Do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of
this or any other appliance. To do so may result in an explosion or fire.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury,
exposure to hazardous materials* or loss of life. Review the information in this manual carefully. Installation and
service must be performed by a qualified installer, service agency or the gas supplier.
* This unit contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future
reference.
heater will operate is the same type as that
specified on the heater rating plate.
WARNING: Should overheating occur or the
gas supply valve fail to shut, do not turn off or
disconnect the electrical supply to the heater.
Instead, shut off the gas supply at a location
external to the heater.
WARNING: Do not use this heater if any part
has been under water. Immediately call a
qualified service technician to inspect the
heater and to replace any part of the control
system and any gas control which has been
under water.
WARNING: To minimize the possibility of
improper operation, serious personal injury,
fire, or damage to the heater:
• Always keep the area around the heater
free of combustible materials, gasoline,
and other flammable liquids and vapors.
• Heater should never be covered or have
any blockage to the flow of fresh air to the
heater.
WARNING: Risk of electrical shock. More
than one disconnect switch may be requir ed to
de-energize the equipment before servicing.
Indicates the presence of immediate hazards which will cause severe personal injury,
death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause severe personal
injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause minor personal
injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
WARNING - CALIFORNIA PROPOSITION 65: This product contains chemicals
known to the State of California to cause cancer, birth defects or other reproductive harm.
CAUTION: Operation of this heater in lowtemperature systems requires special piping.
Harmful internal condensation will occur if
the inlet water temperature does not exceed
105°F. Warranty claims will be denied when
condensation occurs.
CAUTION: If this heater is to be installed
above radiation level, it must be provided with
a low water cut-off device at the time of heater
installation.
CAUTION: This heater requires forced water
circulation when the burner is operating. See
minimum and maximum flow rates. Severe
damage will occur if the heater is operated
without proper water flow circulation.
CAUTION: If this heater is to be installed in
a negative or positive pressure equipment
room, there are special installation requirements. Consult factory for details.
2
Page 5
SECTION C: Installation
SECTION A
Before Installation
Raypak strongly recommends that this manual be reviewed thoroughly before installing your MVB heater.
Please review the General Safety information in Section B before installing the heater. Factory warranty
does not apply to heaters that have been improperly
installed or operated. (Refer to the warranty at the back
of this manual.) Installation and service must be performed by a qualified installer, service agency or gas
supplier. If, after reviewing this manual, you still have
questions which this manual does not answer, please
contact the manufacturer or your local Raypak representative.
Thank you for purchasing a Raypak product. We hope
you will be satisfied with the high quality and durability of our equipment.
Product Receipt
On receipt of your heater it is suggested that you visually check for external damage to the shipping crate. If
the crate is damaged, make a note to that effect on the
Bill of Lading when signing for the shipment. Remove
the heater from the shipping packaging. Report any
damage to the carrier immediately.
When ordering parts, you must specify the model and
serial numbers of the heater. When ordering under warranty conditions, you must also specify the date of
installation.
Purchased parts are subject to replacement only under
the manufacturer’s warranty. Debits for defective replacement parts will not be accepted and will be
replaced in kind only per Raypak’s standard warranties.
Model Identification
The model identification number and heater serial
number are found on the heater rating plate located on
the upper rear jacket panel of the heater. The model
number will have the form H7-2003 or similar
depending on the heater size and configuration. The
letter(s) in the first group of characters identifies the
application (H = Hydronic Heating, WH = Domestic
Hot Water (DHW)). The number which follows identifies the firing mode (7 = electronic modulation). The
second group of characters identifies the size of the
heater (three or four numbers representing the approximate MBTUH input), and, where applicable, a
letter, indicating the manufacturing series.
On occasion, items are shipped loose. Be sure that you
receive the correct number of packages as indicated on
the Bill of Lading.
Claims for shortages and damages must be filed with
the carrier by consignee. Permission to return goods
must be received from the factory prior to shipping.
Goods returned to the factory without an authorized
Returned Goods Receipt number will not be accepted.
All returned goods are subject to a restocking charge.
All Raypak heaters are National Board Approved, and
design-certified and tested by the Canadian Standards
Association (CSA) for the U.S. and Canada. Each heater
is constructed in accordance with Section IV of the
American Society of Mechanical Engineers (ASME)
Heater Pressure Vessel Code and bears the ASME stamp.
The heater also complies with the latest edition of
ASHRAE 90.1 Standard.
WARNING: Altering any Raypak pressure vessel by
installing replacement heat exchangers, tube bundle headers, or any ASME parts not manufactured and/or approved
by Raypak will instantly void the ASME and CSA ratings
of the vessel and any Raypak warranty on the vessel. Altering the ASME or CSA ratings of the vessel also
violates national, state, and local approval codes.
Installations at Elevation
Rated inputs are suitable for up to 4,500 ft elevation without de-rating. Consult the factory for installations at
altitudes over 4,500 ft above sea level. No hardware
changes are required to the heaters for installations up to
10,000 ft (adjustments may be required).
Top panel, blower and gas train omitted for clarity
Fig. 2: Component Locations - Top
Component Locations
Panels omitted for clarity
Fig. 1: Component Locations - Side
Fig. 3: Component Locations – Rear
General Information
Gas
Conn.
(NPT)
N P Flue Intake
Model
No.
MBTUH
Input
Water
Conn.
(NPT)
Max. Min.
503 500 125 2 1 1 6 6
753 750 188 2 1 1 6 6
1003 999 250 2-1/2 1-1/4 1 6 6
1253 1250 312 2-1/2 1-1/4 1 8 8
1503 1500 375 2-1/2 1-1/4 1 8 8
1753 1750 438 2-1/2 2 1 8 8
2003 1999 500 2-1/2 2 1 8 8
Vent Size
(in.)
Table A: Basic Data
4
Page 7
SECTION C: Installation
SECTION B
Hot Water Supply
General Safety
To meet commercial hot water use needs, the high limit
safety control on this water heater is adjustable up to
210°F. However, water temperatures over 125°F can
cause instant severe burns or death from scalds. When
supplying general purpose hot water, the recommended
initial setting for the control is 125°F.
Safety and energy conservation are factors to be considered when setting the water temperature on the
thermostat. The most energy-efficient operation will
result when the temperature setting is the lowest that
satisfies the needs of the application.
Water temperature over 125°F can cause instant severe
burns or death from scalds. Children, disabled and elderly are at highest risk of being scalded.
• Feel water before bathing or showering.
• Temperature limiting valves are available.
NOTE: When this water heater is supplying general
purpose hot water for use by individuals, a thermostatically controlled mixing valve for reducing point of use
water temperature is recommended to reduce the risk
of scald injury. Contact a licensed plumber or the local
plumbing authority for further information.
Maximum water temperatures occur just after the
heater’s burner has shut off. To determine the water
temperature being delivered, turn on a hot water faucet,
place a thermometer in the hot water stream and read
the thermometer.
This section applies to Hot Water Supply Boilers and
Hot Water Heaters ONLY. For sanitary rinse applications where outlet temperatures of 180°F to 195°F are
required, a boiler is recommended since the 210°F limit
on water heaters will NOT allow the heater to maintain
these desired sanitary rinse temperatures.
Water temperature over 125°F can
cause instant severe burns or death
from scalds.
Children, disabled, and elderly are
at highest risk of being scalded.
See instruction manual before setting temperature at water heater.
Feel water before bathing or showering.
Temperature limiting valves are
available, see manual.
5
Page 8
SECTION B: General Safety
Time/Temperature Relationships
in Scalds
The following chart details the relationship of water
temperature and time with regard to scald injury and
may be used as a guide in determining the safest water
temperature for your applications.
Water Temp. Time to Produce Serious Burn
120°F More than 5 minutes
125°F 1-1/2 to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
145°F Less than 3 seconds
150°F About 1-1/2 seconds
155°F About 1 second
Table courtesy of The Shriners Burn Institute
Table B: Time to Produce Serious Burn
CAUTION: Hotter water increases the risk of scald-
ing! There is a hot water scald potential if the
thermostat is set too high.
The temperature of the water in the heater can be regulated by using the Raypak Modulating Temperature
Control. To comply with safety regulations, the control
is set at 120°F when shipped from the factory (Mode 3
default setting for Tank Target).
To adjust the water temperature, follow the instruction
for the operation of the control starting on page 28 of
this manual. The control is shown below for identification purposes only. (See Fig. 4.)
Fig. 4: Modulating Temperature Control
6
Page 9
SECTION C: Installation
SECTION C
Installation
Installation Codes
Installations must follow these codes:
• Local, state, provincial, and national codes, laws,
regulations and ordinances
• National Fuel Gas Code, ANSI Z223.1/NFPA 54 –
latest edition (NFGC)
• National Electrical Code, ANSI/NFPA 70 - latest
edition (NEC)
• Standard for Controls and Safety Devices for Auto-
matically Fired Boilers, ANSI/ASME CSD-1,
(CSD-1) when required
• For Canada only: CAN/CSA B149.1 Natural Gas
and Propane Installation Code and CSA C22.1
C.E.C. Part 1 (C22.1)
Equipment Base
The heater should be mounted on a level, structurally
sound surface. The heater is approved for installation
on a combustible surface but must NEVER be installed
on carpeting. Gas-fueled equipment installed in enclosed parking garages must be located at least 18 in.
above the floor.
When such locations cannot be avoided, it is recommended that a suitable catch pan, adequately drained,
be installed under the appliance. The pan must not restrict air flow.
In addition, the heater shall be installed such that the
gas ignition system components are protected from
water (dripping, spraying, rain, etc.) during appliance
operation or service (circulator replacement, control
replacement, etc.).
Clearances
Indoor Installations
Heater
Side
Floor* 0” 0”
Rear 12” 24”
Right Side1” 1”
Left Side 1” 1”
Top 0” 10”
Front Open 24”
Vent 1” 1”
* DO NOT install on carpeting.
Table C: Clearances – Indoor Installations
Minimum Clearance
from Combustible
Surfaces
Recommended
Service
Clearance
7
Page 10
SECTION C: Installation
Fig. 5: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
U.S. Installations1 Canadian Installations2
Clearance above grade, veranda, porch, deck, or
A
balcony
1 ft (30 cm) 1 ft (30 cm)
4 ft (1.2m) below or to side
B Clearance to window or door that may be opened
of opening; 1 foot (30 cm)
3 ft (91 cm)
above opening
C Clearance to permanently closed window
* *
Vertical clearance to ventilated soffit located
D
above the terminal within a horizontal distance of
5 ft (1.5m)
*
2 ft (61cm) from the centerline of the terminal
E Clearance to unventilated soffit
F Clearance to outside corner
G Clearance to inside corner 6 ft (1.83m)
Clearance to each side of center line extended
H
above meter/regulator assembly
I Clearance to service regulator vent outlet
Clearance to non-mechanical air supply inlet to
J
building or the combustion air inlet to any other
4 ft (1.2m) below or to side
of opening; 1 ft (30 cm)
appliance
K Clearance to mechanical air supply inlet
Clearance above paved sidewalk or paved
L
driveway located on public property
3 ft (91 cm) above if within
10 ft (3m) horizontally
M Clearance under veranda, porch, deck or balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
2
In accordance with the current CAN/CGA-B149 Installation Codes
t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that serves both dwellings
TT Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal and underside of
veranda, porch, deck or balcony is greater than 1 ft (30cm)
* Clearances in accordance with local installation codes and the requirements of the gas supplier
* *
* *
*
3 ft (91 cm) within a height
*
15 ft above the me-
ter/regulator assembly
*
6 ft (1.83m)
3 ft (91 cm)
above opening
6 ft (1.83m)
7 ft (2.13m)
*
7 ft (2.13m) t
12 in. (30 cm) TT
Table D: Vent/Air Inlet Termination Clearances
8
Page 11
SECTION C: Installation
the heater to be serviced without removing any structure around the heater.
Outdoor Installations
These heaters are design-certified for outdoor installation. Heaters must not be installed under an overhang
that is less than 3 ft from the top of the vent terminal.
Three sides must be open in the area under the overhang. Roof water drainage must be diverted away from
heaters installed under overhangs.
Heater
Side
Min. Clearance
from Combustible
Surfaces
Rear 12” 24”
Right Side 1” 1”
Left Side 1” 1”
Top Unobstructed Unobstructed
Vent
12” 12”
Termination
Recommended
Service
Clearance
Venting not shown for clarity. Heater must be vented
per instructions in this manual
Fig. 6: Minimum Clearances from Combustible
Surfaces – Indoor and Outdoor Installations
When installed according to the listed minimum clearances from combustible construction, these heaters can
still be serviced without removing permanent structural
construction around the heater. However, for ease of
servicing, we recommend a clearance of at least 24 in.
in front, at least 24 in. on the rear and 10 in. above the
top of the heater. This will allow the heater to be serviced in its installed location without movement or
removal of the heater.
Service clearances less than the minimum may require
removal of the heater to service either the heat exchanger or the burner components. In either case, the
heater must be installed in a manner that will enable
Table E: Clearances – Outdoor Installations
The combustion air intake terminal MUST be used for
outdoor installations. The hood is shipped loose and
installed on the rear of the heater at the jobsite.
Combustion and Ventilation Air
NOTICE: Use of the heater in construction areas
where fine particulate matter, such as concrete or drywall dust, is present may result in damage to the burner
that is not covered by the warranty. If operated in a
construction environment, a clean source of combustion air must be provided directly to the heater.
Indoor Units
The heater must be supplied with sufficient quantities
of non-contaminated air to support proper combustion
and equipment ventilation. Combustion air can be supplied via conventional means where combustion air is
drawn from the area immediately surrounding the
heater, or via direct vent, where combustion air is
drawn directly from outside. All installations must
comply with the requirements of the NFGC (U.S.) and
B149.1 (Canada), and all local codes.
