Quadra-Fire DV400S User Manual

DV400S
O-T L
Tested and
Listed by
Beaverton
Oregon USA
OMNI-Test Laboratories, Inc.
C
A Division of Hearth Technologies Inc.
R
DIRECT VENT ROOM HEATER
OWNER’S MANUAL
AND INSTALLATION INSTRUCTIONS
WARNING!
If the information in this manual is not followed exactly, a fire or explosion may result causing property dam­age, personal injury or loss of life.
-Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
-WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
-Installation and service must be performed by a qualified installer,
service agency or the gas supplier.
WARNING!
Improper installation, adjustment, alteration, service or maintenance can cause injury or property dam­age. Refer to this manual. For assistance or addi­tional information, consult a qualified installer, ser­vice agency or the gas supplier.
FOR YOUR SAFETY
The appliance area must be kept clear and free from com­bustible materials, gasoline and other flammable vapors and liquids.
This manual must be used for installation of the DV400S Direct Vent Heater and retained by the homeowner for operating and maintenance instructions. This heater may be installed with a vertical or horizontal direct vent terminator system.
1445 North HIghway
Colville, WA 99114
#30211C March 4, 2002
This appliance may be installed in an aftermarket, permanently located, Manufactured (Mobile) Home, where not prohibited by Local Codes.
This appliance is only for use with the type of fuel indicated on the Rating Plate. This appliance is not convertible for use with other gases, unless a certi­fied Conversion Kit is used.
aladdin@aladdinhearth.com
DV400S DIRECT VENT ROOM HEATER
R
Aladdin Hearth Products welcomes you to our tradition of excellence! In choosing a Quadra-Fire appliance, you have our assurance of commitment to quality, durability, and performance.
This commitment begins with our research of the market, including ‘Voice of the Customer’ contacts, ensuring we make products that will satisfy your needs. Our Research and Development facility then employs the world’s most advanced technology to achieve the optimum operation of our stoves, inserts and fireplaces. And yet we are old­fashioned when it comes to craftsmanship. During manufacturing each unit is meticulously fabricated and gold surfaces are hand-finished for lasting beauty and enjoyment. Our pledge to quality is completed as each model undergoes a quality control inspection. Additionally, we feel it is important to offer you several finishing options and accessories to compliment your home’s décor, individualize the use of your appliance, and provide financial options in acquiring a quality hearth appliance. Ask your Quadra-Fire Dealer for information on these options. From design, to fabrication, to shipping; our guarantee of quality is more than a word, it’s Quadra-Fire tradition, and we proudly back this tradition with a Lifetime Warranty.
Prior to installation, we ask you to take a few moments to read this manual. It has been our experience that your overall enjoyment of your new appliance will be greatly enhanced by becoming familiar with its installation, operation and maintenance requirements. We wish you and your family many years of enjoyment in the warmth and comfort of your hearth appliance. Thank you for choosing Quadra-Fire.
With warm regards,
______________________  Group Vice President
_______________________  Controller
_______________________  Manufacturing Engineer  Manager
_______________________ Order Fulfillment Manager
______________________  Vice President Research & Development
______________________  General Manager
_______________________  Central Sales Manager
_______________________  Sr. Purchasing Agent
_____________________  Vice President Marketing & Product Planning
______________________  Quality / Technical  Support Manager
______________________ Eastern Sales Manager
______________________  Human Resources &  Community Relations
March 4, 2002 Page 2 30211C
DV400S DIRECT VENT ROOM HEATER
R
OWNER'S NOTES:
Important!
Complete now for future reference.
MODELNAME DV400S
Serial Number
Located on the Ratings Label on back of unit.
Date Purchased
Dealership Where Purchased
Dealer Phone
Table of Contents
Safety Precautions 4
Listings and Code Approvals 5
Ratings Label 5
Description of the DV400S Room Heater 6
Heater System Components 7
Clearances 8
Termination 9
A. Horizontal Termination 10-13
B. Vertical Termination 14-16
C. Existing Masonry Chimney Installation 16-17
D. Existing Class A Metal Chimney
Additional Information:
After completing your warranty card, attach your sales receipt and warranty stub here for future reference.
