Raypak H7-1005A Installation Manual

INSTALLATION & OPERATING
ULTRA HIGH EFFICIENCY
INSTRUCTIONS
Models 1005A–2005A
Types H, WH & P
WARNING: Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury, exposure to hazardous materials* or loss of life. Review the information in this manual carefully. *This unit contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future reference.
CATALOG NO. 3400.552 Effective: 08-02-13 Replaces: NEW P/N 241513 Rev. 1
2
CONTENTS
WARNINGS 4 BEFORE INSTALLATION 5
Product Receipt 5 Model Identification 5 Ratings and Certifications 5 Installations at Elevation 5 Component Locations 6 General Information 6
GENERAL SAFETY 7
Time/Temperature Relationships in Scalds 7
INSTALLATION 8
Installation Codes 8 Equipment Base 8 Clearances 8 Combustion and Ventilation Air 9 Conventional Combustion Air Supply 11 Water Piping 13 Hydronic Heating 15 Applications & Modes 16 Domestic Hot Water 17 Pool Heating 19 Gas Supply 21 Electrical Power Connections 22 Field Wiring Connection 24 Venting 27
Venting Installation Tips 30 Venting Configurations 30 Outdoor Installation 35 Controls 36 User Interface 38
WIRING DIAGRAM 44 START-UP 45
Pre Start-up 45 Start-Up 46
OPERATION 50
Lighting Instructions 50 To Turn Off Gas To Appliance 50
TROUBLESHOOTING 50 MAINTENANCE 53
Suggested Minimum Maintenance Schedule 53 Preventative Maintenance Schedule 54 Filter Maintenance 55 Filter Replacement 55
APPENDIX 56
Inside Air Contamination 56
IMPORTANT INSTRUCTIONS FOR THE COMMONWEALTH OF MASSACHUSETTS 57 START-UP CHECKLIST 59 WARRANTY 60
3

WARNINGS

Pay Attention to These Terms
ndicates the presence of immediate hazards which will cause severe
DANGER:
I personal injury, death or substantial property damage if ignored.
WARNING:
CAUTION:
NOTE:
DANGER: Make sure the gas on which the heater
will operate is the same type as that specified on the heater rating plate.
WARNING: Should overheating occur or the gas supply valve fail to shut, do not turn off or disconnect the electrical supply to the heater. Instead, shut off the gas supply at a location external to the heater.
WARNING: Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
WARNING: To minimize the possibility of improper operation, serious personal injury, fire, or damage to the heater:
Always keep the area around the heater free of combustible materials, gasoline, and other flammable liquids and vapors.
Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
WARNING: Both natural gas and propane have an odorant added to aid in detecting a gas leak. Some people may not physically be able to smell or recognize this odorant. If you are unsure or unfamiliar with the smell of natural gas or propane, ask your local gas supplier. Other conditions, such as "odorant fade," which causes the odorant to diminish in intensity, can also hide, camouflage, or otherwise make detecting a gas leak by smell more difficult.
WARNING: UL recognized fuel gas detectors are recommended in all enclosed propane and natural gas applications wherein there is a potential for an explosive mixture of fuel gas to accumulate and their installation should be in accordance with the detector manufacturer's recommendations and/or local laws, rules, regulations, or customs.
WARNING - CALIFORNIA PROPOSITION 65: This product contains chemicals known to the
State of California to cause cancer, birth defects or other reproductive harm.
Heater should never be covered or have any blockage to the flow of fresh air to the heater.
WARNING: Risk of electrical shock. More than one disconnect switch may be required to de-energize the equipment before servicing.
CAUTION: If this heater is to be installed above radiation level, it must be provided with a low water cut-off device at the time of heater installation.
CAUTION: If this heater is to be installed in a negative or positive pressure equipment room, there are special installation requirements. Consult factory for details.
4

BEFORE INSTALLATION

Raypak strongly recommends that this manual be re­viewed thoroughly before installing your XTherm heater. Please review the General Safety information before installing the heater. Factory warranty does not apply to heaters that have been improperly installed or operated. (Refer to the warranty at the back of this manual.) Installation and service must be performed by a qualified installer, service agency or gas supplier. If, after reviewing this manual, you still have questions which this manual does not answer, please contact your local Raypak representative or visit our website at www.raypak.com.
Thank you for purchasing a Raypak product. We hope you will be satisfied with the high quality and durability of our equipment.

Product Receipt

On receipt of your heater it is suggested that you visu­ally check for external damage to the shipping crate. If the crate is damaged, make a note to that effect on the Bill of Lading when signing for the shipment. Next, remove the heater from the shipping packaging. Report any damage to the carrier immediately.
On occasion, items are shipped loose. Be sure that you receive the correct number of packages as indi­cated on the Bill of Lading.
he upper rear jacket panel of the heater. The model
t number will have the form H7 or similar depending on the heater size and configuration. The letter(s) in the first group of characters identifies the application (H =
ydronic Heating, WH = Domestic Hot Water (DHW),
H and P = Pool heating). The number which follows iden-
ifies the firing mode (7 = electronic modulation). The
t second group of characters identifies the size of the heater (the four numbers representing the approxi­mate MBTUH input), and, where applicable, a letter, indicating the manufacturing series.

