Regency U32 User Manual

Page 1
U32 Gas Insert
Owners &
Installation Manual
MODELS: U32-NG5 Natural Gas U32-LP5 Propane
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult an authorized installer, service agency or the gas supplier.
Installation and service must be performed by an authorized installer, service agency or the gas supplier.
Tested by:
918-677e
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
www.regency-fi re.com
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
07/12/12
Page 2
TO THE NEW OWNER
Congratulations! You are the owner of a state-of-the-art Gas Insert by FPI.
The FPI Gas Insert Series of hand crafted appliances has been designed to provide you with all the warmth and charm of a fi replace, at the fl ick of a switch. The models U32-NG5 and U32-LP5 of this series have been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow.
Please take a moment now to acquaint yourself with these instructions and the many features of your FPI Fireplace.
2
U32-5 FPI Direct Vent Gas Insert
Page 3
40-1/4"
1-3/8"
10-3/4"
26-1/4"
20"
21-1/16"
28"
13-3/4"
Note: Oversize faceplate is 44" x 28"
40-3/4” (1036mm)
35-15/16” (912mm)
27-7/8” (708mm)
23-15/16” (607mm)
14-5/8” (371mm)
21-15/32” (545mm)
Low Profi le Faceplate Dimensions
7/8”
(22mm)
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
9-15/16”
(252mm)
This FPI product has been tested and listed by Warnock Hersey as a Direct Vent Wall Furnace to the following standards: CAN/ CGA-2.17-M91, and ANSI Z21.88a-2007/CSA 2.33ba-2007.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada. See section "Manufactured Mobile Home Additional Requirements" for additional requirements.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This FPI Mobile/Manufactured Home Listed appliance comes
factory equipped with a means to secure the unit.
This FPI Mobile/Manufactured Home listed appliance comes equipped with a dedicated #8 ground lug to which an 18 gauge copper wire from the steel chassis ground must be attached.
U32-5 FPI Direct Vent Gas Insert
3
Page 4
TABLE OF CONTENTS
SAFETY LABEL
Copy of the Safety Label ...............................................5
REQUIREMENTS
MA Code - CO Detector.................................................6
(for the State of Massachusetts only) ............................6
INSTALLATION
Important Message ......................................................8
For Your Safety ..............................................................8
Specifi cations ................................................................8
Gas Pressure Testing .................................................... 8
Installation Into A Solid Fuel Burning Fireplace Or
Factory Built Fireplace ...................................................8
Before You Start ............................................................8
Installation Checklist ......................................................9
Manufactured Mobile Home Additional Requirements ..9
Materials Required ........................................................9
Minimum Fireplace Dimensions ....................................9
Clearances To Combustibles .........................................9
Gas Connection ..........................................................10
Venting.........................................................................10
Flue Liner Installation ..................................................10
Gas Pipe Pressure Testing .......................................... 11
Gas Insert Aeration System .........................................11
Optional Brick Panel .................................................... 11
Log Set Installation ......................................................12
Regency Faceplate & Trim Installation ........................16
Standard Flush Door ...................................................17
Flush Louvers ..............................................................17
Conversion from NG to LP ........................................18
Full Screen doors ........................................................21
Contemporary Faceplate & doorframe installation ......23
Optional hearth trim installation ...................................25
Low profi le Faceplate installation ...............................26
Low profi le hearth trim .................................................28
Optional Wall Thermostat ...........................................29
Optional Remote Control ............................................29
Final Check..................................................................29
Wiring Diagrams ..........................................................30
OPERATING INSTRUCTIONS
Operating Instructions ................................................32
Lighting Procedure ......................................................32
Shutdown Procedure ...................................................32
First Fire ......................................................................32
Automatic Convection Fan Operation.........................32
Normal Operating Sounds Of Gas Appliances ............ 32
MAINTENANCE
Maintenance Instructions............................................33
Copy Of Lighting Instruction Plate ............................... 33
General Vent Maintenance ..........................................34
Log Replacement ........................................................34
Glass Gasket ...............................................................34
Gold-plated Trim .......................................................... 34
Door Glass ..................................................................34
Fan Maintenance .........................................................35
Valve Replacement ......................................................36
PARTS LIST
Main Assembly ............................................................37
Burner Assembly & Log Set.........................................38
Flush Front Assembly ..................................................39
Faceplate Assembly ....................................................40
Contemporary faceplate and doorframe ......................41
Low profi le faceplate ...................................................42
WARRANTY
Warranty ......................................................................43
4
4
U32-5 FPI Direct Vent Gas Insert
Page 5
SAFETY LABEL
This is a copy of the labels that accompany each U32-5 Gas Insert. We have printed a copy of the contents here for your review. The safety label is located on a plate inside the base of the unit visible when the bottom louver is opened.
Duplicate Serial number
Listed:
VENTED GAS FIREPLACE HEATER
/
FOYER AU GAZ À ÉVACUATION
Certified for/Certifi e pour: Tested to:
16117
WN#
NATURAL GAS FIREPLACE INSERT:
Model/Modele:
U32-NG5
Model/Modele:
U32-LP5
Factory Equipped For Altitude 0-4500ft. (0-1370m)
Min. supply pressure 5“ WC (1.25 kpa) Low Setting Man. pressure 1.1" WC (0.27 kpa) Max. Manifold pressure 3.8" WC (0.95 kpa) Orifice size 37 DMS Minimum input 15,300 Btu/h (4.48 ) Maximum input 30,000 Btu/h (8.79 kW)
PROPANE GAS FIREPLACE INSERT:
Factory Equipped For Altitude 0-4500ft. (0-1370m)
Min. supply pressure 12" WC (2.99 kpa) Low Setting Man. pressure 2.9" WC (0.72 kpa) Max. Manifold pressure 11" WC (2.74 kpa) Orifice size 52 DMS Minimum input 15,000 Btu/h (4.48 kW) Maximum input 30,000 Btu/h (8.79 kW)
Minimum Clearances to Combustibles from Insert
Mantel width M 12" (305mm) Mantel height N 17" (432mm) Mantel width O 3-1/2" (89mm) Mantel height P 13" (330mm) Floor to top of unit Q 20" (508mm)
FPI Fireplace Products International Ltd.,
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1. This appliance must be installed in accordance with the Standard CAN/CSA Z240 MH, Mobile Housing, in Canada, or with the Manufactured Home Construction andSafety Standard,Title24 CFR, Part3280, inthe United States,or when sucha standard isnot applicable,ANSI/NCSBCS A225.1/NFPA 501A, ManufacturedHome InstallationsStandard This applianceis only foruse with thetype of gasindicated on therating plate andmay be installedin an aftermarket,permanently located, manufactured (mobile) homewhere notprohibited by localcodes. Seeowner's manual fordetails. This applianceis notconvertible for usewith othergases unless acertified kitis used. WARNING.This fireplace hasbeen converted foruse with agas fireplace insertonly and cannotbe used forburning wood orsolid fuels unlessall original parts havebeen replaced,and the fireplacere-approved bythe authority havingjurisdiction. Installer l'appareil selonles codesou règlements locaux, ou, en l'absence detels règlements, selon les codes d'installationANSI Z223.1, National Fuel Gas Codeou CSA-B149.1en vigueur. Installer l'appareil selonla norme CAN/CSA-Z240, Série MM,Maison mobiles ou CAN/CSA-Z240 VC, Véhicules decamping, ou la norme 24CFR Part 3280, Manufactured Home Construction and Safety Standard. Si ces normes ne sont pas pertinentes, utilisez la normeANSI/NCSBCS A225.1/NFPA 501A, ManufacturedHome InstallationsStandard Cet appareil doit être utilize uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil peut être installé dans une maison préfabriquée ou mobile (É.-U. seulement) installée à demeure si les règlements locaux le permettent. Voir la notice de l'utilisateur pour plus de renseignements. Cetappareil nepeut pas êtreutilisé avecd'autres gaz saufsi unetrousse de conversioncertifiée estfournie. Cet appareiln'est pasconvertible pour uneutilisation avecd'autres gaz, saufsi unkit certifié estutilisé. AVERTISSEMENT : Ce foyer a été converti pour utilisation avec un foyer au gaz encastrable et ne peut être utiliser pour brûler du bois ou d'autres combustibles solidesà moinsque toutes lespièces d'origineaient été remplacéeset quele foyer aitété approuvéde nouveau parl'autorité compétente.
This ventedgas fireplaceheater is notfor usewith air filters. Ne pasutiliser defiltre à airavec cefoyer au gazà évacuation.
For usewith glassdoors certified withthe applianceonly
Delta BC, CANADA
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUELS. / GAZ À ÉVACUATION -
é
CAN/CGA-2.17-M91, ANSI Z21.88-2009 / CSA 2.33-2009
CANADA and U.S.A.
MODEL U32-NG5
kW
MODEL U32-LP5
Mantel Clearances with Bay & Flush Louvers in Masonry Fireplace Installation
Side wall A 10"(255mm) Ceiling B 47-1/2"(1205mm)
M
N
O
P
Q
Alcove Width K 48"(1220mm) Max. Alcove Depth L 36"(915mm)
Pour utilisationuniquement avecles portes enverre certifiéesavec l'appareil
NE PAS UTILISER AVEC DUCOMBUSTIBLE SOLIDE.