9
Page 12
SECTION C: Installation
CAUTION: Combustion air must not be contaminated
by corrosive chemical fumes which can damage the
heater and void the warranty. (See Section H.)
NOTICE: It is recommended that the intake vent be
insulated to minimize sweating.
Optional Construction Air Filter
An optional construction air filter is available for use.
The filter should be removed after construction is finished to allow for unrestricted air flow to the heater.
Direct Vent
If outside air is drawn through the intake pipe directly
to the unit for combustion:
1. Install combustion air direct vent in accordance
with Fig. 24 (horizontal) or Fig. 25 (vertical) of
this manual (pages 26 & 27 respectively).
2. Provide adequate ventilation of the space occupied
by the heater(s) by an opening(s) for ventilation air
at the highest practical point communicating with
the outdoors. The total cross-sectional area shall be
at least 1 in.
2
mm
per kW) of total input rating of all equipment
2
of free area per 20,000 BTUH (111
in the room when the opening is communicating
directly with the outdoors or through vertical
duct(s). The total cross-sectional area shall be at
least 1 in.
mm
2
2
of free area per 10,000 BTUH (222
per kW) of total input rating of all equipment
in the room when the opening is communicating
with the outdoors through horizontal duct(s).
3. In cold climates, and to mitigate potential freeze-
up, Raypak highly recommends the installation of
a motorized sealed damper to prevent the circulation of cold air through the heater during nonoperating hours.
TruSeal™ Combustion Air
In addition to the 3 previous steps, combustion air may
be ducted directly to the heater by using PVC, CPVC
or sealed single-wall galvanized ducting. The duct will
attach directly to the air collar located on the rear of the
heater, using three or four sheet metal screws (not supplied) equally positioned around the circumference of
the duct. The screen assembly should be removed before attaching any air duct to the heater. The screws
and duct connection point must be sealed with RTV
(not supplied). TruSeal is generally used when damaging contaminants are present in the mechanical room.
All ducting should be self-supported.
CAUTION: Use TruSeal combustion air if damaging
airborne contaminants are or may be present in the
heater area. See Section H of this manual regarding air
contamination.
Conventional Combustion Air Supply
U.S. Installations
All Air from Inside the Building
The confined space shall be provided with TWO per-
manent openings communicating directly with an
additional room(s) of sufficient volume so that the
combined volume of all spaces meets the criteria for a
room large in comparison (NFGC). The total input of
all gas utilization equipment installed in the combined
space shall be considered in making this determination.
Each opening shall have a minimum free area of 1 in.
per 1,000 BTUH (2,225 mm
rating of all gas utilization equipment in the confined
space, but not less than 100 in.
2
per kW) of the total input
2
(645 cm2). One opening shall commence within 12 in. (305 mm) of the top,
and one opening shall commence within 12 in. (305
mm) of the bottom of the enclosure. The minimum
dimension of air openings shall be not less than 3 in.
(76 mm) in any direction.
All Air from Outdoors
The confined space shall communicate with the outdoors in accordance with one of the methods below.
The minimum dimension of air openings shall not be
less than 3 in. (76 mm) in any direction. Where ducts
are used, they shall be at least of the same crosssectional area as the net free area of the openings to
which they connect.
1. Two permanent openings, one commencing
within 12 in. (305 mm) of the top, and one commencing within 12 in. (305 mm) of the bottom of
the enclosure, shall be provided. The openings
shall communicate directly, or by ducts, with the
outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
a. Where directly communicating with the out-
doors or where communicating to the outdoors
through vertical ducts, each opening shall
have a minimum free area of 1 in.
BTUH (550 mm
2
per kW) of total input rating
of all equipment in the enclosure.
2
per 4,000
2
10
Page 13
SECTION C: Installation
b. Where communicating with the outdoors
through horizontal ducts, each opening shall
have a minimum free area of 1 in.
BTUH (1,100 mm
2
per kW) of total input rat-
2
per 2,000
ing of all equipment in the enclosure.
2. One permanent opening, commencing within 12
in. (305 mm) of the top of the enclosure, shall be
permitted where the equipment has clearances of at
least 1 in. (25 mm) from the sides and back and 6
in. (152 mm) from the front of the appliance. The
opening shall directly communicate with the outdoors or shall communicate through a vertical or
horizontal duct to the outdoors or spaces that
freely communicate with the outdoors, and shall
have a minimum free area of:
a. 1 in.
2
per 3,000 BTUH (740 mm2 per kW) of
the total input rating of all equipment located
in the enclosure, and
b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING: Do not use the “one permanent opening”
method if the equipment room may be under negative
pressure conditions.
Canadian Installations
CAUTION: All combustion air must be drawn from
the air outside of the building; the mechanical equipment room must communicate directly with the
outdoors.
1. Ventilation of the space occupied by the heater
shall be provided by an opening(s) for ventilation
air at the highest practical point communicating
with the outdoors. The total cross-sectional area of
such an opening(s) shall be at least 10% of the area
required in 2. and 3. (below), but in no case shall
the cross-sectional area be less than 10 in.
2
cm
).
2. For heaters using a barometric damper in the vent
system there shall be a permanent air supply opening(s) having a cross section area of not less than 1
2
in.
per 7,000 BTUH (320 mm2 per kW) up to and
including 1 million BTUH, plus 1 in.
BTUH (160 mm
2
per kW) in excess of 1 million
BTUH. This opening(s) shall be either located at
or ducted to a point not more than 18 in. (450 mm)
nor less than 6 in. (152 mm) above the floor level.
The duct can also “goose neck” through the roof.
The duct is preferred to be straight down and ter-
2
(65
2
per 14,000
minated 18 in. (450 mm) from the floor, but not
near piping. This air supply opening requirement
shall be in addition to the air opening for ventilation air required in 1. (above).
WARNING: Care must be taken to ensure that the
equipment room is not under negative pressure
conditions.
3. For heaters not using a barometric damper in the
vent system, and when air supply is provided by
natural air flow from outdoors for a power burner
and there is no draft regulator, drafthood or similar
flue gas dilution device installed in the same space,
in addition to the opening for ventilation air required in 1., there shall be a permanent air supply
opening(s) having a total cross-sectional area of
not less than 1 in.
2
mm
per kW) of total rated input of the burner(s),
2
for each 30,000 BTUH (74
and the location of the opening(s) shall not interfere with the intended purpose of the opening(s)
for ventilation air referred to in 1. This opening(s)
can be ducted to a point not more than 18 in. (450
mm) nor less than 6 in. (152 mm) above the floor
level. The duct can also “goose neck” through the
roof. The duct is preferred to be straight down 18
in. (450 mm) from the floor, but not near piping.
4. Refer to B149.1 for additional information.
Water Piping
General
The heater should be located so that any water leaks
will not cause damage to the adjacent area or structures.
CAUTION: This heater requires forced water circula-
tion when the burner is operating. See Table F for
minimum and maximum flow rates for water pump
selection. The pump should be interlocked with the
heater to prevent heater operation without water circulation.
NOTICE: Minimum pipe size for in/out connections is
2 in. NPT for 503 and 753 models and 2-½ in NPT for
1003 – 2003 models. Verify proper flow rates and ∆T
as instructed in this manual.
11
Page 14
SECTION C: Installation
Relief Valve Piping
WARNING: Pressure relief valve discharge piping
must be piped near the floor and close to a drain to
eliminate the potential of severe burns. Do not pipe to
any area where freezing could occur. Refer to local
codes.
Hydrostatic Test
Unlike many types of heaters, this heater does not require hydrostatic testing prior to being placed in
operation. The heat exchanger has already been factory-tested and is rated for 160 psi operating pressure.
However, Raypak does recommend hydrostatic testing
of the piping connections to the heater and the rest of
the system prior to operation. This is particularly true
for hydronic systems using glycol-based antifreeze.
Raypak recommends conducting the hydrostatic test
before connecting gas piping or electrical supply.
Leaks must be repaired at once to prevent damage to
the heater. NEVER use petroleum-based stop-leak
compounds.
To perform hydrostatic test:
1. Connect fill water supply. With field-installed
bleed valve open, fill heater with water. When water flows from bleed valve, shut off water. Close
bleed valve. Carefully fill the rest of the system,
making sure to eliminate any entrapped air by using high-point air vents. Close feed valve. Test at
standard operating pressure for at least 24 hours.
2. Make sure constant gauge pressure has been main-
tained throughout test.
3. Check for leaks. Repair if found.
Cold Water Operation
CAUTION: Damage due to internal condensation may
occur if the heater inlet water temperature does not
exceed 120˚F (49ºC) within 7 minutes of start-up.
This heater is equipped with a proprietary condensate
evaporation system which will evaporate any condensate that may begin to accumulate inside the primary
heat exchanger with water temperatures as low as
120ºF (49ºC).
Heaters operated with an inlet temperature of less than
120ºF (49ºC) MUST have a manual bypass (see Fig.
14) or an approved low-temperature operation system
to prevent problems with condensation. This piping is
like a primary/secondary boiler installation with a bypass acting as the secondary boiler piping. Raypak
strongly recommends that thermometer(s) be placed
into the heater piping next to the in/out header to facilitate temperature adjustment. Inlet water temperatures
below 120ºF (49ºC) can excessively cool the products
of combustion, resulting in collection of condensate in
the heat exchanger area beyond the capacity of the
condensate evaporation system.
NOTE: Vent piping MUST contain a condensate
drain which is installed according to the vent manufacturer’s instructions and plumbed to an appropriate
condensate management system (field supplied).
Failure to reach or exceed 120ºF (49ºC) within 7 minutes may damage or cause failure of the heat exchanger,
combustion chamber, or other parts within the combustion chamber. It can cause operational problems, bad
combustion, sooting, flue gas leakage and reduced service life of the vent system. A bypass allows part of the
heater discharge water to be mixed with the cooler water returning to the heater inlet to increase the heater
inlet temperature above 120ºF (49ºC). This precautionary measure should prevent the products of combustion
from condensing beyond the ability of the condensate
management system employed in this heater in most
installations. Warranty claims will be denied for damage or failures caused by condensation.
Cold water operation issues are applicable to both cold
water start and cold water run applications. Cold water
operation for 7 minutes or less on initial daily start-up
is acceptable. Where cold water starts will last longer
than 7 minutes or where cold water operation is continuous, provisions must be made to mix higher
temperature outlet water with the colder inlet water and
thereby raise the inlet temperature to at least 120ºF
(49ºC) within the 7-minute time limit.
Cold Water Starts
Cold water starts, wherein the inlet water temperature
remains below 120ºF (49ºC) for more than 7 minutes,
must
have cold water start protection. Known pro-
tection methods consist of mixing heated outlet water
with the inlet water with a bypass to raise the inlet to
120ºF (49ºC) or higher. Once the system is heated up
and has return water temperatures of 120ºF (49ºC) or
higher, the mixing of outlet water with inlet water is no
longer needed and the bypass can be shut off. If the
bypass is not shut off as the system heats up, the outlet
temperature may continue to climb and trip the high
limit, thereby shutting down the heater. Thus an auto-
12
Page 15
SECTION C: Installation
matic valve system, such as a three-way proportional
valve or a modulating two-way valve to control the
bypass, should be utilized.
Fig. 7: Cold Water Start
Cold Water Run
Cold water run differs from cold water start in that the
system water entering the heater remains below 120ºF
(49ºC) continuously. Typically, this is the case in
swimming pool heating and water source heat pump
applications as well as some others. If the system water
is kept in a narrow temperature range of no more than
10ºF, a permanent manual bypass can be employed and
manually adjusted to achieve an inlet temperature of
120ºF (49ºC) or higher as adjusted at the minimum
temperature in this narrow temperature range (i.e.
Range 75ºF – 85ºF – adjust bypass with temperature at
75ºF) so that when temperature is 85ºF, minimum inlet
temperature would be 130ºF. An injector pump arrangement may also be utilized to keep the heater loop
at or above 120ºF (49ºC). An injector pump approach
has the added value of being able to adjust to changes
in the system water coming back to the heater take-off.
Fig. 8: Cold Water Run
Temperature & Pressure Gauge
The temperature and pressure gauge is shipped loose
for field installation in the outlet piping.
Notes: 1. Basis for minimum flow is ∆T . Basis for maximum flow is gpm.
Min. Flow Max Flow
gpm
Table F: Heater Rates of Flow and Pressure Drops
∆
P (ft)
gpm
∆
P (ft)
gpm
∆
P (ft) ∆T
13
gpm
∆
P (ft) ∆T
Page 16
SECTION C: Installation
Hydronic Heating
Pump Selection
In order to ensure proper performance of your heater
system, you must install a correctly-sized pump. Raypak recommends designing for a ∆T within the range
of 10°F to 40°F. See Table F for acceptable flow rates
for each model (∆T is the temperature difference between the inlet and outlet water when the heater is
firing at full rate).
Feedwater Regulator
Raypak recommends that a feedwater regulator be installed and set at 12 psi minimum pressure at the
highest point of the system. Install a check valve or
back flow device upstream of the regulator, with a
manual shut-off valve as required by local codes.
Piping
All high points should be vented. A heater installed
above radiation level must be provided with a low water cut-off device (sales order option F-10). The heater,
when used in connection with a refrigeration system,
must be installed so that the chilled medium is piped in
parallel with the heater with appropriate valves to prevent the chilled medium from entering the heater.
Three-Way Valves
Three-way valves intended to regulate system water
temperatures by reducing flow in the boiler should not
be used. Raypak heaters are high-recovery, low-mass
heaters which are not subject to thermal shock.
Fig. 10: Single Heater - Low-Temperature (Heat
Pump) Application with Primary/Secondary Piping
See Fig. 14 and instructions on page 16 for adjusting
the manual bypass.
The piping system of a hot water heater connected to
heating coils located in air handling units where they
may be exposed to circulating refrigerated air, must be
equipped with flow control valves or other automatic
means to prevent gravity circulation of the heater water
during the cooling cycle. It is highly recommended that
the piping be insulated.
