Precision Digital PD6730X User guide

Page 1
PD6730X Field-Mount Modbus® Scanners
PRECISION DIGITAL CORPORATION
www.predig.com
Instruction Manual
• NEMA 4X, IP66 Field-Mount Modbus Scanners
• Modbus Master, Slave, or Snooper Mode
• 0.4" (10.2 mm) 7 Alphanumeric Characters Lower Display for Process Variables, Custom Units, and Tags
• 5-Digit Decimal Display or Feet & Inches Display
• Display Mountable at 0°, 90°, 180°, & 270°
• SafeTouch Through-Window Button Programming
• Scan up to 16 Modbus Process Variables
• Independent Scaling, Tag, and Unit for Each PV
• Backlight Standard on All Models
• Isolated 4-20 mA Output Option
• Two Isolated Pulse Outputs Standard, up to 5 kHz
• Operating Temperature Range: -40 to 75°C (-40 to 167°F)
• Conformal Coated PCBs for Dust and Humidity Protection
• Password Protection
• Data Logging Functions and Modbus Accessible Data
• Free ScanView EX Programming Software
• On-Board Three-Wire Isolated RS-485 with Modbus RTU
• Wide Viewing Angle
• Flanges for Wall or Pipe Mounting
• Three 3/4" NPT Threaded Conduit Openings (Two Plugs Provided)
• 2" U-Bolt Kits Available
• Stainless Steel Tag Available
• 3-Year Warranty
233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • Fax (508) 655-8990
Page 2
PD6730X Field-Mount Modbus Scanners
Disclaimer
The information contained in this document is subject to change without notice. Precision Digital Corporation makes no representations or warranties with respect to the contents hereof; and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
• Read complete instructions prior to installation and operation of the scanner.
• Risk of electric shock or personal injury.
• This product is not recommended for life support
applications or applications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. Precision Digital Corporation shall not be held liable for damages resulting from such improper use.
• Failure to follow installation guidelines could result in death or serious injury. Make sure only qualified personnel perform the installation.
WARNING
Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Limited Warranty
Precision Digital Corporation warrants this product against defects in material or workmanship for the specified period under “Specifications” from the date of shipment from the factory. Precision Digital’s liability under this limited warranty shall not exceed the purchase value, repair, or replacement of the defective unit. See Warranty Information and Terms & Conditions on www.predig.com details.
© 2021 Precision Digital Corporation. All rights reserved.
for complete
Instruction Manual

Introduction

The field-mount Vantageview Super Snoopers are serial input RS-485 Modbus Modbus devices are ideal for applications in need of a rugged solution. The Vantageview decimal version has a two-line decimal display. The Vantageview feet & inches version’s top line displays level in feet and inches up to 399 ft, 11 and 15/16 inches. It includes a 20-segment tank level indicator.
Each can accept up to 16 Modbus process variables (PVs), from up to 16 devices. The scanners automatically cycle through the PVs, with the ability to manually cycle PVs or pause scanning.
Up to four math channels (CV1-CV4) may be used to perform math functions on any of the input variables. Math functions include sum, difference, weighted average, ratio and more. Nested math functions may be used in these math equations, allowing for complex math functions.
The display is programmable to show any input, math channel, units, or tags, on a variety of display combinations between the top and bottom displays.
Standard features include SafeTouch through-window buttons for operating the scanner without removing the cover, a backlight that makes the display mode visible in any lighting condition, 511 points of input data logging, and two open collector pulse or alarm outputs. A 4-20 mA output is available as an option.
The enclosure has three threaded conduit holes, inte­grated pipe or wall mounting flanges, and allows for easy installation of tamper seals. Two conduit plugs are installed; additional plugs are available (part num­ber PDAPLUG75P).
Free, PC-based, ScanView EX software that connects to the scanner via the PDA8068, PDA7485-I, or the
PDA8485-I is available for programming and setup of
the instrument.
The instrument can also be programmed using the four SafeTouch through-window buttons, without removing the cover, or with four internal push-buttons.
The PD6730X includes on-board data logging of up to 511 points.
®
RTU scanners. These
2
Page 3
PD6730X Field-Mount Modbus Scanners

Ordering Information

Model Description
PD6730-AX0-I-2 Modbus RS-485 RTU scanner,
PD6730-AXA-I-2
PD6730-AX0-I-L
PD6730-AXA-I-L Modbus RS-485 RTU scanner,
Accessories
Model Description
PDAPLUG75P 3/4" Plastic Conduit/Stopping Plug
PDA0001 3/4" M-NPT to F-M20 Reducer
PDA0002 3/4" M-NPT to 1/2" F-NPT Reducer
PDA1024-01 24 VDC Power Supply for DIN Rail
PDA8068 USB Serial Adapter for Programming
PDA7485-I PDA7485 RS-232 to RS-485 Converter
PDA8485-I USB to RS-485 Isolated Converter
PDA6846
PDA6846-SS
PDA-SSTAG
9-30 VDC power.
Modbus RS-485 RTU scanner, isolated 4-20 mA output, 9-30 VDC power.
Modbus RS-485 RTU scanner, feet & inches display, 9-30 VDC power.
feet & inches display, isolated 4-20 mA output, 9-30 VDC power.
Steel 2" U-Bolt Kit. All Material: Zinc Plated Steel; (1) U-Bolt for 2" Pipe with (2 each) Washers, Lock Washers, and Nuts.
Stainless Steel 2" U-Bolt Kit. All
Material: Stainless Steel; (1) U-Bolt for 2" Pipe with (2 each) Washers, Lock Washers, and Nuts.
Custom Stainless Steel Tag (see website for convenient ordering form)
Instruction Manual
PDA1024-01 24 VDC Power Supply
The PDA1024-01 is a DIN rail mounted 1.5 A, 24 VDC power supply that can be used to power the PD6730X.
PDA8068 USB Serial Adapter
The PDA8068 USB serial adapter is used to connect the PD6730X directly to a computer via USB. It is intended to be used for programming only. No live monitoring is possible with this module.
PDA6846 2" U-Bolt Kits
The PDA6846 U-Bolt Kits provide a convenient way to mount the PD6730X to 1.5" or 2" pipes. They are
available in steel and stainless steel
.
PDA-SSTAG Stainless Steel Tag
The PDA-SSTAG is a laser etched stainless steel tag that can be customized with three lines of text. Each tag comes with a stainless steel wire and lead seal for easy mounting wherever you need.
3
Page 4
PD6730X Field-Mount Modbus Scanners
Table of Contents
Introduction ......................................................................................................... 2
Ordering Information .......................................................................................... 3
Specifications ..................................................................................................... 7
General ............................................................................................................ 7
Modbus Operating Modes ............................................................................. 8
Serial Communications ................................................................................. 8
Modbus Scanner Process Variables............................................................. 8
Math Channels ................................................................................................ 9
4-20 mA Transmitter Output .......................................................................... 9
Open Collector Outputs ................................................................................. 9
ScanView EX Programming Software ........................................................ 10
Safety Information ........................................................................................ 11
Tag and Tamper Seal Loop ......................................................................... 11
PDA-SSTAG Stainless Steel Tag .............................................................. 11
Installation......................................................................................................... 12
Unpacking ..................................................................................................... 12
Conduit Plugs ............................................................................................... 12
Mounting ....................................................................................................... 12
Dimensions ................................................................................................... 12
Connections ................................................................................................. 13
Wiring Diagrams ........................................................................................... 14
DC Power Connection ............................................................................... 14
4-20 mA Transmitter Output Connections .................................................. 14
RS-485 Signal Connections ....................................................................... 14
Open Collector Output Connections .......................................................... 14
Setup and Programming .................................................................................. 15
Overview ....................................................................................................... 15
ScanView EX Programming Software ........................................................ 15
SafeTouch Buttons ...................................................................................... 15
SafeTouch Button Tips and Troubleshooting ............................................. 16
Buttons and Display ..................................................................................... 17
Setting Numeric Values ............................................................................... 18
Setting Alphanumeric Labels (LABEL) ......................................................... 18
Main Menu ......................................................................................................... 19
Display Functions & Messages ................................................................... 19
Main Menu Programming ............................................................................ 21
Select Operating Mode (MODE) ..................................................................... 21
Master Mode (MASTER) .................................................................................. 22
PV Number Configuration (PV NUM) ........................................................... 22
Poll Time (T POLL) ..................................................................................... 23
Response Timeout (TIMEOUT) .................................................................... 23
Retries Before Error (RETRIES) .................................................................. 23
Slave Mode (SLAVE) ...................................................................................... 24
PV Number Configuration (PV NUM) ........................................................... 24
Slave Response Timeout (TIMEOUT) .......................................................... 24
Snooper Mode (SNOOPER) ............................................................................. 25
Snooper Mode Response Time (T RESP) .................................................. 25
Setup the Display (SETUP) ............................................................................ 26
Instruction Manual
4
Page 5
PD6730X Field-Mount Modbus Scanners
Setting Up the Display (DISPLAY) ................................................................ 26
Top Display (TOPDSP) ................................................................................. 27
Bottom Display (BOTDSP) ............................................................................ 27
PV Display Setup (PVSETUP) ...................................................................... 28
Math Channel Display Setup (MATH) .......................................................... 31
Tank Size Indicator (TANKSZ) ..................................................................... 33
Tag Display Time (T-TAG) .......................................................................... 33
Units Display Time (T-UNITS) .................................................................... 33
Scan Time (T-SCAN) ................................................................................... 33
Serial Communications Settings (COMM) ..................................................... 34
Scanner Modbus ID (SCAN ID) .................................................................. 34
Baud Rate (BAUD) ....................................................................................... 34
Transmit Delay Time (TXDELAY) ................................................................. 34
Parity (PARTIY)........................................................................................... 34
Advanced Menu ................................................................................................ 35
Display Functions & Messages ................................................................... 35
Advanced Menu Programming (ADVANCE) .................................................. 37
Open Collector Outputs (OUTPUT) .............................................................. 38
Scaling the 4-20 mA Analog Output (Aout) ................................................ 40
Selecting the Analog Output Source .......................................................... 40
Enter Display and Output Values ............................................................... 41
Math Channel (CV1 to CV4) Programming (MATH) ..................................... 41
Setting Up Passwords (PASSWRD) ............................................................... 43
Custom (CUSTOM) ....................................................................................... 44
System (SYSTEM) ........................................................................................ 45
Operation........................................................................................................... 49
Front Panel Buttons Operation ................................................................... 49
Pause/Start Automatic Scanning ................................................................ 50
Manual Scanning .......................................................................................... 50
Reset Scanner to Factory Defaults ............................................................. 50
Factory Defaults & User Settings................................................................ 51
Application Examples ...................................................................................... 55
Example 1: Master Polling Multivariable Level Transmitters ................... 55
Example 2: Snooper Displaying Flow Rate from Modbus Flowmeters ... 59
Troubleshooting ............................................................................................... 61
Troubleshooting Tips ................................................................................... 61
Quick User Interface Reference ...................................................................... 62
Instruction Manual
5
Page 6
PD6730X Field-Mount Modbus Scanners
Table of Figures
Figure 1. Enclosure Dimensions – Front View ................................................... 12
Figure 2. Enclosure Dimensions – Side Cross Section View ........................... 12
Figure 3. Connector Board Mounted in Base of Enclosure .............................. 13
Figure 4. Connectors & Switches on Rear of Display Module .......................... 13
Figure 5. DC Power Connections ........................................................................ 14
Figure 6. 4-20 mA Output Connections .............................................................. 14
Figure 7. RS-485 3-Wire Serial Connections ...................................................... 14
Figure 8. RS-485 5-Wire Serial Connections ...................................................... 14
Figure 9. Open Collector Output Connections ................................................... 14
Figure 10. Real Time Clock Display Example – Decimal Model ........................ 45
Figure 11. Real Time Clock Display Example – Feet & Inches Model .............. 45
Instruction Manual
6
Page 7
PD6730X Field-Mount Modbus Scanners
Display
Top
Five digits, (0-99999),
automatic lead zero blanking.
Bottom
Seven alphanumeric
automatic lead zero blanking.
Symbols
High alarm, low alarm,
mode/disable, password lock
Feet & Inches
Top
Feet & Inches,
or 1/8 fraction display
Bottom
Seven Characters,
14-segment, 7-digits
Tank
Indicator
20-segments, F (Full) Alarm Indication
High and low alarm Backlight
White
Display
Top and Bottom Display*: Process
display used only for level Modbus process variables or math channels.
Backlight
White; it can be disabled/enabled in the
automatically turned off below -20°C.
Alarm Indication
Flashing display plus HI/LO indicators
Scan and
Ambient > -20°C: Modbus PV scan rate
minimum.
Underrange
Upper Display: Decimal display flashes
Lower Display: Flashes -
Overrrange
Upper Display: Decimal display flashes
Lower Display: Flashes
Programming
Four SafeTouch through-window buttons
Free ScanView EX software.
Password
Restricts modifications of programmed
password to make changes.
Input Power
9-30 VDC, 2.2 W
Data Logging
Up to 511 records, recorded 4/day at
log number.
Isolation
All Models:
500 V power-to-RS-485 serial communications
-AXA Models:
500 V power-to-analog output
Environmental
Operating temperature range: -40 to 75°C
Printed circuit boards are conformally coated.
Non-Volatile
All programmed settings are stored in
years if power is lost.
Connections
Screw terminals accept 12 to 22 AWG wire
Enclosure
NEMA 4X, IP66 plastic field enclosure,
Two ¾" NPT plastic conduit plugs included.
Tag or Tamper Seal Loop
Loops molded into base and cover of enclosure for tamper wire or tags.
Mounting
May be mounted directly to conduit. Two
mounting. See Dimensions on page 12.
Display Orientation
Display may be mounted at 90° incre­ments up to 270° from default orientation.
Overall Dimensions
5.67" x 5.25" x 4.18" (W x H x D) (144 mm x 133 mm x 106 mm)
Weight
1.65 lbs (26.4 oz, 0.75 kg)
Warranty
3 years parts and labor. See Warranty
www.predig.com for complete details.

Specifications

Except where noted all specifications apply to operation at +25°C.

