• Important operating and
maintenance instructions
included.
WARNING: If the information in these
instructions is not followed exactly, a fi re
or explosion may result causing property
damage, personal injury, or death.
• Do not store or use gasoline or other fl am-
mable vapors and liquids in the vicinity of this
or any other appliance.
• What to do if you smell gas
- Do not try to light any appliance.
Do not touch any electrical switch. Do not
use any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’ s
instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed
by a qualifi ed installer, service agency , or the
gas supplier.
Installation and service of this appliance should be
performed by qualifi ed personnel. Hearth & Home
T echnologies suggests NFI certifi ed or factory-trained
professionals, or technicians supervised by an NFI
certifi ed professional.
• Read, understand and
follow these instructions
for safe installation and
operation.
DO NOT
DISCARD
• Leave this manual with
party responsible for use
and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• Do not touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fi replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable
materials.
• Keep clothing, furniture, draperies and other fl ammable
materials away.
In the Commonwealth of Massachusetts:
• installation must be performed by a licensed plumber or gas
fi tter.
See Table of Contents for additional Commonwealth of Massachusetts requirements.
This appliance may be installed as an OEM installation in manufactured
home (USA only) or mobile home and must be installed in accordance
with the manufacturer's instructions and the manufactured home construction and safety standard, Title 24 CFR, Part 3280 or Standard for
Installation in Mobile Homes, CAN/CSA Z240MH.
This appliance is only for use with the type(s) of gas indicated on
the rating plate.
Page 1
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
and Welcome to the Quadra-Fire Family!
SAMPLE
Hearth & Home Technologies welcomes you to our tradition
of excellence! In choosing a Quadra-Fire appliance, you
have our assurance of commitment to quality , durability, and
performance.
This commitment begins with our research of the market,
including ‘Voice of the Customer’ contacts, ensuring we
make products that will satisfy your needs. Our Research
and Development facility then employs the world’s most
advanced technology to achieve the optimum operation of
our stoves, inserts and fi replaces. And yet we are old-fash-
ioned when it comes to craftsmanship. Each appliance is
SAMPLE OF SERIAL NUMBER / SAFETY LABEL
LOCATION: ON BACK OF APPLIANCE
MODEL / MODÈLE:
COLUMBIA BAY
VENTED GAS FIREPLACE HEATER.
Report / Rapport
061-S-19b-5
APPROVED FOR CANADA AND USA TO:
ANSI Z21.88a-2001 / CSA 2.33a-M01 Vented Gas Fireplace Heaters, and applicable
sections of UL307b Gas Burning Heating Appliances for Manufactured Homes
and Recreational Vehicles, CAN/CGA 2.17-M91 “Gas Fired Appliances for use
at High Altitudes.” This appliance is manufactured for operation with Natural
Gas. For conversion to propane Manufacturer’s Part #842-4041 and instructions
must be used. This appliance may be installed in a bedroom or bedsitting room;
in Canada remote thermostat installation is required.
FAN TYPE VENTED CIRCULATOR / VENTILATEUR CIRCULATOIRE
Blower Electrical Rating / Évaluation du Ventilateur Électrique:
For use with Natural Gas For use with Propane
Usage Au Gaz Naturel Usage Au Gaz Propane
0-2000’ 0-2000’
Top Vent: Input Rate on “HI” (BTU/Hr) 30,000 30,000 Puissance Évaluée à “HI” (BTU/Hr)
Input Rate on “LO” (BTU/Hr) 21,000 24,500 Puissance Évaluée à “LO” (BTU/Hr)
Maximum Output (BTU/Hr)** 25,250 25,800 Puissance Maximum (BTU/Hr)**
Main Burner Orifice .1065 (36 DMS) .0635 (52 DMS) Orifice du Brûleur Principal
Minimum Inlet Pressure (Inches W.C.) 4.5” 11” Pression Minimum de la Valve (pouces W.C.)
Maximum Inlet Pressure (Inches W.C.) 7.0” 14” Pression Maximum de la Valve (pouces W.C.)
Manifold Pressure on “HI” (Inches W.C.) 3.5” 10”
(pouces W.C.)
**Max Venting, Blower On ** Ventilation Maximum, Ventilateur Allumé
This appliance equipped only for altitudes 0-2000’ (0-610m) in USA; and in Canada for altitudes of 0-4500’ (0-1370m). In USA for Altitudes above 2000’, the vent
configuration, orifice, or combination of both may need to be changed. See Owner’s Manual for information on making these changes.
Cet appareil est équipé pour les altitudes de 0-2000’ (0-610m) aux États-Unis; et au Canada pour les altitudes de 0-4500’ (0-1370m). Pour les altitudes au dessus de 2000’
aux États-Unis, la configuration du ventilateur, son orifice ou les deux peuvent possiblement avoir à être changé. Voyez le manuel du propriétaire pour les informations
sur ces changements.
This appliance must be installed in accordance with local codes, if any (and Commonwealth of Massachusetts approved); if none, follow the National Fuel Gas Code, ANSI
Z223.1 or Canadian Installation Codes, CAN/CGA-B149. Install and use only in accordance with manufacturer’s installation and operating instructions. NOTE: Have the gas
supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts,
installation must be performed by a licensed plumber or gas fitter.)
Cet appareil doit être installé en accord avec les codes locaux, s’il-y-a lieu (et approuvé par dans la République de Massachusetts); sinon lisez ANSI Z223.1/CAN 1-B149.
Installez et utilisez en accords avec les instructions d’installation et d’opération du manufacturier.
de construction locaux. L'installation doit être effectuée par un technicien qualifeé et/ou muni d'une licence de manière à respecter les règlements municipaux. (Dans la
République de Massachusetts, l'installation doit être effectuée par un plombier ou un installateur d'appareils à gaz agrée.)
This appliance must be installed in accordance with the current Standard CAN/CSA Z240 MH, Mobile Housing or with Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280, or when such standard is not applicable, ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installation Standard.
WARNING: Do not operate the appliance until all sections have been assembled and installed in accordance with the manufacturer's instructions.
Installer l'appareil selon la norme CAN/CSA-Z240, Serie MM, Maisons mobiles ou la norme 24 CFR Part 3280, Manufactured Home Construction and Safety Standard. Si ces
normes ne sont pas pertineutes, utilisez la norme ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations Standard.
AVERTISSEMENT: Ne pas utiliser l'appareil tant que toutes les sections n'ont pas ete assemblees et installees selon les instructions du fabricant.
This appliance must be properly connected to a venting system in accordance with the manufacturer's installation instructions.
Cet apprareil doit être correctement raccordé à un système d'évacuation, conformément aux instructions du fabricant.
Keep burner and control compartment clean. See installation and operating instructions accompanying this appliance. This vented gas fireplace heater is not for use with air filters.
Due to high surface temperatures, keep children, clothing and furniture away.
Gardez le brûleur et le compartiment de contrôle propres. Vérifiez les instructions d’installation et d’opération qui accompagnent cet appareil. Cet appareil de chauffage au gaz n’est
pas pour l’usage avec des filtres d’air. Du aux surfaces de températures élevées, gardez les enfants, les vêtements et les meubles à distance éloignée.
2005 2006 2007 Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan
800 West Jefferson Street
Lake City, MN 55041
www.quadrafire.com
115 V., 1.5 Amps, 60 Hz, 150 Watts
SAMPLE
NOT FOR USE WITH SOLID FUEL
FOURNAISE AU GAZ AVEC VENTILATION
NE PAS UTILISER AVEC LE COMBUSTIBLE SOLIDE
APPROUVÉ POUR LE CANADA ET LES ÉTATS-UNIS:
ANSI Z21.88a-2001 / CSA 2.33a-M01 Fournaises au Gaz avec Ventilation, et les sections
applicable de UL 307b Appareils de Chauffage Au Gaz pour les Maisons Mobiles et les
Véhicules Motorisés, CAN/CGA 2.17-M91 “Gas Fired Appliances for use at High Altitudes”.
Cet appareil est manufacturé pour l’opération avec le Gaz Naturel. Pour une conversion
au gaz propane les pièces du Manufacturier #842-4041 et ses instructions doivent être
utilisées. Cet appareil peut être utilisé dans une chambre à coucher ou salle de séjour; au
Canada, l’installation d’un thermostat à distance est exigée.
Thermal Efficiency / Efficacité Thermique*
84% NG (blower on / avec ventilateur allumé)
86% LP (blower on / avec ventilateur allumé)
* With Maximum horizontal length. / Avec longueur horizontale maximum.
P.4.1-02 Canada Minimum pipe (P.4.1-02 Le canada tuyau minimum) 65.42% NG / 65.96% LP
REMARQUE: Le conduit gaz doit être installé conformément aux codes
Date of Manufacture / Date du Manufacturier
SERIAL NO.
002
Pression du Collecteur d’ Échappement à “HI”
meticulously fabricated and gold and nickel surfaces are
hand-fi nished for lasting beauty and enjoyment. Our pledge
to quality is completed as each model undergoes a quality
control inspection. From design, to fabrication, to shipping:
Our guarantee of quality is more than a word, it’s QuadraFire tradition, and we proudly back this tradition with a Limited Lifetime Warranty.
We wish you and your family many years of enjoyment in the
warmth and comfort of your hearth appliance. Thank you for
choosing Quadra-Fire.
MINIMUM CLEARANCES TO COMBUSTIBLES
ESPACE MINIMUM AUX COMBUSTIBLES
Minimum clearances required from combustible construction for all
appliance surfaces.
Espaces minimum exigés de la construction combustible aux surfaces
de l’appareil.
I
B
C
H
A
F
A.
Du coté du poêle au coté du mur
A*. In an Alcove 6-3/4 in. (171 mm)
Dans l’alcôve
B. Rear of control box to back wall 2 in. (51 mm)
Le contrôle arrière au mur arrière
C. Flue pipe to back wall 6 in. (152 mm)
Du tuyau de cheminée au mur arrière
D. Flue pipe to side wall 14 in. (356 mm)
Du tuyau de cheminée au mur du coté
E. Rear corner of stove top to side wall 2 in. (51 mm)
Du coin arrière du poêle au mur de coté
F. Min. Floor to ceiling height (std. room) 84 in. (2134 mm)
Hauteur minimum du plancher au plafond (pièce standard)
G. Top of stove to alcove ceiling 19 in. (483 mm)
Du dessus du poêle au plafond de l’alcôve
H. Maximum alcove depth 36 in. (914 mm)
Profondeur maximum de l’alcôve
I. Minimum alcove width 36 in. (914 mm)
Largeur minimum de l’alcôve
HEARTH: A non-combustible hearth pad is not required. However, the
floor beneath the stove must be stable, level, and strong enough to support
the stove without a tipping hazard.
CHEMINÉE: Un coussinet non-combustible de cheminée n’est pas
exigé. Cependant, le plancher en dessous du poêle doit être droit, à
niveau et assez fort pour supporter le poêle sans le hasard de
basculer.
D
Side of stove top to side wall 6 in. (152 mm)
DO NOT REMOVE THIS LABEL / NE PAS
ENLEVER L’ÉTIQUETTE
Made in U.S.A. / Fait Aux États-Unis
E
A*
Alcove height
G-
Hauteur De
l’Alcôve
E
A*
250-5184
Serial Number
Barcode
Model Name
Test Lab &
Report No.
Manufactured
Date
Page 2
Quadra-Fire • Columbia Bay • 250-5195 Rev.K
10/08
- TABLE OF CONTENTS -
Section 1: Listing and Code Approvals
A. Appliance Certifi cations ......................4
B. Glass Specifi cations ............................4
C. BTU Specifi cations ..............................4
D. High Altitude Installations ....................4
E. Non-Combustible Materials .................4
F. Combustible Materials ........................4
G. Electrical Codes ..................................4
A. Maintenance Tasks .............................39
B. Service and Maintenance Log ............40
Section 12: Reference Materials
A. Appliance Dimension Diagram ...........41
B. Vent Components Diagram ................42
C. Vent Components List ........................43
D. Service Parts List ................................44
E. Warranty Policy ...................................47
F. Contact Information ............................49
10/08
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Page 3
1
Listing and Code Approvals
A. Appliance Certifi cation
MODEL:
LABORATORY:
TYPE:
STANDARD:
The product is listed to ANSI standards for “Vented Gas
Appliance Heaters” and applicable sections of “Gas Burning
Heating Appliances for Manufactured Homes and Recreational Vehicles” and "Gas Fired Appliances for use at High
Altitudes".
