RECOGNIZE THIS SYMBOL
AS AN INDICATION OF
IMPORTANT SAFETY
INFORMATION
WARNING
THESE INSTRUCTIONS
ARE INTENDED AS AN AID
TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR
PROPER INSTALLATION,
ADJUSTMENT, AND
OPERA TION OF THIS
UNIT . READ THESE
INSTRUCTIONS
THOROUGHLY
BEFORE ATTEMPTING
INSTALLATION OR
OPERATION. FAILURE
TO FOLLO W THESE
INSTRUCTIONS MAY
RESULT IN IMPROPER
INSTALLATION,
ADJUSTMENT, SERVICE,
OR MAINTENANCE
POSSIBLY RESULTING IN
FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE,
PERSONAL INJURY, OR
DEATH.
AIR COOLED
CONDENSING UNITS
INSTALLATION INSTRUCTIONS
RA14 MODEL SERIES – 14 SEER
FEATURING INDUSTRY STANDARD
R-410A REFRIGERANT
Do not destroy this manual.
Please read carefully
and keep in a safe place
for future reference by a
serviceman.
[ ] indicates metric conversions.
92-104921-01-01 (11/14) Printed in USA
Page 2
CONTENTS
Important
Safety Information ��������������������������������������������� 3
General Information ����������������������������������������4-6
Checking Product Received ����������������������������������������4
Contents
Application �������������������������������������������������������������������4
Electrical and Physical Data �����������������������������������������5
Specifications ���������������������������������������������������������������6
Proper Installation ��������������������������������������������������������6
Corrosive Environment �������������������������������������������������7
For Units With
Space Limitations ���������������������������������������������������������8
Customer Satisfaction Issues ��������������������������������������8
Unit Mounting ���������������������������������������������������������������8
Factory-Preferred
Tie-Down Method���������������������������������������������������������8
Tools and Refrigerant
Tools Required for Installing and
Servicing R-410A Models ��������������������������������������������9
Specifications of R-410A ���������������������������������������������9
Quick-Reference
Guide for R-410A ���������������������������������������������������������9
Replacement Units �������������������������������������������10
Indoor Coil ��������������������������������������������������������10
Charging Units
With R-410A Refrigerant ��������������������������������������������25
Confirm ID Airflow
and Coils Are Clean ���������������������������������������������������25
Measurement Device Setup ��������������������������������������� 25
Charging by Weight ���������������������������������������������������� 25
Gross Charging by Pressures ������������������������������������ 26
Final Charge by Subcooling ��������������������������������������� 26
Finishing Up Installation ��������������������������������������������� 27
Components and Controls �������������������������� 28-29
Time-Delay Control ����������������������������������������������������29
Hard Start Components ���������������������������������������������29
Low Ambient Control (LAC) ���������������������������������������29
qualified, licensed service personnel for proper
installation, adjustment, and operation of this
unit� Read these instructions thoroughly before
attempting installation or operation� Failure to
follow these instructions may result in improper
installation, adjustment, service, or maintenance
possibly resulting in fire, electrical shock,
property damage, personal injury, or death.
• The unit must be permanently grounded. Failure
to do so can cause electrical shock resulting in
severe personal injury or death.
• Turn off electric power at the fuse box or service
panel before making any electrical connections.
• Complete the ground connection before making
line voltage connections. Failure to do so can
result in electrical shock, severe personal injury,
or death.
• Disconnect all power to unit before starting
maintenance. Failure to do so can cause
electrical shock resulting in severe personal
injury or death.
• Never assume the unit is properly wired and/or
grounded. Always test the unit cabinet with a
noncontact voltage detector available at most
electrical supply houses or home centers before
removing access panels or coming into contact
with the unit cabinet.
• Do not use oxygen to purge lines or pressurize
system for leak test. Oxygen reacts violently with
oil, which can cause an explosion resulting in
severe personal injury or death.
• The top of the scroll compressor shell is hot�
Touching the compressor top may result in serious
personal injury�
• The manufacturer’s warranty does not cover
any damage or defect to the unit caused by the
attachment or use of any components, accessories,
or devices (other than those authorized by the
manufacturer) into, onto, or in conjunction with
the heat pump� You should be aware that the
use of unauthorized components, accessories,
or devices may adversely affect the operation
of the heat pump and may also endanger life
and property. The manufacturer disclaims any
responsibility for such loss or injury resulting
from the use of such unauthorized components,
accessories, or devices�
CAUTIONS:
• R-410A systems operate at approximately 60%
higher pressures (1�6 times) than R-22 systems� Do
not use R-22 service equipment or components on
R-410A equipment� Use appropriate care when using
this refrigerant� Failure to exercise care may result in
equipment damage or personal injury�
• Only match this outdoor unit with a matched indoor
coil or air handler approved for use with this outdoor
unit per the unit manufacturer’s specification sheet�
The use of unmatched coils or air handler will likely
result in a charge imbalance between the cooling
and heating modes which can cause unsatisfactory
operation including a high-pressure switch lockout
condition�
• Only use indoor coils approved for use on R-410A
systems� An R-22 coil will have a TXV or fixed
restrictor device that is not designed to operate
properly in an R-410A system and will result in
serious operational issues� The R-22 coil could also
contain mineral oil which is incompatible with the
POE oil used in R-410A systems and could result in
reliability issues with the compressor and TXVs�
• When coil is installed over a finished ceiling and/or
living area, it is required that a secondary sheet metal
condensate pan be constructed and installed under
the entire unit� Failure to do so can result in property
damage�
• The compressor has an internal overload protector�
Under some conditions, it can take up to 2 hours for
this overload to reset� Make sure overload has had
time to reset before condemning the compressor�
Safety
3
Page 4
GENERAL INFORMATION
WARNING:
Improper installation, or installation not made in
accordance with these instructions, can result
in unsatisfactory operation and/or dangerous
conditions and can cause the related warranty
not to apply.
