WARNING: If these instructions are not followed exactly, a fire or explosion may
result causing property damage, personal injury or death
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and
liquids or other combustible materials in the vicinity of this or any other appliance. To
do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
.
This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for
future reference.
Rev. 9 reflects the following:
Changes to: Illustration on front cover, Fig. 2 on page 5, Fig. 4 on page 7, Wiring Diagram on page 9, Wiring Diagram on
page 11, Illustration on page 15, Illustrated Parts List on page 17
Additions: Wiring Diagram on page 10, Wiring Diagram on page 12
Deletions: None
2
CONTENTS
Warnings3
Pay Attention to These Terms3
Receiving Equipment4
General Specifications4
Installation4
Mounting the Assembly4
Wiring a Power Vent Assembly to
an Appliance with IID Ignition7
Venting7
Wiring Diagrams9
182-260 WH1 (Atmospheric)9
182-260 H4/W1 (Atmospheric)10
181-261 WH1 (Lo NOx)11
181-261 H4/W1 (Lo NOx)12
330-400 H4/WH1 (Atmospheric)13
331-401 H4/WH1 (Lo NOx)14
Sequence of Operation16
Start Up Procedures16
Draft Proving Switch16
Illustrated Parts List17
WARNINGS
Pay Attention to These Terms
DANGER:
WARNING:
CAUTION:
NOTE:
NOTE: Minimum 18 AWG, 105°C, stranded wire
must be used for all low voltage (less than 30 volts)
external connections to the unit. Solid conductors
should not be used because they can cause
excessive tension on contact points. Install conduit
as appropriate. All high voltage wires must be the
same size (105°C, stranded wire) as the ones on the
unit or larger.
Indicates the presence of immediate hazards which will cause severe
personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause
severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause
minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which
are important but not related to personal injury hazards.
3
Receiving Equipment
On receiving your equipment, check the carton visually for external damage. If the carton is damaged, make
note on the Bill of Lading when signing for the equip-
a
ment. Remove the complete assembly from the carton
if it is damaged, and report the damage to the carrier
immediately. Be sure that you receive the number of
packages indicated on the Bill of Lading. Claims for
shortages and damages must be filed with the carrier
by consignee.
Minimum
Model No.
181/1824”008757120V
260/2614”008757120V
330/3314”008758120V
400/4014”008758120V
Table A: Draft Assembly Application and Kit Numbers
Connection
Diameter
Kit
Number
Factory
Wired
Purchased parts are subject to replacement only
under the manufacturer's warranty. Debits for defective replacement parts will not be accepted and
defective parts will be replaced in kind only per our
standard warranties.
When ordering parts, you must specify Model Number
of the unit. When ordering under warranty conditions,
you must also specify date of Installation.
Raypak recommends that this manual be reviewed
thoroughly before installing the D-2 Power Vent. If
there are any questions which this manual does not
answer, please contact your local Raypak
Representative.
THIS MANUAL SHOULD BE MAINTAINED IN LEGIBLE CONDITION AND KEPT ADJACENT TO THE
UNIT.
General Specifications
The D-2 Power Vent Assembly is tested and certified
to the latest edition of the American National Standard
ANSI Z21.56. standard for pool heaters, Z21.10.3 for
water heaters and Z21.13 for boilers.
The Power Vent Assembly is a fan assisted combustion system designed for application to Raypak Heater
Models 181-401. The unit, when installed as directed,
is capable of operating in applications such as through
the wall venting and reduced horizontal and vertical
vent pipe sizes in new and existing installations.
The D-2 Power Vent assembly includes a blower with
a 120/240 volt 60 Hz 1.95/1.0A 3200 RPM motor, a
plenum complete with a draft proving switch and a
motor relay. When provided for field mounting the
assembly is equipped with a wire harness.
Installation
The equipment must be installed in accordance with
local codes, or in the absence of local codes with the
latest edition of the National Fuel Gas Code, ANSI
Z223.1, the National Electrical Code, ANSI/NFPA 70.
