Before commissioning/use of the equipment, these
operating instructions must be read carefully!
16
17
18
19
20
21
22
23
Made by REMKO
These instructions are a part of the device and must thus always be
kept in the direct vicinity of the mounting site or on the device itself.
Subject to changes, errors and typographical errors excepted.
3
Page 4
4
REMKO AMT
Dehumidification
The interrelated processes that
take place during dehumidification
are based on physical laws.
These are to be illustrated here in
simplified form in order to explain
the principle of dehumidification.
The use of
REMKO dehumidifiers
– No matter how well windows
and doors are insulated, damp
and moisture can penetrate
even through thick concrete
walls.
– The water volumes required for
binding concrete, mortar, plaster, etc. are diffused out initially
after 1-2 months under certain
circumstances.
– Even moisture that has penetrat
ed masonry following high water or flooding, is only released
very slowly.
– This applies similarly, e.g. also to
moisture contained in deposited
materials.
The moisture (water vapour) escaping from buildings or materials
is absorbed by the ambient air. This
increases their moisture content
and ultimately results in corrosion,
mould, rot, peeling of paint coatings and other unwanted moisture
damage.
The diagram opposite shows an
example of the rate of corrosion,
e.g. for metal at different humidity
levels.
time of corrosion
rel. air humidity %
This shows that the rate of corrosion below 50% relative humidity
(R H) is insignificant and below
40% R H can be disregarded.
From 60% R H, the rate of corro-
sion increases considerably. This
moisture damage limit applies also
to numerous other materials, e.g.
powders, packaging, wood or electronic units.
Buildings can be dried out in different ways:
By heating and air exchange:
1.
The room air is heated to absorb
moisture in order to then be discharged to the atmosphere. The
total input energy is lost with
the discharged, moist air.
By dehumidification:
2.
The moist air in an enclosed
room is continuously dehumidified by the condensation principle.
In terms of energy consumption,
dehumidification has one decisive
advantage:
Energy expenditure is restricted
solely to the existing room volume.
The mechanical heat released
through the dehumidification process is returned to the room.
With correct use, the dehumidifier only uses about 25% of the
energy that would be needed for
the „heating and ventilation”
principle.
The relative humidity
Our ambient air is a gas mixture
and contains always a certain
amount of water in the form of
water vapour. This water volume is
expressed in g per kg dry air (absolute water content).
1m3 air
weighs about 1,2 kg at 20 ° C
Depending on the temperature,
each kg of air is only able to absorb a certain amount of water vapour. When this absorptive capacity is reached, reference is made to
“saturated” air; this has a relative
humidity of (R H) 100%.
Relative humidity is therefore understood to be the ratio between
the amount of water vapour currently contained in the air and the
maximum water vapour volume at
the same temperature.
The ability of air to absorb water
vapour increases with increasing temperature. This means that
the maximum (= absolute) water
content increases with increasing
temperature.
Page 5
Temp.Water vapour content in g/m3 at a humidity of
°C
30
25
20
15
%r.F.
100
90
80
70
60
50
40
30
20
10
+
+
-
°C40%60%80%100%
-51,31,92,63,3
+103,85,67,59,4
+155,17,710,212,8
+206,910,413,817,3
+259,213,818,423,0
+3012,918,224,330,3
Drying materials
Building material and structures
can absorb considerable amounts
of water, e.g. bricks 90-190 l/m³,
heavy concrete 140-190 l/m³,
sand-lime bricks 180-270 l/m³.
The drying of moist materials, e.g.
masonry, takes place as follows:
■
The contained
moisture
moves from
within the
material to
its surface
■ The air enriched with water va-
pour continuously circulates the
REMKO dehumidifier. It is dehumidified and leaves the unit
at a slightly higher temperature
to absorb water vapour from
anew.
■ In this way, the moisture con-
tained in the material is gradually reduced
The material dries!
The produced condensate is collected in the unit and discharged
■ Evaporation takes place on the
surface = change to water vapour in the ambient air
The condensation of
water vapour
Since the maximum water vapour
volume increases when the air is
heated, the contained water vapour volume remains the same
however, this results in a reduction
of the relative humidity.
In contrast, when the air is cooled,
the capacity to absorb the maximum water vapour volume reduces, the water vapour volume contained in the air remains the same
and the relative humidity increases.
If the temperature falls further, the
capacity to absorb the maximum
water vapour volume is reduced
until it is equal to the contained
water vapour volume.
