Regency U39 User Manual

Page 1
Gas Stoves
U39 Top Vent Freestanding Direct Vent Gas Stove
Model U39-NG1 U39-LP1
Fuel Type Natural Gas Propane
Minimum Supply Pressure 5” W.C. (1.25 kPa) 12” W.C. (3.00 kPa)
Manifold Pressure - High 3.8” W.C. (0.94 kPa) 11” W.C. (2.74 kPa)
Manifold Pressure - Low 1.1” W.C. (0.27 kPa) 2.9” W.C. (0.72 kPa)
Orifi ce Size
Orifi ce Size Altitude 2000-4500ft (610-1370m) #33
Orifi ce Size
Minimum Input
Minimum Input Altitude 2000-4500ft (610-1370m) 19,000 BTU/h
Minimum Input
Maximum Input Altitude 0-2000ft (0-610m) 38,000 BTU/h
Maximum Input Altitude 2000-4500ft (610-1370m) 36,100 BTU/h
Maximum Input Converted to 30,000 Max BTU 30,000 BTU/h 30,000 BTU/h
Vent Sizing 4” Inner / 6-5/8” Outer 4” Inner / 6-5/8” Outer
Altitude 0-2000ft (0-610m) #31
30,000 Max BTU #37 #52
Altitude 0-2000ft (0-610m) 20,000 BTU/h
Converted to 30,000 Max BTU 15,000 BTU/h 15,000 BTU/h
Approved Venting Systems
Flex Vent Systems: FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems: Simpson Dura-Vent® Direct Vent GS
American Metal Products Ameri Vent Security Secure Vent® Selkirk Direct-Temp.
#50
20,000 BTU/h
38,000 BTU/h
C
A
D
U39 Gas Stove
Gas Stoves
K
L
M
J
J
B
E
3/8" NPT gas line in
F
I
mobile home
mounting holes
on bottom pedestal
Dimension Description U39
A Top Width 26” (660mm)
B Unit Height 30” (762mm)
C Top Depth (back to front face) 17-5/8” (448mm)
D Top Depth 17” (432mm)
E Height; Base to Gas Line 3-1/2” (89mm)
F Base Depth 17” (432mm)
G Depth; Flue-Centerline to Back 3-1/2” (89mm)
H Width; Side of unit to Gas Line 10-3/4” (273mm)
I Width - Mobile Home Mounting 13” (330mm)
O
N
O
N
Alcove clearances
Dimension Description U38
J Side Wall to Unit 7-1/2” (190mm)
K Back Wall to Unit 6” (155mm)
L Back Wall to vent centerline 11” (280mm)
M Side Wall to Vent Centerline 20-1/2” (521mm)
Corner Clearances
Dimension Description U38
N Wall to Unit corner 2” (50mm)
O Wall to vent centerline 11” (280mm)
Minimum ceiling height is 36" (914mm) from top of unit.
Minimum clearance to vent is 1-1/4” (32mm).
The above listed clearances are minimum distances to combustible
materials. When installing on carpet or vinyl fl ooring the bottom pedestal
cover plate must be installed.
157June 2007 Regency Product Specifi cations Book
Page 2
U39 Gas Stove
Regency Direct Vent System
Horizontal Terminations Only
These venting systems, in combination with the U39 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram.
FPI Horizontal Termination Kit includes all the necessary parts needed to install the U39.
FPI Kit # Length Contains:
#946-116 2 Feet 1) 6-5/8” Rigid Pipe Section (Kit length)
#946-216 4 Feet
Gas Stoves
2) 4” fl exible liner (Kit length)
3) spring spacers (4)
4) 90° Elbow
5) Adjustable pipe section 13-1/2” to 24”
6) thimble cover (1)
7) thimble (1)
8) adapter
9) AstroCap termination cap (1)
10) trim collar (2)
11) tube of Mill Pac (1)
12) S.S. screws #8 x 1-1/2”, self-tap, (12)
13) Blk. screws #8 x 1-1/2”, self-tap, (14)
14) Blk. screws #8 x 1-1/2” drill point, (4)
15) S.S. screws #8 x 1-1/2” drill point, (4)
16) Wood screws #8 x 1” (8)
17) vinyl siding standoff
(optional #946-206)
Gas Stoves
Vent Restrictor Position
To set the Vent restriction as indicated in the diagram, simply loosen the screws and push the vent restrictor plate to the correct position. Tighten the screws.