Installation 17-18
Gas Line Installation 19
Gas Pressure 19
Field Fuel Conversion 19
High Altitude Conversion 20
Optional Accessories 21-22
Firebox Entry 23-24
Lighting Instructions 25-26
Maintenance Instructions 27
Trouble Shooting 28-29
Replacement Parts 29
Lifetime Warranty 30
March 4, 2002 Page 3 30211C
DV400S DIRECT VENT ROOM HEATER
R
PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE.
Safety Precautions
1. PLEASE READ THESE INSTALLATION INSTRUCTIONS COMPLETELY BEFORE BEGINNING INSTALLATION PROCEDURES.
FAILURE TO FOLLOW THEM COULD CAUSE AN APPLIANCE MALFUNCTION RESULTING IN SERIOUS INJURY AND/OR
PROPERTY DAMAGE.
2. DUE TO HIGH TEMPERATURES THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE
AND DRAPERIES.
3. CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES AND SHOULD STAY
AWAY TO AVOID BURNS OR CLOTHING IGNITION.
4. YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
5. CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
6. ANY SAFETY SCREEN OR GUARD REMOVED FOR SERVICING AN APPLIANCE MUST BE REPLACED PRIOR TO OPERATING
THE APPLIANCE.
7. WARNING: DO NOT OPERATE APPLIANCE WITH THE PANEL(S) REMOVED, CRACKED OR BROKEN. REPLACEMENT OF THE
PANEL(S) SHOULD BE DONE BY A LICENSED OR QUALIFIED SERVICE PERSON.
8. INSTALLATION AND REPAIR SHOULD BE DONE BY A QUALIFIED SERVICE PERSON. THE APPLIANCE SHOULD BE
INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A QUALIFIED SERVICE PERSON. MORE FREQUENT CLEANING
MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
9. ENSURE THAT THE FLOW OF COMBUSTION AND VENTILATION AIR NOT BE OBSTRUCTED.
10. ENSURE THAT ADEQUATE COMBUSTION AND VENTILATION AIR ARE PROVIDED.
NOTE: Illustrations throughout these instructions reflect typical installations and are for design purposes only. Actual installation may vary slightly due to individual design preferences. However, minimum and maximum clearances must be maintained at all times.
The illustrations and diagrams used throughout these installation instructions are not drawn to scale.
March 4, 2002 Page 4 30211C
DV400S DIRECT VENT ROOM HEATER
R
DO NOT REMOVE THIS LABEL /
NE PAS ENLEVER L’ÉTIQUETTE
Made in U.S.A. /
Fait Aux États-Unis
Keep burner and control compartment clean. See installation and operating instructions accompanying this appliance. Gardez le brûleur et le compartiment de contrôle propres. Vérifiez les instructions d’installation et d’opération qui accompagnent cet appareil. This vented gas fireplace heater is not for use with air filters. / Cet appareil de chauffage au gaz n’est pas pour l’usage avec des filtres d’air
MODEL / MODELE: DV400S VENTED GAS FIREPLACE HEATER
FOURNAISE AU GAZ AVEC VENTILATION
NOT FOR USE WITH SOLID FUEL /
NE PAS UTILISER AVEC LE COMBUSTIBLE SOLIDE
SERIAL NO.
A Division of Hearth Technologies Inc.
1445 North Highway Colville,
WA 99114
O-T L
Listed by
Beaverton
Oregon USA
OMNI-Test Laboratories, Inc.