Ratings and Certifications

Standards:
ANSI Z21.13 · CSA 4.9 - latest edition, Gas-Fired Hot Water Boilers
CAN 3.1 - latest edition, Industrial and Commercial Gas-Fired Package Boilers
ANSI Z21.10.3 · CSA 4.3 - latest edition, Gas Wa­ter Heaters
ANSI Z21.56 · CSA 4.7 - latest edition, Gas-Fired Pool Heaters
SCAQMD Rule 1146.2
Low-lead content (<.25%) CSA-certified
All Raypak heaters are National Board Approved, and design-certified and tested by the Canadian Standards Association (CSA) for the U.S. and Canada. Each heater is constructed in accordance with Section IV of the American Society of Mechanical Engineers
Claims for shortages and damages must be filed with the carrier by consignee. Permission to return goods must be received from the factory prior to shipping. Goods returned to the factory without an authorized Returned Goods Receipt number will not be accepted. All returned goods are subject to a restocking charge.
When ordering parts, you must specify the model and serial number of the heater. When ordering under war­ranty conditions, you must also specify the date of installation.
Purchased parts are subject to replacement only under the manufacturer’s warranty. Debits for defec­tive replacement parts will not be accepted. Parts will be replaced in kind only per Raypak’s standard war­ranties.

Model Identification

The model identification number and heater serial number are found on the heater rating plate located on
WARNING: Altering any Raypak pressure vessel by installing replacement heat exchangers, tube bundle headers, or any ASME parts not manufactured and/or approved by Raypak will instantly void the ASME and CSA ratings of the vessel. Altering the ASME or CSA ratings of the vessel also violates national, state, and local approval codes.
(ASME) Heater Pressure Vessel Code and bears the ASME stamp. This heater also complies with the latest edition of the ASHRAE 90.1 Standard.
Installations at Elevation
Rated inputs are suitable for up to 2,000 ft elevation without de-rating. Consult your local representative or the factory for installations at altitudes over 2,000 ft above sea level. No hardware changes are required to the heaters for installations up to 10,000 ft (adjust­ments may be required).
5
INJECTOR PUMP(S)
H
EATER
PUMP

Component Locations

Model
Max
Input Min Input
Water Conn (NPT)
Vent Size
Comb
Air
Xtherm MBTUH MBTUH In Nat LP In In
1005A 999 140 2 1/2 1-1/4 1 6 6
1505A 1500 210 2 1/2 1-1/4 1 8 8
2005A 1999 280 2 1/2 2 1 8 8
Gas Conn
(NPT)
Fig. 3: Component Locations – Rear
Panels omitted for clarity
Fig. 1: Component Locations – Side
Top panel, blower and gas train omitted for clarity
Fig. 4: Component Locations – Top
General Information
Panels omitted for clarity
Fig. 2: Component Locations – Front
Table A: Basic Data
6
GENERAL SAFETY
Water temperature over 125°F can cau s e i nsta n t s e v er e b u r ns or d eath from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
See instruction manual before set­ting temperature at water heater.
Feel water before bathing or show­ering.
Temperature limiting valves are available, see manual.
Water
Temp.
Time to Produce Serious
Burn
120°F More than 5 minutes
125°F 1-1/2 to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
145°F Less than 3 seconds
150°F About 1-1/2 seconds
155°F About 1 second
Table courtesy of The Shriners Burn Institute
To meet commercial hot water use needs, the high limit safety control on this water heater will shut off the main gas valve before the outlet temperature reaches 210°F. However, water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water, the rec­ommended initial setting for the temperature control is 125°F.
This section applies to Hot Water Supply Boilers and Hot Water Heaters ONLY. For sanitary rinse applica­tions where outlet temperatures of 180°F to 195°F are required, a boiler is recommended since the 210°F limit on water heaters will NOT allow the heater to maintain these desired sanitary rinse temperatures.
Safety and energy conservation are factors to be con­sidered when setting the water temperature on the thermostat. The most energy-efficient operation will result when the temperature setting is the lowest that satisfies the needs of the application.
Water temperature over 125°F can cause instant severe burns or death from scalds. Children, disabled and elderly are at highest risk of being scalded.
Feel water before bathing or showering.
Temperature limiting valves are available.
NOTE: When this water heater is supplying general purpose hot water for use by individuals, a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.
Maximum water temperatures occur just after the heater’s burner has shut off. To determine the water temperature being delivered, turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer.
CAUTION: Hotter water increases the risk of scalding! There is a hot water scald potential if the thermostat is set too high.
Time/Temperature Relationships in Scalds
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
Table B: Time to Produce Serious Burn
7
INSTALLATION
Installation Codes
Installations must follow these codes:
Local, state, provincial, and national codes, laws, regulations and ordinances
National Fuel Gas Code, ANSI Z223.1/NFPA 54 – latest edition (NFGC)
National Electrical Code, ANSI/NFPA 70 - latest edition (NEC)
Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, (CSD-1) when required
For Canada only: CAN/CSA B149 Natural Gas and Propane Installation Code and CSA C22.1 C.E.C. Part 1 (C22.1)
CAUTION: This heater should be located in an area where water leakage will not result in damage to the area adjacent to the appliances or to the structure. When such locations cannot be avoided, it
s recommended that a suitable catch pan,
i adequately drained, be installed under the appliance. The pan must not restrict air flow.
