Raypak H3-HD101 Installation Manual

INSTALLATION & OPERATING
®
INSTRUCTIONS
Models HD101–HD401
Types H & WH
WARNING: If these instructions are not followed exactly, a fire or explosion may
result causing property damage, personal injury or death
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
.
This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for future reference.
CATALOG NO. 1000.52D Effective: 10-15-15 Replaces: 09-14-12 P/N 241356 Rev. 5
Rev. 5 reflects the following: Changes to: Table C on page 9, Figs. 7 and 8 on page 10, “Direct Combustion Air” on page 11, “Recovery
Water Connections” on page 13, Figs. 10-12 on page 15, “Piping-Heating Boilers” on page 16, Table G on page 18, Table I on page 22, Table K on page 25, Table L on page 27, Table M on page 29, Table N on page 30, Fig. 27 on page 34, Table P on page 43, Figs 37-38 on page 45, Fig. 39 on page 46.
Additions: “System Design” on page 14, Wiring Diagrams on pages 36-39, Table Q on page 43 Deletions: None
2
CONTENTS
WARNINGS 4
Pay Attention to These Terms 4
BEFORE INSTALLATION 5
Product Receipt 5 Model Identification 5 Ratings and Certifications 5 Installations at Elevation 5 Component Locations 6 General Information 7
GENERAL SAFETY 8
Time/Temperature Relationships in Scalds 8
INSTALLATION 9
Installation Codes 9 Equipment Base 9 Clearances 9 Combustion and Ventilation Air 11 Conventional Combustion Air Supply 11 Water Piping 12 Hydronic Heating 14 Domestic Hot Water Piping 16 Gas Supply 17 Electrical Power Connections 18 Venting 21 Outdoor Installation 31
CONTROLS 32
Ignition Control Module 32 Outdoor Air Reset Temperature Controller (Standard for HD101-HD301 Type H) 32 Digital Temperature Control (Optional) 34 High Limit (Manual Reset) 34 High Limit — Auto Reset (Optional) 34 Flow Switch 35 High and Low Gas Pressure Switches (Optional) 35 Low Water Cut Off (Optional) 35
WIRING DIAGRAM—MODELS HD101–HD151 TYPE WH 36 WIRING DIAGRAM—MODELS HD101-HD151 TYPE H 37 WIRING DIAGRAM—MODELS HD201­HD401 TYPE WH 38 WIRING DIAGRAM—MODELS HD201-HD401 TYPE H 39 HD TROUBLESHOOTING 40 PRE-START-UP 41
Filling System-Heating Heaters 41 Domestic Hot Water Heaters 41 Inspect Venting System 41 Pre-Start-Up Check 41
INITIAL START-UP 41
Tools Needed 41 Preparation for Start-Up 41 Start-Up 42 Main Burner Adjustment 43 Gas Valve Adjustment 43 Gas Type Conversion on Valve 44 Safety Inspection 44 Follow-Up 44
POST START-UP CHECK 45
Air Filter Inspection/Removal 46 Heat Exchanger Removal 46
MAINTENANCE 47
Suggested Minimum Maintenance Schedule 47
APPENDIX 48
Inside Combustion Air Contamination 48 Important Instructions for the Commonwealth of Massachusetts 49
3
WARNINGS — Pay Attention to These Terms
DANGER:
WARNING:
CAUTION:
NOTE:
DANGER: Make sure the gas on which the heater
will operate is the same type as that specified on the heater rating plate.
WARNING: Should overheating occur or the gas supply valve fail to shut, do not turn off or disconnect the electrical supply to the heater. Instead, shut off the gas supply at a location external to the heater.
WARNING: Risk of electrical shock. More than one disconnect switch may be required to deenergize the equipment before servicing.
WARNING - CALIFORNIA PROPOSITION 65: This product contains chemicals known to the
State of California to cause cancer, birth defects or other reproductive harm.
WARNING: This unit contains refractory ceramic fiber (RCF) insulation in the combustion chamber. RCF, as manufactured, does not contain respirable crystalline silica. However, following sustained exposure to very high temperatures (>2192F), the RCF can transform into crystalline silica (cristabolite). The International Agency for Research on Cancer (IARC) has classified the inhalation of crystalline silica (cristabolite) as carcinogenic to humans.
