This service manual is for use by Precor trained service
providers only. If you are not a Precor Trained Servicer, you
should not attempt to service any Precor products. Call your
dealer for service.
This document contains information required to perform the majority of
Section 1 - About This Document
troubleshooting and replacement procedures required to repair and
maintain this product.
This document contains general product information, software diagnostic
procedures (when available), preventative maintenance procedures,
inspection and adjustment procedures, troubleshooting procedures,
replacement procedures and electrical block and wiring diagrams.
This manual covers service information for the GEN-06 / TRM10 Treadmill
Base.
The GEN-06 treadmill base is defined as any treadmill produced between
April of 2006 and April of 2011. GEN-06 Treadmills include the
following models; C952, C954, C956, and C966.
The TRM10 treadmill base is defined as any treadmill produced after
April 2011 and is mated to a Pxx console. All of the base and console
combinations are part of the "Experience" line of products.
Lubricants
Do not apply any lubricants to the deck and belt. Do not use Wax
Blast, silicon sprays, or other applied lubricants. The use of these
lubricants will quickly degrade the low-friction surface of the deck.
Do not use petroleum based lubricants on mechanical components such as
the lift, as this may result in degradation of nylon gearing
mechanisms. Use only synthetic lubricants such as "Super Lube with
Teflon" or "Mobile One Synthetic" grease (RED).
Use of unapproved lubricants, cleaners, or solvents may void the
treadmill warranty.
Electrical Requirements
It is extremely important that any Precor treadmill be connected to and
operated on a dedicated 20 amp AC branch circuit. A Dedicated Branch
Circuit is defined as a circuit fed by a single circuit breaker feeding a
single load, with a single non-shared neutral providing a return line. A
treadmill operating from a non-dedicated branch circuit or a circuit
breaker of less than 20 amps capacity will not have the necessary power
to operate normally under higher load conditions.
Nominal AC operating voltage on 120VAC circuits is 90VAC to 132VAC.
Nominal AC operating voltage on 240VAC circuits is 180VAC to 264VAC. For
operator safety considerations and to minimize electrostatic discharge
conditions the AC frame ground continuity must also be verified to be a
low resistance connection to the AC distribution ground bar.
Important
If the AC circuit feeding a treadmill is found to be a non-dedicated
branch circuit or a circuit equipped with a circuit breaker with a
capacity of less than 20 amps, the AC circuit must be corrected before
any reliable troubleshooting can be performed on the treadmill. More
importantly, a non-dedicated branch circuit may constitute a safety
hazard to the treadmill operator.
120 Vac Systems
120 VAC distribution systems utilize a single pole circuit breaker (hot
lead) and a neutral lead connected to a common neutral (ground) bar. The
A.C. safety ground (green wire) is connected to a separate ground bar in
the distribution system.
If it is determined that any of the above electrical conditions are in
question, please consult with a qualified electrician to make appropriate
circuit changes.
Safety guidelines you should know and follow include:
Section 3 - Safety Guidelines
Read the owner’s manual and follow all operating instructions.
Operate the equipment on a solid, level surface.
Visually check the equipment before beginning service or maintenance
operations. If it is not completely assembled or is damaged in anyway,
do not attempt to operate the equipment.
When operating the treadmill:
Do not wear loose clothing. Do not wear shoes with heels or leather
soles.
Check the soles of your shoes and remove any embedded stones.
Tie long hair back.
Do not rock the unit.
Do not stand or climb on the handlebars, display enclosure or cover.
Do not set anything on the handlebars, display enclosure, or cover.
Never place liquids on any part of the treadmill while performing
service.
To prevent electrical shock, keep all electrical components away from
water and other liquids.
Do not use accessory attachments that are not recommended by the
manufacturer-such attachments might cause injuries.
Removing the hood exposes high voltage components and potentially
dangerous machinery. Exercise extreme caution when you perform
Check, record, and then clear any errors in the error log.
Verify that all LEDs function properly during the Hardware Validation Tests.
Verify that all keys on the keypad function properly during the Hardware Validation Tests.
Verify that the heart rate functions normally and displays a valid heart rate.
Verify the running belt drive system functions properly throughout the minimum to
maximum range of control. All drive system components (deck, belts, rollers, IFT) are free
of excessive noise, vibrations, or smells
Verify the Incline A/D value is approximately 6000+/-500 at 0% incline, the incline operates
within the complete range of the lift when the or keys are pressed and is free of
excessive noise or vibrations.
The STOP button stops the running belt from moving.
Pulling the ESTOP cord stops the running belt from moving.
Check for new errors that may have been recorded in the error log during operation
Club Parameter - Settings (5651565) ............... 17
Information Display (65) .......................... 18
Section 5 - Standardized Service Access
Codes
Service Access Codes
The standardized service access codes are utilized on the following
consoles:
Standard Console
P10 Console
P20 Console
P30 Console
The service codes will allow access to three functional modes, Hardware
Validation, Club Parameters, and a Information Display.
Hardware Validation is a set of functional diagnostic tests that are
useful in troubleshooting problems as well as verifying proper
operation.
Club Parameters are sometimes referred to as Club Settings and are
used to manage usage of the machine.
Information Display is used to access information such as the
odometer, software versions and error logs.
Accessing the Service Software
Accessing these three areas is accomplished the same on all consoles
(Standard, P10, P20, P30) except the P80. To enter Service Software,
press either the STOP, PAUSE, or RESET key (whichever is available on
your specific console) followed by a numeric code for the area of service
software you wish to access.
The standard access codes use sequential key presses, not simultaneously
holding down multiple keys. The allowable delay between key presses is
short. If too much time is taken between key presses or the wrong key is
pressed, the access procedure will be aborted. If the access is aborted,
it will be necessary to start over from the beginning.
P80 Console
1 Use the System Settings to test your equipment and set parameters that
benefit your users and your facility.
2 The Welcome screen will be the first screen you see when you approach
the P80 console. Press the Pause key and continue holding it down
while you double press (prior to 1.1 version software release) or
single press (1.1 version or after software release) in sequential
order an X configuration on the Volume and Channel key pad (Channel
Note: The keypad X configuration sequence should be not faster than 1
second between each key stroke. Any speed faster than 1 second may
result in an unsuccessful access to the sign-in screen.
Figure 1: P80 Sign In Access
3 The sign-in screen will be displayed. Type in the technician access
,5,1,7,6,5,7,6,1, and then touch OK. The Settings menu will be
The P20 console starts with STOP, PAUSE, or RESET, however the numeric
values of the service software code is assigned to the function keys in
the absence of the 10-key pad.
Either enabled or disabled, this setting requires a password
(1234) to be entered in order to start the unit. Factory
default is disabled.
Select Language
Sets the default language for ALL w orkouts on this m achine.
Language for single use w orkouts can still be set by the user
from the w orkout options.
Select Units
Sets units of m easure (US standard or M etric). Factory
default is US standard.
Set M ax W orkout Tim e
Sets the m axim um allowable workout tim e for each user.
Factory default is 60 m inutes.
Set M ax Pause Tim e
Sets the m axim um tim e that the workout can be paused for.
Factory default is 120 seconds.
Set M ax Cool Dow n Tim e
Sets the am ount of tim e that a cool down period will occur at
the end of every w orkout. Factory default is 5 m inutes.
Set M etrics D efault
Sets a m etric that m ay be of specific im portance to the
specific facility or fitness trainer. The selected m etric will
scroll across the screen at regular intervals during the
w orkout. Factory default is “N O NE”
Set Speed Lim it
Sets the m axim um speed that the user can set the unit to.
Factory default is 16m ph.
Set Incline Lim it
Sets a m axim um value that the user can set the incline to.
Factory default is 15% .
Show H idden Program s
Either enabled or disabled, this setting allow s the unit to
access specialized fitness tests designed for police, fire
fighters, and the m ilitary. Factory default is disabled.
Console To Base Communication ..................... 22
Treadmill Base Operation .......................... 23
Section 6 - Theory Of Operation
Consoles
Basic operation of a console
The purpose of this section is to describe the operation and maintenance
of the treadmill base, however it would be difficult to explain the base
operation without referring to the console controls. This section will
explain basic functions that apply to all models of consoles. For
specific details about a particular model of console (Standard, P10, P20,
P30, P80), refer to the applicable console manual.
The Controls
All consoles provide user input (keypad functions), user display (LED
display / user feedback), automated control (heart rate program, interval
program) and service software routines (tests, settings, and
information).
The keypad functions can vary between different console models, however
the basic functions that all consoles have are Quick Start, Incline (up
or down) and Speed (up or down).
The Display
The display features can vary between different console models, however
the information conveyed by those displays are very similar.