The condensing unit is designed to operate with
standard 24 VAC thermostats and air handlers or
gas furnaces�
This installation instruction manual contains
complete instructions for installation and setup
General Information
using conventional 24 VAC controls� Please refer
to the manufacturer’s specification sheets for
complete performance data, thermostat, and
accessory listings�
The information contained in this manual has
been prepared to assist in the proper installation,
operation, and maintenance of the air conditioning
system�
Read this manual and any instructions packaged
with separate equipment required to make up the
system prior to installation� Homeowner should
retain this manual for future reference�
To achieve optimum efficiency and capacity,
the matching indoor cooling coils listed in the
manufacturer’s specification sheet should be used�
Checking Product Received
Upon receiving unit, inspect it for any shipping
damage� Claims for damage, either apparent or
concealed, should be filed immediately with the
shipping company� Check model number, electrical
characteristics, and accessories to determine if they
are correct� Check system components (indoor coil,
outdoor unit, air handler/furnace, etc�) to make sure
they are properly matched�
Application
Before specifying any air conditioning equipment,
a survey of the structure and a heat gain
calculation must be made� A cooling heat gain
calculation determines the amount of heat needed
to be removed� A heat gain calculation also
calculates the extra heat load caused by sunlight
and by humidity removal� These factors must be
considered before selecting an air conditioning
system to provide year-round comfort� The Air
Conditioning Contractors of America (ACCA)
J Manual method of load calculation is one
recognized procedure for determining the heating
and cooling load�
After the proper equipment combination has
been selected, satisfying both sensible and
latent requirements, the system must be properly
installed� Only then can the unit provide the
comfort it was designed to provide�
There are several factors that installers must
consider�
• Outdoor unit location
• Indoor unit blower speed and airflow
• Proper equipment evacuation
• Supply and return air duct design and sizing
• Refrigerant charge
• System air balancing
• Diffuser and return air grille location and sizing
AIR INLET LOUVERS ALLOW
6" [152 mm] OF CLEARANCE ALL SIDES
12" [305 mm] RECOMMENDED
ALLOW 60" [1524mm] OF
CLEARANCE
SERVICE PANELS/
INLET CONNECTIONS /
HIGH & LOW VOLTAGE
ACCESS ALLOW
24" [610 mm] OF
CLEARANCE
CONDENSING UNIT MODEL
LENGTH “H” (INCHES)
LENGTH “L” (INCHES)
WIDTH “W” (INCHES)
Proper Installation
Proper sizing and installation of this equipment is
critical to achieve optimal performance� Use the
information in this Installation Instruction Manual
and reference the applicable manufacturer’s
specification sheet when installing this product�
IMPORTANT: This product has been
designed and manufactured to meet ENERGY
STAR criteria for energy efficiency when matched
with appropriate indoor components� However,
proper refrigerant charge and proper airflow are
critical to achieve rated capacity and efficiency�
Installation of this product should follow the
manufacturer’s refrigerant charging and airflow
instructions� Failure to confirm proper charge
and airflow may reduce energy efficiency and
shorten equipment life�
RA14
0
18, 24
25
19"19"29"23"33"
29.75
351⁄2"401⁄2"443⁄8"443⁄8"443⁄8"
29.75
243⁄4"
18
0
30
27
29.75
29.75
275⁄8"
36, 42
27
33.75
33.75
49043/037060
48
31
33.75
33.75
311⁄2"311⁄2"311⁄2"
35.75
35.75
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
• INDOOR THERMOSTAT
60
35
6
Page 7
Choosing a Location
INSTALLATION
IMPORTANT:
national building codes and ordinances for special
installation requirements� Following location
information will provide longer life and simplified
servicing of the outdoor unit�
Consult local and
NOTICE: These units must be installed
outdoors� No ductwork can be attached, or
other modifications made, to the discharge grille�
Modifications will affect performance or operation�
Operational Issues
IMPORTANT: Locate the unit
in a manner that will not prevent, impair, or
compromise the performance of other equipment
installed in proximity to the unit� Maintain all
required minimum distances to gas and electric
meters, dryer vents, and exhaust and inlet
openings� In the absence of national codes or
manufacturers’ recommendations, local code
recommendations and requirements will take
precedence�
• Refrigerant piping and wiring should be properly
sized and kept as short as possible to avoid
capacity losses and increased operating costs�
• Locate the unit where water runoff will not create
a problem with the equipment� Position the unit
away from the drip edge of the roof whenever
possible� Units are weatherized, but can be
affected by the following:
• Water pouring into the unit from the junction
of rooflines, without protective guttering�
Large volumes of water entering the unit while
in operation can impact fan blade or motor
life, and coil damage may occur if moisture
cannot drain from the unit under freezing
conditions�
• Closely follow the clearance recommendations
on page 8�
• 24" [61.0 cm] to the service panel access
• 60" [152.4 cm] above fan discharge (unit top)
to prevent recirculation
• 6" [15.2 cm] to coil grille air inlets
with 12" [30.5 cm] minimum recommended
Corrosive Environment
The metal parts of this unit may be subject to
rust or deterioration if exposed to a corrosive
environment� This oxidation could shorten the
equipment’s useful life�
Corrosive elements include, but are not limited to,
salt spray, fog or mist in seacoast areas, sulphur or
chlorine from lawn watering systems, and various
chemical contaminants from industries such as
paper mills and petroleum refineries�
If the unit is to be installed in an area where
contaminants are likely to be a problem, special
attention should be given to the equipment
location and exposure�
• Avoid having lawn sprinkler heads spray directly
on the unit cabinet�
• In coastal areas, locate the unit on the side of
the building away from the waterfront�
• Shielding provided by a fence or shrubs may
give some protection, but cannot violate
minimum airflow and service access clearances�
• Elevating the unit off its slab or base enough to
allow air circulation will help avoid holding water
against the base pan�
WARNING: Disconnect all power
to unit before starting maintenance� Failure to do
so can cause electrical shock resulting in severe
personal injury or death�
Regular maintenance will reduce the buildup of
contaminants and help to protect the unit’s finish�
• Frequent washing of the cabinet, fan blade, and
coil with fresh water will remove most of the salt
or other contaminants that build up on the unit�
• Regular cleaning and waxing of the cabinet with
a good automobile polish will provide some
protection�
• A good liquid cleaner may be used several times
a year to remove matter that will not wash off
with water�
Location
7
Page 8
INSTALLATION
6” MIN. [152mm] FOR 1.5 & 2 TON
9”MIN [229mm] FOR 2.5 – 5 TON
24” [610mm]
SERVICE PANELS/INLET CONNECTIONS/
HIGH & LOW VOLTAGE ACCESS
ALLOW 24” [610 mm] OF CLEARANCE
ALLOW 60” [1524 mm]
OF CLEARANCE
AIR INLET LOUVERS ALLOW
6” [152 mm] Min. OF
CLEARANCE ALL SIDES
12” [305 mm] RECOMMENDED
ST-A1226-04-00
Choosing a Location (cont�)
Location
For Units With Space
Limitations
In the event that a space limitation exists, we will
permit the following clearances:
Single-Unit Applications: Side clearances below 6"
[15.2 cm] will reduce unit capacity and efficiency.
Do not reduce the 60" [152.4 cm] discharge or the
24" [61.0 cm] service clearances.
Multiple-Unit Applications: When multiple
condenser grille sides are aligned, a 6" [15.2
cm] clearance is recommended for 1.5 and 2
ton models and 9" [22.9 cm] for 2.5 ton to 5 ton
models� Two combined clearances below the
minimum will reduce capacity and efficiency� Do
not reduce the 60" [152.4 cm] discharge or 24"
[61.0 cm] service clearances.
• If installing a unit on a flat roof, use 4" x 4"
[10.2 cm x 10.2 cm] or equivalent stringers
positioned to distribute unit weight evenly and
prevent noise and vibration�
Factory-Preferred Tie-Down
Method for High Wind or
Seismic Loads
IMPORTANT: The manufacturer-
approved/recommended method is a guide to
securing equipment for wind and seismic loads�
Other methods might provide the same result, but
the manufacturer method is the only one endorsed
by the manufacturer for securing equipment where
wind or earthquake damage can occur� Additional
information is available in the PTS (Product
Technical Support) section of the manufacturer’s
Web sites MyRheem�com or MyRuud�com and
can be found as a listing under each outdoor
model� If you do not have access to this site, your
distributor can offer assistance�
Customer Satisfaction Issues
• The unit should be located away from the living,
sleeping, and recreational spaces of the owner
and those spaces on adjoining property�
• To prevent noise transmission, the mounting pad
for the outdoor unit should not be connected to
the structure and should be located a sufficient
distance above grade to prevent ground water
from entering the unit�
Unit Mounting
WARNING: Secure an elevated unit
and its elevating stand in order to prevent tipping�
Failure to do so may result in severe personal
injury or death�
8
Page 9
Tools and Refrigerant
Ambient and Tube
Thermometers
Manifold
Gauge
Set
Brazing
Rods
TorchNitrogen
Reclaimer
Recovery
Cylinders
Allen Wrench
Crescent Wrench
INSTALLATION
Tools Required for Installing
and Servicing R-410A Models
Manifold Sets:
– Up to 800 PSIG High-Side
– Up to 250 PSIG Low-Side
– 550 PSIG Low-Side Retard
Manifold Hoses:
– Service Pressure Rating of 800 PSIG
Recovery Cylinders:
– 400 PSIG Pressure Rating
– Dept� of Transportation 4BA400 or BW400
CAUTION: R-410A systems operate
at higher pressures than R-22 systems� Do not
use R-22 service equipment or components on
R-410A equipment�
Specifications of R-410A
Application: R-410A is not a drop-in
replacement for R-22� Equipment designs must
accommodate its higher pressures� It cannot be
retrofitted into R-22 heat pumps�
Physical Properties: R-410A has an atmospheric
boiling point of -62.9°F [-52.7°C] and its saturation
pressure at 77°F [25°C] is 224.5 psig.
Composition: R-410A is a near-azeotropic
mixture of 50% by weight difluoromethane (HFC-
32) and 50% by weight pentafluoroethane (HFC-
125)�
Pressure: The pressure of R-410A is
approximately 60% (1�6 times) greater than
R-22� Recovery and recycle equipment, pumps,
hoses, and the like must have design pressure
ratings appropriate for R-410A� Manifold sets
need to range up to 800 psig high-side and 250
psig low-side with a 550 psig low-side retard.