C
Report No. / Rapport Numero
061-S-22-4
APPROVED FOR CANADA AND USA TO: ANSI Z21.88-1998 / CSA 2.33-M98 Vented Gas Fireplace Heaters, and applicable sections of UL307b Gas Burning Heating Appliances for Manufactured Homes and Recreational Vehicles, CAN/CGA 2.17-M91 “Gas Fired Appliances for use at High Altitudes.” This appliance is manufactured for operation with Natural Gas. For conversion to propane Manufacturer’s Part #844-8230 and instructions must be used. This appliance may be installed in a bedroom or bedsitting room; in Canada remote thermostat installation is required. APPROUVÉ POUR LE CANADA ET LES ÉTATS-UNIS: ANSI Z21.88-1998 / CSA 2.33-M98 Fournaises au Gaz avec Ventilation, et les sections applicables de UL 307b Appareils de Chauffage Au Gaz pour les Maisons Mobiles et les Véhicules Motorisés, CAN/CGA 2.17-M91 “Gas Fired Appliances for use at High Altitudes”. Cet appareil est manufacturé pour l’opération avec le Gaz Naturel. Pour une conversion au gaz propane les pièces du Manufacturier #844-8240 et ses instructions doivent être utilisées. Cet appareil peut être utilisé dans une chambre à coucher ou salle de séjour; au Canada, l’installation d’un thermostat à distance est exigée.
FAN TYPE VENTED CIRCULATOR / VENTILATEUR CIRCULATOIRE Opt. Blower Part #844-0150
Blower Electrical Rating / Évaluation du Ventilateur Électrique: 115 V., 1.5 Amps, 60 Hz, 150 Watts
Thermal Efficiency / Efficacité Thermique 77% NG
This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mobile) home where not prohibited by local codes. See owner's manual for details. This appliance is not convertible for use with other gases, unless a certified kit is used. Cet appareil doit etre utilise uniquement avec le type de gaz indique sur la plaque signaletique et peut etre installe dans une maison prefabriquee (mobile) installee a demeure si les reglements locaux le permettent. Voir la notice du proprietaire pour plus de details. Cet appareil ne peut etre converti a d'autres gaz sauf si une trousse de conversion certifiee est utilisee. This appliance must be properly connected to a venting system in accordance with the manufacturer's installation instructions. If venting is disconnected for any reason, the vent-air intake system must be properly resealed and reinstalled. Cet appareil doit ê correctement raccordé á un système d'évacuation, conformément aux instructions du fabricant.
For use with Natural Gas For use with Propane  Usage Au Gaz Naturel Usage Au Gaz Propane  0-4500’ 0-4500’ Input Rate on “HI” (BTU/Hr) 29,500 28,500 Puissance Évaluée à “HI” (BTU/Hr) Input Rate on “LO” (BTU/Hr) 19,500 24,000 Puissance Évaluée à “LO” (BTU/Hr) Maximum Output (BTU/Hr) 22,700 22,500 Puissance Maximum (BTU/Hr) Main Burner Orifice  .106/2.69 DIA./mm .063/1.60 DIA./mm Orifice du Brûleur Principal
Minimum Inlet Pressure (Inches W.C.) 4.5” 11” Pression Minimum de la Valve (pouces W.C.) Maximum Inlet Pressure (Inches W.C.) 7.0” 14” Pression Maximum de la Valve (pouces W.C.) Manifold Pressure on “HI” (Inches W.C.) 3.5” 10” Pression du Collecteur d’ Échappement à “HI” (pouces W.C.)
Date of Manufacture / Date du Manufacturier
2001 2002 2003 Feb Mar Apr May Jun Jul Aug Sep Oct Nov DecJan
This appliance equipped for altitudes 0-2000’ (0-610m) in USA; and in Canada for altitudes of 0-4500’ (0-1370m). In USA for Altitudes above 2000’, the vent configuration, orifice, or combination of both may need to be changed. See Owner’s Manual for information on making these changes. Cet appareil est équipé pour les altitudes de 0-2000’ (0-610m) aux États-Unis; et au Canada pour les altitudes de 0-4500’ (0-1370m). Pour les altitudes au dessus de 2000’ aux États-Unis, la configuration du ventilateur, son orifice ou les deux peuvent possiblement avoir à être changé. Voyez le manuel du propriétaire pour les informations sur ces changements. This appliance must be installed in accordance with local codes, if any; if none, follow ANSI Z223.1 in USA, CAN 1-B149 in Canada.