Service software routines are handled exactly the same for all console
models. Entering into Hardware Validation tests, Club Parameter settings,
or Information Display is also the same and are called Standardized
Service Access Codes.
The service software and standard access codes are described in detail
in, Standardized Service Access Codes (see "Section 5 - Standardized Service Access
Codes" on page 12) section of this manual.
The service software also includes Standard Error Codes, in all console
models. For a full listing of Standard Error Codes used for this model
see, Section 7 - TRM Base Troubleshooting Procedures (on page 31).
The processor in the console provides user input, user display and
automated control to the system. The processor in the lower electronics
module performs the actual machine function.
The two processors communicate via a serial data stream. When the user
makes a requests a machine function to take place via the keypad, the
console processor communicates the request to the processor in the lower
electronics module.
Once the lower processor receives the request the lower control module
performs the machine task associated with the request. The console
processor continues to monitor keypad entry and provide display feedback.
The lower processor also provides status back to the console processor
(via the serial data stream) to report if everything occurred properly,
or if an error code needs to be written to the error log.
The GEN-06 / TRM10 base is equipped with a removable line cord plugged
into a power entry socket. This is designed to accommodate either 120V or
240V NEMA compatible line cords, as well as line cords for other
countries. The diagram below shows a NEMA 20A plug for both 120V and 240V
configurations in the United States.
Figure 6: NEMA Compatible Plugs
120v power, when measured from hot to neutral, should read between 90 and
132v. 240v power, when measured from hot to neutral should read between
180 and 264v. This input voltage is applied through the power entry plug
and wired to the breaker switch. The 120v breaker switch only interrupts
the hot line and the 240v breaker switch interrupts both the hot and
neutral lines. The power is then fed through a line filter which removes
high frequency noise from the line voltage. After the power is cleaned by
the line filter it can be applied to the lower electronics module (IFT
drive).
The lower control module consists of an AC drive motor controller, an AC
lift motor controller and a +8.5V DC power supply to power the console.
The electronic circuits in the console operate on +5V DC, however the
lower control module sends +8.5V DC due to the optional external
equipment such as Fitlinxx, that may be connected to the CSAFE
(Communication Standard for All Fitness Equipment) port. Sending a higher
voltage (+8.5V) and regulating the voltage down to +5V DC, ensures that
we can supply enough power to both the console and the optional external
equipment.
It is important to note that the lower control module is a different part
number for a 120V unit than for a 240V unit.
The Experience Line treadmills use an AC drive system to control a three
phase AC drive motor. In an AC motor, speed is controlled by frequency
independent of voltage or current and torque is controlled by the
voltage/current applied to the 3 windings. The windings (stator) and
rotor core of the motor are designed to spin at a specific speed at the
design frequency. This is by design of the motor itself. By changing the
frequency of the drive current, we can change the speed. The lower
control module generates the correct frequency to drive the motor at the
desired speed. Since the speed of an AC motor is controlled by frequency,
there is no need for a speed sensor.
The frequency is then sent to the motor over 3 lines, with each of those
lines being phase shifted 120 degrees from each other. This type of AC
motor is referred to as a 3 phase AC motor and is used to allow enough
torque to be applied over a continuous duty run time. The amplitude
(voltage/current) of all three sine waves is the same at any given time
and allows the torque to be applied smoothly throughout the rotation of
the motor. Increasing the amplitude increases the torque and decreasing
the amplitude decreases the torque.
The lower electronics module (IFT drive) is responsible for sending the
proper frequency to control speed and the proper amplitude (same on all 3
lines) to control torque. The motor must then be balanced both
mechanically and electrically in order to translate the frequency and
amplitude into fluid motion. Mechanical balance is achieved by balancing
the weight of the flywheel, and electrical balance is achieved by all 3
windings being equal (same number of ohms).
Other features of this AC drive motor controller include "Dynamic
Braking" and "Power Factor Correction". Dynamic Braking addresses an
issue where an over-speed condition could occur. If a heavy user runs at
a high incline, the weight of the user has the potential to push the
running belt to go faster than the motor control was trying to maintain.
The dynamic brake circuit senses the load variations and applies a
braking force within the motor. The system utilizes an external power
resistor to determine the point at which the braking force is applied.
Power Factor Correction is a feature that attempts to reduce power
consumption. The system monitors that this power factor is held within
certain parameters. If it falls outside those parameters (IE, the system
is suing more current than expected), the system will flag an ERROR 29.
Error codes are addressed in detail in the troubleshooting section of
this manual.
The Auto Stop feature monitors up and down movement of the deck. The deck
motion indicates a user is present. The lack of motion indicates that a
user is not present. If the running belt is moving and the Auto Stop does
not detect motion from the running deck, the Auto Stop feature will stop
the motion of the running belt.
Treadmills built between April of 2006 and April of 2011 (referred to as
the Gen-06 Treadmill) did not have this auto-stop feature. Treadmills
built From April of 2011 to present (referred to as the "TRM10
Treadmill") support the auto-stop feature.
The auto-stop feature consists of a magnet mounted on the edge of the
deck, the sensor mounted on the roller mounting bracket and a cable
connecting Auto-stop to the console. When a user is running on the deck,
it causes the magnet to be in motion relative to the sensor. When a
program is entered, Quick Start is pressed or the treadmill has been
resumed after being paused, the treadmill starts at 1 mph. The user will
then have 60 seconds to enter any remaining workout settings before
motion detection begins. Once motion detection has commenced and if no or
very little motion is detected, the Auto Stop feature interprets that the
treadmill is no longer in use. The Auto Stop feature will continue to
monitor the treadmill for motion for 30 seconds; if motion is still not
detected a 10 second count down will be displayed on the console. After
the 10 second count down has elapsed and motion has not been detected,
the Auto Stop feature will stop the motion of the running belt and go
into pause mode. If motion is detected within the 10 second count down
cycles the shut down feature will be aborted.
The Auto Stop feature can be enabled or disabled within the service
software menus. See "Setting Club Parameters" in the corresponding P10
console, P20 console, P30 console or the P80 console service manual.
Note: If enabled, adjustment and tracking procedures should be preformed
while in the Hardware Validation – Belt Speed Test. This is because the
Auto-Stop feature is not active during the Belt Speed Test.
The motor used in the lift system is a "Permanent Split Capacitance"
type, single phase AC motor. What this means is that the motor
incorporates the use of a capacitor to provide the torque required to
lift the weight of the user as well as the weight of the unit. Power to
the lift motor is provided directly from the AC coming into the unit.
In order to turn the motor in 2 directions, the AC motor has 2 separate
windings, one for up and one for down. AC1 has a continuous connection to
the center / common connection of the motor.
The system has a 2A fuse to protect the components from over-current
failure.
When a control signal is applied to the "UP" input, TRIAC 1control line
is active and turns on the up triac. This directs the AC2 connection to
the up winding of the motor, causing the motor to spin in the up
direction.
When a control signal is applied to the "DOWN" input, TRIAC 2 control
line is active, turns on the down triac. This directs the AC2 connection
to the down winding of the motor, causing the motor to spin in the down
direction.
Since the lift motor runs directly on the AC line voltage coming into the
unit, it is important to note that the lift motor is a different part
number for a 120v unit than for a 240v unit.
The unit also requires an absolute measurement of lift position. This is
achieved through the use of a potentiometer. The potentiometer is turned
by connected gears in the lift motor, which changes the wiper resistance.
With +3.3V DC applied across the potentiometer, the center wiper
connection will be a variable voltage (between 0 and +3.3V DC), dependant
on the position of the lift. This variable voltage is applied to the
input of a 16-bit A/D converter which converts the analog voltage into a
16-bit binary numeric representation that the processor can understand.
As the voltage returned by the potentiometer changes between 0 and 3.3V
DC, the corresponding A/D values change between 0 and 65507. In this way,
the processor can keep track of where the lift is positioned.
It is important to note that since the potentiometer is mechanically
connected to the gearing of the motor, it would be highly unlikely for a
lift motor to go out of calibration without having some damage that
needs to be repaired. See the section, Troubleshooting the Incline System (on
Running Belt & Deck Troubleshooting ............... 68
Troubleshooting the Auto Stop Feature ............. 70
Section 7 - TRM Base Troubleshooting
Procedures
methodology for identifying and isolating system issues. Not all system
issues will create an error code condition so the approach is to identify
and verify the stated problem and then use the systems own self tests to
help isolate the problem. In many cases, that will include the use of
error codes, but not always.
Introduction to Treadmill Troubleshooting
The failure that is reported by the user may differ from your
observations as a trained technician. That is why it is important
to validate the reported failure. The first step in this
investigative troubleshooting methodology is to first identify the
current overall operating condition of the treadmill. Is it
operational or not. If the system powers up and can be at lease
partially operated:
o Follow the procedure, Validating the Reported Failure (on page 40).