When removing the burners or heat exchangers, take precautions to avoid creating airborne dust and avoid inhaling airborne fibers. When cleaning spills, use wet sweeping or High Efficiency Particulate Air (HEPA) filtered vacuum to minimize airborne dust. Use feasible engineering controls such as local exhaust ventilation or dust collecting systems to minimize airborne dust. Wear appropriate personal protective equipment including gloves, safety glasses with side shields, and appropriate NIOSH certified respiratory protection, to avoid inhalation of airborne dust and airborne fiber particles.
Indicates the presence of immediate hazards which will cause severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
WARNING: To minimize the possibility of improper operation, serious personal injury, fire, or damage to the heater:
• Always keep the area around the heater free of combustible materials, gasoline, and other flammable liquids and vapors.
Heater should never be covered or have any blockage to the flow of fresh air to the heater.
WARNING: Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
CAUTION: Operation of this heater in low­temperature systems requires special piping. Harmful internal condensation will occur if the inlet water temperature does not exceed 105°F. Warranty claims will be denied when condensation occurs.
CAUTION: If this heater is to be installed above radiation level, it must be provided with a low water cut-off device at the time of heater installation.
CAUTION: If this heater is to be installed in a negative or positive pressure equipment room, there are special installation requirements. Consult factory for details.
CAUTION: This heater requires forced water circulation when the burner is operating. See minimum and maximum flow rates. Severe damage will occur if the heater is operated without proper water flow circulation.
4
BEFORE INSTALLATION
Model Identification
Raypak strongly recommends that this manual be re­viewed thoroughly before installing your Hi Delta heater. Please review the General Safety information before installing the heater. Factory warranty does not
pply to heaters that have been improperly installed or
a operated (refer to the warranty at the back of this man­ual). Installation and service must be performed by a qualified installer, service agency or the gas supplier. If, after reviewing this manual, you still have questions which this manual does not answer, please contact your local Raypak representative or visit our website at www.raypak.com.
Thank you for purchasing a Raypak product. We hope you will be satisfied with the high quality and durability of our equipment.
Product Receipt
WARNING: Pump motors should NOT be
supported by any type of stand or support from above due to possible misalignment of pump and motor which may occur.
On receipt of your heater it is suggested that you visu­ally check for external damage to the shipping crate. If the crate is damaged, make a note to that effect on the Bill of Lading when signing for the shipment. Next, remove the heater from the shipping packaging. Report any damage to the carrier immediately.
On occasion, items are shipped loose. Be sure that you receive the correct number of packages as indi­cated on the Bill of Lading.
Claims for shortages and damages must be filed with the carrier by consignee. Permission to return goods must be received from the factory prior to shipping. Goods returned to the factory without an authorized Returned Goods Receipt number will not be accepted. All returned goods are subject to a restocking charge.
The model identification number and heater serial number are found on the heater data plate located on
he right side jacket of the heater. The model number
t will have the form H3-HD101 or similar depending on the heater size and configuration. The first character of the model number identifies application (H = Hydronic Heating System, WH = Hot Water Supply System). The second character identifies the firing mode (3 ­two stage firing, 4 - On/Off firing ). The next three places identify the size of the heater.
Ratings and Certifications
Standards:
Gas-Fired Low Pressure Steam and Hot Water Heaters, ANSI Z21-13 • CSA 4.9 - latest edition
Industrial and Commercial Gas-Fired Package Heaters, CAN 3.1 - latest edition
Gas Water Heaters, ANSI Z21.10.3 • CSA 4.3 - lat­est edition
All Raypak heaters are National Board Approved, and design-certified and tested by the Canadian Standards Association (CSA) for the U.S. and Canada. Each heater is constructed in accordance with Section IV of the American Society of Mechanical Engineers (ASME) Heater Pressure Vessel Code and bears the ASME stamp. The heater also complies with the latest edition of ASHRAE 90.1 Standard.