Air-Separation/Expansion Tank
All heaters should be equipped with a properly sized
expansion tank and air separator fitting as shown in
Fig. 9.
Fig. 9: Air-Separation/Expansion Tank
Fig. 11: Dual Heaters (Reverse/Return)
with Primary/Secondary Piping
Domestic Hot Water
When designing the water piping system for domestic
hot water applications, water hardness should be considered. Table G indicates the suggested flow rates for
soft, medium and hard water. Water hardness is expressed in grains per gallon.
14
Page 17
Fig. 12: Single Domestic Hot Water Heater and
Storage Tank
Potable Water and Space Heating
CAUTION: When this heater is used for both potable
water and space heating, observe the following to ensure proper operation.
1. All piping materials and components connected to
the water heater for the space heating application
shall be suitable for use with potable water.
2. Toxic chemicals, such as used for boiler treatment,
shall not be introduced into the potable water used
for space heating.
SECTION C: Installation
3. If the heater will be used to supply potable water,
it shall not be connected to any heating system or
components previously used with a non-potable
water heating appliance.
4. When the system requires water for space heating
at temperatures higher than 140°F, a means such
as a mixing valve shall be installed to temper the
water in order to reduce scald hazard potential.
Pool Heating
When a boiler or water heater is used in a pool heating
application, ensure that all the following installation
requirements are met.
CAUTION: Power to the heater should be interlocked
with the main system pump to ensure the heater does
not fire without the main system pump in operation.
Improper flow control can damage the heater. Uncontrolled flow (too high) or restricted flow (too low) can
seriously damage the heater. Follow these instructions
to make sure your heater is properly installed.
The MVB must be equipped with a field-supplied external pump and bypass arrangement. This arrangement
blends outlet water with the inlet water to increase the
inlet water temperature to a minimum of 120°F,
thereby reducing the likelihood of condensation forming on the heat exchanger. The pump also serves to
circulate water through the heater from the main system piping.
Model
No.
Soft (0-4 grains per gallon) Medium (5-15 grains per gallon) Hard* (16-20 grains per gallon)
∆T = Temperature rise, °F
∆P = Pressure drop through heat exchanger, ft
SHL = System head loss, ft (based on heater and tank placed no more than 5 ft apart and equivalent length of 25 ft of tubing)
gpm = Gallons per minute, flow rate
MTS = Minimum tubing size
* Must use optional cupro-nickel tubes. If over 20 grains per gallon, a water softening system must also be used.
Table G: Domestic Water Heater Flow Rate Requirements
15
Page 18
SECTION C: Installation
To complete the installation of the pool heater, the pool
thermostat needs to be installed in the main return water line, upstream of the heater. This will ensure that
the heater will be energized at the right time.
Fig. 13: Single Pool Heater Application
Adjustment of the manual bypass valve is critical to
proper operation of the heater. The manual bypass
valve should be adjusted to achieve a minimum inlet
water temperature of 120°F and a system supply water
temperature below 140°F. When starting with a cold
pool, make initial adjustments. Make final adjustments
when pool water approaches desired temperature.
The use of a bypass is required for proper operation in
a pool heating application. Use the following instructions to set the manual bypass:
1. Turn on pump.
2. Turn on heater and wait until heater goes to full
fire.
3. With the heater operating at 100% firing rate, set
Valve A (the bypass) to ½ open position, and
Valve B to fully open position.
Fig. 14: “H” Bypass Setting
Automatic Chlorinators and Chemical
Feeders
CAUTION: Combustion air must not be contaminated
by corrosive chemical fumes which can damage the
heater and void the warranty.
All chemicals must be introduced and completely diluted into the pool or spa water before being circulated
through the heater. Do not place chlorine tablets or
bromine sticks in the skimmer. High chemical concentrations will result when the pump is not running (e.g.
overnight).
Chlorinators must feed downstream of the heater and
have an anti-siphoning device to prevent chemical
back-up into the heater when the pump is shut off.
NOTICE: High chemical concentrates from feeders
and chlorinators that are out of adjustment will cause
very rapid corrosion of the heat exchanger in the heater.
Such damage is not covered under the warranty.
4. Adjust Valve A until the inlet water temperature is
120°F. NOTE: Opening the valve will increase
the temperature and closing the valve will decrease
the temperature.
5. If this process does not raise the inlet water tem-
perature to 120°F and Valve A is fully open, then
slowly throttle Valve B closed to increase the inlet
water temperature to 120°F.
Winterizing Your Heater
Heaters installed outdoors as pool heaters in freezing
climate areas should be shut down for the winter. To
shut down heater, turn off manual main gas valve and
main gas shut-off. Close isolation valves. Drain the
heater using the hose bibs located on the bottom of the
heat exchanger.
16
Page 19
SECTION C: Installation
NOTE: There are 2 separate drains on the MVB that
must BOTH be drained to protect the heat exchanger.
These are both accessible by removing the lower front
door from the heater. Drain any piping of all water that
may experience below-freezing temperatures.
Pool/Spa Water Chemistry
NOTICE: Chemical imbalance can cause severe dam-
age to your heater and associated equipment.
Water Hardness
Water hardness is mainly due to the presence of calcium and magnesium salts dissolved in the water. The
concentration of these salts is expressed in mg/l, ppm
or grains per gallon, as a measure of relative hardness
of water. Grains per gallon is the common reference
measurement used in the U.S. water heater industry.
Hardness expressed as mg/L or ppm may be divided by
17.1 to convert to grains per gallon. Water may be
classified as very soft, slightly hard, moderately hard or
hard based on its hardness number. The salts in water
will precipitate out when the water is heated and will
cause accelerated lime and scale accumulation on a
heat transfer surface.
Raypak water heaters can operate lime/scale-free using
potable water with a hardness not exceeding 20 grains
per gallon. Proper operation is achieved by setting the
temperature rise/water flow per the guidelines in the
installation instructions. If the hardness of the water
exceeds the maximum level of 20 grains per gallon
special measures must be taken to adjust flow and temperature rise. Water should be softened to a hardness
level no lower than 5 grains per gallon. Water softened
as low as 0 to 1 grain per gallon may be undersaturated with respect to calcium carbonate resulting in
water that is aggressive and corrosive.
pH of Water
pH is a measure of relative acidity, neutrality or alkalinity. Dissolved minerals and gases affect water’s pH.
The pH scale ranges from 0 to 14. Water with a pH of
7.0 is considered neutral. Water with a pH lower than 7
is considered acidic. Water with a pH higher than 7 is
considered alkaline. A neutral pH (around 7) is desirable for most potable water applications. Corrosion
damage and water heater failures resulting from water
pH levels of lower than 6 or higher than 8 are nonwarrantable. The ideal pH range for water used in a
storage tank or a copper water heater system is 7.2 to
7.8.
Total Dissolved Solids
Total dissolved solids (TDS) is the measure of all minerals and solids that are dissolved in the water. The
concentration of total dissolved solids is usually expressed in parts per million (ppm) as measured in a
water sample. Water with a high TDS concentration
will greatly accelerate lime and scale formation in the
hot water system. Most high TDS concentrations will
precipitate out of the water when heated. This can generate a scale accumulation on the heat transfer surface
that will greatly reduce the service life of a water
heater. This scale accumulation can also impede adequate flow of water and may totally block the water
passages in the tubes of the heat exchanger. A heat
exchanger that is damaged or blocked by lime/scale
accumulation must be replaced. Failure of a water
heater due to lime scale build up on the heating surface
is non-warrantable. The manufacturer of the water
heater has no control of the water quality, especially
the TDS levels in your system. Total dissolved solids
in excess of 2,500 ppm will accelerate lime and scale
formation in the heat exchanger. Heat exchanger failure due to total dissolved solids in excess of 2,500 ppm
is a non-warrantable condition. Raypak offers basic
temperature guidelines for operation of a potable water
heater on normal to moderate levels of hardness and
solids but levels of hardness and total dissolved solids
beyond normal limits for operation will require special
setup and operation.
NOTICE: Failure of a heat exchanger due to lime scale
build-up on the heating surface, low pH or other
chemical imbalance is non-warrantable.
Gas Supply
DANGER: Make sure the gas on which the heater will
operate is the same type as specified on the heater’s
rating plate.
Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve lo-
cated outside the heater jacket. It is recommended that
a union be installed in the gas supply piping adjacent to
the heater for servicing. The gas supply pressure to the
heater must not exceed 10.5 in. WC for Natural Gas or
13.0 in. WC for Propane Gas. A pounds-to-inches
regulator must be installed to reduce the gas supply
pressure if it is higher than noted above. This regulator
should be placed a minimum distance of 10 times the
pipe diameter upstream of the heater gas controls.
Refer to Table H for maximum pipe lengths.
17
Page 20
SECTION C: Installation
Model
No.
1” NPT 1-1/4” NPT 1-1/2” NPT 2” NPT 2-1/2” NPT
N P N P N P N P N P
503 15 35 65 150 130 360 N/A N/A N/A N/A
753 5 15 65 100 75 180 250 N/A N/A N/A
1003 N/A N/A 35 55 35 90 125 300 300 N/A
1253 N/A N/A 15 25 25 60 85 225 200 300
1503 N/A N/A 10 15 15 25 60 150 150 275
1753 N/A N/A N/A N/A N/A N/A 45 110 115 230
2003 N/A N/A N/A N/A N/A N/A 35 90 85 210
Natural Gas – 1,000 BTU/ft3, 0.60 specific gravity at 0.5 in. WC pressure drop
Propane Gas – 2,500 BTU/ft
3
, 1.53 specific gravity at 0.6 in. WC pressure drop
Table H: Maximum Equivalent Pipe Length
Gas Supply Connection
CAUTION: The heater must be disconnected from the
gas supply during any pressure testing of the gas
supply system at test pressures in excess of 1/2 psi
(3.45 kPa).
The heater must be isolated from the gas supply piping
system by closing the upstream manual shut-off valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 psi
(3.45 kPa). Relieve test pressure in the gas supply line
prior to reconnecting the heater and its manual shut-off
valve to the gas supply line. FAILURE TO FOL-
LOW THIS PROCEDURE MAY DAMAGE THE
GAS VALVE. Over-pressurized gas valves are not
covered by warranty. The heater and its gas connections shall be leak-tested before placing the appliance
in operation. Use soapy water for leak test. DO NOT
use an open flame.
CAUTION: Do not use Teflon tape on gas line pipe
thread. A pipe compound rated for use with natural and
propane gases is recommended. Apply sparingly only
on male pipe ends, leaving the two end threads bare.
CAUTION: Support gas supply piping with hangers,
not by the heater or its accessories. Make sure the gas
piping is protected from physical damage and freezing,
where required.
Gas Supply Pressure
A minimum of 4.0 in. WC and a maximum of 10.5 in.
WC upstream gas pressure is required under load and
no-load conditions for natural gas. A minimum of 4.0
in. WC and a maximum of 13.0 in. WC is required for
propane gas. The gas pressure regulator(s) supplied on
the heater is for low-pressure service. If upstream pressure exceeds these values, an intermediate gas pressure
regulator, of the lockup type, must be installed.
Fig. 15: Gas Supply Connection
When connecting additional gas utilization equipment
to the gas piping system, the existing piping must be
checked to determine if it has adequate capacity for the
combined load.
The gas valve pressure regulator on the heater is nominally preset as noted in Table I.
18
Page 21
SECTION C: Installation
Model
No.
503 -0.1
753 -0.1
1003 -0.2
1253 -0.1
1503 -0.4
1753 0.4
2003 0.6
NOTE: Manifold pressures should be + 0.2” WC.
Table I: Manifold Gas Pressure Settings
During normal operation, carbon dioxide should be 8.0
to 9.0% at full fire for natural gas and between 9.0 and
10.0% for propane gas. Carbon monoxide should be
‹100ppm.
Manifold Gas Pressure
(High Fire Values)
Natural Gas Propane Gas
-0.1
-0.1
-0.2
-0.1
-0.3
0.4
0.6
Electrical Power Connections
Installations must follow these codes:
• National Electrical Code and any other national,
state, provincial or local codes or regulations having jurisdiction.
• Safety wiring must be NEC Class 1.
• Heater must be electrically grounded as required by
the NEC.
• In Canada, CSA C22. 1 C.E.C. Part 1.
The MVB 503-1503 heaters are wired for 120 VAC, 12
amps while the MVB 1753 & 2003 heaters are wired
for 120 VAC, 18 amps. Consult the wiring diagram
shipped with the heater. Before starting the heater,
check to ensure proper voltage to the heater and pump.
If any of the original wire as supplied with the heater
must be replaced, it must be replaced with 105°C wire
or its equivalent.
Fig. 16: Rear Wiring Box Electrical Connections
All field wiring connections to the MVB heater are
made inside the rear wiring box as shown in Fig. 16.
Pump power should be taken from terminals 2 (Com),
3 (GND) and 6 (Hot) – ¾ hp and smaller ONLY.
Power to the MVB heater should be connected to terminals 1, 2, and 3 as noted in Fig. 16. Sensors,
interlocks, Enable/disable, and various options are
wired into terminals 1 – 12 as noted in Fig. 16.
Field-Connected Controllers
It is strongly recommended that all individuallypowered control modules and the heater should be supplied from the same power source.
NOTICE: Field-supplied isolation relays should be
installed when field-connected controllers are mounted
more than 50 equivalent feet (18 Ga) from heater.
Boiler mounted pumps (up to ¾ hp) get their power
supply directly from the boiler power supply (connections in rear wiring box). Install a circuit breaker sized
sufficiently for both the heater and the pump. Pumps
larger than ¾ hp must use a separate power supply and
run the power through the optional pump contactor
which is located in the rear wiring box (see Fig. 16).
Use appropriately-sized wire as defined by NEC, CSA
and/or local codes. All primary wiring should be 125%
of minimum rating.