General

Instruction Manual
settings to require re-entering the
Display (-L Models)
Assignment
Display
Display
Display
Display
Level
Variables (PV); Alternating PV and Units, Tag and PV, or Tag, PV, and Units. Bottom Display: All Top Display Options or Off Units and tag independent for each PV. * On feet and inches display models, top
0.7" (17.8 mm) high, 7- segment,
characters,
0.4" (10.2 mm) high, 14-segment,
SafeTouch button sleep
0.60" (15.2 mm) high,
FT
0 to 399 7-segment, programmable 1/16
0.4" (10.2 mm) high,
and E (Empty)
1115/16 IN
Memory
specific times or at defined time intervals. Record contains first eight enabled Mod­bus PVs; C1-4 if enabled; date; time, and
Storage temperature range: -40 to 75°C Backlight deactivated below temperatures ≈ -20°C Relative humidity: 0 to 90% non-condens­ing
non-volatile memory for a minimum of ten
polycarbonate with UV stabilizer. Color: grey. Window: Clear polycarbonate with UV stabilizer. Three ¾" NPT threaded conduit openings.
slotted flanges for wall mounting or NPS 1½" to 2½" or DN 40 to 65 mm pipe
Advanced - System menu. The backlight is
Update Rate
Method
programmable from 2 to 99 seconds per PV. Tag and units programmable for 1 to 5 second alternation. Ambient < -20°C: All Modbus scan, alter­nating units and tags 1 update/10 seconds
-9999 Level display flashes to 399FT 1115/16
99999 Level display flashes to 399FT 1115/16
when cover is installed. Four internal pushbuttons when cover is removed.
Information and Terms & Conditions on
IN
999999
IN
999999
7
Page 8
PD6730X Field-Mount Modbus Scanners
Master
Processes and displays data read from
individually.
Slave
Processes data sent to it from a
https://www.predig.com for details.
Snooper
Listens to the Modbus traffic and picks up
returned value will be read.
Master Poll Time
0.1 to 99.9 sec. Time between read­commands.
Master
0.1 to 99.9 seconds. Time elapsed after a
considers that request to have failed.
Number of
1-99. The number of retries the scanner
reporting an error condition on the PV.
Snooper
Time
0.1 to 99.9 seconds. Time since the last
error.
Slave Timeout
0.0 to 99.9 seconds. Time elapsed after the last data received from a master before the scanner considers the data to be out of
despite not being updated regularly.
Protocol
Modbus® RTU
Scanner Id
1 – 247. Specifies the address of the PD6730X.
Baud Rate
1,200; 4,800; 9,600; 19,200; 38,400; 57,600; or 115,200 bps
Transmit Time Delay
Parity/Stop Bit
with 2 stop bits
Byte-to-Byte Timeout
Note: Refer to Modbus Register Tables at www.predig.com for details.
PV Inputs
Up to 16 independently programmed
disabled.
Slave Id
Specifies which device on the bus to
(Slave ID for PV1-16).
Register Number
Specifies which register(s) to read in
only.
Function Code
03, 04, and 65 (used to read 32 bit
only.
Data Type
Select the data format of the PVs.
point only.
Byte Order
Integer data programmable as binary
for short.

Modbus Operating Modes

Modbus RTU slave devices. Up to 16 process variables (PVs) from up to 16 slave devices. Each PV programmed
Modbus RTU master device. Note: Refer to Modbus Register Tables at
a specific register or registers being polled by a Master device from a specific slave device and processes the data being read. Up to 16 process variables (PVs) from up to 16 devices. If multiple registers are polled by the master with one command, only the first
Timeout
Retries
Response
poll request is made before the scanner
will make when requesting data before
PV update the before being considered an
Instruction Manual

Modbus Scanner Process Variables

Modbus process variables (PVs) may be scanned (Master mode) or detected (Snooper mode). Each of the 16 Modbus PVs may be enabled or
monitor. Valid for Master and Snooper modes only. Assign the slave ID or address (1-247) of each of the devices containing the process variables to be displayed
the devices on the bus. 5 Digit Function 03: 40001–49999; 04: 30001–39999; or 65: 1–9999. 6 Digit Function 03: 400001–465535 or 04: 300001–365535; or 65: 1–65535. Range is dependent on Function Code selection (03, 04, or 65) Will read 2 registers for Long integer
and Floating point data types; the register entered and the next consecutive register number. Valid for Master and Snooper modes

Serial Communications

date. Programming 0 disables the timeout, and PV data will be displayed indefinitely
Programmable between 0 and 199 ms
Even, odd, none with 1 stop bit, or none
Max of 1.5 character times or 750 μs
registers). Master & Snooper modes
Select between short integer (2 byte), long integer (4 byte), or floating point (4 byte). Slave mode uses floating
or BCD, and signed or unsigned. Byte order selectable as big-endian (1234), little-endian (4321), byte swap big­endian (2143), or byte swap little­endian (3412). Byte swap unavailable
8
Page 9
PD6730X Field-Mount Modbus Scanners
Math Result
Four math channels CV1-CV4.
programmed for a math function.
Math Functions
Parameter 1 (PAR1), parameter 2
math channel C1-C4.
Math Function
Function
Setting
Addition
PAR1 + PAR2
Difference
PAR1 - PAR2
Multiplication
PAR1 * PAR2
Division
PAR1 / PAR2
Absolute diff.
Abs(PAR1 - PAR2)
Weighted avg.
((PAR1 – PAR2)*PAR3) +PAR2
Draw
((PAR1 / PAR2) – 1) * PAR3
Ratio
(PAR1 / PAR2) * PAR3
Concentration
PAR1 / (PAR1 + PAR2) * PAR3
Constant
Constant
Long Integer
Constant
Floating Pt.
Constant
Absolute Value
Abs(PAR1)
Square Root
√(PAR1)
Parameter
Parameter 1 (PAR1), parameter 2
Parameter
Defining parameter 1 or 2 as a math
Output Source
Modbus PV 1-16, math channel 1-4, or disabled
Scaling Range
4.000 to 20.000 mA for any display range.
Disable
If disabled, the output will output 3.2 mA
Calibration
Factory Calibrated:
0.0 to 1000.0 = 4-20 mA output
Underrange
Output Underrange: 3.8 mA
Overrange
Display Overrange: 20.5 mA
Output Overrange: 20.5 mA
Accuracy
± 0.05% span ± 0.004 mA
Temperature Drift
0.08 µA/°C max from -40 to 75°C ambient
External Loop Power Supply
30 VDC maximum
Output Loop
Power supply
Minimum
Maximum
24 VDC
10 Ω
750 Ω
30 VDC
100 Ω
1100 Ω
Note: loop-powered backlight subtracts 150 Ω from maximum resistance figures above.
Output
Two open collector pulse outputs.
math channel, constant timed pulse output;
Out 2), or off.
Rating
Isolated open collector, sinking NPN, 30 VDC @ 150 mA max.
Alarm Output
Assign to Modbus PV 1-16 or math
point.
Alarm Deadband
0-100% FS, user selectable
Alarm Acknowledge
Front panel ACK button resets output and screen indication.
Pulse Output
The pulse output count (
) is
Count value.
Pulse Output Pulse Width
Unless otherwise stated, pulses are 50% duty cycle for required frequency.
Pulse Output
Frequency
5 kHz, pulse width at 50% duty cycle.
will display
Quadrature
Output set to quadrature will lag the other
output frequency. Minimum 1 Hz
Timer Output
Programmable on and off time, repeating
maximum
second, maximum 10,000 seconds.

Math Channels

Instruction Manual

4-20 mA Transmitter Output

Chanels
None
Selection
Nested Math
Each math channel may be
(PAR2), and parameter 3 (PAR3) independently programmable for each
SUM DIF MULTI DIVIDE DIFABS WAVG DRAW RATIO CONCEN CONST LONG FLOAT
Disable
NONE ABS SQrt
(PAR2), and parameter 3 (PAR3) selectable as: Modbus PV1-16, math channel CV1-4 or any math function.
function will prompt for level 2 parameter 1 (L2P1), level 2 parameter 2 (L2P2), and/or level 2 parameter 3 (L2P3). Level 2 parameters function identically as parameter 1 and 2 for nested math functions.
Resistance

Open Collector Outputs

Assignment
Count
Individually programmable for Modbus PV,
quadrature outputs (requires Out 1 and
channel 1-4, for high or low alarm trip
COUNT
programmable from 0.000001 to 9999999. PV and math channels generate a frequency equal to the PV or math value divided by the
9
Maximum
Output
If the outputs exceed 5 kHz, the scanner
pUlse OVERRNG
pulse output by 90° (1/4 duty cycle) at
cycle. Minimum period 0.1 second, 100,000 seconds. Minimum pulse time 0.01
Page 10
PD6730X Field-Mount Modbus Scanners
System Requirements
Windows® 7/8/10 (Windows 32-bit or 64-bit operating systems)
Communications
485 Isolated
Protocol
Modbus RTU
Scanner Address
1-247
Baud Rate
1200 bps to 115,200 bps
Configuration
Configure one scanner at a time.
Monitor file format: Saved as ".mcf".
Data Logging Report
Saved as “.csv” file format.

ScanView EX Programming Software

PDA8068 Meter-to-USB Adapter for programming,
PDA7485-I RS-232 to RS­Converter (Cable not included),
PDA8485-I USB to RS-485 Isolated Converter (Cable not included).
Instruction Manual
File format: Saved as “.mve". Printing: Configuration can be printed.
The Display window is used for programming the upper display, lower display, dwell times, PV display setup, math display setup, and tank size indicator.
The Mode/PV Setup window is used for selecting master, slave, or snooper modes and setting up from 1-16 PVs.
The Monitor window is used for monitoring up to 16 process variables; each is programmed individually to display information in selected engineering units with custom tags.
The Data Logging window is used to set the computer and meter time/date, set the on-board data log set time or time interval method, set PC data log intervals and time units, and manual control of PC data log with start/stop buttons.
For detailed programming software instructions or to download ScanView EX software, visit predig.com/scanview-ex
10
.
Page 11
PD6730X Field-Mount Modbus Scanners

Safety Information

• Read complete instructions prior to installation and operation of the scanner.
• Installation and service should be performed only by trained service personnel. Service requiring replacement of internal components must be performed at the factory.
• If the scanner is installed in a high voltage environment and a fault or installation error occurs, high voltage may be present on any lead.

Tag and Tamper Seal Loop

Instruction Manual

PDA-SSTAG Stainless Steel Tag

The PDA-SSTAG is a laser etched stainless steel tag that can be customized with three lines of text. Each tag comes with a stainless steel wire and lead seal for easy mounting wherever you need.
Dimensions
The PD6730X comes with tag and tamper seal loops molded into the plastic enclosure. One loop is located on the cover of the enclosure and the other one is on the base of the enclosure. These are used for inserting a stainless steel wire through the holes and attaching a lead seal to prevent unauthorized removal of the enclosure cover. A custom stainless steel tag (PDA­SSTAG) can also be attached to the wire.
Ordering Guide
PDA-SSTAG
When ordering custom tags, enter your custom text in the available form located at predig.com/PDA-SSTAG or click here to download the Stainless Steel Tag Or-
der Form
Custom Stainless Steel Tag (see website for convenient ordering form)
11
Page 12
PD6730X Field-Mount Modbus Scanners
(85.1)
(57.2)
(144.0)
5.25
(133.3)
5.67
3.35
2.25
0.33
(8.3)
(106.1)
4.18
Ø
3.34
(84.9)
Instruction Manual

Installation

• Hazardous voltages may exist within enclosure.
• Installation and service should be performed only
by trained service personnel.
Wiring connectors are accessed by opening the enclosure. To access electrical connectors, remove the two captive screws, then disconnect the ribbon cable from the display module and set the display module aside.

Unpacking

Remove the scanner from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier.
If any part is missing or the scanner malfunctions, please contact your supplier or the factory for assistance.

Conduit Plugs

The PD6730X is supplied with two IP68 rated conduit plugs for installations that require the use of only one conduit entry. The conduit/stopping plugs have 1.29" wrenching flats and a screwdriver slot.

Dimensions

All units: Inches (mm)
Figure 1. Enclosure Dimensions – Front View

Mounting

The PD6730X has two slotted mounting flanges that may be used for pipe mounting or wall mounting. Alternatively, the unit may be supported by the conduit using the conduit holes provided.
Refer to Figure 1.
• Do not attempt to loosen or remove flange bolts while the scanner is in service.
Figure 2. Enclosure Dimensions –
Side Cross Section View
12
Page 13
PD6730X Field-Mount Modbus Scanners
D+
P+

Connections

To access the connectors, remove the enclosure cover and unscrew the two captive screws that fasten the display module into the enclosure. Disconnect the ribbon cable and remove the display module.
RS-485 serial connections are made to a removable terminal block on the back of the display module. Power and signal connections are made to a screw terminal connector in the base of the enclosure.
RS-485 data B (non-inverting) connection
D- RS-485 data A (inverting) connection
G RS-485 shield ground connection
DC Power positive terminal connection
COM
RST Contact closure reset pull-up to 1.8 VDC
S+
S-
OC1+ Open collector output 1 positive terminal
DC power supply input return/negative, reset contact closure common
Pulse input signal positive terminal connection (Refer to LIM6730XPulse for instructions).
Pulse input signal negative terminal connection (Refer to LIM6730XPulse for instructions).
Instruction Manual
• Observe all safety regulations. Electrical wiring should be performed in accordance with all agency requirements and applicable national, state, and local codes to prevent damage to the scanner and ensure personnel safety.
• Static electricity can damage sensitive components.
• Observe safe handling precautions for static-sensitive components.
• If the scanner is installed in a high voltage environment and a fault or installation error occurs, high voltage may be present on any lead or terminal.
OC1- Open collector output 1 negative terminal
OC2+ Open collector output 2 positive terminal
OC2- Open collector output 2 negative terminal
LP+
LP-
Refer to Figure 3 and Figure 4 for terminal positions.
4-20 mA transmitter output DC power positive terminal connection.
4-20 mA transmitter output DC power negative terminal connection.
Figure 3. Connector Board Mounted in Base of
Enclosure
Figure 4. Connectors & Switches on Rear of Display
Module
13
Page 14
PD6730X Field-Mount Modbus Scanners
Power Supply
COM
RST
P+
S+
S-
LP- LP+
Power Supply
4-20 mA Input
Device
Vantageview
DO
DO
DI
DI
GND
RS-485 DEVICE
D+ D­G
+
Alarm Indicator/
Pulse Counter (e.g. PD6300)
-
5-30 VDC
150 mA MAX
P+
COM RST
S+
S-
OC1+
OC1-
OC2+
OC2-
LP+LP-

Wiring Diagrams

DC Power Connection

DC power is wired to terminals P+ and COM as shown in Figure 5. To maintain input isolation, a separate power supply must be used to power the isolated 4-20 mA transmitter as shown in Figure 6.
Figure 5. DC Power Connections

4-20 mA Transmitter Output Connections

Output connections are made to two terminals labeled LP+ and LP-. Connect to an input device such as a re­mote display or chart recorder as shown in Figure 6.
Instruction Manual

RS-485 Signal Connections

The scanner includes a 3-wire RS-485 serial connec­tion. The cabling used for an RS-485 serial communi­cations network should always be a high quality cable such as Belden 8162 or Alpha 6203C. A 3-wire sys­tem requires two twisted pairs (the extra twisted pair is needed for the signal ground).
Figure 7. RS-485 3-Wire Serial Connections
Figure 8. RS-485 5-Wire Serial Connections

Open Collector Output Connections

Open collector output 1 and 2 connections are made to terminals labeled OC1+ and OC1-, and OC2+ and OC2-. Connect the alarm or pulse input device as shown in Figure 9.
Figure 6. 4-20 mA Output Connections
Figure 9. Open Collector Output Connections
14
Page 15
PD6730X Field-Mount Modbus Scanners
front window is being unblocked.