NOTE: FPI units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
328
DO NOT REMOVE THIS LABEL /
NE PAS ENLEVER CETTE ETIQUETTE
328
Serial No. / No de serie
ÉÉQUIP A L'UISINE POUR GAZ NATURAL
Pression d'allimentation minimum
à
Pression la tubulure d' chappement basse
à
Pression la tubulure d' chappement lev e Dimensions de l'orifice
é
D bit Calorifique minimum
é
D bit Calorifique maximum
ÉÉQUIP A L'UISINE POUR GAZ PROPANE
Pression d'allimentation minimum
à
Pression la tubulure d' chappement basse
à
Pression la tubulure d' chappement lev e Dimensions de l'orifice
é
D bit Calorifique minimum
é
D bit Calorifique maximum
MADE IN CANADA /FABRIQUE AU CANADA
é ééé
é ééé
B
L
A
K
FOYER AU
918-678d
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.
U32-5 FPI Direct Vent Gas Insert
5
Page 6
REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
MA Code - CO Detector
(for the State of Massachusetts only)
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
6
U32-5 FPI Direct Vent Gas Insert
Page 7
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The U32 Gas Insert must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fi replace is installed in compliance with manufacturers instructions and all applicable codes.
BEFORE YOU ST ART
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA AS THE APPLI­ANCE. TODDLERS, YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS. A PHYSICAL BARRIERS IS RECOMMEND­ED IF THERE ARE AT RISK INDIVIDUAL IN THE HOUSE. TO RESTRICT ACCESS TO A FIREPLACE OR STOVE, INSTALL AN ADJUSTABLE SAFETY GATE TO KEEP TODDLERS, YOUNG CHILDREN AND OTHER AT RISK INDIVIDUALS OUT OF THE ROOM AND AWAY FROM HOT SURFACES.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPE­CIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
U32-5 FPI Direct Vent Gas Insert
7
Page 8
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The FPI Gas Insert must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the building authority having jurisdiction to determine the need for a permit prior to starting the installation.
NOTE: Failure to follow the instructions could cause a malfunction of the heater which could result in death, serious bodily injury, and/ or property damage. Failure to follow these instructions may also void your fi re insurance and/or warranty.
FOR YOUR SAFETY
This appliance requires air for proper combustion. Always provide adequate combustion and ventilation air. Follow instructions and information in CAN/CGA B149 (in Canada) or the National Fuel Gas Code ANSI Z223.1 (in the USA), regarding requirements for combustion and ventilation air.
SPECIFICATIONS
At pressures over 1/2 psig, the pipe to the unit must be disconnected.
Gas Input Capacity: Natural Gas 30,000 Btu/h Propane 30,000 Btu/h
Min. Input
Natural Gas 15,300 Btu/h Propane 15,300 Btu/h
Fuels: Approved for use with both natural gas, and propane. Approved as is for use at 0' to 4,500' (0-1370m).
Electrical: 120V A.C. system.
Circulation Fan: Variable speed, 110 CFM.
Log Set: Ceramic bre, 7 per set.
Vent System: 3" co-linear aluminum ex.
The effi ciency rating of the appliance is a product thermal effi ciency rating determined under continuous operating conditions and was determined independent of any installed system.
GAS PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa).
INSTALLATION INTO A
SOLID FUEL BURNING
FIREPLACE OR
FACTORY BUILT
FIREPLACE
The U32-5 Gas Inserts have been tested and approved to be vented into any masonry fi replace or approved solid fuel burning factory built
replace that will allow the insert to physically t into the fi rebox. Refer to "Minimum Fireplace
Dimensions" section for minimum fi replace clearances.
If the factory built fi replace* height is too low for your Insert, you may remove the smoke baffl e plate, damper, refractory (fi rebricks), glass doors, screen rails, screen mesh and log grates from the factory built fi replace as long as these items are saved and are reinstalled in the event that the Insert is removed.
Smoke shelves, shields and baffl es may be removed if attached by mechanical fasteners. If any part is removed it must not weaken the structural integrity of the factory built fi replace.
NOTE: Any alterations made to the listed solid fuel burning factory built fi replace may void the listing of the fi replace.
*Check with your local inspector before commencing with this installation.
Installer must mechanically attach the supplied label to the inside of the fi rebox of the fi replace into which the gas fi replace insert is installed.
"WARNING: This fi replace has been converted for use with a gas fi replace insert only and cannot be used for burning wood or solid fuels unless all original parts have been replaced, and the fi replace re-approved by the authority having jurisdiction."
BEFORE YOU ST ART
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
General Safety Information
1) The appliance installation must conform
with local codes or in the absence of local codes, with CAN/CGA B149 (in Canada) or the National Fuel Gas Code ANSI Z223.1 in the U.S.A. This appliance should be installed by a qualifi ed gas fi tter technician only.
2) Installation and repair should be done by a qualifi ed service person.
3) The appliance should be inspected before
use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, animal hair, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
4) See general construction and assembly instructions. This appliance may only be installed in a vented, noncombustible replace.
5) This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
6) Always connect this insert to a vent system venting to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is properly sized and is of adequate height to provide the proper draft.
7) Inspect the venting system annually for blockage and any signs of deterioration.
8) Any glass removed for servicing must be replaced prior to operating the appliance.
9) To prevent injury, do not allow anyone who is unfamiliar with the operation to use the replace.
10) Due to high temperatures, the appliance should be located out of high traffi c areas and away from furniture and draperies. Children and adults should be alerted to the hazards of high surface temperatures, especially the fi replace glass and gold trims, and should stay away to avoid burns or clothing ignition. Young children should be carefully supervised when they are in the same room as the appliance. Clothing or other fl ammable material should not be placed on or near the appliance.
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
8
U32-5 FPI Direct Vent Gas Insert
Page 9
INSTALLATION
CHECKLIST
Before installing vent system ensure that the damper plate is open and secure to prevent the damper plate from falling down and crushing the liner.
The FPI Gas Insert is installed as listed.
1) Check all clearances to combustibles, (Refer to
sections "Minimum Fireplace Dimensions and Clearances to Combustibles)
2) Make the gas connection. (Refer to section
"Gas Connection")
3) Install the 3" fl ue liner to the sliding connector
plate. (Refer to section "Flue Liner Installation.")
4) Slide the unit half way into the replace.
5) Pull the vent connector plate through the tapered
brackets and fasten to the front plate. Refer to section "Flue Liner Installation.")
6) Slide the unit fully into the replace.
7) Test gas pressure (Refer to section "Gas Pipe
Pressure Testing"). Check aeration system (Refer to section "Gas Insert Aeration System").
8) Install standard and optional features. Refer
to the following sections:
a. Brick Panel b. Log Set c. Faceplate & Trim d. Standard Flush Door e. Flush Trim f. Flush Louvers g. Full Screen Doors h. Wall Thermostat i. Remote Control
9) Final check: Before leaving this unit with the
customer, the installer must ensure that the appliance is fi ring correctly. This includes:
a) Clocking the appliance to ensure the correct
ring rate.
b) Adjusting the primary air, if required, to
ensure that the fl ame does not carbon. See "Gas Insert Aeration System" section.
c) Ensuring that the appliance is venting
correctly.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
ground lug provided.
3) Appliance must be anchored to the fl oor
with the supplied anchoring methods.
MATERIALS REQUIRED
No electrical power supply is required for the gas control to operate. A 120 Volt AC power cord is hooked up to the fan. Plug the 3 wire cord into a suitable receptacle. Do not cut the ground terminal off under any circumstances. When connected with 120 volts, the appliance must be electrically grounded in accordance with local codes, current version of CSA C22.1 (in Canada) or in the absence of local codes, with the National Electrical Code ANSI/NFPA 70-1987.
MINIMUM FIREPLACE
DIMENSIONS
The minimum fi replace clearances & dimensions for the FPI gas insert are shown in the following diagrams:
D
Regency Countour
Faceplate
Full
Screen
Doors
Low
Profi le
Faceplate
Max Lentil Bar DepthAHeightBDepth
9" 22" 14" 22-1/2" 26-1/2"
9" 22" 14" 22-1/2" 26-1/2"
8-1/8" 22" 14" 22-1/1" 26-1/2"
Width (rear)
C
D
INSTALLATION
CLEARANCES TO
COMBUSTIBLES
Minimum Clearances to Combustibles
From Unit Sides A 10" / 255 mm Ceiling B 47.5" / 1205 mm Mantel C see Dia. 2 & 3
Max. Mantle Depth G 12" / 305 mm
(see Dia. 2)
Min. Alcove Width K 48" / 1220 mm Max. Alcove Depth L 36" / 915 mm
*No Hearth Required
Diagram 1
Combustible Mantel Clearances
with Flush Louvers in Masonry
and Factory Built
Fireplace Installation
12" Max.
G
Combustible
Flooring
Diagram 2
Width (front)
E
Mantle
Faceplate
C
Flush with Floor
U32-5 FPI Direct Vent Gas Insert
9
Page 10
INSTALLATION
Diagram 3
Note: A noncombustible mantel may be
installed at a lower height if the framing is made of metal studs covered with a noncombustible board.