Hoses need to have a service pressure rating of
800 psig. Recovery cylinders need to have a 400
psig service pressure rating, DOT 4BA400 or DOT
BW400.
Combustibility: At pressures above 1
atmosphere, a mixture of R-410A and air can
become combustible� R-410A and air should
never be mixed in tanks or supply lines or
be allowed to accumulate in storage tanks�
Leak checking should never be done with a
mixture of R-410A and air� Leak-checking can
be performed safely with nitrogen or a mixture of
R-410A and nitrogen�
Quick-Reference Guide For
R-410A
• R-410A refrigerant operates at approximately
60% higher pressure (1�6 times) than R-22�
Ensure that servicing equipment is designed to
operate with R-410A�
• R-410A refrigerant cylinders are light rose in
color�
• R-410A, as with other HFCs, is only compatible
with POE oils�
• Vacuum pumps will not remove moisture from
POE oil used in R-410A systems�
• R-410A systems are to be charged with liquid
refrigerants� Prior to March 1999, R-410A
refrigerant cylinders had a dip tube� These
cylinders should be kept upright for equipment
charging� Post-March 1999 cylinders do not
have a dip tube and should be inverted to ensure
liquid charging of the equipment�
• Do not install a suction line filter drier in the
liquid line�
• A factory-approved biflow liquid line filter drier
is shipped with every unit and must be installed
in the liquid line at the time of installation� Only
manufacturer-approved liquid line filter driers can
be used� These are Sporlan (CW083S) and Alco
(80K083S) driers� These filter driers are rated for
minimum working pressure of 600 psig� The filter
drier will only have adequate moisture-holding
capacity if the system is properly evacuated�
• Desiccant (drying agent) must be compatible for
POE oils and R-410A refrigerant�
Tools
9
Page 10
INSTALLATION
Replacement Units
To prevent failure of a new unit, the existing line set
must be correctly sized and cleaned or replaced�
Care must be exercised that the expansion device
is not plugged� For new and replacement units, a
liquid line filter drier must be installed and refrigerant
tubing must be properly sized� Test the oil for acid� If
positive, a suction line filter drier is mandatory�
Indoor Coil
CAUTION: Only use evaporators
approved for use on R-410A systems that are
specifically matched with the outdoor unit per
the manufacturer’s specification sheets� Use
of existing R-22 evaporators can introduce
mineral oil to the R-410A refrigerant, forming two
different liquids and decreasing oil return to the
compressor� This can result in compressor failure�
REFER TO INDOOR COIL MANUFACTURER’S
INSTALLATION INSTRUCTIONS.
IMPORTANT: The manufacturer is not
responsible for the performance and operation of
a mismatched system or for a match listed with
another manufacturer’s coil�
IMPORTANT: When replacing an
R-22 unit with an R-410A unit, either replace
the line set or ensure that residual mineral oil is
drained from existing lines, including oil trapped in
low spots�
The thermostatic expansion valve in the
matching coil is specifically designed to operate
with R-410A� DO NOT use an R-22 TXV or
evaporator� The existing evaporator must
be replaced with the factory-specified TXV
evaporator specifically designed for R-410A�
Location
Do not install the indoor coil in the return duct
system of a gas or oil furnace� Provide a service
inlet to the coil for inspection and cleaning� Keep
the coil pitched toward the drain connection�
CAUTION: When coil is installed
over a finished ceiling and/or living area, it is
required that a secondary condensate pan be
installed under entire unit� Failure to do so can
result in property damage�
Tubing
10
Interconnecting Tubing
The purpose of this section is to specify the
best construction/sizing practices for installing
interconnection tubing between the indoor and
outdoor unit�
Refrigerant Level Adjustment
All units are factory-charged with R-410A
refrigerant to cover 15 feet of standard size
interconnecting liquid and vapor lines with a
required eld installed lter drier. Adjustment of
charge may be necessary even if the application
has exactly 15 feet of line set due to other
installation variables such as pressure drop,
vertical lift, and indoor coil size. For dierent
lengths, adjust the charge as indicated below�
adjust the charge as indicated below�
• 1/4” ± .3 oz./foot [6.4 mm ± 8.5 g/.30 m]
• 5/16” ± .4 oz./foot [7.9 mm ± 11.3 g/.30 m]
• 3/8” ± .6 oz./foot [9.5 mm ± 17.0 g/.30 m]
• 1/2” ± 1.2 oz./foot [12.7 mm ± 34.0 g/.30 m]
• 6 oz. Required factory supplied eld installed
• lter dry
Charge Adjustment = (Line Set (oz. /ft.) x Total
Length) – Factory Charge for Line Set
Example: A three ton condensing unit with factory
installed 3/8” liquid service valve
requires 75 ft of line set with a liquid line diameter
of 1/2”.
Factory Charge for Line Set = 15ft x �6 oz� = 9 oz�
Charge Adjustment = (1�2 oz� x 75 ft�) – 9 oz� =
+81 oz�
Page 11
Interconnecting Tubing (cont�)
INSTALLATION
Interconnecting Tubing and
Fitting Losses
Refrigerant tubing is measured in terms of actual
length and equivalent length� Actual length is used
for refrigerant charge applications� Equivalent
length takes into account pressure losses from
The purpose of the liquid line is to transport warm
sub-cooled liquid refrigerant from the outdoor unit
to the indoor unit� It is important not to allow the
refrigerant to ash any superheated vapor prior
to the expansion device of the indoor coil� The
ashing of refrigerant can occur for the following
reasons:
• Low refrigerant charge
• Improperly selected liquid line size
• Absorption of heat prior to expansion device
• Excessive vertical rise between the condenser
and evaporator
tubing length, ttings, vertical separation, accessories, and lter dryers. The table below references
dierent commonly used equivalent lengths.
Table 1
Solenoid
Valve
Table 2 lists the equivalent length per 25’ of liquid
line at various diameters up to 300’� The total pressure drop allowed for the liquid line is 50 PSI� The
procedure for selecting the proper liquid line is as
follows:
• Measure the total amount of vertical rise
• Measure the total amount of liquid line needed
• Add all of the equivalent lengths associated with
any ttings or accessories using the table above.
• Add the total length and tting pressure drop.
This will equal your total equivalent length�
• Reference Table 2 to verify the calculated
equivalent length is compatible with the required
vertical rise and diameter of liquid line�
Check
Valve
Site
Glass
Filter
Dryer
Tubing
Note: Elevaon is defined as the
highest point of the line set to the
lowest
11
Page 12
INSTALLATION
Interconnecting Tubing (cont�)
Example: A 3-Ton condensing unit is installed 50’
below the ID unit, requires a 75’ of 1/2” diameter
This application is acceptable because the 50’
vertical rise is less than the maximum rise of 75’ for
this application� The application is also considered
to have a long line set� Reference the long line set
section of the I&O for detail�
Long Line Set Applications
Long line set applications are dened as applications that require accessories or alternate
construction methods� The following are special
considerations that need to be addressed when
installing a long line set application:
• Additional refrigerant charge
• Fitting losses and maximum equivalent length
considerations
• Refrigerant migration during the o cycle
• Oil return to the compressor
• Capacity losses
• System oil level adjustment
Table 2 is used to determine if the application is
considered to have a long line set� The region of
the chart that is shaded grey is considered to
be a long line set application.
Liquid Line Size
Elevation (Above or Below) Indoor Coil
Total
Maximum
Length - Feet [m]
Equivalent
Vertical Separation - Feet [m]
N/R N/R N/R N/R N/R
Oil Level Adjustments for
Long Line Set Applications
Additional oil will need to be added for long line set
applications� (Ref� Table 2)� Below is the equation
for the oil level adjustment and the compressor
Unit Name Plate Charge (oz.)) x (0.022) – [(0.10)
x (Compressor Name Plate Oil Charge (oz.))]