Manufactured Home or Mobile Home installation may occur
only after the home is site located and must conform with
the Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280, or, when such a standard is
not applicable, the Standard for Manufactured Home
Installations, ANSI/NCSBCS A225.1, or Standard for Gas
Equipped Recreational Vehicles and Mobile Housing, CSA
Z240.4.
When installed, the appliance must be electrically grounded
in accordance with local codes or, in the absence of local
codes, with the National Electrical Code, ANSI/NFPA 70, or
the Canadian Electrical Code, CSA C22.1.
* Thermal effi ciency maximum pipe with blower on.
** Canada minimum pipe.
Maximum
Input BTU
30,000 21,000368465.42
30,000 24,500528665.96
Minimum
Input
BTU
Orifi ce
Size
(DMS)
*Effi ciency
Up T o
%
**P.4
%
D. High Altitude Installations
Omni-Test Laboratories listed gas appliances are tested and
approved without requiring changes for elevations from 0 to
2000 feet in the U.S.A. and 0 to 4500 feet in Canada.
When installing this appliance at an elevation above 2000
feet, it may be necessary to decrease the input rating by
changing the existing burner orifi ce to a smaller size. Input
rate should be reduced by 4% for each 1000 feet above a
2000 foot elevation in the U.S.A. If the heating value of the
gas has been reduced, these rules do not apply. To identify
the proper orifi ce size, check with the local gas utility.
If installing this appliance at an elevation above 4500 feet (in
Canada), check with local authorities.
B. Glass Specifi cations
This appliance is equipped with 5mm ceramic glass. Replace
glass only with 5mm ceramic glass. Please contact your
dealer for replacement glass.
NOTE: This installation must conform with local codes. In the
absence of local codes you must comply with the National Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A.
and the CAN/CGA B149 Installation Codes in Canada.
WARNING
Do NOT use this appliance if any part has been under water.
Immediately call a qualifi ed service technician to inspect
the unit and to replace any part of the control system and
any gas control which has been under water.
Page 4
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
E. Non-Combustible Materials
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a Vertical
T ube Furnace at 750°C, shall be considered non-combustible
materials.
F. Combustible Materials
Materials made of or surfaced with wood, compressed
paper, plant fibers, plastics, or other materials that can ignite
and burn, whether flame proofed or not, or whether plastered
or unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1.
• A 110-120 V AC circuit for this product must be protected with
ground-fault circuit-interrupter protection, in compliance with
the applicable electrical codes, when it is installed in locations
such as in bathrooms or near sinks.
10/08
NOTE: The following requirements reference various
Massachusetts and national codes not contained in this
document.
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in whole
or in part for residential purposes, including those owned or
operated by the Commonwealth and where the side wall
exhaust vent termination is less than seven (7) feet above
fi nished grade in the area of the venting, including but not
limited to decks and porches, the following requirements
shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas fi tter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the fl oor level where
the gas equipment is to be installed. In addition, the installing
plumber or gas fi tter shall observe that a battery operated or
hard wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to
secure the services of qualifi ed licensed professionals for the
installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery backup may be installed on the next adjacent fl oor level.
In the event that the requirements of this subdivision can not
be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above
requirements; provided, however, that during said thirty (30)
day period, a battery operated carbon monoxide detector with
an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and
be ANSI/UL 2034 listed and IAS certifi ed.
Signage
A metal or plastic identifi cation plate shall be permanently
mounted to the exterior of the building at a minimum height
of eight (8) feet above grade directly in line with the exhaust
vent terminal for the horizontally vented gas fueled heating
appliance or equipment. The sign shall read, in print size no
less than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
Inspection
The state or local gas inspector of the side wall horizontally
vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon
monoxide detectors and signage installed in accordance with
the provisions of 248 CMR 5.08(2)(a) 1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)
1 through 4:
The equipment listed in Chapter 10 entitled “Equipment
•
Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
Product Approved side wall horizontally vented gas fueled
•
equipment installed in a room or structure separated from
the dwelling, building or structure used in whole or in part
for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas fueled equipment provides a venting system design or venting system components with the
equipment, the instructions provided by the manufacturer for
installation of the equipment and the venting system shall
include:
•
Detailed instructions for the installation of the venting system design or the venting system components; and
•
A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the
parts for venting the fl ue gases, but identifi es “special vent-
ing systems”, the following requirements shall be satisfi ed by
the manufacturer:
•
The referenced “special venting system” instructions shall
be included with the appliance or equipment installation
instructions; and
•
The “special venting system” shall be Product Approved
by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved
side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or
all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.
10/08
Page 5Quadra-Fire • Columbia Bay • 250-5195 Rev. K
2
Getting Started
A
. Design & Installation Considerations
Quadra-Fire direct vent gas appliances are designed to
operate with all combustion air siphoned from outside of the
building and all exhaust gases expelled to the outside. No
additional air source is required.
CAUTION
Check building codes prior to installation.
• Installation MUST comply with local, regional, state
and national codes and regulations.
• Consult local building, fi re offi cials or authorities having
jurisdiction about restrictions, installation inspection,
and permits.
When planning an installation, it is necessary to determine
the following information before installing:
• Where the appliance is to be installed.
•
The vent system confi guration to be used.
• Gas supply piping.
• Electrical wiring.
• Whether optional accessories - devices such as a blower,
thermostat or remote control - are desired.
C. Inspect Appliance & Components
WARNING
Inspect appliance and components for
damage. Damaged parts may impair safe
operation.
• Do NOT install damaged components.
• Do NOT install incomplete components.
• Do NOT install substitute components.
Report damaged parts to dealer.
• Carefully remove the appliance and components from
the packaging.
• Remove cast door and glass door, and set aside on pro-
tective surface.
• Remove log set and component pack from fi rebox.
• Report to your dealer any parts damaged in shipment,
particularly the condition of the glass.
• Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the
installation to ensure maximum safety and benefi t.
WARNING
Keep appliance dry.
• Mold or rust may cause odors.
• Water may damage controls.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following
tools and building supplies are available. Note: Not all
Variable Speed Drill/Driver
Wrench Set
Framing Square
Framing Material
Hi temp caulking material
Voltmeter
Gloves
Safety Glasses
Non-corrosive Leak Check Solution
or combustible gas detector
WARNING
Hearth & Home Technologies disclaims any
responsibility for, and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent
system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home
Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
Page 6
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
3
Appliance Location and Clearances
NOTE:
· Illustrations refl ect typical installations and are FOR
DESIGN PURPOSES ONLY.
· Illustrations/diagrams are not drawn to scale.
· Actual installation may vary due to individual design
preference.
A. Selecting Appliance Location
When selecting a location for your appliance it is important to
consider the required clearances to walls (see Figure 3.1).
NOTE: For actual appliance dimensions refer to Section 12.
B. Clearances
I
E
B
C
G - Alcove Height
A*
WARNING
Fire Risk
Provide adequate clearance:
• Around air openings
• To combustibles
• For service access
Locate appliance away from traffi c areas.
WARNING
Fire Risk.
• Locate and install appliance to all
clearance specifi cations in manual.
A*
A
Columbia Bay FS
Figure 3.1
It is permissible to place the appliance on carpet.
D
ModelAA*BCDEFGHI
H
Inches
Millimeters
E
66-3/42614284193636
152171515152356512134483914914
CAUTION
Some carpet materials may be sensitive to radiant heat from the
appliance causing discoloration or odor.
NOTE: Flooring beneath appliance may reach 90 degrees
plus room ambient temperature. Check with flooring
manufacturer for maximum temperature allowed on flooring
surfaces.
F
WARNING
Fire Risk.
Odor Risk.
Tipping Risk
• Install appliance on a stable, level platform/
fl oor strong enough to support appliance
without tipping.
• USE wood fl ooring, ceramic tile, brick hearth
or high pressure laminate fl ooring applied
directly over the sub-fl ooring material.
10/08
Page 7Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Termination Locations
t
5
5
4
A. Vent Termination Minimum Clearances
WARNING
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles
as specifi ed.
• Do not pack air space with insulation or
other materials.
Failure to keep insulation or other materials
away from vent pipe may cause fi re.
Measure vertical clearances from this surface.
Measure horizontal clearances from this surface.
(See Figure 4.4 for specifi c clearances.)
Figure 4.1 Termination Clearances
GAS, WOOD OR FUEL
OIL TERMINATION
B
HORIZONTAL
2 FT.
MIN.
GAS DIRECT VENT
TERMINATION CAP
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
X
12
ROOF PITCH
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
Roof PitchH (Min.) F
Flat to 6/12 .........................................................1.0*
Over 6/12 to 7/12........................................................1.2
Over 7/12 to 8/12 ............................................... 1.5*
Over 8/12 to 9/12 ............................................... 2.0*
Over 9/12 to 10/12 ............................................. 2.5*
Over 10/12 to 11/12 ........................................... 3.2
Over 11/12 to 12/12 ........................................... 4.0
Over 12/12 to 14/12 ........................................... 5.0
Over 14/12 to 16/12 ........................................... 6.0
Over 16/12 to 18/12 ........................................... 7.0
Over 18/12 to 20/12 ........................................... 7.5
Over 20/12 to 21/12 ........................................... 8.0
* 3 foot minimum in snow regions
OVERHANG
VERTICAL
WALL
IS X/ 12
GAS
TERMINATION
C
A
Gas
Termination
A6 in.20 in. min.Horizontal distance between terminations
B20 in.24 in. min.Distance to perpendicular wall
C18 in.18 in. Vertical distance between terminations
Figure 4.2 Multiple Vertical Termination
Page 8
Wood & Fuel Oil
Termination
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Figure 4.3 Minimum Height from Roof to Lowest Discharge
Opening
Figure 4.3 specifi es minimum vent heights for various
1cap3feet2xQ
2 caps6 feet1 x Q
3 caps9 feet2/3 x Q
4caps12feet1/2xQ
Q
= # termination caps x 3R
MIN
= (2 / # terminationcaps) xQ
MAX
R
MAX
ACTUA L
ACTUA L
ACTUA L
ACTUA L
ACTUAL
_
_
_
_
** a vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and
serves both dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on
a minimum of 2 sides beneath the floor, or meets Note 2.
NOTE 1: On private property where termination is less than 7 feet above
a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed
cap is suggested. (See vents components pages.)
NOTE 2: Termination in an alcove space (spaces only open on one side
and
vinyl or non-vinyl siding and soffits. 1. There must be at least 3 feet
minimum between termination caps. 2. All mechanical air intakes within
10 feet of a termination cap must be a minimum of 3 feet below the
termination cap. 3.All gravity air intakes within 3 feet of a termination cap
must be a minimum of 1 foot below the termination cap.
NOTE 3: Location of the vent termination must not interfere with access
to the electrical service.
an overhang) are permitted with the dimensions specified for
without
Figure 4.4
10/08
NOTE:Local codes or regulations may require different
clearances.
NOTE: Termination caps may be hot. Consider their proximity to
doors or other traffic areas.
WARNING: In the U.S.: Vent system termination is NOT permitted
in screened porches. You must follow side wall, overhang and
ground clearances as slated in the instructions.
In Canada: Vent system termination is NOT permitted in screened
porches. Vent system termination is permitted in porch areas with
two or more sides open. You must follow side wall, overhang and
ground clearances as stated in the instructions.
Quadra-Fire assumes no responsibility for the improper performance of the appliance when the venting system does not meet
these requirements.
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH
VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED (part #VPK-DV).