Setup and Programming

Overview

Setup and programming is done through the infrared through-window SafeTouch buttons, using the me­chanical buttons when uncovered, or with ScanView EX programming software. There are two slide switches located on the display module. One switch is used to lock or unlock the SafeTouch Buttons. The other switch is used to configure the pulse input (Refer to LIM6730XPulse for instructions).

ScanView EX Programming Software

The fastest and easiest way to program the meter is using the free ScanView EX programming software. This software greatly simplifies the programming pro­cess and allows the user to save configuration files for later use.
The ScanView EX software requires one of several options to connect to a PC depending on the PC’s hardware; The PDA8068
PDA7485-I RS-232 to RS-485 converter, or the PDA8485-I USB to RS-485 Isolated Converter to
connect the PC to the meter.
USB serial adapter,
Instruction Manual

SafeTouch Buttons

The PD6730X is equipped with four sensors that operate as through-window buttons so that it can be programmed and operated without removing the cover (and exposing the electronics). These buttons can be disabled for security by using the THRU­GLASS BUTTONS switch and selecting the OFF setting. This switch is located on the back of the removable electronics module.
SafeTouch Button Operation
To actuate a button, press and remove one finger to the window directly over the marked button area. Remove finger to at least 4 inches away from the window in between button activations. SafeTouch and mechanical buttons may be held to cycle through menus or digits in place of repeatedly pushing a button.
SafeTouch Power Save Mode
(Symbol shown on -2 decimal models only)
SafeTouch buttons enter a power saving mode after three minutes of inactivity. This mode is indicated by
a power symbol ( ) appearing in the lower right of the display. Only the MENU button is monitored in this mode. To activate the SafeTouch buttons, press and hold the menu button for up to five seconds. The display will read AWAKE, and the SafeTouch buttons will be fully enabled.
SafeTouch Disabled Mode When the cover is removed, the four mechanical
buttons located next to the sensors may be used. The sensors are disabled when a mechanical button is pressed and will automatically be re-enabled after 60 seconds of inactivity. The SafeTouch power
symbol ( ) will blink in the lower right of the display if the buttons are disabled due to a mechanical pushbutton being pressed.
SafeTouch Button Equalize Delay
The SafeTouch buttons are designed to constantly recalibrate for ambient conditions. When the cover position is changed, the cover is removed, or an ob­ject is removed that was placed over the front win­dow, it may take a moment for the SafeTouch but­tons to recalibrate to the change in conditions.
Allow up to 2 minutes for the SafeTouch buttons to recalibrate to new conditions in these cases where the cover position was changed, or the
To download the ScanView EX programming software, visit predig.com/scanview-ex
.
• SafeTouch will not work if two or more buttons are detected as being pressed simultaneously. Be careful to avoid triggering multiple buttons or reaching across one button location to press another.
15
Page 16
PD6730X Field-Mount Modbus Scanners

SafeTouch Button Tips and Troubleshooting

The SafeTouch Buttons are designed to filter normal levels of ambient interference and to protect against false triggering, however it is recommended that the SafeTouch Buttons be turned off (slide THRU-GLASS BUTTONS switch to OFF) if there is an infrared inter­ference source in line-of-sight to the display or if the buttons are not needed.
SafeTouch Button Tips:
• To the extent possible, install the display facing away from sunlight, windows, reflective objects, and any sources of infrared interference.
• Keep the window clean.
• Tighten the cover securely.
• Use a password to prevent tampering.
• If the cover has not been installed and secured
tightly, it may take a moment for the SafeTouch buttons to properly self-calibrate when the cover is tightened.
After all connections have been completed and veri­fied, connect the ribbon cable to the display module, fasten the display module to the base, install enclo­sure cover, and then apply power.
Instruction Manual
SafeTouch Button Equalize Delay
The SafeTouch buttons are designed to constantly recalibrate for ambient conditions. When the cover position is changed, the cover is removed, or an object is removed that was placed over the front window, it may take a moment for the SafeTouch buttons to recalibrate to the change in conditions.
Allow up to 2 minutes for the SafeTouch buttons to recalibrate to new conditions in these cases where the cover position was changed, or the front window is being unblocked.
16
Page 17
PD6730X Field-Mount Modbus Scanners
HI
High Alarm
LO
Low Alarm
Settings Lockout Password Enabled
SafeTouch Power Save/Dis-
Button
FT
Feet
IN
Inches and Fractional Inches
F
Tank Full Indicator
E
Tank Empty Indicator
HI
High Alarm
LO
Low Alarm
MENU
PREV
NEXT
SCAN

Buttons and Display

Decimal Display
Symbols (-2 Models)
Instruction Manual
Description
able Flashing: Temporarily Disabled Due to Mechanical
Decimal Display Model
Feet & Inches Display Model
Button
Symbol
Menu / SafeTouch Awake
Previous PV or Right Arrow
Up Arrow or Next PV
Enter or Start / Pause Scanning
Description
Feet & Inches Display
Symbols (-L Models)
Menu Button
• Hold the Menu SafeTouch button when in power save mode (display will show ) to
awaken SafeTouch buttons.
• Press the Menu button to enter Programming Mode.
• Press the Menu button during Programming Mode to return to the previous menu selections.
• Hold the Menu button for 1.5 seconds at any time to exit Programming Mode and return to Run Mode.
• Press and hold the Menu button for 3 seconds to access the Advanced Features of the scanner.
Right / Previous Button
• Press Previous to manually display the previous PV or input display.
• Press the Right arrow button in programming mode to move to the next digit or decimal position.
• Press the Right arrow button in programming mode to go backward through most selection menus.
Up / Next Button
• Press Next to manually display the next PV or input display.
• Press the Up arrow button in programming mode to scroll forward through the menus, decimal point, or to increment the value of a digit.
Enter / Scan Button
• Press Scan to pause automatic scanning.
• Press Scan to resume automatic scanning
when paused.
• Press the Enter button in programming mode to access a menu or to accept a setting.
Description
17
Page 18
PD6730X Field-Mount Modbus Scanners

Setting Numeric Values

Instruction Manual
The numeric values are set using the Right and Up arrow buttons. Press Right arrow to select next digit and Up arrow to increment digit.
The digit being changed blinks.
Press the Enter button, at any time, to accept a set­ting or Menu button to exit without saving changes.
The decimal point is set using the Right or Up arrow button in the Setup, Decimal Point menu.
Setting Alphanumeric Labels
LABEL)
(
Fully alphanumeric values are set using the Right button to select the digit, the Up and Right arrow but­tons to select the digit reading, and the Enter button to confirm and select the next digit.
Menus using this entering method include tags and custom units. After selecting the digit, and using the Up and Right arrows to modify the digit, the display will read CHAR.
Press Enter to confirm the new digit and proceed to the next digit.
The digit being changed blinks.
Press the Menu button to exit without saving changes.
18
Page 19
PD6730X Field-Mount Modbus Scanners
Display
Parameter
Action/Setting
PV
UNSIGND

Main Menu

Display Functions & Messages

The scanner displays various functions and mes­sages during setup, programming, and operation. The following table shows the main menu MODE, SETUP, and COMM menu functions and messages in the order they appear in the menu. Functions and messages that appear in the Advanced menu can be found in the Advanced Menu section on page 35.
MODE
MASTER
PV NUM
PV 1
ENABLE
SLAVEID
FUNCODE
REG NUM
DATATYP
FLOAT
SHORT
LONG
BINARY
BCD
SIGNED
BYTE
1234
4321
2143
3412
DISABLE
T POLL
Mode Enter Mode menu
Master Mode Select Master mode
PV Number Enter the Modbus PV
PV 1 – PV 16 Enter PV1 to PV16
Enable Enable the Modbus
Slave ID Enter the slave
Function Code
Register Number
Data Type Set the data type
Float Float data type
Short Short integer data
Long Long integer data
Binary Binary integer type
BCD
Unsigned Unsigned integer
Signed Signed integer type
Byte Select the byte
1243 Big endian
4321 Little endian
2143
3412
Disable Disable the Modbus
Poll Time
configuration menu
configuration menus
Modbus ID
Set the Modbus function code
Enter the slave register number
type
type
Binary coded decimal integer type
type
format
Big endian with byte swap
Little endian with byte swap
PV
Set the Modbus PV poll time
Instruction Manual
Display Parameter Action/Setting
TIMEOUT
RETRIES
SLAVE
PV NUM
PV 1
ENABLE
DISABLE
TIMEOUT
SNOOPER
PV NUM
T RESP
SETUP
DISPLAY
TOPDSP
PV
PV-U
TAG-PV
TG-PV-U
BOTDSP
TAG
TAG-U
UNITS
PV
TG-PV-U
OFF
PVSETUP
PV-1
FORMAT
Response Timeout
Retries Set number of retires
Slave Select Slave mode
PV Number Enter the Modbus PV
PV 1 – PV 16 Enter PV1 to PV16
Enable
Disable
Response Timeout
Snooper Mode Select Snooper
PV Number Enter the Modbus PV
Response Time Set Modbus
Setup Menu Enter Setup menu
Display Enter the Display
Top Display Set the function of
PV Display Modbus PV
PV & Units
Tag & PV Display tag and
Tag, PV, & Units Display tag, Modbus
Bottom Display Set the function of
Tag Display tags
Tag & Units Display tags and
Units Display units
PV Display Modbus PV
Tag, PV, & Units Display tag, Modbus
Off Turn off display
PV Setup
PV-1 to PV-16 Select PV1 to PV16
Format Enter PV display
Set Modbus communication response timeout
before display a PV communication error
configuration menu
configuration menus
Enable the Modbus PV
Disable the Modbus PV
Set Modbus response error time
mode
configuration menu
response error time
menu
the top display
Display Modbus PV and units
Modbus PV
PV, and units
the bottom display
units
PV, and units
Enter the PV Setup menu
format
19
Page 20
PD6730X Field-Mount Modbus Scanners
Display Parameter Action/Setting
TAG
UNITS
DISP.DP
FLOAT.DP
SCALE
FACTOR
LINEAR
MP-SCAL
MATH
CV 1
FORMAT
TAG
UNITS
Disp.DP
TANKSZ
T-TAG
T-UNITS
T-SCAN
PULSE.IN
COMM
SCAN ID
BAUD
TXDELAY
Tag Enter to edit PV tag
Units Enter to edit PV units
Display Decimal Point
Float Decimal Point
Scale Select the PV display
Conversion factor
Linear Linear scaling
Multipoint Scaling
Math
CV1 to CV4 Select math channel
Format Enter CV display
Tag Enter the CV tag
Units Enter the CV units
Display Decimal Point
Tank Size Enter tank level
Tag Time
Units Time Enter unit display
Scan Time Enter scan cycle time
Input Refer to pulse input
Communications Enter the
Scanner ID Enter the scanner’s
Baud Rate Select baud rate
Transmit Delay Enter the transmit
Set the PV display decimal point Note: Not available on Ft-In models.
Set the float decimal point location (if PV is float data type only) Note: Not available on Ft-In models.
scaling: factor, linear 2-point, or multi-point
Conversion factor scaling
Multipoint scaling for PV1
Enter Math menu (Will only appear if at least one math channel is enabled)
to configure CV 1 to CV4
format
Set the CV display decimal point
indicator full value (in feet for Ft & In version only)
Enter tag display time
time
(e.g. PV dwell time)
manual
Communications menu
Modbus ID (used if setup as a slave)
delay
Instruction Manual
Display Parameter Action/Setting
PARITY
EVEN
ODD
NONE 1
NONE2
Parity Select parity mode
Even Even parity
Odd Odd parity
None, 1 Stop Bit No parity, 1 stop bit
None, 2 Stop Bits
No parity, 2 stop bits
20
Page 21
PD6730X Field-Mount Modbus Scanners

Main Menu Programming

Instruction Manual

Select Operating Mode (MODE)

The main menu is used to navigate the programming menus and separates the most commonly used functions. The Mode menu is used to setup the scanner as a Modbus master, slave, or snooper, and define Modbus PVs. The Setup menu is used to setup general scanner parameters, such as display assignments. The Comm menu configures the RS-485 serial communications settings. The Advanced menu is used to configure more complex settings not used with most common applications.
Press Menu button to enter Programming Mode then press the Up arrow button to scroll through the main menu.
The Mode menu is used to select master, slave, or snooper operating mode. Only one of these modes may be used. The programming of each mode is de­tailed below.
Master mode is used to configure the scanner as a Modbus master. It will poll up to 16 registers in up to 16 Modbus slave devices. Slave mode is used to con­figure the scanner as a Modbus slave. A Modbus master must be used to send data to the Modbus reg­isters of the scanner for display. Snooper mode is used to listen for data polled by a Modbus master on the Modbus network. The scanner will detect up to 16 Modbus registers polled by the master.
Press the Enter button to access any menu or press the Up arrow button to scroll through choices.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
Press Menu, at any time, to return to the previous menu selection. Press and hold the Menu button for
1.5 seconds at any time to return to Run Mode.
Changes to the settings are saved to memory only after pressing Enter.
The display moves to the next menu every time a setting is accepted by pressing Enter.
• The Advanced menu contains parameters not required for all applications. The setup of features and functions detailed in the Advanced features menu are found in the Advanced Menu Programming (ADVANCE) section on page 37.
21
Page 22
PD6730X Field-Mount Modbus Scanners