GAS CONNECTION
GAS CONNECTION WARNING: Only persons licensed to work
with gas piping may make the
necessary gas connections
to this appliance.
1) If the appliance is to be installed into an
existing chimney system, thoroughly clean the masonry or factory built fi replace.
2) The appliance is provided with an opening on
the left hand side of the control compartment. A 3/8" NPT gas supply pipe must be brought near this inlet hole.
VENTING
THE APPLIANCE MUST NOT BE
CONNECTED TO A
CHIMNEY FLUE SERVING A
SEPARATE SOLID FUEL
BURNING APPLIANCE.
This appliance is designed to be attached to two 3" (76mm) co-linear aluminium fl ex running the full length of the chimney. The fl ue length must be a minimum length of 8 ' (2.44m) and a maximum of 35' (10.7m). See chart below for minimum distances from roof. Periodically check that the vent is unrestricted.
Masonry chimneys may take various contours which the fl exible liner will accommodate. However, keep the exible liner as straight as possible, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet air collar of the termination cap.
Part # Description
948-305 3" Flex - 35 ft. 946-529 Co-linear DV Vertical Termination Cap
Important:
Air Defl ector (Part #420-119) is required for all LP installations. For Natural Gas installations -the air defl ector is required when venting is a mini­mum of 15ft to a maximum of 35ft. Not required on NG if venting is between 8ft. to 14.99ft
Air Defl ector
The Air Intake pipe must be attached to the inlet air collar of the termination cap.
FLUE LINER
INSTALLATION
1) Cut the ex liner as required.
2) Mark the end of one liner to indicate Inlet.
3) Connect the other end of the above liner to
the inlet side of the termination adaptor, seal connection with high temperature silicone. Secure with gear clamp.
4) Connect the 2nd liner to the exhaust side
of the adaptor, seal connection with high temperature silicone. Secure with gear clamp.
5) Install ashing.
3) Locate the center point where the vent
will pass through the chimney above the appliance. Move the appliance into the exact location where it is to be installed. Ensure that the Insert is level.
10
Install the rear air de ector to the back wall of the
rebox using 2 existing lower 1/4" screws.
Alternate Approved Caps
46dva-VC Vertical Termination Cap 46dva-VCH High Wind Cap 46dva-GK 3" Co-linear Adaptor with fl ashing
In areas of consistently high winds, we recommend using the Simpson Dura-Vent System (46dva-GK adapter and 46dva-VCH high-wind cap). The Air Intake pipe must be attached to the inlet air collar of the termination cap.
6) Insert both liners into chimney, passing
through the damper opening.
7) Install termination cap.
8) Connect the marked end of the liner to
the inlet collar of the vent connector plate marked with an "I", seal connection with high temperature silicone. Secure with gear clamp.
U32-5 FPI Direct Vent Gas Insert
Page 11
INSTALLATION
Be careful not to damage thermal insula-
tion when sliding on vent connector plate.
This could cause blockage.
9) Connect the 2nd liner to the exhaust collar
marked with an "E", seal connection with high temperature silicone. Secure with gear clamp.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a 1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON"
position.
5) The pressure check should be carried out
with the unit burning and the setting should be within the limits specifi ed on the safety label.
6) When fi nished reading manometer, turn
off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver. Note: Screw should be snug,
but do not over tighten.
GAS INSERT
AERATION SYSTEM
The air shutter can be adjusted by moving the adjusting wire up or down. The wire is accessed through the bottom louver opening. Open the air shutter for a blue fl ame or close for a yellower ame. The burner aeration is factory set but may need adjusting due to either the local gas supply or altitude.
OPTIONAL
BRICK PANEL
1) Unwrap the brick pattern panels from the
protective wrapping.
2) Remove the glass front if it is already
installed, see "Standard Flush Door" section.
3) Put the rear brick panel fl at against the back
of the unit.
4) Before installing the side brick panels, loosen
the screws for the brick tabs enough so that you can slide the brick tabs on to the screws easily but that the tabs are secure. For the location of the side brick tab screws see diagram 1.
NOTES:
1) Final gas connection should be made after
unit is in place to avoid damage to line when pushing the unit into position.
2) Mill-pac may be used instead of high
temperature silicone and screws may be used instead of gear clamps at connections of liner to inlet and vent collars.
GAS PIPE
PRESSURE TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be checked using the valve pressure ports on the valve.
Minimum Air Shutter Opening: 3/16" Natural Gas
1/4" Propane
Aeration Adjustment Wire
PULL= Open
PUSH = Close
CAUTION: Carbon will be produced if air shutter is closed too much.
Note: any damage due to carboning resulting from improperly setting the aeration controls is NOT covered under warranty.
Note: Aeration Adjustment should only
be performed by an authorized FPI Installer at the time of installation or service.
Diagram 1
5) Remove the brick tabs and slide the side
brick panels into position. See diagram 1. Install the brick tabs. See diagram 2.
Diagram 2
U32-5 FPI Direct Vent Gas Insert
11
Page 12
INSTALLATION
LOG SET INSTALLATION
Read the instructions below carefully and refer to the images. Dangerous operating conditions may occur if the logs are not positioned in their correct locations. If the logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot operation.
IMPORTANT
For LP units the Air Defl ector MUST be installed prior
to log installation. See "Conversion from NG to LP"
section in manual for installation instructions.
Log kit (Part # 425-930) contains the following pieces:
a) 27-31 Rear Log b) 27-32 Middle Left Log c) 27-33 Front Log d) 27-34 Middle Right Log e) 27-35 Left Log f) 27-36 Right Log g) 902-154 Embers Lava h) 902-179 Vermiculite i) 902-153 Rock Wool j) 946-669 Platinum Embers (supplied with packaged manual)
2) Spread vermiculite around the exposed fi rebox base. Then take some
embers and spread them over the vermiculite as shown.
Vermiculite and Embers
3) Fit log 27-31 into the pins on the rear log tray.
27-36
27-32
27-33
1) Carefully remove the logs from the box and unwrap them. The logs are fragile, handle with care - do not force into position.
27-35
27-34
27-31
27-31
4) Fit log 27-32 into the pins on the middle left hand side of the
burner.
27-32
12
U32-5 FPI Direct Vent Gas Insert
Page 13
INSTALLATION
6) Fit the groove in log 27-34 into the tab on the right side of the burner.
Rest the other end of log 27-34 on the notch in log 27-33.
27-32
5) Fit log 27-33 into the pins at the front of the burner.
27-33
27-34
Tab
27-34
27-33
U32-5 FPI Direct Vent Gas Insert
7) Fit the bottom end of log 27-35 into the pin in log 27-33 and rest the
top end of log 27-35 on the notch in log 27-31.
27-33
27-35
27-33
13
Page 14
INSTALLATION
27-35
9) Place embers along the front of the burner as shown. Ensure not to
cover any burner ports.
8) Fit log 27-36 into the pins on logs 27-33 and 27-31.
27-31
27-33
Embers
10) Separate platinum embers and place on the burner just in front of
the logs as shown. Avoid stacking platinum embers.
27-36
Platinum Embers
14
27-36
U32-5 FPI Direct Vent Gas Insert
Page 15
Completed Log Set Installation
INSTALLATION
27-35
27-31
27-34
27-33
27-32
27-36
U32-5 FPI Direct Vent Gas Insert
15
Page 16
INSTALLATION
REGENCY FACEPLATE
& TRIM
INSTALLATION
1) Lay the faceplate panels at, face down on
something soft so they don't scratch.
2) Take the top faceplate and align the holes
in it with the holes in the side panels. Using the screws provided, attach from the top of the panel (the holes in the top panel are slightly larger than the holes in the side panel to facilitate easier installation). Diagram 1.
Rear View: Trim Assembly
Diagram 2
5) Connect the fan switch wires by taking the
black and red wires with the male ends (in the grey harness) and connect them with the wire connectors from the fan speed control.
6) Connect the ON/OFF switch wires by taking
the black and red wires with the female ends and connect them to the ON/OFF switch.
7) Tuck the wires into the faceplate to keep them
away from the insert using the clip provided. Attach the clip to the rear of the faceplate to ensure that the wires do not touch the side of the unit. Diagram 3.
Diagram 4
Diagram 5
11) Push the Regency
two holes in the bottom left corner of the faceplate.
®
logo plate into the
Rear View: Faceplate Assembly
Diagram 1
Hint: Don't tighten the screws down
completely at this point, continue on with steps 3 and 4 and do a trial fi t to the unit. Make any necessary adjustments and when it fi ts properly then tighten down the screws.
Hearth Trim Option: Hearth Trim is an
option that can be used to fi nish off the installation when the bottom of the fi replace is higher than the hearth or to raise the replace. Attach the Hearth Trim to the bottom of the faceplate side panels with the screws provided. See Diagram 1.
3) Using the connectors provided, join the left
side trim (with the ON/OFF switch) to the top trim. Diagram 2. Connect the right side trim to the top trim.
4) Place the trim on the assembled faceplate
panels, aligning the wire connections from the switches with the notch on the left side panel.
16
Diagram 3
8) The power cord should be run behind the
faceplate panel.
9) Attach the brass trim to the faceplate by drilling
a 1/8" hole through into the faceplate using the hole in the trim as a guide. Fasten the trim to the faceplate panels using the plated screws. Diagram 4.
