Rheem RA1460AJ1NA, RA1448AJ1NA, RA1442AJ1NA, RA1436AJ1NA, RA1430AJ1NA Installation Instructions Manual

...
Page 1
WARNING:
earth friendly refrigerant
e
arthry r
dly
n
fr
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION
WARNING
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT, AND OPERA TION OF THIS UNIT . READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLO W THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE, OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.
AIR COOLED CONDENSING UNITS
INSTALLATION INSTRUCTIONS
RA14 MODEL SERIES – 14 SEER
FEATURING INDUSTRY STANDARD R-410A REFRIGERANT
Do not destroy this manual. Please read carefully and keep in a safe place for future reference by a serviceman.
[ ] indicates metric conversions.
92-104921-01-01 (11/14) Printed in USA
Page 2
CONTENTS
Important Safety Information ��������������������������������������������� 3
General Information ����������������������������������������4-6
Checking Product Received ����������������������������������������4
Contents
Application �������������������������������������������������������������������4 Electrical and Physical Data �����������������������������������������5 Specifications ���������������������������������������������������������������6 Proper Installation ��������������������������������������������������������6
Installation ���������������������������������������������������� 7-17
Choosing a Location ����������������������������������������7-8
Operational Issues��������������������������������������������������������7
Corrosive Environment �������������������������������������������������7 For Units With Space Limitations ���������������������������������������������������������8 Customer Satisfaction Issues ��������������������������������������8 Unit Mounting ���������������������������������������������������������������8 Factory-Preferred Tie-Down Method���������������������������������������������������������8
Tools and Refrigerant
Tools Required for Installing and Servicing R-410A Models ��������������������������������������������9 Specifications of R-410A ���������������������������������������������9 Quick-Reference Guide for R-410A ���������������������������������������������������������9
Replacement Units �������������������������������������������10 Indoor Coil ��������������������������������������������������������10
Location ����������������������������������������������������������������������10
Interconnecting Tubing �������������������������������� 10-20
Vapor and Liquid Lines ����������������������������������������������10 Maximum Length of Lines ������������������������������������������10 Outdoor Unit Installed Above or Below Indoor Coil ��������������������������������� 13-15 Tubing Installation ������������������������������������������������ 18-19 Tubing Connections ��������������������������������������������� 19-20 Leak Testing ���������������������������������������������������������������20
Wiring ���������������������������������������������������������21-22
Control Wiring ������������������������������������������������������������21 Conventional 24 VAC Thermostat Control Wiring �����������������������������������������21 Thermostat Wiring Diagrams ������������������������������� 21-22 Power Wiring �������������������������������������������������������������� 22 Grounding ������������������������������������������������������������������� 22
���������������������������������������� 9
Start-Up
Start-Up ����������������������������������������������������������������������23 Checking Airflow ��������������������������������������������������������23 Evacuation Procedure ����������������������������������������������� 24 Final Leak Testing �������������������������������������������������������24
Checking
Refrigerant Charge �������������������������������������� 25-27
Charging Units With R-410A Refrigerant ��������������������������������������������25 Confirm ID Airflow and Coils Are Clean ���������������������������������������������������25 Measurement Device Setup ��������������������������������������� 25 Charging by Weight ���������������������������������������������������� 25 Gross Charging by Pressures ������������������������������������ 26 Final Charge by Subcooling ��������������������������������������� 26 Finishing Up Installation ��������������������������������������������� 27
Components and Controls �������������������������� 28-29
Compressor
Crankcase Heat (CCH) ��������������������������������������28
High- and Low-Pressure
Controls (HPC and LPC) ������������������������������������28 Hard-Start Components ������������������������������������29
Accessories ����������������������������������������������������� 29
Time-Delay Control ����������������������������������������������������29 Hard Start Components ���������������������������������������������29 Low Ambient Control (LAC) ���������������������������������������29
Diagnostics ������������������������������������������������� 30-38
Cooling Mechanical Checks Flowchart ������������������������������������������������������30 General Troubleshooting Chart ����������������������������������32 Service Analyzer Charts ��������������������������������������� 33-37 Cooling/Heating Tips ��������������������������������������������������38
Wiring Diagrams �����������������������������������������39-40
������������������������������������������������������23–27
2
Page 3
IMPORTANT SAFETY INFORMATION
WARNINGS:
These instructions are intended as an aid to
qualified, licensed service personnel for proper installation, adjustment, and operation of this unit� Read these instructions thoroughly before
attempting installation or operation� Failure to
follow these instructions may result in improper installation, adjustment, service, or maintenance possibly resulting in fire, electrical shock, property damage, personal injury, or death.
• The unit must be permanently grounded. Failure
to do so can cause electrical shock resulting in severe personal injury or death.
• Turn off electric power at the fuse box or service
panel before making any electrical connections.
• Complete the ground connection before making
line voltage connections. Failure to do so can result in electrical shock, severe personal injury, or death.
• Disconnect all power to unit before starting
maintenance. Failure to do so can cause electrical shock resulting in severe personal injury or death.
• Never assume the unit is properly wired and/or grounded. Always test the unit cabinet with a noncontact voltage detector available at most electrical supply houses or home centers before removing access panels or coming into contact with the unit cabinet.
• Do not use oxygen to purge lines or pressurize system for leak test. Oxygen reacts violently with oil, which can cause an explosion resulting in
severe personal injury or death.
The top of the scroll compressor shell is hot� Touching the compressor top may result in serious personal injury�
The manufacturer’s warranty does not cover any damage or defect to the unit caused by the attachment or use of any components, accessories, or devices (other than those authorized by the manufacturer) into, onto, or in conjunction with
the heat pump� You should be aware that the
use of unauthorized components, accessories,
or devices may adversely affect the operation of the heat pump and may also endanger life and property. The manufacturer disclaims any
responsibility for such loss or injury resulting from the use of such unauthorized components, accessories, or devices�
CAUTIONS:
R-410A systems operate at approximately 60%
higher pressures (1�6 times) than R-22 systems� Do not use R-22 service equipment or components on R-410A equipment� Use appropriate care when using this refrigerant� Failure to exercise care may result in equipment damage or personal injury�
Only match this outdoor unit with a matched indoor
coil or air handler approved for use with this outdoor unit per the unit manufacturer’s specification sheet� The use of unmatched coils or air handler will likely result in a charge imbalance between the cooling and heating modes which can cause unsatisfactory operation including a high-pressure switch lockout condition�
Only use indoor coils approved for use on R-410A
systems� An R-22 coil will have a TXV or fixed restrictor device that is not designed to operate properly in an R-410A system and will result in serious operational issues� The R-22 coil could also contain mineral oil which is incompatible with the POE oil used in R-410A systems and could result in reliability issues with the compressor and TXVs�
When coil is installed over a finished ceiling and/or
living area, it is required that a secondary sheet metal condensate pan be constructed and installed under the entire unit� Failure to do so can result in property damage�
The compressor has an internal overload protector�
Under some conditions, it can take up to 2 hours for this overload to reset� Make sure overload has had time to reset before condemning the compressor�
Safety
3
Page 4
GENERAL INFORMATION
WARNING:
Improper installation, or installation not made in accordance with these instructions, can result
in unsatisfactory operation and/or dangerous
conditions and can cause the related warranty not to apply.
The condensing unit is designed to operate with standard 24 VAC thermostats and air handlers or gas furnaces�
This installation instruction manual contains complete instructions for installation and setup
General Information
using conventional 24 VAC controls� Please refer to the manufacturer’s specification sheets for complete performance data, thermostat, and accessory listings�
The information contained in this manual has been prepared to assist in the proper installation, operation, and maintenance of the air conditioning system�
Read this manual and any instructions packaged with separate equipment required to make up the system prior to installation� Homeowner should retain this manual for future reference�
To achieve optimum efficiency and capacity, the matching indoor cooling coils listed in the manufacturer’s specification sheet should be used�
Checking Product Received
Upon receiving unit, inspect it for any shipping damage� Claims for damage, either apparent or concealed, should be filed immediately with the shipping company� Check model number, electrical characteristics, and accessories to determine if they are correct� Check system components (indoor coil, outdoor unit, air handler/furnace, etc�) to make sure they are properly matched�
Application
Before specifying any air conditioning equipment, a survey of the structure and a heat gain calculation must be made� A cooling heat gain calculation determines the amount of heat needed to be removed� A heat gain calculation also calculates the extra heat load caused by sunlight and by humidity removal� These factors must be considered before selecting an air conditioning system to provide year-round comfort� The Air Conditioning Contractors of America (ACCA) J Manual method of load calculation is one recognized procedure for determining the heating and cooling load�
After the proper equipment combination has been selected, satisfying both sensible and latent requirements, the system must be properly installed� Only then can the unit provide the comfort it was designed to provide�
There are several factors that installers must consider�
Outdoor unit location
Indoor unit blower speed and airflow
Proper equipment evacuation
Supply and return air duct design and sizing
Refrigerant charge
System air balancing
Diffuser and return air grille location and sizing
4
Page 5
GENERAL INFORMATION
Electrical and Physical Data
PHYSICALELECTRICAL
Circuit
Fuse or HACR Circuit
Breaker
Minimum
Maximum
Amperes
Amperes
20/20
25/25
25/25
30/30
40/40
45/45
40/40 21.54 [2.00] 1 4139 [1953] 168 [4762] 202 [91.6] 209 [94.8]
50/50
Face
Area Sq.
Ft [m]
No.
Rows
CFM [L/s]
Refrig.