In addition, the heater shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation or service (circulator replacement, control replacement, etc.).
If the heater needs to be secured to the ground, use the hole pattern shown in Fig. 5, following local codes. Additional clearance may be required when using the factory anchor bracket.
Clearances
Fig. 5: Anchor Hole Locations
Heater
Side
Floor* 0” 0”
Rear 12” 36”
Right Side 1” 24”
Left Side 1” 1”
Top 0” 10”
Front Open 24”
Vent 1” 1”
*DO NOT install on carpeting.
Table C: Clearances – Indoor Installations
For ease of servicing, provide a minimum clearance of at least 24 in. on the right side, 24 in. in front, at least 36 in. on the rear and 10 in. above the top of the heater. This will allow the heater to be serviced in its installed location without movement or removal of the heater.
Minimum Clearance
from Combustible
Surfaces
Minimum
Service
Clearance
Equipment Base
The heater should be mounted on a level, structurally sound surface. The heater is approved for installation on a combustible surface but must NEVER be installed on carpeting. Gas-fueled equipment installed in enclosed parking garages must be located at least 18 in. above the floor.
Indoor Installations
Service clearances less than the minimum may require removal of the heater to service either the heat exchanger or the burner components. In either case, the heater must be installed in a manner that will enable the heater to be serviced without removing any structure around the heater.
8
he combustion air intake elbow MUST be used for
T outdoor installations. It is shipped loose to be installed on the air filter intake at the rear of the heater at the job site. The elbow MUST be oriented with the opening
acing downward (shipped loose).
f
in. Clearance
Heater
Side
Rear 12” 36”
Right Side 1” 24”
Left Side 1” 1”
Top Unobstructed 10”
Vent
Termination
Table D: Clearances – Outdoor Installations
M
from Combustible
Surfaces
12” 12”
inimum
M
Service
Clearance
Combustion and Ventilation Air
NOTE: Use of this heater in construction areas
where fine particulate matter, such as concrete or dry-wall dust, is present may result in damage to the heater that is not covered by the warranty. If operated in a construction environment, a clean source of combustion air must be provided directly to the heater.
Fig. 6: Minimum Clearances from Combustible
Surfaces – Indoor and Outdoor Installations
Outdoor Installations
These heaters are design-certified for outdoor installa­tion. Heaters must not be installed under an overhang unless clearances are in accordance with local instal­lation codes and the requirements of the gas supplier. Three sides must be open in the area under the over­hang. Roof water drainage must be diverted away from heaters installed under overhangs.
Indoor Units
This heater must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation. Combustion air can be sup­plied via conventional means where combustion air is drawn from the area immediately surrounding the heater, or via direct vent, where combustion air is drawn directly from outside. All installations must com­ply with the requirements of the NFGC (U.S.) and B149 (Canada), and all local codes.
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can cause non-warrantied damage to the heater. (See the Appendix.)
NOTE: It is recommended that the intake vent be insulated to minimize sweating when inistalled in cold climates.
9
U.S. Installations
1
Canadian Installations
2
A
Clearance above grade, veranda, porch, deck, or balcony
1 ft (30 cm) 1 ft (30 cm)
B
Clearance to window or door that may be opened
4 ft (1.2m) below or to side
of opening; 1 foot (30 cm)
above opening
3 ft (91 cm)
C Clearance to permanently closed window * *
D
Vertical clearance to ventilated soffit located above the terminal within a horizontal dis­tance of 2 ft (61cm) from the centerline of the terminal
5 ft (1.5m) *
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner 6 ft (1.83m) *
H
Clearance to each side of center line ex­tended above meter/regulator assembly
*
I Clearance to service regulator vent outlet * 6 ft (1.83m)
J
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
4 ft (1.2m) below or to side
of opening; 1 ft (30 cm)
above opening
3 ft (91 cm)
K Clearance to mechanical air supply inlet
3 ft (91 cm) above if within
10 ft (3m) horizontally
6 ft (1.83m)
L
Clearance above paved sidewalk or paved driveway located on public property
7 ft (2.13m)
7 ft (2.13m) t
M
Clearance under veranda, porch, deck or balcony
* 12 in. (30 cm) TT
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
2
In accordance with the current CAN/CSA-B149 Installation Codes
t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that se rves
both dwellings
TT Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of term inal and
underside of veranda, porch, deck or balcony is greater than 1 ft (30cm)
* Clearances in accordance with local installation codes and the requirements of the gas supplier
3 ft (91 cm) within a
height 15 ft above the
meter/regulator assembly
Fig. 7: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
Table E: Vent/Air Inlet Termination Clearances
10
Combustion Air Filter
Debris Screen
In take A ir Co llar
his heater is supplied with an integral combustion air
T filter. This filter will reduce the amount of particulates
assed through the combustion system and heat
p exchanger but will not protect against chemical air contamination (See Appendix). The filter must be checked periodically to verify that adequate combus-
ion air is being supplied to the heater. See the
t Maintenance section of this manual for information on checking the filter and establishing service intervals.
