere spostato nella parte inferiore destra della base interna.
Cablaggio morsettiera
12Vcc
+-
ALARM
FREE
YEL
TAMPER
FREE
GREEN
LEDs
AM
ENABL
DUST TEST
SET/
UNSET
+,ALARM
FREE YEL
TAMPER
FREE
GREEN
AM
N.C
12 Vcc
Relé N.C, 24Vcc, 0.1A
Questo è un morsetto libero per il posizionamento di cavi o resistenze di fine linea.
Relé N.C, 24Vcc, 0.1A
Questo morsetto è un morsetto libero per il posizionamento di cavi o resistenze di
fine linea.
L’uscita a relè N.C. (24Vcc; 0,1A) dell’AM, se attiva indica una condizione di
N.C
SCHEDA ELETTRONICA - WatchOUT DT
Mascheramento o una qualsiasi anomalia del rivelatore (questa uscita NON
segnala l’anomalia “Lenti Sporche”).
L’antiprossimità permette di ricevere un segnale di allarme utilizzando entrambi i
canali microonda, prima che il rilevatore venga manomesso o mascherato.
Nota:
Se il microinterruttore DIP8 è in ON, questo relè si attiva momentaneamente alla rilevazione
dell’avvicinamento.
LED
ENABLE
Ingresso usato per controllare da remoto i LED quando il microint. 1 è in ON.
LED abilitati: Tensione +12V presente o morsetto non connesso
LED disabilitati: 0V presente all’ingresso
DUST Uscita N.O. a collettore aperto, massimo 70 mA. Indica che le Lenti dell’unità sono
sporche ed è necessario pulirle.
22 Manuale di installazione WatchOUT 315DT
TEST
fOff
SET/
UNSET
Usato per testare il rivelatore da remoto applicando 0V a questo morsetto.
Test OK: Il relé di allarme si attiva per qualche secondo.
Guasto: L’uscita AM viene attivata.
Questo ingresso permette di abilitare o disabilitare l’antimascheramento e
l’accensione dei LED quando il sistema è inserito (Set) o disinserito (Unset).
A sistema inserito questa funzione disabilita i LED (evitando che un intruso possa
verificare che il sistema ha generato un allarme) e l’antimascheramento.
Stato del sistemaStato ingressoUscita AMLED
Set (Inserito)0VOf
Unset (Disins.)12V o nessuna connessioneOn*On**
* Microint. 7 ON (Antimascheramento abilitato)
Microint. 1 ON (LED abilitati) e ingresso con tensione +12V o nessuna connessione)
**
Italiano
Predisposizione Microinterruttori
O
N
O
3
2
1
7
6
5
4
8
Impostazioni di
Fabbrica
MIC 1: Predisposizione LED
On: LED abilitati
Off: LED disabilitati
MIC 2-3: Sensibilità di rilevazione
Sensibilità MIC2 MIC3
Bassa Off Off
Media Off On
Normale
On Off
(Default)
Massima * On On
* Con sensibilità massima, la SRT è
disabilitata per avere la massima sensibilità
MIC 4: Sensibilità Anti-Mascheramento
On: Alta
Off: Bassa
MIC 5: Ottica Rivelatore
On: Barriera / Lunga portata
Off: Grandangolo
MIC 6: LED Rosso o 3 LED
On: Solo LED rosso
Off: 3 LED
MIC 7: Antimascheramento
On: Abilitato
Off: Disabilitato
MIC 8: Antiavvicinamento
On: Abilitato
Off: Disabilitato
Regolazione microonda
Regolare la portata della microonda utilizzando il potenziometro
posizionato sulla scheda elettronica del rivelatore.
Prova di movimento
Dopo 2 minuti dall’alimentazione del sensore, effettuare una prova di
movimento all’interno dell’area protetta e verificare il buon
funzionamento e la copertura del rivelatore.
Per regolare la copertura del sensore muovere la scheda elettronica
interna del sensore per la predisposizione appropriata in funzione
dell’altezza di installazione desiderata (1.0m, 1.5m, 2.2m, 2.7m)
come stampato nella parte inferiore sinistra della scheda elettronica o
utilizzare lo snodo standard.
Per ridurre l’area di copertura spostare in alto la scheda elettronica o,
se utilizzato, muovere lo snodo verso il basso.
MIN
MAX
PCB
1.00M
1.50M
2.20M
2.70M
Manuale di installazione WatchOUT 315DT 23
Indicatori LED
LED Stato Descrizione
GIALLO
VERDE
ROSSO
TUTTI I
LED
Note:
1. Il microinterruttore 1 deve essere posizionato su ON per abilitare i LED.
2. Solo un LED alla volta può illuminarsi. Per esempio, nel caso di attivazione di entrambe le tecnologie PIR e
MW, o il LED giallo o quello verde si illumina (il primo che rileva), seguito poi dal LED rosso di allarme.