WARNING: Altering any Raypak pressure vessel by installing replacement heat exchangers, tube bundle headers, or any ASME parts not manufactured and/or approved by Raypak will instantly void the ASME and CSA ratings of the vessel and any Raypak warranty on the vessel. Altering the ASME or CSA ratings of the vessel also violates national, state, and local approval codes.
Installations at Elevation
When ordering parts, you must specify the model and serial number of the heater. When ordering under war­ranty conditions, you must also specify the date of installation.
Purchased parts are subject to replacement only under the manufacturer’s warranty. Debits for defec­tive replacement parts will not be accepted. Parts will be replaced in kind only per Raypak’s standard war­ranties.
Rated inputs are suitable for up to 2000 feet elevation without de-rate. Consult the Factory for installations at any altitude in excess of 2000 feet.
5
(BEHIND CONTROLLER)
CONTROLLER (OPTIONAL ON HD401)
Component Locations
Fig. 1: Component Locations — Angle View
Fig. 3: Component Locations — Front (Panels removed for clarity)
Fig. 2: Component Locations — Left Side
6
General Information
Model
No.
HD101 2 4
HD151 3 4
HD201 4 5
HD251 5 5
HD301 6 5
HD401 8 6
uantity of Burners
Q
Table A: Basic Data
Vent Size (in.)
Flue Intake
4
Fig. 4: Air Shutter Adjustment
Fig. 5: Gas Valves
7
GENERAL SAFETY
Water temperature over 125°F can c au se in s t an t s ev e r e b ur n s or de a t h from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
See instruction manual before set­ting temperature at water heater.
Feel water before bathing or show­ering.
Temperature limiting valves are available, see manual.
Water
Temp.
Time to Produce Serious
Burn
120°F More than 5 minutes
125°F 1-1/2 to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
145°F Less than 3 seconds
150°F About 1-1/2 seconds
155°F About 1 second
Table courtesy of The Shriners Burn Institute
To meet commercial hot water use needs, the high limit safety control on this water heater will shut off the main gas valve before the outlet temperature reaches 210°F. However, water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water, the rec­ommended initial setting for the temperature control is 125°F.
Safety and energy conservation are factors to be con­sidered when setting the water temperature on the thermostat. The most energy-efficient operation will result when the temperature setting is the lowest that satisfies the needs of the application.
Water temperature over 125°F can cause instant severe burns or death from scalds. Children, disabled and elderly are at highest risk of being scalded.
Feel water before bathing or showering.
Temperature limiting valves are available.
NOTE: When this water heater is supplying general purpose hot water for use by individuals, a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.
Maximum water temperatures occur just after the heater’s burner has shut off. To determine the water temperature being delivered, turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer.
Time/Temperature Relationships in Scalds
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
Table B: Time to Produce Serious Burn
8
Raypak offers several optional temperature controllers
ADJUSTMENT WHEEL
for regulation of the water temperature in the heater. Type H models 101 through 301 are equipped as stan­dard with an onboard operating controller to provide reset of the water temperature based on outdoor air temperature. To comply with safety regulations, the temperature controller will be set at the lowest setting when shipped from the factory.
Equipment Base
The heater should be mounted on a level, structurally
ound surface. The heater is approved for installation
s on a combustible surface but must NEVER be installed on carpeting. Gas-fueled equipment installed in enclosed parking garages must be located at least
8 in. above the floor.
1
To adjust the water temperature, insert a small straight screwdriver into the adjustment wheel on the front of temperature control and turn the wheel to the desired setting (See Fig. 6).
Fig. 6: Temperature Controller
CAUTION: Hotter water increases the risk of scald­ing! There is a hot water scald potential if the thermostat is set too high.
CAUTION: The heater should be located in an area where water leakage will not result in damage to the area adjacent to the appliance or to the structure. When such locations cannot be avoided, it is recommended that a suitable catch pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.
In addition, the heater shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation or service (circulator replacement, control replacement, etc.).
WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the Commonweatlh of Massachusetts.
Clearances
Indoor/Closet Installations
INSTALLATION
Installation Codes
Installations must follow these codes:
· Local, state, provincial, and national codes, laws, regulations and ordinances.