Page 9Quadra-Fire • Columbia Bay • 250-5195 Rev. K
5
Vent Information
A. Venting Components
In order to comply with applicable codes and product
warranties, use only following venting components:
• Hearth & Home Technologies (HHT)
• Security Chimney's Secure Vent Chimney System
• Selkirk Metalbestos
• AmeriVent
• Simpson Dura-Vent (SDV)
DO NOT USE FIELD-FABRICATED VENTING
COMPONENTS. Refer to the venting manufacturer’s
instructions.
This product is approved to be vented either horizontally,
through the side wall or vertically through the roof. You may
vent through a Class A or masonry chimney if an approved
adapter is used.
This appliance is a direct vent heater. All combustion air must
come directly from the outside of the building. The vent pipe
for this unit consists of an inner and an outer pipe. The inner
pipe carries the appliance exhaust out of the system, and the
outer pipe brings fresh combustion air into the appliance.
•A round support box/wall thimble or heat shield is
required when the venting passes through a combustible wall.
•A support box or ceiling fi restop is required when the
venting passes through a ceiling.
•Roof fl ashing and a storm collar are required when vent-
ing passes through the roof.
•Follow instructions provided with the venting for installation of these items.
B. Use of Elbows
CAUTION
ALL vent confi guration specifi cations MUST be followed.
• This product is tested and listed to these
specifi cations.
• Appliance performance will suffer if specifi cations are
not followed.
Diagonal runs have both vertical and horizontal vent aspects
when calculating the effects. Use the rise for the vertical
aspect and the run for the horizontal aspect. (See Figure
5.1.)
Two 45° elbows may be used in place of one 90° elbow. On
45° runs, one foot of diagonal is equal to 8-1/2 in. (216mm)
horizontal run and 8-1/2 in. (216mm) vertical run. A length of
straight pipe is allowed between two elbows. (See Figure
5.1.)
Vertical
12 in.
8-1/2 in.
8-1/2 in.
Horizontal
Figure 5.1
WARNING
Fire Hazard.
Explosion Risk.
Asphyxiation Risk.
Do NOT connect this gas appliance to a chimney
fl ue serving a separate solid-fuel or gas burning
appliance.
• Vent this appliance directly outside.
• Use separate vent system for this appliance.
May impair safe operation of this appliance or
other appliances connected to the fl ue.
Page 10
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
C. Measuring Standards
Vertical and horizontal measurements were made using the
following standards.
•Pipe measurements are from center line to center line.
•Horizontal terminations are measured to the outside of
the mounting surface (fl ange of termination cap). See Figure 4.1 on page 8.
•Vertical terminations are measured to the top of the last
pipe before termination cap.
•Horizontal pipe installed level with 1/4 in. rise.
10/08
D. How to Use the Vent GraphE. Venting Guidelines
1. Measure the vertical distance from the center line of the
flue pipe to the center of the 90° elbow. On the graph
below, draw a horizontal line from that measurement
on the vertical axis across until it intersects with the
slanted line.
2. From the point of this intersection, draw a vertical line to
the bottom of the graph.
3. The point at which this line meets the bottom line of the
graph is the maximum length of the horizontal run.
EXAMPLE 1: If the vertical dimension from the center line
of the fl ue vent to the center of the 90° elbow is 7 ft. (2m),
the horizontal run to the outer wall fl ange must not exceed
13 ft. (4m).
EXAMPLE 2: If the vertical dimension from the center line
of the fl ue vent is 21 ft. (6m), the horizontal run to the outer
wall fl ange must not exceed 9 ft. (3m).
4. Each 90° elbow is equivalent to 3 ft. (914mm) of vent
pipe and each 45° elbow is equivalent to 1 ft. (305mm)
of vent pipe, and must be subtracted from the vent pipe
run. A single horizontal to vertical 90° elbow is already
calculated into the allowable 15 ft. (5m) run. Each
additional 90° elbow reduces the maximum horizontal
distance by 3 ft. (914mm).
NOTES
The maximum horizontal vent run is 15 ft. (5m) when the
vertical vent rise is 10 ft. (3m).
The minimum horizontal vent run is 11 in. (279mm).
Horizontal sections require a 1/4 in. (6mm) rise for every 12
ft. (305mm) of horizontal travel.
Exterior Vent Diameter = 6 5/8 in. (168mm); Inner Vent Diam-
eter = 4 in. (101mm)
Horizontal sections require noncombustible support every 3
ft. (914mm), e.g. wall straps.
A minimum 2 ft. (610mm) vertical rise is required before the
90 degree elbow.
NOTE: If your installation falls within the gray-shaded area
on graph, see information on Vertical damper adjustment in
Section 8. (In the Commonwealth of Massachusetts, the word
damper shall be replaced with the words flue restrictor.)
EXAMPLE: The use of 3 elbows would reduce the allowable
horizontal run to 9 ft. (3 -1 = 2 elbows x 3 ft. = 6 ft.; 15 ft.
max. - 6 ft. = 9 ft. maximum).
35'
34'
32'
30'
28'
26'
EX. 2
VERTICAL DISTANCE
FROM APPLIANCE TO
TO THE 90° ELBOW
EX. 1
24'
22'
20'
18'
16'
14'
12'
10'
8'
6'
4'
2'
0'
11" 2' 4' 6' 8' 10' 12' 14' 15'
(MIN)
(MAX)
Figure 5.2
10/08
TOTAL HORIZONTAL RUN TO OUTSIDE OF
EXTERIOR WALL (INCLUDING ELBOWS)
Page 11Quadra-Fire • Columbia Bay • 250-5195 Rev. K
F. Horizontal Termination
HHW2 - Recommended for
optimum performance.
90 DEGREE
ELBOW
Female Locking Lugs
Male Locking Lugs
PIPE LENGTH
PIPE
LENGTH
Figure 5.3
WALL
THIMBLE
COVER
WALL THIMBLE
Step 1.
Determine the desired location of the appliance. Check to
ensure that wall studs or roof rafters are not in the way when
the venting system is attached. If this is the case, you may
want to adjust the location of the appliance.
WARNING
Fire Hazard.
Exhaust Fume Risk.
Impaired Performance of Appliance.
• Ensure vent components are locked together correctly.
• Pipe may separate if not properly joined.
Figure 5.4
WARNING
Fire Risk.
Explosion Risk.
Combustion Fume Risk.
Use vent run supports per installation instructions.
Connect vent sections per installation instructions.
• Maintain all clearances to combustibles.
• Do NOT allow vent to sag below connection
point to appliance.
• Maintain specifi ed slope (if required).
Improper support may allow vent to sag or separate.
Step 3.
For installations using a round support box/wall thimble
(check pipe manufacturer's instructions), mark the wall for a
10 in. x 10 in. (254mm x 254mm) square hole. The center
of the square hole should line up with the center line of the
horizontal pipe, as shown in Figure 5.5 on the next page.
Cut and frame the hole in the exterior wall where the vent will
be terminated. If the wall being penetrated is constructed of
noncombustible material, i.e. masonry block or concrete, a 7
in. (178mm) diameter hole is acceptable.
Step 2.
Direct vent pipe is designed with a locking connection. To
connect the venting system to the appliance flue outlet, a
twist-lock adapter is built into the appliance at the factory.
Remember to include wall thickness in minimum clearances
when figuring the measurements for your installation
needs.
Note: Direct vent pipe is designed to slide straight onto
the male ends of adjacent pipes and fittings by orienting the
pipe indentations so they match and slide into the entry slots
on the male ends, see Figure 5.4. Push the pipe sections
completely together, then twist-lock one section clockwise
approximately one-quarter turn, until the two sections are
fully locked. The female locking lugs may not be visible from
the outside, on the pipe or fittings. They may be located by
examining the inside of the female ends.
Page 12
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
HOT
CENTER OF
HOLE
WOOD
SCREW
CENTER
LINE
WALL
THIMBLE
Figure 5.5
CENTER
LINE
NOTE:
(1) Installation requires a minimum of 6 in. (152mm)
horizontal run of vent with a 1/4 in. (6mm) rise run towards
the termination. Each 1 ft. (305mm) of horizontal venting
must include a 1/4 in. (6mm) rise. Never allow the vent
to run downward. This could cause high temperatures
and may present the possibility of a house or structure
fire.
(2) The location of the horizontal termination cap on an
exterior wall must meet all local and national building
codes, and must not be easily blocked or obstructed,
see Figure 4.4 on page 9.
PART HHW2 PART
HOT
841-0670 (Preferred)
WALL THIMBLE
Figure 5.6
NOTES:
(1) The four wood screws provided should be replaced with
appropriate fasteners for stucco, brick, concrete, or
other types of sidings.
(2) Termination cap HHW2 (Part #841-0670) is highly
recommended on a building with vinyl siding, as the
vinyl siding standoff is built in. The pilot hole will be 2 in.
(51mm) closer to the bottom of the square than the top.
Using a framing square, draw a 14 in. x 14 in. (356mm x
356mm) square around the pilot hole in the siding. See
Figure 5.7.
8 in.
(203mm)
7 in.
(178mm)
7 in.
(178mm)
6 in.
(152mm)
(3) For installations requiring a vertical rise on the exterior
of the building, the HHT RHVK snorkel kit (Part #844-
8921) is available with a 14 in. (356mm) and a 36 in.
(914mm) tall snorkel termination cap. Follow the
same installation procedures as used for standard
horizontal terminations. If the snorkel termination must
be installed below grade (i.e. basement application),
proper drainage must be provided to prevent water from
entering the snorkel termination. Do not backfill around
snorkel termination.
Step 4.
Position the horizontal termination cap in the center of the 10
in. x 10 in. (254mm x 254mm) square hole and run a bead
of non-hardening mastic around its outside edges, so as to
make a seal between it and the wall, attach termination cap
to the exterior wall with the four wood screws provided. The
arrow on the vent cap should be pointing up (Figure 5.6)
10/08
Figure 5.7
(NOTE: If you are installing termination cap HHW2, the
pipe will be off center on the flashing). Ensure that proper
clearances to combustible materials are maintained. If
you are using an approved termination cap other than
HHW2 (part #841-0670) on a building with vinyl siding,
a vinyl siding standoff should be installed between the
vent cap and the exterior wall (Figure 5.8, on the next
page). Attach the vinyl siding standoff to the horizontal
vent termination. The vinyl siding standoff prevents
excessive heat from possibly melting the vinyl siding
material. Vent terminal shall not be recessed into a
wall or siding. Remove siding from the area where the
standoff will be located..
Page 13Quadra-Fire • Columbia Bay • 250-5195 Rev. K
VINYL SIDING
APPLY SEALANT
TO ALL FOUR
SIDES
SCREWS
BOLT HORIZONTAL
TOP TO VINYL
STANDOFF
SCREWS
WALL THIMBLE
COVER
Figure 5.8
WALL THIMBLE
VINYL SIDING
STANDOFF WITH
SIDING BENEATH
REMOVED
Step 5.
Place the wall thimble cover over the pipe assembly and
slide the appliance and vent assembly towards the wall,
carefully inserting the vent pipe into the vent cap assembly.
It is important that the vent pipe extend into the vent cap a
sufficient distance so as to result in a minimum pipe overlap
of 1-1/4 in. (32mm). Secure the connection between the vent
pipe and the vent termination cap by attaching the two sheet
metal strips extending from the vent cap assembly into the
outer wall of the vent pipe. Use the two sheet metal screws
provided to connect the strips to the pipe section (Figure
5.9).
WARNING
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as specifi ed.
• Do not pack air space with insulation or other
materials.
Failure to keep insulation or other materials away from
vent pipe may cause fi re.
WARNING
Burn Risk.
• Local codes may require installation of a cap
shield to prevent anything or anyone from
touching the hot cap.
WARNING
Do NOT connect a pipe section to a termination cap without
using the telescoping fl ue section found on the termination
cap.
1/4 in. (6mm)
FOLD STRAP
HERE
SHEET METAL SCREW
Figure 5.9
WALL THIMBLE COVER/CEILING
FIRESTOP AS REQUIRED BY
LOCAL JURISDICTION
STRAP
WALL
THIMBLE
Note: The attachment from the vent pipe to the vent
termination cap must be sealed with silicone. Termination
caps shall not be recessed into a wall or siding.