10) Attach the faceplate panels to the insert
body using the 4 remaining black screws. Diagram 5.
U32-5 FPI Direct Vent Gas Insert
Page 17
INSTALLATION
STANDARD
FLUSH DOOR
The standard fl ush door comes with a black
frame. To install the frame, simply hook the top door fl ange onto the top of the unit and swing the door towards the unit, diagram 1. Be careful that the glass gasket does not roll up; there must be a gap between the gasket and the door lip to ensure that the door sits securely on the unit. Diagram 2.
Diagram 1a
Use the hook to pull the spring out until you can put the hook into the slot on the bottom door bracket. Repeat for 2nd spring. See diagram 3.
Diagram 3
To remove the fl ush door, reverse the above steps.
NOTE: The chain must rest on TOP of the gas inlet pipe never under it.
2) Install the Spring Hinges on the left and right
side of the bottom of the Firebox using 2 screws per hinge.
3) Place the Bottom Louver near the hinge. Flip
hinge over the Bottom Louver and secure using 3 screws.
Hinge
Location
Bottom Louver
Diagram 1b
Diagram 2
FLUSH LOUVERS
1) The top louver is held in place by friction t,
if the louver needs to be adjusted; bend the bracket out as shown in the diagram.
U32-5 FPI Direct Vent Gas Insert
17
Page 18
INSTALLATION
for P36D-1 / P36-4 / U32-5 / U37-1 using SIT 820 NOVA Gas Valve
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER
CONVERSION KIT #514-969 FROM NG TO LP
IF IN DOUBT DO NOT DO THIS CONVERSION !!
Each Kit contains one LPG Conversion Kit and one DC Sparker Kit.
Conversion Kit Contains: Qty. Part # Description
1 904-390 Burner Orifi ce #52 1 904-529 5/32" Allen Key 1 918-590 Decal "Converted to LPG" 1 908-528 Red "LPG" label 1 910-037 LPG Injector (Pilot Orifi ce) 1 918-481 Instruction Sheet
DC Sparker Kit Contains:
Qty. Part # Description
1 820-475 Bracket DC Sparker 1 820-476 Bracket DC Sparker 1 904-153 Washer #8 External Star 1 904-330 Nut 8-32 Hex 2 904-531 Bushing Split Plastic
0.500 in.
1 904-543 Screw 8-32 x 3/4 Pan
Head
2 904-553 Screw #8 x 1/2 Type "B",
Black Oxide
1 910-073 Spark Generator Battery
Holder
1 910-074 Spark Generator Switch
C/W Wire
1 910-078 Battery Size AA
Energizer En91 2 910-199 Clip Wire Holder 1 910-903 Wire Fan To Power Cord
Ground 30 in. 904-781 Velcro Hook, Black 904-782 Velcro Hook, Black
For P36D-1 / P36-4 Only:
5) Remove the 2 screws holding the Burner
Assembly to the fi rebox base. Push the Burner Assembly to the left and lift out.
Remove the 2 screws, push Burner Assembly
to the left and lift out.
For U32-5 Only:
5a) Remove the grate by removing the
screws on each side of the grate.
Remove the 2 screws
holding the grate in position.
5b) Remove the Burner Tray by removing
the screws on each side of the tray. Push the tray to the left and lift up.
6) Pull off the pilot cap to expose the pilot
orifi ce.
7) Unscrew the pilot orifi ce with the allen
key; then replace with the LPG pilot orifi ce and the pilot cap, provided in the kit.
8) Remove burner orifi ce with a 1/2"
wrench. Use another wrench to hold on to the elbow behind the orifi ce. Discard orifi ce.
Installation of LPG Conversion Kit:
1) Shut off the gas supply.
2) Remove the louvers (and bay door if it is
installed).
3) Open the fl ush door and remove the
door.
4) Remove the logs and embers (if already
installed).
18
Burner Orifi ce
Remove the 2 screws,
push Burner Tray to the left, and lift off.
IMPORTANT
Before re-installation of the burner (once
the LP conversion is complete), the air
defl ector must be installed. See step 18a.
U32-5 FPI Direct Vent Gas Insert
Page 19
INSTALLATION
9) Reinstall new burner orifi ce LPG
stamped #52 and tighten.
10) Turn control knob to the “OFF” position.
11) Remove the black
protection cap by hand from the hi-low knob (Fig.1).
Fig.1
12) Insert a 5/32” or 4mm
Allen wrench into the hexagonal key-way of the screw (Fig.
2), rotate it counter­clockwise until it is free and extract it.
Fig.2
13) Check that the screw is clean and if
necessary remove dirt.
16) Verify that if the conversion is from
NG to LPG, the screw must be re­assembled with the red o-ring visible (Fig. 5).
Red o-ring visible
LPG Configuration
Fig.5
17) Re-assemble the black protection
cap (Fig. 6).
Fig. 6
18) Reverse steps 6 - 1.
Installation of the DC Sparker:
21) Locate the Piezo Ignitor situated at the
side of valve.
Piezo Ignitor
22) Remove the Piezo Ignitor by unscrewing
the nut at the back of the mounting bracket.
Ignitor
Wire
Piezo
Ignitor
14) Flip the screw (Fig. 3).
Fig.3
15) Using the Allen wrench
as shown in Fig.4, rotate the screw clockwise until snug, do not overtighten.
Fig.4
WARNING!
Do not over tighten the screw.
Recommended to
grip the wrench by the short side.
For U32-5 Only:
18a) Install the air defl ector to the back wall of
the fi rebox using 2 screws.
Air Defl ector
WARNING!
Also check that the pilot and main
burner injectors are appropriate for
the gas type.
19) Attach the label "This unit has been
converted to LPG" near or on top of the serial # decal.
20) Replace yellow "NG" label with red
"LPG" label.
23) Disconnect the ignitor wire from the
Piezo Ignitor and connect it to the DC Sparker.
DC
Sparker
Ignitor
Wire
24) Connect the DC spark generator wires
to the SIT Valve with the screw, which is provided in the kit.
U32-5 FPI Direct Vent Gas Insert
19
Page 20
INSTALLATION
25) Locate the ground lug.
For P36D-1 / P36-4 Only:
25a) By the receptical box, left of the unit.
For U32-5 Only:
25b) Located on the left side of the unit.
28) Install the 1/2" bushing to the heat
shield.
29) Plug the DC spark generator wires to the
DC Sparker.
32) Mount the heat shield to the DC Sparker.
Secure into place with the velcro, which is provided in the kit.
33) Find a location which is not too hot and
is easy to reach for changing the battery.
Note: It should be kept away from the
chain.
Chain
26) Connect one end of the supplied green
ground wire to the lug with the nut and washer from the kit.
Ground
wire from
kit
27) Run the other end of the ground wire
and DC spark generator wires through the bushing on the heat shield.
Heat Shield
30) Connect the ground wire to the DC Sparker
mounting bracket.
31) Install the supplied battery into the DC Sparker Box by opening the battery compartment.
Battery
Compartment
34) Tie up the loose wires with the wire clip.
35) Check for gas leaks.
36) Check inlet and outlet pressures.
37) Check operation of fl ame control.
38) Check for proper fl ame appearance and
glow on logs.
NOTE: The battery in the DC Sparker
Box will need to be replaced an­ nually.
20
U32-5 FPI Direct Vent Gas Insert
Page 21
FULL SCREEN DOORS
INSTALLATION
1) Hold the full screen door frame up against the unit in order to make
the following wire connections.
Pull the ON/OFF connector wires from the fi rebox and connect them
to the switch.
Connect the fan switch wires with the wire connectors from the fan
speed control. Place clips over wires and tuck into side trim.
3) Completely secure the full screen door frame to the unit by securing
4 screws to the Left and Right Side Trims.
.
NOTE: When mounting the full screen door frame to the unit, the
inside fl ange of the side trims are to fi t over the inner side of the unit ange and NOT next to the outer side of the unit fl ange.
2) Lift unit up slightly and push down on the corners of the Bottom Trim
Bracket and slide under unit. Unit should touch tabs on Bottom Trim Bracket.
Push in Corners
Bottom Trim Bracket
Inside fl ange of Side Trim goes over
the inner side of the unit fl ange.
U32-5 FPI Direct Vent Gas Insert
21
Page 22
INSTALLATION
4) Install Spring Hinges on the Left and Right Side of the bottom of the
rebox using 2 screws per hinge.
5) Place Bottom Frame near hinge. Flip hinge over Bottom Frame and
secure with 3 screws.
Hinge Location
Bottom Frame
7) Install the Left and Right Side Screen Doors in the fully open position
by placing over top of the hinges on the full screen door frame.
Hinge
Screen Door
8) Close screen doors.
6) The Top Frame is held in place by friction t, if the frame needs to
be adjusted; bend the bracket accordingly.
Top Frame
NOTE: If you fi nd that the doors do not align properly, adjust the
hinges on the door(s) by loosening them and adjust accordingly.