Direct Vent
If outside air is drawn through the intake pipe directly to the unit for combustion:
1. Install combustion air direct vent in accordance with Fig. 35 (horizontal) or Fig. 36 (vertical) of this manual (pages 33 and 34, respectively).
2. Ventilation of the space occupied by the heater(s) is recommended and can be provided by an open­ing(s) for ventilation air at the highest practical point communicating with the outdoors. The total cross-sectional areas should be at least 1 in.² of free area per 20,000 BTUH (111 mm² per kW) of total input rating of all equipment in the room, when the opening is communicating directly with the outdoors or through vertical duct(s). The total cross-sectional area should be at least 1in.² of free area per 10,000 BTUH (222 mm² per kW) of total input rating of all equipment in the room, when the opening is communicating with the outdoors through horizontal duct(s). Damage to the equip­ment due to inadequate ventilation of the space is not a warrantable failure.
Fig. 11: Remove the Debris Screen
5. Install the intake air collar using the six screws removed in step 8 above.
3. In cold climates, and to mitigate potential freeze­up, Raypak highly recommends the installation of a motorized sealed damper to prevent the circula­tion of cold air through the heater during the non-operating hours.
4. Remove the debris screen (or cover panel for model 1005) by removing the six screws holding it in place.
Fig. 12: Install the Intake Air Collar
6. Replace all the access panels.
7. Install combustion air direct vent in accordance with Fig. 27 (horizontal) or Fig. 28 (vertical) of this manual (pages 27 and 28, respectively).
8. Ventilation of the space occupied by the heater(s) is recommended and can be provided by an open­ing(s) for ventilation air at the highest practical point communicating with the outdoors. The total cross-sectional areas should be at least 1 in.² of free area per 20,000 BTUH (111 mm² per kW) of total input rating of all equipment in the room, when the opening is communicating directly with the outdoors or through vertical duct(s). The total
11
cross-sectional area should be at least 1in.² of free area per 10,000 BTUH (222 mm² per kW) of total input rating of all equipment in the room, when the opening is communicating with the outdoors through horizontal duct(s). Damage to the equip­ment due to inadequate ventilation of the space is
ot a warrantable failure.
n
9. In cold climates, and to mitigate potential freeze­up, Raypak highly recommends the installation of a motorized sealed damper to prevent the circula­tion of cold air through the heater during the non-operating hours.
(305 mm) of the bottom of the enclosure. The mini­mum dimension of air openings shall be not less than 3 in. (76 mm) in any direction.
ll Air from Outdoors
A
he confined space shall communicate with the out-
T doors in accordance with one of the methods below. The minimum dimension of air openings shall not be less than 3 in. (76 mm) in any direction. Where ducts are used, they shall be of the same cross-sectional area as the net free area of the openings to which they connect.
TruSeal™ Combustion Air
In addition to the nine previous steps, combustion air may be ducted directly to the heater by using PVC, CPVC or sealed single-wall galvanized ducting. The duct will attach directly to the field installed air collar located on the rear of the heater, using three or four sheet metal screws (not supplied) equally positioned around the circumference of the duct. The screws and duct connection point should be sealed with RTV (not supplied). TruSeal is generally used when damaging contaminants are present in the mechanical room. All ducting MUST be self-supported.
Conventional Combustion Air Supply
CAUTION: Use TruSeal combustion air if
damaging airborne contaminants are or may be present in the heater area. See the Appendix of this manual regarding air contamination.
U.S. Installations
All Air from Inside the Building
The confined space shall be provided with TWO per­manent openings communicating directly with an additional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for a room large in comparison (NFGC). The total input of all gas utilization equipment installed in the combined space shall be considered in making this determina­tion. Each opening shall have a minimum free area of
2
per 1,000 BTUH (2,225 mm2per kW) of the total
1 in. input rating of all gas utilization equipment in the con­fined space, but not less than 100 in. opening shall commence within 12 in. (305 mm) of the top, and one opening shall commence within 12 in.
2
(645 cm2). One
1. Two permanent openings, one commencing
within 12 in. (305 mm) of the top, and one com­mencing within 12 in. (305 mm) of the bottom of the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely com­municate with the outdoors.
a. Where directly communicating with the out-
doors or where communicating to the outdoors through vertical ducts, each open- ing shall have a minimum free area of 1 in. per 4,000 BTUH (550 mm2per kW) of total input rating of all equipment in the enclosure.
b. Where communicating with the outdoors
through horizontal ducts, each opening shall have a minimum free area of 1 in.2per 2,000 BTUH (1,100 mm2per kW) of total input rat­ing of all equipment in the enclosure.
2. One permanent opening, commencing within 12
in. (305 mm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (152 mm) from the front of the appliance. The opening shall directly communicate with the out­doors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors, and shall have a minimum free area of:
a. 1 in.2per 3,000 BTUH (740 mm2per kW) of
the total input rating of all equipment located in the enclosure, and
b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING: Do not use the “one permanent opening” method if the equipment room is under negative pressure conditions.
2
12
Canadian Installations
CAUTION: All combustion air must be drawn from
the air outside of the building; the mechanical equip­ment room must communicate directly with the outdoors.