· National Fuel Gas Code, ANSI Z223.1- latest edi­tion (NFGC).
· National Electrical Code, ANSI/NFPA 70 - latest edition (NEC).
· Standard for Controls and Safety Devices for Automatically Fired Heaters, ANSI/ASME CSD-1, when required (CSD-1).
· For Canada only: CAN/CGA B149 Installation Code (B149) and C.S.A. C22. 1 C.E.C. Part 1 (C22. 1).
Heater Side
Front 24”
Rear 2”
Floor* 0”
Top 24”
Left** 12”
Right** 6”
Water Side 24”
*DO NOT install on carpeting. **When water connections are on other side.
Table C: Combustible Clearances — Indoor/Closet
Installations
9
Minimum Installed
Combustible Clearance
Fig. 7: Minimum Installed Service Clearances — Indoor/Closet Installations
CAUTION: Service clearances less than the minimums may require removal of the heater to service either the heat exchanger or the burners.
The heater must be installed in a manner that will enable the heater to be serviced without removing any structure around the heater.
Outdoor Installations
These heaters are design-certified for outdoor installa­tion. Heaters must not be installed under an overhang unless clearances are in accordance with local instal­lation codes and the requirements of the gas supplier. Three sides must be open in the area under the over-
hang. Roof water drainage must be diverted away from heaters installed under overhangs.
Heater Side
Minimum Installed Service Clearance
Front 24”
Rear 12”
Top Unobstructed
Other Side 36”
Water Side 36”
Table D: Service Clearances — Outdoor Installations
Fig. 8: Minimum Installed Service Clearance — Outdoor Installations
10
hese clearances are required when the outdoor
T vent cap is used. If installing the heater outdoors with a vent stack, the indoor clearances may be utilized.
The combustion air intake hood MUST be used for outdoor installations. The hood is shipped loose and installed on the side of the heater over the filter box at the job site.
Combustion and Ventilation Air
Combustion Air Filter
This heater is supplied with an integral combustion air filter. This filter will reduce the amount of particulates passed through the combustion system and heat exchanger but will not protect against chemical inside air contamination (See Appendix). The filter must be checked periodically to verify that adequate combus­tion air is being supplied to the heater. See the Maintenance section of this manual for information on checking the filter and establishing service intervals.
nput rating of all equipment in the room when the
i opening is communicating directly with the out­doors or through vertical duct(s). The total cross-sectional area shall be at least 1 in.
rea per 10,000 BTUH (222 mm
a input rating of all equipment in the room when the opening is communicating with the outdoors through horizontal duct(s). This opening must meet the location requirements of the National Fuel Gas Code.
3. In cold climates, and to mitigate potential freeze­up, Raypak highly recommends the installation of a motorized sealed damper to prevent the circula­tion of cold air through the heater during non-operating hours.
2
p
2
of free
er kW) of total
Conventional Combustion Air Supply
U.S. Installations
All Air from Inside the Building
Indoor Units
The heater must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation. Combustion air can be sup­plied via conventional means where combustion air is drawn from the area immediately surrounding the heater, or via direct vent, where combustion air is drawn directly from outside. All installations must com­ply with the requirements of the NFGC (U.S.) and B149 (Canada), and all local codes.
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty. (See the Appendix.)
Direct Combustion Air
If outside air is drawn through the intake pipe directly to the unit for combustion:
1. Install combustion air direct vent in accordance with the venting section of this manual.
2. Provide adequate ventilation of the space occu­pied by the heater(s) by an opening(s) for ventilation air at the highest practical point com­municating with the outdoors. The total cross-sectional area shall be at least 1 in. area per 20,000 BTUH (111 mm
2
per kW) of total
2
of free
The confined space shall be provided with TWO per­manent openings communicating directly with an additional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each open­ing shall have a minimum free area of 1 in.2 per 1,000 BTUH (22 cm² per kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 in.² (645 cm²). One opening shall commence within 6-3/4 in. of the top, and one opening shall commence within 6-3/4 in. of the bottom, of the enclosure. The minimum dimension of air openings shall be not less than 3 in. (8 cm) in any direction.