If the treadmill does not turn on, trips the breaker or the console
will not illuminate:
o Follow the appropriate procedure for Troubleshooting Tripped Breakers
(on page 31) or Troubleshooting No Power to the Console (on page 35).
Troubleshooting Tripped Breakers
It is extremely important to note whether the unit’s breaker trips or the
wall outlet breaker trips. It is also extremely important to note when
the trip occurs:
Immediately on power up
After the belt starts but before the user walks on the belt
1 Check the voltage coming from the wall. If it is approximately to 0V,
the wall breaker has likely tripped.
2 Inspect the line cord, If damaged, replace the line cord. If the line
cord is not damaged continue with the following steps.
3 Verify if two or more treadmills on the same wall breaker. This will
be especially evident if two or more treadmills shut down at the same
time. To verify if multiple treadmills are sharing the same wall
breaker, manually turned off the wall breaker. If more than one
treadmill loses power, the treadmills are on the same breaker.
If YES, advise the customer to have their facility wiring upgraded
per Precor specifications.
If NO, continue with the following steps.
4 Verify the wall outlets do not share neutral wiring and that each wall
outlet is on a individual branch circuit. A individual branch circuit
will have its own load line, neutral line and ground line. To verify
that the treadmill is not on a individual branch circuit use an AC
voltmeter measure from the hot contact of one AC receptacle to the
neutral contact of another AC receptacle. If AC line voltage is
present then the treadmills are sharing neutral lines.
If YES, advise customer to have their facility wiring upgraded per
Precor specifications, and then continue to step 5.
If NO, Continue to step 6
5 Measure the AC input voltage with the treadmill unloaded (running belt
moving, with no one walking on the running belt) and then again while
loaded (someone walking/running on the belt). The difference between
the two states should be no more than about 6 volts RMS, and ideally
less.
If the voltage variance is more than 6 volts RMS, the distance the
branch circuit wire are runs maybe very long or may have used
smaller diameter wire. Recommend to the club that they should
consult with an electrician if this is suspected.
If NO, Continue to step 6.
6 Overloading is the most frequent cause of treadmill shutting down.
Overloading is most often caused by excess deck/belt friction, but can
be made worse by line voltage conditions. This condition happens more
often with heavier runners, but never walkers. In high user clubs (10
hours or more of use per day), the decks/belts will wear out much
faster than at other locations, sometimes in months rather than years.
It is often accompanied by error codes 27, 28, or 29. Follow the steps
for these errors as per procedure, Troubleshooting the Drive Motor System
(see "Troubleshooting the 3 Phase AC Drive Motor System" on page 48) .
If the Treadmill breaker (power switch) is tripped:
1 Verify the wall outlets do not share neutral wiring and that each wall
outlet is on a individual branch circuit. A individual branch circuit
will have its own load line, neutral line and ground line. To verify
that the treadmill is not on a individual branch circuit use an AC
voltmeter measure from the hot contact of one AC receptacle to the
neutral contact of another AC receptacle. If AC line voltage is
present then the treadmills are sharing neutral lines.
If YES, advise customer to have their facility wiring upgraded per
Precor specifications, and then continue with step 2.
If NO, continue with the following steps.
2 Verify that there long branch run with inadequate gauge wire.
If YES, advise customer to have their facility wiring upgraded per
Precor specifications.
If NO, continue with the following steps.
3 Verify line voltage. Low line voltage for the U.S. is anything below
108VAC, measured while the treadmill circuit breaker is turned "ON",
but the running belt is idle. For international, low line voltage is
anything below 200VAC while the treadmill circuit breaker is turned
"ON" and the running belt is idle. Measure the line voltage with the
treadmill circuit breaker is turned "ON", but the running belt is
idle. Make note of the voltage. Then measure the voltage again using
the instantaneous voltage drop using the min/max function on your volt
meter while someone is running on the treadmill at 7.0 MPH or higher.
If any measurement is below 108VAC (US) or 200VAC (International),
advise the customer to have their facility wiring inspected by an
electrician.
If the measurements are at or above 108VAC (US) or 200VAC
(International), continue with following steps.
4 Does the treadmill trip its breaker immediately on power up?
If YES, it is likely that there is a shorted component (line filter,
lower control module) or faulty/shorted wiring.
If NO, continue with the following steps.
5 Does the treadmill power up, but trips the breaker after the motor is
started?
If YES, it is likely that there is a bad roller or bad drive motor.
If NO, continue with the following steps.
6 Does the drive motor start up fine, but trips the breaker after a user
walks/runs on the running belt?
If YES, Overloading is the most frequent cause of treadmill shutting
down. Overloading is most often caused by excess deck/belt friction,
but can be made worse by line voltage conditions. The overloading
condition happens more often with heavier runners, but never
walkers. In high user clubs (10 hours or more of use per day), the
decks/belts will wear out much faster than at other locations,
This troubleshooting is for Standard, P10, P20, or P30 consoles only. P80
use their own power source separate from the lower control module.
1 Using an AC voltmeter, verify that the outlet voltage is appropriate.
See procedure, Troubleshooting Tripped Breakers (on page 31)
If NO, advise customer to have their facility wiring upgraded per
Precor specifications and then continue with troubleshooting.
If Yes, continue with the following steps.
2 Remove the treadmill hood and measure the AC voltage at the input side
of the line filter with a voltmeter. Verify that line voltage is
present when the breaker switch is turned on.
If NO, Replace the breaker switch.
If Yes, continue with the following steps.
3 Measure the AC voltage at the output side of the line filter with a
voltmeter. Verify that line voltage is present when the breaker switch
is turned on.
If NO, Replace the line filter.
If Yes, continue with the following steps.
4 Use a known good console and communication cable. Plug the test
console and test communications cable into the suspect treadmill lower
control module (IFT drive). Does the test console power up?
If NO, Replace the lower control module (IFT drive).
If Yes, continue with the following steps.
5 If the test console did power up in step 4, re-connect the test
communications cable from the test console to the original console.
Does the original console power up?
If Yes, Replace the Communications Cable.
If No, Replace The upper PCA.
CAUTION: Swapping a lower control module from a good unit into a bad unit
could damage the lower control module from the good unit. If the control
module that is being swapped may have a defect and could damage
components in the good unit.This could potentially produce two bad units
instead of one.
The system generates error codes and stores those codes in a block of
memory known as the ERROR LOG. The error is entered into the error log
when it detects conditions that are defined in the error reporting
software.
The error log displays the 10 most resent errors, with error location one
being the most recent. Not all system issues will generate an error code,
only the errors that can be generated in the treadmill will be described
in this section. The error codes are useful in isolating certain system
issues.
To view errors in the error log, press and hold the reset key for at
least 6 seconds. If there are errors logged, this action will take you
into the error log. The error log can also be accessed through the
Information Display by pressing either STOP, PAUSE, or RESET, then the
numbers 6, 5.
The subsequent pages list the details of each of the error codes that
exist within the Precor software hierarchy. Each page will include a
description of the error code being displayed and the systems associated
with the error code.
Potential causes for the error codes will be listed with the most likely
cause first and the least likely cause listed last. It must be understood
that this document can not anticipate every possible cause for a
particular error code. However, it should list the causes encountered in
the majority of cases.
The document will then list the suggested remedies associated with each
of the possible causes. The possible remedy listing will numerically
coincide with the possible cause listing.
1 Look to see if there is an error in the error log. This is often the
source of vital information to point your troubleshooting in the right
direction. Write down the errors and the odometer readings that are
reported in the log and then clear the error log by pressing and
holding the "Quick Start" key.
2 Run the unit in normal user mode and verify that the reported failure
occurs. Make note of any other observations of things that occur at
the time of the failure.
3 Run the unit in the service access software per the procedure in
section 5 (5-1-7-6-5-7-6-1, Hardware Validation Tests), and verify
that the console (display, keypad, and heart rate) functions are
working normally.
NOTE: Keep in mind that if a key on the keypad does not function, the lower
control module will not be aware of any request for action that the user has
initiated. In this case the cause for the failure would not be in the lower
portion of the unit, and no errors will be logged.
4 Run the unit in the service access software per the procedure in
section 5 (5-1-7-6-5-7-6-1, Hardware Validation Tests), and verify
that the machine (belt speed and incline) functions are working
normally.
NOTE: If a failure is observed in user mode but works perfectly in the
hardware validation tests, this could be an indication that a setting in the
club parameters has been incorrectly set. It is also important to keep in
mind that some problems are weight (load) related and you may need to
recreate that condition.