1. Ventilation of the space occupied by the heater shall be provided by an opening(s) for ventilation air at the highest practical point communicating with the outdoors. The total cross-sectional area of such an opening(s) shall be at least 10% of the area required in 2. and 3. (below), but in no case shall the cross-sectional area be less than 10 in. (65 cm2).
2. For heaters using a barometric damper in the vent system there shall be a permanent air supply opening(s) having a cross section area of not less than 1 in.2per 7,000 BTUH (320 mm2per kW) up to and including 1 million BTUH, plus 1 in.2per 14,000 BTUH (160 mm2per kW) in excess of 1 million BTUH. This opening(s) shall be either located at or ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down and terminated 18 in. (450 mm) from the floor, but not near piping. This air supply opening require­ment shall be in addition to the air opening for ventilation air required in 1. (above).
WARNING: Care must be taken to ensure that the equipment room is not under negative pressure conditions.
3. For heaters not using a barometric damper in the vent system, and when air supply is provided by natural air flow from outdoors for a power burner and there is no draft regulator, drafthood or similar flue gas dilution device installed in the same space, in addition to the opening for ventilation air required in 1., there shall be a permanent air sup­ply opening(s) having a total cross-sectional area of not less than 1 in.
2
per kW) of total rated input of the burner(s),
mm and the location of the opening(s) shall not inter­fere with the intended purpose of the opening(s) for ventilation air referred to in 1. This opening(s) can be ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down 18 in. (450 mm) from the floor, but not near piping.
2
for each 30,000 BTUH (74
4. Refer to the B149 Installation Code for additional information
Water Piping
General
The heater should be located so that any water leaks will not cause damage to the adjacent area or struc-
tures.
CAUTION: This heater must be installed with a Primary-Secondary piping arrangement for the integral pumping system to function properly.
2
NOTE: Minimum pipe size for the heater inlet/outlet connections is dependent on the equivalent length of piping between the load loop and the heater loop, the operating conditions and the size of the heater. See Table F on page 15.
Relief Valve Piping Temperature & Pressure Gauge
The temperature and pressure gauge is shipped mounted on the boiler outlet.
Hydrostatic Test
Unlike many types of heaters, this heater does not re­quire hydrostatic testing prior to being placed in operation. The heat exchanger has already been fac­tory-tested and is rated for 160 psi operating pressure. However, Raypak does recommend hydrostatic test­ing of the piping connections to the heater and the rest of the system prior to operation. This is particularly true for hydronic systems using expensive glycol­based anti-freeze. Raypak recommends conducting the hydrostatic test before connecting gas piping or electrical supply.
Leaks must be repaired at once to prevent damage to the heater. NEVER use petroleum-based stop-leak compounds.
To perform hydrostatic test:
1. Connect fill water supply. Fill heater with water. Carefully fill the rest of the system, making sure to eliminate any entrapped air by using high-point vents. Close feed valve. Test at standard operating pressure for at least 24 hours.
2. Make sure constant gauge pressure has been maintained throughout test.
13
3. Check for leaks. Repair any that are found.
Piping
Raypak Integral Cold Water Protection
XTherm heaters are equipped with an integral cold water protection system. Units equipped with the dual injector pump system are designed to operate with heater inlet water temperatures down to 50°F continu­ous. Under start up conditions the dual injector system can operate with fluid temperatures down to 32°F. Operation at lower temperatures will create unwar­rantable damage to the injector pumps. XTherm WH and WHP models equipped with single injector pumps are designed for typical domestic hot water and com­mercial pool heating operating conditions respectively. Contact your local representative or the factory for
applications assistance.
Hydronic Heating
Pump Selection
The heater is equipped with an integral cold water pro­tection system that includes dual modulating injector pumps to pull the required flow from the system loop and a heater pump, sized by the factory, for the opti­mal ∆T across the primary heat exchanger. The system is designed for continuous return temperatures
from 50°F to 180°F.
Feedwater Regulator
All high points should be vented. A heater installed
bove radiation level must be provided with a low wa-
a ter cut-off device (sales order option F-10). This heater, when used in connection with a refrigeration system, must be installed so that the chilled medium is piped in parallel with the heater with appropriate valves to pre-vent the chilled medium from entering the heater.
NOTE: Hot water heating systems all have unique levels of operating diversity that must be accounted for in the system design. The system should always include adequate system flow in excess of the connected boiler flow for proper operation. Where the system flow may drop below the connected boiler flow a buffer/decoupler may be needed. Failure to design for adequate flow (i.e. bypasses, 3 way control valves, flow limiting balance devices, buffer tanks, etc.) will result in boiler short cycling and may reduce boiler life. Always contact your local Raypak representative for system design assistance to avoid these issues.
The piping system of a hot water heater connected to heating coils located in air handling units where they may be exposed to circulating refrigerated air, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the heater water during the cooling cycle. It is highly recommend­ed that the piping be insulated.
Raypak recommends that a feedwater regulator be in­stalled and set at 12 psi minimum pressure at the highest point of the system. Install a check valve or back flow device upstream of the regulator, with a manual shut-off valve as required by local codes.
14
System
R
eturn Temp Su
pply
Tem p
1
S
u
p
p
l
y
Tem
p
1
Suppl
y
Tem
p
1
(
°F) (°F) <80' equiv. 80-200' equiv. (°F) <80' equiv. 80-200' equiv. (°F) <80' equiv. 80-200' equiv.