Per
Circuit
(oz.) [g]
Compressor
Model Number
RA1418AJ1NA 208-230 160 9.7/9.7 46.00.60 13 20/209.06 [0.84] 1 2225 [1050] 74 [2097] 122 [55.3] 129 [58.5]
RA1424AJ1NA 208-230 16011.2/11.2 60.80.70 15 20/20 11.14 [1.03] 1 2505 [1182] 78.4 [2222] 125 [56.7] 132 [59.9]
RA1430AJ1NA 208-230 16012.8/12.8 64.00.70 17 20/20 12.15 [1.13] 1 2605 [1229] 93.0 [2636] 141 [64.0] 148 [67.1]
RA1436AJ1NA 208-230 16014.1/14.1 77.00.60 19 25/25 14.82 [1.38] 1 3104 [1464] 112 [3175] 150 [68.0] 157 [71.2]
RA1442AJ1NA 208-230 16017.9/17.9 112.01.00 24 30/30 16.15 [1.5]13954 [1866] 125 [3543] 189 [58.7] 196 [88.9]
RA1448AJ1NA 208-230 16019.9/19.9 109.01.00 26 35/35 18.84 [1.75] 1 4264 [2012] 135 [3827] 192 [87.1] 199 [90.3]
RA1460AJ1NA 208-230 16023.7/23.7 152.51.00 31
Voltage Phase Freq
Rated
Load
Amperes
(RLA)
Locked
Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Ampacity
Amperes
Net Lbs.
[kg]
WeightOutdoor Coil
Shipping Lbs. [kg]
General Information
UNIT MODEL NUMBER EXPLANATION
R
24
A
14
AJ1NA
MINOR SERIES
TYPE C - COMMUNICATING
N - NON-COMM
TYPE 1 - SINGLE STAGE
VOLTAGE J= 1 PH, 208-230/60 C= 3 PH, 208-230/60 D= 3 PH, 460/60
MAJOR SERIES
CAPACITY
18 = 18,000 BTU/HR [5.28 kW] 24 = 24,000 BTU/HR [7.03 kW] 30 = 30,000 BTU/HR [8.79 kW] 36 = 36,000 BTU/HR [10.55 kW] 42 = 42,000 BTU/HR [12.31 kW] 48 = 48,000 BTU/HR [14.07 kW] 60 = 60,000 BTU/HR [17.58 kW]
SEER HEAT PUMP BRAND
5
Page 6
GENERAL INFORMATION
“ L”
“W”
“H”
A
I
R
D
I
S
C
H
A
R
G
E
ALLOW 60” [1524mm]
OF CLEARANCE
AIR INLET LOUVERS ALLOW
6” [152mm] Min. OF CLEARANCE ALL SIDES
12” [305mm] RECCOMMENDED
SERVICE PANELS/
INLET CONNECTIONS / HIGH & LOW
VOLTAGE ACCESS
ALLOW 24” [ 610 mm] OF CLEARANCE
ST-A1226-02-00
DIMENSIONAL DATA
Specifications
General Information
AIR INLET LOUVERS ALLOW 6" [152 mm] OF CLEARANCE ALL SIDES 12" [305 mm] RECOMMENDED
ALLOW 60" [1524mm] OF
CLEARANCE
SERVICE PANELS/ INLET CONNECTIONS / HIGH & LOW VOLTAGE ACCESS ALLOW 24" [610 mm] OF CLEARANCE
CONDENSING UNIT MODEL
LENGTH “H” (INCHES)
LENGTH “L” (INCHES)
WIDTH “W” (INCHES)
Proper Installation
Proper sizing and installation of this equipment is critical to achieve optimal performance� Use the information in this Installation Instruction Manual and reference the applicable manufacturer’s specification sheet when installing this product�
IMPORTANT: This product has been
designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate indoor components� However, proper refrigerant charge and proper airflow are critical to achieve rated capacity and efficiency� Installation of this product should follow the manufacturer’s refrigerant charging and airflow instructions� Failure to confirm proper charge
and airflow may reduce energy efficiency and shorten equipment life�
RA14
0
18, 24
25
19" 19" 29"23" 33"
29.75
351⁄2" 401⁄2" 4438"4438" 4438"
29.75
2434"
18
0
30 27
29.75
29.75
2758"
36, 42
27
33.75
33.75
49043/037 060
48 31
33.75
33.75
311⁄2"311⁄2" 311⁄2"
35.75
35.75
MATCH ALL COMPONENTS:
• OUTDOOR UNIT
• INDOOR COIL
• INDOOR AIR HANDLER/FURNACE
• REFRIGERANT LINES
• INDOOR THERMOSTAT
60 35
6
Page 7
Choosing a Location
INSTALLATION
IMPORTANT:
national building codes and ordinances for special installation requirements� Following location information will provide longer life and simplified servicing of the outdoor unit�
Consult local and
NOTICE: These units must be installed
outdoors� No ductwork can be attached, or other modifications made, to the discharge grille� Modifications will affect performance or operation�
Operational Issues
IMPORTANT: Locate the unit
in a manner that will not prevent, impair, or compromise the performance of other equipment installed in proximity to the unit� Maintain all required minimum distances to gas and electric meters, dryer vents, and exhaust and inlet openings� In the absence of national codes or manufacturers’ recommendations, local code recommendations and requirements will take precedence�
• Refrigerant piping and wiring should be properly
sized and kept as short as possible to avoid capacity losses and increased operating costs�
• Locate the unit where water runoff will not create
a problem with the equipment� Position the unit away from the drip edge of the roof whenever possible� Units are weatherized, but can be affected by the following:
• Water pouring into the unit from the junction
of rooflines, without protective guttering� Large volumes of water entering the unit while in operation can impact fan blade or motor life, and coil damage may occur if moisture cannot drain from the unit under freezing conditions�
• Closely follow the clearance recommendations
on page 8�
• 24" [61.0 cm] to the service panel access
• 60" [152.4 cm] above fan discharge (unit top)
to prevent recirculation
• 6" [15.2 cm] to coil grille air inlets with 12" [30.5 cm] minimum recommended
Corrosive Environment
The metal parts of this unit may be subject to rust or deterioration if exposed to a corrosive environment� This oxidation could shorten the equipment’s useful life�
Corrosive elements include, but are not limited to, salt spray, fog or mist in seacoast areas, sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries�
If the unit is to be installed in an area where contaminants are likely to be a problem, special attention should be given to the equipment location and exposure�
• Avoid having lawn sprinkler heads spray directly
on the unit cabinet�
• In coastal areas, locate the unit on the side of
the building away from the waterfront�
• Shielding provided by a fence or shrubs may
give some protection, but cannot violate minimum airflow and service access clearances�
• Elevating the unit off its slab or base enough to
allow air circulation will help avoid holding water against the base pan�
WARNING: Disconnect all power
to unit before starting maintenance� Failure to do so can cause electrical shock resulting in severe personal injury or death�
Regular maintenance will reduce the buildup of contaminants and help to protect the unit’s finish�
• Frequent washing of the cabinet, fan blade, and
coil with fresh water will remove most of the salt or other contaminants that build up on the unit�
• Regular cleaning and waxing of the cabinet with
a good automobile polish will provide some protection�
• A good liquid cleaner may be used several times
a year to remove matter that will not wash off with water�
Location
7
Page 8
INSTALLATION
6” MIN. [152mm] FOR 1.5 & 2 TON
9”MIN [229mm] FOR 2.5 – 5 TON
24” [610mm]
SERVICE PANELS/INLET CONNECTIONS/
HIGH & LOW VOLTAGE ACCESS
ALLOW 24” [610 mm] OF CLEARANCE
ALLOW 60” [1524 mm]
OF CLEARANCE
AIR INLET LOUVERS ALLOW
6” [152 mm] Min. OF
CLEARANCE ALL SIDES
12” [305 mm] RECOMMENDED
ST-A1226-04-00
Choosing a Location (cont�)
Location
For Units With Space Limitations
In the event that a space limitation exists, we will permit the following clearances:
Single-Unit Applications: Side clearances below 6" [15.2 cm] will reduce unit capacity and efficiency. Do not reduce the 60" [152.4 cm] discharge or the 24" [61.0 cm] service clearances.
Multiple-Unit Applications: When multiple
condenser grille sides are aligned, a 6" [15.2 cm] clearance is recommended for 1.5 and 2 ton models and 9" [22.9 cm] for 2.5 ton to 5 ton
models� Two combined clearances below the minimum will reduce capacity and efficiency� Do
not reduce the 60" [152.4 cm] discharge or 24" [61.0 cm] service clearances.
• If installing a unit on a flat roof, use 4" x 4" [10.2 cm x 10.2 cm] or equivalent stringers
positioned to distribute unit weight evenly and prevent noise and vibration�
Factory-Preferred Tie-Down Method for High Wind or Seismic Loads
IMPORTANT: The manufacturer-
approved/recommended method is a guide to securing equipment for wind and seismic loads� Other methods might provide the same result, but the manufacturer method is the only one endorsed by the manufacturer for securing equipment where wind or earthquake damage can occur� Additional information is available in the PTS (Product Technical Support) section of the manufacturer’s Web sites MyRheem�com or MyRuud�com and can be found as a listing under each outdoor model� If you do not have access to this site, your distributor can offer assistance�
Customer Satisfaction Issues
• The unit should be located away from the living,
sleeping, and recreational spaces of the owner and those spaces on adjoining property�
• To prevent noise transmission, the mounting pad
for the outdoor unit should not be connected to the structure and should be located a sufficient distance above grade to prevent ground water from entering the unit�
Unit Mounting
WARNING: Secure an elevated unit
and its elevating stand in order to prevent tipping� Failure to do so may result in severe personal injury or death�
8
Page 9
Tools and Refrigerant
Ambient and Tube
Thermometers
Manifold
Gauge
Set
Brazing
Rods
Torch Nitrogen
Reclaimer
Recovery Cylinders
Allen Wrench
Crescent Wrench
INSTALLATION
Tools Required for Installing and Servicing R-410A Models
Manifold Sets: – Up to 800 PSIG High-Side – Up to 250 PSIG Low-Side – 550 PSIG Low-Side Retard Manifold Hoses: – Service Pressure Rating of 800 PSIG Recovery Cylinders: – 400 PSIG Pressure Rating – Dept� of Transportation 4BA400 or BW400
CAUTION: R-410A systems operate
at higher pressures than R-22 systems� Do not use R-22 service equipment or components on R-410A equipment�
Specifications of R-410A
Application: R-410A is not a drop-in replacement for R-22� Equipment designs must
accommodate its higher pressures� It cannot be retrofitted into R-22 heat pumps�
Physical Properties: R-410A has an atmospheric
boiling point of -62.9°F [-52.7°C] and its saturation pressure at 77°F [25°C] is 224.5 psig.