22
U32-5 FPI Direct Vent Gas Insert
Page 23
INSTALLATION
CONTEMPORARY FACEPLATE AND DOORFRAME INSTALLATION
Kit# 425-914 Contents List:
1 Complete Faceplate with Switches 1 Door Frame 1 Bottom Louver 2 Hinges 2 Bottom Louver Brackets 4 Pan Head Screws 1 Wire Clip 1 Instruction Sheet
1) Bring the faceplate up in front of the unit and connect the red &
black ON/OFF wires from the unit to the ON/OFF switch on the back of the left side of the faceplate.
2) Connect the grey coated female ends of the black & red fan wires
from the unit to the male ends of the fan rheostat on the left side of the faceplate as shown.
Note: Ensure that the fl anges on the sides of the fi rebox are on the outside, when installing the faceplate (see below).
Faceplate
Flange on fi rebox
4) Fold down the 2 hinges on the bottom frame to a fl at position. The bottom frame is installed with a friction fi t - the opening in the corner of each hinge slides over the metal lip located on the fl oor of the unit.
Note: Ensure the bottom frame is positioned properly before installing, by making sure there is equal spacing on either side.
Openings on hinge
Metal Lip
Fan Rheostat
3) Position faceplate on unit lining up screw holes on faceplate with screw holes on unit - secure with 4 screws.
5) Push both bottom frame hinges down on the metal lip until
they are fully seated.
6) Flip bottom louver up to close.
U32-5 FPI Direct Vent Gas Insert
23
Page 24
INSTALLATION
7) Install the door frame by hooking the top fl ange over the top of the glass door.
8) Lower the door frame gently into place.
9) Run supplied 120V power cord along front face of masonry fi replace and plug into nearest receptacle.
10) Slide unit into fi nal position.
Completed Faceplate & Door Frame Installation
24
U32-5 FPI Direct Vent Gas Insert
Page 25
INSTALLATION
OPTIONAL HEARTH TRIM INSTALLATION
The Hearth Trim is an option that can be used to fi nish off the installation when the bottom of the fi replace is higher than the hearth or to raise the fi replace. The faceplate is assembled fi rst and then the hearth trim is attached to the faceplate. There are 2 Hearth Trim options; a 2" and a 4".
2" Hearth Trim Installation:
1) Attach the Hearth Trim to the bottom of the faceplate side
panels with the screws provided (3 per side) as shown in diagram 1. The holes in the Hearth Trim are oblong so the trim can be adjusted inwards or outwards as needed to suit fi nishing.
NOTE: Don't tighten the screws down completely at this point,
do a trial fi t to the unit, make any necessary adjustments, when trim fi ts properly, tighten the screws.
4" Hearth Trim Installation:
1) Secure the two 2" hearth trim pieces together as shown in
diagram 2. Secure using the 2 screws provided.
2) Attach the now 4" Hearth Trim to the bottom of the faceplate
side panels with the screws provided (3 per side) as shown in diagram 1. The holes in the Hearth Trim are oblong so the trim can be adjusted inwards or outwards as needed to suit fi nishing.
Diagram 2
U32-5 FPI Direct Vent Gas Insert
Diagram 1
25
Page 26
INSTALLATION
LOW PROFILE FACEPLATE INSTALLATION
Attach the inner faceplate panel to the insert body using 4 screws
1)
in the locations shown below.
Diagram 1
Diagram 2
4) Tuck the wires into the clip to keep them away from the insert using the clip provided. Attach the clip to the rear of the faceplate to en­sure that the wires do not touch the side of the unit. The power cord should be run behind the inner faceplate panel.
5) Install the on /off switch - fan speed control box to the left hand bot-
tom leg of the inner faceplate. Controls located on the left side.
Diagram 5
6) Secure the wires to the back of the inner faceplate with a wire clip.
2) Connect the male end black and red fan switch wires (in the
black casing) to the wire connectors from the fan speed control.
Diagram 3
3) Connect the female ends of the ON/OFF switch - to the ON/OFF
switch in the control box.
Wire clip
Diagram 6
7) Attach the 2 bottom louver hinges to the bottom fl ange on the fi rebox using 2 screws per hinge.
26
Diagram 4
Diagram 7
U32-5 FPI Direct Vent Gas Insert
Page 27
INSTALLATION
8) Attach the bottom louver to the 2 hinges using 2 screws per
hinge.
Diagram 7
9) Install the top door pressure retainer, required.
10) Take the outer faceplate, line up the openings on the left and right
legs and install onto the inner faceplate panel pins.
Inner faceplate panel pins
Diagram 10
Outer faceplate
Diagram 8
Diagram 9
Final Install
Diagram 11
40-3/4” (1036mm)
35-15/16” (912mm)
27-7/8” (708mm)
14-5/8” (371mm)
23-15/16” (607mm)
21-15/32” (545mm)
U32-5 FPI Direct Vent Gas Insert
27
Page 28
INSTALLATION
LOW PROFILE HEARTH TRIM
OPTIONAL HEARTH TRIM
INSTALLATION
Hearth Trim is an option that can be used to fi nish off the installation when the bottom of the fi replace is higher than the hearth or to raise the fi replace.
1) For units L390E/HZI390E/L540E/HZI540E–remove 4 screws in locations shown below to remove outer faceplate.
Diagram 1–Screw Locations
1a) For units U31/U32/E21/E33–remove outer faceplate by lifting up
and off backing plate.
** If no screw holes are present.
3) Remove backing plate by removing 4 screws–lay down fl at.
Diagram 4–Backing Plate Removal Units L390E/HZI390E/L540E/
HZI540E
Diagram 2–Lift off Front Faceplate
**If no holes are present on the backing plate, proceed to the Step 3.
2) If screw holes are present on backing plate, secure the hearth trim to backing place with 2 screws on each side.
Hearth Trim
Diagram 3–Hearth Trim Secured to Backing Plate
28
Diagram 5–Backing Plate Removal Units U31/U32/E21/E33
4) Secure hearth trim to backing plate with a clip on each side as shown in Diagram 6. Ensure the hearth trim is evenly space on either side of the backing plate.
Clip
5) Reinstall backing plate.
6) Reinstall outer faceplate.
Diagram 6–Hearth Trim Clip
Hearth Trim
U32-5 FPI Direct Vent Gas Insert
Page 29
INSTALLATION
OPTIONAL WALL
THERMOSTAT
A wall thermostat may be installed if desired, follow the wiring diagram below. FPI offers an optional programmable thermostat but any 250-750 millivolt rated non-anticipator type thermostat that is CSA, ULC or UL approved may be used.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size Max. Length
14 GA. 16 GA. 18 GA. 20 GA. 22 GA.
CAUTION
Do not connect the millivolt wall
thermostat wires
to the 120V wires.
50 Ft. 32 Ft. 20 Ft. 12 Ft.
9 Ft.
FINAL CHECK
Before leaving this unit with the customer, the installer must ensure that the appliance is fi ring correctly. This includes:
1) Clocking the appliance to ensure the
correct fi ring rate (rate noted on label) at 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow the unit to burn for 15 min. to stabilize.
3) Check for proper draft.
CAUTION
Any alteration to the product that causes sooting or carboning that results in damage to the exterior facia is not the responsibility of the manufacturer.
OPTIONAL REMOTE
CONTROL
Use the FPI Remote Control Kit approved for this unit. Use of other systems may void your warranty.
The remote control kit comes with a hand held transmitter, a receiver and a wall mounting plate.
1) Choose a convenient location on the wall
to install the receiver and the receptacle box (protection from extreme heat is very important). Run wires from the fi replace to that location. Use Thermostat Wire Table.
2) Connect the wires as per the wiring diagrams
below.
CAUTION
Do not connect the millivolt
remote control wires for
to the 120V wires.
3) Install 3 AAA alkaline batteries in transmitter
and 4 AA alkaline batteries in the receiver. Install the receiver and its cover in the wall. Switch the remote receiver to "remote" mode. The remote control is now ready for operation.
U32-5 FPI Direct Vent Gas Insert
29
Page 30
INSTALLATION
WIRING DIAGRAMS
This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/ thermostat will continue to operate. However, a 120V A.C. power supply is needed for the fan/blower operation.
Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges.
For NATURAL GAS Units and Units NOT Equipped with DC Spark Boxes
Green
Fan
BlackBlack
Control
Pilot
Assembly
Thermopile
Gas Pilot
Electrode
120V AC
Thermocouple
To Thermocouple IN
Neutral
Live
Minimum Convection
Air Temp. Switch
Ground
Ground
ON OFF
Red
Rotary Speed
Black
Gas In
Thermocouple
O
N
T
O
L
I P
F
F
O
"S.I.T" Valve
In
I
H
L
O
Regency
Remote Transmitter
(Optional)
White
Brown
Piezo Ignitor
ONOFF
Remote
Receiver
(Optional)
(Millivolt)
Thermostat
(Optional)
(Millivolt)
Black
Red
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
WARNING: Electrical Grounding Instructions This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three­prong receptacle. Do not cut or remove the grounding prong from this plug.
ON
OFF
Burner
30
U32-5 FPI Direct Vent Gas Insert
Page 31
INSTALLATION
For PROPANE Units and Units Equipped with DC Spark Boxes*
*For installation of the DC Spark Box refer to the LP Conversion instructions in this manual.
U32-5 FPI Direct Vent Gas Insert
31
Page 32
OPERATING
INSTRUCTIONS
Before operating this appliance, proceed through the following check list.