Check the Power Source
WARNING: Using a multi-meter, check the following
voltages at the circuit breaker panel prior to connecting
any equipment. Make sure proper polarity is followed
and house ground is proven. (See Fig. 17.)
19
Page 22
SECTION C: Installation
BLACK
ABC
Fig. 17: Wiring Connections
WHITE
CIRCUIT
BREAKER
GREEN
GROUND
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX
AB = 108 VAC Minimum, 132 VAC MAX
BC = <1 VAC Maximum
proper electrical installation are not covered by
warranty.
5. Provide overload protection and a disconnect
means for equipment serviceability as required by
local and state code.
6. Install heater controls, thermostats, or building
management systems in accordance with the applicable manufacturers’ instructions.
7. Conduit should not be used as the earth ground.
NOTICE: A grounding electrode conductor shall be
used to connect the equipment grounding conductors,
the equipment enclosures, and the grounded service
conductor to the grounding electrode.
Field Wiring Connection
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper
operation after servicing.
DANGER: SHOCK HAZARD
Make sure electrical power to the heater is disconnected to avoid potential serious injury or damage to
components.
Fig. 18: Multi-meter
Making the Electrical Connections
Refer to Fig. 16-19.
1. Verify that circuit breaker is properly sized by
referring to heater rating plate. A dedicated circuit
breaker should be provided.
2. NOTE: Current draw noted on rating plate does
not include pump current.
3. Turn off all power to the heater. Verify that power
has been turned off by testing with a multi-meter
prior to working with any electrical connections or
components.
4. Observe proper wire colors while making electri-
cal connections. Many electronic controls are
polarity sensitive. Components damaged by im-
Fig. 19: Wiring Location
20
Page 23
SECTION C: Installation
Venting
CAUTION: Proper installation of flue venting is criti-
cal for the safe and efficient operation of the heater.
General
Appliance Categories
Heaters are divided into four categories based on the
pressure produced in the exhaust and the likelihood of
condensate production in the vent.
Category I – A heater which operates with a non-
positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in
the vent.
Category II – A heater which operates with a non-
positive vent static pressure and with a vent gas temperature that may cause excessive condensate
production in the vent.
Category III – A heater which operates with a positive
vent pressure and with a vent gas temperature that
avoids excessive condensate production in the vent.
Category IV – A heater which operates with a positive
vent pressure and with a vent gas temperature that may
cause excessive condensate production in the vent.
See Table J for appliance category requirements.
Note: For additional information on appliance categorization, see appropriate ANSI Z21 Standard and the
NFGC (U.S.), or B149.1 (Canada), or applicable provisions of local building codes.
CAUTION: Condensate drains for the vent piping are
required for installations of the MVB. Follow vent
manufacturer instructions for installation and location
of condensate drains in the vent. Condensate drain
must be primed with water to prevent gas flue leak and
must be routed to an appropriate container for neutralization before disposal, as required by local codes.
WARNING: Contact the manufacturer of the vent
material if there is any question about the appliance
categorization and suitability of a vent material for
application on a Category IV vent system. Using improper venting materials can result in personal injury,
death or property damage.
Use only the special gas vent pipes listed for use with
Category IV gas burning heaters, such as the AL29-4C
stainless steel vents offered by Heat Fab Inc. (800-772-
0739), Protech System, Inc. (800-766-3473) or Z-Flex
(800-654-5600). Pipe joints must be positively sealed.
Follow the vent manufacturer’s installation instructions
carefully.
Support of Vent Stack
The weight of the vent stack or chimney must not rest
on the heater vent connection. Support must be provided in compliance with applicable codes. The vent
should also be installed to maintain proper clearances
from combustible materials.
Use insulated vent pipe spacers where the vent passes
through combustible roofs and walls.
Combustion
Air Supply
From Inside Building
(Non-Direct Venting)
From Outside Building
(Direct Venting)
Exhaust
Configuration
Vertical
Venting
Horizontal Through-
the-Wall Venting
Vertical
Venting
Horizontal Through-
the-Wall Venting
Table J: Venting Category Requirements
Heater Venting
Category
IV
21
Certified
Materials
Stainless Steel
AL29-4C
Combustion Air
Inlet Material
Galvanized Steel
PVC
ABS
CPVC
Page 24
SECTION C: Installation
Vent Terminal Location
NOTICE: During winter months check the vent cap
and make sure no blockage occurs from build-up of
snow or ice.
1. Condensate can freeze on the vent cap. Frozen
condensate on the vent cap can result in a blocked
flue condition.
2. Give special attention to the location of the vent
termination to avoid possibility of property damage or personal injury.
3. Gases may form a white vapor plume in winter.
The plume could obstruct a window view if the
termination is installed near windows.
4. Prevailing winds, in combination with below-
freezing temperatures, can cause freezing of condensate and water/ice build-up on buildings, plants
or roofs.
5. The bottom of the vent terminal and the air intake
shall be located at least 12 in. above grade, including normal snow line.
6. Un-insulated single-wall Category IV metal vent
pipe shall not be used outdoors in cold climates for
venting gas-fired equipment without insulation.
7. Through-the-wall vents for Category IV appli-
ances shall not terminate over public walkways or
over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to
the operation of regulators, relief valves, or other
equipment.
8. Locate and guard vent termination to prevent acci-
dental contact by people or pets.
U.S. Installations
Refer to the latest edition of the National Fuel Gas
Code.
Vent termination requirements are as follows:
1. Vent must terminate at least 4 ft below, 4 ft hori-
zontally from or 1 ft above any door, window or
gravity air inlet to the building.
2. The vent must not be less than 7 ft above grade
when located adjacent to public walkways.
3. Terminate vent at least 3 ft above any forced air
inlet located within 10 ft.
4. Vent must terminate at least 4 ft horizontally, and
in no case above or below unless 4 ft horizontal
distance is maintained, from electric meters, gas
meters, regulators, and relief equipment.
5. Terminate vent at least 6 ft away from adjacent
walls.
6. DO NOT terminate vent closer than 5 ft below
roof overhang.
7. The vent terminal requires a 12 in. vent terminal
clearance from the wall.
8. Terminate vent at least 1 ft above grade, including
normal snow line.
9. Multiple direct vent installations require a 4 ft
clearance between the ends of vent caps located on
the same horizontal plane.
Canada Installations
Refer to latest edition of B149.1.
9. DO NOT terminate vent in window well, stairwell,
alcove, courtyard or other recessed area.
10. DO NOT terminate above any door, window, or
gravity air intake. Condensate can freeze, causing
ice formations.
11. Locate or guard vent to prevent condensate from
damaging exterior finishes. Use a rust-resistant
sheet metal backing plate against brick or masonry
surfaces.
12. DO NOT extend exposed vent pipe outside of
building beyond the minimum distance required
for the vent termination. Condensate could freeze
and block vent pipe.
A vent shall not terminate:
1. Directly above a paved sidewalk or driveway
which is located between two single-family dwellings and serves both dwellings.
2. Less than 7 ft (2.13 m) above a paved sidewalk or
paved driveway located on public property.
3. Within 6 ft (1.8 m) of a mechanical air supply inlet
to any building.
4. Above a meter/regulator assembly within 3 ft (0.9
m) horizontally of the vertical centre-line of the
regulator.
22
Page 25
SECTION C: Installation
5. Within 6 ft (1.8 m) of any gas service regulator
vent outlet.
6. Less than 1 ft (305 mm) above grade level.
7. Within 3 ft (0.9 m) of a window or door which can
be opened in any building, any non-mechanical air
supply inlet to any building or the combustion air
inlet of any other appliance.
8. Underneath a verandah, porch or deck, unless the
verandah, porch or deck is fully open on a minimum of two sides beneath the floor, and the
distance between the top of the vent termination
and the underside of the verandah, porch or deck is
greater than 1 ft (305 mm).
Venting Installation Tips
Support piping:
• horizontal runs - at least every 5 ft
• vertical runs - use braces
• under or near elbows
WARNING: Examine the venting system at least once
a year. Check all joints and vent pipe connections for
tightness, corrosion or deterioration.
Venting Configurations
For heaters connected to gas vents or chimneys, vent
installations shall be in accordance with Part 7, Venting
of Equipment, of the NFGC (U.S.), or B149.1 (Canada),
or applicable provisions of local building codes.
Vertical Venting (Category IV)
CAUTION: This venting system requires the installa-
tion of a condensate drain in the vent piping per the
vent manufacturer’s instructions. Failure to install a
condensate drain in the venting system will void all
warranties on this heater.
Installation
The maximum and minimum venting length for this
Category IV appliance shall be determined per the
NFGC (U.S.) or B149.1 (Canada).
The diameter of vent flue pipe should be sized according to Part 11 of the NFGC (U.S.) and Part 7 and
Appendix B of B149.1 (Canada). The minimum flue
pipe diameter for conventional venting using Category
IV, stainless steel AL29-4C vent is: 6 in. for Models
503-1003; and 8 in. for Models 1253-2003.
NOTICE: A vent adapter (field-supplied) may be re-
quired to connect the Category IV vent to the heater.
The connection from the appliance vent to the stack
must be as direct as possible and shall be the same diameter as the vent outlet. The horizontal breaching of a
vent must have an upward slope of not less than 1/4
inch per linear foot from the heater to the vent terminal.
The horizontal portions of the vent shall also be supported for the design and weight of the material
employed to maintain clearances and to prevent physical damage or separation of joints.
Certified
Model
Vent
Material
503 15*
753 75
1003
1253 40
Category IV
(AL29-4C)
1503 75
1753 75
2003
* Vent length may be extended up to 40 ft. using a barometric damper installed at 15 equivalent feet from the heater where the category of the
vent changes from Cat IV to Cat II. NOTE: Special vent materials are still required.
1
Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.
** Subtract 10 ft per elbow. Max. 4 elbows.
Vent Size
(in.)
Vertical Vent
Height
1
(Ft)
Min. Max.
Combustion Air
6
75
Galvanized Steel,
0
8
75
Table K: Category IV Vertical Venting
23
Intake Pipe
Material
PVC,
ABS,
CPVC
Air Inlet
Max. Length** (Ft)
6” Ø 8” Ø 10” Ø
45 100 N/A
N/A 45 85
Page 26
SECTION C: Installation
f
Termination
The vent terminal should be vertical and should terminate outside the building at least 2 ft above the highest
point of the roof within 10 ft. The vent cap should have
a minimum clearance of 4 ft horizontally from and in
no case above or below (unless a 4 ft horizontal distance is maintained) electric meters, gas meters,
regulators and relief equipment. The distance of the
vent terminal from adjacent public walkways, adjacent
buildings, open windows and building openings must
be consistent with the NFGC (U.S.) or B149.1 (Canada). Gas vents supported only by flashing and
extending above the roof more than 5 ft should be securely braced to withstand snow and wind loads.
CAUTION: A listed vent cap terminal suitable for
connection to the Cat IV vent materials, adequately
sized, must be used to evacuate the flue products from
the heaters.
Common Venting
The NFGC does not address sizing guidelines for the
common venting of multiple Category IV heaters. This
is covered in the NFGC under “Engineered Vent Systems”. Table L provides boiler discharge vent pressures
at vent pressure switch and volumes of flue products at
full fire for the calculation of appropriate vent sizing
for common venting.
WARNING: Vent connectors serving any other appliances shall not be connected into any portion of
mechanical draft systems operating under a positive
pressure. If an MVB heater is installed to replace an
existing heater, the vent system MUST be verified to
be of the correct size and of Category IV AL29-4C
vent material construction. If it is NOT, it MUST be
replaced.
NOTE: For extractor sizing, typical CO
8.5% for natural gas and 9.5% for LP gas and flue temperature of 300° F.
Vent
Pressure
(in. WC)
Model
Vent Size
(in.)
503 0.1 160
753 0.2 240
1003
6
0.3 320
1253 0.2 400
1503 0.3 480
8
1753 0.4 560
2003
* NOTE: Data for 100% firing rate.
0.5 640
levels are
2
Volume o
Flue Products
(CFM)
Fig. 20: Vertical Venting
Table L: Vent Pressure and Volume of
Flue Products Data
24
Page 27
SECTION C: Installation
Fig. 21: Typical Common Venting
Horizontal Through-the-Wall Direct
Venting (Category IV)
Fig. 22: Horizontal Through-the-Wall Venting
Fig. 23: Alt. Horizontal Through-the-Wall Venting
NOTE: While a drain connection is required in the
vent of all MVB installations, the drain can be accomplished in several different ways. The figures in
this manual show the drain in a vent tee, however,
this can also be accomplished using an inline collector for condensing stacks or an inline vertical or
horizontal collector available from several of the
listed vent manufacturers.
25
Page 28
SECTION C: Installation
Fig. 24: Horizontal Through-the-Wall Direct Venting
CAUTION: This venting system requires the installa-
tion of a condensate drain in the vent piping per the
vent manufacturer’s instructions. Failure to install a
condensate drain in the venting system will void all
warranties on this heater.
Installation
These installations utilize the heater-mounted blower to
vent the combustion products to the outdoors. Combustion air is taken from inside the room and the vent is
installed horizontally through the wall to the outdoors.
Adequate combustion and ventilation air must be supplied to the equipment room in accordance with the
NFGC (U.S.) or B149.1 (Canada).
The total length of the horizontal through-the-wall flue
system should not exceed 75 equivalent ft in length. If
horizontal run exceeds 75 equivalent ft, an appropriately sized variable-speed extractor must be used. Each
elbow used is equal to 10 ft of straight pipe. This will
allow installation in one of the four following arrangements:
• 75’ of straight flue pipe
• 65’ of straight flue pipe and one elbow
• 55’ of straight flue pipe and two elbows
• 45’ of straight pipe and three elbows
The vent cap is not considered in the overall length of
the venting system.
The vent must be installed to prevent flue gas leakage.