Composition: R-410A is a near-azeotropic mixture of 50% by weight difluoromethane (HFC-
32) and 50% by weight pentafluoroethane (HFC-
125)�
Pressure: The pressure of R-410A is approximately 60% (1�6 times) greater than R-22� Recovery and recycle equipment, pumps,
hoses, and the like must have design pressure ratings appropriate for R-410A� Manifold sets
need to range up to 800 psig high-side and 250 psig low-side with a 550 psig low-side retard. Hoses need to have a service pressure rating of 800 psig. Recovery cylinders need to have a 400 psig service pressure rating, DOT 4BA400 or DOT BW400.
Combustibility: At pressures above 1 atmosphere, a mixture of R-410A and air can become combustible� R-410A and air should
never be mixed in tanks or supply lines or be allowed to accumulate in storage tanks� Leak checking should never be done with a mixture of R-410A and air� Leak-checking can
be performed safely with nitrogen or a mixture of R-410A and nitrogen�
Quick-Reference Guide For R-410A
• R-410A refrigerant operates at approximately
60% higher pressure (1�6 times) than R-22� Ensure that servicing equipment is designed to operate with R-410A�
• R-410A refrigerant cylinders are light rose in
color�
• R-410A, as with other HFCs, is only compatible
with POE oils�
• Vacuum pumps will not remove moisture from
POE oil used in R-410A systems�
• R-410A systems are to be charged with liquid
refrigerants� Prior to March 1999, R-410A refrigerant cylinders had a dip tube� These cylinders should be kept upright for equipment charging� Post-March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment�
• Do not install a suction line filter drier in the
liquid line�
• A factory-approved biflow liquid line filter drier
is shipped with every unit and must be installed in the liquid line at the time of installation� Only manufacturer-approved liquid line filter driers can be used� These are Sporlan (CW083S) and Alco (80K083S) driers� These filter driers are rated for minimum working pressure of 600 psig� The filter drier will only have adequate moisture-holding capacity if the system is properly evacuated�
• Desiccant (drying agent) must be compatible for
POE oils and R-410A refrigerant�
Tools
9
Page 10
INSTALLATION
Replacement Units
To prevent failure of a new unit, the existing line set must be correctly sized and cleaned or replaced� Care must be exercised that the expansion device is not plugged� For new and replacement units, a liquid line filter drier must be installed and refrigerant tubing must be properly sized� Test the oil for acid� If positive, a suction line filter drier is mandatory�
Indoor Coil
CAUTION: Only use evaporators
approved for use on R-410A systems that are specifically matched with the outdoor unit per the manufacturer’s specification sheets� Use of existing R-22 evaporators can introduce mineral oil to the R-410A refrigerant, forming two different liquids and decreasing oil return to the compressor� This can result in compressor failure�
REFER TO INDOOR COIL MANUFACTURER’S INSTALLATION INSTRUCTIONS.
IMPORTANT: The manufacturer is not
responsible for the performance and operation of a mismatched system or for a match listed with another manufacturer’s coil�
IMPORTANT: When replacing an
R-22 unit with an R-410A unit, either replace the line set or ensure that residual mineral oil is drained from existing lines, including oil trapped in low spots�
The thermostatic expansion valve in the matching coil is specifically designed to operate with R-410A� DO NOT use an R-22 TXV or
evaporator� The existing evaporator must be replaced with the factory-specified TXV evaporator specifically designed for R-410A�
Location
Do not install the indoor coil in the return duct system of a gas or oil furnace� Provide a service inlet to the coil for inspection and cleaning� Keep the coil pitched toward the drain connection�
CAUTION: When coil is installed
over a finished ceiling and/or living area, it is required that a secondary condensate pan be installed under entire unit� Failure to do so can result in property damage�
Tubing
10
Interconnecting Tubing
The purpose of this section is to specify the best construction/sizing practices for installing interconnection tubing between the indoor and outdoor unit�
Refrigerant Level Adjustment
All units are factory-charged with R-410A refrigerant to cover 15 feet of standard size interconnecting liquid and vapor lines with a
required eld installed lter drier. Adjustment of
charge may be necessary even if the application has exactly 15 feet of line set due to other installation variables such as pressure drop,
vertical lift, and indoor coil size. For dierent
lengths, adjust the charge as indicated below� adjust the charge as indicated below�
• 1/4” ± .3 oz./foot [6.4 mm ± 8.5 g/.30 m]
• 5/16” ± .4 oz./foot [7.9 mm ± 11.3 g/.30 m]
• 3/8” ± .6 oz./foot [9.5 mm ± 17.0 g/.30 m]
• 1/2” ± 1.2 oz./foot [12.7 mm ± 34.0 g/.30 m]
• 6 oz. Required factory supplied eld installed
lter dry
Charge Adjustment = (Line Set (oz. /ft.) x Total Length) – Factory Charge for Line Set
Example: A three ton condensing unit with factory
installed 3/8” liquid service valve
requires 75 ft of line set with a liquid line diameter
of 1/2”.
Factory Charge for Line Set = 15ft x �6 oz� = 9 oz� Charge Adjustment = (1�2 oz� x 75 ft�) – 9 oz� =
+81 oz�
Page 11
Interconnecting Tubing (cont�)
INSTALLATION
Interconnecting Tubing and Fitting Losses
Refrigerant tubing is measured in terms of actual length and equivalent length� Actual length is used for refrigerant charge applications� Equivalent length takes into account pressure losses from
Equivalent Length for Fings ()
90° Short
Line Size
(in)
3/8 1.3 0.8 0.3 6 4 0.4 6 1/2 1.4 0.9 0.4 9 5 0.6 6 5/8 1.5 1 0.5 12 6 0.8 6 3/4 1.9 1.3 0.6 14 7 0.9 6 7/8 2.3 1.5 0.7 15 8 1 6
1-1/8 2.7 1.8 0.9 22 12 1.5 6
Radius
Elbow
90° Long
Radius
Elbow
45°
Elbow
Liquid Line Selection
The purpose of the liquid line is to transport warm sub-cooled liquid refrigerant from the outdoor unit to the indoor unit� It is important not to allow the
refrigerant to ash any superheated vapor prior
to the expansion device of the indoor coil� The
ashing of refrigerant can occur for the following
reasons:
• Low refrigerant charge
• Improperly selected liquid line size
• Absorption of heat prior to expansion device
• Excessive vertical rise between the condenser
and evaporator
tubing length, ttings, vertical separation, acces­sories, and lter dryers. The table below references dierent commonly used equivalent lengths.
Table 1
Solenoid
Valve
Table 2 lists the equivalent length per 25’ of liquid line at various diameters up to 300’� The total pres­sure drop allowed for the liquid line is 50 PSI� The procedure for selecting the proper liquid line is as follows:
• Measure the total amount of vertical rise
• Measure the total amount of liquid line needed
• Add all of the equivalent lengths associated with any ttings or accessories using the table above.
• Add the total length and tting pressure drop.
This will equal your total equivalent length�
• Reference Table 2 to verify the calculated
equivalent length is compatible with the required vertical rise and diameter of liquid line�
Check
Valve
Site
Glass
Filter
Dryer
Tubing
Note: Elevaon is defined as the
highest point of the line set to the
lowest
11
Page 12
INSTALLATION
Interconnecting Tubing (cont�)
Example: A 3-Ton condensing unit is installed 50’
below the ID unit, requires a 75’ of 1/2” diameter
liquid line, and 4 90° LR elbows�
• Fitting Equivalent Length (ft�) = 4 x �9 = 3�6’
• Total Equivalent Length (ft.) = 75’ + 3.6’ = 78.6’
Tubing
Liquid Line
R-410A
System
Capacity
Model
(excerpt fromTable 2, page 16)
Size
Connection
Size (Inch I.D.) [mm]
37 3/8" [9.53]
Liquid Line
Size (Inch
O.D.) [mm]
1/4 [6.35] 25 [7.62]
5/16 [7.94] 25 [7.62] 50 [15.24] 60 [18.29] 45 [13.72] 35 [10.67] 20 [6.1] 5 [1.52]
3/8 [9.53] 25 [7.62] 50 [15.24] 75 [22.86] 80 [24.38] 80 [24.38] 75 [22.86] 70 [21.34] 65 [19.81] 60 [18.29] 55 [16.76] 50 [15.24] 45 [13.72]
7/16 [11.12] 25 [7.62] 50 [15.24] 75 [22.86] 95 [28.96] 90 [27.43] 90 [27.43] 85 [25.91] 85 [25.91] 85 [25.91] 80 [24.38] 80 [24.38] 80 [24.38]
1/2 [12.71] 25 [7.62] 50 [15.24] 75 [22.86] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 95 [28.96] 90 [27.43] 90 [27.43] 90 [27.43]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72] 175 [53.34] 200 [60.96] 225 [68.58] 250 [76.20] 275 [83.82] 300 [91.44]
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
This application is acceptable because the 50’ vertical rise is less than the maximum rise of 75’ for this application� The application is also considered to have a long line set� Reference the long line set section of the I&O for detail�
Long Line Set Applications
Long line set applications are dened as ap­plications that require accessories or alternate construction methods� The following are special considerations that need to be addressed when installing a long line set application:
• Additional refrigerant charge
• Fitting losses and maximum equivalent length
considerations
• Refrigerant migration during the o cycle
• Oil return to the compressor
• Capacity losses
• System oil level adjustment
Table 2 is used to determine if the application is
considered to have a long line set� The region of
the chart that is shaded grey is considered to be a long line set application.
Liquid Line Size
Elevation (Above or Below) Indoor Coil
Total
Maximum
Length - Feet [m]
Equivalent
Vertical Separation - Feet [m]
N/R N/R N/R N/R N/R
Oil Level Adjustments for Long Line Set Applications
Additional oil will need to be added for long line set applications� (Ref� Table 2)� Below is the equation for the oil level adjustment and the compressor
name plate oil charge for the dierent od units.
OD Model
RP1518
RP1524
RP1530
RP1536
RP1542
RP1548
RP1560
Compressor
ZP16K5E-PFV-13R 21 ZP21K5E-PFV-13R 21 ZP25K5E-PFV-13R 25 ZP31K6E-PFV-130 21 ZP36K5E-PFV-13R 42 ZP40K6E-PFV-130 42 ZP49K6E-PFV-130 42
Oil to be Added = [(Charge Adjustment + OD
Unit Name Plate Charge (oz.)) x (0.022) – [(0.10) x (Compressor Name Plate Oil Charge (oz.))]