60 138 2"NPT 2 1/2"NPT 147 2"NPT 2 1/2"NPT 154 2"NPT 2 1/2"NPT 8
0 138 2"NPT 2 1/2"NPT 147 2"NPT 2 1/2"NPT 154 2 1/2"NPT 3"NPT
1
00 138 2 1/2"NPT 3"NPT 147 2 1/2"NPT 3"NPT 154 2 1/2"NPT 3"NPT 120 145 2 1/2"NPT 3"NPT 158 2 1/2"NPT 3"NPT 170 2 1/2"NPT 3"NPT 1
40 165 2 1/2"NPT 3"NPT 178 2 1/2"NPT 3"NPT 190 2 1/2"NPT 3"NPT 160 185 2 1/2"NPT 3"NPT 198 2 1/2"NPT 3"NPT 210 2 1/2"NPT 3"NPT
1
-
Approximate high fire heater outlet temperature based on the standard heater pump and the recommended connecting pipe
s
ize.
M
odel 1005
M
inimum Pi
p
e Size
2
M
odel 1505
M
inimum Pi
p
e
Size
2
M
odel 2005
M
inimum Pi
p
e Size
2
2
-Minimumpipe size based on total equivalent feet of supply and return
pip
in
g
between the s
y
s
tem loo
p
and heater.
able F: Boiler Temperatures and Minimum Pipe Size at Varying Return Temperatures
T
Air-Separation/Expansion Tank
All heaters should be equipped with a properly sized expansion tank and air separator fitting as shown in Fig. 12 .
Fig. 12: Air-Separation/Expansion Tank
Fitting Type
Equivalent Length (ft)
2-1/2” NPT 3” NPT
90° Elbow (Std.) 8.5 9.4
90° Elbow (Long rad.) 3.5 3.6
45° Elbow 3.0 3.4
Gate Valve (Full open) 1.6 1.6
Swing Check Valve 22 25
15
Three-Way Valves
Three-way valves intended to regulate system water temperatures by reducing flow in the boiler should not be used. Raypak heaters are high-recovery, low-mass heaters which are not subject to thermal shock.
Applications & Modes
The VERSA IC Control system is designed for a wide range of applications. The installer/design engineer should refer to the following Modes to determine which best fits the intended application and functionality for the unit being installed.
Type H models of XTherm have three modes available to them to address the various applications the units can be applied to. Type WH units will only have the WH configuration available to them for use with potable water applications when directly connected to a hot water storage tank.
Fig. 13: MODE 1 - Single Boiler with
Primary/Secondary Piping
Mode 1 (Type H Units Only)
This mode selection is for hydronic heating systems with single or multiple boilers (Maximum 4 boilers) in primary/secondary piping configuration with or without Outdoor Air Reset (S4). The system temperature is controlled by the System sensor (S3). The integral boiler pumps (P1) run during any call for heat. The System Pump (P2) runs whenever the system is enabled for heating and the outdoor air temperature is lower than the warm weather shut down (WWSD) tem­perature setting (if utilized). The System Pump is delayed “off” as user defined in the ADJUST menu.
16
Fig. 14: MODE 1 - Boiler Cascade with
Primary/Secondary Piping
NOTE: MODE 1 can also be used for process heat­ing applications in conjunction with a buffer/storage tank when operating temperatures above 160°F are required. Care must be given to ensure water hard­ness is no more than 15 grains per gallon for scale free operation.
Fig. 15: MODE 2 - Single Boiler with Indirect
on System Loop
Mode 2 (Type H Units Only)
This mode selection is for hydronic heating systems with single or multiple boilers (Maximum 4 boilers) in primary/secondary piping configuration with or without Outdoor Air Reset (S4) with indirect DHW on the sys­tem loop (with or without priority). The system temperature is controlled by the System sensor (S3). The Indirect DHW sensor (S5) determines the indirect call/tank setpoint. The system temperature is boosted to Target Max when using the Indirect DHW sensor (S5) during an indirect call for heat. Priority mode tog­gles off the System Pump (P2) when an indirect call for heat is present. The Indirect DHW Pump (P3) runs during an indirect call for heat with no “off” delay. The System Pump (P2) delay “off” as user defined in the ADJUST menu. The System Pump (P2) runs whenev­er the system is enabled for heating and the outdoor air temperature is lower than the WWSD temperature setting (if utilized) unless an indirect call for heat is present with priority.
Fig. 16: MODE 3 - Single Boiler with Indirect
on Boiler Loop
Mode 3 (Type H Units Only)
This mode selection is for hydronic heating systems with single or multiple boilers (Maximum 4 boilers) in primary/secondary piping configuration with or without Outdoor Air Reset (S4) with indirect DHW on the boil­er loop (with priority). The system temperature is controlled by the Supply sensor (S3) whenever the indirect call for heat is not active. The DHW Supply sensor (S5) determines the indirect call/tank setpoint. During an indirect call for heat the boiler firing rate is determined by the water temperature at the Indirect Supply sensor (S6) and the Target Max setting when using the Indirect DHW sensor (S5). The Indirect DHW Pump (P3) runs during an indirect call for heat with no “off” delay. The System Pump (P2) delay “off” as user defined in the ADJUST menu. The system pump (P2) runs whenever the system is enabled for heating and the outdoor air temperature is lower than the WWSD temperature setting (if utilized) unless an indirect call for heat is present.