1) Read and understand these Instructions before operating this appliance.
2) Check to see that all wiring is correct and enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass door is in place. Never
operate the appliance with the door glass removed.
5) Verify that all venting and the cap is unobstructed.
6) Verify log placement. If the pilot cannot be seen when lighting the unit - the logs or the embers have been incorrectly positioned.
7) The unit should never be turned off and on again without a minimum of a 60 second wait.
8) When lighting the appliance, the inside of the glass may fog up. This will burn off after a few minutes of operation.
DO NOT BURN THE APPLIANCE WITH THE GLASS ASSEMBLY REMOVED.
LIGHTING
PROCEDURE
IMPORTANT
To ignite or reignite the pilot, you must fi rst
release the tension springs below the door.
Only when the pilot holds, without pressure being applied to the control knob, reapply the tension springs to the door. The unit must not be operated with the tension springs unattached.
NOTE: For all propane units and units equipped with electric spark boxes, see "Copy of Light­ing Plate Instructions" section for more details.
IMPORTANT: Gas on/off knob cannot be turned from "PILOT" to "OFF" unless it is partially depressed.
1) Open the bottom louver assembly
2) If the control knob is in the "OFF" position
proceed to Step 5.
3) Push in gas control knob slightly and turn
clockwise to "OFF". Knob cannot be turned from "PILOT" to "OFF" unless knob is pushed in slightly. Do not force.
4) Wait fi ve minutes to allow gas, that may
have accumulated in the main burner compartment, to escape. If you do smell gas, follow the instructions on the front of this manual. If you don't smell gas continue on to the next step.
5) Turn the gas control counter clockwise to
"PILOT".
6) Push in control knob all the way and hold
in. Continually push and release the black button on spark igniter until pilot lights. Continue to hold the control knob in for approximately one minute, then release the gas control knob. The pilot fl ame should continue to burn. If the pilot does not remain lit, repeat operation allowing a longer period before releasing gas control knob.
7) Turn gas control knob counter clockwise to
"ON".
8) Use the rocker switch to operate main burner.
9) Rotate the variable ame control to adjust
the fl ame height higher or lower.
10) Close the bottom louver assembly.
SHUTDOWN
PROCEDURE
1) Use the rocker switch to turn off the main
burner.
2) Open the bottom louver assembly.
3) Push in the gas control knob slightly and
turn clockwise to "OFF". Do not force.
4) Disconnect all electric power and gas to the
appliance if service is to be performed.
FIRST FIRE
The fi rst fi re in your stove is part of the paint curing process. To ensure that the paint is properly cured, it is recommended that you burn your fi replace for at least four (4) hours the fi rst time you use it with the fan on. When rst operated, the unit will release an odour caused by the curing of the paint, the burning off of any oils remaining from manufacturing. Smoke detectors in the house may go off at this time. Open a few windows to ventilate the room for a couple of hours.
The glass panel may require cleaning
after the unit has cooled down. DO
NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS HOT.
Note: When the glass is cold and the
appliance is lit, it may cause condensation and fog the glass. This condensation is normal and will disappear in a few minutes as the glass heats up.
DO NOT BURN THE APPLIANCE WITHOUT THE GLASS FRONT IN PLACE.
During the fi rst few fi res, a white fi lm may develop on the glass front as part of the curing process. The glass should be cleaned or the fi lm will bake on and become very diffi cult to remove. Use a non-abrasive cleaner and NEVER clean the glass while it is hot.
AUTOMATIC
CONVECTION FAN
OPERATION
The fan operates automatically, turn the knob on the side of the faceplate to adjust to the desired speed. The fan will turn on as the stove comes up to operating temperature. After the unit has been turned off and the unit cooled to below a useful heat output range the fan will shut off automatically.
NORMAL OPERATING
SOUNDS OF
GAS APPLIANCES
It is possible that you will hear some sounds from your gas appliance. This is perfectly normal due to the fact that there are various gauges and types of steel used within your appliance. Listed below are some examples. All are normal operating sounds and should not be considered as defects in your appliance.
Blower:
FPI gas appliances use high tech blowers to push heated air farther into the room. It is not unusual for the fan to make a "whirring" sound when ON. This sound will increase or decrease in volume depending on the speed setting of your fan speed control.
Burner Tray:
The burner tray is positioned directly under the burner tube(s) and logs and is made of a different gauge material from the rest of the fi rebox and body. Therefore, the varying thicknesses of steel will expand and contract at slightly different rates which can cause "ticking" and "cracking"
Page 33
OPERATING INSTRUCTIONS
1) Push in gas control knob slightly and turn to “PILOT” position.
2) Push in control knob all the way and hold in untilthe pilot lights up. Continue to hold the control knob in for about 20 seconds after the pilot is lit. Release knob.
3) Push in gas control knob slightly and turn to "ON" position.
4) Turn ON the flame switch.
2) Wait fi ve (5) minutes to clear out any gas. If you then smell gas STOP! follow “B” in the safety information above on this label. If you don’t smell gas, go to the next step.
3) Turn knob on gas control counterclockwise to “PILOT”.
4) Push in control knob all the way and hold in. Immediately push black button on spark igniter until pilot lights. Continue to hold the control knob in for about 1/2 minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 3) and 4). If
knob does not pop up when released, stop and immediately call
your service technician or gas supplier.
If the pilot will not stay lit after several tries, turn the gas control
knob to “OFF” and call your service technician or gas supplier.
5) Turn gas control knob counterclockwise to “ON”.
6) Use rocker switch to operate main burner.
DO NOT REMOVE THIS INSTRUCTION PLATE
FOR YOUR SAFETY READ BEFORE LIGHTING
A) This appliance has a pilot which must be lighted by hand, following the instructions below exactly
.
B) BE FORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the fl
oor because some gas is heavier than
air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electric switch, do not use any phone in your building
- Immediately call your gas supplier from a neighbors phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
C) Us
try to
repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and
to replace any part of the control system and any gas control which has been under water.
E) Thisappliance needs fresh air for safe operation and must be installed so there are provisions adequate combustion + ventilation air.
918-474b
OFF
WARNING: If you do not follow these instructions exactly, a fireor explosion may result causing property damage,
or additional information consult a qualified installer, service agency or gas supplier.
LIGHTING INSTRUCTIONS
TO TURN OFF GAS APPLIANCE
THERMOPILE ELEMENT THERMO­ELECTRIQUE
PILOT BURNER VEILLEUSE
1/
NFPA 54, or Natural Gas and Propane Installation Codes, CSA B149.1. (Australia:A S5601-2004, New Zealand: NZS 5261)
FOR UNITS NOT EQUIPPED WITH ELECTRIC SP
ARK:
. Keep burner
appliance.
STOP! Read the safety information above on this label.
FORALL PROP
ANE UNITS
AND
UNITS EQUIPPED WITH ELECTRIC SPARK BOXES:
1)
Push in gas control knob slightly and turn clockwise
to “OFF”. Knob cannot be turned from “PILOT” to “OFF” unless knob is pushed in slightly. Do not force.
1) Turn off
the flame switch.
2) Push in the gas control knob slightly a
nd turn clockwise to “OFF”. Do not force.
3) Turn off all electric power to the applianc
e if service is to be perfor
med.
You may shut off
the pilot during prolonged non use periods to conserve fuel.
l
sounds. You should also be aware that as there are temperature changes within the unit these
COPY OF LIGHTING INSTRUCTION PLATE
sounds will likely re-occur. Again, this is normal for steel fi reboxes.
Blower Thermodisc:
When this thermally activated switch turns ON it will create a small "clicking" sound. This is the switch contacts closing and is normal.
Pilot Flame: While the pilot fl ame is on it can make a very slight "whisper" sound.
Gas Control Valve: As the gas control valve turns ON and OFF, a dull clicking sound may be audible, this is normal operation of a gas regulator or valve.
Unit Body/Firebox: Different types and thicknesses of steel will expand and contract at different rates resulting in some "cracking" and "ticking" sounds will be heard throughout the cycling process.
MAINTENANCE
INSTRUCTIONS
1) Always turn the gas valve to off before
2) Clean (never when unit is hot) appliance,
The heater is fi nished in a heat resistant
3) Make a periodic check of burner for proper
4) The appliance and venting system must be
During the annual service call, the burners
5) Keep the area near the appliance clear and
U32-5 FPI Direct Vent Gas Insert
cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year. When cleaning the logs, use a clean soft paint brush as the logs are fragile and easily damaged.
door and louvers with a damp cloth. Never use an abrasive cleaner. The gold louvers (and optional gold door) may be scratched if abrasives are used to clean them.
paint and should only be refi nished with heat resistant paint (not with wall paint). FPI uses StoveBrite Paint - Metallic Black #6309.
position and condition. Visually check the ame of the burner periodically, making sure the fl ames are steady; not lifting or fl oating. If there is a problem, call a qualifi ed service person.
inspected before use, and at least annually, by a qualifi ed fi eld service person, to ensure
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURE AND SHOULD STAY AW AY TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
that the fl ow of combustion and ventilation air is not obstructed.
should be removed from the burner tray and cleaned. Replace the embers but do not block the pilot.
free from combustible materials, gasoline and other fl ammable vapours and liquids.