Example: An application requires 125ft of line set
with a liquid line diameter of 3/8”, Charge Adjust­ment = 52�4 oz�, Name Plate Charge = 107 oz�, Name Plate Oil Charge = 25 oz�, Oil to be Added = ((52�4 oz� +107 oz�) x �022) – (�10 x 25 oz�) = 1�0 oz�
Name Plate Oil
Charge (oz)
12
Page 13
Interconnecting Tubing (cont�)
Outdoor and Indoor Same Level
INSTALLATION
Suction Line Selection
Purpose of the suction line is to return superheated vapor to the condensing unit from the evaporator� Proper suction line sizing is important because it plays an important role in returning oil to the com­pressor to prevent potential damage to the bear­ings, valves, and scroll sets� Also, an improperly sized suction line can dramatically reduce capacity and performance of the system� The procedure for selecting the proper suction line is as follows:
• The total amount of suction line needed
• Add all of the equivalent lengths associated with any ttings or accessories using the table on
previous page�
• Add the total length and tting pressure drop.
This will equal your total equivalent length�
• Reference Table 2 to verify that the calculated
equivalent length falls within the compatibility region of the chart�
• Verify Table 3 to verify the capacity dierence is
compatible with the application�
Refrigerant Migration During Off Cycle
Long line set applications can require a consider­able amount of additional refrigerant� This addition­al refrigerant needs to be managed throughout the entire ambient operating envelope that the system will go through during its life cycle. O-Cycle mi­gration is where excess refrigerant condenses and migrates to the lowest part of the system� Exces­sive build-up of refrigerant at the compressor will result in poor reliability and noisy operation during startup� This section demonstrates the required accessories and unit conguration for dierent ap­plications�
Ideally, line set slopes
away from outdoor.
Verify sub-cooling prior
to throling device,
Insulated liquid line
Tubing
Reference Table 2 for
maximum length
limitaons
Figure 3
13
Page 14
INSTALLATION
Indoor Unit Above Outdoor Coil
Interconnecting Tubing (cont�)
For applications that are considered to have a long line set with the outdoor unit and indoor unit on the same level the following is required:
• TXV or EEV on the indoor unit
• Start components may be required depending
upon quality of voltage
• Crankcase heater
• Insulated liquid and suction line
Inverted trap even with
top of the coil
• Vapor line should slope toward the indoor unit
• Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments spelled out in this document and the outdoor units I&O
• Verify adequate sub-cooling at the ID unit prior
to throttling device
Insulated liquid and
sucon line
Reference Table 2
for elevaon
limitaons
Tubing
For applications that are considered to have a long line set with the outdoor unit below the indoor unit the following is required:
• TXV or EEV at the IDunit
• Crankcase heater
• Start components may be required depending
upon quality of voltage
• Inverted vapor-line trap (Reference Figure 3)
• Insulated liquid and suction line
Figure 4
• Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments spelled out in this document and the outdoor units I&O
• Measure pressure at the liquid line service valve
and prior to expansion device� Verify that it is not greater than 50 PSI
• For elevations greater that 25’ can expect a
lower sub-cooling
14
Page 15
p
g
Outdoor Unit Above Indoor Unit
Interconnecting Tubing (cont�)
INSTALLATION
Verify sub-cooling prior
to throlin
device
Insulated liquid and
sucon line
TXV or EEV at indoor
eva
Figure 5
Reference Table 2
for elevaon
limitaons
Tubing
orator
For applications that are considered to have a long line set with the outdoor unit above the indoor unit the following is required:
• TXV at the indoor unit
• Crankcase heater
• Start components maybe required depending
upon quality of voltage
• Insulated liquid and suction line
• Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments spelled out in this document and the outdoor units I&O
• Verify adequate sub-cooling at the ID unit prior
to throttling device
15
Page 16
Grey = Considered a Long Line Se t Application.
NOTES:
N
Tubing
N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R
Maximum
N/R N/R N/R N/R N/R N/R
Elevation Above or Below Indoor Coil
Equivalent
Liquid Line Size
16
N/R N/R
N/R N/R N/R N/R
N/R N/R
Page 17
NOTES:
N/R = Application not recommended.
60 3/8" [9.53]
48 3/8" [9.53]
42 3/8" [9.53]
36 3/8" [9.53]
30 3/8" [9.53]
24 3/8" [9.53]
18 3/8" [9.53]
1-1/8 [28.58] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1 [25.4] 1.00 1.00 1.00 1.00 0.99 N/R N/R N/R N/R N/R N/R N/R
7/8 [22.23] 1.00 0.99 0.99 0.98 0.98 N/R N/R N/R N/R N/R N/R N/R
3/4 [19.05] 0.99 0.98 0.96 0.95 0.94 N/R N/R N/R N/R N/R N/R N/R
5/8 [15.88] 0.97 0.94 0.91 0.89 0.87 N/R N/R N/R N/R N/R N/R N/R
1-1/8 [28.58]
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1 [25.4] 1.00 1.00 0.99 0.99 0.99 0.98 0
.98 0.98 0.98 0.98 N/R N/R
7/8 [22.23] 1.00 1.00 0.98 0.98 0.97 0.97 0.97 0.97 0.96 0.96 N/R N/R
3/4 [19.05] 0.99 0.98 0.97 0.96 0.96 0.95 0.94 0.93 0.92 0.92 N/R N/R
5/8 [15.88] 0.98 0.95 0.93 0.92 0.9 0.88 0.86 0.85 0.84 0.82 N/R N/R
1-1/8 [28.58] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1 [25.4]
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1-1/8 [28.58] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
5/8 [15.88] 1.00 0.97 0.95 0.93 0.92 0.91 0.9 0.89 0.87 0.85 0.85 0.84
3/4 [19.05] 1.00 1.00 0.99 0.99 0.97 0.97 0.97 0.95 0.95 0.95 0.94 0.93
7/8 [22.23] 1.00 1.00 1.01 1.00 1.00 0.99 0.99 0.99 0.99 0.98 0.98 0.98
1 [25.4]
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1-1/8 [28.58] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
5/8 [15.88] 0.99 0.98 0.97 0.96 0.95 0.93 0.93 0.91 0.9 0.9 0.89 0.88
3/4 [19.05] 1.00 1.00 0.99 0.99 0.98 0.99 0.99 0.97 0.98 0.97 0.96 0.96
7/8 [22.23] 1.01 1.01 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.99 0.99 0.98
1 [25.4] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
7/8 [22.23] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1-1/8 [28.58]
5/8 [15.88] 1.00 0.98 0.97 0.97 0.95 0.95 0.94 0.93 0.93 0.92 0.92 0.91
3/4 [19.05] 1.00 1.00 0.99 0.99 0.99 0.98 0.98 0.98 0.97 0.97 0.97 0.96
1 [25.4] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
7/8 [22.23] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
3/4 [19.05] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1-1/8 [28.58]
5/8 [15.88] 0.99 1.00 0.99 0.98 0.97 0.97 0.96 0.95 0.94 0.94 0.93 0.94
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
1 [25.4] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
7/8 [22.23] N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
5/8 [15.88] 1.00 0.99 0.99 0.98 0.98 0.98 0.97 0.97 0.96 0.96 0.96 0.95
3/4 [19.05] 1.00 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.99 0.99 0.99
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72] 175 [53.34] 200 [60.96] 225 [68.58] 250 [76.20] 275 [83.82] 300 [91.44]
Outdoor unit Above or Below Indoor Coil
Total Equivalent Length - Feet [m]
Suction Line Size
Tubing
17
Page 18
INSTALLATION
Interconnecting Tubing (cont�)
Tubing Installation
Observe the following when installing correctly
sized type “L” refrigerant tubing between the
condensing unit and evaporator coil:
• Check the tables on page 10 for the correct
suction line size and liquid line size�
• If a portion of the liquid line passes through a
very hot area where liquid refrigerant can be heated to form vapor, insulating the liquid line is required�
• Use clean, dehydrated, sealed refrigeration-
grade tubing�
• Always keep tubing sealed until tubing is in
place and connections are to be made�
• A high-quality filter drier is included with all
R-410A units and must be installed in the liquid line upon unit installation�
• When replacing an R-22 system with an R-410A
system and the line set is not replaced, drain any oil that has pooled in low spots in the
lineset� Commercially available flush kits are not recommended due to the risk of residual flushing agent being incompatible with POE oils or internal components� Up to 5% mineral oil is considered acceptable in R-410A systems�
• If tubing has been cut, make sure ends are
deburred while holding in a position to prevent chips from falling into tubing� Burrs such as those caused by tubing cutters can affect performance dramatically, particularly on small liquid line sizes�
• For best operation, keep tubing run as short as
possible with a minimum number of elbows or bends�
• Locations where the tubing will be exposed to
mechanical damage should be avoided� If it is necessary to use such locations, the copper tubing should be housed to prevent damage�
Tubing
18
Page 19
INSTALLATION
TEMPORARY
HANGER
PERMANENT
HANGER
ST-A1226-05-00
Interconnecting Tubing
• If tubing is to be run underground, it must be run
in a sealed watertight chase�
• Use care in routing tubing and do not kink or
twist� Use a good tubing bender on the vapor line to prevent kinking�
• Route the tubing using temporary hangers; then
straighten the tubing and install permanent hangers� Line must be adequately supported�
• If the vapor line comes in contact with inside
walls, ceiling, or flooring, the vibration of the vapor line in the heating mode will result in noise inside the structure�
(cont�)
• Be certain both refrigerant shutoff valves at the
outdoor unit are closed�
Remove the caps and Schrader cores from the pressure ports to protect seals from heat damage� Both the Schrader valves and the service valves have seals that may be damaged by excessive heat�
• Blow out the liquid and vapor lines with dry
nitrogen before connecting to the outdoor unit and indoor coil� Any debris in the line set will end up plugging the expansion device�
Tubing Connections
Indoor coils have only a holding charge of dry nitrogen� Keep all tube ends sealed until connections are to be made�
• Use type “L” copper refrigeration tubing. Braze
the connections with the following alloys:
– copper to copper, 5% silver minimum – copper to steel or brass, 15% silver minimum
Clean the inside of the fittings and outside of the tubing with a clean, dry cloth before soldering� Clean out debris, chips, dirt, etc�, that enters tubing or service valve connections�
Wrap valves with a wet rag or thermal barrier compound before applying heat�
Tubing
19
Page 20