3. Per prevenire che malintenzionati riescano ad analizzare il momento di attivazione delle tecnologie di
rilevazione quali PIR, MW, AM e Antiavvicinamento, impostare il microinterruttore 6 in ON (SW1). In questo
modo si accenderà solo il LED rosso.
Microinterruttore Modalità Relé / BUS
Il microinterruttore J-BUS, situato sulla scheda tra i LED rosso e
verde, viene usato per configurare la modalità di funzionamento
del rivelatore (vedi figura al lato).
Acceso Indica rilevazione PIR
Lampeggiante Indica Antimascheramento sull'IR Attivo (AM)
Acceso Indica rilevazione MW
Lampeggiante Indica Antiavvicinamento della sezione MW (AM)
Acceso Indica ALLARME
Lampeggiante Indica una anomalia di comunicazione con la ProSYS
(solo modalità BUS)
Lampeggiante (uno alla
volta)
Inizializzazione dell’unità all’accensione
Modalità
Relé
N
Modalità
BUS
O
N
O
Installazione dello snodo standard
Il kit fornito con il rivelatore da esterno WatchOUT include uno snodo standard per renderne più
flessibile l’installazione. Leggere le istruzioni seguenti per installare il rivelatore con questo snodo.
1. Aprire il coperchio frontale (Allentare C1, figura 1).
2. Sganciare la base interna (Svitare I1, figura 2).
3. Aprire i fori a sfondare della base esterna (figura 6, Dettaglio B)
• W1: Passaggio cavi
• S1,S2: Fori a sfondare per fissare la base esterna allo snodo standard
• S3: Predisposizioni per le viti di fissaggio della base esterna
4. Sullo snodo aprire le predisposizioni per il passaggio cavi S2, S7 o S9 (figura 6, Dettaglio A).
5. Rimuovere il tamper antirimozione dalla base interna (consultare paragrafo "Modifica della posizione
del tamper antirimozione") e collegarlo a S5 (figura 6, Dettaglio A) sullo snodo standard..
Nota:
Accertarsi che il marchio UP è presente nella parte frontale superiore dell snodo.
6. Selezionare le opzioni di installazione di seguito descritte:
Installazione a parete
a. Inserire il cavo esterno attraverso le predisposizioni S2, S7 o S9 (incluso i cavi del tamper)
ed estrarlo facendolo passare attraverso il passaggio cavi dello snodo
(figura 6, Dettaglio B).
b. Fissare lo snodo alla parete tramite i fori S1, S3, S6 ed S8.
24 Manuale di installazione WatchOUT 315DT
Installazione per tubo elettrico
(utilizzare l’adattatore metallico per tubo elettrico - CSMA, figura 6, Dettaglio A)
Dettaglio ADettaglio B
Fori
molla
tamper
CSMA
M1
M2
M3
M4
Ø 16 mm
Ø 21 mm
Nota:
Il CSMA è richiesto quando il cablaggio viene effettuato tramite una tubazione elettrica esterna alla parete.
Questo accessorio va ordinato separatamente con il codice RA300SC0000A.
c. Scegliere l’orientamento del CMSA in riferimento al diametro richiesto: 16mm (0.63 in.) o
21mm (0.83 in.).
d. Inserire il tubo elettrico nel CSMA.
e. Fissare il CSMA alla parete tramite i fori M1 e M4.
f. Inserire i cavi esterni e i cavi del tamper che arrivano dal tubo elettrico facendoli passare
tramite il passaggio cavi dello snodo (Figura 6, Dettaglio A).
g. Fissare lo snodo alla parete tramite i fori S1, S3, S6 ed S8.
Nota:
La molla del tamper S5 (Figura 7) deve essere a contatto della parete tramite gli appositi fori M2 o M3 del
CSMA. Assicurarsi di sentire il "Click" dell’interruttore tamper fissando il dispositivo alla parete.
7. Inserire i cavi del tamper e i cavi esterni che arrivano dallo snodo standard facendoli passare
tramite la predisposizione W1 della base esterna (Figura 7, Dettaglio B).
8. Unire la base esterna allo snodo utilizzando le apposite linguette ad incastro (Figura 7).
S9
S8
Passaggio
cavi dello
snodo
Snodo Standard
S2
S1
S7 S6
S3
(
vedi Dettaglio C
Figura 6
S4
S5
Tamper
Linguette
W1
S1
)
S2
S3
Dettaglio C
Italiano
Manuale di installazione WatchOUT 315DT 25
Figura 7
Nota:
Per fissare la base del rivelatore allo snodo non usare la vite che blocca il fermo posteriore dello snodo. Questa
vite non va usata poichè serve solo per il blocco dello snodo una volta orientato come desiderato.