Care must be taken during assembly to ensure that all
joints are sealed properly and are airtight. The vent
must be installed to prevent the potential accumulation
of condensate in the vent pipes. It is required that:
1. The vent must be installed with a condensate drain
located in proximity to the heater as directed by
the vent manufacturer.
2. The vent must be installed with a slight upward
slope of not less than 1/4 inch per foot of horizontal run to the vent terminal.
Model
Certified Vent
Material
Vent Size
(in.)
503
753
1003
1253
Category IV
(AL29-4C)
1503
1753
2003
* Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.
** Subtract 10 ft per elbow. Max. 4 elbows.
Table M: Category IV Horizontal Vent & Horizontal Direct Vent
Horizontal
Vent Length (Ft)*
Min. Max.
Combustion Air
Intake Pipe
Material
Air Inlet
Max. Length (Ft) **
6”Ø 8” Ø 10” Ø
6 45 100 N/A
Galvanized Steel,
0 75
8
PVC,
ABS,
CPVC
N/A 45 85
26
Page 29
SECTION C: Installation
3. The vent must be insulated through the length of
the horizontal run.
Termination
The flue direct vent cap MUST be mounted on the exterior of the building. The direct vent cap cannot be
installed in a well or below grade. The direct vent cap
must be installed at least 1 ft above ground level and
above normal snow levels. The Raypak-approved
stainless steel flue direct vent cap must be used (sales
order option D-15). The vent terminal must be located
NO CLOSER than 12” off the wall.
WARNING: No substitutions of flue pipe or vent cap
material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.
Direct Vent - Vertical
arrangement that does not exceed the lengths shown in
Table K.
The vent cap is not considered in the overall length of
the venting system.
Care must be taken during assembly that all joints are
sealed properly and are airtight.
The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is
required that:
1. The vent must be installed with a condensate drain
located in proximity to the heater as directed by
the vent manufacturer.
2. The vent must be installed with a slight upward
slope of not more than 1/4 inch per foot of horizontal run to the vent terminal.
3. The vent must be insulated through the length of
the horizontal run.
Termination
The vent cap MUST be mounted on the exterior of the
building. The vent cap cannot be installed in a well or
below grade. The vent cap must be installed at least 1 ft
above ground level and above normal snow levels.
Fig. 25: Direct Vent - Vertical
CAUTION: This venting system requires the installa-
tion of a condensate drain in the vent piping per the
vent manufacturer’s instructions. Failure to install a
condensate drain in the venting system will void all
warranties on this heater.
Installation
These installations utilize the heater-mounted blower to
draw combustion air from outdoors and vent combustion products to the outdoors.
The total length of air supply pipe cannot exceed the
distances listed in Table K. Each elbow used is equal to
10 ft of straight pipe. This will allow installation in any
The vent cap MUST NOT be installed with any combustion air inlet directly above a vent cap. This vertical
spacing would allow the flue products from the vent
cap to be pulled into the combustion air intake installed
above.
This type of installation can cause non-warrantable
problems with components and poor operation of the
heater due to the recirculation of flue products. Multiple vent caps installed in the same horizontal plane
must have a 4 ft clearance from the side of one vent
cap to the side of the adjacent vent cap(s).
Combustion air supplied from outdoors must be free of
particulate and chemical contaminants. To avoid a
blocked flue condition, keep the vent cap clear of snow,
ice, leaves, debris, etc.
WARNING: No substitutions of flue pipe or vent cap
material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.
The stainless steel flue direct vent cap must be furnished by the heater manufacturer in accordance with
its listing (sales order option D-15).
27
Page 30
SECTION C: Installation
Outdoor Installation
Outdoor models are self-venting when installed with
the optional factory-supplied outdoor vent kit. Additional vent materials are required as outlined in the
Outdoor Vent Kit instructions. A special vent cap and
air intake elbow are offered in accordance with CSA
requirements. These must be installed directly on the
vent pipe as illustrated in Fig. 26.
Care must be taken when locating the heater outdoors,
because the flue gases discharged from the vent cap
can condense as they leave the cap. Improper location
can result in damage to adjacent structures or building
finish. For maximum efficiency and safety, the following precautions must be observed:
1. Outdoor models must be installed outdoors. They
must use the outdoor vent cap and air intake elbow
available from the manufacturer (sales order option D-11).
2. Periodically check the venting system. The
heater’s venting areas must never be obstructed in
any way and minimum clearances must be observed to prevent restriction of combustion and
ventilation air. Keep area clear and free of combustible and flammable materials.
3. Do not locate adjacent to any window, door walk-
way, or gravity air intake. The vent must be
located a minimum of 4 ft horizontally from such
areas.
4. Install above grade level and above normal snow
levels.
5. Vent terminal must be at least 3 ft above any
forced air inlet located within 10 ft.
6. Adjacent brick or masonry surfaces must be pro-
tected with a rust-resistant sheet metal plate.
NOTICE: Condensate can freeze on the vent cap. Fro-
zen condensate on the vent cap can result in a blocked
flue condition.
NOTICE: The vent cap and air intake hood must be
furnished by the heater manufacturer in accordance
with its listing (sales order option D-11).
Fig. 26: Outdoor Venting
Freeze Protection
When installing this heater in an outdoor location that
is susceptible to freezing, sales option B-22 should be
installed to energize the heater pump at a present outdoor air temperature and circulate water to reduce the
possibility of freezing and damage to the heat exchanger or headers.
Controls
WARNING: Installation, adjustment and service of
heater controls, including timing of various operating
functions, must be performed by a qualified installer,
service agency or the gas supplier. Failure to do so may
result in control damage, heater malfunction, property
damage, personal injury, or death.
WARNING: Turn off the power to the heater before
installation, adjustment or service of any heater controls. Failure to do so may result in heater malfunction,
property damage, personal injury, or death.
CAUTION: This appliance has provisions to be con-
nected to more than one supply source. To reduce the
risk of electric shock, disconnect all such connections
before servicing.
CAUTION: Risk of electric shock: More than one
disconnect switch may be required to de-energize the
equipment before servicing.
28
Page 31
SECTION C: Installation
The Raypak modulating temperature control is provided to maintain the desired system water temperature.
The control has various modes of operation which are
listed below.
Operating Modes
Mode 1 – Setpoint operation using parallel piping. The
heater outlet water temperature is controlled to the
boiler target setpoint.
Mode 2 – Setpoint operation using primary / secondary
piping. The control modulates the heater to satisfy a
remote header sensor. The heater is turned off based on
boiler max and boiler differential (factory default H7
boilers).
Mode 3 – Dedicated DHW operation using parallel
piping. A call for heat is determined by the DHW sensor. The heater outlet water is controlled to the boiler
target temperature (factory default WH7 water heaters).
Mode 4 – Outdoor reset and reset override operation
using parallel piping. The heater is operated as in Mode
1. However the target temperature is based on outdoor
reset. The outdoor reset temperature can be remotely
overridden.
BOIL MIN - Lowest outlet water temperature that the
control is allowed to use as a target temperature
BOIL ON - Accumulated runtime of heater (up to 999
hours, then resets to 0)
BOIL OUT - Actual heater outlet water temperature
BOIL START - Starting boiler water temperature
BOIL SUP - Actual system supply water temperature
BOIL TARGET - Target temperature that the heater is
trying to maintain
‘BURNER’ DELAY - Heater delay from the start of
the ignition sequence until it fires
DIFF - The operating differential of the heater; The
heater outlet water temperature is allowed to rise above
the BOIL TARGET temperature by 1/2 of this differential before the heater shuts off
MODE - Operating mode of the heater
OUTDR - Outdoor air temperature
OUTDR DESIGN - Design outdoor air temperature
used in the heat loss calculation
Mode 5 – Outdoor reset and reset override operation
using primary/secondary piping. The heater is operated
as in Mode 2. However, the target temperature is based
on outdoor reset. The outdoor reset temperature can be
remotely overridden.
Mode 6 – This mode is used for remote control mode.
The Boil Max setting is the heater shutdown temperature.
Definitions
The following items are common to Modes 1 thru 5.
They are not required for Mode 6 – the mode for external heater control.
% OUT - Current percent modulation rate of heater
BOIL DSGN - Design boiler water temperature used
in heat loss calculations
BOIL MASS - This setting allows adjustment in the
field for high or low thermal masses; High thermal
mass (setting=3) provides slower reaction, lower thermal mass (setting=1) provides faster reaction
BOIL MAX - Highest outlet water temperature that
the control is allowed to use as a target temperature
OUTDR START - Starting outdoor air temperature
PUMP DLY - Sets the operating time of the pump
once the CFH is satisfied
TANK - Current DHW tank temperature (Mode 3)
TANK DIFF - Storage tank differential (Mode 3)
TANK TARGET - Target temperature in the DHW
storage tank (Mode 3)
UNITS - Selects the temperature units to be displayed
o
(
F or oC). For example, if the heater target temperature
is set to 160°F and the differential is set to 10°F, on
temperature rise, the heater will shut off at 165
Once the heater shuts off, it will not come on again
until the temperature falls to 155
o
F.
o
F.
WWSD - Selects the outdoor temperature that shuts
the heater off, no matter what the demand. NOTE: The
WWSD segment is displayed on the LCD.
Operation
The Raypak modulating temperature control uses a
Liquid Crystal Display (LCD) as a method of supplying information. The LCD is used to setup and monitor
29
Page 32
SECTION C: Installation
system operation by means of three push buttons (Item,
▲,▼). Item advances the display, while ▲,▼are used
in the adjust menu.
2 seconds, then the software version is displayed for 2
seconds. At the end of that 4 second period, the control
enters the normal operating mode and “VIEW” is displayed. Pressing the scroll button “scrolls” through the
displayed values in the “VIEW” menu.
Fig. 27: Modulating Temperature Control
User Interface
All items displayed by the control are organized into
two menus, the view menu and the adjust menu. The
active menu is displayed in the upper right hand side of
the display in the menu field. The default menu is the
view menu.
When the modulating temperature control is powered
up, the control turns on all segments in the display for
Table N: Modulating Temperature Control Default Setpoints
30
Page 33
SECTION C: Installation
To make an adjustment to a setting in the control, begin
by selecting the “ADJUST” menu. To change from the
view menu to the adjust menu, simultaneously press
and hold all three buttons for 1 second. The menu
name, “ADJUST” will be displayed in the menu field.
The menu will automatically revert back to the view
menu after 20 seconds of keyboard inactivity. Then
scroll to the desired item using the scroll button. Finally, use the ▲or ▼ button to make the adjustment.
In the absence of other information, the values provided in Table N should be used as default settings.
Heater Sequence of Operation
Model 503 - 1503
1. The black (hot) wire lead, located at the right-
middle front inside the control compartment, goes
directly to the main power switch.
2. When the main power switch is placed in the
“ON” position, the 120 VAC terminal block in the
control compartment, the N.O. contacts of pump
relay, the N.O. contacts of blower relay, the
120/24 VAC transformer, and terminals L1 and F1
of the ignition module are powered.
3. The 120/24 VAC transformer sends a 24 VAC hot
power signal to the 24V Terminal Block .
4. 24 VAC is sent from the 24V Terminal Block to
the NO pump contacts on the modulating temperature control (pin #13), to pin TP2 of the optional
alarm relay, to terminal R of the alarm circuit on
the modulating temperature control (pin #24) and
the green “Power On” LED on the front of the
heater will illuminate.
5. 24 VAC power is sent from 24V Terminal Block
to Pin P1-1 of the UDB board, the 24 VAC terminal of the ignition control module, the NC contact
of the manual high limit, and L1 of the Low Water
Cut Off (if equipped).
24 VAC is sent from the NC contacts of the manual high limit to pin P3-1 & P3-2 of the UDB
board.
Upon loss of water in the heater, the Low Water
Cut Off (if equipped) will send a 24 VAC signal to
pin P3-4 of the UDB board to indicate a safety
fault.
6. A 24 VAC signal is sent from the NO contacts of
the Low Water Cut Off to the common terminal of
the Blocked Vent Switch.
During a blocked vent condition a 24 VAC signal
is sent from the NO open contacts of the Blocked
Vent Switch to pin P3-5 of the UDB board to indicate a safety fault.
7. During normal operation of the heater the 24 VAC
signal exits the NC contacts of the Blocked Vent
Switch and is sent to the common terminal, of the
Low Gas Pressure Switch (if equipped).
During a low gas pressure condition 24 VAC is
sent from the NC contacts of the Low Gas Pressure Switch to pin P3-6 of the UDB board to
indicate a safety fault.
8. 24 VAC is sent from the NO contacts of the Low
Gas Pressure Switch to the common terminal of
the High Gas Pressure Switch (if equipped).
During a high gas pressure condition 24 VAC is
sent from the NO contacts of the High Gas Pressure Switch to pin P3-7 of the UDB board to
indicate a safety fault.
9. 24 VAC is sent from the NC contacts of the High
Gas Pressure Switch to the common terminal of
the Auto Reset High Limit (if equipped) and to energize the coil of optional alarm relay.
If the Auto Hi Limit opens, 24 VAC is sent from
the NO contacts of the Auto Hi Limit to pin P3-3
of the UDB board to indicate a safety fault.
10. 24 VAC is sent from the NC contacts of the Auto
Reset Hi Limit to the common terminal of time delay relay.
11. 24 VAC is sent from the NC contacts of time delay
relay to the common terminal of the burner switch
located on the front exterior panel of the heater.
12. Power then travels to the enable/disable connec-
tion and to the Ht D (heat demand) connection of
the modulating temperature control.
Power splits from the enable/disable and goes to
the stage contact of the modulating temperature
control (pin #15).
13. When the stage contact closes on the modulating
temperature control, 24 VAC is sent to the common terminal of the flow switch and to pin P1-3
31
Page 34
SECTION C: Installation
(CFH) of the UDB board. In addition, the amber
“Call-for-Heat” LED on the front of the heater will
illuminate.