All Air from Outdoors
The confined space shall communicate with the out­doors in accordance with methods 1 or 2 below. The minimum dimension of air openings shall not be less than 3 in. (8 cm) in any direction. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
1. Two permanent openings, one commencing within 12 in. (30 cm) of the top, and one commenc­ing within 12 in. (30 cm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the out­doors or spaces (crawl or attic) that freely communicate with the outdoors.
11
a. Where directly communicating with the out-
doors or where communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in.2per 4000 BTUH (5.5 cm2per kW) of total input rat­ing of all equipment in the enclosure.
b. Where communicating with the outdoors
through horizontal ducts, each opening shall have a minimum free area of 1 in.2per 2000 BTUH (11 cm2per kW) of total input rating of all equipment in the enclosure.
2. One permanent opening, commencing within 12 in. (30 cm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (2.5 cm) from the sides and back and 6 in. (16 cm) from the front of the appliance. The opening shall directly communicate with the out­doors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum free area of:
a. 1 in.2per 3000 BTUH (7 cm2per kW) of the
total input rating of all equipment located in the enclosure, and
b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING: Do not use one permanent opening method if the equipment room is under negative pressure conditions or the equipment is common vented with other gas-fired appliances.
Installations in Canada
air flow from the outdoors for natural draft, partial fan assisted, fan-assisted or power draft-assisted burners, there shall be a permanent air supply opening(s) having a cross section area of not less than 1 in.2per 7000 BTUH (310 mm2per kW) up to and including 1 million BTUH, plus 1 in.2per 14000 BTUH (155 mm2per kW) in excess of 1 mil­lion BTUH. This opening(s) shall be either located at or ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (150 mm) above the floor level. The duct can also "Goose Neck" through the roof. The duct is preferred straight down 18” from floor, but do not place near piping. This air supply opening requirement shall be in addition to the air opening for ventilation air required in (1).
3. For heaters not using a barometric damper in the vent system, and when air supply is provided by natural air flow from outdoors for a power burner and there is no draft regulator, drafthood or similar flue gas dilution device installed in the same space, in addition to the opening for ventilation air required in (1), there shall be a permanent air sup­ply opening(s) having a total cross-sectional area of not less than 1 in.2for each 30,000 BTUH (70 mm2per kW) of total rated input of the burner(s), and the location of the opening(s) shall not inter­fere with the intended purpose of the opening(s) for ventilation air referred to (1). This opening(s) can be ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (150 mm) above the floor level. The duct can also "Goose Neck" through the roof. The duct is preferred to be straight down 18” from floor, but do not place near piping.
4. Refer to the latest version of the B149 for addition­al information.
CAUTION: All combustion air must be drawn from the air outside of the building; the mechanical equipment room must communicate directly with the outdoors.
1. Ventilation of the space occupied by the heater shall be provided by an opening(s) for ventilation air at the highest practical point communicating with outdoors. The total cross-sectional area of such an opening(s) shall be at least 10% of the area required in (2) and (3), but in no case shall the cross-sectional area be less than 10 in. mm2.).
2. For heaters using a barometric damper in the vent system, and when air supply is provided by natural
2
(6500
Water Piping
General
The heater should be located so that any water leaks will not cause damage to the adjacent area or struc-
tures.
CAUTION: This heater requires forced water circulation when the burner is operating. See Table E and Table F for minimum and maximum flow rates and water pump selection. The pump must be interlocked with the heater to prevent heater operation without water circulation.
12
Reversing Water Connections
Follow these instructions to change the water connec­tions from the left-hand side (standard) to the right-hand side. This is an ASME-Certified pressure
essel. It is the installer’s responsibility to ensure that
v the pressure vessel is properly sealed after making these changes.
1. Disconnect all electrical power from the heater (if applicable).
2. Label all electrical connections and conduit lines. This may include the flow switch, low water cut-off probe and/or pump.