250-5911
LISTING & CODE APPROVALS
U.S. CERTIFICATION
The DV400S Series Room Heater has been tested in accordance with the ANSI standard Z21.88 1998 and UL307B and has been listed by OMNI­Test Labs for installation and operation as described in these installation and operation instructions. All components are A.G.A. or UL safety certified.
Canada Certification
The DV400S Series Room Heater has been tested in accordance with CSA 2.33-M98 and has been listed by OMNI-Test Labs for installation and operation as described in these installation and operating instructions. All components are C.G. A. or C.S.A. safety certified.
This Heater is approved for installation in bedrooms and mobile homes in the United States and Canada.
Local Codes
This installatin must conform with local codes or, in the absence of local codes, with theNational Fuel Gas Code, ANSI Z223.1-latest edition, in the U.S.A. and the CAN/CGA B149-latest edition, in Canada.
Efficiency
The efficiency rating of the appliance is a product thermal efficiency rating determined under continuous operating conditions and was determined independently of any installed system.
SERIAL/RATING LABEL
March 4, 2002 Page 5 30211C
DV400S DIRECT VENT ROOM HEATER
R
VENT SECTION
VENT SECTION
VENT SECTION
90û ELBOW
ROUND SUPPORT BOX/WALL THIMBLE
HORIZONTAL TERMINATION CAP
VERTICAL TERMINATION CAP
STORM COLLAR
FLASHING
FIRESTOP SPACER
ROUND SUPPORT BOX/WALL THIMBLE
CATHEDRAL CEILING SUPPORT BOX
DESCRIPTION OF THE HEATER SYSTEM
The DV400S is a Direct Vent Room Heater. Combustion air is supplied from outside, not from inside the house as with other types of heaters. TYPICAL ASSEMBLY The installation of this Quadra-Fire DV400S system consists of the following:
1. Appliance
2. Venting System
3. Termination
Optional Components include:
1. Blower Kit
2. Decorative Glass Accent
3. Warming Shelf
4. Remote Control
NOTE: Operation of a Direct Vent Heater may be sporadic in high wind situations.
DV400S - With Optional BK95 DV400S Front View
March 4, 2002 Page 6 30211C
DV400S DIRECT VENT ROOM HEATER
R
HEATER SYSTEM COMPONENTS
839-0710 DV400S, Matte Black, NG 844-0150 Fan Kit, BK95, Var. Speed, Thermostat “ON/OFF” 844-0140 Decorative Glass accent - gold, DT6G 844-7850 Warming Shelf, Matte Black (pr.) 844-7950 Warming Shelf Bracket - w/mitten rod, Black (pr.) 844-7960 Warming Shelf Bracket - w/mitten rod, Gold (pr.) 844-8230 LP Conversion Kit, SPCK400S 844-8240 NG Conversion Kit, SNCK400S
SECURITY CHIMNEY'S SECURE VENT CHIMNEY SYSTEM
Your Quadra-Fire DV400S has been approved with Security Chimney's Secure Vent Chimney System. Please contact your local dealer and they will advise you of the required parts needed for your installation. All the required certification tests have been successfully completed with OMNI-Test Laboratories, Inc.