This temperature is called the dewpoint temperature. When the air
is cooled below the dew-point
temperature, the contained water
vapour volume is larger than the
maximum water vapour volume.
Water vapour is released.
This condenses to water. The air is
relieved of moisture.
Examples of condensing are misted
windows in winter or misting of a
cold drinks bottle.
The air flow is cooled on its way through or via the evaporator to
below the dew point. The water vapour condenses and is collected
in a condensate trap and discharged.
EvaporatorCondenser
air-temperature
air direktion
humidity
time
The higher the relative humidity,
the higher the dew-point temperature, which is easier to fall below.
5
Page 6
6
REMKO AMT
Heat of condensation
The energy transferred from
the condenser to the air is
composed of:
1. Heat energy extracted from the
evaporator.
2. Electrical drive power.
3. The heat of condensation re
leased through the condensation
of water vapour.
For the change from a liquid to
a gaseous state, energy is necessary. This energy is termed heat of
evaporation. It does not cause any
rise of temperature, it is only necessary for the change from a liquid
to a gaseous state. Vice versa,
-
energy is released during the liquefaction of gas, which is termed
heat of condensation.
The amount of heat of evaporation
and condensation is the same.
For water, this is:
2250 kJ/kg (4.18 kJ = 1kcal)
This shows that a relatively large
amount of energy is released
through the condensation of water
vapour.
If the moisture to be condensed is
not introduced through evaporation in the room itself, but from
outside, e.g. via ventilation, the
heat of condensation released in
the process contributes towards
room heating. In drying processes,
the heat energy is recirculated,
which is consumed during evaporation and released during condensation. The supplied air during
dehumidification creates a large
amount of heat energy, which is
expressed as a rise of temperature.
The time necessary for drying
normally does not depend only on
the unit capacity, but is rather determined by the rate at which the
material or parts of the building
release their moisture.
Safety Instructions
The units were subjected to extensive material, functional and
quality inspections and tests prior
to delivery.
The unit can however constitute
a hazard if used improperly by
untrained persons or not for the
intended purpose.
The following information must be
observed:
■ The units must not be installed
or operated in locations subject
to explosion hazards
■ The units must not be installed
and operated in oil, sulphur,
chlorine or salt containing atmospheres
■ The units must be installed up-
right and stable
■ The units must not be subjected
to a direct jet of water
■ The air inlet and outlet must
always be kept free
■
The intake guard grilles must
always be free of dirt and loose
objects
■ The units must not be covered
during operation
■ Never insert objects in the unit
■ The units must not be trans-
ported during operation
■ The units must only be trans-
ported with drained condensate
containers and dry evaporator
■ All electric cables outside the
units must be protected against
damage (e.g. due to animals)
■ The condensate containers
must be drained prior to each
change of location
CAUTION
Extension of the connecting
cable may only be carried
out by authorised electricians
taking into account the unit
power consumption, cable
length and local use.
CAUTION
Only specially authorised firms
may carry out work on the refrigeration system and electrical equipment.
Page 7
Proper UseEnvironmental
The units are designed and
equipped for drying and dehumidification purposes in industrial or
commercial use.
The equipment may be operated
only by accordingly trained personnel.
The manufacturer is not liable for
damage that occurs due to nonobservance of manufacturer instructions or the legal requirements or
due to unauthorised changes to
the device.
Customer service and
Warranty
The prerequisite for any warranty
claims is that the customer or its
recipient has returned the completed „Warranty Document“ included
in delivery to REMKO GmbH &
Co. KG at the time of the sale and
commissioning of the equipment.
The equipment was
tested several times at the factory
for perfect function.
If any malfunctions should occur, however, which cannot be
eliminated by trouble shooting
measures performed by the operator, please consult your dealer or
contract partner.
Protection and
Recycling
Disposal of packaging
When disposing of the packaging material, please think of the
environment.
Our equipment is carefully packed
for transport and delivered in a
stable cardboard transport package
on a wooden pallet, if necessary.
The packaging materials are environmentally-friendly and can be
recycled.
With the reuse of packaging material, you make a valuable contribution to the reduction of waste and
the preservation of raw materials.
You should thus dispose of the
packaging material at the corre-
NOTE
sponding disposal sites.
Another operation other than
that described in these operating instructions is not permitted. Nonobservance leads to
the extinguishment of any
liability and warranty claims.
NOTE
Adjustment and maintenance
tasks may be performed
only by authorised expert
personnel!
Important information
on recycling
The units are operated with environmentally-friendly and ozone neutral refrigerant R407c or
R134a.