NOTE: A Tank Aquastat can be used in lieu of the Indirect DHW Sensor (S5). See the Versa IC manu­al for additional details.
Domestic Hot Water
When designing the water piping system for domestic hot water applications, water hardness should be con­sidered. Table G indicates the suggested flow rates for soft, medium and hard water. Water hardness is ex­pressed in grains per gallon.
17
T
ank
u
S
tf
o
S
.
p
uS draH
.
p
uS deM/tfo
S
p
meT nr
u
t
eR
p
.
Med Su
p
. Hard Sup
de
M/tfoS
.
(°F)
T
emp
1
(°F) Temp1 (°F)
<80' equiv. 80-200' equiv.
Temp
1
(°F) Temp
1
(°F) Temp1 (°F)
<80' equiv. 80-200' equiv.
Sup. Temp
1
(°F)
<80' equiv. 80-200' equiv.
60 138 135 2" 2 1/2" 150 145 143 2" 2 1/2" 154 2" 2 1/2" 80 138 135 2" 2 1/2" 150 145 143 2" 2 1/2" 154 2 1/2" 3"
1
00 138 135 2 1/2" 3" 150 145 143 2 1/2" 3" 154 2 1/2" 3" 120 146 146 2 1/2" 3" 150 146 146 2 1/2" 3" 155 2 1/2" 3" 1
30 156 156 2 1/2" 3" 156 156 156 2 1/2" 3" 165 2 1/2" 3" 140 166 166 2 1/2" 3" 166 166 166 2 1/2" 3" 175 2 1/2" 3"
1
-Approximate high fire heater outlet temperature based on the specified heater pump and the recommended minimum
tubing
size.
2
-Minimum tubing size based on total equivalent feet of supply and return
pip
ing between the tank and heater.
Model 1005
Minimum Tubin
g
Size
2
Minimum Tubing Size
2
Minimum Tubin
g
Size
2
500
2
led
o
M
5
0
5
1
led
o
M
Table H: Hot Water Supply Temperatures and Minimum Pipe Size at Varying Return Temperatures
∆T = Temperature rise, °F ∆P = Pressure drop through heat exchanger, ft SHL = System head loss, ft (based on heater and tank connections of no more than 100 eq. ft. of tubing) gpm = Gallons per minute, flow rate MTS = Minimum tubing size *Must utilize optional cupro-nickel tubes. If over 25 grains per gallon, a water softener/treatment system must be utilized. **Caution: For scale free operation with "Hard Water" (16-25 grains per gallon of total hardness), the operating control must NOT be set higher than 130 F. For higher than 130 F operation, a water softener/treatment system must be utilized. ***Care should be given to prevent over-softening of the water as over-softened water can become aggressive. Cupro-nickel tubes are recommended for water softened below 5 grains per gallon.
Table G: Domestic Water Heater Flow Rate Requirements
NOTE: Soft = 3–4 grains per gallon; Medium = 5–15 grains per gallon; Hard = 16–25 grains per gallon.
NOTE: WH units will operate to a maximum tank temperature of 160°F. For temperatures required above 160°F an “H” model boiler configured for high temperature potable operation must be used and great care must be given to ensure water hardness is no more than 15 grains per gallon for scale free operation. MODE 1 should be used and configured for setpoint operation for process heating applica­tions.
Potable Water and Space Heating
CAUTION: When this heater is used for both
potable water and space heating, observe the following to ensure proper operation.
Fig. 17: WH Units - Single Water Heater with Tank
H Units - Single Boiler with Process Tank
WH – Direct DHW Configuration
When the unit is ordered as a “WH” configuration the only application available to it is direct DHW with sin­gle or multiple heaters (Maximum 4 heaters). The tank temperature is controlled by the System sensor (S3). The integral Boiler Pumps (P1) run during any call for heat. The System Pump (P2) output is active whenev­er the system is enabled. The Boiler Pumps are delayed “off” after the Tank Target temperature is achieved and as user defined in the ADJUST menu.
NOTE: If local codes require a vacuum relief valve, acquire one locally and install per valve manufacturer’s instructions.
1. All piping materials and components connected to the water heater for the space heating application shall be suitable for use with potable water.
2. Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water used for space heating.
3. If the heater will be used to supply potable water, it shall not be connected to any heating system or components previously used with a non-potable water heating appliance.
4. When the system requires water for space heating at temperatures higher than 140°F (60°C), a means such as a mixing valve shall be installed to temper the water in order to reduce scald hazard potential.
18
F
ROM
FILTER
TO POOL
CPVC, COPPER OR BRASS
A
UTO LIMIT
(SET AT 110°F)
Automatic Chemical Feeders
All chemicals must be introduced and completely dilut­ed into the water before being circulated through the
eater. High chemical concentrations will result when
h the pump is not running (e.g. overnight).
NOTE: High chemical concentrates from feeders that are out of adjustment will cause rapid corrosion to the heat exchanger. Such damage is not covered under the warranty.
NOTE: Failure of a heat exchanger due to lime scale build-up on the heating surface, low pH or other chemical imbalance is non-warrantable.