SIMPSON DURA-VENT PARTS LIST
Termination Caps & Snorkels:
991 High Wind Vertical Termination Cap 986 High Wind Horizontal Termination Cap 980 Vertical Termination Cap w/Wind Halo 983 Vertical Termination 984 Horizontal Termination Cap 981 Snorkel Termination (36”) 982 Snorkel Termination (14”) 950 Vinyl Siding Standoff
Flashing:
941 Cathedral Ceiling Support Box 943 Flashing, 0/12 to 6/12 Roof Pitch 943S Flashing, 7/12 to 12/12 Roof Pitch 943F Flashing, Flat Roof
Support Boxes/Thimbles:
940 Round Ceiling Support/ Wall Thimble Cover 941 Cathedral Ceiling Support Box
Pipe:
908 6” Pipe Length, Galv. 908B 6” Pipe Length, Black 907 9” Pipe Length, Galv 907B 9” Pipe Length, Black 906 12” Pipe Length, Galv. 906B 12” Pipe Length, Black 904 24” Pipe Length, Galv. 904B 24” Pipe Length, Black 903 36” Pipe Length, Galv. 903B 36” Pipe Length, Black 902 48” Pipe Length, Galv. 902B 48” Pipe Length, Black 911 11” -14 5/8” Pipe, Adj. Glv. 911B 11” -14 5/8” Pipe, Adj. Blk. 912 12” - 17” Pipe, Adj. Glv. 912B 12” - 17” Pipe, Adj. Blk
Pipe cont'd
917 17” -24” Pipe, Adj. Glav. 917B 17” -24” Pipe, Adj.Blk. 945 45° Elbow, Galv.
945B 45° Elbow, Black 990 90° Elbow, Galv. 990B 90° Elbow, Black
Misc.
953 Storm Collar 963 Ceiling Firestop 988 Wall Strap 9546 Attic Insulation Shield 942 Wall Thimble/Cathedral Ceiling Collar
SDV KITS
970A Standard Termination Kit includes 1 each of:“ 990B, 940, & 985 See Note #1 below. 971HW Standard Termination Kit includes 1 each of:“990B, 940, 985, 904B, 911B 973 Vertical Termination Kit includes 1 each of:“943, 953, 991 (support box NOT included)
Note #1: Straight pipe lenghts are needed to complete installation, the black 45° elbow is NOT included in kit.
The following venting parts are available from your Dealer:
HHW2 Horizontal High Wind Cap HHW2K Horizontal Kit includes 90° Black Elbow, Wall Thimble, 24" Black Pipe, 11" - 14
5/8" Adjustable Vent, HHW2 Termination Cap.
The VTA1, Vertical Termination Adapter Kit, may also be safely used with this Heater. It is composed of a Vertical Termination Cap and Cover Plate for existing vertical chimney.
March 4, 2002 Page 7 30211C
DV400S DIRECT VENT ROOM HEATER
R
S
T
O
V
E
STOVE
6"
6"
6"
6"
48"
MAX.
4"
4"
STOVE
HEARTH PROTECTION IS NOT
NECESSARY ON THIS GAS HEATER.
DURA-VENT GS VENTING SYSTEM COMPONENTS CATALOG # DESCRIPTION
953 Storm Collar 963 Firestop Spacer 988 Wall Strap 981 Snorkel Termination (36") 982 Snorkel Termination (14") 971 Horizontal Kit (Horizontal Termination Cap, One 90 Degree Black Elbow, Wall Thimble, 24" Black Pipe, 11" - 14 5/8" Adjustable Vent 980 Vertical Termination Cap with Wind Halo 984 Horizontal Termination Cap 909B Retrofit Adjustable Chimney Connector Retrofit Chimney Connector Plate 950 VSS - Vinyl Siding Standoff/Shield 3951 Round Ceiling Support/Wall Thimble Trim Kit, Polished Brass 3960 Cathedral Ceiling Support Trim Kit, Polished Brass HHW2 Horizontal High Wind Cap (recommended for optimal performance) HHW2K Horizontal Kit (One 90 degree Elbow, Wall Thimble, 24" Black Pipe, 11" - 14 5/8" Adjustable Vent, HHW2 Termination Cap.