Example: An application requires 125ft of line set
with a liquid line diameter of 3/8”, Charge Adjustment = 52�4 oz�, Name Plate Charge = 107 oz�,
Name Plate Oil Charge = 25 oz�, Oil to be Added =
((52�4 oz� +107 oz�) x �022) – (�10 x 25 oz�) = 1�0 oz�
Name Plate Oil
Charge (oz)
12
Page 13
Interconnecting Tubing (cont�)
Outdoor and Indoor Same Level
INSTALLATION
Suction Line Selection
Purpose of the suction line is to return superheated
vapor to the condensing unit from the evaporator�
Proper suction line sizing is important because it
plays an important role in returning oil to the compressor to prevent potential damage to the bearings, valves, and scroll sets� Also, an improperly
sized suction line can dramatically reduce capacity
and performance of the system� The procedure for
selecting the proper suction line is as follows:
• The total amount of suction line needed
• Add all of the equivalent lengths associated with
any ttings or accessories using the table on
previous page�
• Add the total length and tting pressure drop.
This will equal your total equivalent length�
• Reference Table 2 to verify that the calculated
equivalent length falls within the compatibility
region of the chart�
• Verify Table 3 to verify the capacity dierence is
compatible with the application�
Refrigerant Migration During
Off Cycle
Long line set applications can require a considerable amount of additional refrigerant� This additional refrigerant needs to be managed throughout the
entire ambient operating envelope that the system
will go through during its life cycle. O-Cycle migration is where excess refrigerant condenses and
migrates to the lowest part of the system� Excessive build-up of refrigerant at the compressor will
result in poor reliability and noisy operation during
startup� This section demonstrates the required
accessories and unit conguration for dierent applications�
Ideally, line set slopes
away from outdoor.
Verify sub-cooling prior
to throling device,
Insulated liquid line
Tubing
Reference Table 2 for
maximum length
limitaons
Figure 3
13
Page 14
INSTALLATION
Indoor Unit Above Outdoor Coil
Interconnecting Tubing (cont�)
For applications that are considered to have a long
line set with the outdoor unit and indoor unit on the
same level the following is required:
• TXV or EEV on the indoor unit
• Start components may be required depending
upon quality of voltage
• Crankcase heater
• Insulated liquid and suction line
Inverted trap even with
top of the coil
• Vapor line should slope toward the indoor unit
• Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments
spelled out in this document and the outdoor
units I&O
• Verify adequate sub-cooling at the ID unit prior
to throttling device
Insulated liquid and
sucon line
Reference Table 2
for elevaon
limitaons
Tubing
For applications that are considered to have a long
line set with the outdoor unit below the indoor unit
the following is required:
• TXV or EEV at the IDunit
• Crankcase heater
• Start components may be required depending
upon quality of voltage
• Inverted vapor-line trap (Reference Figure 3)
• Insulated liquid and suction line
Figure 4
• Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments
spelled out in this document and the outdoor
units I&O
• Measure pressure at the liquid line service valve
and prior to expansion device� Verify that it is
not greater than 50 PSI
• For elevations greater that 25’ can expect a
lower sub-cooling
14
Page 15
p
g
Outdoor Unit Above Indoor Unit
Interconnecting Tubing (cont�)
INSTALLATION
Verify sub-cooling prior
to throlin
device
Insulated liquid and
sucon line
TXV or EEV at indoor
eva
Figure 5
Reference Table 2
for elevaon
limitaons
Tubing
orator
For applications that are considered to have a long
line set with the outdoor unit above the indoor unit
the following is required:
• TXV at the indoor unit
• Crankcase heater
• Start components maybe required depending
upon quality of voltage
• Insulated liquid and suction line
• Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments
spelled out in this document and the outdoor
units I&O
• Verify adequate sub-cooling at the ID unit prior
• If a portion of the liquid line passes through a
very hot area where liquid refrigerant can be
heated to form vapor, insulating the liquid line is
required�
• Use clean, dehydrated, sealed refrigeration-
grade tubing�
• Always keep tubing sealed until tubing is in
place and connections are to be made�
• A high-quality filter drier is included with all
R-410A units and must be installed in the liquid
line upon unit installation�
• When replacing an R-22 system with an R-410A
system and the line set is not replaced, drain
any oil that has pooled in low spots in the
lineset� Commercially available flush kits are
not recommended due to the risk of residual
flushing agent being incompatible with POE oils
or internal components� Up to 5% mineral oil is
considered acceptable in R-410A systems�
• If tubing has been cut, make sure ends are
deburred while holding in a position to prevent
chips from falling into tubing� Burrs such as
those caused by tubing cutters can affect
performance dramatically, particularly on small
liquid line sizes�
• For best operation, keep tubing run as short as
possible with a minimum number of elbows or
bends�
• Locations where the tubing will be exposed to
mechanical damage should be avoided� If it is
necessary to use such locations, the copper
tubing should be housed to prevent damage�
Tubing
18
Page 19
INSTALLATION
TEMPORARY
HANGER
PERMANENT
HANGER
ST-A1226-05-00
Interconnecting Tubing
• If tubing is to be run underground, it must be run
in a sealed watertight chase�
• Use care in routing tubing and do not kink or
twist� Use a good tubing bender on the vapor
line to prevent kinking�
• Route the tubing using temporary hangers; then
straighten the tubing and install permanent
hangers� Line must be adequately supported�
• If the vapor line comes in contact with inside
walls, ceiling, or flooring, the vibration of the
vapor line in the heating mode will result in noise
inside the structure�
(cont�)
• Be certain both refrigerant shutoff valves at the
outdoor unit are closed�
•
Remove the caps and Schrader cores from the
pressure ports to protect seals from heat damage�
Both the Schrader valves and the service valves
have seals that may be damaged by excessive heat�
• Blow out the liquid and vapor lines with dry
nitrogen before connecting to the outdoor unit
and indoor coil� Any debris in the line set will end
up plugging the expansion device�
Tubing Connections
Indoor coils have only a holding charge of
dry nitrogen� Keep all tube ends sealed until
connections are to be made�
• Use type “L” copper refrigeration tubing. Braze
the connections with the following alloys:
– copper to copper, 5% silver minimum
– copper to steel or brass, 15% silver minimum
•
Clean the inside of the fittings and outside of the
tubing with a clean, dry cloth before soldering�
Clean out debris, chips, dirt, etc�, that enters tubing
or service valve connections�
•
Wrap valves with a wet rag or thermal barrier
compound before applying heat�
Tubing
19
Page 20
INSTALLATION
ST-A1226-06-00
Interconnecting Tubing
•
Braze the tubing between the outdoor unit and
indoor coil� Flow dry nitrogen into a pressure port
and through the tubing while brazing, but do not
allow pressure inside tubing which can result in
leaks� Once the system is full of nitrogen, the
nitrogen regulator should be turned off to avoid
pressuring the system�
(cont�)
Leak Testing
Indoor coils have only a holding charge of dry
nitrogen� Keep all tube ends sealed until
connections are to be made�
WARNING: Do not use oxygen
to purge lines or pressurize system for leak test�
Oxygen reacts violently with oil, which can cause
an explosion resulting in severe personal injury or
death�
ST-A1226-07-00
Tubing
• A
fter brazing, use an appropriate heatsink material
to cool the joint�
• Reinstall the Schrader cores into both pressure
ports�
• Do not allow the vapor line and liquid line to
be in contact with each other� This causes an
undesirable heat transfer resulting in capacity
loss and increased power consumption�
•
Pressurize line set and coil through service fittings
with dry nitrogen to 150 PSIG maximum� Close
nitrogen tank valve, let system sit for at least
15 minutes, and check to see if the pressure has
dropped� If the pressure has dropped, check for
leaks at the line set braze joints with soap bubbles
and repair leak as necessary� Repeat pressure
test� If line set and coil hold pressure, proceed
with line set and coil evacuation (see page 21)�
• The vapor line must be insulated for its entire
length to prevent dripping (sweating) and prevent
performance losses� Closed-cell foam insulation
such as Armaflex and Rubatex® are satisfactory
insulations for this purpose. Use 1/2" [12.7 mm]
minimum insulation thickness� Additional
insulation may be required for long runs�
20
Page 21
Control Wiring
WIRING
WARNING: Turn o electric power
at the fuse box or service panel before making
any electrical connections� Also, the ground
connection must be completed before making line
voltage connections� Failure to do so can result in
electrical shock, severe personal injury, or death�
Control Wiring
Running low-voltage wires in conduit with line
voltage power wires is not recommended� Lowvoltage wiring may be run through the plastic
bushing provided in the 7/8" [19 mm] hole in the
base panel, up to and attached to the pigtails from
the bottom of the control box� Conduit can be
run to the base panel if desired by removing the
insulated bushing�
A thermostat and a 24-volt, 40 VA minimum
transformer are required for the control circuit
of the system� The furnace or the air handler
transformer may be used if sufficient� See the
wiring diagram for reference. Use “Wire Size” table
to size the 24-volt control wiring�
Do not use phone cord to connect indoor and
outdoor units and thermostat� This could damage
the controls and may not be adequately sized for
the controls electrical load�
The following figures show the typical wiring
diagrams� Cooling airflows may need to be
adjusted for homeowner comfort once the system
is operational�
WIRE COLOR CODE
BK – BLACK GY – GRAY W – WHITE
BR – BROWN O – ORANGE Y – YELLOW
BL – BLUE PR – PURPLE
G – GREEN R – RED
21
Page 22
WIRING
ST-A1226-09
ST-A1226-09
Control Wiring (cont�)
Field wiring must comply with the National Electric
Code (C�E�C� in Canada) and any applicable local
code�
Power Wiring
It is important that proper electrical power from a
commercial utility is available at the compressor
contactor� Voltage ranges for operation are shown
below�
VOLTAGE RANGES (60 HZ)
Nameplate
Voltage
208/230 187 - 253
(1 Phase)
208/230 187 - 253
(3 Phase)
460 414 - 506
575 517 - 633
Install a branch circuit disconnect within sight of
the unit and of adequate size to handle the starting
current (see “Electrical Data” on page 5�)
Operating Voltage Range at
Copeland Maximum Load Design
Conditions for Compressors
Connect power wiring to line-voltage lugs located
in the outdoor unit electrical box� (See wiring
diagram attached to unit access panel�)
Check all electrical connections, including
factory wiring within the unit and make sure all
connections are tight�
DO NOT connect aluminum field wire to the
contactor terminals�
Grounding
WARNING: The unit must be
permanently grounded� Failure to do so can cause
electrical shock resulting in severe personal injury
or death�
Wiring
22
Power wiring must be run in a rain-tight conduit�
Conduit must be run through the connector panel
below the access cover (see page 6) and attached
to the bottom of the control box�
A grounding lug is provided near the line-voltage
power entrance for a ground wire�
Page 23
Start-Up
At initial start-up or after extended shutdown
periods, make sure the crankcase heater is
energized for at least 12 hours before the
compressor is started� (Disconnect switch is
on and wall thermostat is off�)
Checking Airflow
START-UP
Even though the unit is factory-charged with
Refrigerant-410A, the charge must be checked
to the charge table attached to the service panel
and adjusted, if required� Allow a minimum of
15 minutes of run time before analyzing charge�
CAUTION: Single-pole contactors
are used on all standard single-phase units
through 5 tons� Caution must be exercised when
servicing as only one leg of the power supply is
broken by the contactor�
The air distribution system has the greatest effect
on airflow� The duct system is totally controlled
by the contractor� For this reason, the contractor
should use only industry-recognized procedures�
The correct air quantity is critical to air
conditioning systems� Proper operation, efficiency,
compressor life, and humidity control depend
on the correct balance between indoor load
and outdoor unit capacity� Excessive indoor
airflow increases the possibility of high humidity
problems� Low indoor airflow reduces total
capacity can cause coil icing� Serious harm can
be done to the compressor by low airflow, such as
that caused by refrigerant flooding�
Air conditioning systems require a specified
airflow� Each ton of cooling requires between 320
and 450 cubic feet of air per minute (CFM)� See
the manufacturer’s spec sheet for rated airflow for
the system being installed�
Duct design and construction should be carefully
done� System performance can be lowered
dramatically through bad planning or workmanship�
Air supply diffusers must be selected and located
carefully� They must be sized and positioned
to deliver treated air along the perimeter of the
space� If they are too small for their intended
airflow, they become noisy� If they are not located
properly, they cause drafts� Return air grilles must
be properly sized to carry air back to the blower� If
they are too small, they also cause noise�
The installers should balance the air distribution
system to ensure proper quiet airflow to all rooms in
the home� This ensures a comfortable living space�
These simple mathematical formulas can be used
to determine the CFM in a residential or light
commercial system�
Electric resistance heaters can use:
CFM = volts x amps x 3�413
SHC x temp rise
Gas furnaces can use:
CFM = Output Capacity in BTUH*
SHC x temp rise
*Refer to furnace data plate for furnace output capacity�
SHC = Sensible Heat Constant (see table below)
An air velocity meter or airflow hood can give a
more accurate reading of the system CFM�
The measurement for temperature rise should be
performed at the indoor coil inlet and near the
outlet, but out of direct line of sight of the heater
element or heat exchanger� For best results,
measure air temperature at multiple points and
average the measurements to obtain coil inlet and
outlet temperatures�
ALTITUDE
(FEET)
Sea Level1�0860000�87
500
1000
2000
3000
4000
50000�90200000�50
SENSIBLE HEAT
CONSTANT
(SHC)
1�0770000�84
1�0580000�81
1�0190000�78
0�97100000�75
0�94150000�61
ALTITUDE
(FEET)
SENSIBLE HEAT
CONSTANT
(SHC)
AirflowStart-Up
23
Page 24
START-UP
ST-A1226-08-00
Evacuation
Evacuation and Leak Testing
Evacuation Procedure
Evacuation is the most important part of the entire
service procedure� The life and efficiency of the
equipment is dependent upon the thoroughness
exercised by the serviceman when evacuating air
and moisture from the system�
Air or nitrogen in the system causes high
condensing temperatures and pressure, resulting
in increased power input and nonverifiable
performance�
Moisture chemically reacts with the refrigerant and
oil to form corrosive hydrofluoric acid� This attacks
motor windings and parts, causing breakdown�
• Gauges must be connected at this point to
IMPORTANT: Compressors
(especially scroll type) should never be used to
evacuate the air conditioning system because
internal electrical arcing may result in a damaged
or failed compressor� Never run a scroll
compressor while the system is in a vacuum or
compressor failure will occur�
Final Leak Testing
After the unit has been properly evacuated and
service valves opened, a halogen leak detector
should be used to detect leaks in the system�
All piping within the condenser, evaporator, and
• After the system has been leak-checked and
proven sealed, connect the vacuum pump and
evacuate system to 500 microns and hold 500
microns or less for at least 15 minutes� The
vacuum pump must be connected to both the
high and low sides of the system by connecting
to the two pressure ports� Use the largest size
connections available since restrictive service
connections may lead to false readings because
of pressure drop through the fittings�
interconnecting tubing should be checked for
leaks� If a leak is detected, the refrigerant should
be recovered before repairing the leak� The Clean
Air Act prohibits releasing refrigerant into the
atmosphere�
check and adjust charge� Do not replace caps
yet�
• After adequate evacuation, open both service
valves by removing both brass service valve
caps with an adjustable wrench. Insert a 3/16"
[5 mm] or 5/16" [8 mm] hex wrench into the
stem and turn counterclockwise until the wrench
stops�
24
Page 25
Checking Refrigerant Charge
START-UP
Charge for all systems should be checked against
the Charging Chart inside the access panel cover�
WARNING:
compressor shell is hot� Touching the compressor
top may result in serious personal injury�
The top of the scroll
IMPORTANT: Use factory-approved
charging method as outlined on the next page to
ensure proper system charge�
NOTICE: The optimum refrigerant charge
for any outdoor unit matched with an indoor
coil/air handler is affected by the application�
Therefore, charging data has been developed to
assist the field technician in optimizing the charge
for all mounting configurations (UF – Upflow, DF
– Downflow, LH – Left-Hand Discharge, and RH –
Right-Hand Discharge)� Refer to the charging chart