14. The pump contact on the modulating temperature
control closes sending 24 VAC to the pump switch
located on the front exterior panel of the heater.
15. When the pump switch is closed, 24 VAC is sent
to the coil of the pump relay.
16. The pump relay energizes and closes the contacts,
starting the heater pump.
17. Upon sufficient flow, the flow switch closes and
sends 24 VAC to the common terminal of the air
pressure switch, TH terminal of the ignition module, coil of the ignition lockout relay and the NO
contacts of the ignition lockout relay.
If the flow switch does not close, a 24 VAC signal
is sent to pin P4-9 of the UDB board to indicate an
insufficient flow condition.
When the 24 VAC signal is sent to P4-9 the same
signal then de-energizes the coil of time delay relay to remove a heat demand from the modulating
temperature control and restart the ignition sequence after the 5 second time delay.
Upon ignition lockout, the module energizes the
ignition lockout relay and sends a 24 VAC signal
to pin P4-12 (ignition lockout) of the UDB board.
18. When 24 VAC is received at TH on the ignition
module, the contacts between pins F1 and F2 close
and send 120 VAC to pin 1 of the blower relay.
19. The coil of the blower relay energizes closing the
NO contacts sending 120 VAC to energize the
combustion air blower motor.
The combustion air blower will operate at 50% of
capacity for approximately ninety (90) seconds before the modulating signal from the modulating
temperature control will control the fan speed in
relationship to the system water temperature.
20. Once sufficient air pressure is achieved in the
heater and the air pressure switch closes the NO
contacts, 24 VAC is sent to the heater interlock
connection on the ignition module.
contacts of the air pressure switch to pin P4-10 of
the UDB board to indicate insufficient air pressure.
When the 24 VAC signal is sent to P4-10 the same
signal then de-energizes the coil of the time delay
relay to remove a heat demand from the modulating temperature control and restart the ignition
sequence after the 5 second time delay.
21. After receiving 24 VAC at the heater interlock,
power then travels to the P Switch terminal of the
ignition module.
The ignition module employs a 15 second prepurge before the next sequence.
22. After 15 seconds of combustion chamber pre-
purge, pin S1 sends 120 VAC to the Hot Surface
Igniter.
23. The Hot Surface Igniter will be energized for ap-
proximately 30 seconds and must exceed 3.1 amp
draw during heat up.
24. Once the ignition module determines the proper
operation of the Hot Surface Igniter, a 24 VAC
signal is output from the Valve pin on the module
to energize the gas valve.
25. The gas valve is energized and the blue “Burner
On” LED on the front of the heater energizes.
26. The remote sensor is now trying to rectify the
flame. If the flame is not rectified within 4 seconds,
the ignition module will shut down the gas valve
and lock out.
27. When burner flame is rectified, the gas valve will
remain at 50% fire for the remainder of the ninety
(90) second delay after the CFH was initiated and
then modulate in relationship to the output signal
to the combustion air blower from the modulating
temperature control.
28. When the CFH is satisfied, the heater will return to
a standby condition awaiting the next CFH.
Model 1753 – 2003
1. The black (hot) wire lead, located at the right-
middle front inside the control compartment, goes
directly to the main power switch.
If air pressure is insufficient or lost during heater
operation a 24 VAC signal is sent from the NC
2. When the main power switch is placed in the
“ON” position, the 120 VAC terminal block in the
control compartment, the N.O. contacts of the
32
Page 35
SECTION C: Installation
pump relay and the blower receives power but
does not energize at this time and terminal L1 the
ignition module is powered.
3. The 120/24 VAC transformer sends a 24 VAC hot
power signal to the 24V Terminal Block.
4. 24 VAC is sent from the 24V Terminal Block to
pin L1 of the Low Water Cut Off, the 24 VAC
terminal of the ignition control module, the green
LED on the front of the heater to signify “Power
On”, terminal R (pin #24) of the modulating temperature control, the NC contacts of the manual
high limit, pin P3-1 of the UDB board, pin P1-1 of
the UDB board, pin J5-5 of the UGB board, the
NC contacts of the alarm relay, the red LED on the
front of the heater to signify “Service” if in alarm
mode and the NO pump contacts on the temperature controller.
24 VAC is sent from the NC contacts of the manual high limit to pin P3-2 of the UDB board and to
the common terminal of the Low Water Cut Off (if
equipped).
Upon loss of water in the heater, the Low Water
Cut Off will send a 24 VAC signal to pin P3-4 of
the UDB board to indicate a safety fault.
5. A 24 VAC signal is sent from the NO contacts of
the Low Water Cut Off to the common terminal of
the Blocked Vent Switch.
During a blocked vent condition a 24 VAC signal
is sent from the NO open contacts of the Blocked
Vent Switch to Pin P3-5 of the UDB board to indicate a safety fault.
6. During normal operation of the heater, the 24
VAC signal will exit the NC contacts of the
Blocked Vent Switch and is sent to the common
terminal, of the Low Gas Pressure Switch (if
equipped).
sure Switch to Pin P3-7 of the UDB board to
indicate a safety fault.
8. 24 VAC is sent from the NC contacts of the High
Gas Pressure Switch to energize the alarm relay
coil and to the common terminal of the Auto Reset
High Limit (if equipped).
If the Auto Hi Limit opens, a 24 VAC is sent to
Pin P3-3 of the UDB board to indicate a safety
fault.
9. 24 VAC is sent from the NC contacts of the Auto
Reset Hi Limit to the common terminal of time delay relay.
10. 24 VAC is sent from the NC contacts of time delay
relay to the common terminal of the burner switch
located on the front exterior panel of the heater.
11. Power then travels to the enable/disable connec-
tion and to the Ht D (heat demand) connection of
the modulating temperature control.
Power splits from the enable/disable and goes to
the stage contact of the modulating temperature
control.
12. When the stage contact closes on the modulating
temperature control, 24 VAC is sent to the common terminal of the flow switch and to pin P1-3
(CFH) of the UDB board. 24 VAC is now sent directly to the amber LED on the front of the heater
to signify a “Call For Heat”.
13. The pump contact on the modulating temperature
control closes sending 24 VAC to the pump switch
located on front exterior panel of the heater.
14. When the pump switch is closed 24 VAC is sent to
the coil of the pump relay.
15. The pump relay energizes and closes the contacts,
starting the heater pump.
During a low gas pressure condition, 24 VAC is
sent from the NC contacts of the Low Gas Pressure Switch to Pin P3-6 of the UDB board to
indicate a safety fault.
7. 24 VAC is sent from the NO contacts of the Low
Gas Pressure Switch to the common terminal of
the High Gas Pressure Switch (if equipped).
During a high gas pressure condition, 24 VAC is
sent from the NO contacts of the High Gas Pres-
16. Upon sufficient flow, the flow switch closes and
sends 24 VAC to the common terminal of the air
pressure switch, the lockout relay coil and the NO
contacts of the lockout relay. A 24 VAC signal is
also sent from the common terminal of the air
pressure switch to pin F1 of the ignition module.
If the flow switch does not close, a 24 VAC signal
is sent to pin P4-9 of the UDB board to indicate an
insufficient flow condition.
33
Page 36
SECTION C: Installation
When the 24 VAC signal is sent from the flow
switch to P4-9, the same signal then de-energizes
the coil of the time delay relay to remove a heat
demand from the modulating temperature control
and restart the ignition sequence after the fivesecond time delay.
Upon ignition lockout, the module energizes the
lockout relay and sends a 24 VAC signal to pin
P4-12 (ignition lockout) of the UDB board.
17. When 24 VAC is received at F1 of the ignition
module, it is then routed to the “TH” terminal of
the ignition module.
18. After 24 VAC is received at TH on the ignition
module, the contacts between pins F1 and F2 close
and send 24 VAC to pin J5-6 of the UGB board.
A signal must be received at this terminal to enable output to the blower.
19. A 24 VAC signal is sent from J6-1 to the blower.
20. The blower is controlled by a PWM (pulse width
modulation) signal sent from J6-4 to start the
blower operating at 50% speed.
The combustion air blower will operate at 50% of
capacity for approximately ninety (90) seconds before the modulating signal from the temperature
control will control the blower speed in relationship to the system water temperature.
21. Once sufficient air pressure is achieved in the
heater and the air pressure switch closes the NO
contacts, 24 VAC is sent to the heater interlock
connection.
If air pressure is insufficient or lost during heater
operation, a 24 VAC signal is sent from the NC
contacts of the air pressure switch to pin P4-10 of
the UDB board to indicate insufficient air pressure.
When the 24 VAC signal is sent to P4-10, the
same signal then energizes the coil of the time delay relay to remove a heat demand from the
temperature controller and restart the ignition sequence after the five-second time delay.
23. After 15 seconds of combustion chamber pre-
purge, pin S1 sends 120 VAC to the Hot Surface
Igniter.
The Hot Surface Igniter will be energized for approximately 30 seconds and must exceed 3.1 amp
draw during heat up.
24. During HSI heat-up, the UGB board is monitoring
current draw across pins J4-1 and J4-3.
25. Once the ignition module determines the proper
operation of the Hot Surface Igniter, a 24 VAC
signal is output from Valve pin on the ignition
module to energize the gas valve.
26. A 24 VAC signal is sent to the blue LED on the
front of the heater to signify “Burner Firing” and
to pin J5-2 on the UGB board to prove flame.
27. The gas valve is energized and the burner ignites.
28. The remote sensor is now trying to sense the flame.
If the flame is not rectified within 4 seconds, the
ignition module will shut down the gas valve and
lock out.
29. When burner flame is rectified, the gas valve will
remain at 50% fire for the remainder of the ninety
(90) seconds after CFH and then modulate in relationship to the output signal to the combustion air
blower from the modulating temperature control.
30. When the CFH is satisfied, the heater will return to
a standby condition awaiting the next CFH.
Ignition Module
When additional heat is needed, the combustion air
blower starts to purge air from the combustion chamber
for 15 seconds. On proof-of-air flow, the air-proving
switch closes and the igniter is energized. To ensure
safe operation, the gas valve cannot open until the igniter is verified. The main burner is automatically lit
when the device is powered and pre-purged. The heater
performs its own safety check and opens the main
valve only after the igniter is proven to be capable of
ignition.
22. After receiving 24 VAC at the heater interlock,
power then travels to the P Switch terminal of the
ignition module.
The ignition module employs a 15 second prepurge before the next sequence.
34
Page 37
Fig. 29: Ignition Module
The standard single-try ignition module will lock out
after failing to light one time. To reset it, press and
release the small, recessed black push button located
inside of the cut-out on the lower right-hand corner of
the ignition module case. Turning off the power to the heater WILL NOT reset the ignition module.
The optional ignition module will attempt to light three
times before locking out. To reset it, turn off power to
the heater, wait 30 seconds and re-apply power.
Code Condition
On System OK; No faults present
Off Possible control fault; Check power
SECTION C: Installation
The optional adjustable manual reset high limit is located inside the heater junction box. Push the reset
button and adjust the setting to approx. 40°F above
desired outlet temperature.
Fig. 30: Fixed Setting & Adjustable High Limit
(Manual Reset)
High Limit - Auto Reset (Optional)
The heater may be equipped with an optional adjustable auto reset high limit temperature device.
The optional adjustable auto reset high limit is located
inside the heater junction box. Adjust the setting to
approx. 20°F above desired outlet temperature.
1 Flash Low air
2 Flashes
Flame in combustion chamber;
No call for heat
3 Flashes Ignition lockout
4 Flashes Low HSI current
5 Flashes Low 24 VAC
6 Flashes Internal fault; Replace control
Table O: Ignition Module
Diagnostic LED Flash Codes
High Limit - Manual Reset
The heater is equipped with a fixed setting manual reset high limit temperature device as standard or it may
have an optional adjustable setting manual reset high
temperature device.
The fixed setting manual reset high limit is located on
the In/Out header of the heat exchanger on the right
side of the heater (accessible through the front door for
reset as necessary).
Fig. 31: Adjustable High Limit (Auto Reset)
Flow Switch
This standard, dual-purpose control, mounted and
wired in series with the main gas valve, shuts off heater
in case of pump failure or low water flow.
35
Page 38
SECTION C: Installation
Fig. 32: Flow Switch
Modulating Temperature Control
High and Low Gas Pressure Switches
(Optional)
The optional low gas pressure switch connection
mounts upstream of the gas valve (on the inlet flange to
the gas valve) and is accessible through the removable
access panels on the rear of the heater to reset the gas
pressure switch, as necessary. It is used to ensure that
sufficient gas pressure is present for proper
valve/regulator performance. The low gas pressure
switch automatically shuts down the heater if gas supply drops below the factory setting of 3.0 in. WC for
natural gas or LP gas.
The heater is equipped with a Raypak modulating temperature control. Refer to information starting on page
28 for information on the setting and use of this control.
Fig. 33: Modulating Temperature Control
Low Water Cut-Off (Optional)
The optional low water cut-off automatically shuts
down the burner whenever water level drops below the
level of the sensing probe. A 5-second time delay prevents premature lockout due to temporary conditions
such as power fluctuations or air pockets.
The optional high gas pressure switch connection
mounts down-stream of the gas valve. Special ports
are located on the backside of the gas valve and accessible from the front of the heater (to reset the gas
pressure switch) or through the removable access panels on the rear of the heater (to reset the gas pressure
switch), as necessary. If the gas pressure regulator in
the valve fails, the high gas pressure switch automatically shuts down the burner.
Operation of either the High or Low Gas Pressure
Switch will turn on an LED inside the switch housing.
Push the top of the plastic switch housing as shown in
Fig. 35 to reset a tripped pressure switch. The LED
will go out when the switch is reset.