In accordance with legal and
locally applicable requirements, the
mixture of refrigerant and oil contained in the unit must be disposed
of properly.
Disposal of the old device
The unit production is subject to
continuous quality control.
Only high-quality materials are
used, the majority of which are
recyclable.
You also contribute to environmental protection by guaranteeing that your old equipment is
disposed of in an environmentally
friendly manner.
For this reason, bring the old
equipment only to an authorised
recycling company or to a corresponding disposal site.
7
Page 8
8
REMKO AMT
Device Description
The units are designed for universal and problem-free dehumidification.
Owing to their compact size, they
are easy to transport and install.
The units operate according to the
condensation principle and feature
a hermetically sealed refrigeration
system, low noise and maintenance circulating fan, operating
hour counter and connecting cable
with plug.
Fully automatic electronic control, condensate container with
integrated overflow protection
(not with AMT 110-E) as well as
connections for direct condensate
removal ensure trouble-free continuous use.
The units comply with the fundamental safety and health requirements of the permanent EU
regulations.
The units are reliable and easy to
operate.
Unit applications
The units are used wherever
dehumidication is necessary
and consequential damage (e.g.
through mould formation) is to be
prevented.
Sequence of functions
The electronic control is activated
when the unit is switched on.
The green pilot light in the switch
illuminates.
Owing to automatic pressure
equalisation, the units start with
a delay of about 10 seconds and
then operate in continuous duty.
The circulating fan sucks the moist
room air via the dust filter, evaporator and downstream condenser.
At the cold evaporator, heat is
extracted from the room air and
cooled to below the dew point.
The water vapour contained in the
room air deposits as condensate or
frost on the evaporator fins.
When the temperature sensor
measures a specific minimum value
here, a timer is activated with a
delay of 30 minutes.
If during this time the evaporator
temperature does not rise again,
the cooling circuit is switched to
hot gas defrost after the time has
elapsed.
During the defrost phase, the circulating fan is off.
Diagram of the mode of operation of a REMKO dehumidifier
As soon as the frost (ice) has defrosted and the temperature at the
sensor rises again, the unit switches back to normal dehumidification
operation.
At a sufficiently high room temperature, the gill surface is not cold
enough for the formation of frost
so that defrosting is unnecessary.
This makes dehumidifiers particularly economical in operation.
At the condenser (heat exchanger), the cooled and dehumidified
air is reheated and blown back into
the room via the air outlet.
The conditioned, drier and heated
air mixes with the room air again.
Due to the constant circulation of
the room air through the unit, the
relative humidity in the room is
gradually reduced to the required
humidity (% R.H).
Depending on the room temperature and humidity, only about
30-40% of electrical energy is
required depending on the unit
cooling capacity.
The units are also suitable for drying and dehumidification of:
■ New buildings, industrial build-
ings
■ Cellar rooms, storage rooms
■ Archives, laboratories
■ Weekend homes,
caravans
■ Bathrooms, washrooms and
changing rooms, etc.
Fan
Dehumidified
Room air
Compressor
Condenser
Evaporator
Moist room air
Condensate container
Page 9
Installation
For economical and reliable unit
operation, the following information must be followed in any
event:
■ The units must be installed sta-
ble and horizontal to ensure unhindered condensate discharge
■ The units must be installed in
the centre of the room if possible, so that optimal air circulation is ensured
■ It must be ensured that air is
able to be sucked in freely at
front of the unit and blown out
freely at the rear of the unit
■ A minimum distance of 50 cm
to walls must be maintained
■ The units should not be installed
in the immediate vicinity of
radiators or other heat sources
■ Room air circulation can be
improved by installing the units
raised about 1 metre
■ The room to be dried or dehu-
midified must be closed with
respect to the ambient atmosphere
■ Open windows, doors, etc.
as well as frequent entering
and leaving the room must be
avoided as far as possible
■ If the units are used in dust-lad-
en environments or in stables,
care and maintenance measures
specially adapted to the particular conditions must be taken
■ The unit capacity is solely
dependent upon the spatial conditions, room temperature, relative humidity and observance of
the installation instructions
Electrical connection
■ The equipment is
operated at
230 V/50 Hz AC.
■ Electrical connection takes place
via a fitted mains cable with
earthing pin plug.
NOTE
Electrical connection must take
place to supply points with
residual-current protective
unit according to
VDE 0100, part 704.
For installation of the units
in damp areas such as utility
rooms, shower rooms or similar, the units must be protected
with a residual-current-operated circuit-breaker complying
with the requirements.