inside the access panel cover on the unit and
choose the appropriate column for the specific
application being installed or serviced�
Charging Units With R-410A
Refrigerant
CAUTION:
approximately 60% higher (1�6 times) than R-22
pressures� Use appropriate care when using this
refrigerant� Failure to exercise care may result in
equipment damage or personal injury�
Charge for all systems should be checked against
the Charging Chart inside the access panel cover�
R-410A pressures are
IMPORTANT: Do not operate the
compressor without charge in the system�
Addition of R-410A will raise high-side pressures
(liquid and discharge)�
NOTICE: System maintenance is to be
performed by a qualified and certified technician�
The following method is used for charging systems
in the cooling mode� All steps listed should be
performed to ensure proper charge has been set�
For measuring pressures, the service valve port
on the liquid valve (small valve) and suction valve
(large valve) are to be used
Supply airflow must be between 320 and 450 cfm
per rated cooling ton prior to adjusting system
charge� If a humidification system is installed,
disengage it from operation prior to charge
adjustment. Refer to the “Checking Airflow” section
of this manual for further instruction�
NOTICE: Verify system components
are matched according to the outdoor unit
Specification Sheet�
Measurement Device Setup
1� With an R-410A gauge set, attach the high-
pressure hose to the access fitting on the liquid
(small) service valve at the OD unit�
2�
Attach the low-pressure hose to the access fitting
on the suction (large) service valve�
3. Attach a temperature probe within 6" [15.2 cm]
outside of the unit on the copper liquid line
(small line)� For more accurate measurements,
clean the copper line prior to measurement and
use a calibrated clamp-on temperature probe or
an insulated surface thermocouple�
Charging by Weight
NOTICE:
weight for the straight length of the refrigerant line set�
For a new installation, evacuation of inter-
connecting tubing and indoor coil is adequate;
otherwise, evacuate the entire system� Use the
factory charge shown in “Electrical and Physical
Data” on page 5 of these instructions or on the
unit data plate� Note that the charge value includes
charge required for 15 ft. [4.6 m] of standard-size
interconnecting liquid line without a filter drier�
Calculate actual charge required with installed
Confirm adequate indoor supply airflow prior to
starting the system� See the Technical Specification
Sheet for rated airflow for each ID/OD unit match�
Air filter(s) and coils (indoor and outdoor) are to be
clean and free of frost prior to starting the system�
25
Page 26
START-UP
Checking Refrigerant Charge (cont�)
Refrigerant
With an accurate scale (+/– 1 oz. [28.3 g]) or
volumetric charging device, adjust charge
difference between that shown on the unit data
plate and that calculated for the new system
installation� If the entire system has been
evacuated, add the total calculated charge�
IMPORTANT: Charging by weight is
not always accurate since the application can
affect the optimum refrigerant charge� Charging by
weight is considered a starting point ONLY� Always
check the charge by using the Charging Chart
and adjust as necessary� CHARGING BY LIQUID
SUBCOOLING MUST BE USED FOR FINAL
CHARGE ADJUSTMENT�
With thermostat in the “Off” position, turn on
the power to the furnace or air handler and the
condensing unit� Start the condensing unit and the
furnace or air handler with the thermostat� Verify
that the outdoor unit is operating and the indoor
air mover is delivering the correct airflow for the
system size�
Gross Charging by Pressures
1� Following airflow verification and charge weigh-
in, run the unit for a minimum of 15 minutes
prior to noting pressures and temperature�
or below this range, run the system to bring the
temperature down or run the electric heat/furnace
to bring the temperature within this range� System
pressure values provided in the Charging Chart for
outdoor dry bulbs corresponding to conditions outside
of these ranges are provided as reference ONLY�
If the Indoor temperature is above
2� Note the Outdoor Dry Bulb Temperature,
ODDB° = _____°F [_____°C]� Unit charging is
recommended under the following outdoor
conditions ONLY:
Cooling Mode ONLY: 55°F [12.8°C] outdoor dry
bulb and above
3� Locate and note the design pressures� The
correct liquid and vapor pressures are found at
the intersection of the installed system and the
outdoor ambient temperature on the Charging
Chart located inside the access panel cover�
Liquid Pressure: = ______psig; Vapor Pressure =
______psig
NOTICE:
are for gross charge check ONLY� These pressure
values are typical, but may vary due to application�
Evaporator load (indoor coil in cooling mode/outdoor
coil in heating mode) will cause pressures to deviate�
Note that all systems have unique pressure curves�
The variation in the slope and value is determined
by the component selection for that indoor/outdoor
matched system� The variation from system to
system seen in the table is normal� The values listed
are for the applicable indoor coil match ONLY!
4� If the measured liquid pressure is below the
listed requirement for the given outdoor and
indoor conditions, add charge� If the measured
liquid pressure is above the listed requirement
for the given outdoor and indoor conditions,
remove charge�
The refrigerant pressures provided
Final Charge by Subcooling
1� After gross charging, note the designed
subcooling value� The correct subcooling value
is found at the intersection of the installed
system and the outdoor ambient temperature
on the Charging Chart located inside the access
panel cover�
SC° from Charging Chart = _____°F [_____°C].
IMPORTANT: Indoor conditions as
measured at the indoor coil are required to be
between 70°F [21.1°C] and 80°F [26.7°C] dry
bulb for fine-tuned unit charge adjustment� Unit
charging is recommended under the following
outdoor conditions ONLY:
Cooling Mode ONLY: 55°F [12.8°C] outdoor dry
bulb and above
26
Page 27
Checking Refrigerant Charge (cont�)
START-UP
NOTICE: If the indoor temperature is
above or below the recommended range, run the
system to bring the temperature down or run the
electric heat/furnace to bring the temperature
up� System subcooling values provided in
the Charging Chart for outdoor dry bulbs
corresponding to conditions outside of the above
range are provided as reference ONLY�
2� Note the measured Liquid Pressure, Pliq =
______psig, as measured from the liquid
(small) service valve� Use the Temperature
Pressure Chart below to note the corresponding
saturation temperature for R-410A at the
measured liquid pressure�
Liquid Saturation Temperature, SAT°= _____°F
[_____°C].
3� Note the liquid line temperature, Liq° = _____°F
[_____°C], as measured from a temperature
probe located within 6" [15.2 cm] outside of
the unit on the copper liquid line (small line)�
It is recommended to use a calibrated clampon temperature probe or an insulated surface
thermocouple�
4�
Subtract the liquid line temperature from the
saturation temperature to calculate subcooling�
SAT°_____°F
SC°_____°F
5�
Adjust charge to obtain the specified subcooling
value� If the measured subcool is below the listed
requirement for the given outdoor and indoor
[_____°C]
[_____°C]
- Liq°_____°F
[_____°C]
=
conditions, add charge� If the measured subcool
is above the listed requirement for the given
outdoor and indoor conditions, remove charge�
Finishing Up Installation
• Disconnect pressure gauges from pressure ports;
then replace the pressure port caps and tighten
adequately to seal caps� Do not overtighten.
• Replace the service valve caps finger-tight
and then tighten with an open-end wrench
adequately to seal caps� Do not overtighten.
• Replace control box cover and service panel and
install screws to secure service panel�
• Restore power to unit at disconnect if required.
• Configure indoor thermostat per the thermostat
installation instructions and set thermostat to
desired mode and temperature�
NOTICE: Systems should not be fine-
tune charged below 40°F [4.4°C] outdoor dry bulb.
IMPORTANT: Excessive use of
elbows in the refrigerant line set can produce
excessive pressure drop� Follow industry
best practices for installation� Installation
and commissioning of this equipment is to
be performed by trained and qualified HVAC
professionals� For technical assistance, contact
your Distributor Service Coordinator�
Refrigerant
TEMPERATURE PRESSURE CHART
SATURATION
TEMP
(Deg. F) [Deg.
C]
-150 [-101]
-140 [-96]
-130 [-90]
-120 [-84]
-110 [-79]
-100 [-73]
-90 [-68]
-80 [-62]
-70 [-57]
-60 [-51]0�415 [-9]70�280 [27]235�6145 [63]576�0
-50 [-46]5�120 [-7]78�585 [29]254�5150 [66]612�8
-40 [-40]10�925 [-4]87�590 [32]274�3
-35 [-37]14�230 [-1]97�295 [35]295�3
R-410A
PSIG
–-30 [-34]
–-25 [-32]
–-20 [-29]
–-15 [-26]
–-10 [-23]
–-5 [-21]
–
–
–
SATURATION
(Deg. F) [Deg.