Fig. 34: Low Water Cut-Off
Fig. 35: High/Low Gas Pressure Switch
Air Pressure Switch
The heater is equipped with an air pressure switch to
prove the operation of the blower before allowing the
ignition control to begin a Call for Heat. It is located
on the right side of the lower flange of the blower
mounting assembly, directly behind the junction box.
36
Page 39
Fig. 36: Air Pressure Switch
Blocked Vent Switch
This heater is equipped with a blocked vent pressure
switch to prevent the operation of the heater when too
much of the vent is blocked. This switch is located on
the right side of the heater near the right rear corner.
SECTION C: Installation
Fig. 37: Blocked Vent Switch
UDB Diagnostic Board
This heater is equipped with a diagnostic board which
will indicate faults as they occur. It has the ability to
retain up to 256 faults in history. Refer to the Troubleshooting section for instructions on accessing,
reviewing and clearing these faults.
SW1
SW2
Fig. 38: UDB Diagnostic Board
37
Page 40
SECTION C: Installation
Wiring Diagrams
Models 503-1503
38
Page 41
Models 1753-2003
SECTION C: Installation
39
Page 42
SECTION C: Installation
40
Page 43
SECTION D
Start-up
Pre Start-up
Filling System (Heating Boilers)
Fill system with water. Purge all air from the system.
Lower the system pressure. Open valves for normal
system operation, and fill system through feed pressure.
Manually open air vent on the compression tank until
water appears, then close vent.
Air Purge (Domestic Hot Water
Heaters)
Purge all air from system before lighting heater. This
can be normally accomplished by opening a downstream valve.
Raypak offers an optional air vent for the MVB heaters
which can be screwed directly into the inlet side of the
header to ensure that air is purged from the system.
This option also includes an adapter to allow the air
vent to be piped (in the field) to a suitable drain as required by the jurisdiction having authority.
Venting System Inspection
For Your Safety
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
This appliance has a hot surface igniter. It is equipped
with an ignition device which automatically lights the
burners. Do not try to light the burners by hand.
BEFORE OPERATING, smell all around the appliance
area for gas. Be sure to smell near the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
telephone in your building.
• Immediately call your gas supplier from a
neighbor’s telephone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
1. Check all vent pipe connections and flue pipe ma-
terial.
2. Make sure vent terminations are installed per code
and are clear of all debris or blockage.
• Use only your hand to push in or turn the gas con-
trol knob. Never use tools. If the knob will not turn
by hand, do not try to repair it, call a qualified service technician. Forced or attempted repair may
result in a fire or explosion.
• Do not use this appliance if any part has been under
water, immediately call a qualified service technician to inspect the appliance and to replace any part
41
Page 44
SECTION D: Start up
of the control system and any gas control which has
been under water.
• Check around unit for debris and remove combusti-
ble products, i.e. gasoline, etc.
Pre Start-up Check
1. Verify heater is filled with water.
2. Check system piping for leaks. If found, repair
immediately.
3. Vent air from system. Air in system can interfere
with water circulation. If the heater is equipped
with the optional air vent, ensure that it is adjusted
before firing the heater to make sure all air is
vented prior to start-up.
4. Purge air from gas line up to heater.
Initial Start-up
Tools Needed
• (1) 12-0-12, 24” scale U-tube manometer
• (2) 6-0-6, 12” scale U-tube manometer
• (1) Phillips screwdriver
• (1) Crescent wrench
• (1) Multi-meter
• (1) Amp probe
NOTICE: Digital manometers are not recommended.
Preparation
WARNING: Do not turn on gas at this time.
Attach Manometers to Measure Pressures
1. Turn off main gas valve.
2. Attach (1) 12” scale manometer to an upstream
bleedle valve on the gas supply pipe to the heater
(Measure point “A” in Fig. 39).
3. Attach (1) 24” scale manometer to the manifold
pressure tap located on the valve (Measure point
“C” in Fig. 39).
4. Attach (1) 12” scale manometer near the fan-
proving switch. Pull black cap from air pressure
switch tee and connect the manometer. NOTE: Retain caps for reinstallation later.
Fig. 39: Gas Pressure Measurement Location
Check Gas Supply Pressure
1. Slowly turn on main gas shut-off valve.
2. Read the gas supply pressure from the manometer;
minimum supply pressure for natural gas is 4.0 in.
WC, recommended supply is 7.0 in. WC, minimum supply pressure for propane gas is 4.0 in.
WC, recommended supply is 11.0” WC (dynamic
readings, full fire input).
Check Power Supply
With multi-meter at incoming power, check voltage
between:
Hot - Common (≈120 VAC)
Hot - Ground (≈120 VAC)
Common - Ground (< 1 VAC)
WARNING: If Common - Ground is > 1 VAC, STOP:
Contact electrician to correct ground failure. Failure to
do this may burn out 120V-24V transformer, or may
cause other safety control damage or failure.
3. If the pressure is > 14.0 in. WC, turn off the valve.
4. Check if the service regulator is installed and/or
adjust the service regulator.
Start-Up
Blower Adjustment
1. Turn off power.
2. Unplug cap at pressure switch and connect ma-
nometer to the tee.
3. Close manual firing valve.
4. Turn power on.
42
Page 45
SECTION D: Start up
5. Check blower motor amp draw and the manometer
attached to fan pressure switch with the blower
running at 100% speed. The reading should be as
noted in Tables P and Q for both natural gas and
propane gas. If not, adjust the air shutter on the
blower to attain the correct values.
6. Measure the blower amp draw and compare the
measured values to the values in Table P. If the
measured value is different than the values in the
table (with the noted tolerance), contact the factory.
NOTE: Connect the amp probe to the 14 Ga.
black power wire going into the blower.
7. Turn power off.
8. Disconnect the manometer and reconnect the cap.
Model Amp Draw
503
753
1003
1.9
2.9
4.8
Setting
Tolerance
+0.0/-0.2
+0.0/-0.2
+0.0/-0.2
Manifold Adjustment
1. Turn off unit.
2. Open manual firing valves.
3. Turn on the unit, wait approximately 15 seconds,
and the igniter should glow (observable through
the observation port located at the front, bottom of
the heater). Look into sight glass located at the
bottom of the front panel to check igniter operation.
Gas valve should open in 45-60 seconds.
4. If burner does not light on first trial. It will go into
lockout with the standard ignition module. If it is
equipped with the optional 3-try ignition module,
it will try for ignition up to three times.
5. Main burner ignition: Check manifold gas pressure
at gas valve outlet pressure tap (connection “C” in
Fig. 39). This should read per the values in Table
R for natural gas and propane gas.
6. If the pressure reading differs by more than ± 0.2
in. WC, STOP – Call the factory for directions on
what to do next!
1253
1503
1753
2003
Table P: MVB Blower Amp Draw
Model
6.3
8.1
13.5
14.8
+0.0/-0.2
+0.0/-0.2
+0.0/-0.5
+0.0/-0.5
Air Pressure Setting*
(in. WC)
503 -2.3
753 -2.9
1003 -3.0
1253 -3.5
1503 -4.0
1753 -4.6
2003 -4.1
* Settings +/- 0.2” WC
Table Q: MVB Air Pressure Requirements
CAUTION: Special manifold and air settings may be
required.
Manifold Gas Pressure Setting*
Model
High Fire Values (in. WC)
Natural Gas LP Gas
503 -0.1 -0.1
753 -0.1 -0.1
1003 -0.2 -0.2
1253 -0.1 -0.1
1503 -0.4 -0.3
1753 0.4 0.4
2003 0.6 0.6
* Settings +/- 0.2” WC
Table R: MVB Manifold Gas Pressure Settings
43
Page 46
SECTION D: Start up
Safety Inspection
1. Check all thermostats and high limit settings.
2. During the following safety checks leave manome-
ters hooked up, check and record.
3. If other gas-fired appliances in the room are on the
same gas main, check all pressures on the MVB
with all other equipment running.
4. Check thermostats for ON-OFF operation.
5. Check high limits for ON-OFF operation.
6. While in operation, check flow switch operation
7. Check the low gas pressure switch (if provided).
(For proper adjustment, use the attached manometers, if available, to set pressure. The scales on the
switch are approximate only.) Low gas pressure
switch (if provided) must be set at 3.0 in. WC for
natural gas and propane gas.
8. Make sure that the high gas pressure switch (op-
tional) is set to 3.0 in. WC for both natural gas and
propane gas.
Follow-Up
Safety checks must be recorded as performed.
Turn heater on. After main burner ignition:
1. Check manometer for proper readings.
2. Cycle heater several times and re-check readings.
3. Remove all manometers and replace caps and
screws.
4. Check for gas leaks one more time.
Leak Test Procedure: Dual-Seat Gas
Valve
Proper leak testing requires three pressure test points in
the gas train.
Remove the access panel on the rear of the heater to
access the gas valve for this test. Test point A is a
bleedle valve located upstream of the combination gas
valve on the supply manifold.
Test point B is a bleedle valve located between the two
automatic gas valve seats.
Test point C is a bleedle valve located downstream of
both automatic gas valve seats and upstream of the
manual valve. Refer to Fig. 40.
These tests are to be conducted with the electrical
power to the heater turned OFF.
1. Manually close the downstream leak test valve.
2. Open the bleedle valve at test point A and connect
a manometer to it. Verify that there is gas pressure
and that it is within the proper range (NOTE: must
not exceed 14.0 in. WC).
3. Open test point B and connect a rubber tube to it.
Connect the other end of the tube to a manometer
and look for a build-up of pressure. Increasing
pressure indicates a leaking gas valve which must
be replaced.
4. Next, close the upstream manual gas valve (field
supplied) and remove the manometers from the
bleedle valves in test point A and test point B.
Connect a rubber tube from the test point A
bleedle valve to the test point B bleedle valve and
open the upstream manual gas valve. Make sure
that test point A & B bleedle valves have been
opened so as to allow gas to flow. This will bring
gas pressure to the second valve seat.
5. Open the bleedle valve at test point C and connect
a second rubber tube to it. Connect the other end
of the tube to a manometer and look for a build-up
of pressure. Increasing pressure indicates a leaking
gas valve which must be replaced.
6. Remove rubber tube and manometers. Close each
test point bleedle valve as the tubes are removed.
7. After no leakage has been verified at all valve
seats and test valves, open downstream leak test
valve and restore electrical power to the heater.
44
Page 47
SECTION D: Start up
8. Test limit control: While burner is operating, move
indicator on high limit control below actual water
temperature. Burner should go off while blower
and circulator continue to operate. Raise setting on
limit control above water temperature and burner
should re-ignite after pre-purge time delay.
NOTE: Ignition control may have to be reset after
this portion of the test.
9. Test ignition system safety device:
a. Open manual gas valve. Turn power on.
b. Set thermostat to call for heat.
c. When the heater is in operation, pull cap off of
tee in air switch hose. The burner should go
off almost immediately.
d. Reattach cap on tee. Burner should re-ignite
after pre-purge time delay. NOTE: Ignition
control may have to be reset after this portion
of the test.
Fig. 40: Leak Test Procedure
Post Start-Up Check
Check off steps as completed:
1. Verify that the heater and heat distribution units or
storage tank are filled with water.
2. Confirm that the automatic air vent (if used) was
opened two full turns during the venting procedure.
3. Verify that air has been purged from the system.
4. Verify that air has been purged from the gas piping,
and that the piping has been checked for leaks.
5. Confirm that the proper start-up procedures were
followed.
6. Inspect burner to verify flame.
7. Test safety controls: If heater is equipped with a
low water cut-off or additional safety controls, test
for operation as outlined by manufacturer. Burner
should be operating and should go off when controls are tested. When safety devices are restored,
burners should re-ignite after pre-purge time delay.
10. To restart system, follow lighting instructions in
Section E.
11. Check to see that the high limit control is set above
the design temperature requirements of the system.
For multiple zones: Check to make sure the flow is
adjusted as required in each zone.
12. Check that the heater is cycled with the thermostat.
Raise the setting on the thermostat to the highest
setting and verify that the heater goes through the
normal start-up cycle. Reduce to the lowest setting
and verify that the heater goes off.
13. Observe several operating cycles for proper opera-
tion.
14. Set the heater thermostat to desired temperature.
15. Review all instructions shipped with this heater
with owner or maintenance person, return to envelope and give to owner or place the instructions
inside front panel on heater.
45
Page 48
SECTION D: Start up
46
Page 49
SECTION D: Start up
SECTION E
Operation
Lighting Instructions
1. Before lighting, make sure you have read all of the
safety information in this manual.
2. Remove upper front panel.
3. Set the thermostat to the lowest setting.
4. Turn off all electrical power to the appliance.
5. This appliance is equipped with an ignition device
which automatically lights the burner. Do not try
to light the burner by hand.
6. Turn on main manual gas valve field installed near
gas inlet connection on back of heater.
7. Wait 5 minutes to clear out any gas. Then smell
for gas, especially near the floor. If you then smell
gas, STOP! Follow the steps in the safety information on the front cover of this manual. If you do
not smell gas, go to next step.
8. Turn on all electrical power to the appliance.
9. Set thermostat to desired setting. The appliance
will operate. The igniter will glow after the prepurge time delay (15 seconds). After igniter
reaches temperature (30 seconds) the main valve
should open. System will try for ignition one time
(three times on optional 3-try ignition module). If
flame is not sensed, lockout will commence.
12. If heater fails to start, verify the following:
a. There are no loose connections or that the ser-
vice switch is off.
b. High temperature limit switch is set above wa-
ter temperature or manual reset high limit is
not tripped.
c. Thermostat is set above water temperature.
d. Gas is on at the meter and the heater.
e. Incoming dynamic gas pressure to the gas
valve is NOT less than 4.0 in. WC for natural
gas or propane gas.
To Turn Off Gas To Appliance
1. Shut off manual gas valve field installed near gas
inlet connection on back of heater.
2. Remove upper front panel.
3. Set the thermostat to lowest setting.
4. Turn off all electrical power to the appliance if
service is to be performed.