Page 14
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
G. Vertical Termination
1. Direct Vent Pipe
STORM
COLLAR
FIRESTOP
PIPE
LENGTH
VERTICAL
TERMINATION
CAP
FLASHING
SUPPORT
BOX
NOTE: Maximum vertical rise allowable is 35 ft. (11m)
Figure 5.11).
NOTE: Maximum number of 45° elbows permitted for a
vertical installation is eight, provided their installation does
not decrease maximum allowable horizontal run (as specified
by vent graph, on page 11).
35 ft. (11m)
MAXIMUM
Figure 5.10
Step 1.
Check the installation instructions for required 1 in. (25mm)
clearances (air space) to combustibles when passing
through ceilings, walls, roofs, enclosures, attic rafters, or
other nearby combustible surfaces. See page 16, Figure
5.17. Check the instructions below for maximum vertical rise
of the venting system, and any maximum horizontal offset
limitations. All offsets must fall within the set parameters of
the vent graph (Figure 5.2) located on page 11.
WARNING
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as speci-
fi ed.
• Do not pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe may cause fi re.
Figure 5.11
NOTE: Maximum number of 90° elbows permitted for a
vertical installation is four, provided the termination falls
within the shaded area shown in vent graph on page 10. See
also Figure 5.12, within the four 90° elbows configuration,
the maximum allowable pipe length on the horizontal runs is
1 ft. (305mm) the minimum allowable pipe length on vertical
runs is 1 ft. (305mm).
ADDITIONAL RESTRICTION: This installation may not
have two horizontal sections connected by 90° elbows.
1'
2'
2'
1'
1'
Figure 5.12
10/08
Page 15Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Step 2.
Set the gas appliance in its desired location. Drop a plumb
bob down from the ceiling to the position of the appliance
flue exit, and mark the location where the vent will penetrate
the ceiling. Drill a small hole at this point. Next, drop a plumb
bob from the roof to the hole previously drilled in the ceiling,
and mark the spot where the vent will penetrate the roof.
Determine if ceiling joists, roof rafters, or other framing will
obstruct the venting system. You may wish to relocate the
appliance, or to offset, as shown in Figure 5.13 to avoid
cutting load bearing members. When location is determined,
drill small hole.
PLUMBER'S TAPE
CONNECTED TO
WALL STRAP
Step 4.
Assemble the desired lengths of pipe and elbows necessary
to reach from the appliance up through the round support
box. Ensure that all pipe and elbow connections are in their
fully twist-locked position. Assemble as instructed.
Step 5.
Cut a hole in the roof centered on the small drill hole placed in
the roof in Step 2. The hole should be of sufficient size to meet
the minimum requirements for clearance to combustibles, as
specified. Continue to assemble lengths of pipe and elbows
necessary to reach from the ceiling support box/wall thimble
up through the roof line. Galvanized pipe and elbows may
be utilized in the attic, as well as above the roofline. The
galvanized finish is desirable above the roofline, due to its
higher corrosion resistance.
NOTE:
(1
) If an offset is necessary in the attic to avoid obstructions,
it is important to support the vent pipe every 3 ft. (914mm)
to avoid excessive stress on the elbows, and possible
separation. Wall straps are available for this purpose,
Figure 5.13.
WALL
STRAP
TWO 45 DEGREE
ELBOWS
Figure 5.13
Step 3.
To install the round support box/wall thimble cover in a flat
ceiling, cut a 10 in. (254mm) square hole in the ceiling,
centered on the hole drilled in Step 2. Frame the hole as
shown in Figure 5.14.
CEILING JOISTS
FRAMING
(2) Whenever possible, use 45° elbows, instead of 90°
elbows. The 45° elbow offers less restriction to the flow
of flue gases and intake air.
Step 6.
Slip the flashing over the pipe section(s) protruding through
the roof. Secure the base of the flashing to the roof with
roofing nails. Ensure the roofing material overlaps the top
edge of the flashing as shown in Figure 5.15. Verify that the
chimney is the required height above the roof (see roof pitch
table, Figure 4.3 on page 8).
SHINGLES OVERLAP ON
TOP EDGE OF FLASHING
ROUND CEILING
SUPPORT BOX/WALL
THIMBLE COVER
1-1/2 in. (38mm) LONG
WOOD SCREWS
Figure 5.14
Page 16
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
CAP AND STORM COLLAR NOT SHOWN FOR CLARITY
Figure 5.15
10/08
Step 7.
Continue to assemble pipe sections until the height of the
vent (before adding the termination cap) meets the minimum
code requirements as outlined in the current CAN/CGA-B149
Installation Codes (in Canada), the National Fuel Gas Code
NFPA 54/ANSI Z223.1 (in USA), or local codes. Note that
for steep roof pitches, the vent height must be increased.
See Roof Pitch Table (Figure 4.3, on page 8). In high wind
conditions, nearby trees adjoining rooflines, steep pitched
roofs, and other similar factors can result in poor draft, or
down drafting. In these cases increasing the vent height or
switching to the high wind termination cap may solve this
problem.
Step 8.
Slip the storm collar over the pipe, and push it down to the
top of the flashing (Figure 5.16). Use non-hardening sealant
above and below the joint between the storm collar and the
pipe.
OPTIONAL HIGH WIND
TERMINATION CAP
SECURE FLASHING WITH
NON-HARDENING SEALANT
AND ROOFING NAILS
Figure 5.16
Step 9.
Twist-lock the vent cap and seal.
NAILS
CEILING FIRESTOP
MIN. 1 in. (25mm)
CLEARANCE
MIN. 1 in. (25mm)
CLEARANCE
MIN. 1 in. (25mm)
CLEARANCE
MIN. 1 in. (25mm)
CLEARANCE
Figure 5.17
WARNING
Fire Risk.
Explosion Risk.
• Any occupied areas above the first floor, including
closets and storage spaces, which the vertical
vent passed through must be enclosed. The
enclosure may be framed and sheetrocked with
standard construction materials; however, refer
to these installation instructions for the minimum
allowable clearance between the outside of the
vent pipe and the combustible surfaces of the
enclosure. Do not fill any of the required air space
with insulation.
Note: For multi-story vertical installations, a ceiling firestop
is required at the second floor, and any subsequent floors
(Figure 5.17). The opening should be framed to 10 in. x
10 in. (254mm x 254mm) inside dimensions, in the same
manner as shown in Figure 5.14, on page 16.
10/08
Page 17Quadra-Fire • Columbia Bay • 250-5195 Rev. K
2. Cathedral Ceiling
Step 1.
Follow installation Steps 1 and 2 under vertical installation
section, pages 15-16.
Step 2.
Remove shingles or other roof covering as necessary to cut
the rectangular hole for the support box. Cut the hole 1/8 in.
(3mm) larger than the support box outline.
Step 3.
Lower the support box through the hole in the roof until the
bottom of the support box protrudes at least 2 in. (51mm)
below the ceiling (Figure 5.18). Align the support box both
vertically and horizontally with a level. Temporarily tack the
support box in place through the inside walls and into the
roof sheathing.
Figure 5.19
LEVEL
CATHEDRAL CEILING
SUPPORT BOX
2 in. (51mm)
MIN. BELOW
FINISHED
CUT HOLE 1/8 in.
(3mm) GREATER IN
SIZE THAN PATTERN
OF SUPPORT BOX AS
IT IS PROJECTED
ONTO ROOF LINE
Figure 5.18
CEILING
Step 4.
Using tin snips, cut the support box from the top corners
down to the roofline, and fold the resulting flaps over the
roof sheathing (Figure 5.19). Before nailing it to the roof,
run a bead of non-hardening mastic around the top edges
of the support box to make a seal between it and the roof.
Clean out any combustible material from inside the support
box.
Step 6.
Place the support clamp (provided with the support box)
inside the support box (at the bottom), and secure to the pipe
section. The clamp allows the support box to support the
weight of the pipe sections. Continue to add pipe sections
until you are above the roofline.
Step 7.
Complete the cathedral ceiling installation by following the
same procedures outlined in steps 7 through 9 for vertical
installations, page 17.
Step 8.
Install the black trim collar around the outside of the cathedral
ceiling support box (Figure 5.20). The two pieces of the trim
collar slide over one another to allow for easy adjustment
around the support box. Using the six screws provided,
secure the four corners and the overlapping sections of the
trim collar to the ceiling. Y ou may want to predrill the holes for
the overlapped sections for ease of installation.
TRIM COLLAR
Step 5.
Assemble the desired lengths of pipe and elbows necessary
to reach from the appliance up through the round support
box. Ensure that all pipe and elbow connections are in their
fully twist-locked position. Assemble as instructed.
Page 18
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Figure 5.20
CATHEDRAL
CEILING
SUPPORT
BOX
SCREWS
10/08
3. Class A Metal Chimney
EXISTING
METAL CHIMNEY
SYSTEM
DIRECT
VENT PIPE
TERMINATION
CAP
TOP
ADAPTOR
FLASHING
4 in. (102mm)
FLEX PIPE
RETRO
CONNECTOR
Step 4.
Pass the flex pipe down through the center of the chimney
system, and center the top adapter on the top of the chimney
pipe. Drill four 1/8 in. (3mm) diameter holes through the
top adapter, and into the chimney top. Ensure that you are
drilling into the metal on the chimney. Twist lock the high
wind termination cap onto the top adapter (Figures 5.23
and 5.24).
Figure 5.21
CAUTION
Ensure that existing chimney is functionally sound and clean.
• Have inspection done by qualified chimney sweep or
professional installer BEFORE converting to direct vent
appliance.
Step 1.
Remove existing chimney cap.
Step 2.
Measure the distance from the top of the chimney to the
bottom of the ceiling support box, add 3 in. (76mm) to this
measurement, and cut a section of 4 in. (101mm) flex pipe
to that length (the flex should be fully extended).
Step 3.
Connect the end of the flex pipe section to the underside
of the top adapter, using four sheet metal screws (Figure
5.22).
Top Adapter
Figure 5.23
HIGH WIND
TERMINATION
CAP
SHEET METAL
SCREWS
DRILL FOUR 1/8 in.
(3mm) DIAMETER
HOLES
Figure 5.24
Step 5.
Pull the flex pipe down through the ceiling support box, until
it protrudes approximately 3 in. (76mm). Connect the flex
pipe to the retro connector, and attach with sheet metal
screws.
Flex
Pipe
Sheet Metal Screws
Figure 5.22
10/08
Step 6.
Push the flex pipe back up into the ceiling support box,
center the retro connector, and attach it to the support box
with sheet metal screws.
Step 7.
The connection between the appliance and the retro
connector may be completed with sections of direct vent
pipe.
Page 19Quadra-Fire • Columbia Bay • 250-5195 Rev. K
4. Existing Masonry Chimney
TERMINATION
CAP
STUDWALL
10 in. x 10 in. (254mm x 254mm)
FRAMED OPENING IN WALL
RETRO CONNECTOR
MASONRY
CHIMNEY
TOP ADAPTOR
RETRO CONNECTOR
90 DEGREE
ELBOW
DIRECT VENT PIPE
Figure 5.25
CAUTION
FLASHING
4 in. (102mm)
FLEX LINER
WALL THIMBLE
FOUR MASONRY BOLTS
(NOT INCLUDED)
Figure 5.26
COVER
Step 3.
Secure the flashing to the top of the masonry chimney using
a bead of non-hardening sealant-adhesive. If the flashing is
larger than the top of the chimney, cut and fold flashing as
needed to fit chimney (Figure 5.27).
CUT AND BEND FLASHING AS
NEEDED TO FIT CHIMNEY
Ensure that existing chimney is functionally sound and clean.
• Have inspection done by qualified chimney sweep or
professional installer BEFORE converting to direct vent
appliance.
Step 1.
Before cutting any holes, assemble the desired sections
of direct vent pipe to determine the center of the masonry
penetration.
Step 2.
Once the center point of the penetration has been determined,
cut a 6 in. (152mm) diameter hole in the masonry. If the hole
is too large, the retro connector might not mount properly; if
the hole is too small, the appliance might starve for intake
air. If there is a frame wall in front of the masonry wall, cut
and frame a 10 in. (254mm) square opening in the wall
(centered around the 6 in. (152mm) masonry opening). If
there is sheet rock only (no studs) in front of the masonry the
10 in. (254mm) opening is still needed, but does not need
to be framed. If the hole is framed a wall thimble is required.