■ Extension of the connecting
cable may only take place by
authorised electricians, taking
into account the cable length,
unit installed load and local use.
Keep windows and doors closed!
Distance to walls
minimum 0.5 m
CAUTION
All cable extensions may be
used only when unrolled.
Maintain distance to radiators or
other heat sources.
9
Page 10
10
REMKO AMT
Commissioning
Prior to each commissioning or as
required, the air inlet and outlet
must be checked for clogging.
NOTE
Clogged outlets and filters
must immediately be cleaned
or replaced.
Prior to commissioning
■ All electric extension cables
must have an adequate crosssection and must only be used
fully uncoiled or unrolled.
■ Do not pull at the cable.
■ After switching on, the units
operate fully automatically until
switched off normally via the
float switch of the filled condensate container.
(not with AMT 110-E).
■ The condensate container must
be placed correctly.
■ In order to prevent compressor
damage, the units must be provided with a safeguard preventing immediate reconnection of
the compressor after switching
off.
The compressor initially
switches on again after a waiting time of about 1 minute!
Control panel
1
3
1 = Operating hour counter
2 = Operating switch with
“pilot light”
3 = YELLOW - Pilot light
„Container full”
4 = -RED-Pilot light
„Fault/Overheating“
Starting the unit
1. Set operating switch [2]
to position “0” (Off).
2. Connect the
mains plug of the
unit to a correctly
installed and
protected socketoutlet.
230V/50 Hz
4
.
Operation with a hygrostat
The REMKO hygrostat (accessory)
is supplied with a special adapter
plug.
Commissioning of the units in con-
2
junction with a hygrostat and its
operation take place as follows:
1. Plug the adapter plug into a cor
rectly protected socket-outlet.
2. Place the hygrostat at a suitable
point in the room to be dehumidified. Not in the immediate
vicinity of the unit and heat
sources.
3. Plug the mains plug (or a cable
extension) into the adapter plug.
4. Set the required humidity on the
hygrostat.
5. Set the operating switch [2] on
the unit to the position “I”.
The units switch on automatically
when the prevailing humidity is
higher than the value preset on the
hygrostat.
-
NOTE
At room temperatures below
10°C
and a relative humidity
below
ficient use of the unit is not
ensured.
40%
, economical/ef-
3. Set the operating switch
[2] to position “I” (On).
The green pilot light in the switch
[2] illuminates.
The units switch on with a delay
of about 10 seconds and then
operate in continuous duty.
The units now operate fully automatically until the relative humidity (% RH) is reached or normal
switch off takes place via the float
switch in the condensate container
(not with AMT 100-E). In this case,
the yellow “container full” pilot
light illuminates.
Page 11
Condensate
Depending on the air temperature and relative humidity, the
condensed water drips steadily or
only during the defrost phases in
the condensate trap or condensate
container.
Via a connection (not with AMT
40-E and 110-E), the condensate
flows into the condensate container located below.
In the condensate container is a
float switch which interrupts dehumidification via a water stop switch
when the container is full.
For protection against unintentional shut-off with splashing water,
etc., this protective unit initially
switches off with a delay of 10
seconds. The unit switches off and
the yellow pilot light on the control
panel lights up.
The procedure for emptying the
condensate container is as follows:
3. Carefully place the container
outside the unit and open the
sealing cover [F] of the drain
opening [E].
F
4. Pour the water into a drain.
Unit operation with hose connection
The condensate traps [K] of the
AMT 55 and 80-E are provided
with a connection [A].
E
A standard water hose [S] can be
connected to this connection after
removing the condensate container.
The discharge hose [S] is not
contained in the factory scope of
supply.
A
K
S
With the AMT 40-E, connection of
the hose takes place directly to the
connection [D] of the condensate
container.
1. Set operating switch [2] to posi
tion “0” (Off).
Otherwise, the units AMT 55-E
and AMT 80-E would immediately restart after the container
is removed.
2. Remove the filled condensate
container.
For this purpose, lift the container slightly via the recessed
handle and carefully pull out.
NOTE
Attention must be paid to
dripping condensate.
After switching off the unit,
the evaporator can continue to
defrost under the influence of
the ambient temperature.
-
5. Close the drain opening [E]
again and carefully place the
emptied condensate container
back in the unit.
NOTE
After each emptying, the
condensate container including
float switch must be checked
for any damage, fouling, etc.
6. Switch on the unit again via the
operating switch [2].