3. Disconnect or isolate the main gas pipe from the heater (if applicable).
4. Remove both in/out and return header access panels by removing all sheet metal screws.
5. Remove all plumbing fittings to the header. This will include both inlet and outlet water pipe unions and the pressure relief valve and drain piping.
6. Remove limits, control bulbs and/or sensors.
7. Remove the six flange nuts and the in/out header from the left-hand side.
8. Remove the six flange nuts and the return header from the right-hand side.
9. Remove the header stud bolts from each tube sheet.
10. Reverse the headers and stud bolts to the new location.
Fig. 9: Torque Sequence
Relief Valve Piping
WARNING: Pressure relief valve discharge piping
must be piped near the floor and close to a drain to eliminate the potential of severe burns. Do not pipe to any area where freezing could occur. Refer to local codes.
11. Install NEW red beveled O-rings flush against both tube sheets with the bevel facing outward.
12. Push the header firmly against the O-rings. Install and tighten the flange nuts onto the stud bolts until finger tight.
13. Slowly tighten the flange nuts, starting from the center nut (number 1) in Fig. 9 and working sequentially around the header as indicated. Torque all nuts to 25 ft/lb. DO NOT OVER-TIGHT-
EN.
14. Re-route the capillary(s), wiring, etc., to the new location, adding thermal paste and shim to the capillary well.
13
Hydrostatic Test
Temperature & Pressure Gauge
Unlike many other types of heaters, Raypak heaters do not require hydrostatic testing prior to being placed in operation. The heat exchanger has already been
actory-tested and is rated for 160 PSI maximum oper-
f ating pressure. However, Raypak does recommend hydrostatically testing the piping connections to the heater and the rest of the system prior to operation. This is particularly true for hydronic systems using expensive glycol-based antifreeze. Raypak recom­mends conducting the hydrostatic test before connecting gas piping or electrical supply.
Leaks must be repaired at once to prevent damage to the heater. NEVER use petroleum-based stop-leak compounds.
1. Connect fill water supply. Fill heater with water (be sure bleed valve is open). When water flows from bleed valve, shut off water. Close bleed valve. Carefully fill the rest of the system, being sure to eliminate any entrapped air by using high point vents. Close feed valve. Test at standard operating pressure for at least 24 hours.
2. Make sure constant gauge pressure has been maintained throughout test.
The temperature and pressure gauge is shipped loose for field installation.
Hydronic Heating
System Design
Hot water heating systems all have unique levels of operating diversity. Raypak equipment design utilizes as little water mass as possible to ensure maximum operating efficiency. Primary / Secondary piping arrangement is the method recommended and the only method supported by Raypak for installation of Raypak heating equipment. Proper system design should always include system flow in excess of the connected boiler flow for proper operation (Boiler Flow + 15% = Min. System Flow). When appropriate, a Buffer/De-coupler Tank can be used where system flow may be reduced below the con­nected boiler flow. Failure to design for adequate system flow (i.e. bypasses, 3-way control valves, flow limiting balance devices, buffer tanks, etc.) will result in boiler short-cycling and poor system performance. Always contact your local Raypak representative for system design assistance to avoid these issues.
3. Check for leaks. Repair if found.
Low Temperature System
Heater requires minimum inlet temperature of 105°F. Consult the following sections for piping details.
Model
No.
HD101 100 85 17 1.3 13 0.7 14 44 8.8 4
HD151 150 128 26 3.0 13 0.7 13 0.7 20 44 8.8 6
HD201 199 169 34 5.3 17 1.3 13 3.4 27 44 8.9 8
HD251 250 213 44 9.2 21 2.1 14 1.0 13 0.7 34 44 9.2 10
HD301 299 254 25 3.1 17 1.4 13 0.8 40 44 9.4 12
HD401 399 335 34 5.6 22 2.5 17 1.4 40 44 9.8 15
*Flow switch will not activate at less than 12 gpm. NOTE: Basis for minimum flow — 13 gpm or 40°F ∆T maximum flow — gpm, except for header.