Master Mode (MASTER)

In Master mode, the scanner will poll up to 16 Modbus registers in up to 16 Modbus devices. It will serve as a Modbus network master; polling Modbus slave de­vices for Modbus process variables (PVs) that can be displayed or used in the math functions.
Programming the Modbus Master mode will include defining the Modbus PV registers and devices, select­ing the polling time interval, and the maximum re­sponse time allowed.
Instruction Manual

PV Number Configuration (PV NUM)

The PV Number menu is used to enable and disable each Modbus PV 1 to PV 16. The Modbus device and registers are configured for each of the enabled PVs. PVs that are not enabled will not appear in other pro­gramming menus for display or inclusion in math channel functions (CV).
PV1 to PV16 are programmed using identical menus.
• To enable a PV it must be assigned to a specific slave ID.
Enable/Disable PV (ENABLE, DISABLE)
Enable or disable the Modbus PV. Disabled PVs will require no additional configuration. Disabled PVs will not be accessible in other menus or functions.
Slave ID (SLAVEID)
Enter the Modbus ID of the slave device that contains the PV information.
Function Code (FUNCODE)
Select the Modbus function code necessary to read the device. Use the Up and Down arrows to select the appropriate function code, and press Enter to ac- cept the function code.
See the PD6730X Modbus Register Table available at
www.predig.com
codes.
for more information on function
22
Page 23
PD6730X Field-Mount Modbus Scanners
Register Number (ReG NUM)
Enter the Modbus register number of the PV infor­mation on the Modbus slave device defined in the Slave ID parameter.
Select 5-Digit or 6-Digit Register Number
Data Type (DATATYP)
Enter the data type of the PV information in the Mod­bus register. Selectable data types are float, short in­teger, and long integer.
Use the Up and Down arrows to select the appropri­ate data type and press Enter to accept.
For short and long integer types, select binary or bi­nary coded decimal (BCD) formats as well as signed or unsigned data format.
Byte Format (BYTE)
Select the PV data byte format as it is stored in the Modbus slave device data register. Use the Up and Down arrows to select the appropriate data type re­lated to endianness and byte order.
Byte Selection Byte Type Description
1234
4321
2143 2143
3412 3412
1234 Big endian
4321 Little endian
Big endian with byte swap
Little endian with byte swap
Instruction Manual

Poll Time (T POLL)

Enter the time between read command sequences. In other words, how often the display values are updated in Master mode. The poll time defines how often the device will begin scanning all enabled Modbus PVs. For example, if the Poll Time is two seconds, the scanner will begin polling all Modbus PVs every two seconds.
This parameter defines the approximate time between updates of a PV value. Communications errors may make updating a PV take longer.
Note: Depending on the Response Timeout, and the number of PV poll requests that time out, it may take more than one poll time to poll all enabled Modbus PVs. In this scenario, the scanner will begin another round of polling at the next poll time interval.
For example: Due to transmission errors, the scanner with a 2 second poll time requires 2.5 seconds to up­date all the Modbus PVs. It will begin the second poll­ing of all the Modbus PVs at 4 seconds.
Note: In the feet and inches display models enter this value in the format XX.X seconds, but no decimal point is present in the display. For example: enter 20 for a poll time of 2.0 seconds.

Response Timeout (TIMEOUT)

Enter the time the scanner will wait after a request for information has been sent to a slave device before it will assume an error on that request. Increasing the timeout will help eliminate polling errors when polling slow devices. Increasing the response timeout will also slow the PV update rate in systems that are ex­periencing communications failures.
Note: The feet and inches display models enter this value in the format XX.X seconds, but no decimal point is present in the display. For example: enter 20 for a poll time of 2.0 seconds.

Retries Before Error (RETRIES)

Enter the number of consecutive failures to poll a de­vice that will result in a communications error mes­sage on the display. This is the number of times a specific PV must be polled before the display indi­cates a communication failure rather than displaying the available PV data. Increasing this number will al­low for more polling failures before a communication error is detected, which may be required for some un­reliable networks. Increasing this number will also in­crease how long old data is displayed before a com­munication error is indicated.
23
Page 24
PD6730X Field-Mount Modbus Scanners

Slave Mode (SLAVE)

In Slave mode, a Modbus master may write up to 16 Modbus PVs to the scanner, which can then display and process the data in the PV Modbus registers, such as displaying the data and using them in math functions.
Programming the scanner for Modbus Slave mode will include defining the Modbus PV registers that are enabled, as well as selecting the time between data writes before an error is assumed. In Slave mode the scanner accepts floating point data (Byte order: 1234 big endian).
Instruction Manual
Enable/Disable PV (ENABLE, DISABLE)
Enable or disable the Modbus PV. Disabled PVs will require no additional configuration. Disabled PVs will not be accessible in other menus or functions.
The Slave mode accepts floating point data type (Byte order: 1234 big endian).

Slave Response Timeout (TIMEOUT)

If the Modbus data registers for the enabled Modbus PVs are not updated within a certain period of time, the scanner can presume that there is an error with the data, or that it is too out of date to be worth dis­playing. In this case, the scanner will display this PV as NONE (NONE).
At the Response Timeout menu, enter the time limit for the scanner to continue to display data written to the Modbus PV register. To disable this feature, and always display the last data written to the Modbus register regardless of how long ago the data was updated, set this value to 0 seconds.

PV Number Configuration (PV NUM)

The PV Number menu is used to enable and disable each Modbus PV 1 to 16. PVs that are not enabled will not appear in other programming menus for display or inclusion in math channel functions (CV). PV1 to PV16 are programmed in identical menus.
24
Page 25
PD6730X Field-Mount Modbus Scanners

Snooper Mode (SNOOPER)

In Snooper mode, the scanner will act as a Modbus network packet sniffer. The Snooper mode is used to listen to data being transmitted on the bus. Up to 16 process variables may be read from the RS-485 bus and displayed or used in math functions. The same process variables can be displayed in multiple loca­tions.
Instruction Manual
Snooper Mode PV Configuration
(PV NUM)
The PV Number menu is used to enable and disable each Modbus PV 1 to PV 16. This menu is identical in Master mode. Refer to PV Number Configuration (PV NUM) on page 22.

Snooper Mode Response Time (T RESP)

If the Modbus data registers for the enabled Modbus PVs are not updated within a certain period of time, the scanner can presume that there is an error with the data. After this time has passed, and updated data has not been detected on the Modbus network, the scanner will display this PV as NONE (NONE).
At the Response Time menu, enter the time limit the scanner will display the Modbus PV register last data monitored before it assumes an error.
Notes:
The poll time for scanners set up for Snooper mode must be greater than the Master’s poll time. This setting corresponds to the time window during which the Snooper listens to the bus for a reply by the slave device being polled by the master device. As soon as the Snooper detects a new reply on the bus, the display is updated. If there is no reply within the Response Time setting, the Snooper goes into communications break condition.
To minimize the possibility of communication errors and communication break conditions, use a poll time of 5 seconds or more with slow baud rates (e.g. 4800 bps or less).
• If multiple registers are polled by the master with one command, only the first returned value will be read.
• To snoop multiple PVs, the master must request one PV at a time.
25
Page 26
PD6730X Field-Mount Modbus Scanners
Refer to manual with pulse input
Note 4
Note 4
Note 3
Note 1
Note 2

Setup the Display (SETUP)

Instruction Manual

Setting Up the Display (DISPLAY)

The Setup menu is used to select what information will be displayed on the top and bottom display.
The Display menu is used to select the top and bot­tom display to show Modbus PVs and math channels, and combinations of units and tags. The math chan­nels are configured in the Advanced Features menu.
• The Pulse Input menu is not described or used in this manual.
• For instructions on how to use and configure the pulse input, refer to the LIM6730XPulse manual.
Press the Enter button to access any menu or press the Up arrow button to scroll through choices.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
The Display menu is used to set parameters to show on the top and bottom displays; select which PVs will appear on the top and bottom displays; set how long to display the tags and units; and program the scan time for each channel (how long a specific channel will display before moving to the next value).
Note 1: The Top Display menu does not appear on
feet and inches display models.
Note 2: The math menu (MATH) is only visible if a
math channel has been enabled. See Math Channel (CV1 to CV4) Programming (MATH) on page 41 for details about enabling the math channels.
Note 3: The Tank Size menu appear only in Feet and
Inches Display Models.
Note 4: The Tag Time and Units Time menus will not
appear unless the Top Display or Bottom Dis­play parameters are set to display or alternate a tag or unit.
26
Page 27
PD6730X Field-Mount Modbus Scanners
Tag
Display tag
Tag and Units
Display alternating tag and units
Units
Display units
Display Modbus PVs
Display alternating
and units
Display is turned
operation
Units
Display units
Tag
Display tag
Tag and Units
Display alternating tag and units
Display is turned
operation
Tag
Display tag
Display Modbus PVs
Display alternating
PVs
Display alternating
and units
Display is turned
operation
TAG-PV
Units
Display units
Display Modbus PVs
Display alternating
PVs
Display alternating
and units
Display is turned
operation
Display Modbus PVs
Display alternating
PVs
Display alternating
and units
Display is turned
operation

Top Display (TOPDSP)

Note: The Top Display menu does not appear on feet and inches display models.
The Top Display menu sets what Modbus PV information will be displayed on the top display. A combination of Modbus PVs, tags, and units can be selected to appear individually or as an alternating display.
See PV Setup menu for details on selecting what Modbus PVs appear on the top and bottom display.
Press Enter to access the Top Display menu and Up button to scroll through choices. Press Enter to make a selection and proceed to the next menu.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
Top Display Selection
PV
PV-U PV and Units
TAG-U
TAG-PV Tag and PV
TG-PV-U
Parameter Description
PV Display Modbus PVs
Display alternating Modbus PVs and units
Tag and Units
Tag, PV, and Units
Display alternating tags and units for bot­tom Modbus PVs
Display alternating tag and Modbus PVs
Display alternating tag, Modbus PVs, and units
Top Display Selection
Feet & Inches Display Models
PV
PV-U
OFF Off
PV PV
Bottom Display Selection
TAG
TAG-U
UNITS
PV PV
TG-PV-U
OFF Off
UNITS TAG
TAG-U
OFF Off
TAG
PV PV
TAG-PV Tag and PV
TG-PV-U
UNITS
Parameter Description
Tag, PV, and Units
Tag, PV, and Units
Instruction Manual
tag, Modbus PVs,
off during normal
off during normal
tag and Modbus
tag, Modbus PVs,
off during normal
Note: Some top display selections may not appear if no PV is assigned to display on the top display.

Bottom Display (BOTDSP)

The Bottom Display menu sets what Modbus PV information will be displayed on the bottom display. The available programming options for the bottom display are determined by the Top Display menu setting. For Ft & In level display models, the selections for the Top Display menu are fixed. A combination of Modbus PVs, tags, and units can be selected to appear individually or as an alternating display.
A selection without a PV component will use the bottom display to show the unit or tag of the PV displayed on the top display. These will change as the top display PVs are scanned.
See PV Setup menu for details on selecting what Modbus PVs appear on the top and bottom display.
Press Enter to access the Bottom Display menu and Up button to scroll through choices. Press Enter to make a selection and proceed to the next menu.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
TAG-PV Tag and PV
TG-PV-U
OFF Off
TG-PV-U PV PV
TAG-PV Tag and PV
TG-PV-U
OFF Off
Tag, PV, and Units
Tag, PV, and Units
tag and Modbus
tag, Modbus PVs,
off during normal
tag and Modbus
tag, Modbus PVs,
off during normal
Note: Some top display selections may not appear if no PV is assigned to display on the top display.
27
Page 28
PD6730X Field-Mount Modbus Scanners
No
te 2
Note 1

PV Display Setup (PVSETUP)