NOTE
The AMT 40-E units are only
functional with correctly
placed condensate container.
D
For unit operation, the condensate
container must always be placed
correctly in the AMT 40-E.
The condensate must preferably
be discharged to a lower located
outlet in unsupervised continuous
duty.
When using a collecting container
(container, bucket, etc.), the unit
must be installed at a raised level.
Further ideas, see next page!
11
Page 12
12
REMKO AMT
Condensate drain AMT 110-E
AMT 110-E units are not provided with an internal condensate container
due to their high dehumidification capacity.
Condensate discharge must take place locally into suitable containers or
via the external unit connection.
The following variants are available for discharge of the produced condensate water:
Shutdown
Set the operating switch to
the position „0“ (Off).
In case of longer
standstills, disconnect
the equipment from
the power mains.
Variant A
The water is collected in a sufficiently large dimensioned container
to be provided locally.
The container must be checked
regularly and emptied as necessary.
No overflow protection is provided!
Variant B
The water is initially collected in a
container and pumped to a raised
outlet or to the outside via a separate submersible pump.
This variant is suitable for installation sites without sufficient gradient or without drain.
The condensate container must
be emptied and dried with a clean
cloth.
Pay attention to dripping condensate!
For storage purposes, the units
should be covered with plastic/
sheeting and stored in an upright
position in a protected and dry
location.
The units can be stacked one on
top of the other for space-saving
storage.
For this purpose, they are provided
with special rubber pads on the
base plate.
Variant C
The water flows via a hose into a
lower located drain.
This variant enables unsupervised
continuous duty.
NOTE
These described variants can be used analogous also for all other
unit types for continuous condensate discharge.
CAUTION
The units must be secured
after stacking to prevent them
falling over and against unauthorised access.
Page 13
Unit transportMaintenance and Care
For convenient transport, the units
are provided with two large wheels
and an ergonomically shaped
transport and protective handle.
This can easily be removed if
required.
The following must be observed
for unit transport:
1. Prior to a change of location
switch off the unit and disconnect the mains plug from the
socket-outlet.
2. Empty the condensate
container.
3. As long as there is still moisture
on the evaporator or water in
the condensate container, the
units must only be transported
in an upright position.
NOTE
Attention must be paid to
dripping condensate.
After switching off the unit,
the evaporator can continue to
defrost under the influence of
the ambient temperature.
NOTE
Regular care and maintenance
is a basic precondition for a
long useful life and troublefree operation of the unit.
All moving parts are provided with
low-maintenance permanent lubrication. The refrigeration system is
a hermetically sealed system and
must only be repaired by authorised specialist companies.
CAUTION
Before carrying out all work on
the units, the mains plug must
be removed from the socketoutlet.
■
Observe the regular care and
maintenance intervals.
CAUTION
Regularly check air inlet and
air outlet for fouling.
■ Depending on the particular
operating conditions, the units
must be inspected annually
as required, however, at least
once by an expert for their safe
working condition
■ Keep the units free of dust and
other deposits
■ Clean the devices only with a
dry or moistened cloth
Cleaning the dust filter
CAUTION
Regularly check air inlet and
air outlet as well as the dust
filter for fouling.
Lightly push the guard grille
upwards, pull out and remove
downwards.
Remove the exposed dust filter.
If lightly soiled, the dust filter can
be cleaned by carefully blowing
out or by suction.
For heavy fouling, the filter can be
rinsed in a luke-warm (max. 40°C)
soap solution.
Subsequently rinse thoroughly
with clear water and allow to dry!
It must be ensured that the dust
filter is completely dry and undamaged prior to refitting.
NOTE
Heavily clogged dust filters
must be replaced with
new ones.
Only original spare parts
must be used.
The units must only be operated
with the dust filter fitted.
CAUTION
The mains cable must never
be used for pulling or fixing
purposes.
■ Do not use a direct water jet
such as a high-pressure cleaner, and so on!
■ Do not use caustic cleaning
agents or cleaning agents containing solvents
■ Only use suitable cleaning
agent, even in case of heavy
soiling
13
Page 14
14
REMKO AMT
Cleaning the units
For cleaning the interior of the unit
and to gain access to the electrical components, it is necessary to
open the unit housing.
NOTE
Adjustment and maintenance
tasks may be performed only
by authorised expert
personnel!
1. Remove the two fixing screws
[B].
2. Lift the housing part and hang
out the front tabs.
B
B
3. Clean the condenser fins either
by blowing out, suction or with
a soft brush.