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can cause unwarrantable damage to the heater.
Pool Heating
When a boiler or water heater is used in a pool heat­ing application, ensure that all the following installation requirements are met.
The XTherm must be equipped with a direct coupled Cold Water Run injector pump for pool applications. The integral wet rotor injector pump system supplied with all H and model 1005 WH XTherm heaters must not be used for pool service. The direct coupled Cold Water Run injector pump package is optional on all H and 1005 WH models and standard on 1505 and 2005 WH and all P models. The Cold Water Run system must be set to maintain 120°F at the inlet to the pri­mary heat exchanger on all XTherm models.
To complete installation of the heater, the system sen­sor must be installed in the return water line, upstream of the heater. The supplied electronic operating con­trol is configured to operate as the thermostat. A separate auto limit is shipped loose to be installed in the system piping downstream of the heater outlet. See Fig. 18 for the thermostat/sensor location.
WARNING: To ensure safe operation of the XTherm pool heater, all plumbing from the heater to the main loop must be CPVC, copper or brass.
*Maximum 4 times the pipe diameter or 12”, whichever is less.
Fig. 18: Single Pool Heater Application
CAUTION: Combustion air must not be contami­nated by corrosive chemical fumes which can damage the heater and can cause unwarrantable damage to the heater.
CAUTION: Power to the heater should be interlocked with the main system pump to make sure the heater does not fire without the main system pump in operation. Improper flow control can damage the heater. Uncontrolled flow (too high) or restricted flow (too low) can seriously damage the heater. Follow these instructions to make sure your heater is properly installed.
Winterizing Your Heater
Heaters installed outdoors as pool heaters in freezing climate areas should be shut down for the winter. To shut down the heater, turn off manual main gas valve and main gas shut-off. Close isolation valves. Drain the heater using the hose bibs located on the bottom of both heat exchangers. Disconnect the condensate hose from the stainless steel condensing heat exchanger and drain the condensate trap.
NOTE: There are 3 separate drains on the XTherm that must ALL be drained to protect the heat exchangers. These are accessible by removing the lower front door from the heater for the 2 primary drains and the right-rear panel for the condensing heat exchanger drain. Drain any piping of all water that may experience below-freezing temperatures.
Install limit in supply to pool as shown in Fig. 18.
19
Recommended Level(s) Fiberglass Pools Fiberglass Spas
Other Pool and Spa
ypes
T
ater Temperature
W
H
p
Total Alkalinity (ppm) 120-150 120-150 80-120
Calcium Hardness (ppm) 200-300 150-200 200-400
Salt (ppm) 3000 Maximum 3000 Maximum 3000 Maximum
Free Chlorine (ppm)* 2-3 2-3 2-3
Total Dissolved Solids
(ppm)
*Free Chlorine MUST NOT EXCEED 5 ppm! **In saltwater chlorinated pools, the total TDS can be as high as 4500 ppm.
NOTE: The allowable concentrations of salt and of the Total Dissolved Solids are lower for the XTherm than for a typical residential pool heater, due to the higher water temperatures at which an XTherm operates.
Pool/Spa Water Chemistry
CAUTION: Corrosive water can cause unwar-
rantable damage to the heater.
NOTE: Chemical imbalance can cause severe damage to your heater and associated equipment.
8-88°F (20-31°C)
6
.3-7.4
7
1500 Maximum** 1500 Maximum** 1500 Maximum**
Table H: Pool Water Chemistry
9-104°F (31-40°C)
8
.3-7.4
7
tors are usually more efficient in heater water, unless controlled, they can lead to excessive chlorine level which can damage your heater.
Further advice should be obtained from your pool or spa builder, accredited pool shop, or chemical suppli­er for the correct levels for your water.
8-104°F (20-40°C)
6
.6-7.8
7
Chemical imbalance can cause severe damage to the pool heater and associated equipment. Maintain the water chemistry according to the chart below. If the mineral content and dissolved solids in the water become too high, scale forms inside the heat exchang­er tubes, reducing heater efficiency and damaging the heater. If the pH drops below 7.2, this will cause cor­rosion of the heat exchanger and severely damage the heater. Heat exchanger damage resulting from chem­ical imbalance is not covered by the warranty.
For your health and the protection of your pool equip­ment, it is essential that your water be chemically balanced. The following levels must be used as a guide for balanced water.
Occasional chemical shock dosing of the pool or spa should not damage the heater providing the water is balanced.
Automatic chemical dosing devices and salt chlorina-
Automatic Chlorinators and Chemical Feeders
All chemicals must be introduced and completely dilut­ed into the pool or spa water before being circulated through the heater. Do not place sanitizing chemicals in the skimmer. High chemical concentrations will result when the pump is not running (e.g. overnight).
Chlorinators must feed downstream of the heater and have an anti-siphoning device to prevent chemical back-up into the heater when the pump is shut off.
NOTE: High chemical concentrates from feeders and chlorinators that are out of adjustment will cause rapid corrosion to the heat exchanger. Such damage is not covered under the warranty.
NOTE: Failure of a heat exchanger due to lime scale build-up on the heating surface, low pH or other chemical imbalance is non-warrantable.
20
Loading...
+ 44 hidden pages