5 Look at the error log again to see what errors have returned. This
will validate that they are real and current errors. Do not disregard
the previous errors that were cleared, but understand that the
odometer reading when compared to the total unit odometer reading will
determine how recent the error message occurred.
NOTE: If no error codes are present but the system is not operating
normally, such as irregular or rough drive motor movement, follow the
troubleshooting steps for the most directly related troubleshooting topic.
6 Look up the current service bulletins for this unit. If no service
bulletin exists for this issue, continue with the troubleshooting
steps for the system that is failing (Power & Control, Drive Motor
System, Incline System, Communication, Belt & Deck, Auto Stop, or
Errors in this section cover either input power (error 15 & 16)
conditions, Console controls (error 5 & 80-83), or processor/memory
(error 9 & 11) conditions. These are errors that although they are valid
to the proper function of the machine, are not part of a specific
treadmill base system (lift system, drive system, deck & belt system,
etc…). Follow the steps for error code 5, 9, 12, 15, 16, 80, 81, 82, or
83 on the following pages.
Error 05 - Key Depressed at Power Up
Description
The power up test sequence has detected a key in the operated condition.
The power up test sequence is performed every time the unit is turned on
(powered up). This test is performed because a permanently stuck key will
inhibit the correct operation of the unit.
Possible Causes
1 A key on the display housing is permanently stuck in the operated
condition.
2 One of the upper PCA’s keypad interface chips has failed.
3 Liquid (perhaps perspiration) is present on the surface of the display
overlay.
Possible Remedies
1 Remove the keypad connector cable from the upper PCA. Restart the
power up sequence, if the ERROR 5 is no longer present, the keypad is
the cause. The keypad is typically part of the display housing.
Replace the display housing to correct the problem.
2 Remove the keypad connector cable from the upper PCA. Restart the
power up sequence, if the ERROR 5 is still present, the upper PCA is
the cause. Replace the upper PCA to correct this problem.
3 Wipe the surface of the display overlay clean of all liquid. Restart
the power up sequence, if the ERROR 5 is no longer present, the liquid
Error 09 - Lower PCA Memory Test Errors
Description
Error 09 checks lower PCA memory locations during the power up test
sequence. If a fault is found during the power up test sequence, error 09
will be displayed. This error code is only used on products utilizing the
dual microprocessor system.
Possible Cause
This error message almost always indicates a lower PCA problem when it is
consistently displayed. Failures causing this error message to be
displayed are rare.
Possible Remedy
If the error message is consistently displayed when the unit is powered
up, the lower PCA should be replaced. It is possible to see this error
message displayed intermittently due to external causes. If the unit's
A.C. input significantly dips during the power up test sequence the test
could fail resulting in this message being displayed. Treadmills
operating on non-dedicated A.C. circuits may see this message displayed
on an intermittent basis.
Error 15 - A.C. Input Voltage Too High
Description
This error monitors the AC input voltage. If the AC input momentarily
reaches the upper limit, an error 15 will be logged. The upper acceptable
input voltage limit is 132V AC on 120V AC systems or 264V AC on 240V AC
systems.
When the treadmill is used by a vigorous exerciser walking or running at
steep incline, the AC motor can become a generator, forcing power
backwards into the IFT module. This excess power would cause the IFT’s
internal reservoir, called the Bus Voltage, to rise to the point of
damaging the drive were it not for the DB (dynamic brake) resistor, which
automatically switches on to absorb it.
Error 15 is an indication that the Bus Voltage somehow rose too high,
either because the DB system wasn’t functional or because the Bus Voltage
power was more than the DB system could absorb at once. The power
reservoir is also fed by the input (line) voltage, so it is also possible
that a temporary line voltage surge could result in an Error 15
condition.
Possible Causes
1 AC input voltage transients. Transients can be caused by lightning
strikes or by other pieces of equipment sharing the treadmill’s AC
power.
2 Lower control module failure, or dynamic braking resistor failure.
3 Sticky substances on the underside of the running belt causing high
current.
Possible Remedies
1 Verify that the AC grounding is good at the treadmill’s AC outlet.
Verify that the treadmill is operating on a dedicated 20 amp branch
circuit. This condition would require a licensed electrician to
correct the problem.
2 This could be either the lower control module or the dynamic braking
resistor.
Check error logs to determine Error 15 frequency.
Has this continued to happen for this treadmill, or was it a one-
time event?
Could it have happened when a user intentionally pushed against the
handrail, back-driving the motor for a sustained time?
This error monitors the A.C input voltage. If the A.C. input
momentarily reaches the lower limit, an error 16 will be logged. The
lower acceptable input voltage limit is 90 V.A.C. on 120 V.A.C systems
or 180 V.A.C. on 240 V.A.C. systems
Possible Causes
1 A.C input voltage incorrect, treadmill is operating on undersized
A.C. wiring and/or is drawing high current.
2 Treadmill is operating on a non-dedicated circuit.
Possible Remedies
1 Voltage drop across the AC input wiring is a product of the length
of the wire run and the amount of current being demanded by the
treadmill. The longer the run and the higher the current the larger
the wire must be. The AC wiring must be sized to handle 20 amps of
current over the loop length of the AC wiring. This condition would
require a licensed electrician to correct the problem.
2 Verify that the treadmill is operating on a dedicated 20 amp branch
circuit. This condition would require a licensed electrician to
correct the problem.
Error 80, 81, 82, & 83 – P30 Machine Controls Not Working
Description
This error monitors the incline (up and down), and speed (up and down)
controls of a P30 console. These switches are not traditional
mechanical switches, they are optical switches.
Error 80, P30 Lift Up Not Working
Error 81, P30 Lift Down Not Working
Error 82, P30 Speed Up Not Working
Error 83, P30 Speed Down Not Working
Possible Causes
1 Machine control interconnect cable has come unplugged from the upper
PCA.
2 Bad machine control cable.
3 Bad machine control assembly.
Possible Remedies
1 Open the P30 console to expose the circuit boards, and verify that
the machine control cable has not become unplugged from the upper
PCA.
2 Substitute a known good machine control cable.
3 Substitute a known good machine control assembly.
Occasionally, there may be issues with the proper operation of the
drive system that do not generate error codes. This troubleshooting
procedure is intended for those times.
If there is an error code for the drive system (Error 20 through 29) in
the error log, go to the appropriate error code troubleshooting page
and follow the steps for that error.
If there are no errors in the log, yet the drive system appears to have
an issue (such as jittery motion) follow the steps below.
Note: When taking voltage readings of the AC drive motor, the readings
may not seem accurate because of the frequencies being used, however,
they are indicative of the presence of drive motor voltage and relative
frequency changes.
Procedure:
If the drive motor starts when you force the running belt to move and
once running the drive motor runs rough, skip to step 8. If the drive
motor will not start at all, continue with step 1.
If the drive motor does not start, the lower control module will only
apply voltage for a couple of seconds before it shuts down. Therefore
the voltage readings in the following step must be taken within the
first couple of seconds after the treadmill is instructed to start the
running belt. (A multi-meter with a hold feature is advisable in this
case)
1 Connect an AC voltmeter between terminals 4 (red) & 5 (white) of the
OUTPUT connector on the lower control module. See Figure Below. Set
the treadmill’s on/off switch to the on position. Press the QUICK
START key. If the lower control module is supplying output, you will
momentarily read some value of AC voltage. Make a note of the value
and set the treadmill’s on/off switch to the off position.
2 Set the treadmill’s on/off switch to the off position and repeat the
procedure in step 1 between terminals 4 (red) & 6 (black) of the
OUTPUT connector on the power control module. Voltage should read
the same value as in step 1. Set the treadmill’s on/off switch to
the off position.
3 Set the treadmill’s on/off switch to the off position and repeat the
procedure in step 1 between terminals 5 (white) & 6 (black) of the
OUTPUT connector on the lower control module. Voltage should read
the same value as in step 1. Set the treadmill’s on/off switch to
the off position.
4 If one or more of the voltage readings in steps 1 through 3 are not
present, replace the lower control module. If the voltage readings
in steps 1 through 3 are present, continue with step 5.
NOTE: All resistance measurements must be performed with power
removed from the treadmill. Performing the resistance measurements
with voltage applied may damage your multi-meter.
5 Set the treadmill’s on/off switch to the off position. Disconnect
the drive motor connector from the OUTPUT connector on the power
control module. With an ohmmeter, measure between terminals 4 (red)
& 5 (white), 4 (red) & 6 (black) and 5 (white) & 6 (black) of the
drive motor connector. Each reading should be approximately 2.5 W
(Ohms). If any of the readings are significantly high or open,
replace the drive motor.