This allows the retro connector to mount directly on the
masonry and provide the correct clearances to combustibles
(Figure 5.26).
SEALANT-ADHESIVE
Figure 5.27
Step 4.
To determine the length of flex needed, measure from 3 in.
(76mm) above the top of the flashing down to the level of the
opening. Add the distance from the center of the chimney
out through the wall. Cut a piece of 4 in. (102mm) flex to this
length (extended to its nominal length). Be sure to leave 2-3
in. (51-76mm) of flex above the existing chimney to allow for
connection to the termination kit.
Step 5.
Connect the flex liner to the top adapter using three sheet
metal screws (Figure 5.22, page 19).
Step 6.
Feed the flex liner through the flashing into the chimney.
Carefully feed the flex liner down the chimney to the bottom
and out the opening in the masonry wall, forming an angle to
line up the flex liner with the vent opening on the appliance.
Page 20
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
WARNING
Fire Risk.
Explosion Risk.
Do not let the fl ex liner sag below the level at
•
which it will connect to the appliance or connector.
This could allow hot gas to become trapped and
potentially become a fi re hazard. The fl ex liner path
should always be sloped up toward the termination
cap.
Step 7.
If additional lengths of flex liner are needed to span the
chimney height, use a flex coupler to connect the pieces of
flex liner together. Connect the flex to the coupler by using
four sheet metal screws for each side (Figure 5.28).
FLEX LINER
FLEX COUPLER
Step 9.
Attach the flex to the retro connector. Use three sheet metal
screws to attach the flex liner to the connector (Figure
5.30). Mount the retro connector to the masonry wall using
masonry bolts. Redrill larger holes on connector as needed.
Be careful to ensure that the connector is centered in the
opening and the mounting holes line up with the masonry
wall.
6 in. (152mm)
DIAMETER
OPENING IN
MASONRY
WALL
RETRO CONNECTOR
THREE MASONRY BOLTS
Figure 5.30
(NOT INCLUDED)
SHEET METAL
SCREWS
Figure 5.28
Step 8.
Secure the top adapter to the flashing. Use three sheet
metal screws through the side of the top adapter into the
flange on the flashing (Figure 5.29). Twist lock the high
wind termination cap on to the top adapter.
HIGH WIND
TERMINATION CAP
TOP ADAPTOR
THREE SHEET
METAL SCREWS
Step 10.
Slide the wall thimble cover over retro connector and secure
with masonry bolts (Figure 5.31). If you have a framed wall
in front of the masonry, use wood screws to mount wall
thimble cover to framed wall, over retro connector and 10
in. (254mm) square framed opening (Figure 5.26, page
20). If needed, add a section of direct vent pipe to the retro
connector in order to extend through the opening in the wall
thimble cover.
RETRO CONNECTOR
WALL THIMBLE COVER
FOUR MASONRY BOLTS
(NOT INCLUDED)
Figure 5.31
Figure 5.29
FLASHING
10/08
Step 11.
The connection between the appliance and the retro
connector may be completed with sections of direct vent
pipe.
Page 21Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Gas Information
6
A. Fuel Conversions
Before making gas connections ensure that the appliance
being installed is compatible with the available gas type.
Any natural or propane gas conversions necessary to meet
the appliance and locality needs must be made by a qualifi ed technician using Hearth & Home T echnologies specifi ed
and approved parts.
1. Converting to LP Gas
NOTE: Gas conversions should only be performed
by a qualified service person, and/or where required
by state and local codes, licensed installer/service
technician. In the Commonwealth of Massachusetts,
installation must be performed by a licensed plumber
or gas fitter.
Phillips bit; 5/32 in. Allen wrench; 5/8 in. open-end wrench.
Disconnect power and turn off gas supply if installed.
Remove the front, glass, brick refractory and logs if installed.
(It is only necessary to remove the left brick panel for burner
removal. The metal brick refractory does not need to be
removed.)
Opens Left
:
Power drill (a 90° handle is helpful); #2
Closes Right
Figure 6.2 Lift the burner from the left side and slide left until
free from the orifi ce receiver. Remove from the fi rebox and
handle with care.
Figure 6.3
Replace with appropriate orifi ce.
With a 5/8 in. wrench remove orifi ce retaining nut.
PROPANENATURAL GAS
.0635 (52 DMS).1065 (36 DMS)
If the shutter is removed with the burner as indicated in
Figure 6.2, it must be reinstalled over the orifi ce prior to the
reinstallation of the burner.
Figure 6.1 Loosen the shutter adjustment nut (located under-
neath the appliance) with a 7/16 in. wrench.
It is helpful to remove the nut completely . Slide the shutter to
the right (closed position).
Page 22
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Figure 6.4
in. allen wrench, remove the pilot injector and replace with an
appropriate injector (35 LP, 62 NG).
Reinstall the burner, and reassemble the appliance.
Remove the pilot hood, and set aside. Using a 5/32
10/08
2. Valve Regulator Replacement
WARNING
Fire Risk.
Explosion Risk.
•Disconnect any electrical cords and
turn off gas supply to unit before
proceeding if converting fuel on an
appliance already fully installed.
E
D
Remove upper and lower back shield. Loosen the set collars on the extension rods with the 3/32 in. Allen wrench.
Remove the rods and adapter cap.
A
B
C
Figure 6.5 Turn control knob to the OFF position, ensure that
gas supply to the valve has been turned off. Using a Torx
TH20, or slotted screwdriver, remove the three pressure regulator mounting screws (A), pressure regulator tower (B),
and diaphragm (C).
F
Figure 6.6 Ensure that the rubber gasket (D) is properly posi-
tioned and install the new HI/LO pressure regulator assembly to the valve using the new screws (E) supplied with the
kit. Tighten screws securely. (Reference torque = 25 in./lb.)
Install the enclosed identifi cation label (F) to the valve body
where it can be seen.
Fill out the conversion label and attach it to the valve cover.
WARNING
Fire Risk.
Explosion Risk.
Gas Leak Risk.
• Rubber gasket must be seated properly on valve
face.
• Do no install a valve or regulator that has been
dropped.
WARNING
Fire Risk.
Explosion Risk.
•If the information in these instructions is
not followed exactly, a fi re, explosion or
production of carbon monoxide may result
causing property damage, personal injury
or loss of life.
• The qualifi ed service agency is responsible
for the proper installation of this conversion
kit. The installation is not proper and
complete until the operation of the converted
appliance is checked as specifi ed in the
manufacturer’s instructions supplied with
the kit.
10/08
Page 23Quadra-Fire • Columbia Bay • 250-5195 Rev. K
B. Gas Pressures
Proper input pressures required for optimum appliance performance, gas line sizing requirements need to be followed
from NFPA54.
WARNING
Fire Risk.
Explosion Hazard.
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 1/2 psig.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 1/2 psig.
C. Gas Connection
NOTE: Have the gas supply line installed in accordance with
local building codes, if any. If not, follow ANSI Z223.1. Installation should be done by a qualifi ed installer approved and/or
licensed as required by the locality. (In the Commonwealth of
Massachusetts, installation must be performed by a licensed
plumber or gas fi tter.)
NOTE: A listed (and Commonwealth of Massachusetts
approved) 1/2 inch (13mm) T-handle manual shut-of f valve and
fl exible gas connector are connected to the 1/2 inch (13mm)
control valve inlet.
• If substituting for these components, please consult local
codes for compliance.
WARNING
Verify inlet pressures.
• High pressure may cause overfire
condition.
• Low pressure may cause explosion.
Install regulator upstream of valve if line pressure
is greater than 1/2 psig.
Pressure requirements for appliance are shown in the table
below.
3) that the total gas load for the residence does not exceed
the amount supplied.
The supply regulator (the regulator that attaches directly to the
residence inlet or to the propane tank) should supply gas at
the suggested input pressure listed above. Contact the local
gas supplier if the regulator is at an improper pressure.
WARNING
Gas Leak Risk.
• Support control when attaching pipe to
prevent bending gas line.
NOTE: The gap between the supply piping and gas access
hole may be plugged with non-combustible insulation to prevent
cold air infi ltration.
Leak test all gas line joints and the gas control valve prior
to and after starting the fi replace.
Before making the gas connection, ensure that the appliance
you are installing is designed for the type of gas being
supplied. This information can be found on the Ratings Label
under the appliance. If the appliance has been converted to
propane (LP), the valve cover should have a label stating
that the unit has been converted to propane.
Connect the gas line at the 3/8 in. (9.5mm) pipe connector
on the valve at the back of appliance. We recommend
connecting the appliance with an approved flex gas line.
If flex gas lines are not approved in your area, you must
connect a hard pipe to the gas hookup.
You must supply a manual shut-off valve in a visible location
within 3 feet (914mm) of the appliance.
Page 24
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
WARNING
Fire or Explosion Hazard
• Gas build-up during line purge may ignite.
• Purge should be performed by qualifi ed technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as
sparks or open fl ame.
A small amount of air will be in the gas supply lines. When
•
fi rst lighting appliance it will take a short time for air to
purge from lines. When purging is complete the appliance
will light and operate normally.
Air only needs to be purged again if gas valve has been
turned to the OFF position.
WARNING
CHECK FOR GAS LEAKS
Explosion Risk
Fire Risk
Asphyxiation Risk
• Check all fi ttings and connections.
• Do not use open fl ame.
• After the gas line installation is complete, all
connections must be tightened and checked
for leaks with a commercially-available,
non-corrosive leak check solution. Be sure
to rinse off all leak check solution following
testing.
Fittings and connections may have loosened
during shipping and handling.
Omni-Test Laboratories listed gas appliances are tested
and approved without requiring changes for elevations
from 0 to 2000 feet in the U.S.A. and 0 to 4500 feet in
Canada.
When installing this appliance at an elevation above 2000
feet, it may be necessary to decrease the input rating by
changing the existing burner orifi ce to a smaller size. Input
rate should be reduced by 4% for each 1000 feet above a
2000 foot elevation in the U.S.A. If the heating value of the
gas has been reduced, these rules do not apply . T o identify
the proper orifi ce size, check with the local gas utility.
If installing this appliance at an elevation above 4500 feet
(in Canada), check with local authorities.
WARNING
Fire hazard.
Do NOT change the valve settings.
• This valve has been preset at the factory.
• Changing valve settings may result in fi re
hazard or bodily injury.
10/08
Page 25Quadra-Fire • Columbia Bay • 250-5195 Rev. K
7
This appliance is equipped with a three
pronged (grounding) plug for your protection
against shock hazard and should be plugged
directly into a prop
Electrical Information
A. Recommendation for Wire
See B5 below for recommended maximum lead length (two
wire) when using wall thermostat/switch.
NOTE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code, CSA
C221.1.
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when
it is installed in locations such as in bathrooms or near
sinks.
B. Connecting to the Appliance
WARNING
Wire 110v to electrical junction box.
Do NOT wire 110v to the valve.
Do NOT wire 110V to wall switch.
• Incorrect wiring will damage millivolt
systems.
8. Ensure the thermostat is mounted level for accurate
readings.
9. The thermostat should be mounted on an inside wall
and not in direct line with the appliance convection air.
10. If the thermostat is located too close to the appliance,
you may need to set the temperature setting slightly
higher to maintain the desired temperature in your
home.
Do not connect this appliance to a thermostat serving
any other appliance.
Bedroom installation in Canada requires this appliance
to be connected to a thermostat.
WARNING
Shock hazard.
•
This appliance is equipped with a three
pronged (grounding) plug for your protection
against shock hazard and should be plugged
directly into a properly grounded three prong
receptacle. Do not cut or remove the grounding
prong from this plug.
1. This appliance may be used with a wall switch, wall
mounted thermostat and / or a remote control.
2. If using thermostat, use one compatible with a millivolt
gas valve system.
3. Follow parameters for locating thermostat (see individual thermostat instructions) to ensure proper operation
of appliance.
