Rane CP 64 User Manual

CP 64
RMT
BOTH
Z1 Z2
L1 P
L2 L3
RMT
BOTH
Z1 Z2
ZONE 1 ZONE 2
ZONE ASSIGN LEVEL
L1 P
L2 L3
4k630 1.6k40 100 250
10k
4k630 1.6k40 100 250
10k
CP 64
ACTIVEACTIVE
PAGE 1 PAGE 2
ONOFF
SIGRMT OL
DUCKER
SELECT
PROGRAM
DEPTH
LINE 1 LINE 2 LINE 3 PRIORITY LEVEL
ONOFF
SIGRMT OL
DUCKER
SELECT
PROGRAM
DEPTH
LEVEL
PROGRAM INPUT LEVELS ZONE 1 ZONE 1ZONE 2 ZONE 2
POWER
100
2
4
8
6
100
2
4
8
6
100
2
4
8
6
100
2
4
8
6
100
2
4
8
6
100
2
4
8
6
10
2
4
8
6
10
2
4
8
6
12
•6•••
6120
+
12
•6•••
6120
+
COMMERCIAL
PROCESSOR
COMMERCIAL PROCESSOR
IMPORTANT SAFETY INSTRUCTIONS
For the continued safety of yourself and others we recommend that you read the following safety and installation instructions. Keep this document in a safe location for future reference. Please heed all warnings and follow all instructions.
Do not use this equipment in a location where it might become wet. Clean only with a damp cloth.
is equipment may be installed in an industry standard equipment rack. We recommend that all mounting holes be used, providing the best physical support. e equipment may be used as a table top device, although stacking of the equipment is dangerous and not recommended.
Do not directly block any of the ventilation openings. If rackmounting, please provide adequate ventilation. Equipment may be located directly above or below this unit, but note that some equipment (like large power amplifiers) may cause an unacceptable amount of hum or may generate too much heat and degrade the performance of this equipment.
Protect the power cord and plug from damage caused by being walked on or pinched. Protect the line cord, where it exits the unit, from excessive strain. Only use attachments and acces­sories specified by Rane.
Unplug this equipment during lightning storms or when unused for long periods of time.
Refer all servicing to qualified service personnel. Servicing is required when the apparatus has been damaged in any way, such as power supply cord or plug damage, spilled liquid, fallen objects into an opened chassis, exposure to rain or moisture, a dropped unit, or abnormal operation.
108366
OPERATORS MANUAL CP 64
RMT
BOTH
Z1 Z2
L1 P
L2 L3
RMT
BOTH
Z1 Z2
ZONE 1 ZONE 2
PAGING
ZONE ASSIGN LEVEL
L1 P
L2 L3
4k630 1.6k40 100 250
10k
4k630 1.6k40 100 250
10k
CP 64
ACTIVEACTIVE
PAGE 1 PAGE
2
ONOFF
SIGRMT OL
DUCKER
SELECT
PROGRAM
DEPTH
LINE 1 LINE 2 LINE 3 PRIORITY LEVEL
ONOFF
SIGRMT OL
DUCKER
SELECT
PROGRAM
DEPTH
LEVEL
PROGRAM INPUT LEVELS ZONE 1 ZONE 1ZONE 2 ZONE 2
POWER
100
248
6
100
248
6
100
248
6
100
248
6
100
248
6
100
248
6
10
248
6
10
248
6
12
6
6
12
0
+
12
6
6
12
0
+
COMMERCIAL
PROCESSOR
QUICK START
If you were the type that cheated on school book reports by just skimming through the reading assignments, then this section is for you! It gives you not quite enough information to really know what you’re doing. But, if you follow the recom­mended set up procedure, you should get at least a “B.”
Keep the amplifiers and the CP 64 turned off until all connec­tions are made.
INTERNAL SETTINGS: Access to the following internal controls requires removal of the top cover. All internal settings should be complete before you install the CP 64. e factory default settings work for many applications. However, you may need to change one or more for your system. See the INTERNAL
ADJUSTMENTS description on page Manual-8 for more details
• Each Page Input has a 15 volt Phantom Power switch. e
default is off
• e Page Priority switch assigns priority override to Page
1, Page 2 or NO (none). e default is Page 1. If a Page has priority, it overrides the non-priority Page in the Zone(s) it is assigned. e NO priority setting allows the Pagers to mix.
• Each Page Input may sum with the Program Pre- or Post-
VCA. When set to Pre-VCA, Zone Level, EQ and Limiter circuits act upon the Page. When summed Post-VCA, the Page is not influenced by Zone Level, EQ or Limiter circuits. e default is Pre-VCA.
• e Zone 1 Stereo/Mono switch default is Stereo.
• ere are two internal trim controls for the Program Priority
detector. e Program Priority reshold trim has a range of
-∞ to -35 dBu with a default of -50 dBu. e Program Priority Release Time has a range of 2 to 20 seconds. e default is 12 seconds.
PAGE INPUTS: Connect Page Inputs to the Euroblock on the rear panel and select the appropriate MIC or LINE switch position for each. First, set the gain with the Page TRIM con trol, then set the Page DETECT THRESHOLD and finally the Page Zone LEVEL.
PR 2 REMOTE: If you use the optional PR 2 remote (sold separately), wire it to the rear RMT ZONE ASSIGN Euroblock
.
-
COMMERCIAL PROCESSOR
as indicated. If you require remote control but do not wish to use a PR 2, any simple switch closure to GND will work. ese inputs are also TTL compatible (0 to 5 VDC). See wiring details on pages Manual 5-6.
PROGRAM INPUTS: Connect Program sources to the RCA PROGRAM INPUTS. If you have a priority program, like a jukebox, connect it to the PRIORITY Input. e Pro gram PRIORITY ASSIGN switch assigns priority override to Off, Zone 1, Zone 2, or Both. In the Zone(s) that it is assigned, the priority program is automatically selected when signal is detected.
EXPAND OUTPUTS: Wire the EXPAND OUTPUT Eu roblock for each Zone as required. ese are cross-coupled line drivers and may be used balanced or unbalanced. Each Expand Output can be Page-only, Program-only or its Zone signal. e Zone source will not include the Page if the Page is summed Post­VCA. Page is always available from the Page source.
ZONE OUTPUTS: Wire the two ZONE OUT Euroblocks as required. ese are cross-coupled line drivers and may be used balanced or unbalanced. Set the LIMIT threshold as required.
ZR 1 REMOTE: You may use one or two ZR 1 Remotes with each CP 64. If you use the optional ZR 1 remote (sold sepa rately), wire it to the rear REMOTES Euroblock as indicated. If a ZR 1 remote is not used, any simple switch closure to ground will work for the D0 and D1 pins. ese pins are TTL compat­ible (0 to 5 VDC). e logic is inverse Gray Code. Any ground referenced 5 volt DC control may be used as the input to V1 or V2. Do not ground the Vr1 or Vr2 pins. See wiring details on pages
Manual 5-6.
e CP 64 is very versatile. While this makes a large number of system applications possible, it also results in complexity. For this reason, it is important to use an organized approach for setup
and calibration.
A highly recommended setup procedure appears
on page Manual-7. By following it you will encounter fewer prob­lems and reduce the need to increase our collective phone bills.
-
-
-
WEAR PARTS: is product contains no wear parts.
Manual-1
Loading...
+ 7 hidden pages