6 If the ohm readings are correct, inspect the female terminals of the
drive motor connector. Verify that they are not spread beyond the
point of making good connection with the male pins on the OUTPUT
connector on the power control module. If proper connection is not
being achieved, the connector CAN BE repaired (using the appropriate
crimper and connector ends) as a preferable solution to replacing a
costly drive motor.
7 If you have performed all of the procedures above and have been
unable to correct the problem, call Precor customer support.
Note: All resistance measurements must be performed with power
removed from the treadmill. Performing resistance measurements with
voltage applied may damage your ohmmeter.
Error 20 - Too many Maximum Power Requests in 1 Second
Description
The lower control module monitors drive system loading effects to
determine many parameters of the drive system, including if the motor
starts. If the motor does not start, and error 20 is reported
Possible Causes
1 This error requires that the power must be cycled on the lower
control module.
2 The drive motor could be bad.
3 The lower control module could be bad.
Possible Remedies
1 Cycle the power on the lower control module by setting the units
breaker switch to OFF and then ON again.
2 Test the drive motor per procedure, Troubleshooting the Drive Motor System
(see "Troubleshooting the 3 Phase AC Drive Motor System" on page 48) , step
6. A known good drive motor can be substituted for the existing
drive motor.
3 Test the lower control module per procedure,Troubleshooting the Drive
Motor System (see "Troubleshooting the 3 Phase AC Drive Motor System" on
page 48) , steps 1 thru 4). A known good lower control module can be
substituted for the existing lower control module.
Error 27 - Too Much Drive Motor Current
Description
Some treadmill motor controllers monitor the amount of current being
delivered to the drive motor. The software sets a maximum amount of
allowable drive motor current. This error indicates that maximum drive
motor current has been reached.
Possible Causes
1 The running belt and/or running bed is badly worn.
Possible Remedies
1 A clamp-on AC ammeter must be used to determine the amount of AC
input current being drawn by the treadmill under no load and loaded
conditions. Follow the troubleshooting per procedure, Running Belt &
Some treadmill motor controllers monitor the temperature of the motor
controller output switching device. Typically, these motor controllers
use a fan to force cool the output devices heat sink. This error
indicates that the heat sink temperature has exceeded maximum.
Possible Causes
1 The lower PCA cooling fan is clogged.
2 The lower PCA cooling fan is inoperative.
3 The lower PCA is defective.
Possible Remedies
1 Check the cooling fan mounted on the lower control module to ensure
that the fan is not clogged with dust. Thoroughly clean the fan and
ensure that it spins freely. Insure that machine motor cables are
not routed to close and not touching the fan.
2 The lower PCA is clean and unobstructed but the fan does not spin.
Ensure that the fan wiring is securely and correctly connected to
the lower control module. If the fan is unobstructed and the fan
wiring is good, replace the lower control module.
3 Substitute a known good lower control module to determine if the
lower control module is defective.
NOTE: Some older lower control module software revisions used error
28 as a "catch all" and therefore reported a wider range of errors as an
error 28. Verify lower control module software is current.
This error code is used on three phase AC drive motor systems. If the
AC input current reaches a value slightly over 20 amps R.M.S. or there
is an instantaneous AC input current spike of 65 amps, the drive motor
system will shut down and an error 29 will be logged.
Possible Causes
1 If the facility is powered by a generator, or frequently switches
between city and generator backup voltage, interruption of the
treadmill operation may occur.
2 The neutral wires are shared on multiple outlets.
3 The running belt and/or running bed is badly worn.
4 A shorted lower control module (IFT module).
5 A shorted drive motor is causing the high power demand.
Possible Remedies
1 Call Precor support for lower board built specifically to handle
generator power.
2 The outlet is not on a dedicated 20 amp branch circuit. Using an AC
voltmeter, measure from the hot contact of one AC receptacle to the
neutral contact of another AC receptacle. If AC line voltage is
present then they are sharing neutral lines. If YES, advise customer
to have their facility wiring upgraded per Precor specifications.
This condition would require a licensed electrician to correct the
problem
3 A clamp-on AC ammeter must be used to determine the amount of AC
input current being drawn by the treadmill under no load and loaded
conditions. Follow the troubleshooting procedure, Running Belt & Deck
Troubleshooting (on page 68).
4 A known good drive motor power module must be substituted for the
existing drive motor power module.
5 A known good drive motor must be substituted for the existing drive
The Lift system consists of an AC line voltage driven lift motor
(120VAC or 240VAC), and an internal 1 K W (Ohms) potentiometer for lift
position monitoring. It is important when you start to troubleshoot the
lift system to determine if the problem is due to an inability to move
the lift, or an inability to monitor the lift position.
This will determine whether you need to troubleshoot the AC voltages
going to the motor windings, or if you need to troubleshoot the DC
voltages and/or ohm readings from the potentiometer. The error log will
help determine which is causing the issue.
Press and hold the reset key for at least 6 seconds, if there are
errors logged in the error log this action will take you into the error
log.
If there is an error code for a lift system error (Error 40 through 45)
logged in the error log, go to the appropriate error code
troubleshooting page and follow the steps for that error.
Note: All resistance measurements must be performed with power
removed from the treadmill. Performing resistance measurements with
voltage applied may damage your ohmmeter.
Operation of lift motor for testing:
Most Precor treadmills require the running belt to be moving to operate
the lift. For this reason it is recommended that the servicer use the
Machine Tests within the "Hardware Validation" mode (accessible through
Pause-5-1-7-6-5-7-6-1) to check lift operation.
Error indicates that the incline (lift) system on either a treadmill,
EFX or AMT12 has been instructed to start moving and no lift motion has
been detected by the lift position monitoring system.
Possible Causes
1 The lower control module lift fuse blown.
2 The lift motor is physically jammed and unable to move.
3 The lower control module is bad.
4 The lift capacitor is bad.
5 A lift motor winding is bad.
Possible Remedies
1 Remove power from the unit. Remove the screw from the back of the
lower control (IFT) module and press in the two locking tabs to
remove the cover. Remove the 2amp fuse (it looks like a pencil
eraser) and with an ohmmeter, check the resistance. The ohm value of
the fuse should be less than 1 ohm.
If the fuse is higher than one ohm, replace it.
If the fuse is one ohm or less, plug it back into its socket and
re-install the cover. If the fuse is good and the lift still will
not move, continue to the next possible cause.
3 If this happens the lift will move (either up or down) as soon as
the unit is powered up. The typical result is that the lift will be
physically jammed as described above, and it will also probably
cause the lift fuse to blow. If the lift moves un-commanded as soon
as the power is turned on to the machine and eventually jams, the
lower control module (IFT drive) must be replaced. The lift switch
may also fail in an open condition. If this happens the lift will
not operate in one direction. Perform the following steps to
determine if the switch is open.
With the incline below 15% (to allow room for lift travel up),
connect an AC voltmeter between terminals 1 (white) & 6 (red) of
the INCLINE connector. (See Figure above for connector location,
and Figure below for the connector pin-out). Set the treadmill in
the manual program and press the INCLINE key. The AC voltmeter
should read AC line voltage (either 120VAC or 240VAC). Note that
the AC line voltage reading will only be present before an error
condition is displayed. A correct reading here verifies that the
UP triac switch is working properly.
Figure 14: Lower Control Module Connector Numbering
With the incline above 0% (to allow room for lift travel down),
connect an AC voltmeter between terminals 1 (white) & 5 (black)
of the INCLINE connector. Set the treadmill in the manual program
and press the INCLINE key. The AC voltmeter should read AC line
voltage (either 120VAC or 240VAC). Note that the AC line voltage
reading will only be present before an error condition is
displayed. A correct reading here verifies that the DOWN triac
switch is working properly.
o If either of these conditions fail, the lower control module
must be replaced.
4 The lift capacitor mounted inside the lift motor. If the lift
capacitor is shorted (0 W), the lift fuse will blow. The capacitor
may be checked by disconnecting the lift motor connector from the
lower control module and using an ohmmeter to measure between pins 5
& 6 of the lift motor connector.
If the capacitor is open or leaky it cannot be determined with an
ohmmeter. A leaky capacitor functions normally for light users,
while failing to move the lift for heavier users. An open
capacitor will not function at all and cannot be determined by an
ohmmeter, so the following test will determine if the capacitor
is bad.
With the incline below 15% (to allow room for lift travel),
connect an AC voltmeter between terminals 5 (black) & 6 (red) of
the INCLINE connector. See Figure above and below. Set the
treadmill in the manual program and press the INCLINE key. The
AC voltmeter should read between 1.5 to 2.0 times the AC line
voltage. If this reading is significantly low, replace the lift
motor. Note that the AC line voltage reading will only be present
before an error condition is displayed.
o If the capacitor is bad the lift motor must be replaced.
5 If a lift motor winding is bad, the lift will not operate in one or
both directions depending on the exact fault in the motor.