INSTALLATION
ST-A1226-06-00
Interconnecting Tubing
Braze the tubing between the outdoor unit and indoor coil� Flow dry nitrogen into a pressure port and through the tubing while brazing, but do not allow pressure inside tubing which can result in leaks� Once the system is full of nitrogen, the nitrogen regulator should be turned off to avoid pressuring the system�
(cont�)
Leak Testing
Indoor coils have only a holding charge of dry nitrogen� Keep all tube ends sealed until connections are to be made�
WARNING: Do not use oxygen
to purge lines or pressurize system for leak test� Oxygen reacts violently with oil, which can cause an explosion resulting in severe personal injury or death�
ST-A1226-07-00
Tubing
• A
fter brazing, use an appropriate heatsink material
to cool the joint�
• Reinstall the Schrader cores into both pressure
ports�
• Do not allow the vapor line and liquid line to
be in contact with each other� This causes an undesirable heat transfer resulting in capacity loss and increased power consumption�
Pressurize line set and coil through service fittings with dry nitrogen to 150 PSIG maximum� Close nitrogen tank valve, let system sit for at least 15 minutes, and check to see if the pressure has dropped� If the pressure has dropped, check for leaks at the line set braze joints with soap bubbles and repair leak as necessary� Repeat pressure test� If line set and coil hold pressure, proceed with line set and coil evacuation (see page 21)�
• The vapor line must be insulated for its entire
length to prevent dripping (sweating) and prevent performance losses� Closed-cell foam insulation such as Armaflex and Rubatex® are satisfactory insulations for this purpose. Use 1/2" [12.7 mm] minimum insulation thickness� Additional insulation may be required for long runs�
20
Page 21
Control Wiring
WIRING
WARNING: Turn o electric power
at the fuse box or service panel before making any electrical connections� Also, the ground connection must be completed before making line voltage connections� Failure to do so can result in
electrical shock, severe personal injury, or death�
Control Wiring
Running low-voltage wires in conduit with line voltage power wires is not recommended� Low­voltage wiring may be run through the plastic
bushing provided in the 7/8" [19 mm] hole in the
base panel, up to and attached to the pigtails from the bottom of the control box� Conduit can be run to the base panel if desired by removing the insulated bushing�
A thermostat and a 24-volt, 40 VA minimum transformer are required for the control circuit of the system� The furnace or the air handler transformer may be used if sufficient� See the
wiring diagram for reference. Use “Wire Size” table
to size the 24-volt control wiring� Do not use phone cord to connect indoor and
outdoor units and thermostat� This could damage the controls and may not be adequately sized for the controls electrical load�
FIELD WIRE SIZE FOR 24-VOLT THERMOSTAT CIRCUITS
Thermostat
Load (amps)
3.0 18 16 14 12 10 10 10
2.5 18 16 14 12 10 10 10
2.0 18 16 14 12 10 10 10 20 50 100 150 200 250 300
[6] [15] [30] [46] [51] [76] [91]
(1) Wire length equals twice the run distance� NOTICE: Do not use control wiring smaller than No� 18
AWG between thermostat and outdoor unit�
SOLID COPPER WIRE –AWG.
Length of Run – Feet [m] (1)
CONTROL WIRING FOR GAS OR OIL FURNACE
TYPICAL THERMOSTAT
FOR TYPICAL GAS OR OIL HEAT
BR –BROWN WIRE
YL –YELLOW WIRE
X–WIRE CONNECTION
TYPICAL CONDENSING
UNIT
YL
X
BR
X
IF MAXIMUM OUTLET TEMPERAT URE RISE IS DESIRED, IT IS RECOMMENDED THAT
*
W1 (W/BK) AND W2 (W/BL) BE JUMPERED TOGETHER.
FOR TYPICAL ELECTRIC HEAT
BR –BROWN WIRE
R–RED WIRE
YL –YELLOW WIRE
W/BK –WHITE WIRE WITH BLACK STRIPE
G/BK–GREEN WIRE WITH BLACK STRIPE
PU –PURPLE WIRE (NOT USED)
X–WIRE CONNECTION
TYPICAL CONDENSING
UNIT
YL
BR
*
X X
SUBBASE
YGWR
TYPICAL GAS OR
OIL FURNACE
R
W
G
Y
C
TYPICAL THERMOSTAT
SUBBASE
YGWR
TYPICAL ELECTRIC HEAT
LOW VOLTAGE JUNCTION BOX
W/BL
X X
W/BK
X
G/BK
X X
X
YL
BR PU
R
Wiring
Typical Noncommunicating Thermostat Wiring Diagrams
The following figures show the typical wiring diagrams� Cooling airflows may need to be adjusted for homeowner comfort once the system is operational�
WIRE COLOR CODE
BK – BLACK GY – GRAY W – WHITE BR – BROWN O – ORANGE Y – YELLOW BL – BLUE PR – PURPLE G – GREEN R – RED
21
Page 22
WIRING
ST-A1226-09
ST-A1226-09
Control Wiring (cont�)
Field wiring must comply with the National Electric Code (C�E�C� in Canada) and any applicable local code�
Power Wiring
It is important that proper electrical power from a commercial utility is available at the compressor contactor� Voltage ranges for operation are shown below�
VOLTAGE RANGES (60 HZ)
Nameplate
Voltage
208/230 187 - 253 (1 Phase)
208/230 187 - 253 (3 Phase)
460 414 - 506 575 517 - 633
Install a branch circuit disconnect within sight of the unit and of adequate size to handle the starting
current (see “Electrical Data” on page 5�)
Operating Voltage Range at
Copeland Maximum Load Design
Conditions for Compressors
Connect power wiring to line-voltage lugs located in the outdoor unit electrical box� (See wiring diagram attached to unit access panel�)
Check all electrical connections, including factory wiring within the unit and make sure all connections are tight�
DO NOT connect aluminum field wire to the contactor terminals�
Grounding
WARNING: The unit must be
permanently grounded� Failure to do so can cause electrical shock resulting in severe personal injury or death�
Wiring
22
Power wiring must be run in a rain-tight conduit� Conduit must be run through the connector panel below the access cover (see page 6) and attached
to the bottom of the control box�
A grounding lug is provided near the line-voltage power entrance for a ground wire�
Page 23
Start-Up
At initial start-up or after extended shutdown periods, make sure the crankcase heater is energized for at least 12 hours before the compressor is started� (Disconnect switch is on and wall thermostat is off�)
Checking Airflow
START-UP
Even though the unit is factory-charged with Refrigerant-410A, the charge must be checked to the charge table attached to the service panel and adjusted, if required� Allow a minimum of 15 minutes of run time before analyzing charge�
CAUTION: Single-pole contactors
are used on all standard single-phase units through 5 tons� Caution must be exercised when servicing as only one leg of the power supply is broken by the contactor�
The air distribution system has the greatest effect on airflow� The duct system is totally controlled by the contractor� For this reason, the contractor should use only industry-recognized procedures�
The correct air quantity is critical to air conditioning systems� Proper operation, efficiency, compressor life, and humidity control depend on the correct balance between indoor load and outdoor unit capacity� Excessive indoor airflow increases the possibility of high humidity problems� Low indoor airflow reduces total capacity can cause coil icing� Serious harm can be done to the compressor by low airflow, such as that caused by refrigerant flooding�
Air conditioning systems require a specified airflow� Each ton of cooling requires between 320 and 450 cubic feet of air per minute (CFM)� See the manufacturer’s spec sheet for rated airflow for the system being installed�
Duct design and construction should be carefully done� System performance can be lowered dramatically through bad planning or workmanship�
Air supply diffusers must be selected and located carefully� They must be sized and positioned to deliver treated air along the perimeter of the space� If they are too small for their intended airflow, they become noisy� If they are not located properly, they cause drafts� Return air grilles must be properly sized to carry air back to the blower� If they are too small, they also cause noise�
The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home� This ensures a comfortable living space�
These simple mathematical formulas can be used to determine the CFM in a residential or light commercial system�
Electric resistance heaters can use: CFM = volts x amps x 3�413 SHC x temp rise Gas furnaces can use: CFM = Output Capacity in BTUH* SHC x temp rise
*Refer to furnace data plate for furnace output capacity� SHC = Sensible Heat Constant (see table below)
An air velocity meter or airflow hood can give a more accurate reading of the system CFM�
The measurement for temperature rise should be performed at the indoor coil inlet and near the outlet, but out of direct line of sight of the heater element or heat exchanger� For best results, measure air temperature at multiple points and average the measurements to obtain coil inlet and outlet temperatures�
ALTITUDE
(FEET)
Sea Level 1�08 6000 0�87
500
1000
2000
3000
4000
5000 0�90 20000 0�50
SENSIBLE HEAT
CONSTANT
(SHC)
1�07 7000 0�84
1�05 8000 0�81
1�01 9000 0�78
0�97 10000 0�75
0�94 15000 0�61
ALTITUDE
(FEET)
SENSIBLE HEAT
CONSTANT
(SHC)
Airflow Start-Up
23
Page 24
START-UP
ST-A1226-08-00
Evacuation
Evacuation and Leak Testing
Evacuation Procedure
Evacuation is the most important part of the entire service procedure� The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air and moisture from the system�
Air or nitrogen in the system causes high condensing temperatures and pressure, resulting in increased power input and nonverifiable performance�
Moisture chemically reacts with the refrigerant and oil to form corrosive hydrofluoric acid� This attacks motor windings and parts, causing breakdown�
• Gauges must be connected at this point to
IMPORTANT: Compressors
(especially scroll type) should never be used to evacuate the air conditioning system because internal electrical arcing may result in a damaged or failed compressor� Never run a scroll compressor while the system is in a vacuum or compressor failure will occur�
Final Leak Testing
After the unit has been properly evacuated and service valves opened, a halogen leak detector should be used to detect leaks in the system� All piping within the condenser, evaporator, and
• After the system has been leak-checked and
proven sealed, connect the vacuum pump and evacuate system to 500 microns and hold 500 microns or less for at least 15 minutes� The vacuum pump must be connected to both the high and low sides of the system by connecting to the two pressure ports� Use the largest size connections available since restrictive service connections may lead to false readings because of pressure drop through the fittings�
interconnecting tubing should be checked for leaks� If a leak is detected, the refrigerant should be recovered before repairing the leak� The Clean Air Act prohibits releasing refrigerant into the atmosphere�
check and adjust charge� Do not replace caps yet�
• After adequate evacuation, open both service
valves by removing both brass service valve
caps with an adjustable wrench. Insert a 3/16" [5 mm] or 5/16" [8 mm] hex wrench into the
stem and turn counterclockwise until the wrench stops�
24
Page 25
Checking Refrigerant Charge
START-UP
Charge for all systems should be checked against the Charging Chart inside the access panel cover�
WARNING:
compressor shell is hot� Touching the compressor top may result in serious personal injury�
The top of the scroll
IMPORTANT: Use factory-approved
charging method as outlined on the next page to ensure proper system charge�
NOTICE: The optimum refrigerant charge
for any outdoor unit matched with an indoor coil/air handler is affected by the application� Therefore, charging data has been developed to assist the field technician in optimizing the charge for all mounting configurations (UF – Upflow, DF – Downflow, LH – Left-Hand Discharge, and RH – Right-Hand Discharge)� Refer to the charging chart inside the access panel cover on the unit and choose the appropriate column for the specific application being installed or serviced�
Charging Units With R-410A Refrigerant
CAUTION:
approximately 60% higher (1�6 times) than R-22 pressures� Use appropriate care when using this refrigerant� Failure to exercise care may result in equipment damage or personal injury�
Charge for all systems should be checked against the Charging Chart inside the access panel cover�
R-410A pressures are
IMPORTANT: Do not operate the
compressor without charge in the system� Addition of R-410A will raise high-side pressures
(liquid and discharge)�
NOTICE: System maintenance is to be
performed by a qualified and certified technician� The following method is used for charging systems
in the cooling mode� All steps listed should be performed to ensure proper charge has been set� For measuring pressures, the service valve port on the liquid valve (small valve) and suction valve (large valve) are to be used
Supply airflow must be between 320 and 450 cfm per rated cooling ton prior to adjusting system charge� If a humidification system is installed, disengage it from operation prior to charge
adjustment. Refer to the “Checking Airflow” section
of this manual for further instruction�
NOTICE: Verify system components
are matched according to the outdoor unit Specification Sheet�
Measurement Device Setup
1� With an R-410A gauge set, attach the high-
pressure hose to the access fitting on the liquid (small) service valve at the OD unit�
2�
Attach the low-pressure hose to the access fitting
on the suction (large) service valve�
3. Attach a temperature probe within 6" [15.2 cm]
outside of the unit on the copper liquid line (small line)� For more accurate measurements, clean the copper line prior to measurement and use a calibrated clamp-on temperature probe or an insulated surface thermocouple�
Charging by Weight
NOTICE:
weight for the straight length of the refrigerant line set� For a new installation, evacuation of inter-
connecting tubing and indoor coil is adequate;
otherwise, evacuate the entire system� Use the factory charge shown in “Electrical and Physical
Data” on page 5 of these instructions or on the
unit data plate� Note that the charge value includes
charge required for 15 ft. [4.6 m] of standard-size
interconnecting liquid line without a filter drier� Calculate actual charge required with installed
liquid line size and length using:
1/4" [6.4 mm] O.D. = .3 oz./ft. [8.5 g/.30 m] 5/16" [7.9 mm] O.D. = .4 oz./ft. [11.3 g/.30 m] 3/8" [9.5 mm] O.D. = .6 oz./ft. [17.0 g/.30 m] 1/2" [12.7 mm] O.D. = 1.2 oz./ft. [34.0 g/.30 m]
Add 6 oz� for field-installed filter drier�
Adjust the system charge by
Refrigerant
Confirm ID Airflow and Coils Are Clean
Confirm adequate indoor supply airflow prior to starting the system� See the Technical Specification Sheet for rated airflow for each ID/OD unit match� Air filter(s) and coils (indoor and outdoor) are to be clean and free of frost prior to starting the system�
25
Page 26
START-UP
Checking Refrigerant Charge (cont�)
Refrigerant
With an accurate scale (+/– 1 oz. [28.3 g]) or
volumetric charging device, adjust charge difference between that shown on the unit data plate and that calculated for the new system installation� If the entire system has been evacuated, add the total calculated charge�
IMPORTANT: Charging by weight is
not always accurate since the application can affect the optimum refrigerant charge� Charging by weight is considered a starting point ONLY� Always check the charge by using the Charging Chart and adjust as necessary� CHARGING BY LIQUID SUBCOOLING MUST BE USED FOR FINAL CHARGE ADJUSTMENT�
With thermostat in the “Off” position, turn on
the power to the furnace or air handler and the condensing unit� Start the condensing unit and the furnace or air handler with the thermostat� Verify that the outdoor unit is operating and the indoor air mover is delivering the correct airflow for the system size�
Gross Charging by Pressures
1� Following airflow verification and charge weigh-
in, run the unit for a minimum of 15 minutes prior to noting pressures and temperature�
IMPORTANT: Indoor conditions
as measured at the indoor coil must be within
2°F [1.1°C] of the following during gross charge
(pressure) evaluation:
Cooling Mode: 80°F [26.7°C] Dry Bulb Heating Mode: 70°F [21.1°C] Dry Bulb
NOTICE:
or below this range, run the system to bring the temperature down or run the electric heat/furnace to bring the temperature within this range� System pressure values provided in the Charging Chart for outdoor dry bulbs corresponding to conditions outside of these ranges are provided as reference ONLY�
If the Indoor temperature is above
2� Note the Outdoor Dry Bulb Temperature,
ODDB° = _____°F [_____°C]� Unit charging is recommended under the following outdoor conditions ONLY:
Cooling Mode ONLY: 55°F [12.8°C] outdoor dry
bulb and above
3� Locate and note the design pressures� The
correct liquid and vapor pressures are found at the intersection of the installed system and the outdoor ambient temperature on the Charging Chart located inside the access panel cover�
Liquid Pressure: = ______psig; Vapor Pressure =
______psig
NOTICE:
are for gross charge check ONLY� These pressure values are typical, but may vary due to application� Evaporator load (indoor coil in cooling mode/outdoor coil in heating mode) will cause pressures to deviate� Note that all systems have unique pressure curves� The variation in the slope and value is determined by the component selection for that indoor/outdoor matched system� The variation from system to system seen in the table is normal� The values listed are for the applicable indoor coil match ONLY!
4� If the measured liquid pressure is below the
listed requirement for the given outdoor and indoor conditions, add charge� If the measured liquid pressure is above the listed requirement for the given outdoor and indoor conditions, remove charge�
The refrigerant pressures provided
Final Charge by Subcooling
1� After gross charging, note the designed
subcooling value� The correct subcooling value is found at the intersection of the installed system and the outdoor ambient temperature on the Charging Chart located inside the access panel cover�
SC° from Charging Chart = _____°F [_____°C].
IMPORTANT: Indoor conditions as
measured at the indoor coil are required to be
between 70°F [21.1°C] and 80°F [26.7°C] dry
bulb for fine-tuned unit charge adjustment� Unit charging is recommended under the following outdoor conditions ONLY:
Cooling Mode ONLY: 55°F [12.8°C] outdoor dry
bulb and above
26
Page 27
Checking Refrigerant Charge (cont�)
START-UP
NOTICE: If the indoor temperature is
above or below the recommended range, run the system to bring the temperature down or run the electric heat/furnace to bring the temperature up� System subcooling values provided in the Charging Chart for outdoor dry bulbs corresponding to conditions outside of the above range are provided as reference ONLY�
2� Note the measured Liquid Pressure, Pliq =
______psig, as measured from the liquid (small) service valve� Use the Temperature Pressure Chart below to note the corresponding saturation temperature for R-410A at the measured liquid pressure�
Liquid Saturation Temperature, SAT°= _____°F
[_____°C].
3� Note the liquid line temperature, Liq° = _____°F
[_____°C], as measured from a temperature probe located within 6" [15.2 cm] outside of
the unit on the copper liquid line (small line)� It is recommended to use a calibrated clamp­on temperature probe or an insulated surface thermocouple�
4�
Subtract the liquid line temperature from the
saturation temperature to calculate subcooling� SAT°_____°F SC°_____°F
5�
Adjust charge to obtain the specified subcooling
value� If the measured subcool is below the listed requirement for the given outdoor and indoor
[_____°C]
[_____°C]
- Liq°_____°F
[_____°C]
=
conditions, add charge� If the measured subcool is above the listed requirement for the given outdoor and indoor conditions, remove charge�
Finishing Up Installation
• Disconnect pressure gauges from pressure ports;
then replace the pressure port caps and tighten
adequately to seal caps� Do not overtighten.
• Replace the service valve caps finger-tight
and then tighten with an open-end wrench
adequately to seal caps� Do not overtighten.
• Replace control box cover and service panel and
install screws to secure service panel�
• Restore power to unit at disconnect if required.
• Configure indoor thermostat per the thermostat
installation instructions and set thermostat to desired mode and temperature�
NOTICE: Systems should not be fine-
tune charged below 40°F [4.4°C] outdoor dry bulb.
IMPORTANT: Excessive use of
elbows in the refrigerant line set can produce excessive pressure drop� Follow industry best practices for installation� Installation and commissioning of this equipment is to be performed by trained and qualified HVAC professionals� For technical assistance, contact
your Distributor Service Coordinator�
Refrigerant
TEMPERATURE PRESSURE CHART
SATURATION
TEMP
(Deg. F) [Deg.