The PV Display Setup menu is used to configure the display options for each Modbus PV setup in the PV Number Configuration (PV NUM) menu on page 22. For each Modbus PV, this includes selecting the top or bottom display, entering tag and unit, setting the Float data type decimal location (for Float data types only), setting the display decimal point location, and scaling the Modbus PV to display in engineering units.
Note 1: Not applicable to feet and inches display models.
Note 2: The Float Decimal Point menu only appears if the PV data type has been set to Float (Not applicable to Ft & In model).
Modbus PV Display Format (FORMAT)
The PV Display Setup menu is used to configure the display options for each Modbus PV.
Decimal Display Models
The PV may appear on the top display (TOPDSP) or bottom display (BOTDSP). The PV may also be turned off (OFF) and it will not display; though it may be used in math functions, and the data will be polled if in Modbus Master mode.
Feet and Inches Display Models
The PV may appear on the top feet and inches display with 1/16 of an inch (FtIn16), 1/8 of an inch (FtIn8), or appear on the 7-digit bottom display (DEC) with no decimal points. The PV may also be turned off (OFF) and it will not display; though it may be used in math functions, and the data will be polled if in Modbus Master mode.
Press Enter to access the Format menu and Up button to scroll through choices. Press Enter to make a selection and proceed to the next menu.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
Instruction Manual
Enter Modbus PV Tag (TAG)
Each Modbus PV may have a unique programmable tag to identify the PV while the display is scanning. To program the Modbus PV tag, select the Tag menu and press Enter.
Program the custom tag as described in Setting Al- phanumeric Labels (LABEL) on page 18. When the la­bel has been programmed, press Enter to confirm the label and leave the Tag parameter.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
Enter Modbus PV Units (UNITS)
Each Modbus PV may have a unique engineering unit identifier to display while scanning. To program the Mod­bus PV unit, select the Units menu and press Enter.
Program the custom unit as described in Setting Al- phanumeric Labels (LABEL) on page 18. When the la­bel has been programmed, press Enter to confirm the label and leave the Units parameter.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
Set Float Data Type Decimal Point (FLOAT.DP)
This menu is only used if the PV selected was set to a data type of Float in PV Number Configuration (PV NUM) on page 22. To program the Modbus PV float decimal point location, select the Float Decimal Point menu and press Enter.
Set the decimal point location to correspond to the decimal point location of the float data. Pressing the Right arrow moves the decimal point one place to the right (including no decimal point). Pressing the Up ar­row moves the decimal point one place to the left. Press Enter to confirm the number of decimal; points and continue programming.
Set Display Decimal Point (DISP.DP)
Select the display decimal point location for the scaled Modbus PV value.
Decimal Display Models
Select the display decimal point location for the scaled Modbus PV value.
To program the Modbus PV display decimal point location, select the Display Decimal Point menu and press Enter.
Pressing the Right arrow moves the decimal point one place to the right (including no decimal point). Pressing the Up arrow moves the decimal point one place to the left. Press Enter to confirm the number of decimal; points and continue programming.
Feet and Inches Display Models
On feet and inches display models, this value is fixed, the top display PVs shows feet and inches and the bottom display PVs shows no decimal location.
28
Page 29
PD6730X Field-Mount Modbus Scanners
Temporary Display Will display current value on bottom display
Temporary Display Will display current value on bottom display
Temporary Display Will display current value on bottom display
Temporary Display Will display current value on bottom display
Temporary Display Will display current value on bottom display
Temporary Display Will display current value on bottom display
Instruction Manual
Scale Modbus PV to Engineering Units (SCALE)
The Modbus PVs may be scaled to reflect different engineering units than the data read out of the Modbus slave device register. To do this, use the Scale menu to select the type of scale desired.
Note 1: The bottom display of the feet and inches display models does not show decimal points. While the decimal point may not appear, it is included on the factor programming steps.
For example: To enter a conversion factor of 2.54, select a factor decimal point with 2 decimal locations, and enter a factor value of 254.
Note 2: MP-SCAL is only available when scaling PV1.
29
Page 30
PD6730X Field-Mount Modbus Scanners
Factor (FACTOR)
Factor scaling uses a conversion factor for scaling a number of PV register counts to a single display count. In other words, the factor acts as a multiplier to change Modbus PV register data units into display engineering units.
Factor Decimal Point (FACTR.DP)
Enter the number of decimal point locations necessary to enter the conversion factor.
Conversion Factor Value (VALUE)
Enter the conversion factor; the multiplier value that is applied to the Modbus PV register data to convert it to the desired display engineering units.
For example: if the PV register data is a height in centimeters, but a height in inches is desired on the display, a factor of 0.393701 would be entered.
(Display Value) = (Modbus Register Value) * (Factor)
Example: (386.08 cm) * (0.393701) = (152.00 in) = (12 ft 8 in)
Note: The bottom display of the feet and inches display models does not show decimal points. While the decimal point may not appear, it is included on the factor programming steps.
For example: if the PV register data is 0 to 100 in a flowmeter, but a flow rate desired on the display is 0 to 250 GPM, a factor of 2.5 would be entered. On feet and inches display models, there is no lower display decimal point. Therefore, a factor decimal point of 1 place is selected, and a conversion factor value of 25 is entered.
Instruction Manual
Linear (LINEAR)
Linear scaling is used to convert a linear scale of PV to display value.
Input Values 1 and 2 (INP)
Enter the Modbus PV register data for scaling points 1 and 2.
Display Values 1 and 2 (DSP)
Enter the corresponding display values for input points 1 and 2.
For example: If a PV register contains data in terms of tank height in feet for a 100 feet tank, the display value can be linearly scaled for an input of 0 feet (Input 1) displaying 0 percent (Display 1), and an input of 100 feet (Input 2) displaying as 100 percent (Display 2).
Not available on Modbus PVs assigned to the feet and inches display of feet and inches display models.
Multipoint Scaling (MP-SCAL)
This type of scaling is only available for PV1. Multipoint Scaling is used when multiple linear scaling points are required, such as round horizontal tanks or conical storage silos. Up to 32 linearization points may be entered, with linear scaling between each point.
Not available on Modbus PV1 if assigned to the feet and inches display of feet and inches display model.
Number of Points (NO PTS)
Enter number of linearization points. The default value is 2 points. For linear inputs requiring only 2 scale points, use Linear scaling.
30
Page 31
PD6730X Field-Mount Modbus Scanners
Note 2
Note 1
Ft & In Display
Decimal Display
Instruction Manual

Math Channel Display Setup (MATH)

The Math Channel Display Setup menu is used to configure the display options for each of the four math channels, CV1 to CV4. The Menu will only display the math channels that have been enabled. See Math Channel (CV1 to CV4)
Programming (MATH) on page 41 for details on programming the math functions.
FORMAT
Note 1:
FORMAT
If
Note 2: Display Decimal Point menu is not applicable to feet and inches display format.
must be set to either
is set to
OFF
, these menus are not visible.
TOPDSP
or
BOTDSP
for the
TAG, UNITS
, and
DISP.DP
menus to be visible.
31
Page 32
PD6730X Field-Mount Modbus Scanners
Math Display Format (FORMAT)
The Math Display Format menu is used to configure the display format for each math channel. The Math Display Format must be set to display on either the top or bottom display for the TAG, UNITS and DISP.DP menus to appear.
Decimal Display Models
The math channel value may appear on the top display (TOPDSP) or bottom display (BOTDSP). The math channel value may also be turned off (OFF), and will not display, though it may be used in other math functions.
Feet and Inches Display Models
The math channel may appear on the top feet and inches display with 1/16 of an inch (FtIn16), 1/8 of an inch (FtIn8), or appear on the 7-digit bottom display (DEC) with no decimal points. The math channel may also be turned off (OFF), and will not display, though it may be used in other math functions.
Press Enter to access the Format menu and Up but- ton to scroll through choices.
Press Enter to make a selection and proceed to the next menu.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
Instruction Manual
Set Display Decimal Point (DISP.DP)
Select the display decimal point location for the math channel value. To program the math channel display decimal point location, select the Display Decimal
Point menu and press Enter.
Decimal Display Models
Set the display decimal point location for the math channel. Pressing the Right arrow moves the decimal point one place to the right (including no decimal point). Pressing the Up arrow moves the decimal point one place to the left. Press Enter to confirm the number of decimal points and continue programming.
Feet and Inches Display Models
Feet and inches display models do not have this menu. On feet and inches display models, this value is fixed, the top display PVs showing feet and inches and the bottom display PVs showing no decimal location.
Enter Math Channel Tag (TAG)
Each math channel may have a unique programma­ble tag to identify the math channel while the display is scanning. To program the tag, select the Tag menu and press Enter.
Program the custom tag as described in Setting Al- phanumeric Labels (LABEL) on page 18. When the la­bel has been programmed, press Enter to confirm the label and leave the Tag parameter. Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
Enter Math Channel Units (UNITS)
Each math channel may have a unique engineering unit identifier to display while scanning. To program the units, select the Units menu and press Enter.
Program the custom unit as described in Setting Al­phanumeric Labels (LABEL) on page 18. When the la­bel has been programmed, press Enter to confirm the label and leave the Units parameter.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
32
Page 33
PD6730X Field-Mount Modbus Scanners

Tank Size Indicator (TANKSZ)

The Tank Size menu defines the 100% full level for the 20-segment tank level indicator on feet and inches display models. This menu is not present in decimal display models. All PV values displayed on the top line feet and inches display will use this tank level in­dicator.
To set the maximum height of the tank level indicator, enter the level for thank to display as full. Enter the full value in feet.
See Setting Numeric Values on page 18 for more in- formation on entering the tank full level in feet.
Press Enter to confirm and save the tank level indica­tor full value.

Tag Display Time (T-TAG)

If either display is set to toggle a custom tag as part of the Top Display or Bottom Display programming the scanner will prompt for a toggle time with this menu.
The custom tag for each variable will display before each variable for a number of seconds set by this parameter. The tag may be programmed to display for 1 to 49 seconds.
Press Enter to access the Tag Display Time menu. Use the Up and Right buttons to enter the tag display time. Press Enter to make a selection and proceed to the next menu. See Setting Numeric Values on page 18 for more information.
Press the Menu button to exit without saving changes.
Instruction Manual

Units Display Time (T-UNITS)

If either display is set to toggle units as part of the Top Display or Bottom Display programming the scanner
will prompt for a toggle time with this menu.
The unit for each variable will display before each vari­able for a number of seconds set by this parameter. The unit may be programmed to display for 1 to 49 sec­onds.
Press Enter to access the Units Display Time menu. Use the Up and Right buttons to enter the units dis­play time. Press Enter to make a selection and pro­ceed to the next menu. See Setting Numeric Values on page 18 for more information.
Press the Menu button to exit without saving changes.

Scan Time (T-SCAN)

The scan time defines how long a variable will be shown on the display while automatically scanning. After the scan time has elapsed, the next tag, unit, and variable will be displayed.
The scan time may be programmed to cycle the display to the next variable every 2 to 99 seconds.
Press Enter to access the Scan Time menu. Use the
Up and Right buttons to enter the scan time. Press Enter to make a selection and proceed to the next
menu. See Setting Numeric Values on page 18 for more information.
33
Page 34
PD6730X Field-Mount Modbus Scanners
Serial Communications Settings
COMM)
(
The Serial Communications menu is used to setup se- rial communications parameters necessary for commu­nication via the RS-485 connection and Modbus.
Instruction Manual

Scanner Modbus ID (SCAN ID)

The Scanner Modbus ID menu sets the Modbus ad­dress (ID) of the scanner. The scanner Modbus ID may be programmed between 1 and 247. When using more than one device in a multi-drop mode, each de­vice must be provided with its own unique address.
To program the Modbus ID, refer to Setting Numeric Values on page 18.

Baud Rate (BAUD)

The baud rate may be set to 1,200; 2,400; 4,800; 9,600; 19,200; 38,400; 57,600; or 115,200 bps.
In the Baud Rate menu, use the Up button to scroll through the menu choices.
Press Enter to make a selection and proceed to the next menu.

Transmit Delay Time (TXDELAY)

The transmit delay may be set between 0 and 199 ms.
To program the transmit delay time, refer to Setting Numeric Values on page 18.
Press Enter to access the Serial Communications Settings menu then press the Up to scroll through the menu choices.
Press Enter to select a menu. Press Menu to back out of a menu or hold Menu to exit at any time.
Modbus communications is performed with the 3-wire (including Ground) RS-485 connector.
Refer to the PD6730X Scanner Modbus Register Ta­bles located at www.predig.com information.
for additional Modbus

Parity (PARTIY)

The parity can be set to even (EVEN), odd (ODD), or none with 1 (NONE1) or 2 (NONE2) stop bits.
In the Baud Rate menu, use the Up button to scroll through the menu choices.
Press Enter to make a selection and proceed to the next menu.
34
Page 35
PD6730X Field-Mount Modbus Scanners
Display
Parameter
Action/Setting
ADVANCE
pulse output mode

Advanced Menu

Display Functions & Messages

The scanner displays various functions and messages during setup of advanced features. The following table shows the Advanced Features menu functions and messages in the order they appear in the menu.
OUTPUT
OUT 1
OFF
PULSE
RATE
TOTAL
GrTOTAL
RETRAN
QUAD
TEST
PV
SORUCE
ALARM
PV NUM
PV 1
SET
RESET
ON
OFF
TIMER
Start
PERIOD
TIME
OUT 2
A OUT
Advanced Enter Advanced menu
Output Setup open collector
Output 1 Assign function of open
Off Disable output
Pulse Set Out 1 or Out 2 for
Rate Refer to pulse input
Total
Grand Total
Retransmit
Quadrature Assign pulse output to
Test Assign pulse output to test
Process Variable
Source Set pulse output reference
Alarm
Process Variable Number
Process Variable 1
Set Point Set alarm set point
Reset Point Set alarm reset point
On Set output to on state
Off Set output to off state
Timer
Start Activate timed pulse
Delay Set the time of one period
On Set the active low pulse
Output 2 Assign function of open
Analog Output Enter Analog Output menu
outputs Out 1 and Out 2
collector output 1
manual for any reference to Rate, Total, or Grand Total.
quadrature
mode
Assign pulse output to a PV or CV
variable
Assign Out 1 or Out 2 for alarm output mode
Assign alarm output to a PV or CV
Select Process Variable to assign alarm to (1-16)
Set Out 1 or Out 2 for timed pulse output mode
output
(seconds)
width time
collector output 2
Instruction Manual
Display Parameter Action/Setting
SOURCE
PV1
DSPLY 1
OUt 1
DSPLY 2
OUt 2
SAVE?
CV1
DISABLE
MATH
CV 1
MULTI
PAR1
PAR2
PAR3
L2P1
L2P2
L2P3
DIVIDE
DIFABS
WAVG
DRAW
RATIO
CONCEN
CONST
NONE
ABS
SQRT
SUM
DIF
Source
Process Variable 1
Display 1 Output display 1 value
Output 1 Output 1 value
Display 2 Output display 2 value
Output 2 Output 2 value
Save
Math Channel 1
Disable Turn off the analog output
Math Enter Math menu
Math Channel 1
Multiply Set math to multiply
Parameter 1 Enter math function
Parameter 2
Parameter 3
Level 2 Parameter 1
Level 2 Parameter 2
Level 2 Parameter 3
Divide Set math function to divide
Absolute Difference
Weighted Average
Draw Set math function to draw
Ratio Set math function to ratio
Concentration Set math function to
Constant Set math function to a
None Set math function to none
Absolute Value Set math function to
Square Root Set math function to
Sum Set math function to sum
Difference
Set analog output reference variable
Set PV as analog output source, can select any active PV (1-16)
Save entered analog parameters
Set CV as analog output source, can select any active CV (1-4)
Program math channel (Channel 1-4)
parameter 1
Enter math function parameter 2
Enter math function parameter 3
Enter nested math function level 2 parameter 1
Enter nested math function level 2 parameter 2
Enter nested math function level 2 parameter 3
Set math function to absolute difference
Set math function to weighted average
concentration
constant value
absolute value
square root
Set math function to difference
35
Page 36
PD6730X Field-Mount Modbus Scanners
October
Set month as October
Backup
Enter Backup menu
Display Parameter Action/Setting
GATE
FILTER
CUTOFF
SCALCAL
T RESET
PASSWRD
UNLOCKD
LOCKED
Pass
UnLOC
LOCD
Pass T
Pass GT
CUSTOM
POS 1
SYSTEM
SETTIME
YEAR
MONTH
01
02
03
04
05
06
07
08
09
10
11
12
DAY
TIME
DATALOG
LOGTIME
LOG 1
Gate
Filter
Low-Flow Cutoff
Scale & Calibrate
Total Reset
Password Enter the Password menu
Unlocked Program password to lock
Locked
Password
Unlock
Lock Password has been locked
Password Total
Password Grand Total
Custom Enter Custom menu
Position 1 Set menu position 1 (1-8)
System Enter System menu
Set Time Set real-time clock date
Year Set the year
Month Set the month
January Set month as January
February Set month as February
March Set month as March
April Set month as April
May Set month as May
June Set month as June
July Set month as July
August Set month as August
September Set month as September
November Set month as November
December Set month as December
Day Set the day
Time Set the hour and minute
Data Log Enter Data Log menu
Log Time Set daily data log times
Log 1 Set first daily log time
Refer to pulse input manual
scanner
Enter password to unlock scanner
Program password to lock scanner parameters
Password has been unlocked
Refer to pulse input manual
and time
(1-4)
Instruction Manual
Display Parameter Action/Setting
DISABLE
ENABLE
INTERVL
FULSTOP
CONT
START
LOGVIEW
LOGVIEW ALL
ERASE
ERASE ALL?
BAKLITE
ENABLE
DISABLE
AO CAL
Disable Disable log number
Enable Enable log number
Interval Set interval log time
Stop When Full
Continue Data logging will continue
Start Begin interval logging
Log View View data log
All Log View View all data log points
All Erase Erase all logs
Erase? Confirm to erase all logs
Backlight Enable or disable backlight
Disable Disable backlight
Enable Enable backlight
Analog Output Calibration
Data logging will stop when the log is full
when the log is full, deleting old data
Enter Analog Output Calibration menu
BACKUP
SAVE?
LOAD?
DEFAULT
DFALTS?
INFO
SOFT
VER
MODEL
Save? Save current parameters
Load? Load parameters from
Default Restore factory default
Reset Defaults Confirm factory reset
Info Enter Info menu
Software
Version
Model Display model number
to backup restore
backup restore
parameter settings
Display software ID number
Display software version number
36
Page 37
PD6730X Field-Mount Modbus Scanners
Note 1
Note 2
Note 2
Note 2
Note 2
Note 2
Advanced Menu Programming
ADVANCE)
(
To simplify the setup process, functions not needed for most applications are located in the Advanced menu. Access the Advanced menu features by pressing Enter at the Advance menu in the Main Menu defined on page 19.
Press the Enter button to access any menu or press the Up arrow button to scroll through choices.
Press the Menu button to back out of a menu or hold the Menu button to exit at any time.
The Advanced menu is used to select:
• Open Collector Output Configuration
(OUTPUT)
• Analog Output Configuration (A OUT)
• Math channel functions (MATH)
• Set Passwords (PASSWRD)
• Reconfigure the Main Menu Structure
(CUSTOM)
• Enter the System Menu for Scanner
Operation and Data Logging (SYSTEM)
Instruction Manual
A OUT
Note 1: Analog Output ( for scanners with the analog output option.
Note 2: Refer to pulse input manual
37
) menu displayed only
Page 38
PD6730X Field-Mount Modbus Scanners
Note 1
Note 2
Note 2
Note 2
Note 2