The equipment shall be installed in accordance with
those installation regulations in force in the local area
where the installation is to be made. These shall be
carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are
made.
Mounting the Assembly
Follow these instructions if the Power Vent
venting system was purchased as an
optional assembly kit.
1. Remove existing pagoda top (outdoor units) or
drafthood (indoor units). To remove the pagoda top,
push the four brackets inward and pull up the pagoda
top. The pagoda may then be discarded.
2. Unscrew the four screws holding the outer top using
a phillips screw driver. Remove the jacket top.
3. Replace the inner stack adapter. If the heater had a
drafthood installed previously, remove the inner stack
adapter and replace it with the Power Vent stack
adapter. Otherwise, install the Power Vent stack
adapter.
4. Unscrew the access panel on the right side of the
appliance. Set aside the screws with the access panel.
5. Remove the knurled screw holding the front door
and set it aside with the door.
NOTE: The D-2 Power Vent comes factory-wired for
120V, but can be field-converted for 240V operation.
See wiring diagrams.
6. Mount the jacket top above the unit. Note: Do not
install at this point.
4
7. Mount the Power Vent on the outer top.
TA B S
BEFOREAFTER
TOP VIEW
LEFT SIDEFRONT VIEWREAR VIEW
8. Route the conduit harness of the Power Vent thru
the outer top hole, around the adapter towards the
back of the unit. Continue routing the harness thru the
corner slot, which leads to open area behind the
access panel. Finally, route only the wire harness thru
the 7/8” grommet hole located on the sway brace.
Follow instructions on page 7 to wire the Power Vent.
Note: Newer units have a 7/8” grommet located on the
rain shield, which would eliminate routing the harness
around the back corner.
9. Re-mount the jacket top to its original position and
screw in the four screws holding it down to the appliance.
10. If the appliance is a 181, 182, 330 or 331, remove
the tabs underneath the power vent using a 5/16” nut
driver and relocate them closer to the center of the
Power Vent as shown in Fig. 1.
Fig. 1: Reposition the Tabs as Necessary (see step 10)
to hold the Power Vent in position. Note: While twisting
you may notice some roughness, this is due to a tight
seal between the 6” vent and the Power Vent flue box.
12. Re-mount the access panel.
11. Mount the Power Vent assembly bottom on the 6”
vent as shown below. Twist the assembly downward.
Snap the mounting brackets into their appropriate slot
13. Re-mount the front door along with the knurled
screw on the heater.
Fig. 2: Draft Assembly
5
U.S. Installations
1
Canadian Installations
2
A
Clearance above grade, veranda, porch,
deck, or balcony
1 ft (30 cm) 1 ft (30 cm)
B
Clearance to window or door that may be
opened
4 ft (1.2m) below or to side
of opening; 1 foot (30 cm)
above opening
3 ft (91 cm)
C Clearance to permanently closed window * *
D
Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance of 2 ft (61cm) from the centerline of the
terminal
5 ft (1.5m) *
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner 6 ft (1.83m) *
H
Clearance to each side of center line extended above meter/regulator assembly
*
3 ft (91 cm) within a height
15 ft above the me-
ter/regulator assembly
I Clearance to service regulator vent outlet * 6 ft (1.83m)
J
Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any
other appliance
4 ft (1.2m) below or to side
of opening; 1 ft (30 cm)
above opening
3 ft (91 cm)
K Clearance to mechanical air supply inlet
3 ft (91 cm) above if within
10 ft (3m) horizontally
6 ft (1.83m)
L
Clearance above paved sidewalk or paved
driveway located on public property
7 ft (2.13m)
7 ft (2.13m) t
M
Clearance under veranda, porch, deck or
balcony
* 12 in. (30 cm) TT
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
2
In accordance with the current CAN/CSA-B149 Installation Codes
t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that se rves
both dwellings
TT Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of term inal and
underside of veranda, porch, deck or balcony is greater than 1 ft (30cm)
* Clearances in accordance with local installation codes and the requirements of the gas supplier
Fig. 3: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
Table B: Vent/Air Inlet Termination Clearances
6
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.