C]
-150 [-101]
-140 [-96]
-130 [-90]
-120 [-84]
-110 [-79]
-100 [-73]
-90 [-68]
-80 [-62]
-70 [-57]
-60 [-51] 0�4 15 [-9] 70�2 80 [27] 235�6 145 [63] 576�0
-50 [-46] 5�1 20 [-7] 78�5 85 [29] 254�5 150 [66] 612�8
-40 [-40] 10�9 25 [-4] 87�5 90 [32] 274�3
-35 [-37] 14�2 30 [-1] 97�2 95 [35] 295�3
R-410A
PSIG
-30 [-34]
-25 [-32]
-20 [-29]
-15 [-26]
-10 [-23]
-5 [-21]
SATURATION
(Deg. F) [Deg.
10 [-12] 62�4 75 [24] 217�8 140 [60] 541�2
TEMP
C]
0 [-18] 48�4 65 [18] 185�1 130 [54] 476�5
5 [-15] 55�1 70 [21] 201�0 135 [57] 508�0
R-410A
PSIG
17�9 35 [2] 107�5 100 [38] 317�4
22�0 40 [4] 118�5 105 [41] 340�6
26�4 45 [7] 130�2 110 [43] 365�1
31�3 50 [10] 142�7 115 [46] 390�9
36�5 55 [13] 156�0 120 [49] 418�0
42�2 60 [16] 170�1 125 [52] 446�5
SATURATION
TEMP
(Deg. F) [Deg.
C]
R-410A
PSIG
SATURATION
TEMP
(Deg. F) [Deg.
C]
R-410A
PSIG
27
Page 28
COMPONENTS AND CONTROLS
Compressor Crankcase Heat (CCH)
Components
While scroll compressors usually do not require crankcase heaters, there are instances when a heater should be added� Refrigerant migration during the off cycle can result in a noisy start up� Add a crankcase heater to minimize refrigerant migration and to help eliminate any start up noise
or bearing “wash out.”
NOTE: A crankcase heater should be installed if:
• The system charge exceeds the values listed in
the adjacent tables,
• The system is subject to low voltage variations,
or
• When a low ambient control is used for system
operation below 55°F�
RA14 Charge Limit
ModelCompressorWithout Crankcase
Size Model Number Heat (1 Phase)
18 ZP14KAE 24 ZP20KAE 30 ZP24K5E 36 ZP29K5E 42 ZP34K5E 48 ZP39K5E 60 ZP49K6E
All heaters are located on the lower half of the compressor shell� Its purpose is to drive refrigerant from the compressor shell during long off cycles, thus preventing damage to the compressor during start-up�
At initial start-up or after extended shutdown periods, make sure the heater is energized for at least 12 hours before the compressor is started� (Disconnect switch is on and wall thermostat is off�)
9.6
9.6 lbs.
9.6
9.6 lbs.
9.6
9.6 lbs.
9.6
9.6 lbs.
12
12 lbs.
12
12 lbs.
12
12 lbs.
28
High- and Low-Pressure Controls (HPC and LPC)
HPC and LPC are not installed on RA14**AJINA, but can be field installed using the followiing kit numbers: RXAB-A0z (high pressure control) and RXAC-A0Z (low pressure control)� These controls keep the compressor from operating in pressure ranges which can cause damage to the compressor� Both controls are in the low-voltage control circuit�
The high-pressure control (HPC) is an automatic­reset which opens near 610 PSIG and closes near 420 PSIG�
The low-pressure control (LPC) is an automatic­reset which opens near 15 PSIG and closes near 40 PSIG�
CAUTION: The compressor has
an internal overload protector� Under some conditions, it can take up to 2 hours for this overload to reset� Make sure overload has had time to reset before condemning the compressor�
Page 29
ACCESSORIES
WARNING: Turn o electric power
at the fuse box or service panel before making any electrical connections� Also, the ground connection must be completed before making line voltage connections� Failure to do so can result in electrical shock, severe personal injury, or death�
CAUTION:
SINGLE POLE COMPRESSOR CONTACTOR (CC):
Single pole contactors are used on all single­phase units up through 5 tons� Caution must be exercised when servicing as only one leg of the power supply is broken with the contactor�
Hard Start Components
Time Delay Control (Part No. RXMD-B01)
The time delay control is in the low voltage control circuit� When the compressor shuts off due to a power failure or thermostat operation, this control keeps it off at least 5 minutes which allows the system pressure to equalize, thus not damaging the compressor or blowing fuses on start-up�
Low Ambient Control (LAC) (Part No. RXAD-A08)
This component senses compressor head pressure and shuts the heat pump fan off when the head pressure drops to approximately 250 PSIG� This allows the unit to build a sufficient head pressure at lower outdoor ambient (down to 0°F
[-18°C]) in order to maintain system balance and
obtain improved capacity� Low ambient control should be used on all equipment operated below 70°F [21°C} ambient�
Accessories
Start components are not usually required with the scroll compressors used in RA14 condensing units, but are available for special cases and where start components are desirable to reduce light dimming�
29
Page 30
DIAGNOSTICS
NO
YES
Thermostat
Problem?
Transformer
Problem?
Go to Mechanical Checks
for Cooling or Heating
Hi Pressure Cut-Out
Hot Gas Sensor
Compressor
Time-Delay
Unit Wiring and
Connections
Start Capacitor
Potential Relay
Compressor Internal
Overload Open
Unit Wiring and
Connections
Compressor Winding
Open
Unit
Running?
YES
Repair and
Recheck
YES
Repair and
Recheck
NO
Voltage on Compressor
Side of Contactor?
NO
YES
Run Capacitor
NO
Voltage on Line
Side of Contactor?
NO
Circuit Breakers or
Fuses Open
YES
Compressor Winding
Grounded
Outdoor Fan Motor
Grounded
Grounded Capacitor
Replace Fuses or Reset
Breakers and Recheck
System
YES
Compressor
Contactor
NO
Unit Wiring and
Connections
Electrical Checks Flowchart
Diagnostics
30
Page 31
YES
NO
Pressure
Problems?
Low Liquid
Pressure
Low Suction
Pressure
High Head
Pressure
Go to Electrical
Checks Flowchart
Dirty Filters
Dirty Indoor Coil
Inadequate Indoor
Airow
Inoperative Indoor
Blower
Low on Charge
Open IPR
Valve
Low Ambient
Temperature
Bad
Compressor
Outdoor Check
Valve Closed
Restricted Indoor
Metering Device
Restricted Filter Drier
Dirty Outdoor
Coil
Inoperative Outdoor
Fan
Overcharge
Recirculation of
Outdoor Air
Noncondensibles
Higher Than Ambient Air
Entering Outdoor Coil
Wrong Outdoor
Fan Rotation
Inadequate Ducts
Outdoor Check
Valve Closed
Restricted Filter Drier
Outdoor Unit
Running?
Low on Charge
Restricted Indoor
Metering Device
Restriction in
System
Recirculation of
Indoor Air
Wrong Indoor
Blower Rotation
Cooling Mechanical Checks Flowchart
DIAGNOSTICS
Diagnostics
31
Page 32
DIAGNOSTICS
General Troubleshooting Chart
Diagnostics
WARNING:
Disconnect all power to unit before servicing� Contactor may break only one side� Failure to shut off power can cause electrical shock resulting in personal injury or death�
SYMPTOM POSSIBLE CAUSE REMEDY
Unit will not run • Power o or loose electrical connection
• Thermostat out of calibration – set too high
• Defective control board
• Blown fuses/tripped breaker
• Transformer defective
• High-pressure control open
Low-pressure control open
• Miswiring of communications (communication
light on continuously)
Outdoor fan runs, compressor doesn't
Insucient cooling • Improperly sized unit
Compressor short cycles
Registers sweat • Low indoor airow • Increase speed of blower or reduce restriction.
High head, low vapor pressures
High head, high or normal vapor pressure – Cooling mode
Low head, high vapor pressures
Low vapor, cool compressor, iced indoor coil
High vapor pressure • Excessive load
Fluctuating head and vapor pressures
Gurgle or pulsing noise at expansion device or liquid line
• Run or start capacitor defective
• Contactor defective
• Loose connection
• Compressor stuck, grounded or open motor
winding, open internal overload�
• Low-voltage condition
• Improper indoor airow
• Incorrect refrigerant charge
• Air, noncondensibles, or moisture in system
• Bad ID TXV
• Incorrect voltage
• Defective overload protector
• Refrigerant undercharge
• Restriction in liquid line, expansion device, or lter drier
• Bad TXV
• Dirty outdoor coil
• Refrigerant overcharge
• Outdoor fan not running
• Air or noncondensibles in system
• Bad TXV
• Bad compressor
• Low indoor airow
• Operating below 65°F outdoors
• Moisture in system
• Closed ID circuit
• Defective compressor
• TXV hunting
• Air or noncondensibles in system
• Air or noncondensibles in system • Recover refrigerant. Evacuate and recharge.
• Check for correct voltage at line voltage connections in
condensing unit�
• Reset.
• Check control board diagnostic codes.
• Replace fuses/reset breaker.
• Check wiring. Replace transformer.
• Reset. Also see high head pressure remedy. The high-
pressure control opens at 610 PSIG�
• Check communication wiring.
• Replace.
• Replace.
• Check for correct voltage at compressor. Check and
tighten all connections�
• Wait at least 3 hours for overload to reset. If still open,
replace the compressor�
• Add start kit components.
• Recalculate load.
• Check. Should be approximately 400 CFM per ton.
• Charge per procedure attached to unit service panel.
• Recover refrigerant. Evacuate and recharge. Add lter
drier�
• Replace TXV
• At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating�
• Replace. Check for correct voltage.
• Add refrigerant.
Replace air lter.
• Remove or replace defective component.
• Replace TXV.
• Clean coil.
• Correct system charge.
• Repair or replace.
• Recover refrigerant. Evacuate and recharge.
• Replace TXV.
• Replace compressor.
• Increase speed of blower or reduce restriction. Replace air lter.
• Add Low Ambient Kit.
• Recover refrigerant. Evacuate and recharge. Add lter
drier�
• Repair or replace ID coil
• Recheck load calculation.
• Replace.
• Check TXV bulb clamp. Check air distribution on coil.
Replace TXV�
• Recover refrigerant. Evacuate and recharge.