4. Use low resistance thermostat wire for wiring from ignition system to the wall switch and thermostat.
6. Keep wire lengths as short as possible by removing
any excess wire length.
C. Standing Pilot Ignition System Wiring
This appliance DOES NOT require 110 VAC supply for
operation. A wiring diagram is shown in Figure 7.1 on the
next page.
This appliance is equipped with a millivolt control valve.
7. Low voltage and 110 VAC voltage cannot be shared
within the same wall box.
Page 26
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
Figure 7.1
O
F
F
P
I
L
O
T
O
N
TP
TH
TPTH
L
O
HI
EA
P
I
L
O
T
IGNITOR
ON/OFF
SWITCH
Red 28 in.
(711MM)
Red 28 in.
(711MM)
THERMOPILE
THERMOCOUPLE
GAS PILOT IGNITOR
VALVE
CAUTION
Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
CAUTION
Shock hazard.
• Replace damaged wire with type 105O C
rated wire.
• Wire must have high temperature insulation.
10/08
Page 27Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Appliance Setup
8
A. Remove Shipping Materials
Remove shipping materials from inside or underneath the
fi rebox.
B. Accessories
Install approved accessories per instructions included with
accessories. Refer to Section 12 for appropriate accessories.
WARNING
Shock or fi re risk.
Use ONLY optional accessories approved for
this appliance.
• Using non-listed accessories voids
warranty.
• Using non-listed accessories may result in a
safety hazard.
• Only Hearth & Home T echnologies approved
accessories may be used safely.
C. Door Crown Installation
2 Screws
Figure 8.2 Set the replacement gold crown in place, reinsert
screws and tighten.
IMPORTANT! PREVENT PERMANENT STAINING!
Use a soft cloth and a window cleaning solution to clean
all fingerprint oils from the gold or nickel surface of crown
PRIOR to lighting the appliance.
D. Brick Installation
TOOLS REQUIRED: Phillips head screwdriver.
REMOVAL OF METAL REFRACTORY BRICK
2 Screws
Figure 8.1 Remove the door from the appliance. Remove
the existing black crown by removing the four screws on the
back side of the face, and pull the crown off the door.
Page 28
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Figure 8.3 To remove existing metal refractory remove the
two screws located on the left and the two on the right sides
behind the side curtains.
10/08
Figure 8.4 Holding both sides of the metal refractory brick
piece, pull slightly together and rotate out of the firebox.
INSTALL NEW BRICK SET
E. Positioning the Logs
While still breakable, the logs do not become fragile until
after the appliance is burned and they have cured. After
curing, any handling must be done with care as breakage
can easily occur.
PLEASE NOTE: Logs have been designed to work
specifically with the burner of this appliance. Exact
placement will ensure proper operation of your gas
appliance and reduce sooting.
1
4
23
Figure 8.5 Install rear panel, gently wedging it between sup-
port shelf and baffle base. Install the brick brackets that are
enclosed with the brick set.
Figure 8.6 Install the left and right brick panels. Use the screw
placement shown in Figure 8.3 to secure them in place.
Reassemble appliance.
Figure 8.7 The three piece log set is packed in the compo-
nents box and consists of the following:
Qty.Description#
1Rear Log1
1Left Front Log2
1Right Front Log3
1Twig4
Page 29Quadra-Fire • Columbia Bay • 250-5195 Rev. K
that gas can contact them on all sides. Avoid stacking the
embers on top of each other.
NOTE: Do not block gas ports.
G. Glass Door Replacement
Remove the grille: Slide the grille out of the slots in the existing door.
Figure 8.9 Place right and left front logs on
provided
Figure 8.10
on the burner surface.
Place twig over the locator pin on the rear log,
burner in the grooves
gently laying the log across the two front logs. To complete
your log set application reinstall the front of the unit.
F. Mineral Wool
WARNING
Remove the existing door from the appliance.
Remove the crown from the existing door by removing four
screws on the back side of the door assembly. Pull crown
off door face.
Install replacement door with glass onto appliance.
Reinstall the crown.
Reinstall the grille onto the new door assembly.
CAUTION
Handle glass assembly with care.
• Inspect the gasket to ensure it is undamaged.
• Inspect the glass for cracks, chips or
scratches.
• Do NOT strike, slam or scratch glass.
• Do NOT operate appliance with glass door
removed, cracked, broken or scratched.
• Replace glass assembly as a complete
assembly.
Explosion Risk.
• Follow ember placement instructions in
manual.
• Do NOT place embers directly over
burner ports.
• Replace ember material annually.
Improperly placed embers interferes with proper burner
operation.
Figure 8.11 Place individual pieces of embers in front of and
around the gas log where they can be seen. Space them so
Page 30
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
H. Blower Installation
Turn off power supply.
INCLUDED IN KIT: Blower; 2 female spade wire connectors.
OOLS REQUIRED: Phillips head screwdriver.
T
Blower motor comes standard with 2 male spade wire
connectors. If your appliance has a different connection, use the two female spade wire connectors provided
to modify the appliance wiring harness.
Snap Disk
F
BLACK
F
BLACK
F = Female
M = Male
Remove blower housing from appliance, if necessary.
Disassemble housing if needed, retaining all fasteners, and
remove the blower.
Reassemble blower in housing using fasteners previously
removed.
Reinstall blower housing to appliance.
Turn power supply back on.
Fan Speed
WHITE
WHITE
BLACK
BLACK
Control
F
M
BLACK
Fan Assembly
Figure 8.12 Blower Wiring Diagram
BLACK
M
F
Ground
F
M
GRN
BLACK
WHITE
Strain Relief Bushing
Power Cord (110 VAC)
10/08
Page 31Quadra-Fire • Columbia Bay • 250-5195 Rev. K
I. Vertical Damper Adjustment
Refer to the vent graph on page 11. If your installation falls
within the range of the gray shaded area of graph, it may be
necessary to make an adjustment to the vertical damper to
improve the flame appearance in your appliance.
Figure 8.13The vertical damper adjustment is located on the
right side of the unit behind the side curtain. The damper is
centered towards the top of the unit.
Loosen screws using a Phillips screwdriver.
J. Shutter Adjustment
OPEN
Figure 8.14 The shutter is located on the underside of the
appliance, on the right side. To adjust the shutter, loosen
the wingnut.. Retighten the wingnut after adjustment.
Moving the shutter bolt to the right closes the shutter. Moving
the shutter bolt to the left, will open the shutter. Opening the
shutter causes flames to become shorter and blue. Closing
the shutter creates taller orange/yellow flames.
NOTE: Do not close so much as to cause a sooty flame.
Improper adjustment can cause sooting in the firebox and/or
on the outside of a house with a horizontal termination.
CLOSE
Pivot the vertical damper adjustor in 1/4 in. increments while
observing the flame activity.
Turn clockwise to open the damper = less flame height and
more blue in flame color.
Turn counterclockwise to close damper = increased flame
height and more yellow in flame color.
Make adjustment until flame size and activity suits your
personal preference, and then retighten screws on
adjustment control.
NOTE: In the Commonwealth of Massachusetts, the word
damper shall be replaced with the words flue restrictor.
After adjustment, tighten nut to lock in place.
Page 32
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
Operating Instructions
9
A. Before Lighting Appliance
Read this entire manual prior to using the appliance. Failure
to follow the instructions may result in property damage,
bodily injury, or even death.
•Remove all shipping materials from inside and/or
underneath the fi rebox.
•Review proper placement of logs, mineral wool.
•Check the wiring.
•Check the baffl e adjustment.
•Ensure that there are no gas leaks.
•Ensure that the glass is sealed and in the proper posi-
tion.
•Ensure that the fl ow of combustion and ventilation air
is not obstructed (front grilles and vent caps).
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. Refer to
the owner’s information manual provided with this appliance.
For assistance or additional information consult a qualifi ed
installer, service agency or the gas supplier.
WARNING
Do NOT use this appliance if any part has been under water.
Immediately call a qualifi ed service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
B. Controls
WARNING
Glass door must be in place when appliance is
operating.
Risk of:
• Combustion Fumes
• Fire
Do NOT operate appliance with glass door
removed.
• Open viewing glass for servicing only.
• Glass door MUST be in place and sealed before
operating appliance.
• Only use glass door certifi ed for use with appliance.
• Glass replacement should be done by qualifi ed
technician.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• Do not touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fi replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable
materials.
• Keep clothing, furniture, draperies and other fl ammable
materials away.
FAN SPEED: This knob controls the speed of the blower
that pushes the heated air into the room.
MAIN BURNER: This control is used to turn the appliance
on and off.
PILOT IGNITOR: The pilot ignitor is used only to start
the pilot. When the valve control knob is turned to the
pilot position and fully depressed press the piezo ignitor
repeatedly creating a blue spark directly next to the pilot,
igniting the pilot flame.
VALVE CONTROL: This knob is used to control gas to
the appliance and for starting the pilot. There are three
positions, ON, OFF, & PILOT. The indicator on the valve
indicates the position of the knob.
COMFORT CONTROL: This knob controls the flame height
from low (“LO”) to high (“HI”).
NOTE: If using a remote control wall switch, or thermostat,
the On/Off Switch must be left “OFF”. Turning the On/Off
Switch to “ON” will keep the appliance on continually.
10/08
Page 33Quadra-Fire • Columbia Bay • 250-5195 Rev. K
C. Lighting Appliance
FOR YOUR SAFETY READ BEFORE LIGHTING
LIGHTING INSTRUCTIONS
TO TURN OFF GAS TO APPLIANCE
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury or loss of life
A. This appliance has a pilot that must be lit manually. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING, smell around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier
than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
* Do not try to light any appliance.
* Do not touch any electric switch, do not use any phone in your building.
* Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
* If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't
try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to
and to replace any part of the control system and any gas control which has been under water.
inspect the appliance
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Set the thermostat to the lowest setting (if applicable) and turn off
the switch at the control panel.
3. Disconnect the power from the appliance.
4. Open the door of the appliance. May need to remove face/front first.
5. Push in gas control knob slightly and turn clockwise to the "OFF"
position. Do not force.
6. Wait five (5) minutes to clear out any gas. Smell for gas, including near the floor. If you smell gas, STOP! Follow "B" of the
safety information above. If you don't smell gas go to the next step.
7. Push gas control knob in and turn counterclockwise to the pilot position. NOTE: Knob cannot be turned unless knob is
pushed in slightly. Do not force.
8. PIEZO IGNITER:
(This may take many repetitions for lighting.)
ELECTRONIC IGNITER: If the unit is equipped with an electronic igniter it should begin sparking right away.
9. The pilot should be visible through the door opening.
10. After the pilot is lit, continue holding control knob down for approximately
30 seconds. Release the knob and it will pop back up. Pilot should remain lit.
If it goes out, repeat steps 7 through 9.
* If the knob does not pop up when released, stop and immediately call your
service technician or gas supplier.
* If the pilot will not stay lit after several tries, turn the gas control knob
clockwise to "OFF" and call your service technician or gas supplier.
11. Reinstall door and face. Wait five minutes to allow pilot flame to stabilize and
establish proper draft.
12. Push down and turn gas control knob counterclockwise to "ON".
13. Push burner rocker switch on the control panel to "ON". If thermostat is to be used, leave switch in "OFF" position and set the
thermostat to desired setting.
14. Reconnect electrical power to appliance.
Press down on the gas control knob in pilot position and simultaneously press the piezo igniter.
MILLIVOLT
GENERATOR
PILOT HOOD
THERMOCOUPLE
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Push in gas control knob slightly and turn clockwise to "OFF" position.
Page 34
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
D. After Appliance is Lit
Initial Break-in Procedure
When you light your appliance, you may notice that it produces heat which does have an associated odor or smell. If
you feel this odor is excessive it may require the initial three
to four hour continuous burn on high followed by a second
burn up to 12 hours to fully drive off any odor from paint and
lubricants used in the manufacturing process. Condensation
on the glass is normal.
NOTE: The appliance should be run three to four hours
on the initial start-up. Turn it off and let it cool completely.