Open Collector Outputs (OUTPUT)

The scanner is equipped with two NPN open collector outputs that may be set up for pulse outputs, alarms, timed pulses, or turned off.
Pulse outputs can be based on a Modbus PV value, or math channel value. Both outputs may be used to generate a quadrature output based on any pulse menu output type. An output test mode is also se­lectable to generate pulses at a constant programma­ble frequency.
Alarms are available based on a Modbus PV or math channel. The alarm status will show on the display even if the output is not wired. The outputs may also be forced on or off.
A timed pulse output generates constant pulses at a specified frequency and on time.
The output may be disabled by selecting Off.
Instruction Manual
Output 1 and 2 Setup (OUT 1, OUT 2)
The function of open collector output 1 and 2 is con­figured using the Off (OFF), Pulse (PULSE), Alarm (ALARM), and Timer (TIMER) menus detailed below.
In the Output 1 and 2 menus, use the Up button to scroll through the menu choices.
Press Enter to make a selection and proceed to the next menu.
See Setting Numeric Values on page 18 for more in- formation on programming numeric count, set, and re­set value.
Pulse Output (PUlse)
Pulse outputs may be assigned to Modbus PV (PV), math channel (CV), quadrature (QUAD), or test (TEST).
Note 1:
SOURCE
menu only applicable to PV option.
Note 2: Refer to pulse input manual
38
Page 39
PD6730X Field-Mount Modbus Scanners
Note 1
Note 1
Note 1
Quadrature Pulse Output (QUAD)
The pulse output set to quadrature will duplicate the other open collector output, but lag by ¼ duty cycle (90 degrees out of phase). For example, Out 1 will follow Out 2, if Out 1 is set to QUAD. Only one output should be set to QUAD. If both outputs are set to QUAD, both outputs will be disabled. The other output should be programmed as desired for the quadrature output function, and must be a pulse (PUlse) output selection.
Test Pulse Output (test)
The test output setting programs the output to generate pulses at a programmed constant frequency. Set the frequency decimal point location in the DECPT menu, and then enter the desired output frequency in Hz in the PULSE menu.
Modbus PV or Math Pulse Output (PV)
The pulse output may be based on an enabled Modbus PV or math channels CV1 to CV4. The pulse output frequency in hertz (Hz) is calculated as the value of the selected PV or CV divided by the programmable count (or divisor).
(
  ()=
   

The frequency of the pulse output will update as the PV or CV value is changed. For example, if the output is set to reference PV 2, and PV 2 is reading 1540.5, with a count or 10, the pulse output frequency will be 154.05 Hz.
Alarm Output (ALARM)
Alarm outputs may be assigned to Modbus PV or math channel (PV NUM), always on (ON) or always off (OFF).
)
Instruction Manual
Note 1: Refer to pulse input manual
Modbus PV or Math Alarm (PV NUM)
Program a PV (PV1-16) or math channel (CV1-4) to trigger an alarm. Select the source PV or CV for the alarm and enter the display value set and reset points. The alarm deadband is determined by the difference between set and reset points. Minimum deadband is one display count. If set and reset points are programmed the same, output will reset one count below set point.
39
Page 40
PD6730X Field-Mount Modbus Scanners
Note 1
Note 1
Note 1
Force On State (ON)
This alarm mode forces the output to be active, or on. This mode is primarily used to test alarm systems.
Force Off State (OFF)
This alarm mode forces the output to be inactive, or off. This mode is primarily used to test alarm systems.
Timer Output (TIMER)
The timer output produces a constant pulse width at a constant frequency. Program the Period (PERIOD) from 0.1 to 999999.9 seconds (time from the start of one pulse to the start of the next pulse).
Program the On Time (TIME) for the active low pulse from .01 to 99999.99 seconds (pulse width). The on time must be less than the delay time (Period).
Select Start (START) to begin outputting the constant timed pulse.
Select Stop (STOP) to end outputting the constant timed pulse.
Instruction Manual

Scaling the 4-20 mA Analog Output (Aout)

The Analog Output menu is used to program the 4-20 mA output based on display values. This menu is not present on models without a 4-20 mA output option.
The 4-20 mA analog output (if equipped) can be scaled to provide a 4-20 mA signal for any display range selected for either Modbus PV 1 to 16 or math channel CV 1 to 4.The output may be disabled (DISA- BLE), and it will only output the minimum signal.
No equipment is needed to scale the analog output; simply program two display values and corresponding mA output signals.

Selecting the Analog Output Source

In the Analog Output (A OUT) menu, press the Enter button. In the Source (SOURCE) menu, press the Up button to scroll through the menu choices.
Press Enter to make a selection and proceed to the next menu.
Note 1: Refer to pulse input manual
40
Page 41
PD6730X Field-Mount Modbus Scanners

Enter Display and Output Values

To scale the analog output, enter display value 1 and a corresponding analog output value for this display, and enter display value 2 and a corresponding analog output value for this display value. This will provide a linearly scaled analog output.
On decimal display models, enter the output value in mA. On feet and inches display models, enter the out­put value in µA.
The following diagram details setting the analog out­put when the source is configured to display on the top display of a decimal display model.
The following diagram details setting the analog out­put when the source is configured to display on the top display of a feet and inches display model.
The following diagram details setting the analog out­put when the source is configured to display on the bottom display.
Instruction Manual

Math Channel (CV1 to CV4) Programming (MATH)

The scanner includes four math channels, CV1 to CV4. Each math channel is constructed by selecting a math function and the desired parameters.
Note 1: The current math function selection will dis­play as this menu item.
Note 2: Parameter 1, 2, and 3 will appear in the menu structure based on their use in the selected math function. See the table below for information on what parameters are necessary for each math function. If Constant is selected as the math function, the value will be immediately entered.
See Setting Numeric Values on page 18 for more in- formation on programming the display and output val­ues.
Note 1: On decimal display models, enter the output value in mA. On feet and inches display models, enter the output value in µA.
Note 2:The hundreds digit on the feet display does
0
not display 0 as a seven-segment represented with three horizontal bars as shown.
• Please note that when power is removed from the scanner, the analog output will drop below 1 mA.
• Consider this effect when designing any system using the 4-20 mA output.
; instead 0 is
41
Page 42
PD6730X Field-Mount Modbus Scanners
Selection
Square Root
√(PAR1)
PAR
also selectable
The available math functions are detailed below.
Math
SUM
DIF
MULTI
DIVIDE Division PAR1 / PAR2
DIFABS
WAVG
DRAW
RATIO
CONCEN
CONST
NONE None Disable
ABS
SQRT
Function Equation
Addition PAR1 + PAR2
Difference PAR1 - PAR2
Multiplication PAR1 * PAR2
Absolute diff. Abs(PAR1 - PAR2)
Weighted avg.
Draw
Ratio (PAR1 / PAR2) * PAR3
Concentration
Constant
Absolute Value
((PAR1 – PAR2)*PAR3) +PAR2
((PAR1 / PAR2) –
1) * PAR3
PAR1 / (PAR1 + PAR2) * PAR3
Constant value of
0.0001 to 99999
Abs(PAR1)
Instruction Manual
The available parameters for PAR1, PAR2, and PAR3 shown above are detailed below.
Parameter Description
Selection
The scaled PV1 value;
PV 1
CV 1
ABS
SQRT
SUM
DIF
MULTI
DIVIDE
DIFABS
WAVG
DRAW
RATIO
CONCEN
CONST Constant
NONE None No parameter.
*Selecting this math function as a parameter will enter into the setup for a Nested Math Function. These pa­rameters are not available for level 2 parameters used when setting up the nested math function.
Modbus PV1
Math Channel CV1
Nested Absolute Value*
Nested Square Root*
Nested Addition*
Nested Difference*
Nested Multiplication*
Nested Division*
Nested Absolute diff.*
Nested Weighted avg.*
Nested Draw*
Nested Ratio* (L2P1 / L2P2) * L2P3
Nested Concentration*
PV2 to PV16 also selectable
The math channel CV1 value; CV2 to CV4
Abs(L2 PAR1)
√(L2 PAR1)
L2P1 + L2P2
L2P1 - L2P2
L2P1 * L2P2
L2P1 / L2P2
Abs(L2P1 - L2 PAR2)
((L2P1 – L2P2)* L2P3) + L2P2
((L2P1 / L2P2) – 1) * L2P3
L2P1 / (L2P1 + L2P2) * L2P3
Constant value of
0.0001 to 99999
Nested Math Functions
To create more complicated math functions, the first level parameters allow a math function to be selected as the parameter. In this case, a second level of parameters is selected for the nested math function. These level 2 parameters are level 2 parameter 1, L2P1 (L2P1), level 2 parameter 2, L2P2 (L2P2), level 2 parameter 3, and L2P3 (L2P3). Level 2 parameters are selected similarly to other math parameters; however additional nested math functions are unavailable for selection.
42
Page 43
PD6730X Field-Mount Modbus Scanners
Model
Password
Entering a Constant Value
To enter a constant value, press Enter to select Constant (CONST). Value (VALUE) will display. Press Enter to confirm and enter a constant value. V.DP will display. Use the Up and Right arrows to select the number of decimal points used in the constant value. Press Enter to select the number of decimal points selected. Value will display. Set the constant value. See Setting Numeric Values on page 18 for more information.
No Parameter (NONE)
Selecting a parameter of None will disable the math function. Any math function with a parameter of None will display None (NONE) on the display as the value of the math function.