32
Page 33
DIAGNOSTICS
Service Analyzer Charts
COMPRESSOR OVERHEATING
SYMPTOM POSSIBLE CAUSE CHECK/REMEDY
High superheat (greater than 15°F
[-9°C] at coil)
Low line voltage Loose wire connections
High line voltage Power company problem Have problem corrected�
Low charge Check system charge�
Faulty metering device Restricted cap tube, TEV (TXV)
Power element superheat out of adjustment internally
Foreign matter stopping ow
High internal load Hot air (attic) entering return
Heat source on; miswired or faulty control
Restriction in liquid line
Low head pressure Low charge
Suction or liquid line subjected to high heat source
Power company problem, transformer Have problem corrected before diagnosis continues�
Undersized wire feeding unit Correct and complete diagnosis�
Drier plugged�
Line kinked�
Operating in low ambient temperatures
Hot attic / insulate liquid line
Hot water line
Check wiring�
High head pressure
Short cycling of com­pressor
Overcharge Check system charge�
Dirty outdoor coil Clean coil�
Faulty or wrong size outdoor fan motor Replace fan motor�
Faulty fan blade or wrong rotation Replace fan blade�
Replace with correct rotation motor�
Recirculation of air Correct installation�
Additional heat source Check for dryer vent near unit�
Check for recirculation from other equipment�
Noncondensibles Recover refrigerant� Evacuate and recharge system�
Equipment not matched Correct mismatch�
Faulty pressure control Replace pressure control�
Loose wiring Check unit wiring�
Thermostat Located in supply air stream
Dierential setting too close
Customer misuse
TEV Internal foreign matter
Power element failure
Valve too small
Distributor tube/tubes restricted
Distributor tube Restricted with foreign matter
Kinked
I�D� reduced from previous compressor failure
Diagnostics
33
Page 34
DIAGNOSTICS
Service Analyzer Charts
COMPRESSOR OVERHEATING (cont.)
SYMPTOM POSSIBLE CAUSE CHECK OR REMEDIES
Short cycling of compressor (cont�)
Faulty Compressor Valves
ELECTRICAL
SYMPTOM POSSIBLE CAUSE CHECK OR REMEDIES
Voltage present on load side of com­pressor contactor and compressor won't run
Voltage present on line side of com­pressor contactor only
Diagnostics
No voltage on line side of compressor contactor
Low charge Check system charge�
Low evaporator airow Dirty coil
Dirty lter
Duct too small or restricted
Faulty run capacitor
Faulty internal overload Replace compressor�
Fast equalization/Low pressure dierence Replace compressor and examine system to
Compressor start components Check start capacitor�
Run capacitor Check with ohmmeter
Internal overload Allow time to reset�
Compressor windings Check for correct ohms�
Thermostat Check for control voltage to contactor coil�
Compressor control circuit High-pressure switch
Blown fuses or tripped circuit breaker
Improper wiring Recheck wiring diagram�
Replace�
locate reason�
Check potential relay�
Low-pressure switch
Ambient thermostat
Solid-state protection control or internal thermal sensors
Compressor timed o/on control or interlock
Check for short in wiring or unit�
34
Improper voltage High voltage Wrong unit
Power supply problem
Low voltage Wrong unit
Power supply problem
Wiring undersized
Loose connections
Single Phasing (3 phase)
Check incoming power and fusing�
FLOODED STARTS
SYMPTOM POSSIBLE CAUSE CHECK OR REMEDIES
Liquid in the com­pressor shell
Too much liquid in system
Faulty or missing crankcase heater Replace crankcase heater�
Incorrect piping Check piping guidelines�
Overcharge Check and adjust charge�
Page 35
DIAGNOSTICS
Service Analyzer Charts
CONTAMINATION
SYMPTOM POSSIBLE CAUSE REMEDY
Moisture Poor evacuation on installation or during service In each case, the cure is the same� Recover refrigerant�
High head pressure Noncondensibles air
Unusual head and suction readings
Foreign matter –
copper lings
Copper oxide Dirty copper piping or nitrogen not used when
Welding scale Nitrogen not used during brazing
Soldering ux Adding ux before seating copper partway
Excess soft solder Wrong solder material
Wrong refrigerant or mixed refrigerants
Copper tubing cuttings
brazing
LOSS OF LUBRICATION
SYMPTOM POSSIBLE CAUSE REMEDY
Compressor failures Line tubing too large Reduce pipe size to improve oil return�
Low suction pressure Low charge Check system charge�
Refrigerant leaks Repair and recharge�
Cold, noisy compressor – Slugging
Noisy compressor Migration Check crankcase heater�
Cold, sweating compressor
Low load Reduced airow Dirty lter
Short cycling of compressor
Dilution of oil with refrigerant Observe piping guidelines�
Flooding Check system charge�
Thermostat setting
Faulty high- or low-pressure control Replace control�
Loose wiring Check all control wires�
Thermostat In supply air stream, out of calibration
Add lter drier, evacuate, and recharge.
Dirty coil
Wrong duct size
Restricted duct
Advise customer�
Customer misuse
Diagnostics
SLUGGING
SYMPTOM POSSIBLE CAUSE REMEDY
On start-up Incorrect piping Review pipe size guidelines�
TEV hunting when running
Faulty TEV Replace TEV�
35
Page 36
DIAGNOSTICS
Service Analyzer Charts
FLOODING
SYMPTOM POSSIBLE CAUSE REMEDY
Poor system control
using a TEV
THERMOST A TIC EXPANSION V ALVES
SYMPTOM POSSIBLE CAUSE REMEDY
High Superheat, Low
Suction Pressure
(superheat over
15°F [-9°C])
Diagnostics
Valve feeds too much
refrigerant, with low
superheat and higher
than normal suction
pressure
Loose sensing bulb Secure the bulb and insulate�
Bulb in wrong location Relocate bulb�
Wrong size TEV Use correct replacement�
Improper superheat setting (less than 5°F [-15°C])
Moisture freezing and blocking valve Recover charge, install lter-drier, evacuate system,
Dirt or foreign material blocking valve Recover charge, install lter-drier, evacuate system,
Low refrigerant charge Correct the charge�
Vapor bubbles in liquid line Remove restriction in liquid line� Correct the refrigerant
Misapplication of internally equalized valve Use correct TEV�
Plugged external equalizer line Remove external equalizer line restriction�
Undersized TEV Replace with correct valve�
Loss of charge from power head sensing bulb Replace power head or complete TEV�
Charge migration from sensing bulb to power head (Warm power head with warm, wet cloth� Does valve operate correctly now?)
Moisture causing valve to stick open� Recover refrigerant, replace lter-drier, evacuate system,
Dirt or foreign material causing valve to stick open
TEV seat leak (a gurgling or hissing sound is
heard AT THE TEV during the o cycle, if this is
the cause)� NOT APPLICABLE TO BLEED PORT VALVES�
Oversized TEV Install correct TEV�
Incorrect sensing bulb location Install bulb with two mounting straps, in 2:00 or 4:00
Low superheat adjustment Replace TEV�
Incorrectly installed, or restricted external equalizer line
Replace TEV�
recharge�
recharge�
charge�
Remove noncondensible gases�
Size liquid line correctly�
Ensure TEV is warmer than sensing bulb�
and recharge�
Recover refrigerant, replace lter drier, evacuate system,
and recharge�
Replace the TEV�
position on suction line, with insulation�
Remove restriction, or relocate external equalizer�
36
Page 37
Service Analyzer Charts
THERMOSTATIC EXPANSION VALVES (cont.)
SYMPTOM POSSIBLE CAUSE REMEDY
Refrigerant drainage from ooded evaporator Install trap riser to the top of the evaporator coil�
Compressor ood
back upon start-up
Superheat is low to
normal with low suction pressure
Superheat and
suction pressure
uctuate (valve is
hunting)
Valve does not
regulate at all
Inoperable crankcase heater or crankcase heater needed
Any of the causes listed under symptoms of Electrical problems on page 45
Unequal evaporator circuit loading Ensure airow is equally distributed through evaporator.
Low load or airow entering evaporator coil Ensure blower is moving proper air CFM�
Expansion valve is oversized Install correct TEV�
Sensing bulb is aected by liquid refrigerant or refrigerant oil owing through suction line
Unequal refrigerant ow through evaporator
circuits
Moisture freezing and partially blocking TEV Recover refrigerant, change lter-drier, evacuate system,
External equalizer line not connected or line plugged
Sensing bulb lost its operating charge Replace TEV�
Valve body damaged during soldering or by improper installation
Replace or add crankcase heater�
Any of the solutions listed under solutions of Electrical problems on page 45
Check for blocked distributor tubes�
Remove/Correct any airow restriction.
Relocate sensing bulb in another position around the circumference of the suction line�
Ensure sensing bulb is located properly�
Check for blocked distributor tubes�
and recharge�
Connect equalizer line in proper location, or remove any blockage�
Replace TEV�
DIAGNOSTICS
37
Diagnostics
Page 38
DIAGNOSTICS
SYSTEM
PROBLEM
Overcharge
Undercharge
Liquid Restriction
(Drier)
Low Indoor Airflow
Dirty Outdoor Coil
Low Outdoor
Ambient Temperature
Inefficient
Compressor
Indoor TXV Feeler Bulb Charge Lost
Poorly Insulated
Indoor Sensing Bulb
DISCHARGE
PRESSURE
COOLING MODE
TROUBLESHOOTING TIPS
INDICATORS
SUCTION
PRESSURE
High High Low High High
Low Low High Low Low
Low Low High High Low
Low Low Low Low Low
High High Low Low High
Low Low High High Low
Low High High High Low
Low Low High High Low
High High Low Low High
SUPERHEAT
Normal: 5°–15°F
[-15° – -9°C]
SUBCOOLING
Normal: See
Charging Chart
COMPRESSOR
AMPS
Diagnostics
38
Page 39
For Single-Phase Models
WIRING DIAGRAMS
Wiring Diagrams
39
Page 40
WIRING DIAGRAMS
For Three-Phase Models
Wiring Diagrams
40
Page 41
NOTES
41
Page 42
NOTES
42
Page 43
NOTES
43
Page 44
44
Loading...