Vent Restrictor setting at 38,000 Btu/h
Rigid Pipe Venting Systems
Horizontal or Vertical Terminations
Vent Restrictor setting at 30,000 Btu/h
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex installations.
3) Horizontal sections must be supported every 3 feet.
Wall Thimble
(only required
in Canada)
Thimble
4" ID Liner
Spacer
Spring
Trim Collar
Cover
Trim
Collar
Adjustable Pipe
Length 13-1/2" - 24",
o
90 Elbow
4 ft. Pipe Length with Kit # 946-216 or 2 ft. Pipe Length with Kit # 946-116
Adapter
2 pieces
Alternate Horizontal
Termination Caps
AstroCap
Termination Cap
(Part# 946-523/P)
Alternate: Horizontal Riser Vent Terminal Part# 640-530/P
Vertical
Termination
Cap
Storm Collar
Flashing
Ceiling Firestop
Pipe Length
o
90 Elbow
Pipe
Length
Vinyl Siding
Standoff (Optional)
Adj.Pipe Length
11" - 14-5/8"
Alternate Horizontal
Termination Caps
Wall Thimble
(only required
in Canada)
Horizontal
Termination Cap
(Part # 946-523/P)
Alternate: Horizontal Riser Vent Terminal Part# 640-530/P
If required by the external termination location the listed alternate termination caps may be used. (Refer to Page 11)
158 June 2007 Regency Product Specifi cations Book
Page 3
Gas Stoves
Vertical Terminations using Rigid Pipe Systems
U39 Gas Stove
Vertical Venting with Two (2) 90° Elbows
Two 45° elbows = One 90° elbow
The shaded area in the diagram below shows all allowable combinations of straight vertical and offset to vertical runs with vertical terminations. Maximum two 45º elbows.
If the vent is ENCLOSED in a chase (min. size 9" x 9") maintain a 1-1/4" clearance to combustibles.
May be installed in Manufactured (Mobile) Homes after fi rst sale.
Option V H V+ V1 Maximum total pipe length, of
A) 1’ Min. 1’ Max. 2’ Min.
B) 1’ Min. 2’ Max. 3’ Min.
C) 2’ Min. 3’ Max. 4’ Min.
D) 2’ Min. 4’ Max. 4’ Min.
Vent Restrictor in position “A” (Center), refer to page 124.
all sections, must not exceed 30 feet. Total horizontal sections must not exceed 4 feet.
Minimum of 1 foot between 90° elbows is required.
Gas Stoves
159June 2007 Regency Product Specifi cations Book
Page 4
U39 Gas Stove
Horizontal Terminations for All Venting Systems
The shaded areas in the diagram below show all allowable combinations of vertical runs with horizontal terminations. Maximum one 90° elbow (two 45º
The venting arrangements diagrammed below, have a min. of 75% (fl ue loss) effi ciency with Fan Off, as required for manufactured homes. (Actual effi ciency may be as high as 85%)
Gas Stoves
elbows equal one 90° elbow).
Propane and Natural Gas:
Residential, Manufactured and Mobile Homes
Installations
May be installed in Manufactured (Mobile) Homes after fi rst sale.
Gas Stoves
Horizontal Venting with Two (2) 90° Elbows
Two 45° elbows = One 90° elbow
Option V H + H1 Maximum total pipe length, of all
A) 3’ Min. 2’ Max.
B) 5’ Min. 3’ Max.
C) 8’ Min. 4’ Max.
Vent Restrictor in position “A” (Center), refer to page 124.
sections, must not exceed 30 feet. Total horizontal sections must not exceed 4 feet.
Minimum of 1 foot between 90° elbows is required.
160 June 2007 Regency Product Specifi cations Book