Input
MBTUH
Output
MBTUH
10°F T 20°F T 30°F T Min. Flow Max. Flow
gpm P (ft) gpm P (ft) gpm P (ft) gpm P (ft) T gpm P (ft) T
Pump Selection
In order to ensure proper performance of your boiler system, you must install a properly-sized pump. Raypak recommends using a 20°F ∆T as design ∆T. (∆T is the temperature difference between the inlet and outlet water when the heater is firing at full rate). If a ∆T other than 20°F is necessary, see Table E for flow rate requirements.
Table E: Heater Rates of Flow and Pressure Drops
14
Fig. 10: Single Boiler — Primary/Secondary Piping
*Maximum 4 times the pipe diameter or 12”, Max.
Fig. 11: Single Boiler — Low-Temperature Application (Heat Pump) Primary/Secondary Piping
*Maximum 4 times the pipe diameter or 12”, Max.
Fig. 12: Dual Boiler—Primary/Secondary Piping
15
Pressure Drop in Feet of Head Feedwater Regulator
Raypak recommends that a feedwater regulator be installed and set at 12 psi minimum pressure at the highest point of system. Install a check valve or back
low device upstream of the regulator, with a manual
f shut off valve as required by local codes.
Piping—Heating Boilers
All high points should be vented. Purge valves and a bypass valve should be installed. A boiler installed above radiation level must be provided with a low water cut-off device. The boiler, when used in connec­tion with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler.
System flow must always exceed boiler flow for proper operation. Raypak strongly recommends a minimum system flow of 115% of the boiler flow.
Air-Separation/Expansion Tank
All boilers should be equipped with a properly sized expansion tank and air separator fitting as shown in the piping diagrams (Fig. 10–13).
Three-Way Valves
Valves designed to blend water temperatures or reduce water circulation through the boiler should not be used. Raypak boilers are high recovery low mass boilers not subject to thermal shock. Raypak offers a full line of electric sequencers that produce direct reset of boiler water temperature. Refer to the Controls Section in our Complete Catalog.
The boiler piping system of a hot water heating boiler
Domestic Hot Water Piping
connected to heating coils located in air handling units where they may be exposed to circulating refrigerated air, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. It is highly recom­mended that the piping be insulated.
Model
No.
HD101 100 85 9 20 1.8 1-1/2 3.8 7 26 3.0 1-1/2 6.3 4 45 9.2 1-1/2 18.0
HD151 150 128 13 20 1.8 1-1/2 3.8 10 26 3.1 1-1/2 6.3 6 45 9.2 1-1/2 18.1
HD201 199 169 17 20 1.9 1-1/2 3.9 13 26 3.2 1-1/2 6.4 8 45 9.4 1-1/2 18.2
HD251 250 213 21 20 1.9 1-1/2 3.9 16 26 3.2 1-1/2 6.5 9 45 9.6 1-1/2 18.5
HD301 299 254 25 20 1.9 1-1/2 3.9 20 26 3.2 1-1/2 6.5 11 45 9.8 1-1/2 18.7
HD401 399 339 34 20 2.0 1-1/2 4.0 26 26 3.3 1-1/2 6.6 15 45 10.3 1-1/2 19.1
∆T = Temperature rise, °F. ∆P = Pressure drop through heat exchanger, ft. SHL = System head loss, ft. (System head loss is based on the heater and tank placed no more than 5 feet apart and 50 feet equivalent length of tubing and fittings.) gpm = Gallons per minute, flow rate. MTS = Minimum tubing size. *Must utilize optional cupro-nickel tubes. **With Hard Water (16-25 grains per gallon), the operating control must be set no higher than 130°F for scale free operation. For operating tem­peratures above 130°F, a water softener must be utilized.
Input
MBTUH
Output
MBTUH
Soft (0–4 grains per gallon) Medium (5–15 grains per gallon) Hard* (16–25** grains per gallon)
T gpm P MTS SHL T gpm P MTS SHL T gpm P MTS SHL
When designing the water piping system for domestic water applications, water hardness should be consid­ered. Table F indicates the suggested flow rates for soft, medium and hard water. Hardness is specified as grains per gallon.
Table F: Domestic Water Heater Flow Rate Requirements
16
Loading...
+ 36 hidden pages