10 [-12]62�475 [24]217�8140 [60]541�2
TEMP
C]
0 [-18]48�465 [18]185�1130 [54]476�5
5 [-15]55�170 [21]201�0135 [57]508�0
R-410A
PSIG
17�935 [2]107�5100 [38]317�4
22�040 [4]118�5105 [41]340�6
26�445 [7]130�2110 [43]365�1
31�350 [10]142�7115 [46]390�9
36�555 [13]156�0120 [49]418�0
42�260 [16]170�1125 [52]446�5
SATURATION
TEMP
(Deg. F) [Deg.
C]
R-410A
PSIG
SATURATION
TEMP
(Deg. F) [Deg.
C]
R-410A
PSIG
27
Page 28
COMPONENTS AND CONTROLS
Compressor Crankcase Heat (CCH)
Components
While scroll compressors usually do not require
crankcase heaters, there are instances when a
heater should be added� Refrigerant migration
during the off cycle can result in a noisy start up�
Add a crankcase heater to minimize refrigerant
migration and to help eliminate any start up noise
or bearing “wash out.”
NOTE: A crankcase heater should be installed if:
• The system charge exceeds the values listed in
the adjacent tables,
• The system is subject to low voltage variations,
All heaters are located on the lower half of the
compressor shell� Its purpose is to drive refrigerant
from the compressor shell during long off cycles,
thus preventing damage to the compressor during
start-up�
At initial start-up or after extended shutdown
periods, make sure the heater is energized for at
least 12 hours before the compressor is started�
(Disconnect switch is on and wall thermostat is off�)
9.6
9.6 lbs.
9.6
9.6 lbs.
9.6
9.6 lbs.
9.6
9.6 lbs.
12
12 lbs.
12
12 lbs.
12
12 lbs.
28
High- and Low-Pressure Controls (HPC and LPC)
HPC and LPC are not installed on RA14**AJINA,
but can be field installed using the followiing
kit numbers: RXAB-A0z (high pressure control)
and RXAC-A0Z (low pressure control)� These
controls keep the compressor from operating in
pressure ranges which can cause damage to the
compressor� Both controls are in the low-voltage
control circuit�
The high-pressure control (HPC) is an automaticreset which opens near 610 PSIG and closes near
420 PSIG�
The low-pressure control (LPC) is an automaticreset which opens near 15 PSIG and closes near
40 PSIG�
CAUTION: The compressor has
an internal overload protector� Under some
conditions, it can take up to 2 hours for this
overload to reset� Make sure overload has had
time to reset before condemning the compressor�
Page 29
ACCESSORIES
WARNING:Turn o electric power
at the fuse box or service panel before making
any electrical connections� Also, the ground
connection must be completed before making line
voltage connections� Failure to do so can result in
electrical shock, severe personal injury, or death�
CAUTION:
SINGLE POLE COMPRESSOR
CONTACTOR (CC):
Single pole contactors are used on all singlephase units up through 5 tons� Caution must be
exercised when servicing as only one leg of the
power supply is broken with the contactor�
Hard Start Components
Time Delay Control
(Part No. RXMD-B01)
The time delay control is in the low voltage control
circuit� When the compressor shuts off due to a
power failure or thermostat operation, this control
keeps it off at least 5 minutes which allows the
system pressure to equalize, thus not damaging
the compressor or blowing fuses on start-up�
Low Ambient Control (LAC)
(Part No. RXAD-A08)
This component senses compressor head
pressure and shuts the heat pump fan off when
the head pressure drops to approximately 250
PSIG� This allows the unit to build a sufficient head
pressure at lower outdoor ambient (down to 0°F
[-18°C]) in order to maintain system balance and
obtain improved capacity� Low ambient control
should be used on all equipment operated below
70°F [21°C} ambient�
Accessories
Start components are not usually required with
the scroll compressors used in RA14 condensing
units, but are available for special cases and
where start components are desirable to reduce
light dimming�
29
Page 30
DIAGNOSTICS
NO
YES
Thermostat
Problem?
Transformer
Problem?
Go to Mechanical Checks
for Cooling or Heating
Hi Pressure Cut-Out
Hot Gas Sensor
Compressor
Time-Delay
Unit Wiring and
Connections
Start Capacitor
Potential Relay
Compressor Internal
Overload Open
Unit Wiring and
Connections
Compressor Winding
Open
Unit
Running?
YES
Repair and
Recheck
YES
Repair and
Recheck
NO
Voltage on Compressor
Side of Contactor?
NO
YES
Run Capacitor
NO
Voltage on Line
Side of Contactor?
NO
Circuit Breakers or
Fuses Open
YES
Compressor Winding
Grounded
Outdoor Fan Motor
Grounded
Grounded Capacitor
Replace Fuses or Reset
Breakers and Recheck
System
YES
Compressor
Contactor
NO
Unit Wiring and
Connections
Electrical Checks Flowchart
Diagnostics
30
Page 31
YES
NO
Pressure
Problems?
Low Liquid
Pressure
Low Suction
Pressure
High Head
Pressure
Go to Electrical
Checks Flowchart
Dirty Filters
Dirty Indoor Coil
Inadequate Indoor
Airow
Inoperative Indoor
Blower
Low on
Charge
Open IPR
Valve
Low Ambient
Temperature
Bad
Compressor
Outdoor Check
Valve Closed
Restricted Indoor
Metering Device
Restricted
Filter Drier
Dirty Outdoor
Coil
Inoperative Outdoor
Fan
Overcharge
Recirculation of
Outdoor Air
Noncondensibles
Higher Than Ambient Air
Entering Outdoor Coil
Wrong Outdoor
Fan Rotation
Inadequate Ducts
Outdoor Check
Valve Closed
Restricted
Filter Drier
Outdoor Unit
Running?
Low on Charge
Restricted Indoor
Metering Device
Restriction in
System
Recirculation of
Indoor Air
Wrong Indoor
Blower Rotation
Cooling Mechanical Checks Flowchart
DIAGNOSTICS
Diagnostics
31
Page 32
DIAGNOSTICS
General Troubleshooting Chart
Diagnostics
WARNING:
Disconnect all power to
unit before servicing� Contactor may break only one
side� Failure to shut off power can cause electrical
shock resulting in personal injury or death�
SYMPTOMPOSSIBLE CAUSEREMEDY
Unit will not run• Power o or loose electrical connection
• Thermostat out of calibration – set too high
• Defective control board
• Blown fuses/tripped breaker
• Transformer defective
• High-pressure control open
Low-pressure control open
• Miswiring of communications (communication
light on continuously)
Outdoor fan runs,
compressor doesn't
Insucient cooling• Improperly sized unit
Compressor short
cycles
Registers sweat• Low indoor airow• Increase speed of blower or reduce restriction.
High head, low vapor
pressures
High head, high
or normal vapor
pressure – Cooling
mode
Low head, high vapor
pressures
Low vapor, cool
compressor, iced
indoor coil
High vapor pressure• Excessive load
Fluctuating head and
vapor pressures
Gurgle or pulsing
noise at expansion
device or liquid line
• Run or start capacitor defective
• Contactor defective
• Loose connection
• Compressor stuck, grounded or open motor
winding, open internal overload�
• Low-voltage condition
• Improper indoor airow
• Incorrect refrigerant charge
• Air, noncondensibles, or moisture in system
• Bad ID TXV
• Incorrect voltage
• Defective overload protector
• Refrigerant undercharge
• Restriction in liquid line, expansion device, or
lter drier
• Bad TXV
• Dirty outdoor coil
• Refrigerant overcharge
• Outdoor fan not running
• Air or noncondensibles in system
• Bad TXV
• Bad compressor
• Low indoor airow
• Operating below 65°F outdoors
• Moisture in system
• Closed ID circuit
• Defective compressor
• TXV hunting
• Air or noncondensibles in system
• Air or noncondensibles in system• Recover refrigerant. Evacuate and recharge.