Remove and clean the glass. Replace the glass and run the
appliance for an additional 12 hours. This will help to cure
the products used in the paint and logs.
During this break-in period it is recommended that some
windows in the house be opened for air circulation. This will
help avoid setting off smoke detectors, and help eliminate
any odors associated with the appliance’s initial burning.
WARNING
Fire Risk.
High Temperatures.
Keep combustible household items away from appliance.
Do NOT obstruct combustion and ventilation air.
• Do NOT place combustible items on top of or in front of
appliance.
• Keep furniture, draperies away from appliance.
CAUTION
• Prevent accidental appliance operation when not
attended.
• Unplug or remove batteries from remote control if absent
or if appliance will not be used for an extended period of
time.
• Property damage possible from elevated temperatures.
CAUTION
Smoke and odors released during initial operation.
• Open windows for air circulation.
• Leave room during initial operation.
• Smoke may set off smoke detectors.
Smoke and odors may be irritating to sensitive individuals.
WARNING
Fire Hazard.
Keep combustible materials, gasoline
and other fl ammable vapors and liquids
clear of appliance.
• Do NOT store fl ammable materials in the appliance’s
vicinity.
• Do NOT use gasoline, lantern fuel, kerosene, charcoal
lighter fl uid or similar liquids in this appliance.
• Combustible materials may ignite.
E. Frequently Asked Questions
ISSUESOLUTIONS
Condensation on the glassThis is a result of gas combustion and temperature variations. As the appliance warms,
this condensation will disappear.
Blue fl amesThis is a result of normal operation and the fl ames will begin to yellow as the appliance
is allowed to burn for 20 to 40 minutes.
Odor from applianceWhen fi rst operated, this appliance may release an odor for the fi rst several hours.
This is caused by the curing of the paint and the burning off of any oils remaining from
manufacturing. If appliance has not been used for some time, dust can build up and
cause an odor.
Film on the glassThis is a normal result of the curing process of the paint and logs. Glass should be
cleaned within 3 to 4 hours of initial burning to remove deposits left by oils from the
manufacturing process. A non-abrasive cleaner such as gas appliance cleaner may be
necessary. See your dealer.
Metallic noiseNoise is caused by metal expanding and contracting as it heats up and cools down,
similar to the sound produced by a furnace or heating duct. This noise does not affect
the operation or longevity of the appliance.
10/08
Page 35Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Troubleshooting
10
With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do
experience a problem, this troubleshooting guide will assist a qualifi ed service person in the diagnosis of a problem and the
corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed service technician.
SymptomPossible CauseCorrective Action
1. After repeated triggering of the piezo
button, the spark ignitor
will not light the pilot.
2. The pilot will not stay
lit after carefully following the lighting instructions.
a. Defective ignitor.Check the spark at the electrode and pilot. If no spark and electrode
wire is properly connected, replace the ignitor.
b. Defective pilot or
misaligned electrode
(spark at electrode).
c. No gas or low gas
pressure.
d. No LP in tank.Check the LP (propane) tank. You may be out of fuel.
a. Defective thermo-
couple.
Using a match, light the pilot. If the pilot lights, turn off the pilot and
trigger the piezo button again. If the pilot lights, an improper gas/air
mixture caused the bad lighting and a longer purge period is recommended. If the pilot will not light, ensure the gap at the electrode and
pilot is one-eighth (1/8) inch to have a strong spark. If the gas is OK,
replace the pilot.
Check the remote shut-off valve from the appliance. Usually, there is
a valve near the gas main. There can be more that one (1) valve from
the appliance and the main.
Check that the pilot fl ame impinges on the thermocouple. Clean and /or
adjust the pilot for maximum fl ame impingement.
Ensure that the thermocouple connection at the gas valve is fully
inserted and tight (hand tighten plus 1/4 turn).
3. The pilot is burning,
there is no gas to the
burner, the valve knob is
in the ON position, and
the ON/OFF switch is in
the ON position.
Disconnect the thermocouple from the valve, place one millivolt lead
wire on the tip of the thermocouple and the other meter wire on the
thermocouple copper lead. Start the pilot and hold the valve knob in. If
the millivolt reading is less than 15mV, replace the thermocouple.
b. Defective valve.If the thermocouple is producing more than 15 millivolts, replace faulty
valve.
a. ON/OFF switch or
wires defective.
b. Thermopile may
not be generating
suffi cient millivoltage.
Check the ON/OFF switch and wires for proper connections. Place the
jumper wires across the terminals at the switch. If the burner comes on,
replace the defective switch. If the switch is OK, place the jumper wires
across the switch wires at the gas valve. IF the burner comes on, the
wires are faulty or connections are bad.
If the pilot fl ame is not close enough physically to the thermopile, adjust
the pilot fl ame.
Be sure the wire connections from the thermopile at the gas valve terminals are tight and that the thermopile is fully inserted into the pilot
bracket.
Check the thermopile with a millivolt meter. Take the reading at TH-TP
& TP terminals of the gas valve. The meter should read 325 millivolts
minimum, while holding the valve knob depressed in the pilot position,
with the pilot lit, and the ON/OFF switch in the OFF position. Replace
the faulty thermopile if the reading is below the specifi ed minimum.
With the pilot in the ON position, disconnect the thermopile leads from
the valve. Take a reading at the thermopile leads. The reading should
be 325 millivolts minimum. Replace the thermopile if the reading is
below the minimum.
Page 36
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
SymptomPossible CauseCorrective Action
3. (Continued)c. Defective valve.Turn the valve knob to the ON position. Place the ON/OFF switch in the
ON position. Check the millivolt meter at the thermopile terminals. The
millivolt meter should read greater than 125mV . If the reading is acceptable, and if the burner does not come on, replace the gas valve.
d. Plugged burner
orifi ce.
e. Wall switch or
wires are defective.
4. Frequent pilot outage
problem.
a. Pilot fl ame may
be too high or too
low, or blowing
(high), causing safety
pilot to drop out.
5. The pilot and main
burner extinguish while
in operation.
a. No LP in tank.Check the LP (propane) tank. Refi ll the fuel tank.
b. Inner vent pipe
leaking exhaust
gases back into the
system.
c. Horizontal vent
improperly pitched.
d. Bad thermopile or
thermocouple.
e. Improper vent cap
installation.
6. Glass soots.a. Flame impinge-
ment.
b. Improper shutter
setting.
c. Debris around
opening at base of
burner.
7. Flame burns blue
and lifts off burner.
a. Insuffi cient
oxygen being supplied.
Check the burner orifi ce for stoppage. Remove stoppage.
Follow the corrective action in Symptom and Possible Cause 1.a.
Check the switch and wiring. Replace where defective.
Clean and adjust the pilot fl ame for maximum fl ame impingement on
thermocouple. Follow lighting instructions carefully.
Check for proper vent connection at fl ue collar and all vent joints.
The horizontal vent cap should slope down only enough to prevent any
water from entering the appliance.
Replace if necessary.
Check for proper installation and freedom from debris or blockage.
Adjust the log set so that the fl ame does not excessively impinge on it.
Check that logs are placed according to installation instructions.
Adjust the air shutter at the base of the burner.
Inspect the opening at the base of the burner. NO MATERIAL SHOULD
BE PLACED IN THIS OPENING.
Ensure that the vent cap is installed properly and free of debris. Ensure
that the vent system joints are tight and have no leaks.
Ensure that no debris has been placed at the base of, or in the area of
the air holes in the center of the base pan beneath the burner.
10/08
Ensure that the glass is tightened properly on the appliance, particularly on top corners.
Page 37Quadra-Fire • Columbia Bay • 250-5195 Rev. K
Maintaining and Servicing Your Appliance
11
Although the frequency of your appliance servicing and
maintenance will depend on use and the type of installation,
a qualifi ed service technician should perform an appliance
check-up at the beginning of each heating season.
WARNING
Risk of injury or property damage.
Before servicing:
• Turn off gas.
• Turn off electricity to appliance.
• Ensure appliance is completely cooled.
After servicing:
• Replace front and glass, if removed.
• Reseal and reinstall any venting removed for servicing.
WARNING
Annual inspection by qualifi ed technician recommended.
Check:
• Condition of glass, glass assembly and glass seal.
• Obstructions of combustion and ventilation air.
• Obstructions of termination cap.
• Burner ignition and operation.
• Burner air shutter adjustment
• Gas connections and fi ttings.
Clean:
• Glass
• Air passageways, grilles,
control compartment
• Burner, burner ports. USE CAUTION WHEN CLEANING/
HANDLING CERAMIC BURNER.
Risk of:
• Fire
• Delayed ignition or explosion
• Exposure to combustion fumes
• Odors
CAUTION
Handle glass assembly with care.
NOTE: Clean glass after initial 3-4 hours
operation. Longer operation without cleaning
glass may cause a permanent white fi lm on
glass.
When cleaning glass door:
• Avoid striking, scratching or slamming glass.
• Do NOT use abrasive cleaners.
• Use a hard water deposit glass cleaner on white fi lm.
• Do NOT clean glass when hot.
• T urn of f appliance after 3-4 hours of operation and ALLOW
TO COOL.
• Remove and clean glass assembly.
• Replace glass assembly and operate appliance for additional
12 hours.
Refer to maintenance instructions.
WARNING
Inspect external vent cap regularly.
• Ensure no debris blocks cap.
• Combustible materials blocking cap may
ignite.
• Restricted air fl ow affects burner operation.
Page 38
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
A. Maintenance Tasks
InspectMaintenance Tasks
Doors1. Inspect for scratches, dents or other damage and repair as necessary.
2. Verify no obstructions to air fl ow.
3. Verify maintenance of proper clearance to combustible household objects.
Gasket Seal, Glass
Assembly and Glass
Valve Compartment
and Firebox Top
Logs1. Inspect for broken, damaged, or missing logs. Replace as necessary.
Firebox1. Inspect for paint condition, warpage, corrosion or perforation. Sand and repaint as neces-
Burner Ignition and
Operation
Venting1. Inspect venting for blockage or obstruction such as bird nests, leaves, etc.
Remote Controls1. Verify operation of remote.
1. Inspect gasket seal and its condition.
2. Inspect glass for scratches and nicks that can lead to breakage when exposed to heat.
3. Confi rm there is no damage to glass or glass frame, Replace as necessary.
4. Verify that latches engage properly and glass attachment components are intact and operating properly. Replace as necessary.
5. Clean glass. Replace glass assembly if severely coated with silicate deposits that cannot be
removed.
1. Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these
areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.
2. Remove any foreign objects.
3. Verify unobstructed air circulation.
2. Verify correct log placement and no fl ame impingement causing sooting. Correct as neces-
sary.
sary.
2. Replace appliance if fi rebox has been perforated.
1. Verify burner is properly secured and aligned with pilot or igniter.
2. Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if
necessary. USE CAUTION WHEN CLEANING/HANDLING CERAMIC BURNER.
3. Replace ember material with new dime-size and shape pieces. Do not block ports or obstruct
lighting paths.
4. Check for smooth lighting and ignition carryover to all ports. Verify there is no ignition delay.
5. Inspect for lifting and other fl ame problems.
6. Inspect orifi ce for soot, dirt or corrosion.
7. Verify manifold and inlet pressures. Adjust regulator as required.
8. Inspect pilot fl ame strength. Clean or replace orifi ce as necessary.
9. Inspect thermocouple/thermopile sensor rod for soot, corrosion and deterioration. Clean with
emery cloth or replace as required.
10. Verify millivolt output. Replace as necessary.
2. Confi rm that termination cap remains clear and unobstructed by plants, etc.
3. Verify that termination cap clearance to subsequent construction (building additions, decks,
fences or sheds) has been maintained.
4. Inspect for corrosion or separation.
5. Verify weather stripping, sealing and fl ashing remains intact.
2. Replace batteries in remote transmitters and battery-powered receivers.
10/08
Page 39Quadra-Fire • Columbia Bay • 250-5195 Rev. K
B. Service and Maintenance Log
Date of ServicePerformed ByDescription of Service
Page 40
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
Reference Materials
12
A. Appliance Dimension Diagram
Dimensions are actual appliance dimensions. Use for reference only. For clearances refer to Section 3.