Setting Up Passwords (PASSWRD)

The Password menu is used to program a five-digit password to prevent unauthorized changes to the pro­grammed parameter settings.
The lock symbol is displayed on decimal display mod­els to indicate that settings are password protected.
Record all passwords for future reference. If appropri­ate, it may be recorded in the space provided.
For instructions programming numeric values see Set- ting Numeric Values on page 18 for more information.
Instruction Manual
• Did you forget the passwords? The password may be disabled by entering a master password. If you are authorized to make changes, enter the master settings lockout (PASS) password 50865, to unlock the scanner.
Serial Number:
Setting Lockout Password (PASS):
____ ____ ____ ____ ____
Locking Scanner Setup Parameters (PASS)
Enter the Password menu by pressing Enter. Select Password (Pass) by pressing Enter. Program a five-
digit password. The scanner will return to Run Mode after locking any of the passwords.
Making Changes to a Password Protected Scanner
If the scanner is password protected, the scanner will display the message LOCKED when the Menu button is pressed. Press the Enter button while the message is being displayed and input the correct password followed by the Enter button to gain access to the menu. After exiting the programming mode, the scanner returns to its password protected condition.
Disabling Password Protection
To disable the password protection, access the Password menu, select the type of password to be disabled, and enter the programmed password. That password is now disabled until a new password is entered.
43
Page 44
PD6730X Field-Mount Modbus Scanners
Set no menu position display
Set to show Units menu
Set to show Decimal menu
Set to show Display menu
Set to show Output menu
Program password
parameters
Set to show Output menu
Assign function of pulse output 1
Assign function of pulse output 2
Data Log
Enter Data Log menu
Set daily data log times
Interval
Set interval log times
Log View
Enter Log View menu
Set to show Password menu
menu
Set to show Advanced menu
Set to show System menu
Set to show Mode menu

Custom (CUSTOM)

The Custom menu is used to modify the initial programming menus that appear in the Main Menu when the Menu button is pressed in Run Mode.
Display
NONE None
Parameter/Menu Action
Instruction Manual
Custom Menu Parameters
• Changing the default menu setup with the
Custom menu feature may change the setup and operation procedures described in this manual. Only operators familiar with the programming and operation of this unit should use this feature.
Eight menu positions are available. Menu positions 6 and 7 are factory programmed for Setup and Advanced.
After pressing Enter at the Custom menu, the display will flash Position (POS 1) and then display the parameter to appear in position 1 of the main menu.
To add a menu or parameter to the menu structure, or change the default menus, press Enter at the desired position (POS) to be edited, and use the Up or Right arrows to select the desired menu item for that position. Press Enter to save the setting. See the Custom Menu Parameters chart for a complete list of available menu selections for each position.
UNITS Units
DECIMAL
DISPLAY
A OUT Analog out
PASS
OUTPUT Output
OUT 1
OUT 2
DATALOG
LOGTIME Log Time
INTERVL LOGVIEW
PASSWRD
SETUP
Decimal
Display
Password
Out 1
Out 2
Password
Setup
Analog
to lock scanner
Set to show Setup
ADVANCE Advance
SYSTEM
MODE
System
Mode
44
Page 45
PD6730X Field-Mount Modbus Scanners

System (SYSTEM)

The system function is used to set the real time clock, set daily data log times, enable/disable the backlight, access analog output controls used in troubleshooting, store, restore, and backup restore feature, enable/disable the battery power alert sym­bol on the display, and review basic system identifi­cation information.
Instruction Manual
Set Real Time Clock (SETTIME)
The real time clock is used to trigger data log events, and is recorded at every logged data point. The Set Time menu displays the date and time.
Figure 10. Real Time Clock Display Example –
Decimal Model
Figure 11. Real Time Clock Display Example –
Feet & Inches Model
The above display examples show the date to be June 27, 2013; at 14 hours, 32 minutes, and 36 seconds.
The year, month, day, hour, and minute may all be set by the user. The real time clock will need to be reset if external power and battery power are lost.
To program the time, select the time or date component to be programmed, and press Enter. To enter the time or date as a numeric value, see Setting Numeric Values on page 18 for more information.
Changing the time (hours and minutes) will reset the second clock to 0.
45
Page 46
PD6730X Field-Mount Modbus Scanners
Data Log Setup (DATALOG)
The Data Log menu is used to setup and enable the data log functions. The scanner may contain up to 511 records, each containing the date, time, and log number. Each record may hold the first eight enabled Modbus PVs and all enabled math channel CVs.
The data log can hold 511 records of the first eight enabled Modbus PVs and math channel CVs.
The frequency of these records depends on the data log settings.
For example: If PV 1, 2, 3, and 4 are enabled, and CV 1 and 2 are enabled, the data log may record 511 logs containing PV 1, 2, 3, and 4, as well as CV 1 and CV 2. The data log will record these values even if CV2 is the only value set to display.
Instruction Manual
Log Time and Log Interval
There are two ways to configure the time when a data log record is recorded. The Log Time feature allows up to 4 data log events time to be entered for each day. The Log Interval feature allows a data log record­ing event at the selected time interval. At each data log event, all appropriate data records will be rec­orded.
Only the Log Time or Log Interval may be active at a time. While one type of data logging is enabled, the other menu is inaccessible.
46
Page 47
PD6730X Field-Mount Modbus Scanners
Log Time Setup (LOGTIME)
The Log Time menu contains four log events (LOG 1 to LOG 4). Each log time is configured independently. For each daily log time desired, enable a log, and set the log time for the hours and minutes the log is to be recorded. The time is set in real-time hours and minutes, based on the real time clock setup.
The Log Time feature will roll-over, deleting the oldest data logs (in blocks of 8) when the log is full and new logs must be recorded. This makes it the most useful for long-term data logging.
Interval Setup (INTERVL)
The Interval menu sets the time interval for data log­ging. Every time interval, one data log event will be recorded. To enable interval data logging, enable the feature, and set the interval time for the hours and minutes between each log.
If set to FULSTOP, the Log Interval feature will not de- lete old data, and data logging will stop when the log is full. This makes it the most useful for short periods and logging specific functions.
If set to CONT, the Log Interval feature will delete the old data when full and continue logging data. The Log Interval feature will roll-over, deleting the oldest data logs (in blocks of 8) when the log is full and new logs must be recorded. This makes it the most useful for long-term data logging.
View Data Log (LOGVIEW)
The Log View menu allows on-screen browsing of the data log event records stored in the scanner. Data points may be navigated by viewing the log number, date and time, first eight enabled PVs and four CVs. A known log may be jumped to immediately, avoiding a lengthy search for data. All logs may be deleted with the ERASE command, requiring confirmation.
Instruction Manual
Once the log records are displayed, use the Enter key to display variable within the same log and move to the next log. Use the Up and Right arrows to move to the next or previous log number.
Note 1: All enabled PVs and CVs will display in order, the Tag for each PV and CV will flash before display­ing the value.
Note 2: All tags, values, and units will appear on the lower display with exception of feet and inches for­matted values on the feet and inches display models. These parameters will automatically alternate on the display.
Backlight (BAKLITE)
The Backlight menu is used to enable or disable the backlight. After pressing Enter to access the Back-
light menu, press the Up arrow to Enable (ENABLE) or Disable (DISABLE) for the backlight.
Analog Output Calibration (AO CAL)
This feature is only used at the factory. It is not rec­ommended to access this menu without instruction from technical support.
47
Page 48
PD6730X Field-Mount Modbus Scanners
Backup & Restore (BACKUP)
The scanner saves all parameter settings, and no reprogramming is necessary when power is lost and restored to the scanner.
These features are used to save and restore programmed settings. Programming can be restored to a known saved good configuration, or to factory defaults. This is useful to restore scanners whose programming has been altered in unknown ways, or to quickly restore known good settings if mistakes are made during reprogramming.
The Save feature (SAVE?) saves all current parameter settings into the memory of the backup restore. The backup restore feature is loaded with factory default settings until a new configuration is saved.
The Load feature (LOAD?) restores all parameters to the programmed values stored in backup restore memory. The Load feature will not affect the current password settings.
Instruction Manual
Information (INFO)
The Information menu is part of the System features menu. It shows software identification number, version number, and extended model number. To view this information:
Go to the Information menu (INFO) and press Enter button.
Continue pressing Enter to scroll through the displays.
Following the information display, the scanner will exit the Advanced features menu and return to run mode.
• Once scanner parameters have been saved to memory by the backup restore feature there is no recovering the previously saved settings.
• Once parameters have been loaded into the scanner from the backup restore feature there is no recovering the previously programmed settings.
The Default feature (DEFAULT) restores all parameters to the factory default values. Factory default reset does not change the saved backup restore settings, or override passwords.
In the Backup menu, use the Up arrow key to select the desired menu. Press Enter to execute the save, load, or restore defaults command. To restore the scanner to factory defaults, press Enter again to confirm the request when Defaults? (DEFLTS?) is
blinking.
48
Page 49
PD6730X Field-Mount Modbus Scanners
the Safe Touch buttons will be fully enabled.
SafeTouch Disabled Mode
chanical pushbutton being pressed.
SafeTouch Button Equalize Delay
being unblocked.
MENU
PREV
NEXT
SCAN
Instruction Manual

Operation

Front Panel Buttons Operation

Symbol Description
See SafeTouch Buttons on page 15 for setup.
SafeTouch Button Operation
To actuate a button, press and remove one finger to the window directly over the marked button area. Re­move finger to at least 4 inches away from the window in between button activations. SafeTouch and mechan­ical buttons may be held to cycle through menus or dig­its in place of repeatedly pushing a button.
Hold the Menu SafeTouch button when in power save mode (display
will show ) to awaken SafeTouch buttons.
Press the Menu button to enter Programming Mode.
Press the Menu button during Programming Mode to return to the previous menu selections.
Hold the Menu button for 1.5 seconds at any time to exit Programming Mode and return to Run mode.
Press and hold the Menu button for 3 seconds to access the Advanced features menu.
Press Previous to manually display the previous PV or input display.
Press the Right arrow button in programming mode to move to the next digit or decimal position.
Press the Right arrow button in programming mode to go backward through most selection menus.
Press Next to manually display the next PV or input display.
Press the Up arrow button in programming mode to scroll forward through the menus, decimal point, or to increment the value of a digit
Press Scan to pause automatic scanning.
Press Scan to resume automatic scanning when paused.
Press the Enter button in programming mode to access a menu or to accept a setting.
SafeTouch Power Save Mode
(Symbol shown on -2 decimal models only)
SafeTouch buttons enter a power saving mode after three minutes of inactivity. This mode is indicated by a power
symbol ( ) appearing in the lower right of the display. Only the MENU button is monitored in this mode. To acti­vate the SafeTouch buttons, press and hold the menu but­ton for up to five seconds. The display will read AWAKE, and
When the cover is removed, the four mechanical buttons located next to the sensors may be used. The sensors are disabled when a mechanical button is pressed and will automatically be re-enabled after 60 seconds of inactivity.
The SafeTouch power symbol ( ) will blink in the lower right of the display if the buttons are disabled due to a me-
The SafeTouch buttons are designed to constantly recali­brate for ambient conditions. When the cover position is changed, the cover is removed, or an object is removed that was placed over the front window, it may take a mo­ment for the SafeTouch buttons to recalibrate to the change in conditions.
Allow up to 2 minutes for the SafeTouch buttons to recalibrate to new conditions in these cases where the cover position was changed, or the front window is
• SafeTouch will not work if two or more buttons are detected as being pressed simultaneously. Be careful to avoid triggering multiple buttons or reaching across one button location to press another.
SafeTouch Button Tips and Troubleshooting
The SafeTouch Buttons are designed to filter normal levels of ambient interference and to protect against false triggering, however it is recommended that the Safe Touch BUTTONS switch to OFF) if there is an infrared inter­ference source in line-of-sight to the display or if the buttons are not needed.
SafeTouch Button Tips:
Buttons be turned off (slide THRU-GLASS
• To the extent possible, install the display
facing away from sunlight, windows, reflective objects, and any sources of infrared interference.
• Keep the window clean.
• Tighten the cover securely.
• Use a password to prevent tampering.
• If the cover has not been installed and
secured tightly, it may take a moment for the SafeTouch buttons to properly self-calibrate when the cover is tightened.
• After all connections have been completed
and verified, connect the ribbon cable to the display module, fasten the display module to the base, install enclosure cover, and then apply power.
49
Page 50
PD6730X Field-Mount Modbus Scanners
Instruction Manual

Pause/Start Automatic Scanning

Automatic scanning will cycle through the enabled Modbus PVs and math channel CVs. The time each variable will be displayed is programmed in the Scan Time (T-SCAN) menu on page 33.
To pause scanning on the displayed variable, press the Scan button.
To start scanning again, press the Scan button.

Manual Scanning

The enabled Modbus PVs and math channel CVs can be manually cycled onto the display using the Next and Previous buttons.
The Next button will display the next enabled display variable, proceeding in the order of Modbus PVs and math channel CVs.
The Previous button will display the displayed varia­ble shown prior to the one being displayed, cycling through display variable in the reverse order.

Reset Scanner to Factory Defaults

Reset to factory defaults will restore most scanner pa­rameters to their factory default setting.
When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults.
Factory default reset does not change the saved backup restore settings or override passwords.
Instructions to load factory defaults can be found in the Backup & Restore (BACKUP) menu on page 48.
50
Page 51
PD6730X Field-Mount Modbus Scanners
Instruction Manual