CLEARANCES
The following clearances to combustibles must be main­tained:
Minimum clearances to the floor - 0"
Back of unit to wall - 6”
Sides of unit to wall - 6
Base of the unit to ceiling - 72".
Minimum clearances to Venting are as follows:
Horizontal runs require a 1-1/2” minimum Air Space on the top and an 1/2” minimum Air Space on the sides and bottom of the outer Vent Section. If an Elbow is being used,in an enclosed wall, floor or ceiling, a top Air Space clearance of 3” must be maintained. Vertical rise sections require a 1” minimum Air Space completely around the Vent section. These clearances must be maintained at all times.
This appliance is certified for installation in a bed/sitting room in the U.S. and Canada.
Mobile Home Installations. Appliances installed in Mobile Homes must be secured to the floor in a minimum of two locations.
Positioning the Appliance.
This appliance may be placed on a combustible or non-combus­tible continuous, flat surface. When the appliance is installed directly on carpeting, tile or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance. Slide the Heater into position and level the Heater from side-to-side and front-to-back. Shim as necessary.
Figure 1
Minimum Clearances To Combustibles
March 4, 2002 Page 8 30211C
DV400S DIRECT VENT ROOM HEATER
R
TERMINATION
Four types of Termination are possible for this Heater: Horizontal, Vertical, Existing Masonry or Existing Class A
Class A Metal Chimney
Vertical Flat Ceiling
Cathedral Ceiling
Horizontal Termination
COMMON INSTALLATIONS
March 4, 2002 Page 9 30211C
R
16'
MAX.
15' MAX.
VENTING CAN ONLY TERMINATE WITHIN THIS AREA.
2'
MIN.
10' MAX.
15" MIN.
4'
29"
591/2"*
* MINIMUM VENT HEIGHT (CENTER) (SEE NOTE)
15' MAX. HORIZONTAL RUN
2' 3' 4' 5' 6' 7' 8' 9' 10' 11' 12' 13' 14' 15'
16'
Thru
4'
3'
2'
X
X
XXX
X
X X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X X X
X X X X X
X
X
X X X X X
X
X
X
X
X
X
X
X
X
X
V E R T I C A L
R I S E
A. Horizontal Termination
DV400S DIRECT VENT ROOM HEATER
Refer to Chart A and Figure 2 for horizontal venting recommendations. The minimum vertical rise allowed for horizontal termination is 2" from the top of the
Note: Horizontal runs will require the use of one vent support for every 3' of vent.
heater. The maximum horizontal run allowed for venting is 15' with a minimum 4' rise.
A single vertical to horizontal elbow is already calculated into the allowable 15' run. Each additional elbow reduces the maximum horizontal distance by 3' feet.
Example: When using three elbows, the maximum horizontal distance has been reduced to 9' (3 - 1 = 2 elbows x 3' = 6'; 15' max. - 6' of elbows = 9' of horizontal run.) Even with only these three elbows ( the equivalent of 6' additional horizontal feet) you now need a minimum of 4' of vertical rise. See Chart A.
If a vertical - to - horizontal elbow is enclosed within a wall, floor or ceiling, an air space clearance of 3" must be maintained.
Due to the many different combinations that can be used when constructing venting, the number of vent sections required can only be determined by the installer.
Horizontal venting must terminate within the shaded area shown in Fig. 2. Chart
CHART A - Venting Combinations
Note: A horizontal run of vent must have a 1/4" rise for every 1 ft. of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and the possibility of a fire.
A illustrates the figures included in that shaded area. For example, if your vertical rise is the minimum two feet, venting can terminate anywhere between 20 - 1/2" (includes wall thickness and assumes 4", and venting required to termination cap) and 10' feet.
Venting termination must not be recessed into the wall or siding. Fig 3 on Page 9 illustrates termination cap location and minimum dimensions for each termination application. Or follow ANSI Z223.1, latest edition.
March 4, 2002 Page 10 30211C
Fig. 2 - Horizontal Lenth