Error 42 - Lift Position Value Out of Range
Troubleshooting Procedure
Set the treadmill’s on/off switch in the off position. Visually inspect
the lift motor’s wiring and connector for any broken or improperly
crimped connections. With an ohmmeter, measure between terminals 1
(white) & 5 (black) and 1 (white) & 6 (red) of the INCLINE connector.
Both readings should be approximately 12 (Ohms) for a 120VAC lift
motor and approximately 24 (Ohms) for a 240 VAC lift motor. If
either reading is significantly high or open replace the lift motor.
Description
This error code monitors the physical lift position via a lift position
potentiometer that mechanically tracks the lift's physical position and
sends a DC voltage back to the control system. The voltage is converted
to a 16 bit digital number. This number is then used to represent the
lifts physical position. Software sets upper and lower numerical
limits. If the lift position number is found to be outside of the set
limits, error 42 will be displayed.
When troubleshooting an error 42 it is important to be aware of the
actual physical position of the lift when the error occurs. If the lift
is physically out of range or jammed you must first determine why the
lift is physically out of range. When the lift is out of range the
error 42 is a secondary symptom and the problem should be treated as an
error 40 instead of an error 42.
The A/D value for the home position (0%) is approximately 6200, and its
A/D value at its lowest incline (-3%) is approximately 3200
Possible Cause
1 Incorrect lower control module part number.
2 Bad or intermittent connection in the lift motor connector.
3 The lift motor requires re-calibration.
If the lift had been calibrated correctly at the time of installation and
working for some period of time it would be highly unlikely (if not
impossible) for lift calibration to go out of calibration on its own. It would
be more likely that something has broken causing the A/D value to be
wrong.
1 The vertical market treadmill uses an IFT lower control module that
looks the same, but is programmed differently. One of the things
that is programmed differently is the lowest A/D value for the lift
range (approximately 3000 in the vertical market unit). Having the
wrong lower control module installed could easily cause an out of
range (error 42) condition.
2 Intermittent connections can be difficult to locate. If the error 42
condition is intermittent a connection is almost certainly the
problem. This is especially true if the error 42 occurs while the
lift is within its normal physical range.
Carefully inspect the lift potentiometer connector, repair the
poor connection, if possible. If the intermittent connection
cannot be found or repaired, replace the lift motor.
A lift calibration number of 0 or 65535 indicates an open or
shorted potentiometer connection. This problem could be anywhere
between the lift motor and the upper PCA. It can typically be
found and traced with an ohmmeter.
Figure 15: Lower Control Module Connector Numbering
Set the treadmill’s on/off switch in the off position. Remove the
lift motor’s connector from the INCLINE connector on the power
control (IFT) module. Visually inspect the lift motor’s wiring
and connector for any broken or improperly crimped connections.
With an ohmmeter, read between terminals 3 (red) & 4 (black), 4
(black) & 8 (white) and 3 (red) & 8 (white) of the INCLINE
connector. Terminals 3 (red) & 4 (black) should read
approximately 1K W (Ohms). The sum of the readings between
terminals 4 (black) & 8 (white) and 3 (red) & 8 (white) should
total approximately 1K W (Ohms). If either reading is
significantly high or open, replace the lift motor.
NOTE: Readings While The Unit Is In The Home Position (Level)
Potentiometer resistance black to red = approximately 1kW.
Potentiometer resistance black to white = 20% of black to red
(approximately 200W)
Potentiometer voltage black to red = approximately 3.3 volts.
Potentiometer voltage black to white = 20% of black to red
(approximately 0.66 volts)
A/D value = approximately 6200
3 Refer to the lift calibration procedure. If the lift position number
and physical lift position measurement does not correspond with the
service manual, calibrate the lift motor.
Note: There must be a reason for the lift motor to be out of calibration,
therefore simply re-calibrating the lift motor will often not fix the
problem.
4 If the lift calibration number (A/D value) is not 0 or 65535 and
does not increment when the lift motor moves, replace the lift
motor.
If you have performed all of the procedures above and have been unable
to correct the problem, search for solutions in the service bulletins
or call Precor customer service.
Description
The lift control system has detected that the lift is in motion without
a lift command having been issued. This can happen in one of two ways:
either the lift drive circuit has failed in a turned on condition or
the lift position sensor (lift position potentiometer or revolution
sensor) is sending an erroneous signal to the lift control circuit.
Possible Causes
1 The sensitivity of the 16-bit A/D converter has generated a false
error.
2 Poor or intermittent connection in the lift position sensor
(potentiometer).
3 Bad lift position sensor
4 Bad lower control module.
Possible Remedies
1 Due to the high sensitivity of the 16-bit A/D converter, vibration
during foot plant can cause the A/D value to change enough to
generate this error. This condition is most likely to occur while
the lift is not commanded to move. While the system software detects
this as an error code 44, it does not stop the lift system from
functioning normally. If this is the case the error should be
considered a nuisance error, and the error log should be cleared.
2 This is the most common cause of an error 44. Verify all wiring and
connections associated with the lift position potentiometer. Repair
or replace wiring or connections as appropriate. Because of the
nature of the revolution sensor an error 44 is rarely associated
with it.
3 Operate the lift in the diagnostics while monitoring the lift
position number being displayed. If the reading is erratic and makes
large changes in readings the lift position potentiometer is
probably bad. Replace the lift motor.
4 If there is actual lift motion without a manual or program control
lift command having been issued, replace the lower control module.
Error 45 - Lift Moving in Wrong Direction
Description
The lift control system has detected that the lift is moving in the
opposite direction of the issued lift command.
Possible Causes
1 Lift Motor hysteresis.
2 Bad lower control module
Possible Remedies
1 This error would typically happen when the lift was already in
motion (typically downward) when a lift command in the opposite
direction (lift up) was issued.
Some motors exhibited a very long turnaround time and the lift
motor would still be moving in the original direction (downward)
while the control system was attempting to move the lift in the
opposite direction.
If the error 45 condition is persistent, replace the lift motor.
2 This is a very rare condition, if the lift moves in the opposite
direction of the issued lift command, replace the lower control
module.
Error 30, 31, 32 and 33 - Communications Error
Description
Errors 30 through 33 all indicate the loss of communications or erratic
communications between the microprocessors in the upper PCA and the
lower PCA. The trouble shooting procedures for all of the communication
errors are essentially the same.
Error 30 is defined as upper PCA not receiving from lower PCA.
Error 31 is defined as faulty data received from lower PCA.
Error 32 is defined as lower PCA not receiving from upper PCA.
Error 33 is defined as faulty data received from upper PCA
Possible Causes
1 An upper PCA to lower PCA interconnect cable is bad.
2 The interconnect cable at the upper PCA was mistakenly plugged into
the CSAFE connector.
3 +5V DC power supply is being overloaded by another component that is
plugged onto the lower PCA.
4 A defective lower control module.
5 A defective upper PCA.
Possible Remedies
1 Substitute a know good interconnect cable between the upper and
lower PCAs to determine if the interconnect cable is defective.
2 Remove the interconnect cable from the CSAFE connector and insert it
in the correct upper PCA connector.
3 Unplug all the components from the upper PCA and lower control
module except, data cable, and the AC power going to the lower
control module. If the unit shows an error other than a
communication error, plug in components one at a time, cycling power
after each new component is plugged in. If a communication error is
displayed, the last component plugged in is the cause of the error.
4 Substitute a known good lower control module to determine if the
lower control module is defective.
5 Substitute a known good upper PCA determine if the upper PCAs
The error 37 is generated by the upper PCA in the console when the
lower control module gets into an E-Stop state and the upper PCA in the
console did not know about it. The system uses pin 8 of the data cable
to communicate E-Stop states between the console and the lower control
module.
Possible Cause:
1 Out of date software in a P30 Upper PCA.
2 Bad data cable or mating connector.
3 Bad lower control module.
Possible Remedies:
1 Ensure that the software in the upper PCA is at the current
revision..
2 Substitute a known good data cable.
3 Substitute a known good lower control module.
This procedure is to be used to determine the condition of the running
belt and running deck combination. A clamp-on ammeter will be used to
measure the treadmill’s AC input current under load. The AC input
current is a direct indication of the load being placed on the
treadmill. Treadmill loading consists of several factors, the user’s
weight, treadmill speed and condition of the running belt and running
deck.
The AC input current measurements should be performed at 7-8mph. and 0%
incline. Because the loading varies with the user’s weight, you should
perform the AC input current measurement test on a new running belt and
deck combination. That will provide you with a benchmark reading to
account for your individual weight.