CAUTION: ANY SAFETY SCREEN OR GUARD REMOVED FOR SERVICING AN APPLIANCE MUST BE REPLACED PRIOR TO OPERATING THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE.
6) Each time the appliance is lit, it may cause
condensation and fog the glass. This condensation and fog is normal and will disappear in a few minutes as the glass heats up.
Never operate the appliance without the
glass properly secured in place or with the door open.
7) Do not use this appliance if any part has been
under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace nay part of the control system and any gas control which has been under water.
8) Periodically check the pilot ames. Correct
ame pattern has three strong blue fl ames: 1 owing around the thermopile and 1 around
the thermocouple, and 1 fl owing across the rear of the burner (it does not have to be touching the burner).
3333
Page 34
Top View of pilot fl ame
Incorrect fl ame pattern will have small, probably yellow fl ames, not coming into proper contact with the rear of the burner or thermopile.
Top View of pilot fl ame
If you have an incorrect fl ame pattern, contact your FPI dealer for further instructions.
GENERAL VENT
MAINTENANCE
Conduct an inspection of the venting system semi-annually. Recommended areas to inspect as follows:
1) Check the Venting System for corrosion in
areas that are exposed to the elements. These will appear as rust spots or streaks, and in extreme cases, holes. These components should be replaced immediately.
2) Remove the Termination Cap, and shine a
ashlight down the Vent. Remove any bird nests, or other foreign material.
3) Check for evidences of excessive
condensation, such as water droplets forming in the inner liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fi ttings. It may be caused by having excessive lateral runs, too many elbows, and exterior portions of the system being exposed to cold weather.
4) Inspect joints, to verify that no pipe
sections or fi ttings have been disturbed, and consequently loosened. Also check mechanical supports such as Wall Straps, or plumbers' tape for rigidity.
LOG REPLACEMENT
The unit should never be used with broken logs. Turn off the gas valve and allow the unit to cool before opening door to carefully remove the logs. The pilot light generates enough heat to burn someone. If for any reason a log should need replacement, you must use the proper replacement log. The position of these logs must be as shown in the diagram under Log Installation.
GOLD-PLATED TRIM
The 24 carat gold plated fi nish on the trim requires little maintenance, and need only be cleaned with a damp cloth. DO NOT use abrasive materials or chemical cleaners, as they may harm the fi nish and void the warranty. Clean
any fi ngerprints off before turning the unit on. If the top louvers start to discolour, check the door gasket seal and replace if necessary.
DOOR GLASS
Your FPI insert is supplied with high temperature, 5 mm Neoceram ceramic glass that will withstand the highest heat that your unit will produce. If your glass requires cleaning, we recommend using an approved glass cleaner available at all authorized dealers. Do not use abrasive materials. Do not clean the glass when hot.
In the event that you break your glass by impact, purchase your replacement from an authorized FPI dealer only, and follow our step-by-step instructions for replacement.
Warning: Do not operate appliance with glass panels removed, cracked or broken. Replacement of the glass should be done by a licensed or qualifi ed service person.
Caution: Wear gloves when removing damaged or broken glass.
Flush Glass Replacement
Remove the fl ush door front (as per instructions in section "Standard Flush Doo"). Remove the 4 glass clips from each corner. Slide in the new replacement glass. Push the 4 glass clips back onto the frame.
NOTE: Improper positioning of logs may create carbon build-up and will alter the unit’s performance which is not covered under warranty.
GLASS GASKET
If the glass gasket requires replacement use glass gasket (Part # 936-265) for the Bay Front and a tadpole gasket for the Flush Front (Part # 936-155).
Page 35
MAINTENANCE
Bay Glass Removal
1) Remove the door from the unit and place
on a soft surface to prevent scratching.
2) Remove the nuts holding the glass retainers
in place.
3) Remove the glass retainers (sides, top and
bottom).
4) Replace the glass. The glass must have gasketing around it.
5) Reverse the previous steps, replace the
retainers and fasten with the nuts but do not over tighten, as this can break the glass.
6) Replace door on the stove and check the seal.
TO REMOVE FAN:
1) Turn the unit off and allow it to cool to room
temperature.
2) Unplug or disconnect power source to
stove.
3) Remove glass front (see section "Standard
Flush Door.")
4) Remove logs and brick panels, if used.
5) Remove the grate by loosening the two
screws and sliding the grate out.
6) Remove the burner/front log support
assembly by removing the 2 screws and lifting it out.
Grate screws
7) Remove the 2 screws holding the Air Intake
Hood to the rear fi rebox wall and lift out.
10) Unplug the wires from the fan motor (from
inside the stove).
11) Lift Fan Assembly off of the 2 pins, tip forward
and pull through fi rebox opening.
12) Disconnect green wire from power cord.
FAN MAINTENANCE
If your fan requires maintenance or replacement, access to the fan is through the plate on the rear wall of the fi rebox. NOTE: the unit MUST NOT
be operated without the fan access panel securely in place.
Caution: Label all wires prior to disconnecting when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper
operation after servicing.
8) Remove the 10 screws holding the Access
Panel in place.
9) Remove the Fan Air Duct by loosening the
3 screws, squeeze the sides together to remove.
Replacing fan:
Reverse above steps. Hint for pushing fan down onto pins - rub a bit of dish soap on the grommet so it will slide more easily onto the pin.
Check to make sure the fan is seated properly on the pins, this is very important- try to move the fan back and forth, there should be no noise, if there is check that the grommets haven't come loose.
Seal fan access panel using high temperature silicone (sparingly).
U32-5 FPI Direct Vent Gas Insert
35
Page 36
MAINTENANCE
VALVE REPLACEMENT
1) Shut off the gas supply.
2) Remove the louvers (and bay door if it is
on).
3) Open the ush door and remove the door.
4) Remove the logs and brick panels.
5) Remove the grate by loosening the two
screws and sliding the grate out.
Grate screws
6) Remove the burner assembly by removing
the 2 screws and lifting it out.
11) Push the valve assembly to the left and lift
the entrire assembly out.
12) Remove the valve by removing the 4 screws
in the base of the valve tray.
13) Undo the pilot tube from the valve with a 7/16" wrench.
14) Undo the quick drop out thermocouple nut
on the valve with a 9mm (metric) wrench.
5) Reconnect the pilot tube nut with a 7/16"
wrench.
6) Re-attach the valve mounting bracket to the
valve tray.
7) Scrape off the old gasket from the fl oor of
the fi rebox and from the valve tray.
8) Install a new gasket and reinstall the valve assembly.
Note: Failure to install a new gasket may severely affect the appliance performance.
9) Reinstall the 11 hold down screws.
10) Hook up the TP, TH, and TP/TH wires to
the appropriate connections on the valve.
11) Reinstall the burner assembly.
7) Remove the 2 screws holding the Air Intake
Hood to the rear fi rebox wall and lift out.
8) Disconnect the inlet gas line.
9) Disconnect the TP wire, the TH wire, and
the TH/TP wire from the valve.
10) Remove the 11 Phillips head screws securing
the valve tray in place. and then lift the entire assembly out.
15) Undo the "gas out" fl are nut with a 13/16"
wrench.
16) Undo the "gas out" fl are fi tting with an 11/16"
wrench.
17) Remove the valve mounting brackets.
Hint: If you are using black pipe, ensure that there is a union by the valve, otherwise removal will be almost impossible.
INSTALLING VALVE
1) Re-attach the valve mounting brackets to
the valve.
2) Reconnect the "gas out" fl are fi tting with an
11/16" wrench.
Note: when installing the burner assembly
be sure to slide the aeration adjustment wire
through the hole in the base of the burner
tray.
12) Install the grate.
13) Hook up the gas line and check for gas
leaks with a soap and water solution or a gas leak detector. (Do not use open fl ame for leak testing.)
13) Fire up the unit temporarily and check the
manifold pressure.
14) Reinstall the vermiculite, embers, rockwool,
logs and brick panels as needed.
36
3) Reconnect the "gas out" fl are nut with a . 13/16" wrench.
4) Reconnect the quick drop out thermocouple
nut with a 9mm wrench.
15) Close the door and replace the louvers.
16) Fire up the unit again and check for proper
ame appearance and glow on logs.