5. Replace access panel.
10. If the appliance will not operate, follow the in-
structions “To Turn Off Gas To Appliance,” and
call your service technician or gas supplier.
11. Replace upper front panel.
47
Page 50
SECTION E: Operation
48
Page 51
SECTION D: Start up
p
p
g
p
y
SECTION F
Troubleshooting
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Does the power switch provide
power to the control panel?
YES
YES
Is Disable connection intact?
YES
Does the combustion air
blower come on?
Is 4-20mA present at the quick
disconnects on the black and blue
wires of the tem
YES
Is 24VAC at the NC side of
the air pressure switch?
YES
Is 24VAC at PS on ignition module?
Is connecting plug secure?
YES
Does igniter prove?
YES
Is the flame sensor signal to the
i
nition module greater than 1 uA DC?
YES
Is there a Call For
erature controller?
Does F2 on ignition module
have AC
NO
NO
Heat?
NO
NO
YES
ower?
NO
Is Amp draw during heat-
YES
NO
Check the switch and/or
line voltage
NO
Reattach.
Is there 120VAC at the blower or
blower relay?
YES
NO
NO
Is blower pressure setting
(vacuum) correct?
NO
up for HSI greater than
3.1 Amps?
Is air switch bouncing?
Is gas pressure correct?
YES
Unit is in standby mode.
Is diagnostic board
indicating open
Is there continuity in the wire
between F2 and Pin J5-6?
Correct wiring.
YES
NO
Check and correct power
NO
YES
Replace air pressure switch.
connections at main terminal
block, circuit breaker panel or
NO
NO
Replace HSI
NO
YES
blower relay.
Replace temperature
controller.
Correct Safet
NO
Correct the shutter
setting or blower
amp draw.
NO
Repair or
Re
lace wire.
Step 8
Step 9
Is the unit running?
YES
The unit is okay
Is static and dynamic inlet gas
pressure correct?
NO
Call our Technical Service Department
1-800-927-2975 Outside California
1-800-627-2975 Inside California
YES
49
NO
Replace gas valve
Correct the gas pressure.
Page 52
SECTION F: Troubleshooting
UDB Fault History
To view the fault codes in the UDB history file:
1. Press and hold the switch labeled “SW1” for 5
seconds to access the fault history. LED 17 will
begin to flash when the history has been accessed.
See Fig. 38 on page 37.
2. Press the switch labeled “SW2” to scroll through
the recorded faults in history.
3. When a fault is being displayed, the corresponding
LED will light AND LED 17 will flash at a rate
that corresponds to the fault number.
4. The faults are recorded and displayed on a last in,
first out basis. The last fault recorded will be the
first fault displayed. There is no time or date stamp
associated with these faults.
5. Continue to push “SW2” to view subsequent faults.
6. When the history of faults has been exhausted,
pushing “SW2” again will roll the fault history
over and it will start again.
7. To exit the fault history, press and hold “SW1” for
5 seconds, or wait for 4 minutes and the board will
automatically exit the history mode (fault LEDs
will go out).
To clear the fault history, press and hold both “SW1”
and “SW2” for 5 seconds.
NOTE: Once the history has been cleared, it cannot be
recovered.
50
Page 53
SECTION G
Maintenance
Suggested Minimum
Maintenance Schedule
Regular service by a qualified service agency and maintenance must be performed to ensure maximum operating
efficiency.
Maintenance as outlined below may be performed by the
owner.
Daily
1. Check that the area where the heater is installed is free
from combustible materials, gasoline, and other flammable vapors and liquids.
2. Check for and remove any obstruction to the flow of
combustion or ventilation air to heater.
Monthly
1. Check for piping leaks around pumps, mixing valves,
relief valves, and other fittings. If found, repair at once.
DO NOT use petroleum-based stop-leak compounds.
2. Visually inspect burner flame.
3. Visually inspect venting system for proper function,
deterioration or leakage.
4. Visually inspect for proper operation of the condensate
drain in the venting. If leaks are observed repair at
once.
5. Check air vents for leakage.
Yearly (Beginning Of Each Heating
Season)
Schedule annual service call by qualified service agency.
1. Visually check top of vent for soot. Call service person
to clean. Some sediment at bottom of vent is normal.
2. Visually inspect venting system for proper function,
deterioration or leakage. Ensure that condensate drain
is inspected and ensure that condensate is being directed to appropriate condensate management system
or drain, as required by local codes.
3. Check that area is free from combustible materials,
gasoline, and other flammable vapors and liquids.
4. Check for and remove any obstruction to the flow of
combustion or ventilation air to heater.
5. Follow pre-start-up check in Section D.
6. Visually inspect burner flame. It should be light blue
at full input. Remove and visually inspect hot surface
igniter and sensor for damage, cracking or debris
build-up.
7. Check operation of safety devices. Refer to manufac-
turers’ instructions.
8. Follow oil-lubricating instructions on pump (if re-
quired). Over-oiling will damage pump.
Water-lubricated circulators do not need oiling.
9. To avoid potential of severe burn, DO NOT REST
HANDS ON OR GRASP PIPES. Use a light touch;
return piping will heat up quickly.
10.Check blower and blower motor.
51
Page 54
SECTION G: Maintenance
11. Check for piping leaks around pumps, relief valves
and other fittings. Repair, if found. DO NOT use petroleum-based stop-leak.
Periodically
1. Check relief valve. Refer to manufacturer’s instruc-
tions on valve.
2. Test low water cut-off (if equipped). Refer to manu-
facturer’s instructions.
Preventive Maintenance
Schedule
The following is required procedure in all jurisdictions
which require CSD-1 and good practice for all MVB installations.
Daily
1. Check gauges, monitors and indicators.
2. Check instrument and equipment settings. (See “Post
Start-Up Check” on page 45.)
3. Check burner flame. (Should see light blue flame at
full input rate).
Weekly
For low-pressure heaters, test low-water cut-off device.
(With heater in pre-purge, depress the low water cut-off
test button. Appliance should shut-off and ignition fault
light should come on. Depress reset button on front of
heater control panel to reset).
1. Check igniter. (Resistance reading should be 42-70
ohms at ambient temperature.)
2. Check flame signal strength. (Flame signal should be
greater than 1 microamp as measured at the 2 pins on
the upper left corner of the ignition control).
3. Check flame failure detection system. (See “Post Start-
Up Check” on page 45.)
4. Check firing rate control by checking the manifold
pressure. (See “Manifold Adjustment” on page 43.)
5. Make auditory and visual check of main fuel valve.
Monthly
1. Check flue, vent, stack, or outlet dampers.
2. Test blower air pressure. (See “Blower Adjustment”
on page 42.)
3. Test high and low gas pressure interlocks (if equipped).
(See “Safety Inspection” on page 44.)
Semi-Annually
1. Recalibrate all indicating and recording gauges.
2. Check flame failure detection system components.
3. Check firing rate control by checking the manifold
pressure. (See “Manifold Adjustment” on page 43.)
4. Check piping and wiring of all interlocks and shut-off
valves.
Annually
1. Test flame failure detection system and pilot turndown.
2. Test high limit and operating temperature. (See “Post
Start-Up Check,” page 45.)
3. Check flame sensors.
4. Conduct a combustion test at full fire. Carbon dioxide
should be 8.0 to 9.0% at full fire for natural gas, and
between 9.0 to 10.0% for propane gas. Carbon monoxide should be < 100 ppm.
5. Check valve coil for 60 cycle hum or buzz. Check for
leaks at all valve fittings using a soapy water solution
(while heater is operating). Test other operating parts
of all safety shut-off and control valves and increase or
decrease settings (depending on the type of control)
until the safety circuit opens. Reset to original setting
after each device is tested.
6. Perform leakage test on gas valves. (See Fig. 40.)
7. Test air switch in accordance with manufacturer’s
instructions. (Turn panel switch to the “On” position
until blower is proven, then turn the switch to “Off.”
8. Inspect burner.
As Required
1. Recondition or replace low water cut-off device (if
equipped).
2. Check drip leg and gas strainers.
3. Perform flame failure detection tests.
4. Test safety/safety relief valves in accordance with
ASME Heater and Pressure Vessel Code Section IV.
52
Page 55
SECTION H
Appendix
Inside Air Contamination
All heaters experience some condensation during startup. The condensate from flue gas is acidic. Combustion
air can be contaminated by certain vapors in the air
which raise the acidity of the condensate. Higher acidity levels attack many materials including stainless
steel, which is commonly used in high efficiency systems. The heater can be supplied with corrosionresistant, non-metallic intake air vent material. You
may, however, choose to use outside combustion air
for one or more of these reasons:
1. Installation is in an area containing contaminants
listed below which will induce acidic condensation.
2. You want to reduce infiltration into your building
through openings around windows and doors.
3. You are using AL29-4C stainless steel vent pipe,
which is more corrosion-resistant than standard
metallic vent pipe. In extremely contaminated areas, this may also experience deterioration.
Products causing contaminated combustion air:
• spray cans containing chloro/fluorocarbons
• permanent wave solutions
• chlorinated waxes/cleaners
• chlorine-based swimming pool chemicals
• calcium chloride used for thawing
• sodium chloride used for water softening
• refrigerant leaks
• paint or varnish removers
• hydrochloric acid/muriatic acid
• cements and glues
• antistatic fabric softeners used in clothes dryers
• chloride-type bleaches, detergents, and cleaning
solvents found in household laundry rooms
• adhesives used to fasten building products
• similar products.
Areas where contaminated combustion air commonly
exists:
• dry cleaning/laundry areas
• metal fabrication plants
• beauty shops
• refrigeration repair shops
• photo processing plants
• auto body shops
• plastic manufacturing plants
• furniture refinishing areas and establishments
new building construction
•
• remodeling areas
• open pit skimmers.
Check for areas and products listed above before installing heater. If found:
• remove products permanently, OR
• install TruSeal direct vent.
53
Page 56
LIMITED PARTS WARRANTY
MVB – TYPES H AND WH
MODELS 503-2003
SCOPE
Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this heater which are actually manufactured by Raypak will be free
from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this Warranty. Labor
charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this Warranty but are the
owner’s responsibility.
HEAT EXCHANGER WARRA NTY
Domestic Hot Water
Five (5) years from date of heater installation. Includes copper heat exchanger with bronze waterways.
Ten (10) years from date of heater installation. Includes only cupro-nickel heat exchanger with bronze waterways.
Space Heating (Closed Loop System)
Ten (10) years from date of heater installation. Includes both cupro-nickel and copper heat exchanger with bronze water-ways.
Thermal Shock Warranty
Twenty (20) years from date of heater installation against “Thermal Shock” (excluded, however, if caused by heater operation at large
changes exceeding 150°F between the water temperature at intake and heater temperature, or operating at heater temperatures exceeding 230°F).
ANY OTHER PART MANUFA CTURED BY RAYPAK
One (1) year warranty from date of heater installation, or eighteen (18) months from date of factory shipment based on Raypak’s records,
whichever comes first.
SATISFACTORY PROOF OF INSTALLATION DATE, SUCH AS INSTALLER INVOICE, IS REQUIRED. THIS WARRANTY WILL BE
VOID IF THE HEATER RATING PLATE IS ALTERED OR REMOVED.
ADDITIONAL WARRANTY EXCLUSIONS
This warranty does not cover failures or malfunctions resulting from:
1. Failure to properly install, operate or maintain the heater in accordance with our printed instructions provided;
2. Abuse, alteration, accident, fire, flood and the like;
3. Sediment or lime build-up, freezing, or other conditions causing inadequate water circulation;
4. High velocity flow exceeding heater design rates;
5. Failure of connected systems devices, such as pump or controller;
6. Use of non-factory authorized accessories or other components in conjunction with the heater system;
7. Failing to eliminate air from, or replenish water in, the connected water system;
8. Chemical contamination of combustion air or use of chemical additives to water.
PARTS REPLACEMENT
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if requested,
with transportation charges prepaid, and all applicable warranty conditions found satisfied. The replacement part will be warranted for
only the unexpired portion of the original warranty. Raypak makes no warranty whatsoever on parts not manufactured by it, but Raypak
will apply any such warranty as may be provided to it by the parts manufacturer.
TO MAKE WARRANTY CLA IM
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and description of the problem. The installer must then notify his Raypak distributor for instructions regarding the claim. If either is not available, contact Service
Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 or call (805) 278-5300. In all cases proper authorization must first be
received from Raypak before replacement of any part.
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY
This is the only warranty given by Raypak. No one is authorized to make any other warranties on Raypak’s behalf. THIS WARRANTY IN
LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. RAYPAK’S SOLE LIABILITY AND THE SOLE REMEDY AGAINST
RAYPAK WITH RESPECT TO DEFECTIVE PARTS SHALL BE AS PROVIDED IN THIS WARRANTY. IT IS AGREED THAT RAYPAK
SHALL HAVE NO LIABILITY, WHETHER UNDER THIS WARRANTY, OR IN CONTRACT, TORT, NEGLIGENCE OR OTHERWISE,
FOR ANY SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGE, INCLUDING DAMAGE FROM WATER LEAKAGE. Some states
do not allow limitations on how long an implied warranty lasts, or for the exclusion of incidental or consequential damages. So the above
limitation or exclusion may not apply to you.
This Limited Warranty gives you specific legal rights. You may also have other rights which may vary from state to state. We suggest that
you complete the information below and retain this certificate in the event warranty service is needed. Reasonable proof of the effective
date of the warranty (date of installation) must be presented, otherwise, the effective date will be based on the rate of manufacture plus
thirty (30) days.
Original Owner Model Number
Mailing Address Serial Number
Date of Installation
City State Zip Code Installation Site
Daytime Telephone Number Contractor/Installer
RAYPAK, INCy 2151 Eastman Avenue y Oxnard, CA 93030-9786 y (805) 278-5300 y Fax (800) 872-9725 y www.raypak.com