Because the AC input current reading will pulse between a high value
(during foot plant) and a low reading (between foot plants) we suggest
the use of an analog clamp-on ammeter. An analog ammeter makes it very
easy to see the AC current pulses. The refresh rate on digital ammeters
may make it difficult to see the current peaks unless the digital
ammeter is equipped with a peak hold feature.
Procedure
1 Remove the treadmill’s motor cover and place the A.C clamp-on
ammeter on the brown wire from the A.C. input module (or A.C. power
cord) to the circuit breaker (on/off switch). See the illustration
below.
2 Set the treadmill’s speed at 7-8 m.p.h. and the incline at 0%. Walk
on the treadmill and observe the average A.C. current reading.
Typical average A.C. current readings on a new running belt and deck
are between 8 to 12 amperes. average readings (those read by a
digital meter) could be as high as 20 amps, even on a new belt and
deck.
3 If the average current reading approaches 20 amperes, the running
belt should be replaced. The running deck should be flipped or
replaced if the running deck has been previously flipped. See
Procedure, Running Belt and/or Deck Replacement (on page 111) for running
belt and running deck replacement.
4 If the average AC current readings are greater than on a new running
belt and deck combination but not approaching 20 amperes, the
reading will give you an indication of the running belt and deck
combination’s general condition.
NOTE: Repeat the amp draw test after replacing a running belt
and deck.Damage to the lower control module can occur if the
unit had been run in an overload/high current condition for
prolonged periods of time. This type of damage would not
generate an error code, but would cause the breaker to trip
intermittently. An amp draw test will catch this condition.
Auto stop is a feature incorporated into all next generation Experience
series treadmills. This procedure will provide troubleshooting steps
for the Auto Stop feature
Procedure:
1 If the Auto Stop feature does not function continue with step 3.
2 If the Console is displaying Temporarily Out of Order (P80) or
Please use another Treadmill (P30, P20, P10) go to step 7.
3 Check the treadmill to ensure the Auto Stop hardware is installed.
See Figure Below.
If the Auto Stop hardware is not installed, contact Precor
customer support to see if your treadmill is compatible for the
Auto Stop or arrange the installation of the Auto Stop hardware.
If the Auto Stop hardware is installed, Continue.
4 Verify that the Auto Stop cable was plugged into the correct port in
the console. The connector for the Auto Stop is the same number of
pins as the connector for the heart rate grips, and you need to make
sure that they were not reversed.
If the cables were reversed, swap the connectors and re-test.
If the cables were correctly connected, continue
5 If the Auto Stop hardware is installed, access the club settings and
check if the Auto Stop feature is enabled. If it is not enabled,
enable the feature. See Procedure (P80), (P30), (P20) or (P10)
Setting Club Parameters.
6 If the Auto Stop feature is enabled and you have performed steps 3
and 4 contact Precor customer service.
7 Access the service access software (hardware validation tests), and
select the Auto Stop test (see section-5). If the feature is enabled
the P80 Auto Stop sensor test will count the number of times the
magnet crosses the sensor. The P10, P20, or P30 consoles will
display USER DETECTED if motion is detected from the running deck or
NO USER DETECTED if no motion is detected from the running deck. If
the unit passes this test or a USER DETECTED is displayed and the
Auto Stop feature still does not function contact Precor Customer
Support. If the Auto Stop did not pass the test continue with step
Caution: Do not place the auto stop magnet on or near a steel
structure. If the magnet assembly comes in contact with a steel
structure and then pulled away from the steel structure, the magnet can
become dislodged from the magnet assembly housing. Should this occur,
contact PRECOR customer service for possible options for repairing the
magnet assembly or to obtain a replacement part.
8 The Auto Stop system consists of a magnet holder mounted to the
right front corner of the deck and a Hall Effect sensor mounted to
the drive roller bracket of the frame. Check the alignment and gap
(3/16") between the Auto Stop magnet holder and the Auto Stop
sensor. If the alignment and gap are not correct, it may be
necessary to loosen the deck and adjust so that the magnet is gapped
and positioned properly relative to the sensor. Reference Procedure,
Replacing the Auto Stop Magnet. If the alignment and the gap between
the Auto Stop magnet holder and the Auto Stop sensor are correct
continue with step 9.
9 The Auto Stop sensor will display a green blinking LED visible next
to the connector, indicating that power is being applied to the
sensor board. The LED does not tell you if the voltage is correct,
just that it is present. If the LED is not lit or if LED is lit
continue with step 9. See Figure Below.
10 The connector has 3 wires (red, black, and green), which can be
metered for troubleshooting. Unplug the Auto Stop connector from the
Auto Stop Sensor.
11 Place the meter’s red lead to the red wire and black lead to the
black wire of the Auto Stop connector. The meter should indicate 5
volts +/- 0.1 volt. If 5 volts is present skip to step 12.
12 If the 5 volts is not present of significantly low temporarily
replace the Auto Stop cable with a known good cable and repeat step
10. If the 5 volts is not present or the voltage is still
significantly low replace the console or upper PCA. If 5 volts is
present permanently replace the Auto Stop cable.
Note: The running belt does not need to be moving for this test.
13 With the Auto Stop connector plugged into the Auto Stop sensor place
the meter’s red lead to the green wire and black lead to the black
wire. The meter should indicate 5 volts +/- 0.1volt. While
monitoring this voltage, have someone step and/or bounce on the deck
The voltage between the black and green wires should fluctuate when
the deck is moving up and down. If the voltage does not change with
movement replace the Auto Stop Sensor.
14 If you have preformed all the described steps and the Auto Stop
feature will still not function contact Precor Customer Support.
Error 60 or “Temporarily Out of Order” – Auto Stop Not Working
Description
The error indicates the Auto Stop feature has stopped functioning
during a workout. If the error is detected while a workout is in
progress, the treadmill will operate normally until the workout has
ended. At the end of the workout, the error will lock out the next
user, displaying "Temporarily Out of Order, Please Use another
treadmill" on the P80 console and "PLEASE USE ANOTHER TREADMILL" on the
P30 and P20 consoles.
When this error occurs "1376256 E_AUTOSTOP_SENSOR_FAILURE" will be
recorded to the event log of the P80 console. Error 60 will be recorded
in the error log of the P10, P20 or P30 console.
Possible Causes
1 Intermittent connections.
2 Bad upper PCA or Console.
3 Bad Auto Stop cable.
4 Damaged or faulty Auto Stop sensor.
5 Damaged or missing Auto Stop magnet.
6 The gap or alignment between the Auto Stop magnet and sensor is
incorrect.
Possible Remedies
1 Check that the Auto Stop cable connectors are secure at the sensor
and console.
2 Check for 5VDC at the upper PCA or console. Disconnect the Auto Stop
cable connector from the upper PCA or console and measure the
voltage from the console. If 5VDC is not present replace the upper
PCA or console. If 5VDC is present then continue troubleshooting
the Auto Stop cable.
3 Check for 5VDC at the Auto Stop sensor. Disconnect the Auto Stop
cable connector from the Auto Stop sensor, turn the treadmill’s
"On/Off" switch to "On", and check for 5VDC between the red and
black wire in the Auto Stop cable connector. If 5VDC is present at
the at the Auto Stop connector of the console, but not at the end of
the cable, then replace the Auto Stop cable.
4 Visually inspect the Auto Stop sensor for physical damage. Replace
if appropriate. Access the Service Access software (hardware
validation tests), and select the Auto Stop test (see section-5).
If the feature is enabled the P80 Auto Stop sensor test will
count the number of times the magnet crosses the sensor.
o The P10, P20 and P30 consoles will display "USER DETECTED" if
motion is detected from the running deck or "NO USER DETECTED"
if no motion is detected from the running deck. If the Auto
Stop test in the P80 did not count steps or if the P10, P20 or
P30 consoles displayed "NO USER DETECTED", disconnect the Auto
Stop cable from the Auto Stop sensor and check for 5vDC between
the red and black wire.
If 5VDC is present replace the Auto Stop sensor.
5 Ensure the Auto Stop magnet and/or holder is mounted on the edge of
the running deck and visually inspect for damage. Replace if
appropriate.
6 Check the gap and alignment between the Auto Stop magnet and sensor.
The gap should be approximately 3/16 of an inch and the center
markings on the top of the magnet and sensor should be aligned. If
the gap is larger than 3/16"and/or the magnet and sensor are not
aligned, adjust the running deck to the correct alignment and gap.
Error 61 or “Temporarily Out of Order” – Auto Stop Not Present
Description
This error is associated with the TRM Treadmill. The error indicates
the Auto Stop sensor is not detected. If the error is detected the user
will be locked out, displaying "Temporarily Out of Order, Please Use
another treadmill" on the P80 console and "PLEASE USE ANOTHER
TREADMILL" on the P30 and P20 consoles. When this error occurs
"1376257-E_AUTOSTOP_SENSOR_NOT_INSTALLED" will be recorded to the event
log of the P80 console. Error 61 will be recorded in the error log of
the P10, P20 or 30 console.