9. Fissare la base esterna allo snodo con due viti tramite le predisposizioni S1 e S2 (figura 7).
10. Inserire nello snodo standard la vite (fornita) di fissaggio ad angolo facendola passare dalla
base esterna attraverso il foro a sfondare S3 (figura 7).
11. Orientare orizzontalmente e verticalmente lo snodo fino ad ottenere la posizione desiderata e
poi stringere la vite di blocco orientamento snodo.
12. Infilare la base interna nella base esterna ed inserire tutti i cavi attraverso la base interna.
13. Fissare la base interna a quella esterna (fissare I1, figura 2).
14. Per regolare lo snodo standard quando viene installata la scheda elettronica (figura 7):
a. Spostare la gomma nera situata sulla scheda elettronica sotto al LED rosso (quanto
basta per raggiungere la vite di blocco dello snodo).
b. Utilizzare un cacciavite per svitare la vite di blocco (vedi figura 8).
c. Orientare orizzontalmente e verticalmente lo snodo fino ad ottenere la posizione
desiderata.
d. Stringere la vite di blocco orientamento snodo.
Nota:
Quando i punti marcati delle due parti mobili sono allineati (figura 8), lo snodo standard si trova in posizione 0°.
Ogni “click” verticale da questa posizione corrisponde ad un incremento / decremento di 5°.
15. Chiudere il coperchio frontale (fissare C1, figura 1) e proseguire con la prova di movimento
per verificare l’area di copertura del rivelatore.
Nota:
La vite deve passare attraverso la base esterna ed essere fissata allo snodo.
26 Manuale di installazione WatchOUT 315DT
Figura 8
Sostituzione delle Lenti
1. Nella parte interna del coperchio frontale svitare le sei viti che mantengono il supporto lenti.
2. Per sganciare il supporto delle Lenti effettuare una leggera pressione sulle lenti dalla parte
anteriore del coperchio.
3. Sganciare le Lenti dal supporto facendo leggermente leva sulle clip laterali delle Lenti.
4. Sostituire le Lenti. Inserire le 4 clip delle Lenti negli appositi fori del supporto.
5. Inserire il supporto delle Lenti nel coperchio frontale del rivelatore. Prestare particolare
attenzione a riposizionare il supporto esattamente sopra la guarnizione di gomma, verificando
che anche la lente utilizzata per la protezione verticale dell’unità abbia la guarnizione
correttamente posizionata.
6. Fissare il supporto tramite le 6 viti.
Viti di fissaggio
supporto
Clip di
blocco Lenti
Italiano
Fori per clip
di blocco
Lenti
Supporto Lenti
Guarnizione
Vite di
fissaggio
coperchio
frontale
Manuale di installazione WatchOUT 315DT 27
Tipologie di Lenti
Grandangolo (RL300) /
Discriminazione animali –
Installazione bassa (RL300F) :
Vista dall’alto
11
9
7
5
3
1
0
1
3
5
7
9
11
2468100121415
Altezza di
installazione
tipica 2.2m
Discriminazione animali – Installazione bassa
Altezza di
90°
installazione
tipica 1.5m
Nota:
L’immunità agli animali del rivelatore (altezza di un animale, nessuna limitazione di peso), è fino a 70 cm,
quando viene installato il rivelatore a 2.2m. Se l’installazione è al di sotto di questa altezza, l’immunità agli
animali diminuisce proporzionalmente; ogni 10 cm di diminuzione dell’altezza di installazione fa si che
l’immunità agli animali diminuisca di 10 cm.
Lenti Lunga Portata (RL300LR):
Vista dall’alto
1
0
1
Metri
24681001214161820 2223
Lenti Lunga Portata (RL300LR):
Altezza di
install azione
tipica 2.2m
Metri
3
1
0
Vista laterale
246810012141618202223
Grandangolo (RL300):
Vista laterale
3
1
0
Metri
2468100121415
(RL300F) :
Vista laterale
2
1
0
Metri
2468100121415
Lenti Barriera (RL300B):
Metri
1
0
1
5°
Lenti Barriera (RL300B):
Altezza di
installazione
tipica 2.2m
Vista dall’alto
2468100121415
Vista laterale
3
1
0
Metri
2468100121415
5°
28 Manuale di installazione WatchOUT 315DT
Caratteristiche Tecniche
Elettriche
Assorbimento di corrente 30mA a 12 Vcc (a riposo)
Requisiti di alimentazione 9 -16 Vcc
Contatti di Allarme 24 Vcc, 0.1 A
Contatti Antimascheramento 24 Vcc, 0.1 A
Uscita “Lenti Sporche” Collettore aperto 70mA max.