Page 41Quadra-Fire • Columbia Bay • 250-5195 Rev. K
B. Vent Components Diagram
9-7/16 in.
240 mm
SLP45
6-5/8 in.
168 mm
13-1/4 in.
7-1/4 in.
184 mm
6-9/16 in.
167 mm
337 mm
6-5/8 in.
168 mm
6-9/16 in.
167 mm
6-5/8 in.
168 mm
5-1/4 in.
133 mm
6 in.
152 mm
SLP4
6-5/8 in.
168 mm
6-9/16 in.
167 mm
6-5/8 in.
168 mm
9-3/4 in.
248 mm
6-1/2 in.
165 mm
SLP90
7-1/4 in.
184 mm
6-9/16 in.
167 mm
9-1/4 in.
235 mm
6-5/8 in.
168 mm
SLP6
6-5/8 in.
168 mm
13-1/4 in.
337 mm
SLP6A
6-5/8 in.
168 mm
6-9/16 in.
167 mm
SLP12
25-1/4 in.
641 mm
SLP12A
6-5/8 in.
168 mm
6-9/16 in.
167 mm
SLP24
37-1/4 in.
946 mm
6-5/8 in.
168 mm
6-9/16 in.
167 mm
SLP36
49-1/4 in.
1251 mm
6-9/16 in.
167 mm
SLP48
Note: Pipes overlap 1-3/8 inches (34.93 mm) at each joint.
Figure 12.2 SLP Series Vent Components
Page 42
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
C. Vent Components List
COMPONENTS
SLP-WT-BKCeiling Support / Wall Thimble, Black
SLP-CCS-BKCathedral Ceiling Support, Black
SLP6-BK6 inch Pipe Length, Black
SLP4-BK9 inch Pipe Length, Black
SLP12-BK12 inch Pipe Length, Black
SLP34-BK24 inch Pipe Length, Black
SLP36-BK36 inch Pipe Length, Black
SLP48-BK48 inch Pipe Length, Black
SLP6A-BK11 inch - 14-5/8 inch Pipe Length, Black
SLP12A-BK12 inch - 17 inch Pipe, Adjustable, Black
SLP45-BK45 degree Elbow, Black
SLP90-BK90 degree Elbow, Black
SLP44 inch Pipe
SLP66 inch Pipe
SLP1212 inch Pipe
SLP2424 inch Pipe
SLP3636 inch Pipe
SLP4848 inch Pipe
SLP4545 degree Elbow
SLP9090 degree Elbow
SLP6A3-6 in. Adjustable Pipe Extension
SLP12A3-12 in. Adjustable Pipe Extension
SLP-RF60/12 - 6/12 Roof Flashing
SLP-RF127/12 - 12/12 Roof Flashing
SL-SCDStorm Collar
SLP-FSCeiling Firestop
SLP-WSWall Firestop
SLP-HVSPipe Support Hanger
950Vinyl Protector Kit - SL Pipe
DRC-RADIUSDecorative Radius Cover
HTI-DV-WTWall Thimble
RF4-8Roof Flashing
TERMINATION KITS
SLP-TRAP2Trapezoid Termination Kit
SLP-TVHWVertical Termination Cap - High Wind
SLP-SK-BKHorizontal Termination Kit (includes 904B,
930D, SLK-01TRD)
SLK-SNKDSnorkel Kit
LINK-STOVE Adapter Kit (includes 30 ft. of 4 inch flex,
apapters, wall thimble, masonry
& ZC flashing, 991DA cap and hardware
package
VPK-DVVinyl Siding Protector Kit
SLP-HHW2HHW2 Horizontal High Wind Cap
(recommended for optimal performance)
899-4491HHW2K Horizontal Kit (one 90 degree
black wall thimble, 24 inch black
pipe, 11 inch - 14-5/8 inch adjustable
vent, HHW2 termination cap)
844-8921RHVK Snorkel Kit (with Dura-Vent parts
Page 43Quadra-Fire • Columbia Bay • 250-5195 Rev. K
R
D. Service Parts List
COLBAY-FS-B
Service Parts Diagram
Columbia Bay Free Standing
1
2
3
5
4
Beginning Manufacturing Date: Feb 2005
Ending Manufacturing Date: ______
9
6
8
7
Log Set Assembly
Part number list on following page.
Page 44
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
R
D. Service Parts List
Service Parts List
Columbia Bay Free Standing
Beginning Manufacturing Date: Feb 2005
COLBAY-FS-B
Ending Manufacturing Date: ______
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for
your appliance please provide model number and serial number. All parts listed in this manual may
be ordered from an authorized dealer.
ITEMDESCRIPTIONCOMMENTSPART NUMBER
Log Set Assembly
1Top Assembly
2Curtian Side
3Refractory Assembly
4Burner Assembly
5Grill Bar Assembly
6Door AssemblyDOOR-COLBAY
7Door Crown
8Latch Assembly
9Valve Cover
Adaptor
Adaptor
Baffl e Assembly
Baffl e Hanger
Brick Refractory Ceramic
Burner Pan
Burner Support Kit
Electrode
Face Support
Flex Line
Flex Line
Mineral Wool
Orifi ce NG (.106)
Orifi ce LP (.063)
Power Cord
Snap Disc
Wire Harness
Component Pack474-5070
Thermocouple200-2950
Thermopile842-0250
Touch Up Paint
Conversion Kit NG NGK-MB
Conversion Kit LP LPK-MB
Pilot Orifi ce NG 842-4440
Pilot Orifi ce LP 200-2630
Regulator NG230-1570
Regulator LP230-1520
Additional service part numbers appear on following page.
Metal452-0440
Pre SN #653758842-4070
Post SN #653758842-5180
Black474-5050
GoldRDGRL-CB-GD
NickelRDGRL-CB-NL
Matte black452-0130
GoldDC-CB-GD
NickelDC-CB-NL
Inner 4"200-2470
6 5/8"7000-162
EZ Flush 42842-4580
3/8 comp x 30 "200-2940
24"2098-034
842-4111
452-0380A
452-0360
452-5070
474-0240
842-4051
452-0030
841-0810
474-0080
842-5190
474-0260
050-721
19837
17236
832-2410
230-0960
474-0350
7003-304
Stocked
at Depot
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
10/08
Page 45Quadra-Fire • Columbia Bay • 250-5195 Rev. K
R
D. Service Parts
Valve and Pedestal Components
Columbia Bay Free Standing
COLBAY-FS-B
Beginning Manufacturing Date: Feb 2005
Ending Manufacturing Date: ______
Valve Components
1
2
3
Pedestal Components
4
5
6
9
7
8
14
13
10
11
12
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
Hearth & Home Technologies (“HHT”) and its respective brands extends the following warranty for HHT gas, wood, pellet
and electric appliances purchased from an authorized HHT dealer and installed in the United States of America or Canada.
Warranty starts with date of purchase by the original owner (End User) except as noted for replacement parts.
Warranty PeriodHHT Manufactured Appliances and Venting
PartsLaborGasWoodPellet
1 YearXXXXXX
EPA
Wood
ElectricVenting
Components Covered
All Parts and Material Except as
covered by Conditions, Exclusion,
and Limitations listed
XX
2 years
3 yearsXFirepots
5 years3 yearsXXCastings & Baffl es
7 years3 yearsXXX
10 years1 yearXBurners, Logs & Refractory
Limited
Lifetime
1 yearXFirebox & Heat Exchanger
90 DaysXXXXXX All Replacement Parts
XXXXBlowers
XMolded Refractory Panels
Igniters, Electronic Components,
and Glass
Firebox, HHT Chimney,
Termination & Heat
Exchanger
See Conditions, Exclusions, and limitations. 9-01-08
CONDITIONS, EXCLUSIONS & LIMITATION OF LIABILITY
• This warranty applies to the original owner and is transferable up to two years from date of purchase to the new homeowner,
provided the purchase was made through an authorized dealer or distributor of HHT, and the appliance remains in its
original place of installation.
• The maximum amount recoverable under this warranty is limited to the purchase price of the product.
• In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product.
• Adjustments, regular maintenance, cleaning and temporary repairs, or the failure to duplicate the problem in the home is
not covered under this warranty.
Page 1 of 24021-645A 09-01-08
10/08
Page 47Quadra-Fire • Columbia Bay • 250-5195 Rev. K
E. Limited Lifetime Warranty (continued)
• This limited warranty does not extend to or include surface fi nish on the appliance or terminations, door gasketing, glass
gasketing, glass discoloration, fi rebrick, pellet logs, kaowool or other ceramic insulating materials. Rust and/or corrosion
on any of the metal surfaces, cast iron components, baffl es, fi repots, doors, or fi rebox area are not covered by this
warranty.
• Noise resulting from minor expansion, contraction, or movement of certain parts is normal and complaints related to this
noise are not covered by this warranty.
• HHT’s obligation under this warranty does not extend to damages resulting from: (1) installation, operation or maintenance
of the appliance not in accordance with the installation instructions; operating instructions and the listing agent identifi cation
label furnished with the appliance; (2) installation which does not comply with local building codes; (3) shipping, improper
handling, improper operation, abuse, misuse, accident or unworkmanlike repairs; (4) environmental conditions, inadequate
ventilation or drafting caused by tight sealing construction of the structure or handling devices such as exhaust fans or forced
air furnaces or other such causes; (5) use of fuels other than those specifi ed in the operating instructions; (6) installation
or use of components not supplied with the appliance or any other components not expressly authorized and approved
by HHT; and/or (7) modifi cation of the appliance not expressly authorized and approved by HHT in writing.
• This warranty does not apply to non-HHT venting components, hearth components or other accessories used in conjunction
with the installation of this product.
• This warranty is void if the appliance has been over-fi red or operated in atmospheres contaminated by chlorine, fl uorine,
or other damaging chemicals the appliance is subject to prolonged periods of dampness or condensation, or there is any
damage to the appliance or other components due to water or weather damage which is the result of, but not limited to,
improper chimney or venting installation.
• HHT’ s liability under this warranty is limited to the replacement and repair of defective components or workmanship during
the applicable period. HHT may fully discharge all of its obligations under such warranties by repairing the defective
component(s) at HHT’s discretion. Shipping costs are not covered under this warranty.
• Some states do not allow exclusions or limitation of incidental or consequential damages, so those limitations may not
apply to you. This warranty gives you specifi c rights; you may also have other rights, which vary from state to state.
• EXCEPT TO THE EXTENT PROVIDED BY LAW, HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE
WARRANTY SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF
THE WARRANTY SPECIFIED ABOVE.
This Limited Warranty is effective on all HHT appliances sold after September 01, 2008 and supersedes any and all
warranties currently in existence.
If warranty service is needed, you should contact your installing dealer. If the installing dealer is unable to provide necessary
parts or components, contact the nearest authorized HHT dealer or supplier.
Page 2 of 24021-645A 09-01-08
Page 48
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
______________________________________
_______________________________________
_______________________________________
__________________
__________________
__________________
__________________
R
CONTACT INFORMATION:
Hearth & Home Technologies
1445 North Highway
Colville, WA 99114
Division of HHT INDUSTRIES
Please contact your Quadra-Fire dealer with any questions or concerns.
For the number of your nearest Quadra-Fire dealer,
please visit our web site www.quadrafi re.com
CAUTION
Do NOT discard this manual.
• Important operating and maintenance
instructions included.
• Read, understand and follow these instructions for safe installation and operation.
• Leave this manual with party responsible
for use and operation.
Your Records for Model:
Columbia Bay
Direct Vent Gas Appliance
DEALERSHIP WHERE PURCHASED:
______________________________________
SERIAL NUMBER:
DATE PURCHASED:
DATE INSTALLED:
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322,
4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983, 5429495,
5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112,
5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226,
6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942,
6769426, 6774802, 6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884,
D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250, 780403, 1418504 or
other U.S. and foreign patents pending.
__________________
__________________
__________________
_______________________________________
_______________________________________
DEALER TELEPHONE:
__________________
Page 49
Quadra-Fire • Columbia Bay • 250-5195 Rev. K
10/08
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.