• Check for correct voltage at line voltage connections in
condensing unit�
• Reset.
• Check control board diagnostic codes.
• Replace fuses/reset breaker.
• Check wiring. Replace transformer.
• Reset. Also see high head pressure remedy. The high-
pressure control opens at 610 PSIG�
• Check communication wiring.
• Replace.
• Replace.
• Check for correct voltage at compressor. Check and
tighten all connections�
• Wait at least 3 hours for overload to reset. If still open,
replace the compressor�
• Add start kit components.
• Recalculate load.
• Check. Should be approximately 400 CFM per ton.
• Charge per procedure attached to unit service panel.
• Recover refrigerant. Evacuate and recharge. Add lter
drier�
• Replace TXV
• At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating�
• Replace. Check for correct voltage.
• Add refrigerant.
Replace air lter.
• Remove or replace defective component.
• Replace TXV.
• Clean coil.
• Correct system charge.
• Repair or replace.
• Recover refrigerant. Evacuate and recharge.
• Replace TXV.
• Replace compressor.
• Increase speed of blower or reduce restriction.
Replace air lter.
• Add Low Ambient Kit.
• Recover refrigerant. Evacuate and recharge. Add lter
drier�
• Repair or replace ID coil
• Recheck load calculation.
• Replace.
• Check TXV bulb clamp. Check air distribution on coil.
Replace TXV�
• Recover refrigerant. Evacuate and recharge.
32
Page 33
DIAGNOSTICS
Service Analyzer Charts
COMPRESSOR OVERHEATING
SYMPTOMPOSSIBLE CAUSECHECK/REMEDY
High superheat
(greater than 15°F
[-9°C] at coil)
Low line voltageLoose wire connections
High line voltagePower company problemHave problem corrected�
Low chargeCheck system charge�
Faulty metering deviceRestricted cap tube, TEV (TXV)
Power element superheat out of adjustment internally
Foreign matter stopping ow
High internal loadHot air (attic) entering return
Heat source on; miswired or faulty control
Restriction in liquid line
Low head pressureLow charge
Suction or liquid line subjected to high heat
source
Power company problem, transformerHave problem corrected before diagnosis continues�
Undersized wire feeding unitCorrect and complete diagnosis�
Drier plugged�
Line kinked�
Operating in low ambient temperatures
Hot attic / insulate liquid line
Hot water line
Check wiring�
High head
pressure
Short cycling of compressor
OverchargeCheck system charge�
Dirty outdoor coilClean coil�
Faulty or wrong size outdoor fan motorReplace fan motor�
Faulty fan blade or wrong rotationReplace fan blade�
Replace with correct rotation motor�
Recirculation of airCorrect installation�
Additional heat sourceCheck for dryer vent near unit�
Check for recirculation from other equipment�
NoncondensiblesRecover refrigerant� Evacuate and recharge system�
Equipment not matchedCorrect mismatch�
Faulty pressure controlReplace pressure control�
Loose wiringCheck unit wiring�
ThermostatLocated in supply air stream
Dierential setting too close
Customer misuse
TEVInternal foreign matter
Power element failure
Valve too small
Distributor tube/tubes restricted
Distributor tubeRestricted with foreign matter
Kinked
I�D� reduced from previous compressor failure
Diagnostics
33
Page 34
DIAGNOSTICS
Service Analyzer Charts
COMPRESSOR OVERHEATING (cont.)
SYMPTOMPOSSIBLE CAUSECHECK OR REMEDIES
Short cycling of
compressor (cont�)
Faulty Compressor
Valves
ELECTRICAL
SYMPTOMPOSSIBLE CAUSECHECK OR REMEDIES
Voltage present on
load side of compressor contactor
and compressor
won't run
Voltage present on
line side of compressor contactor
only
Diagnostics
No voltage on line
side of compressor
contactor
Low chargeCheck system charge�
Low evaporator airowDirty coil
Dirty lter
Duct too small or restricted
Faulty run capacitor
Faulty internal overloadReplace compressor�
Fast equalization/Low pressure dierenceReplace compressor and examine system to
Compressor start componentsCheck start capacitor�
Run capacitorCheck with ohmmeter
Internal overloadAllow time to reset�
Compressor windingsCheck for correct ohms�
ThermostatCheck for control voltage to contactor coil�
Compressor control circuitHigh-pressure switch
Blown fuses or tripped circuit breaker
Improper wiringRecheck wiring diagram�
Replace�
locate reason�
Check potential relay�
Low-pressure switch
Ambient thermostat
Solid-state protection control or internal thermal sensors
Compressor timed o/on control or interlock
Check for short in wiring or unit�
34
Improper voltageHigh voltageWrong unit
Power supply problem
Low voltageWrong unit
Power supply problem
Wiring undersized
Loose connections
Single Phasing (3 phase)
Check incoming power and fusing�
FLOODED STARTS
SYMPTOMPOSSIBLE CAUSECHECK OR REMEDIES
Liquid in the compressor shell
Too much liquid in
system
Faulty or missing crankcase heaterReplace crankcase heater�
Incorrect pipingCheck piping guidelines�
OverchargeCheck and adjust charge�
Page 35
DIAGNOSTICS
Service Analyzer Charts
CONTAMINATION
SYMPTOMPOSSIBLE CAUSEREMEDY
MoisturePoor evacuation on installation or during serviceIn each case, the cure is the same� Recover refrigerant�
High head pressureNoncondensibles air
Unusual head and
suction readings
Foreign matter –
copper lings
Copper oxideDirty copper piping or nitrogen not used when
Welding scaleNitrogen not used during brazing
Soldering uxAdding ux before seating copper partway
Excess soft solderWrong solder material
Wrong refrigerant or mixed refrigerants
Copper tubing cuttings
brazing
LOSS OF LUBRICATION
SYMPTOMPOSSIBLE CAUSEREMEDY
Compressor failuresLine tubing too largeReduce pipe size to improve oil return�
Low suction pressure Low chargeCheck system charge�
Refrigerant leaksRepair and recharge�
Cold, noisy
compressor –
Slugging
Noisy compressorMigrationCheck crankcase heater�
Cold, sweating
compressor
Low loadReduced airowDirty lter
Short cycling of
compressor
Dilution of oil with refrigerantObserve piping guidelines�
FloodingCheck system charge�
Thermostat setting
Faulty high- or low-pressure controlReplace control�
Loose wiringCheck all control wires�
ThermostatIn supply air stream, out of calibration
Add lter drier, evacuate, and recharge.
Dirty coil
Wrong duct size
Restricted duct
Advise customer�
Customer misuse
Diagnostics
SLUGGING
SYMPTOMPOSSIBLE CAUSEREMEDY
On start-upIncorrect pipingReview pipe size guidelines�
TEV hunting when
running
Faulty TEVReplace TEV�
35
Page 36
DIAGNOSTICS
Service Analyzer Charts
FLOODING
SYMPTOMPOSSIBLE CAUSEREMEDY
Poor system control
using a TEV
THERMOST A TIC EXPANSION V ALVES
SYMPTOMPOSSIBLE CAUSEREMEDY
High Superheat, Low
Suction Pressure
(superheat over
15°F [-9°C])
Diagnostics
Valve feeds too much
refrigerant, with low
superheat and higher
than normal suction
pressure
Loose sensing bulbSecure the bulb and insulate�
Bulb in wrong locationRelocate bulb�
Wrong size TEVUse correct replacement�
Improper superheat setting (less than 5°F [-15°C])
Moisture freezing and blocking valveRecover charge, install lter-drier, evacuate system,
Dirt or foreign material blocking valveRecover charge, install lter-drier, evacuate system,
Low refrigerant chargeCorrect the charge�
Vapor bubbles in liquid lineRemove restriction in liquid line� Correct the refrigerant
Misapplication of internally equalized valveUse correct TEV�
Plugged external equalizer lineRemove external equalizer line restriction�
Undersized TEVReplace with correct valve�
Loss of charge from power head sensing bulbReplace power head or complete TEV�
Charge migration from sensing bulb to power
head (Warm power head with warm, wet cloth�
Does valve operate correctly now?)