Fisiche
Dimensioni LxWxD 230 x 123 x 123mm
Peso 0.632 Kg
Ambientali
Immunità RF Conforme alla normativa EN50130-4
Temperatura di
Funzionamento/Stoccaggio
* La tecnologia di rilevazione PIR è limitata in condizioni ambientali critiche.
42mA a 12 Vcc (max. con LED illuminati)
Da -30°C a 60°C
Informazioni per l’ordine
Unità standard
Modello Descrizione
WatchOUT 315DT WatchOUT DT + snodo
Nota:
Ogni rivelatore include lo snodo standard e 3 Lenti:
Discriminazione animali per installazioni basse fino a 1.7m (RL300F), Lunga portata (RL300R) e Barriera
(RL300B). (I codici prodotto sono marcati sulle Lenti)
Kit Accessori
Modello DescrizionePeso
RA300B kit snodo per protezione a barriera 0.1 Kg
RA300P kit adattatore da palo 0.25 Kg
RA300C kit adattatore per tubo elettrico 0.6 Kg
RA300HS contenitore demo WatchOUT - RA300SC adattatore metallico per tubo elettrico per il montaggio con
snodo
Opzioni Telecamera
Modello Descrizione
WatchOUT VC1 coperchio WatchOUT comprensivo di staffa per telecamera
WatchOUT VC017 kit telecamera grandangolo
WatchOUT VC053 kit telecamera lunga portata
WatchOUT VCPS alimetatore 220V per telecamera
WatchOUT VCPS alimentatore 120V per telecamera
1Kg
Italiano
Manuale di installazione WatchOUT 315DT 29
Installazione in modalità BUS
Introduzione
Le informazioni di questa sezione fanno riferimento all’installazione del WatchOUT 315DT
collegato via BUS ai sistemi ProSYS di RISCO. Si possono installare fino a 32 rivelatori connessi
al BUS RS-485 della centrale ProSYS risparmiando così tempo per la stesura dei cavi e
ottenendo il vantaggio di poter configurare e testare questi rivelatori sia elettricamente che
funzionalmente, in locale o da postazione remota.
Cablaggio morsettiera
+,-
YELLOW
GREEN
TAMPER
LED
ENABLE
Nota:
I morsetti non descritti in tabella non vengono utilizzati nella modalità di connessione BUS.
Tamper Antiapertura e Antirimozione
BUS
ProS YS
COM
AU X
BLK
RED
Utilizzati per l’alimentazione 12Vcc del rivelatore. Collegare questi morsetti (+)
e (–), rispettivamente ai morsetti AUX RED e COM BLK della centrale ProSYS.
Usato per la comunicazione dei dati via bus ProSYS. Collegare questo
morsetto al BUS YEL della ProSYS.
Usato per la comunicazione dei dati via bus ProSYS. Collegare questo
morsetto al BUS GRN della ProSYS.
Usato per il cablaggio del circuito antimanomissione. Consultare gli schemi che
seguono.
Usato per il cablaggio del circuito antimanomissione. Consultare gli schemi che
seguono.
Solo Tamper Antiapertura
Modalità BUS
Cablaggio tamper
Antiapertura e Antirimozione
Cortocircuitare
BUS
YEL
GRN
TAMPER ANTIRIMOZIONE(N.C)
BUS
ProSY S
COM
AUX
BUS
BLK
RED
YEL
GRN
Cortocircuitare
Modalità BUS
Cablaggio Tamper
Antiapertura
+-
ALARM
TAMPER
GRE EN
FREE
FREE
YEL
LEDs
AM
ENA BLE
DUST TEST
UNS ET
SET/
+-
ALARM
TAMPER
FREE
YEL
GREEN
Tamper Antiapertura ad un Ingresso di Zona
BUS
ProSYS
COM
AUX
BLK
RED
+-
Ingresso
Zona
BUS
YEL
GRN
ALARM
FREE
YEL
COM
Z1Z2
TAMPER
Modalità BUS
Tamper Antiapertura tramite
ingresso di zona
Cortocircuitare
GR EE N
FREE
LEDs
AM
DUST TEST
ENA BLE
UNSE T
SET/
30 Manuale di installazione WatchOUT 315DT
FREE
LEDs
AM
ENAB LE
DUS T TES T
UNS ET
SET/
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.