Possible Causes
1 Intermittent connections.
2 Bad upper PCA or Console.
3 Bad Auto Stop cable.
4 Damaged or faulty Auto Stop sensor.
Possible Remedies
1 Visually verify the Auto Stop hardware components are installed onto
the treadmill frame. The Auto Stop feature was not on the TRM as a
standard feature until 12/28/2010 but may have shipped with a P80
console prior to 12/28/2010. If the Auto Stop hardware is not
present contact Precor Customer Support. Check that the Auto Stop
cable connectors are secure at the sensor and console.
2 Check for 5vDC at the upper PCA or console. Disconnect the Auto Stop
cable connector from the upper PCA or console and measure the
voltage from the console. If 5vDC is not present replace the upper
PCA or console. If 5vDC is present then continue troubleshooting
the Auto Stop cable.
3 Check for 5vDC at the Auto Stop sensor. Disconnect the Auto Stop
cable connector from the Auto Stop sensor, turn the treadmill’s
"On/Off" switch to "On", and check for 5vDC between the red and
black wire in the Auto Stop cable connector. If 5vDC is present at
the at the Auto Stop connector of the console, but not at the end of
the cable, then replace the Auto Stop cable.
4 Visually inspect the Auto Stop sensor for physical damage. Replace
if appropriate. Access the Service Access software (hardware
validation tests), and select the Auto Stop test (see section-5).
If the feature is enabled the P80 Auto Stop sensor test will count
the number of times the magnet crosses the sensor. The P10, P20 and
P30 consoles will display "USER DETECTED" if motion is detected from
the running deck or "NO USER DETECTED" if no motion is detected from
the running deck. If the Auto Stop test in the P80 did not count
steps or if the P10, P20 or P30 consoles displayed "NO USER
DETECTED", disconnect the Auto Stop cable from the Auto Stop sensor
and check for 5vDC between the red and black wire. If 5vDC is
present replace the Auto Stop sensor.
1 Verify wireless heart rate with a known good chest strap transmitter
or test transmitter. If the heart rate reading is erratic,
incorrect, or absent, continue with step 2.
NOTE: It may be necessary to lean in closer to the console at first to
allow receiver to begin to acquire a heart rate signal.
2 Verify that the HHHR board has the correct operating voltage.
Connect a voltmeter to VCC and Ground on the Power/Signal connector.
The voltage should read between 4.5 and 5.5VDC.
3 Identify other sources of wireless interference signals in close
proximity to the unit (such as Wi-Fi networks, cordless phones,
etc.).
NOTE: Wi-Fi network is transmitting in close proximity to the treadmill
the heart rate system MAY pick it up. Using an ohmmeter, verify that
upper and lower PCAs have a good electrical path to chassis ground.
4 If the above procedures do not correct the problem, replace the
heart rate board.
Possible sources of interference signals include, BUT NOT LIMITED TO:
Wi-Fi Network Routers
Cordless Telephones
Cell Phones
Electronic Dog Fences
Garage Door Remotes
Noisy AC feeds
Florescent light ballasts
1 Set the treadmill circuit breaker in the off position and unplug the
treadmill’s line cord from the AC outlet.
2 Remove the treadmill’s hood.
3 Remove the two screws that fasten the AC input panel to the frame.
4 Disconnect the wiring from the circuit breaker (2 blue wires on 120
Vac treadmills or 2 blue and 2 brown wires on 240 Vac
treadmills).Note: The figure below is showing a 240 volt
configuration.
Figure 22: AC Input Panel
5 Lift the AC input panel from the frame and rotate it to expose the
circuit breaker mounting screws.
Figure 23: AC Input Panel Hardware
6 Remove the two screws retaining the circuit breaker and remove the
7 Reference the label on the replacement circuit breaker and set the
circuit breaker in its mounting position with the LINE side of the
breaker facing the input module and the LOAD side of the circuit
breaker facing the AC line filter. Fasten the circuit breaker with the
hardware removed in step 6.
NOTE:
On 120 Vac treadmills connect the blue wire from the input module to the
LINE terminal on the circuit breaker and the blue wire from the AC line filter
to the LOAD terminal on the circuit breaker.
On 240 Vac treadmills connect the blue wire from the input module to the
upper LINE terminal on the circuit breaker and the blue wire from the AC
line filter to the upper LOAD terminal on the circuit breaker. Connect the
brown wire from the input module to the lower LINE terminal on the circuit
breaker and the brown wire from the AC line filter to the lower LOAD
terminal on the circuit breaker.
8 Set the input panel in its mounting position and fasten it with the
hardware removed in step 3.
9 Thoroughly check the treadmill per, Checking Treadmill Operation (see
1 Set the treadmill circuit breaker in the off position and unplug the
treadmill’s line cord from the AC outlet.
2 Remove the treadmill’s hood.
3 Remove the two screws that fasten the AC input panel to the frame, See
Figure below.
4 Disconnect the wiring from the AC line filter (2 blue wires, 2 brown
wires and a green/yellow wire).
5 Lift the AC input panel from the frame and rotate it to expose the AC
line filter mounting screws.
Figure 24: AC Input Panel Hardware
6 Remove the screws that retain the AC line filter. Remove the AC line
filter.
7 Set the replacement AC line filter in its mounting position with the
side with three terminals facing the circuit breaker and replace the
screws removed in step 6.
NOTE: On 120 Vac and 240 Vac treadmills, connect the blue wire from the
power control module to the L1 terminal on the LOAD side of the AC line
filter and the brown wire from the power control module to the L2 terminal
on the LOAD side of the AC line filter.
On 120 Vac treadmills, connect the blue wire from the input module to the
L1 terminal on the LINE side of the AC line filter, the brown wire from the
circuit breaker to the L2 terminal on the LINE side of the AC line filter and
the green/yellow wire to the (non-insulated) terminal mounted directly on
the line filter case.
On 240 Vac treadmills, connect the blue wire from the circuit breaker to the
L1 terminal on the LINE side of the AC line filter, the brown wire from the
circuit breaker to the L2 terminal on the LINE side of the AC line filter and
the green/yellow wire to the (non-insulated) terminal mounted directly on
the line filter case.
Caution: Do not place the auto stop magnet on or near a steel structure.
If the magnet assembly comes in contact with a steel structure and then
pulled away from the steel structure, the magnet can become dislodged
from the magnet assembly housing. Should this occur, contact PRECOR
customer service for possible options for repairing the magnet assembly
or to obtain a replacement part.
1 Remove the motor hood.
2 Unplug the Auto Stop Cable from the Auto Stop assembly.
3 The auto stop sensor assembly has round alignment tabs that match the
holes of the treadmill frame support. With one hand grasp the side of
the Auto Stop sensor assembly that is closest to the outside of the
treadmill and apply pressure toward the running deck. With your other
hand push on each alignment tab from the inside of the frame mounting
holes. The Auto Stop Assembly should disengage from the frame.
Figure 28: Auto Stop Sensor Mounting
4 Position the replacement auto stop assembly with the cable connector
facing to the right side of the treadmill. Slide the auto stop
assembly over the treadmill frame support and push down until the
round tabs align with the holes in the support. The round tabs will
snap into the treadmills frame mounting holes securing the auto stop
assembly in place.
5 Check the alignment of the magnet and the auto stop assembly. The
magnet and the auto stop assembly each have an alignment mark on the
top of their housings. The magnet mark and the auto stop mark should
align and the gap should be approximately 3/16 of an inch between the
housings. A 3/16 allen wrench can be used as a feeler gauge to set the
correct gap. If the gap or alignment are off adjust the running deck
until the magnet and auto housing are properly aligned. See procedure,
Replacing the Auto Stop Magnet (on page 89)
6 Replace the Auto Stop Cable to the Auto Stop Sensor Assembly.
1 Remove the motor hood.
2 Remove the left and right trim strips from the treadmill deck.
3 Remove the four mounting bolts and two top plates that fasten the
running deck to the pivot bracket at the back end of the treadmill.
4 Pull the running deck out from the right side of the treadmill just
far enough to expose the front right edge of the running deck. (Left
and Right side orientations are based as if you were standing on the
treadmill facing the console.)
Figure 29: Running Deck Removal
5 Pry out the two push fasteners from the deck using a flat head screw
driver and remove the Auto Stop magnet.
6 Align the replacement magnet on the running deck and then secure the
magnet to the running deck using the two push fasteners removed in
step 4.
7 Slide the running deck back into position over the running deck pivot
bracket. Align the bottom plate and pivot bracket holes with the