4. Clean the evaporator fins, e.g.
with a luke-warm soap solution
or similar.
NOTE
Particular care must be taken
when cleaning the exchanger
as the fine aluminium fins bend
very easily.
9. After cleaning, the unit must be
dried.
Pay special attention to the
electrical components!
10. Refit all removed parts correctly
in reverse order.
11. Carry out a functional check
and safety test on the unit.
CAUTION
After completing all work on
the units, an electrical safety
test must be carried out in
accordance with VDE 0701.
Trouble Shooting
The units were manufactured using the latest production methods
and tested repeatedly for perfect
function. If faults should still occur,
the unit must be checked against
the following list.
The unit does not start.
■ Check the operating switch set-
ting. The green pilot light must
illuminate
■ Check the supply connection
and local system fuse 230V/1~/
50Hz
■ Check the mains plug and mains
cable for damage
■ Check the level in the conden-
sate container and the container
for correct seating. (not for AMT
110-E)
The red (Fault) pilot light illuminates
■ The cooling circuit is overloaded
or overheated
■ Before restarting the unit, the
cause of the fault must first be
located.
To be noted is that the unit restarts automatically after cooling
down
The unit operates, but no
condensate forms
■ Check the room temperature.
The operating range of the unit
is between 3°C and 32°C
■ Check the humidity, min. 40%
RH necessary
■ Check the dust filter for clog-
ging and clean or replace as
necessary
■ Check the evaporator and
condenser fins for clogging and
clean if necessary
■ Check the evaporator for pos-
sible icing/frost formation.
If this is the case, the automatic
defrost function and temperature sensor must be checked
■ If the unit does not operate cor-
rectly despite the checks carried
out, an authorised specialist
company should be notified
5. Do not use a direct water jet.
6. Rinse with clean water to re
move adhering soap residues.
7. Clean the inner surfaces of the
unit and fan impeller.
8. Clean the condensate trap and
connection.
-
■ Check the hygrostat setting (ac-
cessory).
The setting must be lower
than the relative humidity in
the room in which the unit is
installed
■ Check the adapter plug of the
hygrostat for damage and correct seating
CAUTION
Only specially authorised
firms may carry out work on
the refrigeration system and
electrical equipment.
Page 15
Test
230V/1~/50Hz
LNPE
Steuerplatine
NTCNTC
Rot
Gelb
SW
COMP.FANMOTOR
M1M2
S1
Test
230V/1~/50Hz
LNPE
Steuerplatine
C1
S
C R
PE
NTCNTC
Rot
Gelb
SW
M1M2
COMP.FANMOTOR
S1
Electrical wiring diagram
Test
NTCNTC
Rot
AMT 40-E
T
AMT 55-E to 110-E
= Test button
T
T
only AMT 110-E
T
The test button is only intended for service and testing on the control pcb.
Pressing this button reduces the timer times.
15
Page 16
16
REMKO AMT
Exploded view AMT 40-E
50
49
48
1
4546
2
40
3
4
5
6
7
8
10
11
12
13
14
15
30
47
31
2627
29
25
32
24
34
33
36
35
37
39
38
18
17
2225
23
16
20
21
We reserve the right to make changes in dimensions and design in the interest of technical advances.
(DER) = dehumidification performance coefficient according to DIN EN 810
1) Noise measurement DIN 45635 - 13 - Category 3
We reserve the right to make changes in dimensions and design in the interest of technical advances.
23
Page 24
REMKO EUROPE-WIDE
… and somewhere near you!
Take advantage of our experience and consulting services
Consulting
With intensive training seminars, we
keep our consultants up to date with
the latest technical knowledge. This
has given us the reputation of being
more than just a good, reliable supplier:
REMKO, a partner
that helps solve problems.
Sales
REMKO not only provides an extensive
sales network in Germany and abroad,
but also unusually highly qualified sales
experts.
REMKO sales representatives are more
than just salespeople: they must also be
customer consultants in air conditioning
and heating technology.
Customer Service
Our products are designed for precise
and reliable operation. If a malfunction
appears, however, REMKO Customer
Care is on the job. Our extensive network of experienced specialist retailers
guarantees our customers a fast and
reliable service at all times.
REMKO GmbH & Co. KG
Air Conditioning and Heating Technology
Im Seelenkamp 12 · 32791 Lage, Germany
Post office box 1827 ·D-32777 Lage
Phone +49 5232 606-0
Fax +49 5232 606-2 60
E-mail info@remko.de
URL www.remko.de
Subject to technical changes!
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.