Factory Defaults & User Settings

The following table shows the factory setting for most of the programmable parameters on the scanner. Next to the factory setting, the user may record the new setting for the particular application.
Model: _______________________ S/N: _______________________ Date: ____________
Parameter Display1 Default Setting User Setting & Notes
Mode
Modbus PV1 PV 1 Enable
Slave ID SLAVEID 1
Function Code FUNCODE Function 03
Register Number
Data Type
Byte BYTE 1234
Modbus PV2 PV 2 Enable
Slave ID SLAVEID 2
Function Code FUNCODE Function 03
Register Number
Data Type
Byte BYTE 1234
Modbus PV3 PV 3 Enable
Slave ID SLAVEID 3
Function Code FUNCODE Function 03
Register Number
Data Type
Byte BYTE 1234
Modbus PV4 PV 4 Enable
Slave ID SLAVEID 4
Function Code
Register Number
Data Type
Byte BYTE 1234
Modbus PV5-16 PV 5-16 Disable
Poll Time T POLL 2.0 seconds
Modbus Timeout
Retries to Error
Setup
Display DISPLAY
Top Display
(Decimal Display Models Only)
Bottom Display
MODE
REG NUM
DATATYP
REG NUM
DATATYP
REG NUM
DATATYP
FUNCODE
REG NUM
DATATYP
TIMEOUT
RETRIES
SeTUP
TOPDSP PV
BOTDSP
Master
40001
Float
40001
Float
40001
Float
Function 03
40001
Float
0.2 seconds
3
Tag
51
Page 52
PD6730X Field-Mount Modbus Scanners
Parameter Display1 Default Setting User Setting & Notes
PV Setup
PV 1 PV 1
Format
(Decimal Display Models)
Format
(Feet & Inches Display Models)
Tag TAG PV 1
Units UNITS FEET
Display Decimal Point
(Decimal Display Models Only)
Float Decimal Point
(Decimal Display Models Only)
Scale
Factor Decimal Point
Factor Value VALUE 1.000
PV 2 PV 2
Format
(Decimal Display Models)
Format
(Feet & Inches Display Models)
Tag TAG PV 2
Units UNITS FEET
Float Decimal Point
(Decimal Display Models Only)
Display Decimal Point
(Decimal Display Models Only)
Scale
Factor Decimal Point
Factor Value VALUE 1.000
PV 3 PV 3
Format
(Decimal Display Models)
Format
(Feet & Inches Display Models)
Tag TAG PV 3
Units
Float Decimal Point
(Decimal Display Models Only)
Display Decimal Point
(Decimal Display Models Only)
Scale
Factor Decimal Point F.DP 3
PVSETUP
FORMAT Top Display
FORMAT
DISP.DP
FLOAT.DP 1
SCALE
F.DP
FORMAT Top Display
FORMAT Ft-In-16
FLOAT.DP
DISP.DP 1
SCALE
F.DP
FORMAT
FORMAT Ft-In-16
UNITS
FLOAT.DP 1
DISP.DP 1
SCALE
Ft-In-16
1
Factor
3
1
Factor
3
Top Display
FEET
Factor
Instruction Manual
52
Page 53
PD6730X Field-Mount Modbus Scanners
Parameter Display1 Default Setting User Setting & Notes
Factor Value
PV 4 PV 4
Format
(Decimal Display Models)
Format
(Feet & Inches Display Models)
Tag TAG PV 4
Units UNITS FEET
Float Decimal Point
(Decimal Display Models Only)
Display Decimal Point
(Decimal Display Models Only)
Scale
Factor Decimal Point
Factor Value VALUE 1.000
Math Channel Setup MATH
CV 1 CV 1
Format FORMAT Off
CV 2
Format
CV 3 CV 3
Format FORMAT Off
CV 4 CV 4
Format FORMAT Off
Tag Display Time
Units Display Time
Scan Time T-SCAN 2 seconds
Pulse Input Setup PULSE.IN Disabled
Communications COMM
Scanner Modbus ID
Baud Rate
Transmit Delay
Parity PARITY Even
Advanced Features ADVANCE
Open Collector Output OUTPUT
Output 1
Output 2
Analog Output AOUT
Source SOURCE Disable
Math Functions MATH
VALUE
FORMAT Top Display
FORMAT
FLOAT.DP
DISP.DP 1
SCALE
F.DP
CV 2
FORMAT
T-TAG
T-UNITS
SCAN ID
BAUD
TXDELAY
OUT 1
OUT 2
1.000
Ft-In-16
1
Factor
3
Off
2 seconds
2 seconds
240
9600 bps
50 ms
Off
Off
Instruction Manual
53
Page 54
PD6730X Field-Mount Modbus Scanners
Parameter Display1 Default Setting User Setting & Notes
Channel 1
Channel 2 CV 2 None
Channel 3 CV 3 None
Channel 4 CV 4 None
Password
Parameter Lock Password
Additional Parameters & Notes
CV 1
PASSWRD
PASS
None
00000 (unlocked)
Instruction Manual
1. Feet and Inches display models do not include lower display decimal points.
54
Page 55
PD6730X Field-Mount Modbus Scanners
Address (Slave ID)
001
002
003
004
Baud Rate
4800 bps
4800 bps
4800 bps
4800 bps
Parity
None 1
None 1
None 1
None 1
Byte Order
1234 (big-endian: most significant digits register first)
Instruction Manual

Application Examples

The following applications show how the scanner can be configured for common applications.

Example 1: Master Polling Multivariable Level Transmitters

In this application we have a system consisting of four MTS LP-Series multivariable tank level gauges connected to a PD6730-AX0-I-2 displaying product level, interface level, and average temperature. The PD6730X is setup for Master mode, and it is polling the Modbus transmitters.
Note: As a tank level indicator displaying in units of feet, a PD6730-AX0-I-L could also be considered for this applica­tion. This would display feet and inches in the upper display and includes a tank level indicator.

Example 1 Level Transmitter Setup, Register Numbers, & Process Variables

Serial Communications Parameters
Transmit Delay 50 ms 50 ms 50 ms 50 ms
Fixed Serial Data Parameters
Level Register 30001, 30002
Interface Register 30003, 30004
Ave Temp Register 30017, 30018
Data Type Long Integer (2 registers), Binary, Signed
Tank 1 Transmitter
Tank 2 Transmitter
Tank 3 Transmitter
MTS LP-Series Transmitter Data
Tank 4 Transmitter
55
Page 56
PD6730X Field-Mount Modbus Scanners
Parameter
PD6730X
Description/Comment
Display
Mode
Master
PV1
Enable
Register PV1
30001
Tank 1 Product Level
Byte Order
1234
Function Code
04
Data Type
Long integer Binary, Signed
PV3 Slave ID
1
Register PV3
30017
Tank 1 Average Temperature
PV4
Enable
Function Code
04
Byte Order
1234
PV5 Slave ID
2
Data Type
Long integer Binary, Signed
PV6
Enable
Register PV6
30017
Tank 2 Average Temperature
Byte Order
1234
The following table shows the PD6730X setup to work with the MTS LP-Series gauges.
PV1 Slave ID 1
Function Code 04
Instruction Manual
Data Type Long integer Binary, Signed
PV2 Enable
PV2 Slave ID 1
Register PV2 30003 Tank 1 Interface
Byte Order 1234
PV3 Enable
Function Code 04
Data Type Long integer Binary, Signed
Byte Order 1234
PV4 Slave ID 2
Register PV4 30001 Tank 2 Product Level
Data Type Long integer Binary, Signed
PV5 Enable
Function Code 04
Register PV5 30003 Tank 2 Interface
Byte Order 1234
PV6 Slave ID 2
Function Code 04
Data Type Long integer Binary, Signed
56
Page 57
PD6730X Field-Mount Modbus Scanners
Parameter
PD6730X
Description/Comment
Display
Function Code
04
Byte Order
1234
PV8
Enable
Byte Order
1234
Data Type
Long integer Binary, Signed
Register PV10
30001
Tank 4 Product Level
Function Code
04
PV12 Slave ID
4
Poll Time
5.0 seconds
PV7 Enable
PV7 Slave ID 3
Register PV7 30001 Tank 3 Product Level
Data Type Long integer Binary, Signed
PV8 Slave ID 3
Function Code 04
Register PV8 30003 Tank 3 Interface
Data Type Long integer Binary, Signed
PV9 Enable
PV9 Slave ID 3
Function Code 04
Register PV9 30017 Tank 3 Average Temperature
Byte Order 1234
PV10 Enable
PV10 Slave ID 4
Function Code 04
Instruction Manual
Data Type Long integer Binary, Signed
Byte Order 1234
PV11 Enable
PV11 Slave ID 4
Register PV11 30003 Tank 4 Interface
Data Type Long integer Binary, Signed
Byte Order 1234
PV12 Enable
Function Code 04
Register PV12 30017 Tank 4 Average Temperature
Data Type Long integer Binary, Signed
Byte Order 1234
Timeout 0.3 seconds
Retries 3 Default Value
57
Page 58
PD6730X Field-Mount Modbus Scanners
Serial Communications
Transmit Time Delay
50 ms
Bottom Display
Tag & Units
Show Tag and Units for Each PV
Units
FEET
Input 2
12000
x1000 inch
Units
FEET
Input 2
12000
x1000 inch
Units
°F
Input 2
10000
x10,000 deg F
Parameter PD6730X Description/Comment
Scanner ID 246 Must be Unique on the Network
Baud 4800 bps Must Match All Network Devices
Parity None 1 Must Match All Network Devices
Setup
Display
Top Display PV Show Only PVs
PV Setup
PV 1 Identical for PV1, 4, 7, and 10
Format Top Display
Tag T1 LVL Indicates Tank 1 Level
Display Decimal Point 2
Scale Scaling for Level
Input 1 00000
Display 1 0.00
Instruction Manual
Display 2 10.00
PV 2 Identical for PV2, 5, 8, and 11
Format Top Display
Tag T1 INT Indicates Tank 1 Interface Registers
Display Decimal Point 2
Scale Scaling for Interface Registers
Input 1 00000
Display 1 0.00
Display 2 10.00
PV 3 Identical for PV3, 6, 9, and 12
Format Top Display
Tag T1TEMP T1 Indicates Tank 1 Average Temperature
Display Decimal Point 1
Scale Scaling for Temperature Registers
Input 1 00000
Display 1 0.0
Display 2 10.0
Feet
Feet
Deg F
58
Page 59
PD6730X Field-Mount Modbus Scanners
Address (Slave ID)
100
200
N/A
Baud Rate
4800 bps
4800 bps
4800 bps
Parameters
Flow Data Register
40001, 40002
Instruction Manual

Example 2: Snooper Displaying Flow Rate from Modbus Flowmeters

In this application we have a system consisting of two Modbus enabled flowmeters connected to a SCADA system operated out of a control room. A Modbus PLC polls the data out of the flowmeters. A PD6730-AX0-I-2 has been added to the system as a Modbus Snooper, to provide the operators an easy to read field display near the flow lines.
The scanner displays one flow rate on the top display, and one on the bottom display. Each has an alternating tag and units for clear identification.

Example 2: Flow Meter & PLC Setup, Register Numbers, & Process Variables

Serial Communications Parameters
Transmit Delay 50 ms 50 ms 50 ms
Parity None, 1 Stop Bit None, 1 Stop Bit None, 1 Stop Bit
Flow Transmitter 1 Flow Transmitter 2 Control Room PLC
Fixed Serial Data
Data Type Long Integer (2 registers), Binary, Signed
Byte Order 1234 (big-endian: most significant digits register first)
Modbus Flow Meter Data
59
Page 60
PD6730X Field-Mount Modbus Scanners
Parameter
PD6730X
Description/Comment
Mode
Snooper
PV1
Enable
PV1 Slave ID
100
Flow Meter 1 Address
Function Code
03
Register PV1
40001
Flow Meter 1 Rate
Data Type
Long integer Binary,
Byte Order
1234 PV2
Enable
PV2 Slave ID
200
Flow Mater 2 Address
Function Code
03 Register PV2
40001
Flow Meter 2 Rate
Data Type
Long integer Binary,
Byte Order
1234
Snooper Mode Response Time
2.0 seconds
Default Value
Serial Communications
Scanner ID
246
Must be Unique on the Network
Baud
4600 bps
Must Match All Network Devices
Transmit Time Delay
50 ms
Parity
None, 1 Stop Bit
Must Match All Network Devices
Setup
Display
Top Display
PV, Tag, & Units
Show PV, Tag, and Units for Each Top PV
Bottom Display
PV, Tag, & Units
Show PV, Tag, and Units for Each Bottom PV
PV Setup
PV 1
Format
Top Display
Show PV 1 (Flow Meter 1 Rate) on Bottom Display
Tag
RATE 1
Indicates Flow Meter 1 Rate
Units
GPM
Indicates Gallons Per Minute
Display Decimal Point
1 Scale
Scaling for Rate
Input 1
00000
Display 1
0.0 Input 2
50000
Display 2
5000.0
PV 2
Format
Bottom Display
Show PV 2 (Flow Meter 2 Rate) on Bottom Display
Tag
RATE 2
Indicates Flow Meter 2 Rate
Units
GPM
Indicates Gallons Per Minute
Display Decimal Point
1 Scale
Scaling for Rate
Input 1
00000
Display 1
0.0 Input 2
50000
Display 2
5000.0
The following table shows the PD6730X setup to work with two Modbus flowmeters.
Instruction Manual
60
Page 61
PD6730X Field-Mount Modbus Scanners
Instruction Manual

Troubleshooting

Due to the many features and functions of the scanner, it’s possible that the setup of the scanner does not agree with what an operator expects to see. If the scanner is not working as expected, refer to the Diagnostics menu and consult the recommendations described below.

Troubleshooting Tips

Symptom Check/Action
No display or faint display Check power connection.
Press and hold Menu key for 5 seconds to check for Standby mode. If “WAKEUP?” is displayed, press the Enter key to awaken the scanner from Standby mode.
SafeTouch Buttons do not respond
Scanner channel displays NONE
Long time between channel value updates
Scanner displays span error message during scaling
Scanner flashes maximum display
If the display locks up or the scanner does not respond
Backlight does not appear.
Other symptoms Call Technical Support for assistance.
If is displayed, hold Menu SafeTouch button to leave power save mode.
If is flashing, wait 60 seconds to leave mechanical pushbutton lockout mode. If the cover was recently tightly secured, you may need to wait up to 2 minutes for
buttons to self-calibrate to the new cover position due to window reflection. Verify THRU-GLASS BUTTONS switch on display module is in ON position. Sunlight can interfere with the sensors. It is recommended to shield the window
while operating the buttons by standing so as to block direct sunlight.
Verify that the polling parameters (slave address, register, etc) are correct. If the channel is a math channel CV, verify the chosen math function does not include any NONE selections or un-programmed Modbus PVs.
Verify all channels are communicating. Errors, combined with long timeouts and high allowable number of failures when polling Modbus devices, will combine to significantly delay the polling speed. Reduce the number of allowable timeout errors to check that communications are successful, and if there are errors, reduce the timeout if possible.
Verify minimum input span requirements
Check slave device registers are valid. Check math channels are not exceeding maximum possible display. Check input signal is within scaled range of 99999.
Perform hard reset by removing the display module or by removing DC power.
Backlight is intended for viewing assistance in dim lighting. It may not be noticeable under good lighting conditions.
Note: Certain sequences of events can cause unexpected results. To solve these issues, it is best to start fresh from factory defaults and map changes ahead of time, rather than at random.
61
Page 62
PD6730X Field-Mount Modbus Scanners
MENU
PREV
NEXT
SCAN

Quick User Interface Reference

Pushbutton Function
Go to Main menu. Back out one level of programming.
Hold to enter Advanced menu.
Return to previous display variable.
Move to next digit or decimal point position.
Return to previous same-level programming menu.
Display next display variable.
Move to next selection or increment digit.
Enter max/min display mode.
Pause/start automatic display scanning.
Accept selection/value and move to next selection.
Acknowledge Alarm.
Instruction Manual
62
Page 63
PD6730X Field-Mount Modbus Scanners
PRECISION DIGITAL CORPORATION
www.predig.com
Contact Precision Digital
Technical Support
Call: (800) 610-5239 or (508) 655-7300
Fax: (508) 655-8990
Sales Support
Call: (800) 343-1001 or (508) 655-7300
Fax: (508) 655-8990
Instruction Manual
Place Orders
For the latest version of this manual please visit
www.predig.com
233 South Street • Hopkinton MA 01748 USA Tel (800) 343-1001 • Fax (508) 655-8990
SFT092 & 93 Ver 1.200 & up
LIM6730X_D
08/21
Loading...