U32-5 FPI Direct Vent Gas Insert
Page 37
21
21
BRICK PANEL SET
36
34
33
12
44
42
42
46
45
47
48
50
43
51
36
35
3
1
2
5
17
7
18
13
19
15
14
16
8
10
52
53
9
41
MAIN ASSEMBLY
Part # Description Part # Description
1) 420-122 Fan Access Panel
2) 420-142 Gasket - Fan Access Panel 422-518/P Fan Assembly:
3) 910-215/P Fan Motor (120 V)
5) 910-750 Power Cord (120 V) 910-752 Wire Harness (intermediate)
7) 910-142 Thermodisc-Fan Auto ON/OFF
8) * Fan Switch Cover
9) * Thermodisc Bracket
10) 420-140 Flue Restrictor
12) 420-119 Air Hood
13) * Levelling Bolt 5/16 x 3" Hex Hd
14) 948-045 Jack Chain
15) 948-247 Spring Lever Handle
16) 948-025 Door Extension Spring
17) * Wire Holder Clip
18) * Strain Relief
19) * Grommet for Power Cord 514-972 Conversion Kit to Propane 918-846 Manual
21) 420-920 Flush Louvers (Set) - Black/Gold 420-922 Flush Louvers (Set) - Black 420-923 Flush Louvers (Set) - Black/Steel
422-901 Brick Panel Set - Standard Brown 422-902 Brick Panel Set - Standard Red 422-903 Brick Panel Set
- Herringbone Brown
33) * Brick Panel - Right Side
34) * Brick Panel - Left Side
35) * Brick Panel - Back
36) 400-090 Brick Clip
41) 420-157 Gasket - Transition Box Bottom
42) 420-054 Gasket - Transition Box Top
43) * Stove Top
44) 420-048 Thermal Insulation
45) * Adaptor Stop
46) * Adaptor Holding Brkt-Left
47) * Adaptor Holding Brkt-Right
48) 320-518 Flue Adaptor Assy
50) * Insulation Hold Down Brkt
51) 420-170 Top Fan Air Channel
52) 420-171 Upper Fan Air Channel
53) 420-172 Lower Fan Air Channel
*Not available as a replacement part.
Page 38
PARTS LIST
BURNER ASSEMBLY & LOG SET
Part # Description
423-574/P Valve Assembly - NG 423-576/P Valve Assembly - LP
52) 910-478 Valve - SIT NG / LP
53) 910-190 Ignitor Piezo and Nut
55) * Valve Tray
58) 904-240 Burner Orifi ce Nat. Gas #37 904-390 Burner Orifi ce LP # 52 936-170 Orifi ce Gasket
66) 910-038 Pilot Assembly - 3 Flame (NG) 910-039 Pilot Assembly - 3 Flame (LP)
67) * Pilot Holder
68) W840470 Pilot Assembly Gasket
425-930 Log Set
70) 420-143 Valve Tray Gasket
71) 402-526 Grate/Diffuser Assy
72) 402-519 Burner Assembly (NG/LP)
73) * Log Tray Mount Bracket
74) * Log Tray Rear
90) 910-421 Pilot ON/OFF 3" (SIT) Extension Knob
91) 910-422 HI/LOW 3" (SIT) Extension Knob
*Not available as a replacement part.
38
U32-5 FPI Direct Vent Gas Insert
Page 39
PARTS LIST
FLUSH FRONT ASSEMBLY
Part # Description
Flush Door
422-530 Complete Flush Door Assy
112) 904-196 1" Round Magnet
135) 940-307/P Flush Glass
137) 904-691 U Clip
139) 936-155 Tadpole Glass Gasket
149
112
112
137
139
135
137
137
112
137
FLUSH FRONT
U32-5 FPI Direct Vent Gas Insert
112
140
39
Page 40
PARTS LIST
LOGOPLATEHERE
LOGOPLATEHERE
F ACEPLATE ASSEMBL Y
Part # Description Part # Description 402-919 Complete Faceplate (Set) Contour
with Black Trim-Oversize
51) * Faceplate Side Right - Oversize
59) * Faceplate Top - Oversize
60) * Faceplate Side Left Assy-Oversize 402-534 Trims Pkg. Black - Oversize, Zero Clearance
65) * Faceplate Trim Right - Oversize
68) * Faceplate Trim Top - Oversize
70) * Faceplate Trim Left Assy - Oversize
97) 910-246 2-way Gold Contact Switch
98) 910-330 Fan Speed Control (120 V)
99) 904-569 Fan Speed Control Knob (120 V)
400-917 Complete Custom Faceplate (Set)
71) * Faceplate Side Right - Custom
72) * Faceplate Top - Custom
73) * Faceplate Side Left - Custom
74) 904-586 Speed Control Knob c/w Spring Clip
99
180) 400-950 Hearth Trim 1" - Regular
181) 320-940 Hearth Trim 1" - Oversize
180) 400-926 Hearth Trim 2" - Regular
181) 320-942 Hearth Trim 2" - Oversize
180) 400-928 Hearth Trim 4" - Regular
181) 320-944 Hearth Trim 4" - Oversize
180) 400-959 Hearth Trim 6" - Regular
181) 320-946 Hearth Trim 6" - Oversize
190) * Screw #8 x 1/2" Black self-tapping
191) * Screw #8 x 1/2" Brass self-tapping
199) 948-216 Regency
®
Logo Plate
*Not available as a replacement part.
97
98
DETAIL 'A' REAR VIEW
SEE DETAIL 'A'
95
99
SEE DETAIL 'A'
68
402-918 Complete Faceplate (Set) Standard Contour with Black
Trim
91) * Faceplate Side Right - Standard
92) * Faceplate Top - Standard
93) * Faceplate Side Left Assy - Standard 402-532 Trims Pkg. - Standard Black 402-950 Trim Pkg. - Standard Brass
94) * Faceplate Trim Right - Standard
95) * Faceplate Trim Top - Standard
96) * Faceplate Trim Left Assy - Standard
97) 910-246 2-way Gold Contact Switch
98) 910-330 Fan Speed Control (120 V)
99) 904-569 Fan Speed Control Knob (120 V)
199
96
92
93
STANDARD SIZE FRONT VIEW
91
180
190
CUSTOM FACEPLATES REAR VIEW
190
191
94
199
190
181
60
59
70
L O G
O P L A T
E H E R
E
OVERSIZE FRONT VIEW
65
51
191
73
98
72
74
L O
G O P L
A T E
H E
R E
199
CUSTOM FACEPLATES FRONT VIEW
97
71
40
U32-5 FPI Direct Vent Gas Insert
Page 41
CONTEMPORARY FACEPLATE AND DOORFRAME
Part # Description
1) 425-512 Door Bottom Assembly
2) 425-513 Frame Inside
3) 425-514 Faceplate Outside
4) 425-942 Hearth Trim
PARTS LIST
3
2
1
U32-5 FPI Direct Vent Gas Insert
41
Page 42
PARTS LIST
Part # 425-924 Description
1) * Backplate Assembly
2) * Bottom Louver
3) * Right mounting bracket
4) * Left mounting bracket
5) * Front Frame
LOW PROFILE FACEPLATE
5
4
1
2
3
42
U32-5 FPI Direct Vent Gas Insert
Page 43
WARRANTY
c
L
h
h
g
o
a
e
g
n
n
r
d
a
i
d
c
n
l h
Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects ea
y before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchas
roduct. This warranty is not transferable.
nty: Limited Lifetime
stion chamber, heat exchanger, burner tubes/pans, logs, brick panels and gold plating (against defective manufacture only) are covered under the Limited
or fi ve (5) years for parts and subsidized labour* and parts only thereafter.
vered for lifetime against thermal breakage only, parts and subsidized labour* for fi ve (5) years and parts only thereafter from date of purchase.
sting, surrounds and grills are covered against cracks and warps resulting from manufacturer defects, parts and subsidized labour* for three (3) years from t
e and parts only thereafter.
ishes - One year on brushed nickel and antique copper full screens and doors. You can expect some changes in color as the product "ages" with constant . FPI warranties the product for any manufacturing defects on the original product. However, the manufacturers warranty does not cover changing colors and
rints, etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.
nd mechanical components such as blowers, switches, wiring, thermodiscs, FPI remote controls, spill switches, thermopiles, thermocouples, pilot assembly comp lves are covered for two years parts and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered rep s if new with appliance. ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from date of replacem
components are covered parts and subsidized labour* for three (3) years from date of purchase.
ura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.
lacement parts purchased by the consumer from FPI after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt o
to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.
s:
parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent p
fective part be returned to the distributor or agent Transportation Prepaid, if requested.
namel - Absolute perfection is neither guaranteed nor commercially possible. Any chips must be reported and inspected by an authorized dealer within three
. Reported damage after this time will be subject to rejection.
neral practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and ev
cturer defect.
rized selling dealer is responsible for all in-fi eld service work carried out on your Regency product. FPI will not be liable for results or costs of workmansh
ed service persons or dealers.
FPI reserves the right to inspect product in the fi eld which is claimed to be defective.
must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer
ate, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
s:
Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.
will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufa ucts evolve, fi eld modifi cations or upgrades will not be performed.
t be liable for travel costs for service work.
and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
ckwool, gaskets, door handles and paint are not covered under the terms of this warranty policy.
hich shows signs of neglect or misuse is not covered under the terms of this warranty policy.
ty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, neg
t, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mec
ch as furnaces, fans, clothes dryer, etc.
U32-5 FPI Direct Vent Gas Insert
43
Page 44
Register your Regency® warranty online
www.regency-fi re.com
Reasons to register your product online today!
• View and modify a list of all your registered products.
• Request automatic email notifi cation of new product updates.
• Stay informed about the current promotions, events, and special offers on related products.
Installer: Please complete the following information
Dealer Name & Address: ______________________________________________ ___________________________________________________________________ Installer: ___________________________________________________________ Phone #: ___________________________________________________________ Date Installed: ______________________________________________________ Serial No.: __________________________________________________________
FPI, Regency® and Hampton® are trademarks of FPI Fireplace Products International Ltd.
© Copyright 2012, FPI Fireplace Products International Ltd. All rights reserved.
Printed in Canada
Loading...